Sunteți pe pagina 1din 125

TheCOBieGuide:

acommentarytotheNBIMSUSCOBiestandard
byDr.BillEast,PhD,PE,F.ASCE1,MariangelicaCarrasquilloMangual2

EXECUTIVESUMMARY

TheConstructionOperationsBuildinginformationexchange(COBie)formatistheinternational
standardfortheexchangeofinformationaboutmanagedfacilityassets.COBiedoesnotaddnew
requirementstocontracts;itsimplychangestheformatofexistingdeliverablesfrompaper
documentsandproprietaryformats,toanopen,internationalstandardformat.
WhileCOBieprovidestheformatfortheexchangeofrequiredassetinformation,itdoesnot
providedetailsonwhatinformationistobeprovidedwhen,andbywhom.ThisGuideprovides
bestpracticeguidelinesfortheserequirements.ThisGuidecanbeconsideredthecommentary
thataccompaniestheCOBieformatspecification.
Tousethisguide,customizationsreflectingregionalpractices,specializedprojecttypes,and
clientsrequirementsshouldbedocumentedinAppendixA.ThecorrectapplicationoftheCOBie
Guidemaythenbereferencedirectlyinappropriatespecifications.
Asof2012overtwentycommercialsoftwareproductssupportCOBie.Theseproductscoverthe
entirefacilitylifecyclefromplanning,design,construction,commissioningtooperations,
maintenance,andspacemanagement.Softwareimplementerswillfindtheinformationin
AppendixBhelpfulforlowlevelmappingofrequiredproperties.

ResearchCivilEngineer,EngineerResearchandDevelopmentCenter,2902NewmarkDr,Champaign,IL
61822,bill.east@us.army.mil,2713736710.
2
ResearchCivilEngineer,EngineerResearchandDevelopmentCenter

20130312COBieGuidePublicv05

ACKNOWLEDGEMENTS
TheauthorsofthisGuidewouldliketothankthosewhoparticipatedinthethreemonthopen
reviewofthisguidethatconcludedon1October2012.Therewere1,195worldwideviewsofthe
commentspostedtotheForum.Thefollowingpersonsarespecificallythankedfortheirdetailed
reviewoftheoriginaldraft:NicholasNisbet(AEC3UK),IgorStarkov(EcoDomus),RichardMitrenga
(AutoDesk),andMartyChabot(FMSystems).DanielleLove,formerlyoftheEngineerResearch
andDevelopmentCenter,isalsorecognizedforheroriginalcontributiontothefirstdraftofthis
document.

20130312COBieGuidePublicv05

TableofContents

INTRODUCTION...........................................................................................................................9

PURPOSEOFTHISCOBieGUIDE..................................................................................................9

THECOBiePROCESS..................................................................................................................10

TheCOBieBUSINESSCASE........................................................................................................11

TEAMRESPONSIBILITIES............................................................................................................12

COBieDELIVERABLES.................................................................................................................13
DesignDevelopmentDeliverable(35%Design)............................................................................13
ConstructionDocumentsDesignDeliverable(100%Design).......................................................14
BeneficialOccupancyConstructionDeliverable...........................................................................16
AsBuiltConstructionDeliverable.................................................................................................17

DELIVERABLEEVALUATIONCRITERIA.......................................................................................17
OneFacilityPerCOBieFile............................................................................................................17
UniqueAssetNaming....................................................................................................................18
COBie.Space.NameQualityGuidelines.....................................................................................18
COBie.Type.NameQualityGuidelines.......................................................................................19
COBie.Component.NameQualityGuidelines............................................................................19
COBie.TypeProductSpecification.............................................................................................20
ComponentSpatialContainment..................................................................................................20
ComponentSpatialPlacement......................................................................................................20
SiteSpatialContainment...............................................................................................................20
FacilityGeolocation......................................................................................................................21
Categories.....................................................................................................................................21
Zones.............................................................................................................................................21
Systems.........................................................................................................................................22
UnitsofMeasure...........................................................................................................................23
UseofCommercialSoftware.........................................................................................................23
MultipleModelMerging...............................................................................................................24

EQUIPMENTANDPRODUCTREQUIREMENTS..........................................................................25
8.1

GeneralRequirements......................................................................................................25

20130312COBieGuidePublicv05


8.1.1

ProjectTeamResponsibility......................................................................................26

8.1.2

UniqueComponentNameandTypeName..............................................................26

8.1.3

SpecificationReference.............................................................................................27

8.1.4

ElectricalProperties.................................................................................................27

8.1.5

Placement..................................................................................................................27

8.1.6

ConstructionDocumentsDeliverableBasisofDesign............................................27

8.1.7

OccupancyandAsBuiltDeliverablesAsInstalledCommonProperties................28

8.1.8

OccupancyandAsBuiltDeliverableAsInstalledElectricalCircuit........................28

8.1.9

OccupancyandAsBuiltDeliverablesAsInstalledSystemsofComponents.........28

8.1.10

OccupancyandAsBuiltDeliverablesAsInstalledAssembliesofComponents....28

8.1.11

OccupancyandAsBuiltDeliverableAsInstalledAssetTypeProperties...............28

8.2

RequiredHVACSystemAssets..........................................................................................29

8.2.1

Chiller........................................................................................................................29

8.2.2

Boiler.........................................................................................................................30

8.2.3

AirHandlingUnits.....................................................................................................31

8.2.4

Fancoilunits.............................................................................................................32

8.2.5

Filters.........................................................................................................................33

8.2.6

Pumps........................................................................................................................34

8.2.7

Fans...........................................................................................................................35

8.2.8

Motors.......................................................................................................................36

8.2.9

Compressors..............................................................................................................37

8.2.10

VariableAirVolumeboxes........................................................................................38

8.2.11

Valves........................................................................................................................38

8.2.12

Traps..........................................................................................................................39

8.2.13

Strainer......................................................................................................................39

8.3

RequiredPlumbingSystemAssets....................................................................................40

8.3.1

WatertreatmentAssemblies....................................................................................40

8.3.2

Valves........................................................................................................................41

8.3.3

PlumbingFixtures......................................................................................................41

8.4

RequiredFireSuppressionSystemAssets.........................................................................42

8.4.1

Pumps........................................................................................................................42

8.4.2

Valves........................................................................................................................43

20130312COBieGuidePublicv05


8.4.3

Sprinklerheads..........................................................................................................43

8.4.4

Fireextinguishers......................................................................................................44

8.5

RequiredElectricalSystemAssets.....................................................................................44

8.5.1

Lightfixtures..............................................................................................................44

8.5.2

Outlets.......................................................................................................................45

8.5.3

Switches....................................................................................................................47

8.5.4

Distributionpanel......................................................................................................48

8.5.5

Switchgear.................................................................................................................49

8.5.6

Generator..................................................................................................................50

8.6

RequiredControlSystemAssets.......................................................................................51

8.6.1

Sensors......................................................................................................................51

8.6.2

Controllers.................................................................................................................52

8.7

RequiredElevatorSystemAssets......................................................................................53

8.7.1
8.8

Elevator.....................................................................................................................53

RequiredFoodServiceSystemAssets...............................................................................54

8.8.1

Sinks...........................................................................................................................54

8.8.2

WasteDisposer.........................................................................................................55

8.8.3

Dishwasher................................................................................................................56

8.8.4

Refrigerator...............................................................................................................57

8.8.5

Icemaker....................................................................................................................58

8.8.6

Range.........................................................................................................................59

8.8.7

Fryer..........................................................................................................................60

8.8.8

Freezer.......................................................................................................................61

8.9

RequiredArchitecturalAssets...........................................................................................62

8.9.1

Doors.........................................................................................................................62

8.9.2

Windows....................................................................................................................63

8.9.3

Finishes......................................................................................................................64

8.10

FurnishingAssets...............................................................................................................65

8.11

SiteAssets.........................................................................................................................66

8.11.1

SiteWaterDistributionSystem.................................................................................66

8.11.2

SiteFireSuppressionSystem....................................................................................68

8.11.3

WaterSupplyWells...................................................................................................70

20130312COBieGuidePublicv05

8.11.4

SiteSanitarySewer....................................................................................................71

8.11.5

FuelDistribution........................................................................................................74

PARTS&CONSUMABLES...........................................................................................................77
9.1

CommonFacilityConsumables.........................................................................................77

9.2

EquipmentSpecificConsumables.....................................................................................78

APPENDIXAOWNERSREQUIREMENTS.........................................................................................79
1

AutomatedTools.......................................................................................................................79
Design............................................................................................................................................79
Construction..................................................................................................................................79
Commissioning..............................................................................................................................79

MandatoryClassification...........................................................................................................79
COBie.ContactClassification.........................................................................................................80
COBie.FacilityClassification..........................................................................................................80
COBie.SpaceClassification............................................................................................................80
COBie.ZoneClassification..............................................................................................................80
COBie.TypeClassification..............................................................................................................80
COBie.SystemClassification..........................................................................................................80

APPENDIXBMAPPINGFOREQUIPMENT/ASSETSCHEDULEREQUIREMENTS.............................81
1

RequiredHVACSystemAssets..................................................................................................81
1.1

Chiller................................................................................................................................81

1.2

Boiler.................................................................................................................................82

1.3

AirHandlingUnits.............................................................................................................84

1.4

Fancoilunits.....................................................................................................................85

1.5

Filters.................................................................................................................................87

