SPLIT-TYPE, AIR CONDITIONERS
SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS
INDOOR UNIT
No. OB385
SERVICE MANUAL
REVISED EDITION-B
Wireless type
Models
E1
E1
E1
NOTE:
This service manual describes technical data of the indoor units.
RoHS compliant products have <G> mark on the spec name plate.
For servicing of RoHS compliant products, refer to the RoHS PARTS LIST (RoHS compliant).
OB385B.qxp
07.5.21 4:41 PM
Page 2
Revision A:
RoHS PARTS LIST has been added.
Revision B:
Indoor heat exchanger of MSC-GA35VB -
E1
OB385B.qxp
07.5.21 4:41 PM
Page 3
TECHNICAL CHANGES
MSC-A07YV - E1 MSC-GA20VB - E1
1. Indication of capacity has been changed. (BTU base kW)
2. P.C. board has been changed.
3. Air cleaning filter has been changed to optional parts.
4. Fan motor has been changed.
5. Fan motor capacitor has been changed.
6. Color of indoor unit has been changed.
MSC-A09YV - E1 MSC-GA25VB - E1
1. Indication of capacity has been changed. (BTU base kW)
2. P.C. board has been changed.
3. Air cleaning filter has been changed to optional parts.
4. Fan motor has been changed.
5. Fan motor capacitor has been changed.
6. Color of indoor unit has been changed.
MSC-A12YV - E1 MSC-GA35VB - E1
1. Indication of capacity has been changed. (BTU base kW)
2. P.C. board has been changed.
3. Air cleaning filter has been changed to optional parts.
4. Fan motor has been changed.
5. Fan motor capacitor has been changed.
6. Color of indoor unit has been changed.
MSC-GA20VB
MSC-GA25VB
MSC-GA35VB
Front panel
Air inlet
to Breaker
Panel
Catechin air filter
(With deodorizer)
Air outlet
Vertical vanes
Fan
Horizontal vane
Remote controller
Display section
Operation section
(When the front panel is opened)
Remote control
receiving section
OB385B.qxp
07.5.21 4:41 PM
Page 4
MSC-GA20VB
MSC-GA25VB
MSC-GA35VB
ACCESSORIES
1 Installation plate
REMOTE CONTROLLER
Signal transmitting section
PM
AM
OPERATE /STOP
(ON /OFF) button
TOO
ON/OFF WARM
TOO
COOL
TEMPERATURE buttons
CLOCK
PM
AM
TOO
ON/OFF WARM
TOO
COOL
FAN
STOP
VANE
START
I FEEL COOL
HEAT
/FAN
DRY
MODE
HR.
ECONO COOL
MIN.
RESET CLOCK
OFF-TIMER button
ON-TIMER button
HR. button
MIN. button
(TIME SET button)
CLOCK SET button
VANE CONTROL button
RESET button
07.5.21 4:41 PM
Page 5
SPECIFICATION
Indoor model
Function
Indoor unit power supply
Special
remarks
Fan
motor
Electrical
data
K /h
A
A
W
%
A
"
mm
kg
dB
rpm
k"
k"
MSC-GA25VB
MSC-GA35VB
MSC-GA20VB
Heating
Heating
Heating
Cooling
Cooling
Cooling
Single phase
Single phase
Single phase
230V,50Hz
230V,50Hz
230V,50Hz
474/372 w/276 w 510/420 w /342w 474/384 w/306w 588/456 w/342w 582/444 w/324w 606/498 w/396w
10
10
10
0.17
0.19
0.17
35
40
35
90
92
90
0.17
0.19
0.17
RC4V19-JA
RC4V19-HA
RC4V19-JA
WHT-BLK 283
WHT-BLK 224
WHT-BLK 283
BLK-RED 188
BLK-RED 318
BLK-RED 188
815O278O244
815O278O244
815O278O244
9
10
9
5
5
5
36/31w /25 w 36/31 w /25 w
36/31w /25 w
39/32w/25 w
40/33w/26 w
39/33w/26 w
900/750w/600 w 950/820 w /700 w 900/770w/650w 1,050/870w/700w 930/760w/600w 960/830w/700 w
3
3
3
10
10
10
10
10
10
KP1A or KM04F
KP1A or KM04F
KP1A or KM04F
Heating : Indoor
Outdoor
DB20C
DB7C WB6C
MSC-GA20VB
COOLING
SPL(dB(A))
MSC-GA25VB
LINE
36
High
HEATING
Test conditions,
Cooling : DB27:
Heating : DB20:
90
90
80
80
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
APPROXIMATE
TERESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
125
500
1000
2000
4000
HEATING
39
LINE
WB19:
WB -:
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
250
36
70
NC-20
10
63
SPL(dB(A))
COOLING
Test conditions.
