Documente Academic
Documente Profesional
Documente Cultură
BORDA
FACT SHEET - DEWATS AT ISOLATION HOSPITAL
Isolation Hospital staff quarters - Kolhapur, Maharashtra.
Project background
Isolation Hospital staff quarters is situated next to the outer ring road near Subhash
Nagar in Kolhapur with a population about 125 people. 2 rows of staff quarters are
located in front of Isolation Hospital. 5 numbers of single storied building with
population of 25 peoples in first row and in second row, two storied building with
population of 100 people. The DEWATS unit is constructed and maintained by the
Kolhapur Muncipal Corporation.
Salient Features
Source
Design capacity
No of users
Peak flow
Influent quality
Effluent quality
: Toilets, bathrooms,
Laundry, kitchen and
urinals
: 10 cmt / day
: 125
: 8h
: BOD 300 mg/l
: N/A
Purpose
Safe disposal of wastewater.
To improve deteriorating environmental and hygienic conditions due to absence of
wastewater treatment or appropriate disposal.
Reuse for gardening / discharge in to open drain.
To reduce the environmental pollution
System in brief
The wastewater streams are channeled from all the sources and collected in a
common register near the treatment system, which consists of 4 modules : Settler,
Baffled reactor, Planted gravel filter and Collection tank.
1. Settler is a sedimentation tank for retaining particles by settling over a specific time
frame.
2. Baffle reactor ensures anaerobic degradation of suspended and dissolved solids
by mixing fresh wastewater with an active sludge blanket.
3. Planted gravel filter is used as tertiary treatment unit where aerobic and facultative
degradation of dissolved organic occurs.
4. The collection tank is used to store the treated water
Modules adopted
DEWATS Unit
Settler-1
Volume
Area of construction
No. Of chambers
Settler-2
Volume
Area of construction
No. Of chambers
Baffle reactor
Volume
Area of construction
No. of chambers
Anaerobic Filter
Volume
Area of construction
No. Of chambers
Planted gravel filter
Volume
Area of construction
Filter material used
Plants used
Colacasia
Collection Tank
Volume
Area of construction
Built up area
: 3.0 m3
: 3.2 m2
: 2
: 4.4 m3
: 4.3 m2
: 2
: 13.2 m3
: 13.6 m2
: 5
: 9.0 m3
: 7.7 m2
: 3
:
:
:
:
36.0 m3
80.0 m2
Gravel
Reed juncas,
: 5.3 m3
: 9.0 m2
: 1460.0 m2
Project no - 611171
Update 05/01/2009
27
Typical drawing
Settler
Baffled Reactor
Reuse options
Reuse of treated water for irrigation & gardening.
Monitoring results
Monitoring of wastewater flow and quality will be carried out by IIYW in January 2008.
Sample points
08.01.2008
Outlet to drain*
DATE OF
Inlet to plant
Inlet ABR
Inlet PGF
Outlet to drain*
SAMPLING:
176 51
208 65
144 43
96
30
08-01-2008
335
415
267
178
Sample points
500
400
COD
300
BOD
200
TSS
100
0
Inlet to plant
Inlet ABR
Inlet PGF
Outlet to
drain*
Concentration m g/L
Project photos
28