1.6

Pumps................................................................................................................................88

1.7

Fans...................................................................................................................................89

1.8

Motors...............................................................................................................................90

1.9

Compressors......................................................................................................................91

1.10

VariableAirVolumeboxes................................................................................................92

RequiredPlumbingSystemAssets............................................................................................93
2.1

WatertreatmentAssemblies............................................................................................93

2.1

PlumbingFixtures..............................................................................................................94

20130312COBieGuidePublicv05

RequiredFireSuppressionSystemAssets................................................................................95
3.1

Pumps................................................................................................................................95

3.2

Fireextinguishers..............................................................................................................96

RequiredElectricalSystemAssets.............................................................................................97
4.1

Lightfixtures......................................................................................................................97

4.2

Distributionpanel..............................................................................................................98

4.3

Switchgear.......................................................................................................................100

4.4

Generator........................................................................................................................101

RequiredControlSystemAssets.............................................................................................102

5.1

Sensors............................................................................................................................102

5.2

Controllers.......................................................................................................................103

RequiredElevatorSystemAssets............................................................................................104
6.1

Elevator...........................................................................................................................104

RequiredFoodServiceSystemAssets.....................................................................................105
7.1

Sinks................................................................................................................................105

7.2

WasteDisposer...............................................................................................................106

7.3

Dishwasher......................................................................................................................107

7.4

Refrigerator.....................................................................................................................108

7.5

Icemaker..........................................................................................................................109

7.6

Range...............................................................................................................................110

7.7

Fryer................................................................................................................................111

7.8

Freezer.............................................................................................................................112

RequiredArchitecturalAssets.................................................................................................113
8.1

Doors...............................................................................................................................113

8.2

Windows..........................................................................................................................114

8.3

Finishes............................................................................................................................115

FurnishingAssets.....................................................................................................................116

10

SiteAssets...........................................................................................................................117

10.1

SiteWaterDistributionSystem.......................................................................................117

10.1.1

Pumps......................................................................................................................117

10.1.2

Tanks.......................................................................................................................118

10.2

SiteFireSuppressionSystem..........................................................................................119

20130312COBieGuidePublicv05


10.2.1
10.3

WaterSupplyWells.........................................................................................................120

10.3.1
10.4

Hydrants..................................................................................................................119

Pumps......................................................................................................................120

SiteSanitarySewer..........................................................................................................121

10.4.1

Manholes.................................................................................................................121

10.4.2

Pumps......................................................................................................................122

10.4.3

Tanks.......................................................................................................................123

10.5

FuelDistribution..............................................................................................................124

10.5.1

FuelPumps..............................................................................................................124

10.5.2

FuelTanks................................................................................................................125

20130312COBieGuidePublicv05

1 INTRODUCTION
BuildingInformationModeling(BIM)technologyhasdemonstrateditsabilitytoreduceoverall
projectcostthroughtheidentificationofphysicalconflictsbetweenbuildingcomponentspriorto
construction.Resolvingsuchissuesduringdesigneliminatesexpensivetearoutandrework
duringthatwouldhaveotherwiseoccurredduringconstruction.TheuseofBIMforgeometric
collisiondetectionhasbeenthestartingpointtounderstandthepotentialuseofbuilding
information.
ThebuildingSMARTalliance3hasbeguntounlockthenongeometricinformationcontentinBIM
throughthestandardizationofcontractedinformationexchangesthatwilleventuallyreplacethe
paperbaseddocumentexchangescurrentlyspecifiedbycontracts.Thegoalofthesestandardsis
toprovidetherequiredinformationcontentwhencreated,andsecurelyshareandupdate
specifiedportionsofthatinformationwithauthorizedteammembersastheprojectproceeds.
Ratherthanproducingwastefulpaperdocumentswhosecontentisimpracticaltoextract,multiple
timesduringafacilitylifecycle,standardinformationexchangesstreamlinecurrentprocessto
eliminatewasteandincreaseprofitability.Thefirstofthesestandards,theConstruction
OperationsBuildinginformationexchange(COBie4)deliversfacilityassetinformation.These
assetsaresimplythescheduledequipment,products,andspacesthatappearondesigndrawings.
ReadersunfamiliarwithCOBieshouldbeginbywatchingthefollowingtwoonlinepresentations:

Class1.Overview5
Class2.HowTo6

Itisassumedthatreadersofthisdocumenthaveviewedthesetwoonlinepresentations.

2 PURPOSE OF THIS COBie GUIDE


ThepurposeofthisGuideistoidentifytherequirementsofCOBiedeliverablesfordesignand
constructioncontracts.Thisdocumentisnotasoftwareusermanual.
Therearetwopartstothisdocument.Firstarecommonrequirementstobemetregardlessof
client.Thesecondpartisthesetofclientspecificrequirementsthatmustbemetinadditionto
thegeneralrequirements.ClientspecificrequirementsmaybefoundinAppendixAOwners
Requirements.

buildingsmartalliance.orgACounciloftheNationalInstituteofBuildingSciences.
wbdg.org/resources/cobie.phpTheCOBiehomepage.
5
youtube.com/playlist?list=PL9E7A408B074B90C9&feature=plcpCOBieCollege.Class1.Overview.
6
youtube.com/playlist?list=PL9703BB3F0E9EACA9&feature=plcpCOBieCollege.Class2.HowTo.
4

20130312COBieGuidePublicv05


Thereareovertwentycommercialofftheshelfsoftwareproductsthatsupporttheproduction
and/orconsumptionofbuildingassetinformationthroughCOBie.Instructionsonusingthese
systemstoproduceorconsumeCOBiedatamustbeobtaineddirectlyfromthesoftware
company.
TheresultsofindependentsoftwaretestingconductedbytheNationalInstituteofBuilding
SciencesaredocumentedontheCOBieMeansandMethodswebpage7.Giventhedifferencesin
softwareconfigurationandversion,thoseproducingorconsumingCOBiedeliverablesusing
commercialsoftwaresolutionsshouldconducttheirowntestusinganyoneofthreecommontest
models8.

3 THE COBie PROCESS


TheprocessofcreatingCOBiedeliverablesfollowsthesameprocessesusedintodaysdesignand
construction.COBiesimplytransformstheinformationprovidedinpaperdocumentsinto
informationthatcanbereusedthroughtheproject.ThefigurebelowsummarizestheCOBie
process.

Figure1.COBieProcess

Duringearlydesign,Architectsdevelopthespacesandgroupsofspacesneededtosupportthe
activitiesrequiredbytheownerprogrambrief.Thisinformationisdeliveredthroughthe
SchematicDesigndrawings.COBiedeliversthesubsetoftheSchematicDesigninformation
relatedtospaces,zoning,androomdatasheets.SchematicDesignstageCOBieinformationis
usedtoverifythatthefacilitybeingdesignedmeetstheownersprogrambrief.SinceCOBieisan
extractfromtheSchematicDesigndeliverables,theinformationinCOBiedatafilesmustmatch

7
8

buildingsmartalliance.org/index.php/projects/cobieTheCOBieMeansandMethodspage.
buildingsmartalliance.org/index.php/projects/commonbimfiles/TheCommonBIMfilepage.

20130312COBieGuidePublicv05

10


theinformationaboutspacesandarchitecturalproductsandschedulesfoundonSchematic
Designsubmittal.
Asthedesignnearscompletion,Engineersdesignthesystemsthatdelivertherequiredservices,
suchaselectricity,water,appropriatetemperature,fireprotection,security,etctoallowthe
activitiestotakeplace.ThisinformationisdeliveredattheConstructionDocumentsdesignstage.
Inadditiontotheupdatedarchitecturalinformation,COBiedeliversthesubsetoftheConstruction
Documentsinformationrelatedtotheproductandequipmentassetsthatwillultimatelybe
managedbytheowner.Thisassetinformationisfoundinthedesigndrawingsequipmentand
productschedules.SinceCOBieisanextractfromtheConstructionDocumentsDesign
deliverables,theinformationinCOBieshouldbeaperfectmatchfortheprintedonthedrawings
fromthatdeliverable.
Duringconstruction,thegenericassetinformationfoundintheConstructionDocumentsstageis
filledintoprovidetheCOBieconstructiondeliverables.ACOBiesubmittalpriortoBeneficial
Occupancyallowsthefacilitymanagertobeginefficientlyoperatingtheirfacilityuponoccupancy.
ACOBieAsBuiltsubmittalisalsoprovidedtoreflectallfinalchangesandasbuiltconditions.
Duringconstructionthisinformationislinkedfromothersourcessuchasdocumentscontaining
approvedsubmittals,warrantycertificates,etcAsaresultconstructioninformationmaybe
gleaneddirectlyfromelectronicsubmittalrecords.Otherinformation,documentingthespecific
installationandtestingofequipment,includessomespecificinformationsuchasserialnumber
andinstallationdatesforeverymajorbuildingasset.Theresultingdatasetisnomore,ornoless,
thanasetofOperationsandMaintenanceManualsthatcanactuallybeusedbyoperations,
maintenance,andassetmanagementpersonnel.
Followingthedeliveryoffacilityasset,maintenanceandoperationsinformationtheownerwill
loadthisinformationdirectlyintotheirCOBiecompatiblemaintenancemanagementsystemand
immediatelybegintheefficientoperationofthatfacility.UpdatestoCOBiedataresultingfrom
workordersshouldbedocumenteddirectlyinnextgenerationmaintenancemanagement
systems.ResultsofrenovationssimplyupdatethatsubsetofexistingCOBiedatawiththechanges
comingfromtherenovationproject.