Cooling : DB27:
Heating : DB20:
WB19:
WB -:
OB385B.qxp
APPROXIMATE
TERESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
NC-20
10
8000
63
125
250
500
1000
2000
4000
8000
OB385B.qxp
07.5.22 7:48 AM
MSC-GA35VB
Page 6
SPL(dB(A))
COOLING
40
HEATING
39
Test conditions.
Cooling : DB27:
Heating : DB20:
LINE
WB19:
WB -:
90
80
70
NC-70
60
NC-60
50
NC-50
INDOOR UNIT
WALL
40
NC-40
1m
30
NC-30
20
APPROXIMATE
TERESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
0.8m
NC-20
MICROPHONE
10
63
125
250
500
1000
2000
4000
8000
133.5
231.5
Installation plate
Indoor unit
Unit: mm
271
81.5
MSC-GA20VB
MSC-GA25VB
4.5
81.5
326
42
41
2.5
783
81.5
326
242
278
7 or more
815
19
162
58
90
149
606
30
60
Installation plate
Air out
Power supply cord
Lead to right 1.0m
Lead to left 0.3m
110
244
Page 7
MSC-GA35VB
161.5
161.5
2.5
41
81.5
326
42
Indoor unit
258
218.5
Installation plate
783
Unit: mm
17.5
07.5.21 4:41 PM
81.5
326
242
Installation plate
7 or more
815
278
58
90
149
606
30
60
19
110
Air out
244
162
WIRING DIAGRAM
TB
BRN
BRN
3
FOR MUH OR
MXZ-A TYPE
12V
RED
BLU
BLU
FOR
MU OR
MUX TYPE
12V
WHT
BLK
LD103
PE
CIRCUIT BREAKER
SYMBOL
NAME
CN
151
LD105
CN
112
CN201
3
2
1
CN202
2
1
CN
111
CN
109
T11
NR11
CN
121
C11
F11
SR141
1
3
5
RT12
RT11
3
BLK
GRY
YLW
BRN
WHT
RED
1
2
3
4
5
6
MF
CN211
CN
125
GRN
POWER
SUPPLY
CORD
~/N 230V
50Hz
GRN/YLW
OB385B.qxp
2
5
POWER MONITOR
RECEIVER P.C.BOARD
MV
REMOTE
CONTROLLER
NAME
SYMBOL
SYMBOL
NAME
C11
NR11
VARISTOR
TB
TERMINAL BLOCK
F11
FUSE(3.15A)
RT11
T11
TRANSFORMER
MF
RT12
MV
VANE MOTOR
SR141
NOTE:1. About the outdoor side electric wiring, refer to the outdoor unit electric wiring diagram for servicing.
2. Use copper conductors only. (For field wiring)
3. Symbols below indicate.
/: Terminal block,
: Connector
OB385B.qxp
07.5.21 5:14 PM
Page 8
MSC-GA20VB
MSC-GA25VB
MSC-GA35VB
Refrigerant pipe [9.52
(with heat insulator)
Indoor
heat
exchanger
Unit:mm
Indoor coil
thermistor
RT12
Flared connection
Room temperature
thermistor
RT11
Flared connection
Refrigerant flow
in cooling
SERVICE FUNCTIONS
MSC-GA20VB
MSC-GA25VB
MSC-GA35VB
For modification, take out the batteries and press the OPERATE/STOP(ON/OFF) button twice or 3 times at
first. After modification, put back the batteries then press the RESET button.
J1
8
OB385B.qxp
07.5.21 4:41 PM
Page 9
J1
J2
The P.C. board has the print J1 and J2. Solder J1 and J2 according to the number of indoor unit as shown in Table 1.
