TCE CONSULTING ENGINEERS LIMITED

30421007-3OQ00002-P0C

SHEET 1 OF 1
I/O LIST FOR SEQUENCE OF EVENTS RECORDER

SAUDI ELECTRICITY COMPANY


EASTERN OPERATING AREA
Dammam, Saudi Arabia
GENERATION EXPANSION OF ARAR POWER PLANT
(CONTRACT NO : 30421007/00)

I/O LIST FOR SEQUENCE OF EVENTS RECORDER

DOCUMENT NO : 30421007-3OQ-00002-P0C
MAY 2005

ENGINEERING CONSULTANT
TCE CONSULTING ENGINEERS LIMITED
73/1, ST.MARK'S ROAD
BANGALORE 560001
INDIA

CONTRACTOR:
AL-TOUKHI COMPANY FOR INDUSTRY & TRADING
P.O.BOX 497, RIYADH 11411, KINGDOM OF SAUDI ARABIA
TEL.00966-1-4633660 : FAX.00966-1-4631150

P0C

19-05-05

REV NO. DATE

278171846.xls
SECTION :cover sheet

AE

SR

PREPARED BY

CHECKED BY

CLEARED BY

APPROVED BY

SHEET 1 OF 29

REV NO. DATE

278171846.xls
SECTION :cover sheet

PREPARED BY

CHECKED BY

CLEARED BY

APPROVED BY

SHEET 2 OF 29

Annexure-1: SOER Signals for Arar Power Plant

SL.No.

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34

Alarm
Code.

Tag No.
A.
81O
81O
24
24
27P
27P
32-1
32-2
40-1,2
40-1,2
46
46
51PV
51PV
59P
59P
81 U
81 U
87S
87S
27TN
27TN
50/27
50/27
21
21
78
78
59N
59N
VTFF
VTFF
Critical
Failure
Critical
Failure

List of Digital Signals for SOER

Remarks
As per GE's dwg
no.GR0976-207D3312

GTG-7
Over Frequency alarm -G60A
Over Frequency alarm- G60B
Volts/Hertz Alarm-G60A
Volts/Hertz Alarm -G60B
Under voltage Alarm-G60A
Under voltage Alarm-G60B
Reverse power Trip -G60A
Reverse power Trip -G60B
Loss of excitation Trip -G60A
Loss of excitation Trip -G60B
Generator unbalance(Negative sequence) trip G60A
Generator unbalance(Negative sequence) trip G60B
Voltage Restrained Overcurrent-Trip -G60A
Voltage Restrained Overcurrent-Trip -G60B
Over voltage Alarm-G60A
Over voltage Alarm-G60B
Under frequency Trip-G60A
Under frequency Trip-G60B
Stator Differential Trip-G60A
Stator Differential Trip-G60B
3rd Harmoic Neutral Undervoltage Trip-G60A
3rd Harmoic Neutral Undervoltage Trip-G60B
Inadvertance energization Trip-G60A
Inadvertance energization Trip -G60B
Phase Distance Trip-G60A
Phase Distance Trip-G60B
Out of step Trip-G60A
Out of step Trip-G60B
Over voltage Neutral Trip-G60A
Over voltage Neutral Trip-G60B
Voltage transformer fuse failure Alarm-G60A
Voltage transformer fuse failure Alarm-G60B
G60A fail Alarm
G60B fail Alarm

3 of 29

Annexure-1: SOER Signals for Arar Power Plant

SL.No.

35
36
37
38
39
40

Alarm
Code.

Tag No.
86G-1A
86G-2A
86G-1B
86G-2B
86IE
86U
86BF
B.
74/TC-1
74/TC-2
94GB1
94GB2

List of Digital Signals for SOER


Lock out relay 86G-1A operated
Lock out relay 86G-2A operated
Lock out relay 86G-1B operated
Lock out relay 86G-2B operated
Lock out relay 86IE operated
Lock out relay 86U operated
Lock out relay 86BF operated
Generator Circuit Breaker Unit-7
Breaker Status
CB Trip coil -1 supervision operated
CB Trip coil -2 supervision operated
CB Operating Mechanism failed
Generator breaker alarm (grouped alarm)
Generator breaker fault (grouped fault)

Remarks

As per GE's dwg


no.GR0976-207D3312
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61

C.
81O
81O
24
24
27P
27P
32-1
32-2
40-1,2
40-1,2
46
46
51PV
51PV
59P
59P
81 U
81 U
87S
87S
27TN

GTG-8
Over Frequency alarm -G60A
Over Frequency alarm- G60B
Volts/Hertz Alarm-G60A
Volts/Hertz Alarm -G60B
Under voltage Alarm-G60A
Under voltage Alarm-G60B
Reverse power Trip -G60A
Reverse power Trip -G60B
Loss of excitation Trip -G60A
Loss of excitation Trip -G60B
Generator unbalance(Negative sequence) trip G60A
Generator unbalance(Negative sequence) trip G60B
Voltage Restrained Overcurrent-Trip -G60A
Voltage Restrained Overcurrent-Trip -G60B
Over voltage Alarm-G60A
Over voltage Alarm-G60B
Under frequency Trip-G60A
Under frequency Trip-G60B
Stator Differential Trip-G60A
Stator Differential Trip-G60B
3rd Harmoic Neutral Undervoltage Trip-G60A

4 of 29

Annexure-1: SOER Signals for Arar Power Plant

SL.No.
62
63
64
65
66
67
68
69
70
71
72
73
74

75
76
77
78
79
80
81
82
83
84
85
86
87
88

Alarm
Code.

Tag No.
27TN
50/27
50/27
21
21
78
78
59N
59N
VTFF
VTFF
Critical
Failure
Critical
Failure
86G-1A
86G-2A
86G-1B
86G-2B
86IE
86U
86BF
D.
74/TC-1
74/TC-2
94GB1
94GB2
E.
81O
81O
24
24
27P
27P
32-1
32-2

List of Digital Signals for SOER


3rd Harmoic Neutral Undervoltage Trip-G60B
Inadvertance energization Trip-G60A
Inadvertance energization Trip -G60B
Phase Distance Trip-G60A
Phase Distance Trip-G60B
Out of step Trip-G60A
Out of step Trip-G60B
Over voltage Neutral Trip-G60A
Over voltage Neutral Trip-G60B
Voltage transformer fuse failure Alarm-G60A
Voltage transformer fuse failure Alarm-G60B
G60A fail Alarm
G60B fail Alarm
Lock out relay 86G-1A operated
Lock out relay 86G-2A operated
Lock out relay 86G-1B operated
Lock out relay 86G-2B operated
Lock out relay 86IE operated
Lock out relay 86U operated
Lock out relay 86BF operated
Generator Circuit Breaker Unit-8
Breaker Status
CB Trip coil -1 supervision operated
CB Trip coil -2 supervision operated
CB Operating Mechanism failed
Generator breaker alarm (grouped alarm)
Generator breaker fault (grouped fault)
Future GTG
Over Frequency alarm -G60A
Over Frequency alarm- G60B
Volts/Hertz Alarm-G60A
Volts/Hertz Alarm -G60B
Under voltage Alarm-G60A
Under voltage Alarm-G60B
Reverse power Trip -G60A
Reverse power Trip -G60B

5 of 29

Remarks

Annexure-1: SOER Signals for Arar Power Plant

SL.No.
89
90
91
92
93
94
95
96
97
98
99
100
101
102
103
104
105
106
107
108
109
110
111
112
113
114

115
116

Alarm
Code.

Tag No.
40-1,2
40-1,2
46
46
51PV
51PV
59P
59P
81 U
81 U
87S
87S
27TN
27TN
50/27
50/27
21
21
78
78
59N
59N
VTFF
VTFF
Critical
Failure
Critical
Failure
86G-1A
86G-2A
86G-1B
86G-2B
86IE
86U
86BF
F.
74/TC-1

List of Digital Signals for SOER


Loss of excitation Trip -G60A
Loss of excitation Trip -G60B
Generator unbalance(Negative sequence) trip G60A
Generator unbalance(Negative sequence) trip G60B
Voltage Restrained Overcurrent-Trip -G60A
Voltage Restrained Overcurrent-Trip -G60B
Over voltage Alarm-G60A
Over voltage Alarm-G60B
Under frequency Trip-G60A
Under frequency Trip-G60B
Stator Differential Trip-G60A
Stator Differential Trip-G60B
3rd Harmoic Neutral Undervoltage Trip-G60A
3rd Harmoic Neutral Undervoltage Trip-G60B
Inadvertance energization Trip-G60A
Inadvertance energization Trip -G60B
Phase Distance Trip-G60A
Phase Distance Trip-G60B
Out of step Trip-G60A
Out of step Trip-G60B
Over voltage Neutral Trip-G60A
Over voltage Neutral Trip-G60B
Voltage transformer fuse failure Alarm-G60A
Voltage transformer fuse failure Alarm-G60B
G60A fail Alarm
G60B fail Alarm
Lock out relay 86G-1A operated
Lock out relay 86G-2A operated
Lock out relay 86G-1B operated
Lock out relay 86G-2B operated
Lock out relay 86IE operated
Lock out relay 86U operated
Lock out relay 86BF operated
Generator Circuit Breaker Future Unit
Breaker Status
CB Trip coil -1 supervision operated

6 of 29

Remarks

Annexure-1: SOER Signals for Arar Power Plant

SL.No.
117
118
119
120
121
122
123
124
125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
140
141
142
143
144
145
146
147
148
149
150
151
152
153

Alarm
Code.

