Section 3

REU615 standard configurations

1MRS757054 F

Section 3

REU615 standard configurations

3.1

Standard configurations
REU615 is available in two standard configurations. The standard signal
configuration can be altered by means of the signal matrix or the graphical
application functionality of the Protection and Control IED Manager PCM600.
Further, the application configuration functionality of PCM600 supports the
creation of multi-layer logic functions using various logical elements, including
timers and flip-flops. By combining protection functions with logic function
blocks, the IED configuration can be adapted to user-specific application
requirements.
The IED is delivered from the factory with default connections described in the
functional diagrams for binary inputs, binary outputs, function-to-function
connections and alarm LEDs. The positive measuring direction of directional
protection functions is towards the outgoing feeder.
Table 9:

Standard configurations

Description

Table 10:

Std.conf.

Voltage and frequency based protection and measurement functions, synchrocheck


and load shedding

Automatic voltage regulator

Supported functions

Function

IEC 61850

Protection1)
Three-phase non-directional overcurrent protection, low stage

PHLPTOC

Three-phase non-directional overcurrent protection, high stage

PHHPTOC

Three-phase non-directional overcurrent protection, instantaneous stage

PHIPTOC

Residual overvoltage protection

ROVPTOV

Three-phase undervoltage protection

PHPTUV

Three-phase overvoltage protection

PHPTOV

Positive-sequence undervoltage protection

PSPTUV

Negative-sequence overvoltage protection

NSPTOV

Frequency protection

FRPFRQ

Three-phase thermal overload protection for power transformers, two time


constants

T2PTTR

Master trip

TRPPTRC

1
3 2)

1
2 3)

2
4)

Arc protection

ARCSARC

Multi-purpose protection 3)5)

MAPGAPC

18

Load shedding and restoration

LSHDPFRQ

(3)

18

Control

Table continues on next page

REU615
Application Manual

29

Section 3
REU615 standard configurations

1MRS757054 F

Function

IEC 61850

Circuit-breaker control

CBXCBR

1 3)

Disconnector control 3)

DCXSWI

Earthing switch control 3)

ESXSWI

DCSXSWI

ESSXSWI

Disconnector position indication


Earthing switch indication

3)

3)

Tap changer position indication

TPOSSLTC

Tap changer control with voltage regulator

OLATCC

Synchronism and energizing check

SECRSYN

Trip circuit supervision

TCSSCBR

2 3)

Current circuit supervision

CCRDIF

Fuse failure supervision

SEQRFUF

Condition monitoring

3)

2
1
1

MDSOPT

Disturbance recorder

RDRE

Load profile record

LDPMSTA

Three-phase current measurement

CMMXU

Sequence current measurement

CSMSQI

Three-phase voltage measurement

VMMXU

Residual voltage measurement

RESVMMXU

Sequence voltage measurement

VSMSQI

Three-phase power and energy measurement

PEMMXU

RTD/mA measurement

XRGGIO130

Frequency measurement

FMMXU

IEC 61850-9-2 LE (Voltage sharing) 6)

SMVSENDER

Runtime counter for machines and devices


Measurement

1
1
1
1
1
(1)
1
(1)

(1)

1, 2, ... = number of included instances


() = optional

1)
2)
3)
4)
5)
6)

The instances of a protection function represent the number of identical protection function blocks available in the standard configuration.
Uo selectable by parameter, "Uo measured" as default
Must be added with Application Configuration to be available in Signal Matrix and in IED
Light only
Multi-purpose protection is used, for example, for RTD/mA-based protection, or analog GOOSE.
Only available with COM0031-0034

3.1.1

Addition of control functions for primary devices and the


use of binary inputs and outputs
If extra control functions intended for controllable primary devices are added to the
configuration, additional binary inputs and/or outputs are needed to complement
the standard configuration.
If the number of inputs and/or outputs in a standard configuration is not sufficient,
it is possible either to modify the chosen IED standard configuration in order to
release some binary inputs or binary outputs which have originally been configured
for other purposes, or to integrate an external input/output module, for example
RIO600, to the IED.
The external I/O modules binary inputs and outputs can be used for the less timecritical binary signals of the application. The integration enables releasing some
initially reserved binary inputs and outputs of the IEDs standard configuration.

30

REU615
Application Manual

Section 3
REU615 standard configurations

1MRS757054 F

The suitability of the IEDs binary outputs which have been selected for primary
device control should be carefully verified, for example make and carry and
breaking capacity. If the requirements for the primary device control circuit are not
met, using external auxiliary relays should be considered.

3.2

Connection diagrams

GUID-E8E4A6F1-57F5-4E53-AACF-FA95E7D92D83 V1 EN

Figure 11:

REU615
Application Manual

Connection diagram for the A configuration (voltage protection with


phase-to-phase voltage measurement)
31

Section 3
REU615 standard configurations

1MRS757054 F

GUID-46B7ECD1-0F3F-4DCA-8144-8A485D02061A V1 EN

Figure 12:

32

Connection diagram for the A configuration (voltage protection with


phase-to-earth voltage measurement)

REU615
Application Manual

Section 3
REU615 standard configurations

1MRS757054 F

GUID-64ADD3D1-99D0-458B-8E28-5023277CFD6C V1 EN

Figure 13:

REU615
Application Manual

Connection diagram for the B configuration (on-load tap changer


control with phase-to-phase voltage measurement)

33

Section 3
REU615 standard configurations

1MRS757054 F

GUID-AE8916E5-D21C-4C90-B38A-C93EDE80FF2E V1 EN

Figure 14:

Connection diagram for the B configuration (on load tap changer


control with phase-to-earth voltage measurement)

3.3

Standard configuration A

3.3.1

Applications
The standard configuration is intended for voltage protection and synchronism
check in the medium voltage networks. The configuration handles fault conditions

34

REU615
Application Manual