After modification, press the RESET button.
Table 1
No. 1 unit
No. 2 unit
No. 3 unit
No. 4 unit
1 unit operation
No modification
2 units operation
Same as at left
Solder J1
3 units operation
Same as at left
Same as at left
Solder J2
4 units operation
Same as at left
Same as at left
Same as at left
Solder both J1 and J2
How to set the remote controller exclusively for particular indoor unit
After you turn the breaker ON, the first remote controller that sends the signal to the indoor unit will be regarded as the
remote controller for the indoor unit.
The indoor unit only accepts the signal from the remote controller that has been assigned to the indoor unit once they are
set.
The setting will be cancelled if the breaker has turned OFF, or the power supply has shut down.
Please conduct the above setting once again after the power has restored.
The position
of the slide
switch
OB385B.qxp
07.5.21 4:41 PM
Page 10
8-4. MU & MUX TYPE / MUH & MXZ TYPE SWITCH OVER AND AUTO RESTART FUNCTION
1. MU & MUX TYPE / MUH & MXZ TYPE SWITCH OVER
SW2-1 sets the AUTO RESTART FUNCTION ON / OFF.
The indoor units for MU & MUX type and MUH & MXZ type SW2-2 switches over the MU & MUX type / MUH & MXZ type.
are common specifications. Set switch according to the
When the units are shipped from the factory, SW2 is as follows.
type of outdoor unit. The units are set for
SW2-1: AUTO RESTART FUNCTION ON
MUH & MXZ type when they are shipped from the factory.
SW2-2: MUH & MXZ type
F11
1
C1
L101
C
N
1
21
LD105
CN202
IC101
SW1
1 2
1 2
SW2
1 2
1 2
SW2
CN151
Outdoor unit
MUH & MXZ type
Set 2 switch downside.
SW2
Outdoor unit
MU & MUX type
Set 2 switch upside.
FRONT
1 2
1 2
CN121 CN112
CN201
How to switch over MU & MUX TYPE / MUH & MXZ TYPE
! Turn OFF the main power for the unit.
@ Pull out the electronic control P.C. board, and change
switch(SW2-2) on the indoor electronic control P.C. board
according to the type of outdoor unit as following figures.
SW2
1 2
1 2
SW2
1 2
1 2
SW2
NOTE
The operation settings are memorized when 10 seconds have passed after the remote controller was operated.
If main power is cut while AUTO START/STOP timer is active, the timer setting is cancelled.
If the unit has been off with the remote controller before power failure, the auto restart function does not work as the
power button of the remote controller is off.
To prevent breaker off due to the rush of starting current, systematize other home appliance not to turn ON at the same
time.
When some air conditioners are connected to the same supply system, if they are operated before power failure, the
starting current of all the compressors may flow simultaneously at restart.
Therefore, the special counter-measures are required to prevent the main voltage-drop or the rush of the starting current
by adding system that allows the units to start one by one.
10
OB385B.qxp
07.5.21 4:41 PM
Page 11
TROUBLESHOOTING
MSC-GA20VB
MSC-GA25VB
MSC-GA35VB
9-1. Cautions on troubleshooting
1. Before troubleshooting, check the following:
1) Check the power supply voltage.
2) Check the indoor/outdoor connecting wire for mis-wiring.
2. Take care of the following during servicing
1) Before servicing the air conditioner, be sure to turn OFF the main unit first with the remote controller. After confirming
the horizontal vane is closed, turn OFF the breaker and/or disconnect the power plug.
2) Be sure to turn OFF the power supply before removing the front panel, the cabinet, the top panel, and the electronic
control P.C. board.
3) When removing the electronic control P.C. board, hold the edge of the board with care NOT to apply stress on the
components.
4) When connecting or disconnecting the connectors, hold the housing of the connector. DO NOT pull the lead wires.
Lead wiring
Housing point
3. Troubleshooting procedure
1) First, check if the OPERATION INDICATOR lamp on the indoor unit is flashing on and off to indicate an abnormality.
To make sure, check how many times the abnormality indication is flashing on and off before starting service work.