4 The COBie BUSINESS CASE


ThedeliveryofCOBieisnotanewrequirement.COBie,fromthedesignersside,issimplya
reportfromtheexistingdesignoftheassetstobedelivered.COBie,fromthecontractorsside,
transformscurrentpaperdeliverablesintodatatooperatethefacility.Participantsonprojects
requiringCOBiecancreatethedeliverablesinthesamewayastheyproducethecurrentpaper
documents,orusethisnewformatasanopportunitytoeliminatewastedtimeandeffort
associatedwiththeproductionofafterthefact,errorpronepaperdocuments.Inthisview,
COBieisthedirectapplicationofleanmethodologiestoeliminatenonproductivewastein
administrativecontractingprocedures.

20130312COBieGuidePublicv05

11


Hereisoneexamplewherecurrentprocesscanbetransformed,withtherightsetoftechnologies,
toeliminatewastedeffortassociatedwiththeproductionofpaperOperationsandMaintenance
Manuals.ThiscurrentlaborintensiveprocesstocreateO&MManualsincludesaphysicaljob
crawltocollectequipmentnameplateinformationfollowedbymanmonthsofcollationof
existingdocumentsintoO&Mbinders.Thecontractmayalsoelecttocaptureelectronic
submittalsandinstallationinformationastheyoccurandreducetheircost.
TheNationalInstituteofBuildingSciencesisdevelopingaCOBieCalculatorthatwillprovidealife
cyclereviewofthecostofsuchwasteandthesavingsthatmaybeachieved.Whenpublishedin
January2013,theCOBieCalculatorandassociatedreportsmaybefoundthroughtheWhole
BuildingDesignGuidesCOBiehomepage9.

5 TEAM RESPONSIBILITIES
Duringthecourseofaproject,differentteammembershaveprimaryresponsibilitiestocreate
COBiedeliverables.GiventhatmanyteamswilluseBuildingInformationModelingtools,
particularlyduringthedesignstage,tocreatetherequiredcontractdrawings,theidentificationof
COBieresponsibilitiesshouldbeexplicitlyincludedintheteamsBIMExecutionPlan.
Onetoolthatcanassistteamsinidentifyingresponsibilitieswithrespecttotheproductionof
COBiedeliverablesistheCOBieResponsibilityMatrix10.Thismatrixallowstheteamtocolorcode
differentpartsofaCOBiedeliverabletodefinepreciserequirementsastowhatindividual,from
whichrelevantfirm,willberesponsiblefortheproductionofspecificdatawithinCOBie.
Whileprojectteamswilldefinespecificindividualsresponsiblewithintheirfirms,thefollowing
generalresponsibilitiesfortheproductionofCOBiedatashouldbeobserved.
1. RegardlessoftheformofcontracttheArchitecturalfirmisresponsibleforDesign
Development(35%Design)Deliverable.

2. Regardlessoftheformofcontract,theArchitecturalFirmisresponsibleforthe
CoordinationofalldesignDisciplinesinputtotheConstructionDocumentDesign(100%)
Deliverable.

3. Regardlessoftheformofcontract,theGeneralContractorshallberesponsibleforthe
BeneficialOccupancyandtheAsBuiltConstructionDeliverables.

4. ForprojectsthatemployThirdPartycommissioning,theCommissioningAgentmayassist
theGeneralContractortocoordinateandvalidatethequalityoftheGeneralContractor
deliverablesattheBeneficialOccupancyandtheAsBuiltConstructionDeliverables.

wbdg.org/resources/cobie.phpTheCOBiehomepage.
projects.buildingsmartalliance.org/files/?artifact_id=4093COBieResponsibilityMatrix.

10

20130312COBieGuidePublicv05

12

6 COBie DELIVERABLES
TherequirementsforthetimingofCOBiedeliverablesontypicalfacilityacquisitionprojectsare
providedinthissection.Participantsinspecificcontractsshouldreviewindividualcontract
requirementsforanychangestothesegeneralrequirements,including,butnotlimitedto,
AppendixAofthisdocument.
OneCOBiefileshallbeprovidedforeachfacilityontheproject.Iftherearemultiplefacilities,
thenanadditionalCOBiefileidentifyingtheassetsfortheSite,shallalsobeprovided.
InformationfoundinaCOBiefileshallaccuratelyreflecttheassociatedinformationondesignand
asbuiltdrawingsschedulesatthatstageoftheproject.AllCOBiefilesaretobesubmittedfor
clientapproval.Asufficientportionoftheprogresspaymentfortheoveralldeliverablepackage
shallbewithheldfornoncompliantCOBiedeliverablestocoverthepotentialcostofmanually
creatingaccurateCOBiedeliverables.
COBiedeliverablesincreaseincontentovertimetoreflecttheincreasingmaturationofthedesign
orcompletionoftheconstructionproject.RefertoDeliverableEvaluationCriteriaforthe
contentrequiredateachdeliverable.Inaddition,refertoAssetRequirementsforaminimum
listofassetstobeincludedinthemodelandminimumrequiredpropertiesforsuchassets.
AlldeliverablesshallcomplywiththeFacilityManagementHandoverModelViewDefinitionas
describedintheNationalBIMStandardUnitedStates.UnlessotherwisespecifiedCOBie
deliverablesshallbeprovidedinIndustryFoundationClass(IFC)fileformat(STEPPart21)or
COBie2.4spreadsheetformat.FilesreferencedintheCOBie.Documentsworksheetshallbe
providedwiththeCOBiefilesubmissioninPortableDocumentFormat(PDF),TagImageFile
Format(TIFF),orJointPhotographExpertsGroup(JPEG).

Design Development Deliverable (35% Design)


Regardlessoftheformofcontract,theArchitecturalfirmisresponsibleforDesignDevelopment
(35%Design)Deliverable.ThisphasemayalsobereferredtoastheSchematicDesignphase.
TheDesignDevelopmentDeliverableshallbeprovidedinasinglefileforeachfacilityinthe
project(andsite,ifapplicable)containingdesigninformationdevelopedbythoseinthe
Architecturaldiscipline.Thefocusofthedesigndevelopmentdeliverableistoprovideanaccurate
representationofspaceandarchitecturalfacilityassets.Spaceassetattributesshallbecompleted
toallowthepresentationofroomdatasheetreportscorrespondingtothelevelofdetailfoundin
theassociateddrawings.
Architecturalproducttypes,suchasdoorandwindowschedules,shallbeidentifiedifsuchassets
arefoundontheassociateddrawings.Ifplumbingandlightingassetsarefoundintheassociated
drawings,thentheseassetsshallbeidentifiedintheinformationdeliverableaswell.
TheDesignDevelopmentDeliverableshallalsoidentifytheexpectedsystemsrequiredtoprovide
heating,cooling,electricity,water,fireprotection,andotherservices.Atthisstageofthedesign,

20130312COBieGuidePublicv05

13


thesysteminformationprovidedshallbeinnameandclassificationonlywithoutreferencetothe
specificcomponentsthatcomprisethesesystems.Allsuchinformationisprovided,indetail,
duringthenextstageofdesign.
Thecontentofthedeliverableshallbeevaluatedbasedoncompliancewiththedataformat
(eitherIFCorspreadsheet)andcontent.TheCOBieworksheets(orequivalentIFCfiledata)listed
inthefigurebelowshallbeprovidedasnotedintheAssetRequirementsandDeliverable
EvaluationCriteriasections.Thepurposeoftheserequirementsistostandardizeproductand
equipmentschedulesondesigndrawingsandhavetheinformationinthoseschedulesreflectedin
theassociatedCOBiedeliverable.
ThecontentoftheDesignDevelopmentDeliverableshallreflectthespaceandscheduledproducts
andequipmentassetsaspresentedonthecorrespondingdeliverabledrawings.TheArchitectis
responsibletocorrectalldeviationsincontentbetweentheassociatedDesignDevelopment
drawingsandtheinformationdeliverabledescribedinthissection.
Table1.SchematicDesignCOBieDeliverable

COBieWorksheet
Contact
Facility
Floor
Space
Zone
Type
Component
System
Document
Attribute

RequiredContent
OnerowforthedesignersBIMmanagershallbeprovided.
OnefacilityperCOBiefile.
Onerowforeachverticalleveltoincludefoundations,floors,roofs,andsite.
Onerowperfunctionalspace,perroom.Mult.spacesinaroompossible.
OnerowforeachCOBie.SpaceandCOBie.Zonetype.
Onerowforeachscheduledproducttypefoundondesigndrawings.
Onerowforeachindividualscheduledproductfoundondesigndrawings.
Onerowforeachsystemtobedefinedinthenextstageofdesign.
Onerowforeachassociateddeliverabledocumentlinkedtorelevantsheet.
OnerowlistingURLoftargetproductCOBie.Typeselected.
OnerowforeachrequiredCOBie.SpaceAttribute.
OnerowforeachrequiredCOBie.TypeAttribute.
OnerowforeachrequiredCOBie.ComponentAttribute.

