Documente Academic
Documente Profesional
Documente Cultură
1, JANUARY 2012
325
I. INTRODUCTION
Manuscript received May 20, 2011; revised August 01, 2011; accepted
September 08, 2011. Date of publication October 18, 2011; date of current
version December 23, 2011. This work was supported by the National Science
Foundation under Grant ECCS-0801367. Paper no. TPWRD-00425-2011.
N. Kang is with ABB Corporate Research Center, Raleigh, NC 27606 USA
(e-mail: ning.kang@us.abb.com).
Y. Liao is with the Department of Electrical and Computer Engineering, University of Kentucky, Lexington, KY 40506 USA (e-mail: yliao@engr.uky.edu).
Digital Object Identifier 10.1109/TPWRD.2011.2168547
voltage and current data, with the estimation accuracy being influenced by the fault resistance. Eriksson et al. employ phase
voltages and currents from the near end of the faulted section
as input signals and fully compensate the error introduced by
the fault resistance [9]. Based on the assumption that the line
is homogeneous, [10] makes use of modal transformation and
the local terminal voltage and current to locate the fault. Six
voltage equations are constructed around the parallel loops for
positive-, negative- and zero-sequence networks in [11], from
which the fault location is solved. By building voltage equations along parallel loops, the authors in [12] address fault location for the nonearth fault. Reference [13] constructs the voltage
equations but does not include the current phasors of the adjacent sound line local end information based on the consideration that in some practical systems, these current phasors are
not available. Izykowski et al. [14] formulate the generalized
model for fault loops by using local-end voltages and complete
currents from healthy and faulted double-circuit lines. Using the
technique similar to [11][14], the authors of [15] have developed a fault-location algorithm applicable to untransposed lines,
which utilizes the lumped line model ignoring the shunt capacitance. The common characteristic of [11][15] is that they are
all one-end algorithms and independent of the fault resistance.
A two-terminal method by using unsynchronized voltage and
current phasors based on the distributed parameter model is
discussed by Johns et al. [16]. The authors in [17] have proposed an iterative approach to improve the accuracy of the fault
distance estimate and it does not require synchronization of
measurements. Reference [18] relates the synchronized voltage
and current phasors of the sending end and receiving end with
parameters, from which the fault location is derived.
In [19], based on the differential component net decomposed
from the original net, two voltage distributions along the line
are calculated from the unsynchronized two-terminal currents.
The fault location is determined based on the fact that these two
voltage distributions have the least difference at the fault point.
Chen et al. [20] have proposed a new protection scheme by using
synchronized phasors at both terminals of the line for transposed
and untransposed parallel lines. By decoupling the parallel lines
using eigenvalue theory, both the fault detection and location indices have been obtained. Based on a three-terminal fault location algorithm and an equivalent conversion from an n-terminal
system to a three-terminal system, the method proposed in [21]
utilizes unsynchronized current phasors of all terminals to locate
the fault, neglecting shunt capacitances. Funabashi et al. [22]
present two multiterminal lumped parameter model-based algorithms: impedance calculation and current diversion ratio.
326
and
327
where
(9)
(10)
(11)
(12)
and
zero-sequence per-unit length self-series impedance
of the line between buses and ;
zero-sequence per-unit length self-shunt admittance
(S/mile) of the line between buses and ;
zero-sequence per unit length mutual-series
between the two lines of buses
impedance
and ;
zero-sequence per-unit length mutual-shunt
admittance (S/mile) between the two lines of buses
and .
Fig. 2. Zero-sequence network with two additional fictitious buses.
Note that the studied parallel lines in our paper have identical
,
,
and
parameters, i.e.,
. The parameters in Fig. 2 in terms of
are as
follows [26]:
(1)
..
.
..
..
.
..
.
..
..
.
..
.
..
.
(2)
..
.
..
..
.
..
.
..
..
.
..
.
..
.
(3)
(4)
(13)
,
, and
are derived with respect to network parameters as in (14) and (15) with the detail referenced
to Appendix A.