2) If the electronic control P.C. board is supposed to be defective, check the copper foil pattern for disconnection and the
components for bursting and discoloration.
3) When troubleshooting, refer to 9-2. Instruction of troubleshooting and 9-3. Troubleshooting check table.
4. How to replace batteries
Weak batteries may cause the remote controller malfunction.
In this case, replace the batteries to operate the remote controller normally.
2 Press the RESET button.
1 Remove the front lid and insert batteries.
Then reattach the front lid.
/
HE
/FA AT
N
HE
/FA AT
N
RESET button
NOTE1 : If the RESET button is not pressed, the remote controller may not operate correctly.
NOTE2 : INFORMATION FOR MULTI SYSTEM AIR CONDITIONER
(OUTDOOR UNIT : MXZ-A14WV MXZ-A18WV MXZ-A26WV MXZ-A32WV )
Multi system air conditioner (Outdoor unit MXZ-A14WV MXZ-A18WV MXZ-A26WV MXZ-A32WV) can connect two or
more indoor units with one outdoor unit.
According to the capacity, two or more units can operate simultaneously.
When you try to operate two or more indoor units with one outdoor unit simultaneously, one for the cooling and the
other for heating, the operation mode of the indoor unit that operates earlier is selected. The other indoor units that
will start the operation later cannot operate, indicating as shown in the figure below. In this case, please set all the
indoor units to the same operation mode.
Operation Indicator
lighted
flashing
When indoor units starts the operation while the defrosting of outdoor unit is being done, it takes a few minutes
(max. 10 minutes) to blow out the warm air.
In the heating operation, though indoor unit that does not operate may get warm or the sound of refrigerant flowing
may be heard, they are not malfunction. The reason is that the refrigerant continuously flows into it.
11
OB385B.qxp
07.5.21 4:41 PM
Page 12
MSC-GA20VB
MSC-GA25VB
MSC-GA35VB
Start
Indoor unit
operates.
Outdoor unit
doesn't operate
normally.
Indoor unit
operates.
Outdoor unit
doesn't
operate.
Outdoor unit
operates only
in Test Run
operation.w2
Outdoor unit
doesn't
operate
even in
Test Run
operation.w2
Check room
temperature
thermistor.
Refer to 9-6.
"Test point
diagram and
voltage".
MUH-GA20/GA25/GA35VB
MUX-2A28/2A59/3A60/
3A63/2A70/4A73VB
Refer to
"Check of
outdoor unit".
Outdoor unit
doesn't
stop even
if indoor unit
stops.
MU-GA20/GA25/GA35VB
Check of wiring
diagram of
outdoor unit".
MUH-GA20/GA25/GA35VB
Refer to
"Check of
outdoor unit".
Indoor unit
doesn't receive
the signal from
remote controller.
OPERATION
INDICATOR
lamp on the
indoor unit is
flashing on
and off.
Unit doesn't
operate
normal
operation in
COOL or
HEAT mode.
Indoor unit
operates,
when the
EMERGENCY
OPERATION
switch is
pressed.
Indoor unit
doesn't operate,
when the
EMERGENCY
OPERATION
switch is
pressed.
MUH-GA20/GA25/GA35VB
MXZ-A14/A18/A26/A32WV
Refer to
"Check of
R.V. coil" and
others.
Refer to 9-5.
B "Check of
remote
controller
and receiver
P.C. board".
1. Check indoor /
outdoor
connecting wire.
2. Refer to 9-5. C
"Check of indoor
electronic control
P.C. board".
MUH-GA20/GA25/GA35VB
MXZ-A14/A18/A26/A32WV
Flash on and off at
0.5-second intervals
Cause:
Indoor/Outdoor unit
Mis-wiring or
trouble of serial signal
2-time flash
Cause:
Indoor unit
Trouble of
room temperature/
indoor coil
thermistor
3-time flash
Cause:
Indoor unit
Trouble of
indoor fan
motor
4-time flash
Cause:
Indoor unit
Trouble of
indoor unit
control
system
Check room
temperature
thermistor
and indoor
coil thermistor.
Refer to 9-6.
"Test point
diagram and
voltage".
Refer to 9-5.
A "Check of
indoor fan
motor".
