30421007-3CL-00006P0A
SHEET i OF i
SIZING REPORT
ENGINEERING CONSULTANT
TCE CONSULTING ENGINEERS LIMITED
73/1, ST. MARKS ROAD
BANGALORE 560 001
INDIA
CONTRACTOR:
AL-TOUKHI COMPANY FOR INDUSTRY & TRADING
P.O. BOX 497, RIYADH 11411, KINGDOM OF SAUDI ARABIA
TEL. 00966-1-4633660 : FAX. 009661-4631150
P0A
29-07-2004
DG
SR
REV NO . DATE
PREPARED BY
CHECKED BY
CLEARED BY
APPROVED BY
30421007-3CL-00006P0A
CONTENTS
SHEET i OF i
SIZING REPORT
CONTENTS
CLAUSE No.
DESCRIPTION
PAGE No.
1.0
INTRODUCTION
2.0
OBJECT
3.0
REFERENCES
4.0
ASSUMPTIONS / CONSIDERATIONS
5.0
SIZING CALCULATION
6.0
CONCLUSIONS
ISSUE
A
FILE NAME: F120R1
WRITEUP
SHEET 1 OF 8
SIZING REPORT
1.0
INTRODUCTION:
1.1
Al-Toukhi company for Industry & Trading has been awarded turnkey
contract for Open Cycle Gas Turbine based CPS expansion project at
Arar of Saudi Electric Company-Eastern Operation Area (SEC-EOA),
Saudi Arabia.
1.2
ISSUE
A
FILE NAME: F120R1
WRITEUP
SHEET 2 OF 8
SIZING REPORT
2.0
OBJECT:
2.1
2.1.1
ISSUE
A
FILE NAME: F120R1
WRITEUP
SHEET 3 OF 8
SIZING REPORT
3.0
REFERENCES:
3.1
3.2
ISSUE
A
FILE NAME: F120R1
WRITEUP
SHEET 4 OF 8
SIZING REPORT
4.0
ASSUMPTIONS/CONSIDERATIONS:
The following assumptions are made for purpose of Station
Transformer sizing calculations.
4.1
4.2
4.3
4.4
The final rating of the transformer will not be less than the rating
indicated in the Technical proposal.
4.5
4.5.1
4.5.2
During failure of one ST, the other ST will feed the entire 4.16kV
Switchgear loads. Under this condition, outage of two UATs and
starting of one 4.16kV Starting motor is considered, such that the
ST will be feeding the starting motor, entire station loads and two
Unit auxiliary Switchgear loads.
ISSUE
A
FILE NAME: F120R1
WRITEUP
SHEET 5 OF 8
SIZING REPORT
5.0
SIZING CALCULATION :
5.1
5.1.1
5.1.2
1765kVA
(Refer to Page 2 of 2, Annexure-II of Doc.No.30421007-3CL-00003P0A: Station and Unit Auxiliary transformers sizing report )
Considering 10 % margin, Base load = 1765 x 1.1 = 1941.5 kVA
5.1.3
(As per preliminary load list. This rating would be confirmed with
Sub Vendor)
Starting Motor kVA
= 663 / 0.85x0.95
= 821 kVA
ISSUE
A
FILE NAME: F120R1
WRITEUP
SHEET 6 OF 8
SIZING REPORT
5.1.4
1941.5 + 4515.5
6457 kVA
5.2
5.2.1
5.2.2
1765kVA
(Refer to Page 2 of 2, Annexure-II of Doc.No.30421007-3CL-00003P0A: Station and Unit Auxiliary transformers sizing report )
Considering 10 % margin, Base load = 1765 x 1.1 = 1941.5 kVA
5.2.3
= 663 / 0.85x0.95
= 821 kVA
5.2.4
1941.5 + 821
2762.5 kVA
ISSUE
A
WRITEUP
SHEET 7 OF 8
SIZING REPORT
5.3
5.4
i)
ii)
iii)
5.5
6.0
CONCLUSION:
6.1
Parameter
Unit
ST
Rating
kVA
7500
Voltage
load)
kV
33/4.16
%Impedance
Vector Group
Dyn1
Cooling Type
ONAN
Indoor / Outdoor
Outdoor
ratio
(No
Reference
As per Cl No.5.0
above
As per Cl No.3.03.2
of PTS-1022
As per Cl No.3.03.2
of PTS-1022
As per Cl No.3.03.2
of PTS-1022
As per Cl No.3.03.2
of PTS-1022
As per Cl No.3.03.2
of PTS-1022
ISSUE
A
WRITEUP
SHEET 8 OF 8
SIZING REPORT
Sl.No.
Parameter
Dry type
type
/Oil
filled
Tap changer
Unit
ST
Oil Filled
Off circuit
tap
Changer
+/- 5%
Reference
As per Cl No.3.03.2
of PTS-1022
As per Cl No.3.03.2
of PTS-1022
ISSUE
A
FILE NAME: F120R1