(5)
(14)
(6)
(7)
(8)
(15)
where , , , and are formulated with
,
,
,
,
,
,
and
;
and
in (15) can be obtained
and
in (14).
by letting
Substituting (1)(8) into (14) and (15) leads to the formulaand
with respect to and
tions of
known network parameters.
328
where
prefault positive-sequence voltage at bus
;
positive-, negative-, and zero-sequence
voltage at bus during fault, respectively;
positive-, negative-, and zero-sequence
fault current at the fault point, respectively.
(18)
(19)
and
positive-sequence per-unit length self-series
impedance
of the line between buses
;
positive-sequence per-unit length self-shunt
admittance (S/mile) of the line between buses
and
and .
Note that all of the sequence voltages and currents are for
phase A.
Equations (20)(22) demonstrate that the sequence voltage
change during the fault at any bus can be expressed with respect to the corresponding transfer impedance and sequence
fault current.
A. Two-Bus Fault-Location Algorithm
1) Fault Location With Synchronized Measurements From
Two Buses: Suppose the voltage measurements at buses and
are available. For bus , similar to (20),
the following formula exists:
(23)
Eliminating
(24)
Defining
(16) into (24) gives
and substituting
(20)
(21)
(22)
(25)
(16)
(17)
329
(30)
(26)
The fault-location formula in (26) is applicable only if a path
exists, which passes through the faulted line and does not pass
any bus more than once, between buses and [24]. Otherwise,
the ratio of voltage changes at these two buses will be constant
and independent of the fault-location variable. Since most of the
power network is interconnected, most combinations are able to
produce the fault-location estimate.
Negative- or zero-sequence voltage measurements, where applicable, can also be employed for fault location. However, positive-sequence voltages are preferred due to the fact that no
fault-type classification is needed.
2) Fault Location With Unsynchronized Measurements From
Two Buses: Taking the absolute value of (25) leads to
(27)
The NewtonRaphson approach can be utilized here to iteratively solve for the unknown fault location . An initial value of
0.5 p.u. is adopted for the iteration process and the convergence
criterion is that the update for the fault location becomes smaller
than 1.0e-7. As will be illustrated in the evaluation studies, of
all the cases we have tested, all of them have converged within
10 iterations.
B. One-Bus Fault-Location Algorithms
For the scenario where measurements are only available from
a single bus, we have developed one-bus fault-location algorithms for different types of fault. Supposedly, the voltage measurements are from a single bus
.
1) LG Fault: For a phase-A-to-ground fault, the boundary
condition
exists. Eliminating
and
from (21) and (22) yields
where
denotes the prefault positive-sequence voltage at
the fault point and can be calculated as
(34)
and
are the prefault positive-sequence voltwhere
ages at the two terminals of the faulted line and are assumed to
be known.
Using (16), (17), and (34), together with (33), will produce a
as unknowns, the solution of
nonlinear equation with and
which is similar to (30).
4) LLL Fault: For the three-phase balanced fault, we have
(35)
Replacing
(28)
(36)
Replacing the transfer impedance terms in (28) by (14) and
(16), a nonlinear equation involving one unknown variable
can be formulated, which can be separated into real and imaginary part to formulate two real equations. To solve it, least
squares method can be utilized. An initial value of 0.5 p.u. for
can be adopted.
2) LLG Fault: For the phase-B-to-C-to-ground fault, the following condition is satisfied:
(29)
330
and
For any two sets of measurements from buses
, the following equation is yielded based on
(25):
(38)
Define the unknown variables as
(39)
where
, variables to represent the
positive-sequence superimposed voltage caused
);
by the fault (i.e.,
fault-location variable.
The combinations of any two sets of measurements out of
sets include
, the total
. Here, represents the combinumber of which is
nation calculation. For any possible combination, say
, by
employing the defined variables, (38) can be written as
(37)
where
is the vector transpose operator, and
number of measurements set.
is the total
(40)
331
(44)
where Re(.) and Im(.) yield the real and imaginary part of the
input argument, respectively.
The measurement vector and function vector are related by
(45)
is a vector representing measurement errors and dewhere
pendent on the meter characteristic.
is obtained by minimizing the
The optimal estimate of
cost function defined as
(46)
where
(47)
And
signifies the variance of measurement ,
indicates
the expected value, and
means a diagonal matrix consisting of the values contained in the square bracket.
is the total number of measurements. A smaller value of
indicates a more accurate meter.