Replace the
indoor
electronic
control
P.C. board.
Indoor unit
operates.
But indoor
unit doesn't
blow out
cool air.
MUX-2A28/2A59/3A60/
3A63/2A70/4A73VB
Refer to
"Check of
indoor/outdoor
units' connection
and outdoor
unit".
MXZ type
7-time flash
6-time flash
5-time flash
Cause:
Cause:
Cause:
Outdoor unit
Outdoor unit
Outdoor unit Trouble of
Trouble of
Outdoor
outdoor
thermistor
power
control
in
outdoor
system
system
unit
abnormality
Refer to
"Check of
inverter/
compressor"
and "Check
of power
supply".
MUH-GA20/GA25/GA35VB
MXZ-A14/A18/A26/A32WV
Refer to
"Check of
outdoor
thermistor"
and others.
MUH-GA20/GA25/GA35VB
MXZ-A14/A18/A26/A32WV
Replace the
deicer
P.C. board
and others.
12
10-time flash
Cause:
Outdoor unit
MXZ type
Outdoor
refrigerant
system
abnormality
MXZ type
Refer to
outdoor
refrigerant
system
related items.
OB385B.qxp
07.5.21 4:41 PM
Page 13
Flashing of the OPERATION INDICATOR lamp (on the left-hand side) indicates possible abnormalities.
The OPERATION INDICATOR lamp (on the left-hand side) is lighting during normal operation.
Before taking measures, make sure that the symptom reappears, for accurate troubleshooting.
Self check table
No.
Abnormal
point
MUH or
MXZ type
Mis-wiring
or Serial
signal
Indoor coil
thermistor
Outdoor unit
does not run.
Detect Indoor coil/room temperature thermistor short or open circuit every 8 seconds during operation.
Check resistance of
thermistor.
Reconnect connector.
Check indoor electronic
control P.C.board.
Disconnect connector
CN211 and check
connector CN121 2-3 to
make sure rotational
frequency feedback signal of
1.5V or over exists.
Check indoor electronic
control P.C. board.
Check indoor fan motor.
Reconnect connector.
Outdoor unit
does not
operate.
Outdoor unit
does not run.
Outdoor unit
does not run.
Outdoor unit
does not run.
When it cannot properly read data in the nonvolatile memory of outdoor electronic control
P.C. board.
Outdoor unit
does not run.
When the compressor operation has been interrupted by LEV protection continuously 5
minutes, the compressor stops operation.
Outdoor unit
operates but
indoor unit
does not run.
2.5-second OFF
2.5-second OFF
2-time flash
3-time flash
Indoor
control
system
Outdoor unit
does not run.
0.5-second OFF
Indoor fan
3 motor
4-time flash
Checkpoint
Check switch SW2-2.(MU &
MUX type or MUH & MXZ
type)
Check wiring (visual check
and conductivity check).
Check indoor electronic
control P.C.board.
Check outdoor DEICER P.C.
board and others.
Check electrical parts.
0.5-second ON
2
Room
temperature
thermistor
Detection method
Symptom
2.5-second OFF
MXZ type
Outdoor
power
system
MUH or
MXZ type
Defrost
thermistor
MUH or
MXZ type
Outdoor
control
system
error
5-time flash
2.5-second OFF
6-time flash
2.5-second OFF
7-time flash
2.5-second OFF
10-time flash
MXZ type
Outdoor
refrigerant
system
error
2.5-second OFF
MXZ type
Operation
9 mode
setting
Operation Indicator
Lighted
Flashing
2.5-second OFF
13
OB385B.qxp
07.5.21 4:41 PM
Page 14
MSC-GA20VB
MSC-GA25VB
MSC-GA35VB
Figure
Part name
Room
temperature
thermistor (RT11)
Indoor coil
thermistor (RT12)
Normal
Abnormal
MSC-GA20/GA25/GA35VB
Open or
short-circuit
8k ~ 20k
Normal
Color of
lead wire
MSC-GA20/GA25VB
MSC-GA35VB
WHT-BLK
271 ~ 295
215 ~ 233
BLK-RED
180 ~ 196
305 ~ 331
Abnormal
WHT
RED
Open or
short-circuit
BLK
FUSE
YLW
Normal
Color of
lead wire
Sensor part
Indoor fan
motor (MF)
INNER FUSE
136i3C
CUT OFF
Motor part
MSC-GA20/GA25/GA35VB
BRN-YLW
4.5 ~ 5.5V
YLW-GRY
GRY
Abnormal
BRN
Remain 0V or 5V
Normal
Abnormal
MSC-GA20/GA25/GA35VB
Open or
short-circuit
240 ~ 260
RED
ROTOR
YLW
BRN
ORN
Yes
No
Resolder it.
