Documente Academic
Documente Profesional
Documente Cultură
com
Course HV-2005
B64
Engineering Guidelines
Acoustical Applications
and Factors
Air terminals are the most noise sensitive of all HVAC
products since they are almost always mounted in or
directly over occupied spaces. They usually determine the
residual background noise level from 125 Hz to 2,000 Hz.
The term Air Terminals has historically been used to
describe a number of devices which control airflows into
occupied spaces at the zone (or individual temperature
control area) level. There are two types: those that control
the amount of airflow to a temperature zone (Air Control
Units, ACUs, or more commonly Boxes), and those that
distribute or collect the flow of air (Grilles & Diffusers,
GRDs). On some occasions, the two functions are
combined. As these two elements are the final
components in many built-up air delivery systems and
those closest to the building occupants, both are critical
components in the acoustical design of a space. There is
also a critical interplay between acoustics and the primary
function of these devices; providing a proper quantity of
well mixed air to the building occupants. Before discussing
types of devices, we must have an understanding of some
issues regarding sound levels in occupied spaces.
The sound level in an occupied space can be measured
directly with a sound level meter, or estimated from
published sound power after accounting for room volume
and other acoustical factors. Sound level meters measure
the sound pressure level at the microphone location.
Estimation techniques calculate sound pressure level at a
specified point in an occupied space. Measured sound
pressure levels in frequency bands can then be plotted and
analyzed, and compared with established criteria for room
sound levels.
NC - Noise Criteria
Sound Pressure Levels (Lp) are measured directly by
sound level meters at one or more points in a room.
They reference a pressure rather than a power. A products
estimated Sound Pressure Level (Lp) performance curve is
obtained by subtracting space (or other appropriate) sound
attenuation effects from the unit sound power (Lw).
Currently, most Air Outlet and Inlets (GRDs) sound
performance is reported by subtracting a 10 dB attenuation
from all octave band sound power levels, and determining
the NC rating. (This room effect approximates a
3,000 cu. ft. room, 10 ft. from the source for VAV Boxes,
which peak in lower frequencies, and a 2,500 cu. ft. room
7 ft. from a diffuser, which typically peaks @ 1000 Hz.
(This is defined in the ASHRAE\ARI Standard 885 space
effect calculation described later in this section). NC curves
were developed to represent lines of equal hearing
perception in all bands and at varying sound levels. Most
air terminal products are currently specified and reported
as single number NC ratings.
Center Frequency
Band Designation
63
1
125
2
250
3
500
4
1000
5
2000
6
4000
7
8000
8
B65
B
NC CURVE EXAMPLE
80
NC RATING GIVEN IS NC-30 SINCE THIS IS HIGHEST
NC-70
SOUND POWER
60
NC-60
50
NC-50
dB
40
NC-40
30
NC-30
20
APPROXIMATE
THRESHOLD
OF HUMAN
HEARING
NC-20
10
63
125
250
500
1K
2K
4K
8K
MID - FREQUENCY, Hz
2500 CuFt
3000 CuFt
5000 CuFt
Band
Hz
@ 5ft
@ 10ft
@ 15ft
@ 5ft
@ 10ft
@ 15ft
@ 5ft
@ 10ft
@ 15ft
@ 5ft
@ 10ft
@ 15ft
63
1
-4
-7
-9
-4
-7
-9
-5
-8
-10
-6
-9
-11
125
2
-5
-8
-10
-5
-8
-10
-6
-9
-10
-7
-10
-12
250
3
-6
-9
-10
-6
-9
-11
-7
-10
-11
-8
-11
-12
500
4
-7
-10
-11
-7
-10
-12
-7
-10
-12
-9
-12
-13
1000
5
-7
-11
-12
-8
-11
-13
-8
-11
-13
-9
-12
-14
2000
6
-8
-11
-13
-9
-12
-14
-9
-12
-14
-10
-13
-15
4000
7
-9
-12
-14
-10
-13
-15
-10
-13
-15
-11
-14
-16
8000
8
-10
-13
-15
-11
-14
-15
-11
-14
-16
-12
-15
-17
Engineering Guidelines
B66
Engineering Guidelines
RCRoom Criteria
Room Criteria (RC) is based on ASHRAE sponsored
studies of preference and requirements for speech
privacy, along with ratings for Acoustical Quality. RC
ratings contain both a numerical value and a letter
Quality rating. The RC numerical rating is simply the
arithmetic average of the sound pressure level in the 500,
1,000, and 2,000 Hz octave bands, which is the speech
interference level (SIL). These are the frequencies that
affect speech communication privacy and impairment.
