Sunteți pe pagina 1din 2

Flatpack2, Cabinetized

Power Supply System 96kW


Versatile and powerful solution for any application
The combination of cost-effective design, power density and
reliability makes the Flatpack2 a product family that truly stands
outs and provides unparalleled network availability. The versatility
of the Flatpack2 rectifier means that it can be used in a wide
variety of 48VDC and 24VDC applications across the globe.

Product Description
The Flatpack2 48V, 96kW system proves that Flatpack2 is
the ultimate building block in any telecom application. The
system includes a complete power system with up to 2000A
rectifier capacity, controller and flexible distribution options,
all in a single cabinet.

Key Features
Basic configuration is with six power shelves with the
possibility to expand up to 12 (in steps of three). Standard
distribution modules are available with the variety of knife
fuses and MCBs. A high degree of flexibility makes it easy to
meet most customer requirements fast and cost efficient.

Applications
The Flatpack2 Cabinetized 2000A system is ideal for the
application needing a higher power requirement. It has a
wide application range in both mobile and fixed networks.
Wireless, fiber and fixed line communication
Todays communications demand state of the art, cost
effective and compact DC power systems. Flatpack2
delivers an industry leading power density and superb
reliability at lowest lifetime cost
Broadband and network access
Increasing network speed demands flexible and expandable
DC power solutions. The Flatpack2 rectifiers are your key
building blocks for future needs.
Small and large
Due to the high power density, cost competitive design and
a highly flexible system communication interface, Flatpack2
rectifiers are used in system solutions from 5kW to 96kW.

Highest efficiency in minimum space


Resonant topology makes the module efficiency industry
leading and contributes to the rectifiers ultra compact
dimensions.
Digital controllers
Primary and secondary controls are digitalized, enabling
excellent monitoring and regulation characteristics. Thus,
the number of component has been reduced by 40% - for
highly reliable, long life, trouble free DC power systems.
Heat management
Front-to-back air flow with chassis-integrated heat sinks
gives the module the most suitable working environment
and no limitations in the scalability of the desired system
solution.
Unique connection
A true plug-and-play connection system: time-to-install and
cost-reducing solution.
Global approvals
Flatpack2 is CE marked, UL recognized and NEBS certified for
worldwide installation.

See reverse side for specifications

Distributed by: Power Sources Unlimited, Inc., Wrentham, MA Tel: 508-384-1419 | E-mail: sales@psui.com | Website: www.psui.com

Flatpack2 PS System 96kW, Cabinetized


Additional Technical Specifications
DC Distribution Options

AC Input
Voltage

230 VAC, single phase


230 VAC, 3-phase IT network
230/400 VAC, 3-phase TN network

Frequency

45 to 66Hz

Maximum Current

See Flatpack2 48VDC datasheet


(241115.001.DS3)

Input Protection

o
o
o
o

Soft start
Surge protection (varistors)
Internal fuses (L & N)
Disconnect above 290 VAC

Monitoring

MCB load
distribution
unit

o 30 x MCBs (DIN rail mounted, 2-63A)


o Options: LVLD (300A)
o Connection:
Directly in MCB, max 16mm2

Bulk load
distribution
unit
(Isolated knife
fuse holders)

o 4 outputs, max 630A each


o Options:
- Additional 4 outputs, max.630A
- LVLD (1200A)
o Connection: M10 bolt

Battery
distribution
unit
(Isolated knife
fuse holders)

o Alt 1: 4 outputs, max.630A each


o Alt 2: 2 outputs, max 1600A each
o Options
- LVBD contactor, 1200A or 1800A
o Connection: M10 bolt

Monitoring Unit

See Smartpack (242100.100.DS3)


datasheet

Local Operation

Menu driven software via


keypads and LCD or PC (PowerSuite)

Remote Operation

PowerSuite via modem or Web NMS via


SNMP-agent

Isolation

Alarm Relays

6 relays are standard

Operating
temp.

-40 to +60C (-40 to +140F)

Visual Indications

o
o
o
o

Storage
temp.

-40 to +85C (-40 to +185F)

Dimensions
(Ref. ETSI std)

600 x 600 x 2000mm (wxdxh)


(23.6 x 23.6 x 78.74)

Weight /2.0m

Appr. 150kg (330.7lbs) excl. rectifiers

Green LED System ON


Yellow LED Minor alarm(s)
Red LED Major alarm(s)
LCD system status

Digital Inputs

6 (for monitoring of external


equipment)

Current
Measurements

Battery current
Rectifier current

Alarms

o
o
o
o
o
o
o
o
o
o

Load fuse alarm


Battery fuse alarm
LVD operated
Low output voltage alarms
(2 individual alarm levels)
High output voltage alarms
(2 individual alarm levels)
Battery capacity
Temperature alarm
Symmetry alarm

Other Specifications

Applicable Standards
Electrical safety

IEC 60950, UL 60950

EMC

ETSI EN 300 386 V.1.3.1


(telecommunication network)
EN 61000-6-3
(emission, light industry)
EN 61000-6-2
(immunity, industry)

Environment

Storage: ETS 300 019-2-1


Transport: ETS 300 019-2-2
Operation: ETS 300 019-2-3

DC Output
Voltage

48 VDC

Current

From 1U PR (150A) up to 12U PR


(2000A)

o 3.0 KVAC input and output


o 1.5 KVAC input earth
o 0.5 KVDC output earth

Specifications are subject to change without notice


211977.000.DS3 v2

Ordering Information

Part no.

Description

241115.100
Flatpack2 48VDC/2000
211977.xxxxx Flatpack2 48VDC/ 96kW Power Rack Sales configured system (CTO)

Distributed by: Power Sources Unlimited, Inc., Wrentham, MA Tel: 508-384-1419 | E-mail: sales@psui.com | Website: www.psui.com