Option: potentiometer
for analog output
Eject gap
10
11
-
12
13
14
Analog
output
(option)
PT100 (2-wire)
DT 3.202.110C (200C)
DT 3.206.110C (600C)
DT 3.302.110C (200C)
DT 3.306.110C (600C)
115 VAC
230 VAC
2 wire
2 wire
3+2 wire
3+2 wire
PT100 (3-wire)
Options
z green LED
z Protection IP54
z Protection IP65
z Analog output 0-10 VDC/10 mA
z Analog output 0-20 mA/load 50 0
z Analog output 4-20 mA/load 500
z Analog output 0-10 VDC/10 mA
(power supply 24 VDC galvanically insulated)
z Analog output 0-20 mA/load 500 (power supply 24 VDC galvanically insulated)
z Analog output 4-20 mA/load 500 (power supply 24 VDC galvanically insulated)
z Analog output with customer specified offset
The measuring inputs are not galvanically insulated from the analog output!
z Power supply 24/48 VAC
z PT 100 with 4-wire on demand - connection see PT4.106.1x2
z Setpoints see type PTE 4.xxx.1xx
DT 3.202.170C (200C)
DT 3.206.170C (600C)
DT 3.302.170C (200C)
DT 3.306.170C (600C)
Input
Output
Type
DT3.xx2.1xxC
Housing
Assembly cut out
Fastening
Housing material
Protective system
Weight
Connection
PT100
Analogue output
Measuring range
Resolution
Measuring range
Resolution
Sensor current
-50.0 up to 199.9 C
0.1 C
-100 up to +600 C
1 C
approx. 1 mA
Indication
Measuring fault
Measuring fault
Temp. drift
Measuring principle
Supply voltage
Power consumption
Display
Ambient
conditions
Indication time
Line break
Working temperature
Storing temperature
DT3.xx6.1xxC
Accuracy
DT3.xx2.1xxC
DT3.xx6.1xxC
Power unit
Housing:
111 mm
48 mm
96 mm
89 mm
43 mm
131 mm
(with plug in terminal 148 mm)
126 mm
CE-sign
For unlimited use of the instrument within the directives for electromagnetic compatibility 89/336/EC measuring
wires have to be used with shielded cable and cable's shield connected to earth ground at one end only.
Setting
The unit is adjusted ex works. Later adjustments are necessary in applications with long distance wiring only.
1. Connect the instrument according to the wiring diagram and turn power on.
2. Setting of sensor and line balancing: Remove the front pane using the eject gap.
3. Connect PT100 simulator and set temperature to 0C.
4. If necessary deviations on the display have to be corrected with potentiometer for line balancing.