Tag No.
74/TC-2
94GB1
94GB2
G.
63-1 GT
63-2 GT
63-1 OLTC
63-2 OLTC
49-1 OGT
49-2 OGT
49-1 WGT
49-2 WGT
71 GT
63 PRGT
87 GT
87 GT
87 GT
87 GTG
51N GGT
87 OA
87 OA
87 OA
87 GT FDR
87 GT FDR
87 GT FDR
86 GT-1
74/86
86 GT-2
74/86
51 GT
51 GT
51 GT
27

List of Digital Signals for SOER


CB Trip coil -2 supervision operated
CB Operating Mechanism failed
Generator breaker alarm (grouped alarm)
Generator breaker fault (grouped fault)
Generator Transformer of Unit-7
T607 Buchholz relay alarm operated
T607 Buchholz relay Trip operated
OLTC of T607 Buchholz relay alarm operated
OLTC of T607 Buchholz relay Trip operated
T607 Oil temperature high - Alarm
T607 Oil temperature very high - Trip
T607 Winding Temperature high - Alarm
T607 Winding Temperature very high - Trip
T607 Low Oil Level - Trip
T607 Pressure Relief Device operated - Trip
T607 87GT Differential protection PH-A operated
T607 87GT Differential protection PH-B operated
T607 87GT Differential protection PH-C operated
T607 Restricted Ground Differential protection operated
T607 Ground Over Current backup protection operated
T607 Overall Unit Differential Protection PH-A operated
T607 Overall Unit Differential Protection PH-B operated
T607 Overall Unit Differential Protection PH-C operated
T607 132kV side Feeder Differential protection PH-A operated
T607132kV side Feeder Differential protection PH-B operated
T607 132kV side Feeder Differential protection PH-C operated
Gen.Transformer T607 Lockout relay-1 operated
Gen.Transformer T607 Lockout relay-1 supervision relay operated
Gen.Transformer T607 Lockout relay-2 operated
Gen.Transformer T607 Lockout relay-2 supervision relay operated
T607 phase fault back up over current protection PH-A operated
T607 phase fault back up over current protection PH-B operated
T607 phase fault back up over current protection PH-C operated
T607 Tap changer device fail alarm
OLTC pressure relief device operated
OLTC protection relay operated
OLTC Low oil level alarm
Transformer membrane failure alarm

7 of 29

Remarks

Annexure-1: SOER Signals for Arar Power Plant

SL.No.
154
155
156
157
158
159
160
161
162
163
164
165
166
167
168
169
170
171
172
173
174
175
176
177
178
179
180
181
182
183
184
185
186
187
188

Alarm
Code.

Tag No.

74DC
74DC

87GT
50/51
87OA
87 GT FDR
H.
74/TC-1
74/TC-2

List of Digital Signals for SOER


Cooling system failed alarm
Transformer low oil level alarm
Maintenance switch open
DC circuit supervision relay (74DC)in the ckt of 86-1
DC circuit supervision relay (74DC)in the ckt of 86-2
Primary protection SOE common +ve open
Backup protection SOE common +ve open
Mechanical protection SOE common +ve open
86-1 Trip opened at FT
86-2 Trip opened at FT
86-3 Trip opened at FT
Relay 87GT faulty
Relay 50/51 GT faulty
Overall differential relay 87OA faulty
Feeder differential relay 87GT FDR faulty
132kV Circuit Breaker Unit-7
Breaker Status
CB Trip coil -1 supervision operated
CB Trip coil -2 supervision operated
CB Operating Mechanism failed
SF6 Gas pressure low
Breaker failure relay operated
Breaker failure lockout relay operated
BF relay Circuit DC differential supervision relay operated
Generator Transformer of Unit-8
T608 Buchholz relay alarm operated
T608 Buchholz relay Trip operated
OLTC of T608 Buchholz relay alarm operated
OLTC of T608 Buchholz relay Trip operated
T608 Oil temperature high - Alarm
T608 Oil temperature very high - Trip
T608 Winding Temperature high - Alarm
T608 Winding Temperature very high - Trip
T608 Low Oil Level - Trip
T608 Pressure Relief Device operated - Trip

E.
63-1 GT
63-2 GT
63-1 OLTC
63-2 OLTC
49-1 OGT
49-2 OGT
49-1 WGT
49-2 WGT
71 GT
63 PRGT
COOLER
FAILURE T608 Cooling System failed - Trip
87 GT
T608 87GT Differential protection PH-A operated

8 of 29

Remarks

Annexure-1: SOER Signals for Arar Power Plant

SL.No.
189
190
191
192
193
194
195
196
197
198
199
200
201
202
203
204
205
206
207
208
209
210
211
212
213
214
215
216
217
218
219
220
221
222
223
224
225

Alarm
Code.

Tag No.
87 GT
87 GT
87 GTG
51N GGT
87 OA
87 OA
87 OA
87 GT FDR
87 GT FDR
87 GT FDR
86 GT-1
74/86
86 GT-2
74/86
51 GT
51 GT
51 GT
27

List of Digital Signals for SOER


T608 87GT Differential protection PH-B operated
T608 87GT Differential protection PH-C operated
T608 Restricted Ground Differential protection operated
T608 Ground Over Current backup protection operated
T608 Overall Unit Differential Protection PH-A operated
T608 Overall Unit Differential Protection PH-B operated
T608 Overall Unit Differential Protection PH-C operated
T608 132kV side Feeder Differential protection PH-A operated
T608132kV side Feeder Differential protection PH-B operated
T608 132kV side Feeder Differential protection PH-C operated
Gen.Transformer T608 Lockout relay-1 operated
Gen.Transformer T608 Lockout relay-1 supervision relay operated
Gen.Transformer T608 Lockout relay-2 operated
Gen.Transformer T608 Lockout relay-2 supervision relay operated
T608 phase fault back up over current protection PH-A operated
T608 phase fault back up over current protection PH-B operated
T608 phase fault back up over current protection PH-C operated
T608 Tap changer device fail alarm
OLTC pressure relief device operated
OLTC protection relay operated
OLTC Low oil level alarm
Transformer membrane failure alarm
Cooling system failed alarm
Transformer low oil level alarm
Maintenance switch open
74DC
DC circuit supervision relay (74DC)in the ckt of 86-1
74DC
DC circuit supervision relay (74DC)in the ckt of 86-2
Primary protection SOE common +ve open
Backup protection SOE common +ve open
Mechanical protection SOE common +ve open
86-1 Trip opened at FT
86-2 Trip opened at FT
86-3 Trip opened at FT
87GT
Relay 87GT faulty
50/51
Relay 50/51 GT faulty
87OA
Overall differential relay 87OA faulty
87 GT FDR Feeder differential relay 87GT FDR faulty
H.
132kV Circuit Breaker Unit-8

9 of 29

Remarks

Annexure-1: SOER Signals for Arar Power Plant

SL.No.
226
227
228
229
230
231
232
233
234
235
236
237
238
239
240
241
242
243
244
245
246
247
248
249
250
251
252
253
254
255
256
257
258
259
260
261

Alarm
Code.