Yes
Disconnect lead wires from connector CN211 on indoor electronic control P.C. board.
Measure resistance between lead wires No.1 and No.5, then No.3 and No.5.
No
(others)
Yes ( 0 or )
No
14
GRN
OB385B.qxp
07.5.21 4:41 PM
Page 15
Indoor unit operates by pressing the EMERGENCY OPERATION switch, but doesnt operate with the remote controller.
No
(not clear)
Yes
Remove batteries, then set them back and press the RESET
button. Check if the unit operates with the remote controller.
No
Yes
No
Is noise heard from radio?
OK
Yes
Are there any fluorescent lights of
inverter or rapid-start type within
the range of 1m?
Yes
No
Yes
Is the voltage approx. 4V DC?
No(5V or 0V DC)
Replace the power monitor, receiver P.C. board.
Yes
Is winding
resistance of
vane motor 0 "?
No
No
No
Replace the indoor
electronic control
P.C. board.
Yes
Replace the varistor.
Replace the fan motor.
15
No
OB385B.qxp
07.5.21 4:41 PM
Page 16
<MUH-GA20/GA25/GA35VB, MXZ-A14/A18/A26/A32WV>
w 1 Set the switch(SW2-2) on indoor electronic control P.C. board to
MU or MUX type, when the outdoor unit is MU or MUX type.
If the setting is MUH or MXZ type, the unit does not work.
Start
No
Yes
Does the unit operate?
No
Refer to the
"Instruction of
troubleshooting."
1. Turn OFF the power supply(indoor / outdoor unit) and disconnect indoor and outdoor connecting wire on indoor side.
2. Short-circuit between indoor terminal block N and 3.
3. Turn ON the power supply(indoor unit) and press once EMERGENCY OPERATION switch.
No
Yes
Turn OFF the power supply(indoor unit).
Connect indoor and outdoor connecting wire.
Turn ON the power supply(outdoor unit).
Is there 230V AC between outdoor terminal
block L-N (TB1)?
No
Yes
No
Yes
Turn ON the power supply(indoor unit).
16
No
OK
07.5.21 4:41 PM
Page 17
MSC-GA20VB
MSC-GA25VB
MSC-GA35VB
Indoor electronic control P.C. board
R132
Safety device of
fan by horizontal
vane CN1R1
Room temperature
thermistor RT11
Indoor coil
thermistor
RT12
Varistor
(NR11)
J12
12V
DC
J33
J33
SW2
(Refer to 8-4.)
1sets the Auto restart
function ON/OFF.
2switches over MU&MUX type/
MUH & MXZ type.
J23
Power monitor,
receiver P.C. board
Emergency
operation switch
5V DC
CN302
Resistance (k")
OB385B.qxp
Temperature (:)
17
OB385B.qxp
10
07.5.21 4:41 PM
Page 18
DISASSEMBLY INSTRUCTIONS
<"Terminal with locking mechanism" Detaching points>
The terminal which has the locking mechanism can be detached as shown below.
There are two types ( Refer to (1) and (2)) of the terminal with locking mechanism.
The terminal without locking mechanism can be detached by pulling it out.
Check the shape of the terminal before detaching.
(1) Slide the sleeve and check if there is a locking lever or not.
Sleeve
Locking lever
PHOTOS
Photo 1
18
Photo 2
Terminal block
fixing screw
Screw of the
earth wire
Indoor electronic
control P.C. board
OB385B.qxp
07.5.21 4:41 PM
Page 19
OPERATING PROCEDURE
PHOTOS
Photo 3
Vane motor
connector
Screw of the
electrical box
Photo 4
Drain hose
5. Removing the indoor fan motor and the line flow fan
(1) Remove the front panel. (Refer to 1.)