Construction Documents Design Deliverable (100% Design)


Regardlessoftheformofcontract,theArchitecturalFirmisresponsibleforthecoordinationofall
theinputfromthedesigndisciplinestotheConstructionDocumentDesign(100%)Deliverable.
IfCOBiedataattheConstructionDocumentsDesignstageisextractedfrommultipleBIMfiles
eachoftherequiredBIMfilesshallbeprovidedasapartofthatCOBiedeliverable.Regardlessof
thenativefileformatforBIMmodels,asinglemergedCOBiefileshallbeprovidedforeachfacility
intheproject(andsite,ifapplicable).ThissetofCOBiefilesshallbethebasisforclientevaluation
ofthesubmittal.ThepartysubmittingtheCOBiefileshallberesponsibletoverifythatthe
submissiondoesnotcontainduplicativeassetsorgeometry.Modelswithduplicateassetsor
geometryshallbedisapprovedbytheclient.

20130312COBieGuidePublicv05

14


Thecontentofthedeliverableshallbeevaluatedbasedoncompliancewiththedataformat
(eitherIFCorspreadsheet)andcontent.TheCOBieworksheets(orequivalentIFCfiledata)listed
inthefigurebelowshallbeprovidedasnotedintheAssetRequirementsandDeliverable
EvaluationCriteriasections.Thepurposeoftheserequirementsistostandardizeproductand
equipmentschedulesondesigndrawingsandhavethatstandardizationreflectedintheproduct
andequipmentinformationdelivered.
Table2.ConstructionDocumentsCOBieDeliverable

COBieWorksheet
RequiredContent
Contact
OnerowforthedesignersBIMmanagershallbeprovided.
Facility
OnefacilityperCOBiefile.
Floor
Onerowforeachverticalleveltoincludefoundations,floors,roofs,and
site.
Space
Onerowperfunctionalspace,perroom.Mult.spacesinaroompossible.
Zone
OnerowforeachCOBie.SpaceandCOBie.Zonetype.
Type
Onerowforeachscheduledproducttypefoundondesigndrawings.
Component
Onerowforeachindividualscheduledproductfoundondesigndrawings.
System
OnerowforeachCOBie.ComponentidentifyingtherelatedCOBie.System.
Onerowforeachassociateddeliverabledocument.Linkedtorelevant
sheet.
Document
OnerowlistingURLoftargetproductCOBie.Typeselected.
Attribute
OnerowforeachrequiredCOBie.SpaceAttribute.
OnerowforeachrequiredCOBie.TypeAttribute.
OnerowforeachrequiredCOBie.ComponentAttribute.

TherearetwoprimarydifferencesinthedeliverablesattheDesignDevelopmentand
ConstructionDocumentsstage.
First,thecontentoftheConstructionDocumentsDeliverableshallreflectthecompletesetofall
spaces,scheduledproducts,andequipmentassetsaspresentedonthecorrespondingdeliverable
drawings.AttheConstructionDocumentsstagethislistofproductsandequipmentisexpected
tobecomplete.Theattributesofthescheduledpropertiesoftheseproductswillbeupdatedto
reflecttheattributesreflectingtheBasisofDesign.Again,thisisnodifferentthansimplylifting
theinformationfromConstructionDocumentstagedrawingsandprovidingthatinformationin
theCOBieopenstandardformat.
TheseconddifferenceindeliverablesbetweenDesignDevelopmentandConstructionDocuments
stageisthattheConstructionDocumentstagemodelgroupsproductsandequipmentintothe
systemsthatprovidespecificservicesthroughoutthebuilding.
AswithdesigndrawingsattheConstructionDocumentsstage,theArchitectsresponsibilityto
coordinatedesigndrawingsofmultipledisciplinesextendstotheArchitectsresponsibilityto
ensurethatthedataprovidedfromthesedesigndrawingsisalsocoordinated.

20130312COBieGuidePublicv05

15

Beneficial Occupancy Construction Deliverable


TheGeneralContractorshallberesponsiblefortheBeneficialOccupancyandtheAsBuilt
ConstructionDeliverables.ForprojectsthatemployThirdPartycommissioning,the
CommissioningAgentmayassisttheGeneralContractortocoordinateandvalidatethequalityof
theGeneralContractordeliverablesattheBeneficialOccupancyandtheAsBuiltConstruction
Deliverables.
ThefollowingCOBieworksheets(orequivalentIFCfiledata)shallbeprovidedasnotedinthe
DeliverableEvaluationCriteriasection.
TheBeneficialOccupancyConstructionDeliverablewillbeprovidedasasingleCOBiefileforeach
facilityintheproject(andsite,ifapplicable)thatreflectstheasinstalledandcommissioned
facilityatthetimeofbeneficialoccupancy.ThisfileshallupdatetheConstructionDocuments
modeltoreflectanyadditions,updates,ordeletionstotheunderlyingbuildingsandassociated
COBiedata.Thecompletesetofcommissioninginformationcompletedatthetimeofbeneficial
occupancyshallbeprovidedwiththisdeliverable.Theattributesofthescheduledpropertiesof
installedproductswillbeupdatedtoreflectanydifferencesbetweeninstalledequipmentand
attributesreflectingthebasisofdesign.Informationneededtooperateandmaintainthe
occupiedportionsofthefacilityshallalsobeincludedinthisCOBiedeliverable.
Table3.BeneficialOccupancyCOBieDeliverable

COBieWorksheet
Contact
Facility
Floor
Space
Zone
Type
Component
System
Spare
Resource
Job

Document

Attribute

RequiredContent
OnerowforthedesignersBIMmanagershallbeprovided.
OnefacilityperCOBiefile.
Onerowforeachverticalleveltoincludefoundations,floors,roofs,and
site.
Onespaceperfunctionaluse.
OnerowforeachCOBie.SpaceandCOBie.Zonetype.
Onerowforeachscheduledproducttypefoundondesigndrawings.
Onerowforeachindividualscheduledproductfoundondesigndrawings.
OnerowforeachCOBie.ComponentidentifyingtherelatedCOBie.System.
Row(s)foreachspare,part,orlubricantforeachCOBie.Type
Onerowforeachmaterial,labor,training,orotherrequiredresource
Row(s)foreachCOBie.TypeidentifyingPMSchedules
Row(s)forCOBie.TypesidentifyingOperationsSchedules
Row(s)forCOBie.ComponentsidentifyingOperationsSchedules
Row(s)foreachCOBie.Typelistingeachapprovedsubmittaldocument.
Row(s)foreachCOBie.Typelistingallcommissioningsubmittals.
Row(s)foreachCOBie.Componentlistingallcommissioningsubmittals.
OnerowforaphotographofeachCOBie.Componentequipment
nameplate.
OnerowforeachrequiredCOBie.SpaceAttribute.
OnerowforeachrequiredCOBie.TypeAttribute.
OnerowforeachCOBie.Componentequipmentnameplateinformation

20130312COBieGuidePublicv05

16

AsBuilt Construction Deliverable


TheGeneralContractorshallberesponsiblefortheBeneficialOccupancyandtheAsBuilt
ConstructionDeliverables.ForprojectsthatemployThirdPartycommissioning,the
CommissioningAgentmayassisttheGeneralContractortocoordinateandvalidatethequalityof
theGeneralContractordeliverablesattheBeneficialOccupancyandtheAsBuiltConstruction
Deliverables.
TheCOBieworksheets(orequivalentIFCfiledata)requiredatBeneficialOccupancyshallbe
providedasnotedintheDeliverableEvaluationCriteriasection.
TheAsBuiltConstructionDeliverablewillbeprovidedasasingleCOBiefileforeachfacilityinthe
project(andsite,ifapplicable)thatreflectstheasbuiltdesigndocumentsdeliveredasfiscal
completionoftheproject.ThisfileshallupdatetheBeneficialOccupancyDeliverablemodelto
reflectanyadditions,updates,ordeletionstotheunderlyingbuildingsandassociatedCOBiedata.
Thecompletesetofcommissioninginformationshallbeprovidedwiththisdeliverable.
InformationneededtooperateandmaintainthefacilityshallalsobeincludedinthisCOBie
deliverable.

7 DELIVERABLE EVALUATION CRITERIA


COBiemodelsmustconformtoallformatandbusinessrulesfoundinNBIMSUS.Quality
requirementsmustbemetbyacombinationoftheuseofCOBietestedsoftwareanduseofthat
softwareinaccordancewithmanufacturersrecommendations.Thequalityguidelinesidentified
inthissectionareissuesthathavearisenduringsoftwaretestingduetoincorrectsoftware
configurationorincorrectuseofthatsoftware.Theprojectteamisresponsibleforunderstanding
howtousetheirselectedsoftwaretoensurecompliance.
Inaddition,theremaybeclientspecificrequirementsfoundinmorespecificcontract
requirements.Participantsinspecificcontractsshouldreviewindividualcontractrequirements
andAppendixAofthisdocumentforclarificationsorchangestothesegeneralrequirements.
COBiefilesthatdonotmeettherequirementsofNBIMSUS,includingthoserulesspecifically
highlightedbelow,andownerspecificrequirementsshallberequiredtobemanuallycorrected
andresubmitteduntilapprovedbytheclient.

One Facility Per COBie File


COBierepresentsthesetofassetsmanagedinanindividualfacility.Iftherearemultiplefacilities
andcommonsiteworkassociatedwithagivenproject,theCOBiefilesshallbepreparedforeach
individualfacility.SiteworkshallbeidentifiedinaseparateCOBiesitefileevenforstandalone
facilities.