Tag No.
74/TC-1
74/TC-2

F
63-1 GT
63-2 GT
63-1 OLTC
63-2 OLTC
49-1 OGT
49-2 OGT
49-1 WGT
49-2 WGT
71 GT
63 PRGT
COOLER
FAILURE
87 GT
87 GT
87 GT
87 GTG
51N GGT
87 OA
87 OA
87 OA
87 GT FDR
87 GT FDR
87 GT FDR
86 GT-1
74/86
86 GT-2
74/86
51 GT
51 GT

List of Digital Signals for SOER


Breaker Status
CB Trip coil -1 supervision operated
CB Trip coil -2 supervision operated
CB Operating Mechanism failed
SF6 Gas pressure low
Breaker failure relay operated
Breaker failure lockout relay operated
BF relay Circuit DC differential supervision relay operated
Generator Transformer of Unit-5
T605 Buchholz relay alarm operated
T605 Buchholz relay Trip operated
OLTC of T605 Buchholz relay alarm operated
OLTC of T605 Buchholz relay Trip operated
T605 Oil temperature high - Alarm
T605 Oil temperature very high - Trip
T605 Winding Temperature high - Alarm
T605 Winding Temperature very high - Trip
T605 Low Oil Level - Trip
T605 Pressure Relief Device operated - Trip
T605 Cooling System failed - Trip
T605 87GT Differential protection PH-A operated
T605 87GT Differential protection PH-B operated
T605 87GT Differential protection PH-C operated
T605 Restricted Ground Differential protection operated
T605 Ground Over Current backup protection operated
T605 Overall Unit Differential Protection PH-A operated
T605 Overall Unit Differential Protection PH-B operated
T605 Overall Unit Differential Protection PH-C operated
T605 132kV side Feeder Differential protection PH-A operated
T605132kV side Feeder Differential protection PH-B operated
T605 132kV side Feeder Differential protection PH-C operated
Gen.Transformer T605 Lockout relay-1 operated
Gen.Transformer T605 Lockout relay-1 supervision relay operated
Gen.Transformer T605 Lockout relay-2 operated
Gen.Transformer T605 Lockout relay-2 supervision relay operated
T605 phase fault back up over current protection PH-A operated
T605 phase fault back up over current protection PH-B operated

10 of 29

Remarks

Annexure-1: SOER Signals for Arar Power Plant

SL.No.
262
263
264
265
266
267
268
269
270
271
272
273
274
275
276
277
278
279
280
281
282
283
284
285
286
287
288
289
290
291
292
293
294
295
296
297

Alarm
Code.

Tag No.
51 GT
27

74DC
74DC

87GT
50/51
87OA
87 GT FDR
H.
74/TC-1
74/TC-2

G
63-1 GT
63-2 GT
63-1 OLTC
63-2 OLTC
49-1 OGT
49-2 OGT
49-1 WGT

List of Digital Signals for SOER


T605 phase fault back up over current protection PH-C operated
T605 Tap changer device fail alarm
OLTC pressure relief device operated
OLTC protection relay operated
OLTC Low oil level alarm
Transformer membrane failure alarm
Cooling system failed alarm
Transformer low oil level alarm
Maintenance switch open
DC circuit supervision relay (74DC)in the ckt of 86-1
DC circuit supervision relay (74DC)in the ckt of 86-2
Primary protection SOE common +ve open
Backup protection SOE common +ve open
Mechanical protection SOE common +ve open
86-1 Trip opened at FT
86-2 Trip opened at FT
86-3 Trip opened at FT
Relay 87GT faulty
Relay 50/51 GT faulty
Overall differential relay 87OA faulty
Feeder differential relay 87GT FDR faulty
132kV Circuit Breaker Unit-5
Breaker Status
CB Trip coil -1 supervision operated
CB Trip coil -2 supervision operated
CB Operating Mechanism failed
SF6 Gas pressure low
Breaker failure relay operated
Breaker failure lockout relay operated
BF relay Circuit DC differential supervision relay operated
Generator Transformer of Unit-6
T606 Buchholz relay alarm operated
T606 Buchholz relay Trip operated
OLTC of T606 Buchholz relay alarm operated
OLTC of T606 Buchholz relay Trip operated
T606 Oil temperature high - Alarm
T606 Oil temperature very high - Trip
T606 Winding Temperature high - Alarm

11 of 29

Remarks

Annexure-1: SOER Signals for Arar Power Plant

SL.No.
298
299
300
301
302
303
304
305
306
307
308
309
310
311
312
313
314
315
316
317
318
319
320
321
322
323
324
325
326
327
328
329
330
331
332
333
334

Alarm
Code.

Tag No.
49-2 WGT
71 GT
63 PRGT
COOLER
FAILURE
87 GT
87 GT
87 GT
87 GTG
51N GGT
87 OA
87 OA
87 OA
87 GT FDR
87 GT FDR
87 GT FDR
86 GT-1
74/86
86 GT-2
74/86
51 GT
51 GT
51 GT
27

74DC
74DC

List of Digital Signals for SOER


T606 Winding Temperature very high - Trip
T606 Low Oil Level - Trip
T606 Pressure Relief Device operated - Trip
T606 Cooling System failed - Trip
T606 87GT Differential protection PH-A operated
T606 87GT Differential protection PH-B operated
T606 87GT Differential protection PH-C operated
T606 Restricted Ground Differential protection operated
T606 Ground Over Current backup protection operated
T606 Overall Unit Differential Protection PH-A operated
T606 Overall Unit Differential Protection PH-B operated
T606 Overall Unit Differential Protection PH-C operated
T606 132kV side Feeder Differential protection PH-A operated
T606132kV side Feeder Differential protection PH-B operated
T606 132kV side Feeder Differential protection PH-C operated
Gen.Transformer T606 Lockout relay-1 operated
Gen.Transformer T606 Lockout relay-1 supervision relay operated
Gen.Transformer T606 Lockout relay-2 operated
Gen.Transformer T606 Lockout relay-2 supervision relay operated
T606 phase fault back up over current protection PH-A operated
T606 phase fault back up over current protection PH-B operated
T606 phase fault back up over current protection PH-C operated
T606 Tap changer device fail alarm
OLTC pressure relief device operated
OLTC protection relay operated
OLTC Low oil level alarm
Transformer membrane failure alarm
Cooling system failed alarm
Transformer low oil level alarm
Maintenance switch open
DC circuit supervision relay (74DC)in the ckt of 86-1
DC circuit supervision relay (74DC)in the ckt of 86-2
Primary protection SOE common +ve open
Backup protection SOE common +ve open
Mechanical protection SOE common +ve open
86-1 Trip opened at FT
86-2 Trip opened at FT

12 of 29

Remarks

Annexure-1: SOER Signals for Arar Power Plant

SL.No.
335
336
337
338
339
340
341
342
343
344
345
346
347
321
322
323
324
325
326
327
328
329
330
331
332
333
334
335
336
337
338
339
340
341
342

Alarm
Code.

Tag No.

List of Digital Signals for SOER


86-3 Trip opened at FT
87GT
Relay 87GT faulty
50/51
Relay 50/51 GT faulty
87OA
Overall differential relay 87OA faulty
87 GT FDR Feeder differential relay 87GT FDR faulty
H.
132kV Circuit Breaker Unit-6
Breaker Status
74/TC-1 CB Trip coil -1 supervision operated
74/TC-2 CB Trip coil -2 supervision operated
CB Operating Mechanism failed
SF6 Gas pressure low
Breaker failure relay operated
Breaker failure lockout relay operated
BF relay Circuit DC differential supervision relay operated
H
63-1 GT
63-2 GT
63-1 OLTC
63-2 OLTC
49-1 OGT
49-2 OGT
49-1 WGT
49-2 WGT
71 GT
63 PRGT
COOLER
FAILURE
87 GT
87 GT
87 GT
87 GTG
51N GGT
87 OA
87 OA
87 OA
87 GT FDR
87 GT FDR
87 GT FDR

Generator Transformer of Future Unit


T609 Buchholz relay alarm operated
T609 Buchholz relay Trip operated
OLTC of T609 Buchholz relay alarm operated
OLTC of T609 Buchholz relay Trip operated
T609 Oil temperature high - Alarm
T609 Oil temperature very high - Trip
T609 Winding Temperature high - Alarm
T609 Winding Temperature very high - Trip
T609 Low Oil Level - Trip
T609 Pressure Relief Device operated - Trip
T609 Cooling System failed - Trip
T609 87GT Differential protection PH-A operated
T609 87GT Differential protection PH-B operated
T609 87GT Differential protection PH-C operated
T609 Restricted Ground Differential protection operated
T609 Ground Over Current backup protection operated
T609 Overall Unit Differential Protection PH-A operated
T609 Overall Unit Differential Protection PH-B operated
T609 Overall Unit Differential Protection PH-C operated
T609 132kV side Feeder Differential protection PH-A operated
T609132kV side Feeder Differential protection PH-B operated
T609 132kV side Feeder Differential protection PH-C operated

13 of 29

Remarks

Annexure-1: SOER Signals for Arar Power Plant

SL.No.
343
344
345
346
347
348
349
350
351
352
353
354
355
356
357
358
359
360
361
362
363
364
365
366
367
368
369
370
371
372
373
374
375
376
377
378

Alarm
Code.