(2) Remove the electrical box. (Refer to 3.)
(3) Pull out the drain hose from the nozzle assembly, remove
the nozzle assembly. (Refer to 4.)
(4) Remove the screw of the lead cover and lead cover.
(5) Release the hooks to open the motor band slightly.
(6) Loosen the hexagon socket set screw from the line flow
fan.
(7) Remove the screws fixing the motor bed, remove the fan
motor with motor band and the motor bed.
(8) Remove the screws fixing the left side of the heat
exchanger.
(9) Lift the left side of the heat exchanger.
(10) Remove the line flow fan.
Photo 6
Screw of
the lead
cover
Photo 5
Screws of the
left side of the
heat exchanger
Photo 7
Hooks of the
motor band
19
Screws of
the motor
bed
OB385B.qxp
07.5.21 4:41 PM
11
Page 20
MSC-GA20VB
MSC-GA25VB
MSC-GA35VB
11-2. ACCESSORY AND
REMOTE CONTROLLER
10
8 (W)
Optional parts
(See 13. Optional parts.)
3
4
6 (W)
1
2
3
4
5
6
7
8
Part No.
E02
E02
E02
E02
E02
E02
E02
E02
E02
E02
E02
763
764
959
763
959
408
763
764
763
408
751
234
234
000
067
010
142
100
100
975
970
970
Part Name
BOX
BOX
PANEL ASSEMBLY
SCREW CAP
FRONT PANEL
CATCH
CATECHIN AIR FILTER
CATECHIN AIR FILTER
CORNER BOX (RIGHT)
INSTALLATION PLATE
INSTALLATION PLATE
Q'ty/unit
in Wiring MSC-GA20VBE1
Diagram
1
MSC-GA25VB-
MSC-GA35VB-
E1
E1
Remarks
1
2
1
2
2
1
2
1
2
2
1
1
1
1
1
1
2
1
2
2
1
Including No.3,4,5
2PCS/SET
2PCS/SET
1PCE/SET
1PCE/SET
1
1
20
1
1
1
1
KP1A, KM04F
OB385B.qxp
07.5.21 4:41 PM
Page 21
17
20 (W)
15
16
14
2
1
3
12
21
13
11
22
5
6
8 9 10
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
Part No.
E02
E02
E02
E02
E02
E02
E02
E02
E02
E02
E02
E02
E02
E02
E02
E02
E02
E02
E02
E02
E02
E02
E02
001
661
A59
781
781
127
829
763
815
962
963
964
749
151
749
691
749
751
749
749
408
751
749
504
702
235
040
041
382
385
034
468
452
452
452
303
308
333
375
300
300
307
302
509
509
385
Part Name
SLEEVE BEARING
DRAIN HOSE
NOZZLE ASSEMBLY
VANE UPPER
VANE LOWER
FUSE
VARISTOR
VANE CRANK SET
POWER MONITOR, RECEIVER P.C. BOARD
ELECTRONIC CONTROL P.C.BOARD
ELECTRONIC CONTROL P.C.BOARD
ELECTRONIC CONTROL P.C.BOARD
VANE MOTOR
ROOM TEMPERATURE THERMISTOR
MOTOR BAND
TERMINAL BLOCK
INDOOR FAN MOTOR(RC4V19- )
INDOOR FAN MOTOR(RC4V19- )
INDOOR COIL THERMISTOR
LINE FLOW FAN
BEARING MOUNT
BEARING MOUNT
VARISTOR
Symbol
in Wiring MSC-GA20VBE1
Diagram
1
1
1
1
1
1
1
1
1
1
F11
NR11
Q'ty/unit
MSC-GA25VB-
MSC-GA35VB-
E1
E1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
MV
RT11
TB
MF
MF
RT12
NR12
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Remarks
3.15A
AUTO RESTART
AUTO RESTART
AUTO RESTART
3P
Including fan motor rubber
mount 2PCS/SET
Including fan motor rubber
mount 2PCS/SET
1
1
A59
964
151
815
151
620
620
666
666
667
21
1
1
{9.52
{9.52
{6.35
OB385B.qxp
07.5.21 4:41 PM
12
Page 22
MSC-GA20VB
MSC-GA25VB
MSC-GA35VB
12-2. ACCESSORY AND
REMOTE CONTROLLER
10
8 (W)
Optional parts
(See 13. Optional parts.)