20130312COBieGuidePublicv05

17


Itistheresponsibilityofthedesigner,consultant,orcontractorteammemberdesignatedinthe
teamsCOBieimplementationplantoensurethatinformationfrommultiplesourcescanbeeasily
integratedtoproduceasinglesetofCOBieinformationforeachfacility,ateachdeliverablestage,
suchthattheinformationintheCOBiefilematchestheinformationfoundonthedesigndrawings.
Ifspecificsetsoftoolsareprovidedbyyourcurrentagencytosupportintegrationefforts,these
toolswillalsobelistedinAppendixAOwnersRequirements.

Unique Asset Naming


Withoutuniquenames,specificassetscannotbeeffectivelymaintained.Allmanagedspaces,
productsandequipmentfoundondesignschedulesanddrawingsshallbeuniquelynamed.These
namesmustprovideinformationabouttheassetoutsidethecontextofthedesignschedule.The
namesonthedesigndrawingsmustmatchthosefoundintheCOBiedeliverable.
Duringdesign,theArchitectshallberesponsibletoresolveallconflictsinduplicativenamingby
theirownstaffandallconsultingengineers.Softwaresfailureeitherthroughconfiguration,
setup,use,orunderlyinginabilitytoimplementuniquenamingalgorithmsshallrequirethe
Architecttomanuallyupdatealleffecteddrawings,buildingmodels,andCOBiefiles.
Duringconstruction,theGeneralContractorshallberesponsibletoresolveallconflictsin
duplicativenamingofComponentsinadditiontothosedeliveredduringthedesignstages.
Softwaresfailureeitherthroughconfiguration,setup,use,orunderlyinginabilitytoimplement
uniquenamingalgorithmsshallrequiretheGeneralContractortomanuallyupdatealleffected
drawings,buildingmodels,andCOBiefiles.
ThefollowingaretheminimumqualityguidelinesrelatedtoCOBieassetnamingtobeappliedon
thesubjectcontract.
COBie.Space.Name Quality Guidelines

EachvalueinthisColumnshallbeunique.

ThecharactersinthisfieldshallbefoundwithintherangeofASCIIcharactersbetween[0
9],[az],[AZ],andthetwosymbolsdash()andunderline(_).Unlessotherwise
notedtheASCIIspacecharacters,CHR(20),inNamefieldsisprohibitedduetothe
inconsistencyofparsingsoftware.Othercharacters,includingnonprintingASCIIcontrol
charactersareexpresslyprohibited.

OneCOBie.Spacerowshallbeprovidedforeachfunctionalareaineveryphysicalroomin
everyfacility.Forlargeroomswithmultiplefunctionalareas,spacesshallbedefinedfor
eachofthefunctionalareasanddesignatedwithadashfollowedbyaletterdesignation
startingwithAandworkingthrougheachofthesubsequentspaces.

20130312COBieGuidePublicv05

18

COBie.Space.Namesshallexactlymatchthespacenamesshowntherelateddesignand
constructiondeliverables.

COBie.Space.Tagfieldshallbeusedforbuildingsignage.

COBie.Space.Namerequirementsforuniquenamingoffunctionalareasshallextendto
differentworkareasonlargeroofingspacesordiscretegeographicregionsinsitemodels.

COBie.Space.Descriptionvaluesnotpublishedoncontractdrawingsshallhavegeneric
spacedescriptions.

COBie.Type.Name Quality Guidelines

EachvalueinthisColumnshallbeunique.

ThecharactersinthisfieldshallbefoundwithintherangeofASCIIcharactersbetween[0
9],[az],[AZ],andthetwosymbolsdash()andunderline(_).Unlessotherwise
notedtheASCIIspacecharacters,CHR(20),inNamefieldsisprohibitedduetothe
inconsistencyofparsingsoftware.Othercharacters,includingnonprintingASCIIcontrol
charactersareexpresslyprohibited.

Scheduledequipmentandproductsfoundonthedrawingsshallbeuniquelynamed.

Unlessotherwisespecifiedbytheclient,thenameofeachCOBie.Typeofproductand
equipmentshallbeginwithasignifieroftheproducttypethatwouldberecognizabletoa
facilitymanageroutsidethecontextofthespecificdesign.Forexample,thedesignation
DOORAuniquelydistinguishesthatCOBie.TypefromthelightfixturetypeLIGHTA.

Thedesignershalleitherutilizeclientsuppliedtemplateobjectsorexplicitlycoordinate
thenamesofallproducttypes,inadvance,withtheowneranddocumentalldecisions.
COBie.Component.Name Quality Guidelines

EachvalueinthisColumnshallbeunique.

ThecharactersinthisfieldshallbefoundwithintherangeofASCIIcharactersbetween[0
9],[az],[AZ],andthetwosymbolsdash()andunderline(_).Unlessotherwise
notedtheASCIIspacecharacters,CHR(20),inNamefieldsisprohibitedduetothe
inconsistencyofparsingsoftware.Othercharacters,includingnonprintingASCIIcontrol
charactersareexpresslyprohibited.

20130312COBieGuidePublicv05

19

Individualinstancesofeachtypemustalsobeunique.Forlargepiecesofscheduled
equipmentsuchasAirHandlingUnits,suchuniquenamingiscommonlyfoundondesign
schedules.

Unlessotherwisespecifiedbytheclient,foritemswheredesignschedulesdescribeonly
theassettypes,suchlightingorplumbingfixtureschedules,thefollowingformulafor
creatingauniquecomponentnameshallbeused.
COBie.Type.Name&&COBie.Space.Name&&ItemCountinSpace.
Forexample,ifthereweretwosinksoftypeSinkAinspace100theuniquenamesof
eachofthesecomponentsfollowingthealgorithmshallbeSinkA10001andSinkA
10002.

COBie.Type Product Specification


DuringthecourseoftheCOBiedeliverablesthespecificityofinformationaboutCOBie.Typewill
typicallyincreasefromanotionalperformancespecification,toidentificationoftheBasisof
Designofspecificmanufacturer,totheproductactuallyapprovedandinstalledbytheContractor.
GiventhedifferencesbetweenvarioussoftwareproductsimplementingCOBieandtheir
treatmentofthisproductlifecycle,requirementsforBasisofDesigndocumentationshallbe
identifiedasspecifiedinthisdocument.

Component Spatial Containment


AllCOBie.ComponentrecordsshallbeidentifiedintheCOBie.Spaceinwhichtheassetisfoundor
theCOBie.Spacefromwhichtheassetisoperated.

Component Spatial Placement


ACOBie.AttributenamedSpatialPlacementshallbeprovidedforeachCOBie.Component.This
Attributeidentifiesinformationneededbythefacilitymanager,operatorormaintainertoaccess
thatcomponent.TypicalvaluesoftheSpatialPlacementAttributeshallincludeUnderFloor,
AboveCeiling,InWall,InSpace,OnRoof,OnSite.

Site Spatial Containment


Foreachfacilitycompoundorcampuswithsharedsitework,aseparateCOBieSitefileshallbe
submitted.AsingleCOBie.Floorrowwillbecreatedforthissitefileandidentifiedasa
COBie.Floor.FloorTypeofSite.Definableareaswithinthatsitewillbeidentifiedinrowsinthe
COBie.Spaceworksheet.ExamplesoftypicalCOBie.SpacerowswithinCOBie.Floor=Sitesare
parkinglots,utilitypads,loadingdocks,etcThedefaultlistofSitespacesthatshallbeincluded
foragivenclientareidentifiedinAppendixA.

20130312COBieGuidePublicv05

20

Facility Geolocation
ToensurecoordinationofCOBiedatawithcampusmanagementandGeographicInformation
Systems,thefollowingCOBie.AttributesshallrowsbeprovidedforeachCOBie.FacilityRecord
basedon(intheNorthernHemisphere)thelowerlefthandspatialcoordinateofeachfacility.

Longitude
Latitude
Elevation
Rotation

Categories
Largepublicclientsmanagedifferenttypesoffacilitiesonmultiplecampuses.Toeffectively
managetheseportfolios,COBiedeliverablesarerequiredtoreceivebuildinginformationina
consistentway.InCOBiethisisaccomplishedthroughtheuseofseveraldifferenttypesof
Classifications.ClassificationsarecategorycodesofdifferenttypesusedinCOBie.TheNBIMS
USrequiresclassificationforthefollowingCOBieworksheets.

Contact
Facility
Space
Type
System

NBIMSUSdesignatesOmniClass11asthedefaultclassificationmethodusedifnoothermethodis
specifiedincontract.ThedefaultlistofmandatoryCOBieClassificationsthatshallbeincludedfor
agivenclientareidentifiedinAppendixA.
NotethataclientsrelianceonOmniClassalonemaynotensurecrossprojectcompatibilityover
time.TheOmniClassclassificationtables,justlikeallclassificationsystems,changeovertimeas
updatesareincorporated.Itistotheclientsbenefittodetermineandpublishtheprecise
classificationschemerequiredacrossallprojects.

Zones
Buildingscontaingroupsofspacesthat,whenconnected,providespecificcapabilitiestothe
owner.TheCOBie.Zoneworksheetisdesignedtoidentifythespacesthatmakeupagivenzone.
Ingeneral,zonesshallbeidentifiedbyzonetypeandcharacteristics.Zonesnaminginlarge
facilitiesshallalsobeidentifiedfloorandwingappended.Thenamesofzonesandsubzonesshall
beapprovedbytheowner.Thedefaultlistofzonesthatshallbeusedforagivenclientare
identifiedinAppendixA.

