Documente Academic
Documente Profesional
Documente Cultură
MANUAL
ELMO-PackTM
OIL-SEALED LIQUID RING
VACUUM SYSTEMS
Prepared By:
NOTICE
UNPACK WITH CARE
See Section 2.1, page 25 for specific instructions.
Please do not discard any packing materials
until the contents of this shipment have been carefully
compared with the shipping documents.
If any materials are unsatisfactory,
notify Siemens and hold materials.
In case of damage, notify delivering carrier at once for an
inspection. If terms of sale are F.O.B. destination, one copy of
the carrier inspection report and a copy of the delivery receipt
indicating exception at time of delivery must be returned to
Siemens VPC.
Table of Contents
SECTION 1.0 DESCRIPTION .............................................................................................................. 6
1.1 GENERAL ........................................................................................................................................ 6
1.2 OPERATING PRINCIPLES ................................................................................................................... 6
1.2.1 Siemens liquid ring vacuum pump............................................................................................. 9
1.2.2 Electric Motor.......................................................................................................................... 9
1.2.3 Air / Oil Separator ................................................................................................................... 9
1.2.4 Coalescing Filter.................................................................................................................... 10
1.2.5 Heat Exchanger ..................................................................................................................... 10
1.2.6 Inlet Check Valve ................................................................................................................... 10
1.2.7 Inlet Vacuum Gauge............................................................................................................... 10
1.2.8 High Temperature Switch ....................................................................................................... 10
1.2.9 Thermal Bypass Valve ............................................................................................................ 11
1.2.10 Compound Gauge................................................................................................................. 11
1.2.11 Pressure Gauge.................................................................................................................... 11
1.2.12 Oil Level Gauge ................................................................................................................... 11
1.2.13 Drain Valve.......................................................................................................................... 11
1.2.14 Gauge Cocks........................................................................................................................ 11
1.2.15 Structural steel Base............................................................................................................. 12
1.2.16 Temperature Gauge.............................................................................................................. 12
1.2.17 Ball Valves........................................................................................................................... 12
1.2.18 Y-Strainer ............................................................................................................................ 12
1.2.19 Sight Flow Indicator............................................................................................................. 12
1.2.20 Low Level Switch (optional) ................................................................................................. 13
1.2.21 High Level Switch (optional) ................................................................................................ 13
1.2.22 Inlet Filter (optional)............................................................................................................ 13
1.2.23 Non-Expandible Control Panel (optional)............................................................................. 13
1.2.23.1 Control Panel (optional)................................................................................................. 13
1.2.23.2 Power Supply ................................................................................................................ 14
1.2.23.3 Combination/Non-Combination Starter Panel................................................................. 14
1.2.23.4 Non-expandable Control Panel Description .................................................................... 15
1.2.23.5 Non-expandable control panel sequence of operation...................................................... 16
1.3 EXPANDABLE SYSTEMS ................................................................................................................. 18
1.3.1 Description ............................................................................................................................ 18
1.3.2 NFPA vs. Standard Systems.................................................................................................... 19
1.3.2.1 Expandable Control Panel Description ............................................................................. 22
1.3.2.2 Operation (25 HP or less)................................................................................................. 23
1.3.2.3 Operation (30 HP or larger) ............................................................................................. 24
1.4 APPLICATION LIMITS ..................................................................................................................... 24
SECTION 2.0 INSTALLATION ......................................................................................................... 26
2.1 UNPACKING .................................................................................................................................. 26
2.2 ELECTRICAL POWER SUPPLY.......................................................................................................... 26
2.3 LOCATION ..................................................................................................................................... 27
2.4 WIRING INSTALLATION .................................................................................................................. 27
2.5 OIL FILL AND PRIME ...................................................................................................................... 30
SECTION 3.0 OPERATION................................................................................................................ 31
3.1 PRELIMINARY INSPECTION ............................................................................................................. 31
3.2 STARTUP ....................................................................................................................................... 32
3.3 SHUT DOWN .................................................................................................................................. 32
3.4 VACUUM SWITCH ADJUSTMENT (EXPANDIBLE SYSTEMS ONLY) ........................................................ 33
3.4.1 Operation............................................................................................................................... 33
3.4.2 Adjustment ............................................................................................................................. 34
3.4.3 Operating range adjustment ................................................................................................... 34
3.4.4 Differential adjustment........................................................................................................... 34
The cooler is designed to remove the thermal load, about equal to the motor horsepower,
from the oil before it is sucked back into the pump. Since the cooler uses ambient air to
operate, the oil discharge temperature will be somewhat dependent on the local air
density and temperature.
CAUTION
Operating the system at altitudes above 3000 feet or more may
cause discharge temperatures to be above the
recommended maximum unless specially designed coolers are utilized.
CAUTION
Do not operate the system in a closed room.
Adequate ventilation is required to ensure proper operation.
CAUTION
Operation of the system in ambient
temperatures greater than 104F is not recommended.
Each system contains the following components described below. Refer to Figure 1-1 for relative
placement in the systems.
1.2.1 Siemens liquid ring vacuum pump.
The Siemens liquid ring vacuum pump is the heart of the system. A liquid ring vacuum
pump is a non-pulsating rotary vacuum pump that compresses gasses using liquid as a
compressing medium. The Siemens liquid ring vacuum pump has a simple design for
reliability. A single moving part, the impeller, rotates forcing the operating liquid to form
a liquid ring within the casing. This liquid acts as a sealant, as a compressing media and
as a coolant. Wear is minimized because there is no mechanical contact of moving parts.
On the suction cycle, liquid recedes from the impellers hub, drawing gas to be
compressed through the axial suction port. Because the impeller is off-center to the ring
of rotating liquid, the liquid reciprocates into spaces between the blades much like the
operation of a cylinder, compressing the gas against the hub. After almost one revolution,
the compressed gas is discharged through axial discharge ports. The Siemens variable
discharge port provides maximum efficiency at different vacuum levels.