3
4
6 (W)
No.
1
2
3
4
5
6
7
8
RoHS
G
G
G
G
G
G
G
G
G
G
G
Symbol
Part No.
E12
E12
E12
E12
E12
E12
E12
E12
E12
E12
E12
763
764
959
763
959
408
763
764
763
408
751
234
234
000
067
010
142
100
100
975
970
970
Part Name
BOX
BOX
PANEL ASSEMBLY
SCREW CAP
FRONT PANEL
CATCH
CATECHIN AIR FILTER
CATECHIN AIR FILTER
CORNER BOX (RIGHT)
INSTALLATION PLATE
INSTALLATION PLATE
Q'ty/unit
in Wiring MSC-GA20VBE1
Diagram
1
MSC-GA25VB-
MSC-GA35VB-
E1
E1
Remarks
1
2
1
2
2
1
2
1
2
2
1
1
1
1
1
1
2
1
2
2
1
Including No.3,4,5
2PCS/SET
2PCS/SET
1PCE/SET
1PCE/SET
1
1
22
1
1
1
1
KP1A, KM04F
07.5.21 4:55 PM
Page 23
17
20 (W)
15
16
14
2
1
3
12
21
13
11
22
5
6
8 9 10
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
RoHS
OB385B.qxp
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
G
Part No.
E12
E12
E12
E12
E12
E12
E12
E12
E12
E12
E12
E12
E12
E12
E12
E12
E12
E12
E12
E12
E12
E12
E12
001
897
A59
781
781
A49
829
763
815
962
963
964
749
151
749
691
749
751
749
A59
408
751
749
504
702
235
040
041
382
385
034
468
452
452
452
303
308
333
375
300
300
307
302
509
509
385
Part Name
SLEEVE BEARING
DRAIN HOSE
NOZZLE ASSEMBLY
VANE UPPER
VANE LOWER
FUSE
VARISTOR
VANE CRANK SET
POWER MONITOR, RECEIVER P.C. BOARD
ELECTRONIC CONTROL P.C.BOARD
ELECTRONIC CONTROL P.C.BOARD
ELECTRONIC CONTROL P.C.BOARD
VANE MOTOR
ROOM TEMPERATURE THERMISTOR
MOTOR BAND
TERMINAL BLOCK
INDOOR FAN MOTOR(RC4V19- )
INDOOR FAN MOTOR(RC4V19- )
INDOOR COIL THERMISTOR
LINE FLOW FAN
BEARING MOUNT
BEARING MOUNT
VARISTOR
Q'ty/unit
Symbol
in Wiring MSC-GA20VB- MSC-GA25VB- MSC-GA35VBE1
E1
E1
Diagram
1
1
1
1
1
1
1
1
1
1
F11
NR11
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
MV
RT11
TB
MF
MF
RT12
NR12
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Remarks
3.15A
AUTO RESTART
AUTO RESTART
AUTO RESTART
3P
Including fan motor rubber
mount 2PCS/SET
Including fan motor rubber
mount 2PCS/SET
1
1
E12
E12
E12
E12
A59
964
151
151
620
620
666
667
23
1
1
1
{9.52
{6.35
OB385B.qxp
13
07.5.21 4:41 PM
Page 24
OPTIONAL PARTS
AIR CLEANING FILTER
AIR CLEANING FILTER removes fine dust of 0.01 micron from air by means of static electricity.
Normal life of AIR CLEANING FILTER is 4 months. However, when it becomes dirty, replace it as soon as possible.
Clogged AIR CLEANING FILTER may reduce the air conditioner capacity or cause frost on the air outlet.
DO NOT reuse AIR CLEANING FILTER even if it is washed.
DO NOT remove or attach AIR CLEANING FILTER during unit operation.
Model
MSC-GA20VB
MSC-GA25VB
MSC-GA35VB
Part No.
MAC-1300FT