Documente Academic
Documente Profesional
Documente Cultură
installers
HANDBOOK
1
I N T R O D U C T I O N
Contents
System Design
Examples
13
False Alarms
15
Installation of Cables
16
Panel Installation
18
Check List
21
System Schematic
22
23
Auxiliary Contacts
25
Commissioning
27
29
Trouble Shooting
30
2
S Y S T E M
D E S I G N
3
S Y S T E M
D E S I G N
Beam Detector
Although traditionally restricted to
specialist applications, beam detection
may provide more cost effective solutions
to point detection over long distances.
4 Corridors
4 Warehouses
4 Ceiling voids
4 Hangars
4 Open shopping areas
Heat Detectors
Heat detectors are used where the
environment is subject to constant levels
of smoke or dirt.
4 Boiler rooms
4 Busy kitchens and laundries
Duct Detector
The duct housing unit is designed to
detect smoke in air conditioning
systems. It is fitted to the outside of the
duct and has 2 probes that protrude
inside the duct to monitor the air.
4
S Y S T E M
D E S I G N
7.5m
5.3m
7.5m
5.3m
MID POINT
OF AREA
MID POINT
OF AREA
7.5m
5.3m
7.5m
5.3m
Diagram 2.
Obstacle
0.5m 0.5m
Min Min
If less than
150mm ignore
If greater than
10% of ceiling
height treat as
wall
End
View
5
S Y S T E M
D E S I G N
7.
5+
5m
5+
1.
1.
1.
5m
17.9 m
S
1.
5m
7.
5+
1.
5m
7.
5+
Smoke
Detector
7.
5+
Smoke
Detector
1.
5m
2m
7.
5+
5m
Wall
Plan View
5.
5m
5.
13.5 m
H
5m
5.
Heat
Detector
5m
3+
1.
1.
3+
5.
5.
3+
1.
5m
Heat
Detector
1.
3+
5m
2m
3+
1.
1.
Wall
5.
5m
3+
Corridors
Detectors in corridors may
generally be spaced more widely.
4 This is NOT applicable to
life safety applications unless all
adjoining rooms have smoke
detection.
4 This is NOT applicable to
corridors greater than 5 metres
wide (treat as for flat horizontal
ceilings)
Detectors may be placed at
horizontal distances extended
up to 50% of the difference
between the actual corridor
width and 5 metres (see table).
E.g. (5-2) x 0.5=1.5m.
Corridor
width
(m)
Heat (m)
1.2
18.8
14.4
1.6
18.3
14.0
2.0
17.9
13.5
2.4
17.4
13.0
2.8
17.0
12.5
3.2
16.5
12.0
3.6
16.0
11.5
4.0
15.5
10.9
4.4
15.0
10.3
4.8
14.4
9.7
6
S Y S T E M
Pitched roofs
A row of sensors should be installed
along the apex of any pitched roof or
north-light roof. Smoke sensors should
be not more than 600mm from the apex
of the roof. Horizontal spacing between
sensors may be extended when used
under pitched roofs.
The horizontal distance may be extended
by up to 1% for each degree of slope of
the roof (relative to horizontal) up to a
maximum of 25%.
D E S I G N
Roof
Roof
20
Wall
Heights
Maximum heights of detectors are dependant on the fire brigade response available:
Detector/
Sensor type
General applications
(m)
Smoke
10.5
15.0
Heat grade 1
9.0
13.5
Heat grade 2
7.5
12.0
6.0
10.5
Beam
25
40
Minimum (m)
Maximum (m)
2.7
25*
100
0.3
0.6
14
See Notes
* The height may be increased to 40m provided that the general height to which combustibles are stored in the
building does not exceed 5m and that the fire brigade can attend within 5 minutes.
NOTE: Generally the beam should not pass closer, to a wall or partition, than 500mm and not closer to an obstruction,
than 600mm. However, up to 3m of the beam may be closer than this. Always consult Gent if in doubt.
Where the beam detector is mounted in the apex of a pitched or north-light roof the horizontal distance can be increased
by 1% for each degree of slope up to a maximum of 25% (eg 20 slope of roof 20% of 7.5m = 1.5m).
600mm
Max
7
S Y S T E M
D E S I G N
Design Tip!
It is good practice to site
detectors in toilets, however they
need not have
independent coverage if cover is
provided in a common lobby.
8
S Y S T E M
D E S I G N
Light Street
Noise
Average Office
Noise
Stock Room
Noise
Light Assembly
Room Noise
Dispatch Room
Noise
Heavy Street
Noise
Heavy Assembly
Room Noise
Light
Machine
Noise
Punch Press
Room Noise
Threshold
of Pain
Boiler
Factory Noise
Whisper at
1m
Heavy
Machine
Noise
Conversation
at 1m
Hammering
on Steel
30
40
50
60
70
80
90
dB(A)
100
110
120
130
140
9
S Y S T E M
D E S I G N
Design Tips!