CAUTION
On initial start up of the system, be sure to place the
recommended (See Table 2-1) priming oil in the pump. This is
in addition to the oil placed in the separator. Damage to the
system is possible if this oil is not added on initial start-up.
1.2.2 Electric Motor
The electric motor provides an efficient, reliable prime mover for the pump. A variety of
motor designs can be provided including explosion proof motors and motors for a variety
of voltages. The correct motor voltage must be specified and is the responsibility of the
user.
1.2.3 Air / Oil Separator
The liquid ring pump discharges both oil and air into a special discharge separator. The
separator is designed to separate the oil from the air. The oil is separated and settles to the
bottom of the separator tank where it is returned to the pump through the cooling system.
The air is discharged through a fitting located at the top of the separator. The separator
also has a port for convenient filling of the system.
CAUTION
Do not fill the system through the discharge gas fitting.
Use the oil fill port on the side of the separator.
CAUTION
Do not operate the vacuum system unless the
discharge high temperature switch is connected.
Operation at excessive temperatures
could damage the pump or
cause early or excessive system wear.
10
CAUTION
Do not operate the pump with a high discharge back pressure
since this will cause the motor to draw excessive power.
1.2.12 Oil Level Gauge
A separator level gauge provides easy monitoring of the system oil level. The oil level
should be at the pump shaft centerline for Siemens model 2BE vacuum pumps (30 to 75
Horsepower) and approximately even with the centerline of the operating liquid inlet
connection on the pump for Siemens model 2AV or 2BV (1.5 to 25 Horsepower) vacuum
pumps.
1.2.13 Drain Valve
The separator is equipped with a separator drain valve. This will allow the user to drain
away water that may have collected in the system from the process and to drain the oil for
maintenance and/or changing. Water will eventually settle to the bottom of the separator
tank. The drain line is connected to the bottom of the separator tank for convenient
draining.
1.2.14 Gauge Cocks
Gauge cocks are provided with pressure gauges (items 7 & 10) to provide isolation of the
gauges for easy replacement or removal without affecting system operation.
11
CAUTION
The system should be installed on a flat, level surface.
If anchored to the surface with bolts, take care in avoiding excessive
piping stress on the pump, which could cause leaks or
vibration during operation.
1.2.16 Temperature Gauge
A discharge temperature gauge is provided to indicate the operating temperature of the
system. The acceptable range is 150F to 190F.
1.2.17 Ball Valves
The Y-strainer can be cleaned without loss of oil by closing two isolation valves located
at each end of the strainer. These valves should be fully opened during normal
operation.
WARNING
Do not operate the system without oil or with any of the oil system
valves in the closed position as severe damage can result.
1.2.18 Y-Strainer
The oil is collected in the bottom of the separator and returned to the pump after passing
through a Y-Strainer and the heat exchanger. The Y-Strainer is in the system to remove
any foreign debris that may have been introduced from the users process.
1.2.19 Sight Flow Indicator
A scavenge line is provided from the bottom of the coalescing filter to the suction port of
the liquid ring vacuum pump. This will remove any oil that has collected in the bottom of
the filter. The line runs externally from the upper portion of the separator tank (which
contains the coalescing filter) to the inlet manifold on the pump. A sight flow indicator is
12
provided in this line. It is normal for a SLIGHT amount of oil to flow in this line. A
constant flow of oil indicates that the coalescing filter requires replacement. [Note that a
small needle valve is included in high vacuum systems to allow operation above 28
inches Hg vacuum.]
1.2.20 Low Level Switch (optional)
A separator low-level switch may be provided to indicate a low oil level condition. This
switch has common and normally open contacts, which should be tied into the motor
control panel using a time delay to eliminate false trips due to tank turbulance. A lowlevel condition should shut down the pump drive motor. Low oil level can result in loss
of the liquid ring and possible damage to the pump.
1.2.21 High Level Switch (optional)
A separator high-level switch may be provided to indicate a high oil level condition. This
switch has common and normally open contacts, which should be tied into the motor
control panel using a time delay to eliminate false trips due to tank turbulance. A highlevel condition should shut down the pump drive motor. High oil level can result in
motor overload and possible damage to the pump.
1.2.22 Inlet Filter (optional)
An inlet filter with 10-micron polyester element may be provided for applications where
particulate matter may be present in the users process.
1.2.23 Non-Expandible Control Panel (optional)
1.2.23.1 Control Panel (optional)
The optional base-frame mounted integral control panel is provided with motor starter
including overloads, on-off switch, motor running light, high temperature light and
high/low-level indicator lights. A reset switch is provided to clear any shut down
condition. The panel will automatically shut down the pump drive motor in the event of
over-temperature, low or high oil level (if supplied with the system) or motor overload
conditions. The indicator lights will show the reason for shut down. The panel has an
hour meter that will indicate total running hours for the pump drive motor.
The panel provides motor protection that will prevent motor burn out in overload
conditions. The operator should limit the number of across the line starts. This is to
prevent potential motor damage from excessive starting. All electric motors require high
starting current and the number of starts per hour should be limited to the motor
manufacturers recommendations (usually one hot or 2 cold starts per hour).
The panel can be provided dedicated for one system (simplex) or can be ordered for an
expandable system.
13
CAUTION
The non-expandable system panel does not
control the system vacuum level.
If system vacuum level control is required,
an expandable panel with PLC control is required.
The non-expandable simplex control panel will be provided attached to the standard
structural base fame that accommodates the system.
1.2.23.2 Power Supply
The panel has been designed for the voltage indicated on the supplied panel-wiring
diagram.
CAUTION
Operation of this system at voltages
other than those specified in the
supplied system documentation
can cause extreme damage.
The customer must provide a fusible disconnect or circuit breaker unless a combination
starter is specified for the control panel.