Tag No.
86 GT-1
74/86
86 GT-2
74/86
51 GT
51 GT
51 GT
27

List of Digital Signals for SOER


Gen.Transformer T609 Lockout relay-1 operated
Gen.Transformer T609 Lockout relay-1 supervision relay operated
Gen.Transformer T609 Lockout relay-2 operated
Gen.Transformer T609 Lockout relay-2 supervision relay operated
T609 phase fault back up over current protection PH-A operated
T609 phase fault back up over current protection PH-B operated
T609 phase fault back up over current protection PH-C operated
T609 Tap changer device fail alarm
OLTC pressure relief device operated
OLTC protection relay operated
OLTC Low oil level alarm
Transformer membrane failure alarm
Cooling system failed alarm
Transformer low oil level alarm
Maintenance switch open
74DC
DC circuit supervision relay (74DC)in the ckt of 86-1
74DC
DC circuit supervision relay (74DC)in the ckt of 86-2
Primary protection SOE common +ve open
Backup protection SOE common +ve open
Mechanical protection SOE common +ve open
86-1 Trip opened at FT
86-2 Trip opened at FT
86-3 Trip opened at FT
87GT
Relay 87GT faulty
50/51
Relay 50/51 GT faulty
87OA
Overall differential relay 87OA faulty
87 GT FDR Feeder differential relay 87GT FDR faulty
H.
132kV Circuit Breaker Future Unit-6
Breaker Status
74/TC-1 CB Trip coil -1 supervision operated
74/TC-2 CB Trip coil -2 supervision operated
CB Operating Mechanism failed
SF6 Gas pressure low
Breaker failure relay operated
Breaker failure lockout relay operated
BF relay Circuit DC differential supervision relay operated
I
Unit Auxiliary Transformer UAT 307
49-1WUAT Unit Auxiliary Transformer Winding Temperature high - Alarm

14 of 29

Remarks

Annexure-1: SOER Signals for Arar Power Plant

SL.No.
379
380
381
382
383
384
385
386
387
388
389
390
391
392
393
394
395
396
397
398
399
400
401
402
403
404
405
406
407
408
409
410
411
412
413
414

Alarm
Code.

Tag No.
49-2WUAT
51G UAT
51G UAT
50/51 UAT
50/51 UAT
50/51 UAT
50/51 UAT
50/51
50/51
50/51
51N
50/51N
86-A201
74/86
74/DC
86-UAT
74/86/UAT
J
74/TC

J
49-1WUAT
49-2WUAT
51G UAT
51G UAT
50/51 UAT
50/51 UAT
50/51 UAT
50/51 UAT
50/51
50/51
50/51
51N
50/51N
86
74/86
74/DC

List of Digital Signals for SOER


Unit Auxiliary Transformer Winding Temperature very high -Trip
Unit Auxiliary Transformer Ground Over Current protection operated
Unit Auxiliary Transformer Ground Over Current relay faulty
Unit Auxiliary Transformer HV Side over current protection Phase -A operated
Unit Auxiliary Transformer HV Side over current protection Phase -B operated
Unit Auxiliary Transformer HV Side over current protection Phase -C operated
Unit Auxiliary Transformer HV Side over current relay faulty
Unit Auxiliary Transformer LV side INST/ Inverse Time Over current protection Phase-A operated
Unit Auxiliary Transformer LV side INST/ Inverse Time Over current protection Phase-B operated
Unit Auxiliary Transformer LV side INST/ Inverse Time Over current protection Phase-C operated
Unit Auxiliary Transformer LV side Inverse Ground fault protection operated
Unit Auxiliary Transformer LV side O/C, E/F relay faulty
Unit Auxiliary Transformer Breaker Lockout relay operated
Unit Auxiliary Transformer Breaker Lockout relay supervision relay operated
Unit Auxiliary Transformer Breaker DC Supply Failure relay operated
Unit Auxiliary Transformer Lockout relay operated
Unit Auxiliary Transformer Lockout relay supervision relay operated
Unit Auxiliary Transformer UAT 307 LV side Breaker(A201)
Unit Auxiliary Transformer Breaker Trip Coil Supervision relay operated
Unit Auxiliary Transformer Breaker Status
Unit Auxiliary Transformer Breaker Operating Mechanism failed
Unit Auxiliary Transformer UAT 308
Unit Auxiliary Transformer Winding Temperature high - Alarm
Unit Auxiliary Transformer Winding Temperature very high -Trip
Unit Auxiliary Transformer Ground Over Current protection operated
Unit Auxiliary Transformer Ground Over Current relay faulty
Unit Auxiliary Transformer HV Side over current protection Phase -A operated
Unit Auxiliary Transformer HV Side over current protection Phase -B operated
Unit Auxiliary Transformer HV Side over current protection Phase -C operated
Unit Auxiliary Transformer HV Side over current relay faulty
Unit Auxiliary Transformer LV side INST/ Inverse Time Over current protection Phase-A operated
Unit Auxiliary Transformer LV side INST/ Inverse Time Over current protection Phase-B operated
Unit Auxiliary Transformer LV side INST/ Inverse Time Over current protection Phase-C operated
Unit Auxiliary Transformer LV side Inverse Ground fault protection operated
Unit Auxiliary Transformer LV side O/C, E/F relay faulty
Unit Auxiliary Transformer Breaker Lockout relay operated
Unit Auxiliary Transformer Breaker Lockout relay supervision relay operated
Unit Auxiliary Transformer Breaker DC Supply Failure relay operated

15 of 29

Remarks

Annexure-1: SOER Signals for Arar Power Plant

SL.No.
415
416
417
418
419
420
421
422
423
424
425
426
427
428
429
430
431
432
433
434
435
436
437
438
439
440
441
442
443
444
445
446
447
448

Alarm
Code.

Tag No.
86-UAT
74/86/UAT
J
74/TC

List of Digital Signals for SOER


Unit Auxiliary Transformer Lockout relay operated
Unit Auxiliary Transformer Lockout relay supervision relay operated
Unit Auxiliary Transformer UAT 308 LV side Breaker(A201)
Unit Auxiliary Transformer Breaker Trip Coil Supervision relay operated
Unit Auxiliary Transformer Breaker Status
Unit Auxiliary Transformer Breaker Operating Mechanism failed
Unit Auxiliary Transformer (Future Unit)
Unit Auxiliary Transformer Winding Temperature high - Alarm
Unit Auxiliary Transformer Winding Temperature very high -Trip
Unit Auxiliary Transformer Ground Over Current protection operated
Unit Auxiliary Transformer Ground Over Current relay faulty
Unit Auxiliary Transformer HV Side over current protection Phase -A operated
Unit Auxiliary Transformer HV Side over current protection Phase -B operated
Unit Auxiliary Transformer HV Side over current protection Phase -C operated
Unit Auxiliary Transformer HV Side over current relay faulty
Unit Auxiliary Transformer LV side INST/ Inverse Time Over current protection Phase-A operated
Unit Auxiliary Transformer LV side INST/ Inverse Time Over current protection Phase-B operated
Unit Auxiliary Transformer LV side INST/ Inverse Time Over current protection Phase-C operated
Unit Auxiliary Transformer LV side Inverse Ground fault protection operated
Unit Auxiliary Transformer LV side O/C, E/F relay faulty
Unit Auxiliary Transformer Breaker Lockout relay operated
Unit Auxiliary Transformer Breaker Lockout relay supervision relay operated
Unit Auxiliary Transformer Breaker DC Supply Failure relay operated
Unit Auxiliary Transformer Lockout relay operated
Unit Auxiliary Transformer Lockout relay supervision relay operated
Unit Auxiliary Transformer -Future LV side Breaker(A201)

K
49-1WUAT
49-2WUAT
51G UAT
51G UAT
50/51 UAT
50/51 UAT
50/51 UAT
50/51 UAT
50/51
50/51
50/51
51N
50/51N
86
74/86
74/DC
86-UAT
74/86/UAT
J
74/TC
Unit Auxiliary Transformer Breaker Trip Coil Supervision relay operated
Unit Auxiliary Transformer Breaker Status
Unit Auxiliary Transformer Breaker Operating Mechanism failed
L
Station Auxiliary Transformer SAT T201
63-1 SAT Station Aux.Transformer T201 Buchholz relay alarm operated
63-2 SAT Station Aux.Transformer T201 Buchholz relay Trip operated
49-1 OSAT Station Aux.Transformer T201 Oil temperature high - Alarm
49-2 OSAT Station Aux.Transformer T201 Oil temperature very high - Trip
49-1 WSAT Station Aux.Transformer T201 Winding Temperature high - Alarm
49-2 WSAT Station Aux.Transformer T201 Winding Temperature very high - Trip
71 SAT
Station Aux.Transformer T201 Low Oil Level - Alarm
63 P SAT Station Aux.Transformer T201 Pressure Relief Device operated - Trip

16 of 29

Remarks

Annexure-1: SOER Signals for Arar Power Plant

SL.No.
449
450
451
452
453
454
455
456
457
458
459
460
461
462
463
464
465
466
467
468
469
470
471
472
473
474
475
476
477
478
479
480
481
482
483
484
485

Alarm
Code.