1. Use sensor sounders in small rooms
where the sound level has been
attenuated by door partitioning
(32000/Vigilon systems only).
85dB
(1m)
100dB
(1m)
10
S Y S T E M
D E S I G N
Design Tip!
11
S Y S T E M
D E S I G N
12
S Y S T E M
D E S I G N
Stage 6. Zoning
Zoning
For several reasons a building must be
split into a number of fire detection and
alarm zones.
Notes:
1. A fire compartment is an area
bordered by a fire-resisting structure
usually at least 30 minutes resistance.
Design Tip!
Remote indicator lamps can be used
to reduce the need for small complex
zones.
They are also useful for voids and
locked cupboards.
13
E X A M P L E S
WC
WC
WC
Office
Stores
WC
Reception
Office
Assembly Area
Boiler
Room
Canteen
Warehouse
WC
>1
7.5
m H
Stores
S Office
WC
WC
S
WC
Reception
S
S
S
Office
Boiler
Room
Assembly Area
approx 550m2
S
S
Canteen
B
Warehouse
H Heat detector
B Beam detector
14
E X A M P L E S
WC
Stores
Office
WC
WC
WC
Reception
Office
Boiler
Room
Assembly Area
Canteen
Warehouse
Stage 6. Zoning
4 Floor areas should not exceed
2000m2.
WC
Remote LEDs.
WC
WC
Office
Stores
WC
Zone 1
Reception
Zone 2
Zone 3
Zone 4
Boiler
Room
Assembly Area
Office
Canteen
Warehouse
15
F A L S E
A L A R M S
16
I N S T A L L A T I O N
O F
C A B L E S
Wiring
Since every site is different, it is only
possible to give general guidance, refer to
BS 5839 for more details.
A fire alarm system depends on its
wiring. There are 2 group classes of
cable:
4 Cables NOT required to operate
after a fire has been detected e.g.
detectors and manual call points
(group 1).
4 Cables required to operate during a
fire, e.g. power supplies and sounders
(group 2).
While mineral insulated cables are
preferable for all fire alarm applications
the following cables can be used for the
two groups:
Group 1
1. MICC to BS 6207: Part 1 (with or
without sheath)
2. Cables complying with BS 6387
categories AWX, SWX, A or S.
3. PVC - insulated to BS 6004 sheathed
or non-sheathed with mechanical
protection.
4. Rubber insulated to BS 6007
5. PVC single type BK, BR and BU to
BS 6231
6. PVC insulated SWA to BS 6346
7. Cross-linked polyethylene or hard
ethylene-propylene rubber insulated
SWA to BS 5467
8. Polyethylene insulated PVC sheathed
coaxial cable to the dimensional
requirements of BS 2316: Part 3 but
with a minimum of 16 strands
/0.2mm diameter central conductor.
17
I N S T A L L A T I O N
O F
C A B L E S
18
P A N E L
111mm
Panel fixing
Panel size
395mm wide x 274mm high x 87mm deep
89mm
89mm
How to knock-in
a cable entry point
Transformer
cables
to electronic
assembly
197mm
Earth connection
to the electronic
assembly
Panel Backbox
Fixing points for the
electronic assembly
Electronic assembly
Red
Battery connections
Black
19mm
Dedicated mains
cable entry points
I N S T A L L A T I O N
19
P A N E L
I N S T A L L A T I O N
Cable termination
Earth
drain
Cable
Gland
13-back
13-top
cable entry points
Electronic assembly
Panel backbox
20
P A N E L
I N S T A L L A T I O N
Cables
For the wiring of:
Length per circuit
Type of circuit
2m
1Km
Zone circuit
1km
Sounders circuit
100m
Auxiliary circuit
l00m
l00m
500m
Power Supply
Standby Supply
With the recommended battery and zone
loading the control panel will provide a
standby supply under mains failure
conditions, for a period of 72 hours
followed by 30 minutes of alarm load.
24V Supply
The power supply terminals 24 + and 0
may drive external ancillary equipment
and is designed to be used in conjunction
with auxiliary contacts and common fire
and fault outputs.
Note: The use of the 24V supply will
affect the panel standby capability.