14
Color
Pump Running
High Discharge Temperature Alarm
* Low Level Alarm
* High Level Alarm
Green
Amber
Amber
Amber
15
CAUTION
When the panel is connected to the users power supply, assure that the
proper voltage is applied. Refer to the wiring diagram furnished with
the system.
CAUTION
The user must provide required primary circuit protection disconnect
in compliance with NEC and local codes. This may be a fusible
disonnect or circuit breaker.
CAUTION
Only qualified personnel
Should attempt to work on the control panel.
Dangerous voltages are present.
16
17
CAUTION
Modification of the Siemens panel
should only be attempted by a qualified electrician
and done per manufacturers instructions.
1.3.1 Description
The expandable system consists of one or more simplex systems as previously described
plus an additional base frame containing a vacuum receiver tank and an expandable
control panel. Each vacuum pump system will be referred to as an Expansion Module.
The system can handle up to three Expansion Modules. If it is initially ordered with one
or two pumps, additional ELMO-Pack TM Expansion Modules can be added later and
field installed. The additional electrical components can be field installed in the
Expandable Control Panel by a qualified electrician and are included with each expansion
module. The panel is pre-wired and designed to accept the expansion module
components. A qualified plumber can pipe the additional expansion modules into the
system.
The panel is normally furnished in a NEMA 12 or NEMA 7 enclosure with noncombination starters. The customer must provide a fusible disconnect or circuit breaker.
A normal NFPA 99 system includes disconnects.
The Vacuum receiver tank is included to provide vacuum storage to accommodate
changes in demand from the customers process. The vacuum receiver is a Carbon steel
ASME code vessel that functions as an accumulator. If there are sudden changes in
demand from the process, the vacuum receiver volume will respond by providing a stored
vacuum source that will help maintain the system pressure. This will prevent excessive
starting and stopping of the pumps. The receiver tank is provided with a sight level
gauge and drain valve.
18
In addition to these basic system components, the NFPA 99 compliant system includes:
-
19
20
21
Color
Pump #1 Running
* Pump #2 Running
* Pump #3 Running
Green
Green
Green
Red
Red
Red
Red
Red
Red
Red
Red
Red
22
CAUTION
When the panel is connected to the users power supply, assure that the
proper voltage is applied. Refer to wiring diagram furnished with the
system.
CAUTION
For non-NFPA 99 systems, the user must provide a primary circuit
protection disconnect in compliance with NEC. This may be a fusible
disconnect or circuit breaker. These are provided per NFPA 99
requirements on NFPA systems.
The Expandable Control Panel provides manual or automatic operation of one, two or
three pumps. The requirement for running pumps is determined by vacuum switches. If
the system has three pumps and all three units are in the automatic mode position, the
system will operate as follows: On start-up, all three pumps will be started immediately
and will continue to run until vacuum increases beyond the set-point of VAC-1 vacuum
switch. This switch is set to the highest vacuum of all three switches. We will refer to this
switch as the lead vacuum switch. When vacuum increases beyond the lead vacuum
switch set point, all pumps will shut down after a user adjustable time delay has timed
out. The time delay prevents overheating of the motors caused by excessive repeated
starts.
System vaccum will decrease with process demand. When system vacuum decreases to
the set point plus the adjustable dead band of the lead vacuum switch (VAC-1), the lead
pump will start. This pump will continue to run until process vacuum has reached the set
point of the lead vacuum switch and the adjustable run timer TR-1 has timed out.
If system vacuum decreases with only one pump running and reaches the set point of
VAC-2 (lag vacuum switch), the lag pump will start. Both pumps will continue to run
until the system vacuum has reached the set point of the lead pressure switch and the
adjustable run timer TR-1 has timed out.
23
If system vacuum continues to decrease with two pumps running and reaches the set
point of VAC-3 (lag-lag vacuum switch), the lag-lag pump will start. All three pumps
will continue to run until the system vacuum has reached the set point of the lead pressure
switch and the adjustable run timer TR-1 has timed out.
Each time the lead vacuum switch shuts down the pumps (on increasing vacuum), the
roles of lead, lag and lag-lag pump functions will be alternated between pump #1,
pump #2 and pump #3 to provide even cycle time for all three pumps. If one pump is
shut down because of an alarm condition, the other pumps will continue to run on
demand as described above.
CAUTION
Only qualified personnel
Should attempt to work on the control panel.
Dangerous voltages are present.
1.3.2.3 Operation (30 HP or larger)
System panel configuration logic is custom designed for larger horsepower units to meet
customer requirements. Please refer to the custom documentation included with your
large horsepower system for specific details of operation.
1.4 Application Limits
The ELMO-Pack TM Oil Seal System is a liquid ring vacuum pump package with a selfcontained cooling system. The system is designed to operate with a special sealing oil
that is provided with the system. This oil will provide increased vacuum levels (deeper
vacuum) at increased operating temperatures. The pump can operate at a higher
temperature without cavitation, and there will not be loss of operating liquid due to
evaporation because oil has a much lower vapor pressure (higher boiling point) than
water. Normal operating temperature for the system is 150 -190F.
These systems are ideal where it is not convenient for a user to provide a water supply to
a typical liquid ring pump application.
24
Liquid ring pumps are ideal for applications requiring a rugged vacuum pump that can
tolerate entrained liquid and solids. However, there are some situations that require
special designs. If the following limits are observed, the standard system will give years
of trouble free operation.
-
Ambient Temperature must not exceed 104F while using the standard motors.
Altitude at installation location must be 3000 ft. above mean sea level.
Water vapor or the condensable load must not be excessive. Contact the factory
for assistance in determining if excessive vapor is present in your suction gas.
The use of an inlet filter is advisable if particulate matter is present in the suction
stream. This will prolong the life of the oil.
If reactive chemicals are present, special oils may be required. The standard oil is
an ISO 22 non-detergent semi-synthetic (Poly-alpha olefin) oil selected for
vacuum service. Contact the factory for assistance in selecting the proper oil for
your application.