Equation (46) can be solved iteratively [27]. During the th
iteration, the unknown vector is updated as
(48)
(49)
(50)
where
iteration number starting from 0;
variable vector before and after the th iteration;
variable update during the th iteration.
To initiate the iteration process, we can choose 0.1 p.u. and
for the magnitude and angle of positive-sequence superimposed voltage, respectively, and 0.5 p.u. for the fault-location
estimate. When the variable update is smaller than the specified
is
tolerance, the iteration process can be terminated. After
obtained, we can use (44) to compute the estimated values of
measurements.
(51)
332
TABLE I
TWO-BUS SYNCHRONIZED FAULT-LOCATION RESULTS
TABLE II
TWO-BUS UNSYNCHRONIZED FAULT-LOCATION RESULTS
TABLE III
ONE-BUS FAULT-LOCATION RESULTS FOR AG AND BCG FAULTS
TABLE IV
ONE-BUS FAULT-LOCATION RESULTS FOR BC AND ABC FAULTS
333
TABLE V
TWO-BUS SYNCHRONIZED FAULT-LOCATION RESULTS
FOR UNTRANSPOSED LINES
TABLE VI
ONE-BUS AG FAULT-LOCATION RESULTS FOR UNTRANSPOSED LINES
TABLE VII
ONE-BUS AG FAULT-LOCATION RESULTS WITH 3%
ERROR IN ZERO-SEQUENCE IMPEDANCES
in Table VII. The fault-location accuracy has decreased compared to Table III. However, the errors are still quite small. Note
that only the one-bus algorithm involving ground is affected by
zero-sequence parameter errors, since two-bus methods will use
positive-sequence parameters.
B. Case With Bad Measurement
This case study illustrates how to detect and identify bad measurements with the proposed optimal estimator. A value of 1e-6
is chosen as variance for the first
measurements and 1e-4
for the variance for the voltage measurements. In our studied
case, the voltage measurements at buses 4, 6, 8, and 19 are utilized to obtain the fault location.
Suppose there is a BCG fault with the actual fault location
being 0.3 p.u. and the fault resistance as 50 . Suppose that
there is an error of 50% in the superimposed positive-sequence
voltage at bus 4.
The optimal estimation result is shown in Table VIII. There
are 20 equations and 9 state variables; therefore, we have
11 and
24.73. The estimated value of cost function
is computed as 34.58, which is greater than
. Thus,
the presence of bad measurements is suspected. Following the
method outlined in Section IV-B, the normalized error vector
334
TABLE VIII
OPTIMAL ESTIMATES WITH BAD MEASUREMENT
TABLE IX
OPTIMAL ESTIMATES WITH BAD MEASUREMENT REMOVED
is obtained and the largest value corresponds to the magnitude of superimposed positive-sequence voltage at bus 4, which
is hence identified as a bad measurement.
After the bad measurement is removed, a new set of optimal
estimates is calculated as shown in Table IX. In this scenario,
the expected value of cost function is equal to 5 and
15.09. The estimated value of cost function
is 6e-4. Since
is much less than
, all of the data are considered fairly
accurate and the estimates are regarded as satisfactory. A comparison of Table VIII indicates that the fault-location accuracy
has considerably improved.
VI. CONCLUSION
In this paper, novel one-bus and two-bus fault-location algorithms applicable to double-circuit transmission lines are developed. The distinctive feature of the proposed method is that only
voltage measurements from one or two buses are needed which
may be a distance away from the faulted section. The distributed
parameter line model is utilized which fully takes the shunt capacitance of long lines into account.
Simulation studies have shown that the proposed algorithms
can yield quite accurate estimates under various fault conditions. For the two-bus fault-location method, a unique fault-location estimate is produced by using synchronized and unsynchronized voltage measurements, and the fault-type classification is not required. For one-bus fault-location algorithms, the
fault type is a prerequisite. For LG and LLG faults, a unique
fault-location estimate can be obtained. For LL and LLL faults,
prefault measurements at the two terminals of the faulted line
are demanded and, in certain cases, two possible fault-location
estimates may be produced, both of which will be treated as a
likely fault location.