11

omniclass.org/OMNIClassConstructionClassificationSystem.

20130312COBieGuidePublicv05

21


ACOBie.Spacemayonlybelistedonceforagiventypeofzone.ACOBie.Spacemay,however,be
partofmultipletypesofzones.
AsanexampleconsiderSpace100inabuildingwhereCirculationZoneandFireProtection
zoninginformationisrequiredbytheowner.InthisexampleSpace100couldbepartofthe
CirculationZonePublicCirculationZoneandtheFireProtectionZoneFirstFloorWestWing
FireProtectionZone.Itisnot,however,possibleforSpace100tobepartofboththeFire
ProtectionZoneFirstFloorWestWingandFireProtectionZoneFirstFloorEastWingzones.
Zonesmaybenested.Nestingmustbeaccomplishedthroughthenameofthezone.For
example,theremaybesharedspacesthatsupportboththeFireProtectionZoneFirstFloor
WestWingandFireProtectionZoneFirstFloorEastWingzone.Suchzonescanbeidentified
intheFireProtectionZoneFirstFloorzone.
Ifagreedtobytheprojectteam,thenestingofzonesmaybeaccomplishedthroughtheuseof
COBie.AttributesthatidentifytheParentZoneofthecurrentzone.

Systems
Buildingscontaingroupsofcomponentsthat,whenconnected,providespecificrequiredservices.
TheCOBie.Systemworksheetisdesignedtoidentifythecomponentsthatmakeupagivensystem.
Ingeneral,systemsshallbeidentifiedbybuildingservice,floorandwing.Thenamesofsystems
withineachsystemtypeshallbeapprovedbytheowner.Subsystems,ifrequired,shallbe
identifiedusinganownerapprovednamingconvention.Thelistofsystemspossibleforatypical
projectforyourcurrentagencymaybefoundinAppendixAOwnersRequirements.
ACOBie.Componentmayonlybelistedonceforagiventypeofsystem.ACOBie.Componentmay,
however,bepartofmultipletypesofsystems.
AsanexampleconsiderComponentSensorTemperature101inabuildingwhereHVAC
systemandSensorSysteminformationisrequiredbytheowner.Inthisexample,thesensor
couldbepartofboththeHVACSystemChilledWaterandtheBASSystemHVACSensors
system.Itisnot,however,possibleforthesensortobepartofboththeHVACSystemChilled
WaterandHVACSystemFirstFloorHeatingDistributionsystem.
Systemsmaybenested.Nestingmustbeaccomplishedthroughthenameofthesystem.For
exampleaFireProtectionSystemmayhaveasetofequipmentsupportingFireProtection
CommonandequipmentsupportingspecificareasofthebuildingsuchaFireProtectionFirst
Floor,WestWingandaFireProtectionFirstFloor,EastWing.
Aquestionthatmaycomeupistherelationshipbetweensystemsandzones.Thisisrelevant
sincesomesystemsandzoneshaveoverlappingboundaries.Thelinkcanbedirectlyfoundinthe
COBiedataspecificationfromeitherthedirectionofcomponentsorspaces.Tofindthe
COBie.ComponentsandCOBie.Systemsthatsupportspecificspaces,aquerycanbemadetolook

20130312COBieGuidePublicv05

22


forallcomponentsthatarefoundintheCOBie.SpacesidentifiedwithinagivenCOBie.Zone.The
inversequerycanalsobemadetoidentifytheCOBie.SpacessupportedbyagivenCOBie.System.

Ifagreedtobytheprojectteam,thenestingofsystemsmaybeaccomplishedthroughtheuseof
COBie.AttributesthatidentifytheParentSystemofthecurrentsystem.

Units of Measure
COBiemodelsrequireasinglestandardsetofunitsofmeasureforlinear,area,andvolumetric
measures.Thisunitofmeasurestandardisappliedonallunitsthatdonototherwisehaveunits
attached.Designersshalldesignatetherequiredunitsofmeasurefortheirprojectsforowner
approvalpriortostartingdesign.Allotherdisciplinesshallberequiredtousethesameunitsof
measuredefinedbythedesigner.
Thearchitecturalmodelandallothermodelsshallbeorientedtoprojectnorth.Thedifference
betweenprojectnorthandmagneticnorthshallbedefinedbythearchitect.Thedesignershall
designatetheelevationoftheprojectforasingleoriginpoint.LatitudeandLongitudeshallbe
definedbasedonthesingleoriginpoint.Allotherdisciplinesshallberequiredtoreferencethe
projectnorthrotationandelevationoriginpointdesignatedbythedesigner.
Unitsonattributesshallberequiredtobeidentifiedwitheachnumericvalueinthe
COBie.Attributesworksheet.ThisappliesregardlessofthetypeofAttributebeingprovided.
Giventhedifferencesinsoftwareimplementationofunits,itiscriticalthatthedesignteam
evaluatetheirproductusingsmalltestingmodelstoensurethatthisrequirementcanbemet.It
wouldbeexpectedthatcommercialproductCOBiepointsofcontactwillneedtobeidentifiedand
contactedtoreducepostdesignorpostconstructionmanualupdatingofCOBiedeliverables.
DuringdesigntheArchitectshallberesponsibleforthemanualupdateofallCOBie.Attributesnot
automaticallyprovidedbydesignsoftware.DuringconstructiontheContractororCommissioning
AgentshallberesponsibleforthemanualupdateofallCOBie.Attributesnotautomatically
providedbysoftwareusedtocreatetheirrequireddeliverables.

Use of Commercial Software


ManycommercialproductscanproduceCOBiedataautomatically.Itiscritical,whenusingthese
products,thatthesoftwarevendorssetupinstructionsarefollowedpriortotheuseofthat
software.Withoutthecorrectinitialconfiguration,thedesigner,commissioningagent,or
contractormayberequiredtorekeybyhandtheinformationrequiredinCOBiedeliverables.
AllCOBiedeliverablesshallbeaccompaniedbyareportthatdemonstratesthatthefileprovided
meetstheformattingrequirementsoftheCOBiespecification.

20130312COBieGuidePublicv05

23


Differentcheckingtoolshavedifferentcapabilities.SomecheckbothIFCbasedandspreadsheet
basedfiles.Othersonlycheckspreadsheetbasedfiles.Thelistofavailabletoolsmaybefoundon
theCOBieMeansandMethodsPage12.
Iftherearespecificcheckingtoolrequirementsforagivenowner,thesemaybefoundin
AppendixAOwnersRequirements.

MultipleModel Merging
Giventhevarietyoftechnology,approachestoprovidingCOBiedata,andnewlyemerging
practicalexpertiseinmergingCOBiedata,specialconcernshouldpaidbythosepreparingCOBie
deliverablesfrommultipleunderlyingsourcefiles.Thediscussionbelowmayhelptoclarifythese
issuesforthosewhoattempttoaggregateCOBiedatafrommultiplesources.
Therearetwogeneralclassesofproblemsthatmaybeencountered.Inthefirstcase,problems
arerootedindesignpractice.Inthesecondcasesproblemsstemfromincompleteadoptionopen
standardsbysoftwarefirms.
ConsidertheworkflowintheDesignDevelopmentstagewhenanArchitectwillproducea
reflectedceilingplancontainslightingfixturesandplumbingfixtureschedule.Laterduring
ConstructionDocumentsstagetheelectricalEngineerslightingfixturescheduleandmechanical
Engineersplumbingfixtureschedulewillbecompleted.Itissometimesthecaseindesign
practicethatsuchinformationwillnotexactlymatch.Thegeneralruletointerpretingdrawing
inconsistenciesisthatthemoredetailedinformationgovernsoverlessdetailedinformation.The
practicalimpactofthisruleisthattheconstructionbidswillalmostalwaysbemadeagainstthe
electricallightingfixturescheduleandnottheArchitectsreflectedceilingplan.
ThesecondtypeofissuethatmayimpactonthemergingofCOBiedatafrommultiplesourcesis
thatsoftwarethatimportstheArchitectsoriginalmodelmaynotmaintainuniqueSpace,Typeor
Componentnames.Insomecaseswhenthedatafromthisadditionalsoftwareismergedback
intoasinglefilemultiplespacesandequipmentandassociatedpropertiesandgeometrymaybe
found.
ItisrecommendedthatwhenpreparingaCOBiedeliverablefrommultiplemodelsthatapre
flightcheckofmodelmergingoperationsbeconductedtodetermineifassetsareduplicatedin
differentmodels.Ifautomatedmethodsforsupportingdesignqualitycontrolarenotavailableby
thedesignteamscommercialsoftwareproduct,thedesignersBIMmanagerwillhaveto
completethisreviewand/ormergingmanually.
Ifthereisaquestionregardingtheorderofprecedenceinmerging,thenmergingshouldfollow
standardcontractinterpretationrulesofprecedence.Thestandardapproachisthatmoreprecise
information(providedbyarespectivedesigndiscipline)takesprecedenceoverthemoregeneral
Architecturalinformation.Aspecificsetofrulesshouldbedevelopedbytheteamwhenmerging

12

buildingsmartalliance.org/index.php/projects/cobieTheCOBieMeansandMethodspage.

20130312COBieGuidePublicv05

24


multiplefiles.ThebuildingSMARTalliance13hascurrentlypublishedadocumentcontainingan
examplesetofmergingrulesattheconstructiondocumentstage.