Liquid ring pumps may not operate properly below 29 inches Hg vacuum. If
excessive vibration or noise at low pressures is experienced, contact the factory
for assistance.
WARNING
Operation of the standard system outside the application limits
described above could cause a hazardous condition,
damage to the equipment and will void the factory warranty.
25
WARNING
If the voltage reported on the wiring diagram supplied with the system
does not match your supply voltage,
contact the factory immediately.
Do not attempt to install the system if the supply voltage and the system
voltage requirement do not match, as a hazardous condition and severe
damage could result.
26
2.3 Location
The ELMO-Pack TM must be installed on a horizontal, level surface. Floor anchors are not
required because of low vibration levels. If anchors are used, care must be taken to
eliminate pipe stress load on the inlet piping. A flex connector should be installed.
At least 2 feet of air space should be allowed between any wall or obstruction and the
heat exchanger air intake. This will assure adequate flow of cooling air and provide
maintenance access.
For expandable systems, place the vacuum receiver skid on the far left of the installation
pad. Then place each expansion module next to the receiver skid and connect the piping
as indicated in Figure 2-1.
For expandable systems, run the provided wiring from the panel to the vacuum expansion
modules.
27
28
29
Fill the oil reservoir with the recommended amount of Siemens vacuum oil. (See Table
2-1.) All valves in the service liquid line must be open while filling the system with the
seal oil. See Figure 4-5 in Section 4.4.2 for fill location on separator tank.
CAUTION
Do not fill the system through the gas discharge port, as an oil cloud will
develop on start up.
Table 2.1 ELMO-Pack TM System Oil Capacity
ELMO-Pack
TM
System Oil
Capacity
(Gallons)
Pump Priming
Capacity
(Gallons)
BV2060
BV2061
BV2070
BV2071
AV2110
AV2111
AV2121
AV2131
AV2161
BE1153
BE1202
BE1203
BE1252
10
10
20
30
40
55
0.25
0.8
0.8
2.1
NOT
NOT
REQUIRED REQUIRED
Before start-up, prime the vacuum pumps unit through the suction as shown in Table 2.1
and Figure 2-3 if required. Priming is not required if the system has previously been
operated and the vacuum pump was not drained.
WARNING
Do not run the ELMO-PackTM system DRY!
30
Check the seal-oil liquid level and prime the pump with oil as described in
Section 2.5.
2. Open all valves in the operating liquid line to allow service liquid flow.
3. Make sure all drain valves are closed.
4. Open block valves on all gauges.
5. Check all piping making sure the connections are in accordance with Figure 2-2.
6. Open any isolation valves in the suction and discharge piping.
7. Check that the power supply to the motor has correct voltage and amperage as
specified in supplied wiring diagram.
8. Isolate the power source from the motor to prevent accidental starting of the motor
and system.
9. Install all necessary disconnects in accordance with local codes.
10. For each installed pump briefly jog the motor by placing the panel selector in the
manual position for a few seconds. Observe the direction of rotation of the pump.
Correct direction of rotation of the vacuum pump for BV2 and AV2 systems is
clockwise when viewed from the non-drive end of the motor; for BE1 systems the
correct direction of rotation of the vacuum pump is clockwise when viewed from the
drive end of the pump. Change pump or panel wiring (switch location of 2 leads) if
pump is operating in opposite direction from that indicated.
WARNING
Local codes may require and Siemens recommends installation of fused
disconnects or circuit breakers within sight of the control panel.
Standard control panels are not supplied with disconnects.
Check local code requirements prior to installation.
CAUTION
Only a qualified electrician should attempt
electrical installation of this system.
31
3.2 Startup
With steps 1 through 9 complete from section 3.1 (Preliminary Inspection), switch all
pumps to auto mode. All vacuum pumps should start. Observe the vacuum gauge on the
inlet connection. The gauge should start to indicate vacuum within 15 seconds. If no
vacuum is indicated, turn off the system immediately. Perform all steps 1 through 9 from
section 3.1 (Preliminary Inspection). There will not be a vacuum if there is no system
resistance to gas flow at the suction.
CAUTION
Repeated starts can cause overheating of the motor, which may result in
motor burnout (particularly for across the line starting).
If repeated starts are made, allow sufficient time between trails to
permit heat to dissipate from windings and rotor to prevent
overheating. Please consult the motor manual.
1. Confirm the oil in the separator is at the correct level and trace the operating liquid
line confirming all valves are open and the seal liquid is flowing from the separator to
the pump.
2. Confirm that there are no closed valves in the discharge piping from to the pump.
(NFPA systems only)
Run the system for hour and check for the following:
1.
2.
3.
4.
5.
Stable vacuum.
No unusual vibration or noise.
Operating temperature should be 150-190F.
Acceptable operating pressure at the separator should be 1-3 psig.
Acceptable operating pressure for the operating oil at the pump should be 1-8 Hg
Vacuum.
6. Seal oil level in separator level gauge.
3.3 Shut down
The ELMO-Pack TM system design makes shut down and re-start virtually one step
operations. When the system is to be shut down simply turn the power supply to the
system off. The ELMO-Pack Oil TM seal system is supplied with an inlet check valve to
prevent any fluid being pulled from the pump back up into the system piping.
32
Figure 3-2
3.4.2 Adjustment
Generally, unless otherwise specified, controls shipped from the factory are set at the
operating range vacuum indicated in Table 1-2 and minimum differential.
3.4.3 Operating range adjustment
Turn range adjustment Screw A counterclockwise to lower the upper and lower
vacuum settings. To increase the upper and lower settings, turn Screw A clockwise.
The approximate upper vacuum setting is shown by indicators on the outer edges of the
nameplate.
3.4.4 Differential adjustment
When the differential blade is at the low point of the differential cam the control will
function at minimum differential. To increase the differential, turn adjustment Screw B
counterclockwise. This will decrease the higher vacuum setting only. To decrease the
differential, turn differential adjustment Screw B clockwise. This will lower the higher
setting only.