Studies show that an RC between 35 and 45 will usually
provide speech privacy in open-plan offices, while a value
below 35 does not. Above RC45, the sound is likely to
interfere with speech communication.
NO RUMBLE, NO HISS
NO IDENTIFIABLE MACHINERY
SOUNDS NO TIME MODULATION
NOT TO BE FELT
Occupancy
Private residence
Apartments
Hotels/motels
Individual rooms or suites
Meeting/banquet rooms
Halls, corridors, lobbies
Service/support areas
Offices
Executive
Conference rooms
Private
Open-plan areas
Business mach
Computers
Public circulation
Hospitals and clinics
Private rooms
Wards
Operating rooms
Laboratories
Corridors
Public areas
Churches
Schools
Lecture and classrooms
Open-plan classrooms
RC
NC
RC 25-30(N)
RC 30-35(N)
NC 25-30
NC 30-35
RC 30-35(N)
RC 30-35(N)
RC 35-40(N)
RC 40-45(N)
NC 30-35
NC 30-35
NC 35-40
NC 40-45
RC 25-30(N)
RC 25-30(N)
RC 30-35(N)
RC 35-40(N)
RC 40-45(N)
NC 25-30
NC 25-30
NC 30-35
NC 35-40
NC 40-45
RC 40-45(N)
NC 40-45
RC 25-30(N)
RC 30-35(N)
RC 25-30(N)
RC 35-40(N)
RC 30-35(N)
RC 35-40(N)
RC 30-35(N)
NC 25-30
NC 30-35
NC 25-30
NC 35-40
NC 30-35
NC 35-40
NC 30-35
RC 25-30(N)
RC 35-40(N)
NC 25-30
NC 35-40
B67
B
The Four Quality letter
designations currently in use are:
A
80
OCTAVE
BAND
SOUND
PRESSURE
LEVEL,
dB re 20
MICROPASCALS
70
REGION B: moderate
probability that noise induced
vibration will be noticeable
in lightweight fixtures,
doors, and windows.
60
50
RC
40
50
45
C
30
40
35
20
30
THRESHOLD OF
AUDIBILITY
25
10
16
63
250
1K
4K
60
OCTAVE
BAND
SOUND 50
PRESSURE
LEVEL
40
30
PSIL = (35+36+34) / 3 = 35
20
RC-35(H)
10
16
63
250
1K
4K
Engineering Guidelines
R Rumble
H Hiss
V Vibration (acoustically
induced)
N Neutral
B68
B
RUMBLE AND INDUCED VIBRATION (RV)
Engineering Guidelines
80
90
A
80
B
70
60
OCTAVE
BAND
SOUND 50
PRESSURE
LEVEL
40
C
30
20
RC-33(RV)
PSIL= (38+32+29) / 3 = 33
10
16
63
250
1K
4K
SOUND POWER L w
C = Casing Radiated
and Induction Inlet
D = Discharge Sound
O = Outlet Generated
Sound
B69
Ceiling/Space Effect
ARI 885 combines the effect of the absorption of the ceiling
tile, plenum absorption, and room absorption into the
Ceiling/Space Effect. Experience has shown that the STC
rating (Sound Transmission Class) for ceiling tiles, which is
based on a two room pair test, is not well correlated with
observed data for a noise source located above a ceiling.
The ARI 885 Ceiling/Space Effect table D14 (Table 16) is
derived from a number of manufacturers observations and
is only found in the ARI Standard. This table assumes that
the plenum space is at least 3 ft. deep, is over 30 ft. wide or
lined with insulation, and that there are no penetrations
directly under the unit.
From the ARI Standard, the following attenuation values,
or transfer functions, should be used for the ceiling/space
effect:
Once the ceiling/space effect has been determined, they
are added to the sound pressure level to determine the
maximum acceptable sound power levels. This must be
done for each octave band.
Table 16. Ceiling / Space Effect (Table D14, ARI
885-98)
Frequency
Env Factor
Octave Band
Mineral Fiber
Tile Ceiling
16
18
20 26 31 36
16
15
17 17 18 19
Solid Gypsum
Board 58
23
27
27 29 29 30
LW RAD
where:
LP + S + P/C + Env
= Space Effect
P/C
= Plenum/Ceiling Effect
Env
= Environmental Effect
Engineering Guidelines
B70
Engineering Guidelines
is the sound that travels down the duct and discharges into
the room along with the conditioned air. The procedure for
determining the maximum acceptable discharge sound
power levels requires the addition of the space effect, end
reflection, duct insertion, flow division (or branch power
division), and elbow and tees to the maximum acceptable
room sound pressure levels. If more than one outlet
supplies air to a room, separate evaluations should occur
for each discharge path. This is done for each octave band.