8 EQUIPMENT AND PRODUCT REQUIREMENTS


COBiedeliversinformationaboutmanagedassets.Spatialassetsshallbeidentifiedinthe
COBie.SpaceworksheetandhavepropertiescorrespondingtoarchitecturalRoomDataSheetsas
specifiedbytheclient.Equipmentandproductassetsdescribedinthissectionappearinthe
COBie.TypeandCOBie.Componentworksheets.Attributesofsuchassetsappearinthe
COBie.Attributeworksheet.
ItisarequirementofCOBieChallengeeventsbeginninginJanuary2013thatallsoftware
producingorusingCOBiedataprovideexplicitenduserinstructionsregardingtheapplicationof
regional,national,orclientspecificpropertysets.Anexampleofaregionalpropertysetproject
underwayintheUnitedStatesistheSpecifiersPropertiesinformationexchange(SPie)project.In
thefuture,itisexpectedthatclientswillspecifytheuseofpreparedtemplateobjectswith
mandatorypropertiesthatreflecttheiruniquerequirements.
Inabsenceofclientspecifiedregional,national,orclientspecificpropertysets,theprojectteam
maydevelopequipmentandproductschedulesaccordingcurrentbusinesspractices,andsubmit
forclientapprovaltheseschedulesthatwillbereviewedagainstthequalitystandardsidentifiedin
thisGuide.Whendevelopingequipmentandproductschedules,designersandconsultantsshall
ensurethatscheduleheadingsarenormalizedtoeliminateduplication,resolvesynonyms
betweendisciplines,andconsistentlynameobjectstoprovideinformationuponwhichthefacility
maybeefficientlymaintained,operated,andmanaged.Unitsforallattributesshallalsobe
identifiedandcoordinatedbetweendesignersandconsultants.
Regardlessofthesourceofthepropertiesspecifiedinclientcontracts,COBie.Attributesforall
COBie.TypeandCOBie.Componentrecordsshallmatchthepropertiesfoundonequivalentdesign
drawingequipmentandproductschedules.
Section8.1identifiescommonCOBiequalityattributesthatapplytoallprojects,regardlessof
regional,national,orclientspecificpropertysets.Subsectionsbeginningwithsection8.2
identifypropertiesidentifiedbyassettype.Thesearelistedinroughorderofthetempoof
requiredmaintenanceandoperationalactivitiesforthoseassets.Thoseassesrequiringthemost
attentionappeartowardthetopofthelist.

8.1 General Requirements


Thefollowingrequirementsshallgovernthedeliveryofalltypesofequipmentandproductsfound
inallCOBiedeliverables.

13

buildingsmartalliance.orgACounciloftheNationalInstituteofBuildingSciences.

20130312COBieGuidePublicv05

25


8.1.1 Project Team Responsibility
Inabsenceofspecifiedregional,national,orclientspecificpropertysets,theprojectteamshall
precoordinatetheidentificationofrequiredequipmentandproductproperties.Documentation
ofthisprecoordinationshallbesubmittedforclientapprovalpriortothestartofdesign.This
submittalshallincludethelistofscheduledequipmentandproductschedulesandtheheadings
expectedtoappearonalldrawingsschedules.Thissubmittalshallbeprovidedforclientapproval.
Thepurposeofthisprecoordinationsubmittalistoeliminatelaterpossiblereworkbytheproject
teamthatmaybeneededtobringCOBiedeliverablesuptothedataqualitystandardsidentifiedin
thisGuide.
Theclientmayexplicitlyrequirethattheprojectteamconformtothepropertiesprovidedinthis
Guide.Thesepropertieswereselectedfromdesignschedulesfoundinstandarddesignsofseveral
UnitedStatesfederalgovernmentagencies.Thatinformationwascollated,normalizedto
eliminateduplicationandresolvesynonyms,andconsistentlyorganizedinthetablesprovidedin
thissection.UnitsforeachAttributehavealsobeenidentified.Theefforttakentoresolvesuch
issuesinthisGuideisexpectedtosavetheprojectteamasignificantamountofeffortuntilsuch
timeasregional,national,orclientspecificrequirementsarecompleted.
ThefirstcheckofCOBiedataqualityconductedbytheclientshallbeareviewofallscheduled
equipmentandproducts.Iftherearediscrepancies,theclientshallrejecttheCOBiedeliverable
andholdretainageuntilsuchtimeastheCOBiequalitystandardsaremet.Theclientsretainage
oftheCOBiedeliverableshallbebasedonthetimerequiredtomanuallydocumentallscheduled
assets.
8.1.2 Unique Component Name and Type Name
Allequipmentschedulesthatidentifyindividualcomponentsshallbeginwiththeattributeslisted
below.TheassetsnameComponent.nameandassettypenameComponent.Typeprovided
inalldesignschedulesshallbeuniqueacrossallclassesofasset.

Name
Type

Adefaultnamingschemeforschedulesthatidentifyindividualcomponentsandthosewhichonly
identifyequipmentorproducttypeswasprovidedpreviouslyinthisGuide.
8.1.3 NonSubstantive Attributes
AttributesprovidedinCOBiedeliverablesshallberestrictedtothosethatprovideinformation
aboutthespecificationoroperationofthemanagedassetandnotinformationpertainingtothe
internalconfigurationofthesoftwaresystemoroutputformatsprovidedbytheimplementing
softwaresystems.

20130312COBieGuidePublicv05

26


8.1.4 Type versus Component Attributes
AttributesincommonacrossagivenequipmentorproductTypeshallbeassociatedwiththe
COBie.Typerecord.AttributesuniquetoaspecificComponentmaybeassociatedwiththe
COBie.Componentrecord.
8.1.5 Specification Reference
AttheConstructionDocumentsdeliverableandbeyondallCOBie.Typerecordsshallbeidentified
withthespecificationsectionthatreferencestheirrequirements.Thisshallbeaccomplishedby
theCOBie.TypeAttributecalledSpecificationSection.
8.1.6 Electric al Properties
Allequipmentschedulesthatidentifyindividualcomponentsthatuseelectricalpowershallhave
thenextthreeheadingsoftheirschedulescontainthefollowingassetinformation.This
informationshallbeincludedintheCOBiefileasattributesontheassetType.

Current
Voltage
Frequency

8.1.7 Placement
Allmanagedassetsshallbeidentifiedbyitsplacementwithinthefacility.Attheconstruction
DocumentsDesignstagethisrequirementwillapplytoallCOBie.Componentrecordsusingthe
COBie.AttributeSpatialPlacement.AttheBeneficialOccupancyandAsBuiltstagesof
construction,thisrequirementwillapplytobothscheduledandtaggedassets.Thevaluesthat
canbeusedfortheSpatialPlacementattributeshallinclude,butnotbelimitedto,thefollowing
list.

AboveCeiling
InSpace
InWall
OnRoof
OnSite
UnderFloor

8.1.8 Construction Documents Deliverable Basis of Design


ThesepropertiesshallbeaddedtotheCOBie.Attributeworksheetandassociatedwithevery
COBie.TyperecordattheConstructionDocuments(100%Design)Deliverable.Thefield
BasisOfDesignNotesreproducesnotesassociatedwitheachtypeofscheduledassetsasfound
ondesigndrawings.

BasisOfDesignManufacturer
BasisOfDesignModelNumber
BasisOfDesignNotes

20130312COBieGuidePublicv05

27


8.1.9 Occupancy and AsBuilt Deliverables AsInstalled Common Properties
TheBeneficialOccupancyandAsBuiltCOBiedeliverablesshallupdatethefollowingadditional
attributesofalldesignedassetsbasedonthepropertiesofinstalledproducts.
COBieWorksheet

COBieField

Type

Manufacturer

Type

ModelNumber

Type

WarrantyGuarantorLabor

Type

WarrantyDurationLabor

Type

WarrantyDurationUnit

Attribute(ofType)

ApprovedDeviations

Component

SerialNumber

Component

InstallationDate

Component

TagNumber

8.1.10 Occupancy and AsBuilt Deliverable AsInstalled Electrical Circuit


Eachscheduled/namedassetthatuseselectricity,shallinadditiontootherrequiredproperties,
havethefollowingtwopropertiesthatidentifytheelectricalcircuitrequiredtodeenergizethat
equipment.ThesepropertieswillbeaddedtotheCOBie.AttributeworksheetfortheBeneficial
OccupancyandAsBuiltCOBiedeliverables.

ElecticalPanelName
ElectricalPanelCircut

8.1.11 Occupancy and AsBuilt Deliverables AsInstalled Systems of Components


Eachscheduled/namedsystemassetshallbeidentifiedintheCOBie.Systemworksheettoidentify
thegroupingofdifferentcomponentsintosystemswithinthefacility.
8.1.12 Occupancy and AsBuilt Deliverables AsInstalled Assemblies of Components
Engineeredtoorderproductsareassembledofindividualproductsthathavedifferent
preventativemaintenanceschedulesandreplacementpartsrequirements.Tocorrectlyinclude
theseinCOBietheremustbeaCOBie.TypeandCOBie.Componentforboththeassemblyandfor
theindividualpiecesofequipmentwithintheoverallassembly.BODandAsBuiltDeliverables
RequiredTypeProperties
TheBeneficialOccupancyandAsBuiltCOBiedeliverablesshallupdatetheattributesofall
scheduledassetTypestomatchthosepropertiesoftheactuallyselectedproductTypes.
8.1.13 Occupancy and AsBuilt Deliverable AsInstalled Asset Type Properties
TheBeneficialOccupancyandAsBuiltCOBiedeliverablesshallupdatetheattributesofall
designedassetstomatchthosepropertiesofinstalledproducts.