Condensed instructions are supplied with open style controls and are on the inside of the
cover on enclosed devices.
NOTE: Use the vacuum gauge (See Figure 1-1) when setting the control.
CAUTION
The range adjustment Screw A should not be adjusted beyond the
pressure indicated on the pressure scale as this may cause the control to
malfunction.
It is recommended that a periodic inspection of gauge vacuum be made and the vacuum
control adjusted to compensate for application variables.
34
35
WARNING
Shut down the system and lock out power
before proceeding with any of the scheduled maintenance.
4.3 Strainer
With the pump shut down, close the ball valves located directly upstream and directly
downstream from the strainer. Place a catch pan directly below the strainer to catch
escaping oil from the strainer and pipe (see Figure 4-1). With proper sized wrench,
loosen the screen cover nut and remove (see Fig 4-2). Note that the stainless steel screen
should slide out easily. Remove the screen from the housing, clear any dirt or debris, and
inspect screen for tears, old oil buildup or damage. After clearing the screen replace it
and be sure that the screen slides easily back into place. Do not force the screw anchors
into place; if resistance is felt, check the housing cavity for obstructions. Use Teflon tape
to reseal the threads of the strainer. Once the seal is re-established, be sure to open both
isolation valves to ensure proper operation of the system.
36
DANGER
Operation on improperly selected oil can cause overheating,
overloading of the motor or degradation of the elastomers used in the
pump.
Use only Siemens ELMO-22005G vacuum oil to preserve warranty
coverage.
If removing the pump from the system, be sure to drain all of the oil from the casing. To
do this, locate the total drain on the bottom of the pump cover. Remove the drain plug
and allow the oil to flow into a catch basin. Replace the total drain plug, along with the
reusable gasket when finished.
37
CAUTION
Do not add oil through the gas discharge opening, since
it will collect in the oil mist coalescing element and cause start-up
problems. Only add oil through the oil fill connection.
4.5 Inlet Filter (optional)
Check after 50 hours of pump operation, clean or replace the element every 1000 to 3000
operating hours depending on the application or when excessive loss of vacuum is
noticed during operation. Be careful during inspection and cleaning not to knock off
excessive dirt or debris into the pump inlet. Remove any foreign debris from the filter
housing.
38
39
4.7 Cooler
The air cooler should maintain a 150-190F pump discharge temperature. If this
temperature is not maintained, check the following:
1.
2.
3.
4.
5.
Fan motor not functioning (contact Siemens customer service for replacement.)
Fan motor amps too high (check voltage).
Visually inspect fan and radiator for any visible damage or wear.
Clean Radiator fins as required if damaged, bent or clogged with debris.
Oil flow blocked. Check y-strainer and clean as required.
CAUTION
Exercise care when touching piping with hot oil flowing inside.
Do not touch if the discharge temperature gauge reads above 160F, as
burns may result.
4.10 Pump Disassembly
4.10.1 Applicability
These instructions apply only to the 7.5 Horsepower through 25 horsepower model AV2
ELMO-Pack TM systems. For the systems below 7.5 horsepower consult the appropriate
Siemens Manual for 2BV style pumps. For systems greater than 25 HP, consult the
Siemens Manual for 2BE1 style pumps. Copies of these manuals are supplied when
applicable or may be obtained directly from our website, www.siemensvpc.com.
40
CAUTION
Be sure that the work surface chosen for the disassembly
and re-assembly can support the weight of the unit.
41
CAUTION
Do not apply excessive force when removing the port plate
from the casing as damage to the port plate could result.
42
CAUTION
The flapper valve must be installed
for proper operation of the pump.
Operation without a flapper valve or
a damaged flapper valve
will affect pump and system
performance.
43
CAUTION
Reuse of the tolerance ring during
re-assembly may cause the
impeller to seat improperly or
move on the shaft, which could
damage the pump.
44
CAUTION
Do not operate the pump using motors
running at speeds other than those recommended by Siemens.
Performance and system reliability will be affected.
4.10.10 Shaft Removal
The pedestal houses the shaft and two deep groove
ball bearings. From the pump side of the pedestal,
remove the v-ring and bearing cover. There are
two shims under the bearing cover. Remove these
and store in a clean area (Figure 4-15). On the
motor side of the shaft, remove the bearing cover
and the compression washers. With both bearings
exposed, gently remove the shaft from the
pedestal. Both bearings will be secured to the
shaft.
45
4.10.12 Re-assembly
Re-assembly is the opposite of disassembly, with the following additional instructions.
4.10.12.1 Clearances
When re-assembling the impeller to the shaft, use a feeler gauge to measure the clearance
between the front face of the impeller and a metal straight edge placed against the face of
the casing. Refer to Table 4-1 for required clearances.
Table 4-1 Recommended clearances for 2AV2 pumps.
HORSEPOWER
7.5
10
15
20
25
MODEL
2AV2110
2AV2111
2AV2121
2AV2131
2AV2161
CLEARANCE
.15 to .20 mm
(.006 to .008 inches)
46
CAUTION
Do not lubricate motor while in operation, since excess grease will be
forced through the bearings and into the motor before it will force its
way out of the drain plug. Excess grease accumulation on windings
reduces insulation life.
Bearing life is assured by maintaining proper alignment, proper belt tension, and good
lubrication at all times.
Prior to shipment, motor bearings are lubricated with the proper amount and grade of
grease to provide six months of satisfactory service under normal operation and
conditions.
For best results, grease should be compounded from a polyurea base and a good grade of
petroleum oil. It should be of No. 2 consistency and stabilized against oxidation.
Operating temperature range should be from 15F to +300F for class F and H
insulation. Most leading oil companies have special bearing greases that are satisfactory,
such as Exxon Unirex N3.
Re-lubricate bearings every six months (more often if conditions require), as follows:
1.