Space Effect. The discharge sound space effect is
determined in the same manner as the radiated sound
space effect. The sound source in this case might be the
outlet (i.e., grille, register, or diffuser) supplying air to the
space, or may be sound from an upstream noise source
(damper or fan) which passes through the outlets, or a sum
of both. (Table 12)
End Reflection. When the area across the airstream
expands suddenly as the duct work terminates or ends at
the outlet to the occupied space, a significant amount of
low frequency sound is reflected back into the duct work.
This is called end reflection. The amount of end reflection
varies based on the inlet size and type of duct.
(ARI 885-98)
Duct
Diameter
6
12
24
48
0.59
0.46
0.25
0
0.93
0.81
0.57
0.18
Octave Band
4
5
1.53
1.45
1.28
0.63
2.17
2.18
1.71
0.26
2.31
1.91
1.24
0.34
2.04
1.48
0.85
0.45
2
0.6
0.4
0.2
0.1
3
1.5
0.8
0.5
0.3
Octave Band
4
5
2.7
5.8
1.9
4.0
1.4
2.8
1.0
2.0
6
7.4
4.1
2.2
1.2
7
4.3
2.8
1.8
1.2
1
17
15
13
12
9
2
12
9
8
6
5
3
6
5
3
3
2
24
Octave Band
4
5
3
1
2
0
1
0
1
0
0
0
0
6
0
0
0
0
0
7
0
0
0
0
0
8
0
0
0
0
0
Duct
Duct
Diameter Length
Inches
Feet
10
4
5
3
10
5
5
3
10
6
5
3
10
8
5
3
10
10
5
3
10
12
5
3
10
14
5
3
10
16
5
3
2
10
7
5
10
6
5
10
6
5
10
6
4
9
5
4
8
4
3
6
3
2
4
2
1
Insertion Loss, dB
Octave Bands
3
4
5
9
27
33
5
16
24
4
12
20
12
28
33
7
17
23
5
13
19
15
28
33
9
18
22
6
13
17
18
29
32
10
18
20
7
14
15
19
28
31
11
18
18
7
14
12
17
26
29
9
16
16
6
12
10
13
23
26
7
14
14
4
10
9
7
19
24
2
11
12
0
8
8
6
38
27
23
37
25
21
35
24
19
32
21
16
29
18
13
26
15
11
23
13
9
20
11
8
7
24
18
15
23
16
13
22
15
11
20
12
8
18
9
6
15
7
4
12
6
4
8
5
4
B71
10
15
20
30
40
50
60
Attenuation
31
10
ARI 885-98)
Duct
Width
5-10
11-20
21-40
41-80
0
1
6
6
0
6
6
11
Octave Band
4
5
1
6
11
10
6
11
10
10
Duct
Width
11
10
10
10
10
10
10
10
5-10
11-20
21-40
41-80
0
1
2
2
0
2
2
3
Octave Band
4
5
1
2
3
3
2
3
3
3
3
3
3
3
3
3
3
3
LW DIS
= LP + S + ER + I +
D + T/E + Env
where: LW DIS= Discharge
Sound
Power Level
LP = Sound
Pressure Level
S = Space Effect
ER = End Reflection
I = Duct Insertion
2
1
= Casing
Radiated & Inlet
= Duct Breakout
= Distribution
Duct Breakout
= Flex Duct
Breakout
= Discharge
5
5
6
6
= Outlet
Generated Sound
D = Flow Division
T/E = Tee/Elbow
Env = Environmental
Factor
Engineering Guidelines
B72
3
Correction To Be Added To
Higher Value (dB)
Engineering Guidelines
2.5
80 dB
+ 74 dB
2
1.5
154 dB (Incorrect)
Difference in Values: 6 dB
0.5
0
0
80 dB
+ 1 dB
10
Difference In Decibels
Between Two Values Being
Added (dB)
81 dB
(Correct)
>3D
Maximize Height
Above Ceiling
VAV
UNIT
Flexible Connectors
For Fan Powered Units
Ceiling
4' Min.