Tag No.
63 OLTC
27
51G LV
51G LV
50/51
50/51
50/51
50N/51N
50/51N
50G
86 B212
74/86
86 A101
74/86
74 TC
74 DC
51
51
51
51N
51/51N

M
63-1 SAT
63-2 SAT
49-1 OSAT
49-2 OSAT
49-1 WSAT
49-2 WSAT
71 SAT
63 P SAT
63 OLTC
27
51G LV

List of Digital Signals for SOER


Station Aux.Transformer T201 OLTC Buchholz trip
Station Aux. Transformer T201 Tap changer device failure alarm
Station Aux.Transformer T201 Neutral Ground Fault protection operated
Station Aux.Transformer T201 Neutral Ground Fault relay faulty
Station Aux.Transformer T201 HV BKR INST/ Inverse Time O/C Phase-A operated
Station Aux.Transformer T201 HV BKR INST/ Inverse Time O/C Phase-B operated
Station Aux.Transformer T201 HV BKR INST/ Inverse Time O/C Phase-C operated
Station Aux.Transformer T201 HV BKR INST/ Inverse Time Ground fault protection operated
Station Aux.Transformer T201 HV BKR INST/ Inverse Time O/C, E/F relay faulty.
Station Aux.Transformer T201 HV BKR CBCT protection operated
Station Aux.Transformer T201 HV BKR lockout relay operated
Station Aux.Transformer T201 HV BKR Lockout relay supervision relay operated
Station Aux.Transformer T201 LV BKR Lockout relay operated
Station Aux.Transformer T201 LV BKR Lockout relay supervision relay operated
Station Aux.Transformer T201 LV BKR Trip coil supervision relay operated
Station Aux.Transformer T201 LV BKR DC supply supervision relay operated
Station Aux.Transformer T201 LV BKR inverse time O/C Phase -A operated
Station Aux.Transformer T201 LV BKR inverse time O/C Phase -B operated
Station Aux.Transformer T201 LV BKR inverse time O/C Phase -C operated
Station Aux.Transformer T201 LV BKR inverse time earthfault relay operated
Station Aux.Transformer T201 LV BKR inverse time O/C, E/F relay faulty
OLTC pressure relief device operated
OLTC protection relay operated
OLTC Low oil level alarm
Transformer membrane failure alarm
Maintenance switch open
Station Auxiliary Transformer SAT T202
Station Aux.Transformer T202 Buchholz relay alarm operated
Station Aux.Transformer T202 Buchholz relay Trip operated
Station Aux.Transformer T202 Oil temperature high - Alarm
Station Aux.Transformer T202 Oil temperature very high - Trip
Station Aux.Transformer T202 Winding Temperature high - Alarm
Station Aux.Transformer T202 Winding Temperature very high - Trip
Station Aux.Transformer T202 Low Oil Level - Alarm
Station Aux.Transformer T202 Pressure Relief Device operated - Trip
Station Aux.Transformer T202 OLTC Buchholz trip
Station Aux. Transformer T202 Tap changer device failure alarm
Station Aux.Transformer T202 Neutral Ground Fault protection operated

17 of 29

Remarks

Annexure-1: SOER Signals for Arar Power Plant

SL.No.
486
487
488
489
490
491
492
493
494
495
496
497
498
499
500
501
502
503
504
505
506
507
508
509
510
511
512
513
514
515
516
517
518
519
520
521
522

Alarm
Code.

Tag No.
50/51
50/51
50/51
50N/51N
50/51N
50G
86 B225
74/86
86 A102
74/86
74 TC
74 DC
51
51
51
51N
51/51N

N
63-1 SAT
63-2 SAT
49-1 OSAT
49-2 OSAT
49-1 WSAT
49-2 WSAT
71 SAT
63 P SAT
63 OLTC
27
51G LV
50/51
50/51
50/51
50N/51N

List of Digital Signals for SOER


Station Aux.Transformer T202 HV BKR INST/ Inverse Time O/C Phase-A operated
Station Aux.Transformer T202 HV BKR INST/ Inverse Time O/C Phase-B operated
Station Aux.Transformer T202 HV BKR INST/ Inverse Time O/C Phase-C operated
Station Aux.Transformer T202 HV BKR INST/ Inverse Time Ground fault protection operated
Station Aux.Transformer T202 HV BKR INST/ Inverse Time O/C, E/F relay faulty.
Station Aux.Transformer T202 HV BKR CBCT protection operated
Station Aux.Transformer T202 HV BKR lockout relay operated
Station Aux.Transformer T202 HV BKR Lockout relay supervision relay operated
Station Aux.Transformer T202 LV BKR Lockout relay operated
Station Aux.Transformer T202 LV BKR Lockout relay supervision relay operated
Station Aux.Transformer T202 LV BKR Trip coil supervision relay operated
Station Aux.Transformer T202 LV BKR DC supply supervision relay operated
Station Aux.Transformer T202 LV BKR inverse time O/C Phase-A operated
Station Aux.Transformer T202 LV BKR inverse time O/C Phase-B operated
Station Aux.Transformer T202 LV BKR inverse time O/C Phase-C operated
Station Aux.Transformer T202 LV BKR inverse time earthfault relay operated
Station Aux.Transformer T202 LV BKR inverse time O/C, E/F relay faulty
OLTC pressure relief device operated
OLTC protection relay operated
OLTC Low oil level alarm
Transformer membrane failure alarm
Maintenance switch open
Station Auxiliary Transformer (Future Unit)
Station Aux.Transformer (Future) Buchholz relay alarm operated
Station Aux.Transformer (Future) Buchholz relay Trip operated
Station Aux.Transformer (Future) Oil temperature high - Alarm
Station Aux.Transformer (Future) Oil temperature very high - Trip
Station Aux.Transformer (Future) Winding Temperature high - Alarm
Station Aux.Transformer (Future) Winding Temperature very high - Trip
Station Aux.Transformer (Future) Low Oil Level - Alarm
Station Aux.Transformer (Future) Pressure Relief Device operated - Trip
Station Aux.Transformer (Future) OLTC Buchholz trip
Station Aux. Transformer (Future) Tap changer device failure alarm
Station Aux.Transformer (Future) Neutral Ground Fault protection operated
Station Aux.Transformer (Future) HV BKR INST/ Inverse Time O/C Phase-A operated
Station Aux.Transformer (Future) HV BKR INST/ Inverse Time O/C Phase-B operated
Station Aux.Transformer (Future) HV BKR INST/ Inverse Time O/C Phase-C operated
Station Aux.Transformer (Future) HV BKR INST/ Inverse Time Ground fault protection operated

18 of 29

Remarks

Annexure-1: SOER Signals for Arar Power Plant

SL.No.
523
524
525
526
527
528
529
530
531
532
533
534
535
536
537
538
539
540
541
542
543
544
545
546
547
548
549
550
551
552
553
554
555
556
557
558
559

Alarm
Code.

