Object affected:
Object state:
Module/Unit:
Minor
TRX
Enabled
ECxx, ERxA,
EXxA, EOCA
Fault reason:
Instruction:
ESMA System module has EOCA Optical module is not responding to ESMA System module.
lost connection to XEOCA 1. If on Local EOCA:
Optical module.
1.1 Check the bus cable, cable connectors between ESxx and Local
EOCA.
1.2 Replace Local EOCA.
2. If on Remote EOCA:
2.1 Replace Remote EOCA.
Note: If this alarm is starting and cancelling repeatedly then check
input voltage supplied to alarming EOCA. Ensure that power supply
provides voltage within 42V - 57.0V DC range.
EXxx TRX module cooling The cooling fan speed of TRX module has increased substantially
fan speed has increased
from the commanded fan speed.
from the set speed.
1. Check the ESMA operational voltage as an increased ESMA
voltage could lead to overspeeding of the fans.
2. Replace the fan unit.
3. Replace EXxx.
EXxx TRX module cooling The cooling fan speed has reduced substantially from the
fan speed has reduced from commanded fan speed.
the set speed.
1. Check that nothing obstructs the fan(s) from rotating.
2. Clean the fan unit of dust and/or dirt.
3. Replace the fan unit.
4. Replace EXxx.
Note: If "Temperature high/dangerously high" and/or 7621 alarm(s)
are also active, perform these actions as soon as possible.
EXxx TRX module has detected that its internal temperature has
exceeded +90C/+194F.
1. Ensure that the ambient temperature of the base station is below
+50C/+122F.
2. Check if any fan alarms are also active. If active, refer to fan
alarm instructions to resolve.
3. Replace the EXxx.
Note that this alarm remains active if the temperature still increases
and the "temperature dangerously high" alarm is activated.
EXxx TRX module unable There is no temperature measurement in the EXxx TRX module. All
to read internal temperature temperature sensors inside the module are broken. Fans are rotating
sensors.
at maximum speed.
1. Replace the EXxx.
Note: If fan alarm(s) are active at EXxx, perform this action as soon
as possible.
Temperature inside
Internal temperature of EOCA Optical module has exceeded +85C/
XEOCA exceeds specified +185F.
temperature range.
1. Ensure that the ambient temperature of the base station is below
+50C/+122F.
2. Check if fan alarm is also active. If active, refer to fan alarm
instructions to resolve.
3. Replace the alarming EOCA.
XEOCA Optical module EOCA Optical module detected reduced or no rotation of fan
detected cooling fan speed against commanded speed.
degradation.
1. Check that nothing obstructs the fan from rotating.
2. Clean the fan unit of dust and/or dirt.
3. Replace the fan unit.
4. Replace the alarming EOCA.
Note: If temperature alarms are also active, perform these actions as
soon as possible.
XEOCA Optical module Over current occured on the output power port(s) of Remote EOCA
detected over current on its Optical module. Affected EXxx TRX module(s) are powered down.
output power port(s).
1. Check the power cable between Remote EOCA and EXxx.
2. Replace EXxx.
3. Replace Remote EOCA.