Documente Academic
Documente Profesional
Documente Cultură
Experiment No:
OBJECTIVES
1. To determine the effectiveness of heat exchanger under parallel flow and counter flow condition.
2. To determine the overall heat transfer coefficient of heat exchanger under parallel flow and counter
flow condition.
3. Theoretical estimation of overall heat transfer coefficient for the experiment conditions.
4. Comparison of experimental and theoretical heat transfer coefficient.
5. Determine NTU (no. of transfer unit for outer surface) for parallel flow and counter flow conditions
THEORY
A double pipe heat exchanger consists of two concentric, different diameter tubes with fluid flowing in each
as indicated in Figures 1. If the two fluids travel in opposite directions as illustrated in Figure 1a, the
exchanger is a counter flow type. If the fluids travel in the same direction as shown in Figure 1b, parallel
flow exists. The same apparatus is used for either flow configuration.
Overall Heat Transfer Coefficient (U)
The heat transfer in parallel and counter flow arrangement is given as;
q = U 0 A0 ( T ) LMTD
Where Uo is overall heat transfer coefficient, Ao is outer surface area of tube and ( T ) LMTD is Logarithmic
Mean-Temperature Difference.
The experimental overall heat transfer coefficient can be written as;
U 0, EXP =
q
A0 ( T ) LMTD
The heat exchange between the hot and cold water can be written as;
qh = m h , w c pw (Thi Tho )
qc = m c , wc pw (Tco Tci )
The average heat transfer can be written as;
q=
qh + qc
2
( T )LMTD =
T1 T2
T
ln 1
T2
Counter Flow:
( T )LMTD =
T1 T2
T
ln 1
T2
Effectiveness:
It is defined as the ration of actual heat transfer to maximum heat transfer that could be possibly be
transferred from one fluid to the other.
Ch (Thi Th 0 )
Cmin (Thi Tci )
Cc (Tco Tci )
Cmin (Thi Tci )
Where Ch , Cc and Cmin represent heat capacity of hot, cold fluid and minimum heat capacity of fluid
respectively.
T1
T1
T2
T2
(a)
(b)
Figure 1 Concentric tube heat exchanger (a) Counter flow arrangement (d) Parallel flow arrangement
APPARATUS
The apparatus consists of a concentric tube heat exchanger. The hot water is supplied from an electric
geyser passes through the inner tube, while the cold water from over head tank passes through outer tube.
The flow rate of both hot and cold water is controlled by the flow control valve. Inlet and exit temperatures
of hot and cold water are measured using thermocouples. Flow rate of the water is measured by the
rotameter. The outer tube is provided with insulation to minimize the heat loss to the surroundings.
TECHNICAL SPECIFICATIONS
Test Section
:
: 0.0095 m
:
: 0.0127 m
: 1.6 m
Thermocouples
Type
Numbers
Range
: K Type
: 04
: 0-200 C
OPERATION PROCEDURE
1. Make all the connections as shown in figure and check valve positions and any leakage through the
system
2. Connect the equipment to the power supply.
3. Switch on the main system.
4. Adjust the desired flow rate of water either parallel/counter flow heat exchanger.
5. Switch on the electric geyser set the hot water temperature say 50 to 60 C.
6. Allow sufficient time for thermal equilibrium to attain between hot and cold water
7. After reaching to thermal equilibrium conditions, note down the readings of temperature by rotating
knob.
8. Note down the reading of hot and cold water flow rate.
9. Repeat the experiment for different flow rates.
10. Follow the steps 1 to 8 by changing the flow conditions through the test rig.
OBSERVATION TABLE
Table 1: Parallel Flow Condition
Sr.
No.
Flow rate
(Kg/hr)
Hot Water
Inlet Temp. Outlet Temp.
(C)
(C)
Flow rate
(Kg/hr)
Cold Water
Inlet Temp. Outlet Temp.
(C)
(C)
Flow rate
(Kg/hr)
Cold Water
Inlet Temp. Outlet Temp.
(C)
(C)
1
2
3
Table 2 Counter Flow Condition
Sr.
No.
Flow rate
(Kg/hr)
Hot Water
Inlet Temp. Outlet Temp.
(C)
(C)
1
2
3
SHUTDOWN PROCEDURE
1.
2.
3.
4.
Date of Performance
Sign of Faculty