When synchronized voltage measurements from multiple
(more than three) buses are available, which may not necessarily be captured from the buses of the faulted line, an
optimal fault-location estimator is proposed that is capable of
identifying bad measurement data and, thus, enhancing the
fault-location estimate. This approach is preferred over the
and
(A5)
(A6)
(A7)
Based
on
(A9)
(A10)
335
TABLE X
TRANSMISSION-LINE DATA
TABLE XI
GENERATOR DATA
TABLE XII
LOAD DATA
(A17)
(A18)
With six unknown variables
(A13)(A18) reaches the expression of
, solving
as follows:
(A11)
(A19)
Substituting (A1) into (A8) will result in (14).
To derive
, let us inject one current source of 1 A into
bus . Based on the bus impedance matrix in (13), the voltages
at buses , , and in Fig. 2 are
where
(A12)
(A20)
From Fig. 2, the following equations hold:
(A13)
(A14)
(A15)
(A16)
336
[16] A. T. Johns and S. Jamali, Accurate fault location technique for power
transmission lines, Proc. Inst. Elect. Eng. Gen., Transm. Distrib., vol.
137, no. 6, pp. 395402, Nov. 1990.
[17] A. L. Dalcastagne, S. N. Filho, H. H. Zurn, and R. Seara, An iterative
two-terminal fault-location method based on unsynchronized phasors,
IEEE Trans. Power Del., vol. 23, no. 4, pp. 23182329, Oct. 2008.
[18] D. J. Lawrence, L. Z. Cabeza, and L. T. Hochberg, Development of
an advanced transmission line fault location system part II-Algorithm
development and simulation, IEEE Trans. Power Del., vol. 7, no. 4,
pp. 19721983, Oct. 1992.
[19] G. Song, J. Suonan, Q. Xu, P. Chen, and Y. Ge, Parallel transmission lines fault location algorithm based on differential component net,
IEEE Trans. Power Del., vol. 20, no. 4, pp. 23962406, Oct. 2005.
[20] C. S. Chen, C. W. Liu, and J. A. Jiang, A new adaptive PMU based
protection scheme for transposed/untransposed parallel transmission
lines, IEEE Trans. Power Del., vol. 17, no. 2, pp. 395404, Apr. 2002.
[21] T. Nagasawa, M. Abe, N. Otsuzuki, T. Emura, Y. Jikihara, and M.
Takeuchi, Development of a new fault location algorithm for multiterminal two parallel transmission lines, IEEE Trans. Power Del., vol.
7, no. 3, pp. 15161532, Jul. 1992.
[22] T. Funabashi, H. Otoguro, Y. Mizuma, L. Dube, and A. Ametani, Digital fault location for parallel double-circuit multi-terminal transmission lines, IEEE Trans. Power Del., vol. 15, no. 2, pp. 531537, Apr.
2000.
[23] J. Gracia, A. J. Mazon, and I. Zamora, Best ANN structures for fault
location in single- and double-circuit transmission lines, IEEE Trans.
Power Del., vol. 20, no. 4, pp. 23892395, Oct. 2005.
[24] N. Kang and Y. Liao, Fault location for double-circuit lines utilizing
sparse voltage measurements, in Proc. Power Energy Soc. Gen.
Meeting, Calgary, AB, Canada, Jul. 2630, 2009, pp. 17.
[25] J. Grainger and W. Stevenson, Power System Analysis. New York:
McGraw-Hill, 1994.
[26] Y. Liao, Equivalent pi circuit for zero-sequence networks of parallel
transmission lines, Elect. Power Compon. Syst., vol. 37, no. 7, pp.
787797, Jul. 2009.
[27] A. Abur and A. G. Exposito, Power System State Estimation-Theory
and Implementation. New York: Marcel Dekker, 2004.
[28] Alternative Transient Program, User Manual and Rule Book, Leuven
EMTP Centre, Leuven, Belgium, 1987.