Dear Mr. Sarang Joshi, thanks for your inputs. Please note that, condenser type
bushings are not used for this transformer.
Still we would take your point and act....
February 22, 2012
* remove the oil and clean the tank, and test tan delta and IR without the oil
* send to vapor phase for dry out and record the water content
* retest tan delta and IR
* put back the oil and perform FDS or dielectric response
actually, if high CH, tx grounding can b the main concern...you might focus it...
February 22, 2012
Don Dorris
Abhijeet,
If you could provide a little more information I might be able to suggest some things. Why
was the unit being tested?
Do you have a current oil analysis?
Do you have seperate test results of the high windings, low windings & both together?
Wye-wye connections sometimes have a common connection inside the transformer?
Was this isolated before the test?
D.D.
February 22, 2012
Sarang Joshi
Porcelain bushings may cause Tan delta problem, due to ingress of moisture. I have
faces this problem in some of the transformers but after heating values were OK
February 22, 2012
Naveen Jain
Please do one thing,take hot air blower, apply hot air on porcelin of boshing atleast 1/2
hr,sorrounding bushing & check the tan delta, if u found improovement in results than go
for Mr. sarang`s suggestion.
February 23, 2012
vijay Krishna
Bushings or moisture in insulation may be the cause of poor tan delta value. Only oil
filtration will not be effective. Better to carry out short circuit heating of the job along with
the oil filtarion.
February 24, 2012
Abhijeet Sahu
Thank you all for extending your inputs. Pleased to inform you that the problem has been
rectified. FYI the core coil assembly was put under vacuum for 4 hours and heated for 36
hours and the tan delta values measured as under:
High Voltage: (At 10 kV): GST mode: 0.424, GSTg mode: 0.648 and UST mode: 0.338
Low Voltage: (At 5 kV): GST mode: 0.386, GSTg mode: 0.417 and UST mode: 0.358
Please suggest if the aforesaid values are under permissible limit, and convey the
Standard, clause.
Abhijeet
April 13, 2012
kapil dubey
For bushing and winding the permissible limit is .007 and the rate of raised should be
less than .001. In case any one of data found crossing limit than necessary action to be
taken .
May 27, 2013