Tag No.
50/51N
50G
86 B221
74/86
86
74/86
74 TC
74 DC
51
51
51
51N
51/51N

O
63-1 ST
63-2 ST
49-1 OST
49-2 OST
49-1 WST
49-2 WST
71 ST
63 PST
51G1
51G2
51G1
51G2
87REF LV
87REF LV
50/51
50/51
50/51
50N/51N
50/51N

List of Digital Signals for SOER


Station Aux.Transformer (Future)HV BKR INST/ Inverse Time O/C, E/F relay faulty.
Station Aux.Transformer (Future) HV BKR CBCT protection operated
Station Aux.Transformer (Future) HV BKR lockout relay operated
Station Aux.Transformer (Future) HV BKR Lockout relay supervision relay operated
Station Aux.Transformer (Future) LV BKR Lockout relay operated
Station Aux.Transformer (Future) LV BKR Lockout relay supervision relay operated
Station Aux.Transformer (Future) LV BKR Trip coil supervision relay operated
Station Aux.Transformer (Future) LV BKR DC supply supervision relay operated
Station Aux.Transformer (Future) LV BKR inverse time O/C Phase-A operated
Station Aux.Transformer (Future) LV BKR inverse time O/C Phase-B operated
Station Aux.Transformer (Future) LV BKR inverse time O/C Phase-C operated
Station Aux.Transformer (Future) LV BKR inverse time earthfault relay operated
Station Aux.Transformer (Future) LV BKR inverse time O/C, E/F relay faulty
OLTC pressure relief device operated
OLTC protection relay operated
OLTC Low oil level alarm
Transformer membrane failure alarm
Maintenance switch open
Station Transformer ST T401
Station Transformer T401 Buchholz relay alarm operated
Station Transformer T401 Buchholz relay Trip operated
Station Transformer T401 Oil temperature high - Alarm
Station Transformer T401 Oil temperature very high - Trip
Station Transformer T401 Winding Temperature high - Alarm
Station Transformer T401 Winding Temperature very high - Trip
Station Transformer T401 Low Oil Level - Alarm
Station Transformer T401 Pressure Relief Device operated - Trip
Station Transformer T401 Neutral Ground fault protection-1 operated
Station Transformer T401 Neutral Ground fault protection-2 operated
Station Transformer T401 Neutral Ground fault Relay-1 faulty
Station Transformer T401 Neutral Ground fault Relay-2 faulty
Station Transformer T401 REF protection operated
Station Transformer T401 REF Relay faulty
Station Transformer T401 HV BKR INST/Inverse Time O/C Phase-A operated
Station Transformer T401 HV BKR INST/Inverse Time O/C Phase-B operated
Station Transformer T401 HV BKR INST/Inverse Time O/C Phase-C operated
Station Transformer T401 HV BKR INST/Inverse Time Ground fault protection operated
Station Transformer T401 HV BKR INST/Inverse Time O/C, E/F relay faulty.

19 of 29

Remarks

Annexure-1: SOER Signals for Arar Power Plant

SL.No.
560
561
562
563
564
565
566
567
568
569
570
571
572
573
574
575
576
577
578
579
580
581
582
583
584
585
586
587
588
589
590
591
592
593
594
595
596

Alarm
Code.

Tag No.
87T T401
87T T401
2/50 BF
50 BF
86-1 B419
86-2 B419
86-3 B419
74/86-1
74/86-2
74/86-3
74 TC-1
74 TC-2
86-1
86-2
74/86-1
74/86-2
50/51
50/51
50/51
51N
50/51N
86 A201
74/86
74 TC-1
74 TC-2

List of Digital Signals for SOER


Station Transformer T401 Differential Protection operated
Station Transformer T401 Differential Protection relay faulty
Station Transformer T401 HV side Breaker failure protection Timer operated -I stage Alarm
Station Transformer T401 HV side Breaker failure relay operated -II stage
Station Transformer T401 Lockout relay-1 operated
Station Transformer T401 Lockout relay-2 operated
Station Transformer T401 Lockout relay-3 operated
Station Transformer T401 Lockout relay-1 supervision relay operated
Station Transformer T401 Lockout relay-2 supervision relay operated
Station Transformer T401 Lockout relay-3 supervision relay operated
Station Transformer T401 HV BKRTrip Coil-1 Supervision relay operated
Station Transformer T401 HV BKRTrip Coil-2 Supervision relay operated
Station Transformer T401 HV BKR Lockout relay -1 operated
Station Transformer T401 HV BKR Lockout relay -2 operated
Station Transformer T401 HV BKR Lockout relay-1 supervision relay operated
Station Transformer T401 HV BKR Lockout relay-2 supervision relay operated
Station Transformer T401 LV BKR INST/Inverse Time O/C Phase-A operated
Station Transformer T401 LV BKR INST/Inverse Time O/C Phase-B operated
Station Transformer T401 LV BKR INST/Inverse Time O/C Phase-C operated
Station Transformer T401 LV BKR Inverse Time E/F relay operated
Station Transformer T401 LV BKR INST/Inverse Time O/C, E/F relay faulty
Station Transformer T401 LV BKR Lockout relay operated
Station Transformer T401 LV BKR Lockout relay supervision relay operated
Station Transformer T401 LV BKR tripcoil-1 supervision operated
Station Transformer T401 LV BKR tripcoil-2 supervision operated
Maintenance switch open
Breaker failure relay stage-1operated
Breaker failure relay stage-2 operated
Breaker failurerelay lockout relay operated
Breaker failurerelay lockout relay supervision relay operated
P
Station Transformer ST T402
63-1 ST Station Transformer T402 Buchholz relay alarm operated
63-2 ST Station Transformer T402 Buchholz relay Trip operated
49-1 OST Station Transformer T402 Oil temperature high - Alarm
49-2 OST Station Transformer T402 Oil temperature very high - Trip
49-1 WST Station Transformer T402 Winding Temperature high - Alarm
49-2 WST Station Transformer T402 Winding Temperature very high - Trip
71 ST
Station Transformer T402 Low Oil Level - Alarm

20 of 29

Remarks

Annexure-1: SOER Signals for Arar Power Plant

SL.No.
597
598
599
600
601
602
603
604
605
606
607
608
609
610
611
612
613
614
615
616
617
618
619
620
621
622
623
624
625
626
627
628
629
630
631
632
633
634

Alarm
Code.

Tag No.
63 PST
51G1
51G2
51G1
51G2
87REF LV
87REF LV
50/51
50/51
50/51
50N/51N
50/51N
87T T402
87T T402
2/50 BF
50 BF
86-1 B421
86-2 B421
86-3 B421
74/86-1
74/86-2
74/86-3
74 TC-1
74 TC-2
86-1
86-2
74/86-1
74/86-2
50/51
50/51
50/51
51N
50/51N
86 A203
74/86
74 TC-1
74 TC-2

List of Digital Signals for SOER


Station Transformer T402 Pressure Relief Device operated - Trip
Station Transformer T402 Neutral Ground fault protection-1 operated
Station Transformer T402 Neutral Ground fault protection-2 operated
Station Transformer T402 Neutral Ground fault Relay-1 faulty
Station Transformer T402 Neutral Ground fault Relay-2 faulty
Station Transformer T402 REF protection operated
Station Transformer T402 REF Relay faulty
Station Transformer T402 HV BKR INST/Inverse Time O/C Phase-A operated
Station Transformer T402 HV BKR INST/Inverse Time O/C Phase-B operated
Station Transformer T402 HV BKR INST/Inverse Time O/C Phase-C operated
Station Transformer T402 HV BKR INST/Inverse Time Ground fault protection operated
Station Transformer T402 HV BKR INST/Inverse Time O/C, E/F relay faulty
Station Transformer T402 Differential Protection operated
Station Transformer T402 Differential Protection relay faulty
Station Transformer T402 HV side Breaker failure protection Timer operated -I stage Alarm
Station Transformer T402 HV side Breaker failure relay operated -II stage
Station Transformer T402 Lockout relay-1 operated
Station Transformer T402 Lockout relay-2 operated
Station Transformer T402 Lockout relay-3 operated
Station Transformer T402 Lockout relay-1 supervision relay operated
Station Transformer T402 Lockout relay-2 supervision relay operated
Station Transformer T402 Lockout relay-3 supervision relay operated
Station Transformer T402 HV BKRTrip Coil-1 Supervision relay operated
Station Transformer T402 HV BKRTrip Coil-2 Supervision relay operated
Station Transformer T402 HV BKR Lockout relay -1 operated
Station Transformer T402 HV BKR Lockout relay -2 operated
Station Transformer T402 HV BKR Lockout relay-1 supervision relay operated
Station Transformer T402 HV BKR Lockout relay-2 supervision relay operated
Station Transformer T402 LV BKR O/C Phase-A operated
Station Transformer T402 LV BKR O/C Phase-B operated
Station Transformer T402 LV BKR O/C Phase-C operated
Station Transformer T402 LV BKR Inverse Time E/F relay operated
Station Transformer T402 LV BKR INST/Inverse Time O/C, E/F relay faulty
Station Transformer T402 LV BKR Lockout relay operated
Station Transformer T402 LV BKR Lockout relay supervision relay operated
Station Transformer T402 LV BKR tripcoil-1 supervision operated
Station Transformer T402 LV BKR tripcoil-2 supervision operated
Maintenance switch open

21 of 29

Remarks

Annexure-1: SOER Signals for Arar Power Plant

SL.No.
635
636
637
638
639
640
641
642
643
644
645
646
647
648
649
650
651
652
653
654
655
656
657
658
659
660
661
662
663
664
665
666
667
668
669
670
671

Alarm
Code.

Tag No.