21
C H E C K
L I S T
MANUAL
CALL
POINT
To
Transformer(s)
Initiating contacts to
auxiliary equipment,
such as manned centre link
and magenetic door holders
FIRE
DETECTOR
MAINS
TERMINAL
N E L
To dedicated
mains isolating
protection unit
RED
TA
TB
E
Board
Auxiliary
contacts
Sounder
Zone
Zone
Zn+ Zn-
Sounder
Sn+ Sn-
There can be up to 8
Fire detection (zone) circuit
and sounder circuit depending
on the panel size
S1+ S1-
Z1+ Z1-
CFR
CFT
24V+ supply
BLACK
NC
NC
N0
N0
END OF
LINE
RESISTOR
10KOhms
Common fault
Common fire
R+
RRepeat
panel
S Y S T E M
0V supply
END OF
LINE
CAPACITOR
UNIT
22
S C H E M A T I C
23
F I R E
D E T E C T I O N
C I R C U I T S
END OF
LINE
CAPACITOR
UNIT
RED
FIRE
DETECT OR
A fire detector head
may be fitted
to a diode-base for
continuity when a detector
head is removed
and there can be
a maximum of up to
20 diode-bases
per zone circuit
MANUAL
CALL
POINT
RED
BLACK
Z1+ Z1-
Z2+ Z2-
Zone
Circuit
Zone
Circuit
Contol panel
24
F I R E
D E T E C T I O N
C I R C U I T S
S1+ S1Sounder
Sn+ SnSounder
Control panel
1 & 2 Zone
Panel
4 & 8 Zone
Panel
1A maximum
Alarm sounder
load per panel
1.5A maximum
Alarm sounder
load per panel
25
A U X I L I A R Y
C O N T A C T S
NC
NC
N0
N0
100m maximum
cable distance
Control panel
Auxiliary
contacts
100m maximum
Cable distance
CC1 Cc2
Class change
Control panel
Class Change
A pair of unmonitored
terminals allow only
the system alarm
sounders to be actuated
from a remote position.
It is considered that
the major use for
these will be for class
change functions in
schools and colleges.
Note:There is no
indication at the panel
of class change push
button operation.
26
A U X I L I A R Y
Panel outputs
CFR
Repeat Panel
There can be up to 6
repeat panels series
connected from the
control panel.
A repeat panel
duplicates fire and
fault indications
together with system
controls.
Common Fire
CFR
Common
Fault
Relay
CFT
CFT
Common Fault
24V + Supply
24+
C O N T A C T S
R+RControl panel
Screen linked
R+RRepeat panel 1
27
C O M M I S S I O N I N G
Initial power up
a) Disconnect cables to terminals of zone,
sounder, class change, auxiliary,
common fire and fault circuits. Ensure
each cable is marked for reconnection
to respective terminals later.
b) Connect end-of-line units to zones and
sounder circuits for initial power up.
c) Check mains connection and switch on
the mains power to the control panel.
d) Now connect the battery supply, see
below.
e) Check the panel provides a normal
healthy indication, with the green light
lit.
Battery installation
Control panel
FIRE
Cancel Reset
Buzzer System
Sound Silence
Alarms Alarms
Display
Test
Faults
System
Power
Earth
Day/Night
Sounder
Disabled
Power
Access /
Function
Shift
b) Remove the
lower inner plate
28
C O M M I S S I O N I N G
Panel terminals
Auxiliary contacts
1A at 24Vdc resistive
NO
NC
NO
NC
Class change,
Common fault,
Common Fire
Repeat panel
P3 to P6
CC1
CC2
To transformer
T1A
T1B
P7
P1
T1A
T1B
CN5
CN6
T2A
T2B
CN7
NC
NO
NO
CN30
Z1+
Z1-
CN8
POWER 2
F1
NC
CN29
POWER 1
S1+
S1-
Z2+
CN9
CN10
BATTERIES
F2
Z2-
S2+
CN11
S2-
Z3+
CN12
SECTOR 1
F3
Z3-
S3+
CN13
S3-
Z4+
Z4-
CN14
S4+
S4-
CN15
SECTOR 2
F4
Z5+
Z5-
CN16
S5+
S5-
CN17
SECTOR 3
F5
Z6+
CN18
Z6-
S6+
S6-
Z7+
CN19
SECTOR 4
F6
CN20
Z7-
S7+
S7-
CN21
Z8+
CN22
SECTOR 5
F7
Z8-
S8+
S8-
CN23
CC1
CC2
CN24
SECTOR 6
F8
24+
CN25
CFT
CFR
CN26
CN27
SECTOR 7
R+
R-
CN28
SECTOR 8
F9
F10
F11
Zones
FIRE
Test
Faults
Software
version
label
Fuses
Cancel Reset
Buzzer System
Sound Silence
Alarms Alarms
Display
System
Power
Day/Night
Power
Earth
Sounder
Disabled
9
v
Shift
Access /
Function
Panel
CFT
24+
CFR 0 R+ R-
29
I N S TA L L E D
S Y S T E M
T E S T S
On completion
Ensure the persons responsible for the
system are made aware of:
Test A
Test B
Fire indication
for 10 seconds
duration
followed by a
system reset
System alarm
sounds for the first
2 seconds and at the
same time a Fire
indication is
given for l0 seconds
duration followed
by a system reset
1 system operation
1 basic controls
1 their responsibility
1 and the need to log system events in
the log book.
30
T R O U B L E S H O O T I N G
SERVICE HOTLINE
0500 334455