Flexible Ducts
To Diffusers
B73
LP (RC 40N)
55
50
45
40
35
30
Rumble
Roof
Hiss Roof
Max Room
Sound
Pressure
60
55
45
40
35
33
Engineering Guidelines
Specifying Maximum
Sound Power Levels
for Manufacturers Data
B74
Engineering Guidelines
18
20
26
31
36
Lp (RC 40N)
60
55
45
40
35
33
C/S (Table 5)
Env Effect
(Table 4)
16
2
18
1
20
0
26
0
31
0
36
0
Lw
78
65
66
66
Octave Band
Space Effect
69
2
9
3
10
4
10
5
11
6
12
7
13
74
2
9
3
5
4
2
5
0
6
0
7
0
Duct insertion for 5 ft. of 8 in. lined flex duct can be taken
from Table 20, page B70.
Octave Band
Flex Insertion Loss
2
6
3
10
4
18
5
20
6
21
7
12
2
3
3
3
4
3
5
3
6
3
7
3
2
0
3
0
4
1
5
2
6
3
7
3
2
2
3
4
4
10
5
20
6
21
7
14
2
60
2
9
9
6
3
0
2
91
3
55
1
10
5
10
3
0
4
88
4
45
0
10
2
18
3
1
10
89
5
40
0
11
0
20
3
2
20
96
6
35
0
12
0
21
3
3
21
95
7
33
0
13
0
12
3
3
14
78
B75
B
Discharge Attenuation Elements
DischargeAttenuationElements
RC 40
90
Lp (RC 40N)
Rumble Roof
80
Hiss Roof
70
Env Effect
dB
Space
60
End Ref
50
Flex
40
Flow Div
Elbow & Tee
30
Rect Duct
20
125
250
500
1K
2K
4K
2
83
3
74
4
61
5
56
6
53
7
52
Diffuser Specifications
Diffusers are commonly specified and reported in NC,
rather than RC. In most cases, there is no difference
between NC and RC for diffusers as they usually peak in
the 5002,000 Hz region, and the resultant numerical
specification is the same for both NC and RC. Diffuser NC
ratings commonly subtract 10 dB from measured sound
power levels in all bands to account for room attenuation.
As described earlier, this will be a valid assumption for a
number of combinations of room volume and distance to
the source. While an ideal specification will be based on
octave band sound levels, these are seldom available for
Engineering Guidelines
100
B76
Engineering Guidelines
Example:
The open office from the previous example is used here.
The room is large and speech privacy is desired,
requiring an RC 40N specification.
Step 1: From ARI 885 (or ASHRAE) the appropriate
sound pressure levels for an RC 40 can be
determined. In the 5th band the RC is = to the
sound pressure level requirement, 40 dB.
Step 2: The room absorption is determined from the
space effect equation. With a 10 ft. ceiling and
the terminal located a few feet away from the
receiver, the distance variable will equal 10 ft.
The volume of the room is 3,000 ft.3. The
frequency varies with the octave band. The
space effect in the 5th band will be obtained
from Table 12, page B65, and is
= 11 dB. 40 + 11 = 51 dB.
Step 3: Subtract 10 dB = the diffusers NC requirement,
or NC 41.
Octave Band
Unit Pwl
C/S (Table 16)
Env Effect (Table 15)
Estimated Room Spl
2
71
16
2
53
3
64
18
1
45
4
59
20
0
39
5
57
26
0
31
6
50
31
0
19
7
45
36
0
9
Octave Band
2
Diffuser Pwl
Space Effect (Table 12) 9
Env Effect (Table 15)
2
Estimated Diffuser Spl
3
10
1
4
48
10
0
38
5
45
11
0
34
6
40
12
0
28
7
13
0
Determining Compliance
to a Specification
When determining if a unit will meet a specification, it may
be necessary to conduct a total room sound evaluation with
multiple sound sources and multiple paths. These are
added using logarithmic addition to determine total sound
level. Once all path elements are identified, the noncritical
paths can be determined using Figure 116, page B72.
Paths which are 10 dB or more below the loudest, in any
given band, can usually be ignored.
Example:
A project engineer desires a space sound pressure level
of RC 35N for a private office. He has selected a TITUS
TQS Fan Terminal, size 512, at 1500 CFM, with a
design inlet pressure of 1 in. static pressure. From the
sound tables for the product, the sound power levels for
this unit and the reduction factors as in the previous
example are shown above:
Octave Band
Diffuser Pwl
Terminal Spl
Log Sum
53
53
45
45
38
39
41
34
31
36
28
19
29
9
9
Octave Band
Rumble Roof
2
55
3
50
4
40