2.
3.
4.
47
CAUTION
Do not attempt to clean motor while it is operating. Contact with
rotating parts can cause severe personal injury or property damage.
Stop the motor and lock out switch before cleaning.
The motor exterior must be kept free of oil, dust, dirt, water, and chemicals. For fan
cooled motors, it is particularly important to keep the air intake openings free of foreign
material. Do not block air outlet or inlet.
On non-explosion-proof TEFC motors, a removable plug in the bottom center of the
motor frame or housing permits removal of accumulated moisture. Drain regularly.
48
Figure 4-17. Check individual unit rotation arrows to determine proper direction of
rotation.
49
50
Check inlet check valve and inlet filter (optional). Ensure no lines are open to atmosphere causing loss of
vacuum.
Ensure that the oil level is correct and that the pump is primed.
Check the vacuum switch setting, if supplied.
Check for low oil level, add oil if needed (Oil to be above level shutoff switch).
Check discharge temperature and high temperature switch (switch set at 200F).
Check the oil scavenger line for a "high vacuum" needle valve (necessary for operation above 28" Hg V).
Pu
ACTIONS
m
va p o
cu pe
SY
um ra
M
t
Pu
es
PT
m
,b
O
p
ut
M
sh
S
d
Pu
ut
oe
s
m
s
do
p
no
o
w
td
v
M
n
e
ot
ev
r
u
h
or
ne
ea
el
xp
op
ki
Pu
ck ts o
ec
r
s
m
te
op
ou
p
dl
w
er
y
t
A
i
a
a
ll
bn
fte
te
n
or
s
ot
rs
m
st
ev abo
Pu
al
a
er
ve
no r t
m
al
p
20
i
s
s
do
es
0
ta
F
rt
Ex
es
or
s
ce
no
s
ss
t o ou
iv
nd
Ex
bt
e
ai
ce
fr
vi
n
om
br
ss
de
a
i
Pu
ve
tio
pu
si
re
m
n
m
oi
d
p
p
lu
v
w
sa
ac
ill
uu
no ge
m
or
tr
le
ot
m
ve
at
is
e
tin
l
g
X
X
X
X
X
X
X
X
X
X
X
X
X
X
Check the oil cooler and fan. Clean the cooler, ensure that 24"-30" inches of space is available in front of the
cooler, and that ambient temperature is below 104F.
Check the overload setting on the starter and fuses. Ensure proper voltage is supplied and that the wire size
is correct. Check if the disconnect is switched on.
X
X
Check if the pump has seized. If seized, consult the factory or authorized service center at once.
Check the oil return line from the seperator and ensure that the oil flows. Check for a plugged line or closed
isolating valve.
X
X
Check the pressure gauge on the separator and replace element if it reads higher than 3 psig.
Check the coupling and element and replace as needed.
Rotate the pump by hand. If rubbing noise or binding is observed, consult factory. Pump should rotate freely
by hand. Check if the bearings are greased.
Check if the pump rotation is correct.
X
X
X
X
Check the pump mounting bolts, coupling, fan, and cooler are not loose. Tighten as required.
Check if the thermostatic bypass valve is working properly and if the oil is flowing through the cooler.
Caution: HOT OIL!
X
X
X
X
X
X
Check motor amp draw. If voltage is correct then reduce oil flow by throttling valve in oil line.
X
X
51
Appendix A-1
Type
Serial (No)..
Was located at
and came into contact with substances which are subject to identification requirements
and detrimental to health. The vacuum pump/compressor was cleaned thoroughly, both
inside and outside and rinsed and completely drained.
We certify that the above information is correct and complete and that shipment was carried out in
accordance with the relevant statutory provisions.
Company .
Tel .
Fax
Address ..
..
Position ..
Date
52
Appendix A-2
MATERIAL SAFETY
DATA SHEET
DATE: 07/26/00
REVISED:
SUPERSEDES:
PRODUCT IDENTIFICATION
Trade Name:
ELMO-22005G
Chief Constituent:
Petroleum Hydrocarbon
Hazardous Ingredients/OSHA:
None
Ingredients/OSHA/NTP/IARC:
None
Ingredients Regulated by SARA Title 3, Section 313: None
II. WARNING STATEMENTS
None
Stable
Strong oxidizers
Will not occur
Oxides of carbon nitrogen, and sulphur at combustion
temperatures.
DATE: 07/26/00
REVISED:
SUPERSEDES:
53
SIEMENS: ELMO-22005G
Health
Flammability
Reactivity
1 = Slight
0 = Minimal
54
Appendix A-3
Customer shall notify Siemens, Norwood, with request for return authorization in writing with the
following information: customer name, contact person, telephone/fax numbers, pump model details
(quantity, description of problem, if warranty claim, we will require a copy of the invoice for the item
stating when it was shipped initially).
2.
A return Authorization Form indicating a Return Authorization Number will then be completed and
faxed to the Customer.
3.
The customer shall attach a copy of the Return Authorization Form to the shipping papers of the goods
being returned. The Return Authorization Number must appear on all shipping documents. Customer
will be subject to a minimum $100.00 inspection fee for each unit, which will be waived if the
inspection determines that it is a warranty case. The Purchase Order has to be submitted to SE&A to
Terry Conley before we will proceed with the inspection of the unit.
CAUTION !
It is the customers' responsibility to ensure adequate packaging and transportation
methods are used to securely return this product in its original condition. Any damages resulting
from inadequate packaging or transportation methods will be charged to the customer. Our
experience has shown that United Parcel Service (U.P.S.) is inadequate for transporting SIEMENS
pumps beginning with a model # 2BV, 2BH or 2AV.
4.
The goods shall be cleaned, dried and suitably packaged prior to shipment by the
customer.
5.
All return items shall be shipped pre-paid. (No collect shipments will be accepted.)
6.
