Technical Specifications
6 WATER PROOFING
6.1
General
The principal work of this Section includes, but may not be limited to:
a. Application of waterproof membrane to all portions below ground and up to
300 mm above grade of tanks and structures and roofs, floors of wet rooms
like toilets, kitchens etc.
b. application of waterproofing to floors, walls and soffits of water tanks and
reservoirs (internal faces), walls of wet rooms, walls of planters, etc.,
c. Protective painting of concrete foundation and sunken courts in contact with
soil.
6.2
Materials
Products and manufacturers specified hereinafter are specified for establishing minimum
quality standards. Products equal in quality to, or better than those specified, will be
considered acceptable but the decision of acceptability rests with the Employers
Representative.
6.2.1
Test Method
Typical Results
Long 42 N/mm2
Trans 51 N/mm2
UNOPS- MVPC
Lot-1: Construction of Treatment Plant Building and Civil Works for Water Supply System
Technical Specifications
Tear strength
membrane
- ASTM D1004
Long 30 N
Trans 30 N
Adhesion to primed
concrete
Adhesion to self
Puncture
resistance
of
membrane
Water absorption after 24 hours
Water absorption after 35 days
Environmental
resistance
Water
vapour
transmission rate
at 25oC, 75 % RH
ASTM D1000
2.0 N/mm
ASTM D1000
ASTM E154
4.0 N/mm
230 N 53 mm
ASTM D570
0.13% by weight
1.0 % by weight
ASTM D543
Conforms
ASTM E96
0.3 g/m2/24 hours
at 35oC, 90 % RH
110 oC
6.3
Surface preparation, storage of materials application and curing shall be strictly as per the
manufacturers specification.