Q
63-1 ST
63-2 ST
49-1 OST
49-2 OST
49-1 WST
49-2 WST
71 ST
63 PST
51G1
51G2
51G1
51G2
87REF LV
87REF LV
50/51
50/51
50/51
50N/51N
50/51N
87T T403
87T T403
2/50 BF
50 BF
86-1
86-2
86-3
74/86-1
74/86-2
74/86-3
74 TC-1
74 TC-2
86-1
86-2

List of Digital Signals for SOER


Breaker failure relay stage-1operated
Breaker failure relay stage-2 operated
Breaker failurerelay lockout relay operated
Breaker failurerelay lockout relay supervision relay operated
Station Transformer (Future Unit)
Station Transformer (Future) Buchholz relay alarm operated
Station Transformer (Future) Buchholz relay Trip operated
Station Transformer (Future) Oil temperature high - Alarm
Station Transformer (Future) Oil temperature very high - Trip
Station Transformer (Future) Winding Temperature high - Alarm
Station Transformer (Future) Winding Temperature very high - Trip
Station Transformer (Future) Low Oil Level - Alarm
Station Transformer (Future) Pressure Relief Device operated - Trip
Station Transformer (Future) Neutral Ground fault protection-1 operated
Station Transformer (Future) Neutral Ground fault protection-2 operated
Station Transformer (Future) Neutral Ground fault Relay-1 faulty
Station Transformer (Future) Neutral Ground fault Relay-2 faulty
Station Transformer (Future) REF protection operated
Station Transformer (Future) REF Relay faulty
Station Transformer (Future) HV BKR INST/Inverse Time O/C Phase-A operated
Station Transformer (Future) HV BKR INST/Inverse Time O/C Phase-B operated
Station Transformer (Future) HV BKR INST/Inverse Time O/C Phase-C operated
Station Transformer (Future) HV BKR INST/Inverse Time Ground fault protection operated
Station Transformer (Future) HV BKR INST/Inverse Time O/C, E/F relay faulty.
Station Transformer (Future) Differential Protection operated
Station Transformer (Future) Differential Protection relay faulty
Station Transformer (Future) HV side Breaker failure protection Timer operated -I stage Alarm
Station Transformer (Future) HV side Breaker failure relay operated -II stage
Station Transformer (Future) Lockout relay-1 operated
Station Transformer (Future) Lockout relay-2 operated
Station Transformer (Future) Lockout relay-3 operated
Station Transformer (Future) Lockout relay-1 supervision relay operated
Station Transformer (Future) Lockout relay-2 supervision relay operated
Station Transformer (Future) Lockout relay-3 supervision relay operated
Station Transformer (Future) HV BKRTrip Coil-1 Supervision relay operated
Station Transformer (Future) HV BKRTrip Coil-2 Supervision relay operated
Station Transformer (Future) HV BKR Lockout relay -1 operated
Station Transformer (Future) HV BKR Lockout relay -2 operated

22 of 29

Remarks

Annexure-1: SOER Signals for Arar Power Plant

SL.No.
672
673
674
675
676
677
678
679
680
681
682
683
684
685
686
687
688
689
690
691
692
693
694
695
696
697
698
699
700
701
702
703
704
705
706
707
708

Alarm
Code.

Tag No.
74/86-1
74/86-2
50/51
50/51
50/51
51N
50/51N
86
74/86
74 TC-1
74 TC-2

R
87 B1
87 B1
87 B1
87 B2
87 B2
87 B2
51
51
51
51N
51/51N
86 A205
74/86
74 DC
74 TC-1
74 TC-2
95B1
95B1
95B1
95B2
95B2

List of Digital Signals for SOER


Station Transformer (Future) HV BKR Lockout relay-1 supervision relay operated
Station Transformer (Future) HV BKR Lockout relay-2 supervision relay operated
Station Transformer (Future) LV BKR INST/Inverse Time O/C Phase-A operated
Station Transformer (Future) LV BKR INST/Inverse Time O/C Phase-B operated
Station Transformer (Future) LV BKR INST/Inverse Time O/C Phase-C operated
Station Transformer (Future) LV BKR Inverse Time E/F relay operated
Station Transformer (Future) LV BKR INST/Inverse Time O/C, E/F relay faulty
Station Transformer (Future) LV BKR Lockout relay operated
Station Transformer (Future) LV BKR Lockout relay supervision relay operated
Station Transformer (Future) LV BKR tripcoil-1 supervision operated
Station Transformer (Future) LV BKR tripcoil-2 supervision operated
Maintenance switch open
Breaker failure relay stage-1operated
Breaker failure relay stage-2 operated
Breaker failurerelay lockout relay operated
Breaker failurerelay lockout relay supervision relay operated
4.16kV Switchgear
4.16kV Switchgear Bus Section-1 87 B1 Phase-A operated
4.16kV Switchgear Bus Section-1 87 B1 Phase-B operated
4.16kV Switchgear Bus Section-1 87 B1 Phase-C operated
4.16kV Switchgear Bus Section-2 87 B2 Phase-A operated
4.16kV Switchgear Bus Section-2 87 B2 Phase-B operated
4.16kV Switchgear Bus Section-2 87 B2 Phase-C operated
4.16kV Bus Section breaker Inverse time O/C Phase-A operated
4.16kV Bus Section breaker Inverse time O/C Phase-B operated
4.16kV Bus Section breaker Inverse time O/C Phase-C operated
4.16kV Bus Section breaker Ground fault protection operated
4.16kV Bus Section breaker O/C, E/F relay faulty
4.16kV Bus section breaker Lockout relay operated
4.16kV Bus section breaker Lockout supervision relay operated
4.16kV Bus section breaker DC supply failure relay operated.
4.16kV Bus Section breaker trip coil-1 supervision relay operated
4.16kV Bus Section breaker trip coil-2 supervision relay operated
4.16kV SWGR Busbar-1 CT supervision relay(95B1) phase-A operated
4.16kV SWGR Busbar-1 CT supervision relay(95B1) phase-B operated
4.16kV SWGR Busbar-1 CT supervision relay(95B1) phase-C operated
4.16kV SWGR Busbar-1 CT supervision relay(95B2) phase-A operated
4.16kV SWGR Busbar-1 CT supervision relay(95B2) phase-B operated

23 of 29

Remarks

Annexure-1: SOER Signals for Arar Power Plant

SL.No.
709
710
711
712
713
714
715
716
717
718
719

Alarm
Code.

Tag No.
95B2
95BX1
95BX2
86B1
86B2
74/86B1
74/86B2
74DC1
74DC2
27
27

List of Digital Signals for SOER


4.16kV SWGR Busbar-1 CT supervision relay(95B2) phase-C operated
4.16kV SWGR Bus-1 BB protection CT shorting lockout Relay (95BX1) operated
4.16kV SWGR Bus-2 BB protection CT shorting lockout Relay (95BX2) operated
4.16 SWGR BB-1 Protection lock relay operated
4.16 SWGR BB-2 Protection lock relay operated
4.16 SWGR BB-1 lock relay coil supervision 74/86B1 operated.
4.16 SWGR BB-2 lock relay coil supervision 74/86B2 operated.
4.16kV SWGR Bus section 74DC1 failed
4.16kV SWGR Bus section 74DC2 failed
4.16 kV SWGR Bus-1 UV trip lockout relay(27/UV) operated
4.16 kV SWGR Bus-2 UV trip lockout relay(27/UV) operated

720
721
722
723
724
725
726
727
728
729
730
731
732
733
734

STM
50M/51M
50M/51M
50M/51M
50M/51M
50G
86M
74 TC-1
74 TC-2
74/86
49-1B
49-2B
49A
WTI A
WTI TRIP

GTG-7 Starting motor protection relay operated


GTG-7 starting motor feeder O/C Phase-A operated
GTG-7 starting motor feeder O/C Phase-B operated
GTG-7 starting motor feeder O/C Phase-C operated
GTG-7 starting motor feeder O/C relay faulty
GTG-7 starting motor feeder CBCT fault protection operated
GTG-7 starting motor feeder breaker lockout relay operated
GTG-7 starting motor feeder breaker trip coil-1supervision relay operated
GTG-7 starting motor feeder breaker trip coil-2 supervision relay operated
GTG-7 starting motor feeder breaker lockout relay supervision relay operated
GTG-7 starting motor bearing temperature high alarm
GTG-7 starting motor bearing temperature very high trip
GTG-7 starting motor cooler failure
GTG-7 starting motor winding temperature high alarm
GTG-7 starting motor winding temperature very high trip

735
736
737
738
739
740
741
742
743
744

STM
50M/51M
50M/51M
50M/51M
50M/51M
50G
86M
74 TC-1
74 TC-2
74/86

GTG-8 Starting motor protection relay operated


GTG-7 starting motor feeder O/C Phase-A operated
GTG-7 starting motor feeder O/C Phase-B operated
GTG-7 starting motor feeder O/C Phase-C operated
GTG-7 starting motor feeder O/C relay faulty
GTG-8 starting motor feeder CBCT fault protection operated
GTG-8 starting motor feeder breaker lockout relay operated
GTG-8 starting motor feeder breaker trip coil-1supervision relay operated
GTG-8 starting motor feeder breaker trip coil-2 supervision relay operated
GTG-8 starting motor feeder breaker lockout relay supervision relay operated

24 of 29

Remarks

Annexure-1: SOER Signals for Arar Power Plant

SL.No.
745
746
747
748
749

Alarm
Code.