Upon receipt of the returned goods, Siemens will inspect them and submit an inspection report to
the customer outlining findings and disposition within 10 working days after receipt of returned
goods. The customer will then be given 10 working days to respond with instructions on how to
proceed. If the inspection determines a non-warranty situation, then the customer is required to
issue a confirming purchase order for the amount indicated in the inspection report before we can
proceed with repairs. No items, unless warranty, will be returned to customer without confirming
purchase order. If the item is scrapped, the $100 inspection fee is still due and payable.
7.
For requests for Return Authorization, please fax the above described information to:
Warranty and Repair Items:
Craig Howell
Telephone Number:
(513) 841-3302
55
(513)-942-727
RETURN ADDRESS:
SIEMENS E & A, VPC
c/o SIBAR Engineering, INC.
Building C
6872 Fairfield Business Center
Fairfield, OH 45014
M
A
T
E
R
I
A
L
Cust. Number:
Customer:
Address:
City, ST Zip:
Contact:
Phone:
Fax:
Line #
QTY
Part Number
Date:
Inspected By:
D
I
S
P
O
S
I
T
I
O
N
(513)942-7070x106
(513)942-7272
(513)841-3272
(513)841-3302
Date:
Recommended Disposition:
Recommendation By:
Disposed:
Date:
Disposed By:
Date:
56
Appendix A-4
1.5 HP BV2060
Quantity per
System
1
1
2 PAILS
1
1
1
1
1
1
1
1
Item Number
007A
008A
033A
035A
048A
050A
057A
068B
Part Number
20IB11.0E001
35A09X016001
ELMO-22005G
2BY6256205
2BY62560042ZC3U
2BV2-030.40598/26
2BY20680BV035A
2BV2-173.40513/27
2BV2-165.41535/01
2BV2-030.20718/01
2BV2-0000531190
Description
Polyester Inlet Filter Element
Coalescing Filter Element
Operating Oil 5 Gallon Pail
Bearing DE
Bearing NDE
V-Ring
Mechanical Seal
Tolerance Ring
Valve Plate
Cover Gasket
Drain Plug O-Ring
2.5 HP BV2061
Quantity per
System
1
1
2 PAILS
1
1
1
1
1
1
1
2
Item Number
007A
008A
033A
035A
048A
050A
057A
068B
Part Number
20IB11.0E001
35A09X016001
ELMO-22005G
2BY6256206
2BY62560042ZC3U
2BV2-030.40598/27
2BY20680BV035A
2BV2-173.40513/27
2BV2-165.415535/01
2BV2-030.20718/01
2BV2-0000531190
57
Description
Polyester Inlet Filter Element
Coalescing Filter Element
Operating Oil 5 Gallon Pail
Bearing DE
Bearing NDE
V-Ring
Mechanical Seal
Tolerance Ring
Valve Plate
Cover Gasket
Drain Plug O-Ring
4.5 HP BV2070
Quantity per
System
1
1
2 PAILS
1
1
1
1
1
1
1
2
Item Number
007A
008A
033A
035A
048A
050A
057A
068B
Part Number
2BX150SS849
35A09X016001
ELMO-22005G
2BY6256308C3
2BY6256205ZC3
2BV2-030.40598/29
2BY20780BV035A
2BV2-173.40513/28
2BV2-165.41535/02
2BV2-030.20717/01
2BV2-0000531190
Description
Polyester Inlet Filter Element
Coalescing Filter Element
Operating Oil 5 Gallon Pail
Bearing DE
Bearing NDE
V-Ring
Mechanical Seal
Tolerance Ring
Valve Plate
Cover Gasket
Drain Plug O-Ring
7.2 HP BV2071
Quantity per
System
1
1
2 PAILS
1
1
1
1
1
1
1
2
Item Number
007A
008A
033A
035A
048A
050A
057A
068B
Part Number
2BX150SS849
35A09X016001
ELMO-22005G
2BY6256308C3
2BY6256208ZC3
2BV2-030.40598/29
2BY20780BV035A
2BV2-173.40513/29
2BV2-165.41535/02
2BV2-030.20717/01
2BV2-0000531190
Description
Polyester Inlet Filter Element
Coalescing Filter Element
Operating Oil 5 Gallon Pail
Bearing DE
Bearing NDE
V-Ring
Mechanical Seal
Tolerance Ring
Valve Plate
Cover Gasket
Drain Plug O-Ring
7.5 HP 2AV2110
Quantity per
System
1
1
2 PAILS
1
1
1
1
1
1
1
2
Item Number
007A
008A
033A
035A
048A
050A
058A
068B
Part Number
2BX150FF851
35A09X016001
ELMO-22005G
2BY6256211ZC3
2BY6256209ZC3
2BV6-030.40598/39
2BY51100BV035A
2BV5-173.40513/31
2BV5-165.41526/02
2BV5-0000531040
2BV2-0000531191
58
Description
Polyester Inlet Filter Element
Coalescing Filter Element
Operating Oil 5 Gallon Pail
Bearing DE
Bearing NDE
V-Ring
Mechanical Seal
Tolerance Ring
Valve Plate
Cover O-Ring
Drain Plug O-Ring
10 HP 2AV2111
Quantity per
System
1
1
2 PAILS
1
1
1
1
1
1
1
2
Item Number
007A
008A
033A
035A
048A
050A
058A
068B
Part Number
2BX150FF851
35A09X016001
ELMO-22005G
2BY6256313ZC3
2BY6256211ZC3
2BV6-030.40598/38
2BY51100BV035A
2BV5-173.40513/31
2BV5-165.41526/02
2BV5-0000531040
2BV2-0000531191
Description
Polyester Inlet Filter Element