Tag No.
49-1B
49-2B
49A
WTI A
WTI TRIP

List of Digital Signals for SOER


GTG-8 starting motor bearing temperature high alarm
GTG-8 starting motor bearing temperature very high trip
GTG-8 starting motor cooler failure
GTG-8 starting motor winding temperature high alarm
GTG-8 starting motor winding temperature very high trip

750
751
752
753
754
755
756
757
758
759
760
761
762
763
764

STM
50M/51M
50M/51M
50M/51M
50M/51M
50G
86M
74 TC-1
74 TC-2
74/86
49-1B
49-2B
49A
WTI A
WTI TRIP

Future GTG Starting motor protection relay operated


GTG-7 starting motor feeder O/C Phase-A operated
GTG-7 starting motor feeder O/C Phase-B operated
GTG-7 starting motor feeder O/C Phase-C operated
GTG-7 starting motor feeder O/C relay faulty
Future GTG starting motor feeder CBCT fault protection operated
Future GTG starting motor feeder breaker lockout relay operated
Future GTG starting motor feeder breaker trip coil-1supervision relay operated
Future GTG starting motor feeder breaker trip coil-2 supervision relay operated
Future GTG starting motor feeder breaker lockout relay supervision relay operated
Future GTG starting motor bearing temperature high alarm
Future GTG starting motor bearing temperature very high trip
Future GTG starting motor cooler failure
Future GTG starting motor winding temperature high alarm
Future GTG starting motor winding temperature very high trip

765
766
767
768
769
770
771
772
773
774
775
776

S
51
51
51
51N
51
86 A103
74/86
74 DC
74 TC
27
27
T

777
778
779

480V Station Switchgear


480V Bus Section breaker Inverse time O/C Phase-A operated
480V Bus Section breaker Inverse time O/C Phase-B operated
480V Bus Section breaker Inverse time O/C Phase-C operated
480V Bus Section breaker Inverse time E/F relay operated
480V Bus Section breaker Inverse time O/C, E/F Relay faulty
480V Bus section breaker Lockout relay operated
480V Bus section breaker Lockout relay Supervision relay operated
480V Bus section breaker DC supply failure relay operated
480V Bus Section breaker trip circuit supervision relay operated
480V Bus Section-1 UV trip lockout relay(27/UV) operated
480V Bus Section-2 UV trip lockout relay(27/UV) operated
Fuel oil System
Forwarding pump1 Trip
Forwarding pump2 Trip
Forwarding pump3 Trip

25 of 29

Remarks

Annexure-1: SOER Signals for Arar Power Plant

SL.No.
780
781
782
783
784
785
786
787
788
789
790
791
792
793
794
795
796
797
798
799
800
801
802
803
804
805

806
807
808
809
810
811

Alarm
Code.

Tag No.

List of Digital Signals for SOER


Forwarding pump4 Trip
Level switch High High DFO Tank#1(FOS-10-LSHH-01)
Level switch High DFO Tank#1(FOS-10-LSH-02)
Level switch Low DFO Tank#1(FOS-10-LSL-03)
Level switch Low Low DFO Tank#1(FOS-10-LSLL-04)
Level switch High High DFO Tank#2(FOS-10-LSHH-05)
Level switch High DFO Tank#2(FOS-10-LSH-06)
Level switch Low DFO Tank#2(FOS-10-LSL-07)
Level switch Low Low DFO Tank#2(FOS-10-LSLL-08)
Level switch High High DFO Tank#3(FOS-10-LSHH-09)
Level switch High DFO Tank#3(FOS-10-LSH-10)
Level switch Low DFO Tank#3(FOS-10-LSL-11)
Level switch Low Low DFO Tank#3(FOS-10-LSLL-12)
Level switch High High DFO Tank#4(FOS-10-LSHH-13)
Level switch High DFO Tank#4(FOS-10-LSH-14)
Level switch Low DFO Tank#4(FOS-10-LSL-15)
Level switch Low Low DFO Tank#4(FOS-10-LSLL-16)
V
EXCITATION(Unit-7)
64F
Field ground fault
94EX-1
Exciter trip output relay
59F
Exciter Overvoltage
V
EXCITATION (Unit-8)
64F
Field ground fault
94EX-1
Exciter trip output relay
59F
Exciter Overvoltage
V
EXCITATION (Future Unit)
64F
Field ground fault
94EX-1
Exciter trip output relay
59F
Exciter Overvoltage
W
MISCELLANEOUS
Unit-7
74GT/52GT Gas Turbine fault inducing generator trip
98(VT-2) Voltage Transformer -2 fuse fail
98(VT-4) Voltage Transformer -4 fuse fail
NGT alarm NGT Over heating alarm
NGT trip NGT Over heating trip
Unit-8
74GT/52GT Gas Turbine fault inducing generator trip

26 of 29

Remarks

Annexure-1: SOER Signals for Arar Power Plant

SL.No.
812
813
814
815
816
817
818
819
820

821
822
823
824
825
826
827
828
829
830
831
832

833
834
835
836
837
838
839
840
841
842

Alarm
Code.

Tag No.
98(VT-2)
98(VT-4)
NGT alarm
NGT trip

List of Digital Signals for SOER


Voltage Transformer -2 fuse fail
Voltage Transformer -4 fuse fail
NGT Over heating alarm
NGT Over heating trip
Future Unit
74GT/52GT Gas Turbine fault inducing generator trip
98(VT-2) Voltage Transformer -2 fuse fail
98(VT-4) Voltage Transformer -4 fuse fail
NGT alarm NGT Over heating alarm
NGT trip NGT Over heating trip
X
OTHER ALARMS
Unit-7
Bearing Vibration
Bearing Oil Temp.High
Negative Sequence Current
Generator Overvoltage
Unit-8
Bearing Vibration
Bearing Oil Temp.High
Negative Sequence Current
Generator Overvoltage
Future Unit
Bearing Vibration
Bearing Oil Temp.High
Negative Sequence Current
Generator Overvoltage
Y
STATOR COOLING WATER SYSTEM
Unit-7
Inlet Temp.High
Inlet Flow low
Inlet Pressure Low
Liquid Header Outlet Temp High
Bulk water Outlet Temp.High
Conn.Ring Temp.High
Conn.Ring Flow Low
HV Bushing Outlet Temp.High
HV Bushing Flow Low
Main Filter Diff.Pressure High

27 of 29

Remarks

Annexure-1: SOER Signals for Arar Power Plant

SL.No.
843
844
845
846
847
848
849
850
851
852
853
854
855
856
857
858
859
860
861
862
863
864
865
866
867
868
869
870
871
872
873
874

Alarm
Code.

Tag No.

List of Digital Signals for SOER


Conductivity High
Tank Level High/Low
Reservce Pump running
Runback Initiated
Unit-8
Inlet Temp.High
Inlet Flow low
Inlet Pressure Low
Liquid Header Outlet Temp High
Bulk water Outlet Temp.High
Conn.Ring Temp.High
Conn.Ring Flow Low
HV Bushing Outlet Temp.High
HV Bushing Flow Low
Main Filter Diff.Pressure High
Conductivity High
Tank Level High/Low
Reservce Pump running
Runback Initiated
Future Unit
Inlet Temp.High
Inlet Flow low
Inlet Pressure Low
Liquid Header Outlet Temp High
Bulk water Outlet Temp.High
Conn.Ring Temp.High
Conn.Ring Flow Low
HV Bushing Outlet Temp.High
HV Bushing Flow Low
Main Filter Diff.Pressure High
Conductivity High
Tank Level High/Low
Reservce Pump running
Runback Initiated

28 of 29

Remarks

Annexure-1: SOER Signals for Arar Power Plant

SL.No.

Alarm
Code.

Tag No.

List of Digital Signals for SOER

NOTE : The points considerd above are excluding the required no.of spare points and Minimum points as
per clause 7.1 and 7.2 of PTS document 1022 Appendix-V

29 of 29

Remarks