Coalescing Filter Element
Operating Oil 5 Gallon Pail
Bearing DE
Bearing NDE
V-Ring
Mechanical Seal
Tolerance Ring
Valve Plate
Cover O-Ring
Drain Plug O-Ring
15 HP 2AV2121
Quantity per
System
1
1
4 PAILS
1
1
1
1
1
1
1
2
Item Number
Part Number
2BX150FF851
007A
008A
033A
035A
048A
050A
058A
068B
35A12X024001
ELMO-22005G
2BY6256313ZC3
2BY6256211ZC3
2BV6-030.40598/40
2BY51210BV035A
2BV5-173.40513/33
2BV5-165.41524/02
2BV5-0000531029
2BV2-0000531191
Description
Polyester Inlet Filter Element
Coalescing Filter Element
Operating Oil 5 Gallon Pail
Bearing DE
Bearing NDE
V-Ring
Mechanical Seal
Tolerance Ring
Valve Plate
Cover O-Ring
Drain Plug O-Ring
20 HP 2AV2131
Quantity per
System
1
1
4 PAILS
1
1
1
1
1
1
1
2
Item Number
007A
008A
033A
035A
048A
050A
058A
068B
Part Number
2BX150FF851
35A12X024001
ELMO-22005G
2BY6256315ZC3
2BY6256311ZC3
2BV6-030.40598/42
2BY51210BV035A
2BV5-173.40513/33
2BV5-165.41521/02
2BV5-0000531029
2BV2-0000531191
59
Description
Polyester Inlet Filter Element
Coalescing Filter Element
Operating Oil 5 Gallon Pail
Bearing DE
Bearing NDE
V-Ring
Mechanical Seal
Tolerance Ring
Valve Plate
Cover O-Ring
Drain Plug O-Ring
25 HP 2AV2161
Quantity per
System
1
1
6 PAILS
1
1
1
1
1
1
1
2
Item Number
007A
008A
033A
035A
048A
050A
058A
068B
Part Number
20IB13.0E001
35A19X25001
ELMO-22005G
2BY6256315ZC3
2BY6256311ZC3
2BV6-030.40598/42
2BY51610BV035A
2BV5-173.40513/36
2BV5-165.41531/01
2BV5-0000531189
2BV2-0000531191
Description
Polyester Inlet Filter Element
Coalescing Filter Element
Operating Oil 5 Gallon Pail
Bearing DE
Bearing NDE
V-Ring
Mechanical Seal
Tolerance Ring
Valve Plate
Cover O-Ring
Drain Plug O-Ring
40 HP 2BE1153
Quantity per
System
1
1
8 PAILS
2
2
1
1
2
3
2
1
2
Item Number
5.02
15.12
12.01
13.01
13.02
13.09
13.10
13.50
Part Number
20IB13.0E001
35A19X025001
ELMO-22005G
2BY11587BE270A
2BY70657JY651B
2BY11010AE121A
2BY11010AE121A
2BY11010AE132A
2BY70086WY640A
2BY80440AY641E
2BY11087QE670B
065-58U-D/10704
Description
Polyester Inlet Filter Element
Coalescing Filter Element
Operating Oil 5 Gallon Pail
Valve Plate
Flat Gasket (same as 11.03)
Cylindrical Roller Bearing
Cylindrical Roller Bearing
Deep Groove Ball Bearing
Compensating Washer
Compensating Washer
Sealing Ring Set (12.04+12.07+13.04)
Mechanical Seal
50 HP 2BE1202
Quantity per
System
1
1
11 PAILS
2
2
1
1
2
3
2
1
2
Item Number
Part Number
20IB15.0E001
5.02
15.12
13.01
13.01
13.02
13.09
13.10
13.50
35A19X025001
ELMO-22005G
2BY112087BE270A
2BY70957JY651B
2BY12020AE121A
2BY12020AE121A
2BY12020AE132A
2BY70086WY640A
2BY80710AY641E
2BY12087QE670B
095-58U-D/10708
60
Description
Polyester Inlet Filter Element
Coalescing Filter Element
Operating Oil 5 Gallon Pail
Valve Plate
Flat Gasket (same as 11.03)
Cylindrical Roller Bearing
Cylindrical Roller Bearing
Deep Groove Ball Bearing
Compensating Washer
Compensating Washer
Sealing Ring Set (12.04+12.07+13.04)
Mechanical Seal
60 HP 2BE1203
Quantity per
System
1
1
11 PAILS
2
2
1
1
2
3
2
1
2
Item Number
5.02
15.12
13.01
13.01
13.02
13.09
13.10
13.50
Part Number
20IB15.0E001
35A19X025002
ELMO-22005G
2BY112087BE270A
2BY70957JY651B
2BY12020AE121A
2BY12020AE121A
2BY12020AE132A
2BY70086WY640A
2BY80710AY641E
2BY12087QE670B
095-58U-D/10708
Description
Polyester Inlet Filter Element
Coalescing Filter Element
Operating Oil 5 Gallon Pail
Valve Plate
Flat Gasket (same as 11.03)
Cylindrical Roller Bearing
Cylindrical Roller Bearing
Deep Groove Ball Bearing
Compensating Washer
Compensating Washer
Sealing Ring Set (12.04+12.07+13.04)
Mechanical Seal
75 HP 2BE1253
Quantity per
System
1
1
11 PAILS
2
2
1
1
2
3
2
1
2
Item Number
Part Number
20IB16.0E001
5.02
15.12
13.01
13.01
13.02
13.09
13.10
13.50
35A19X036001
ELMO-22005G
2BY112587BE270A
2BY71307JY651B
2BY12520AE121A
2BY12520AE121A
2BY12520AE132A
2BY70106WY640A
2BY80980AY641E
2BY12587QE670B
130-58U-D/10733
61
Description
Polyester Inlet Filter Element
Coalescing Filter Element
Operating Oil 5 Gallon Pail
Valve Plate
Flat Gasket (same as 11.03)
Cylindrical Roller Bearing
Cylindrical Roller Bearing
Deep Groove Ball Bearing
Compensating Washer
Compensating Washer
Sealing Ring Set (12.04+12.07+13.04)
Mechanical Seal