20130312COBieGuidePublicv05

28

8.2 Required HVAC System Assets


8.2.1 Chiller
ThefollowingminimumsetofinformationshallbeprovidedinConstructionDocumentsstage
designdeliverablescheduleandreflectedintheCDStageCOBieDeliverableandsubsequent
constructiondeliverables.
Table4DesignMinimumChillerScheduleHeadings

Heading
Name
Type
SpecificationSection
Location
Current
Voltage
Frequency
Power
Capacity
WaterFlow
AmbientTemp
PressureDrop
EnteringWaterTemp
LeavingWaterTemp
MotorController
UnloadingSteps
ChillerMedia
ChillerType
RefrigerantType
EnergyEfficiencyRatio(EER)
IntegratedPartLoadValue(IPLV)
HeatReclaim
SpatialPlacement
BasisOfDesignManufacturer
BasisOfDesignModelNumber
BasisOfDesignNotes

TypicalUnit
ChillerTypeXXSpace#01
ChillerTypeXX
(asidentifiedinclientscontract)
(Space.Name)
Amps
Volts
Hz
kW
kW
m3/hr
C
kPa
C
C

Btu/hrtokW

(fromapprovedlistofplacementtypes)
(Iffoundondrawingschedules)
(Iffoundondrawingschedules)
(Iffoundondrawingschedules)

Constructiondeliverableswillbeupdatedtoreflectinstalledequipmentandotherinformation
describedintheGeneralRequirementsSection.Inaddition,theBeneficialOccupancyandAsBuilt
InDeliverablesshallprovidethefollowingadditionalattributes:

ElecticalPanelName
ElectricalPanelCircut

20130312COBieGuidePublicv05

29


8.2.2 Boiler
ThefollowingminimumsetofinformationshallbeprovidedinConstructionDocumentsstage
designdeliverablescheduleandreflectedintheCDStageCOBieDeliverableandsubsequent
constructiondeliverables.
Table5DesignMinimumBoilerScheduleHeadings

Heading
Name
Type
SpecificationSection
Location
Current
Voltage
Frequency
InputPower
OutputPower
WaterFlow
EnteringWaterTemp
LeavingWaterTemp
VentDiameter
Passes
PressureDrop
EnergySource
FuelType
OutputMedia
SpatialPlacement
BasisOfDesignManufacturer
BasisOfDesignModelNumber
BasisOfDesignNotes

TypicalUnit
BoilerTypeXXSpace#01
BoilerTypeXX
(asidentifiedinclientscontract)
(SpaceName)
Amps
Volts
Hz
kW
kW
m3/hr
C
C
mm

kPa

(fromapprovedlistofplacementtypes)
(Iffoundondrawingschedules)
(Iffoundondrawingschedules)
(Iffoundondrawingschedules)

Constructiondeliverableswillbeupdatedtoreflectinstalledequipmentandotherinformation
describedintheGeneralRequirementsSection.Inaddition,theBeneficialOccupancyandAsBuilt
Deliverablesshallprovidethefollowingadditionalattributes:

ElecticalPanelName
ElectricalPanelCircut

20130312COBieGuidePublicv05

30


8.2.3 Air Handling Units
ThefollowingminimumsetofinformationshallbeprovidedinConstructionDocumentsstage
designdeliverablescheduleandreflectedintheCDStageCOBieDeliverableandsubsequent
constructiondeliverables.
Table6DesignMinimumAirHandlingUnitScheduleHeadings

Heading
Name
Type
SpecificationSection
Location
Current
Voltage
Frequency
FanFlowMaximum
FanFlowNominal
FanOutsideFlow
FanExtPressureDrop
FanMotorPower
FanSpeed
FanSoundLevel
CoilFlow
CoilVelocity
CoilCapacity
EnteringAirTempDB
EnteringAirTempWB
LeavingAirTempDB
LeavingAirTempWB
EnteringWaterTemp
LeavingWaterTemp
ChilledWaterRate
RunoutInletSize
RunoutOutletSize
CoilAirPressureDrop
CoilWaterPressureDrop
SpatialPlacement
BasisOfDesignManufacturer
BasisOfDesignModelNumber
BasisOfDesignNotes

TypicalUnit
AHUTypeXXSpace#01
AHUTypeXX
(asidentifiedinclientscontract)
(SpaceName)
Amps
Volts
Hz
L/s
L/s
L/s
kPa
kW
RPM
dB
L/s
m/min
W
C
C
C
C
C
C
L/s
mm
mm
Pa
kPa
(fromapprovedlistofplacementtypes)
(Iffoundondrawingschedules)
(Iffoundondrawingschedules)
(Iffoundondrawingschedules)

Constructiondeliverableswillbeupdatedtoreflectinstalledequipmentandotherinformation
describedintheGeneralRequirementsSection.Inaddition,theBeneficialOccupancyandAsBuilt
Deliverablesshallprovidethefollowingadditionalattributes:

ElecticalPanelName
ElectricalPanelCircut

20130312COBieGuidePublicv05

31


8.2.4 Fan coil units
ThefollowingminimumsetofinformationshallbeprovidedinConstructionDocumentsstage
designdeliverablescheduleandreflectedintheCDStageCOBieDeliverableandsubsequent
constructiondeliverables.
Table7DesignMinimumFanCoilUnitScheduleHeadings

Heading
Name
Type
SpecificationSection
Location
Current
Voltage
Frequency
AirFlow
FanSpeed
ExitStaticPressure
EnteringAirTempDB
EnteringAirTempWB
LeavingAirTempDB
LeavingAirTempWB
TotalCapacity
SensibleCapacity
EnteringWaterTemp
LeavingWaterTemp
ChilledWaterFlow
CoolingCoilDeltaP
CoolingRows
FanMotorPower
Phase
CabinetType
SpatialPlacement
BasisOfDesignManufacturer
BasisOfDesignModelNumber
BasisOfDesignNotes

TypicalUnit
FanCoilTypeXXSpace#01
FanCoilTypeXX
(asidentifiedinclientscontract)
(SpaceName)
Amps
Volts
Hz
L/s

Pa
C
C
C
C
kW
kW
C
C
L/s
kPa

kW

(fromapprovedlistofplacementtypes)
(Iffoundondrawingschedules)
(Iffoundondrawingschedules)
(Iffoundondrawingschedules)

Constructiondeliverableswillbeupdatedtoreflectinstalledequipmentandotherinformation
describedintheGeneralRequirementsSection.Inaddition,theBeneficialOccupancyandAsBuilt
Deliverablesshallprovidethefollowingadditionalattributes:

ElecticalPanelName
ElectricalPanelCircut

20130312COBieGuidePublicv05

32


8.2.5 Filters
ThefollowingminimumsetofinformationshallbeprovidedinConstructionDocumentsstage
designdeliverablescheduleandreflectedintheCDStageCOBieDeliverableandsubsequent
constructiondeliverables.
AirFlowmaximumwasincludedinthistablesinceitwasfoundinanoteassociatedwitheach
filter.Theefficiencyratingidentifiedinthetableistoogeneralandshouldbeclarifiedaseither
NominalCountedEfficiencyorNominalWeightedEfficiency.
Notethattheexpectednamingofthiscomponentshouldreflectthetypeandcomponents
specificuseinasystem.
Table8DesignMinimumFilterScheduleHeadings

Heading

TypicalUnit
HVACFilterTypeXXSpace#01
HVACFilterTypeXX
(asidentifiedinclientscontract)
(SpaceName)
mm
mm
mm

Name
Type
SpecificationSection
Location
Length
Width
Height
AirFlowMaximum
AirFlowNominal
NominalPressureDrop
EfficiencyRating
ResidenceTime
SpatialPlacement
BasisOfDesignManufacturer
BasisOfDesignModelNumber
BasisOfDesignNotes

L/s
L/s
Pa
%
Sec
(fromapprovedlistofplacementtypes)
(Iffoundondrawingschedules)
(Iffoundondrawingschedules)
(Iffoundondrawingschedules)

Constructiondeliverableswillbeupdatedtoreflectinstalledequipmentandotherinformation
describedintheGeneralRequirementsSection.

20130312COBieGuidePublicv05

33


8.2.6 Pumps
ThefollowingminimumsetofinformationshallbeprovidedinConstructionDocumentsstage
designdeliverablescheduleandreflectedintheCDStageCOBieDeliverableandsubsequent
constructiondeliverables.
Notethattheexpectednamingofthiscomponentshouldreflectthetypeandcomponents
specificuseinasystem.
Table9DesignMinimumPumpScheduleHeadings

Heading
Name
Type
SpecificationSection
Location
Current
Voltage
Frequency
RatedFlow
ChurnPressure
ControllerType
SpatialPlacement
BasisOfDesignManufacturer
BasisOfDesignModelNumber
BasisOfDesignNotes

TypicalUnit
HVACPumpTypeXXSpace#01
HVACPumpTypeXX
(asidentifiedinclientscontract)
(SpaceName)
Amps
Volts
Hz
L/s
kPa

(fromapprovedlistofplacementtypes)
(Iffoundondrawingschedules)
(Iffoundondrawingschedules)
(Iffoundondrawingschedules)

Constructiondeliverableswillbeupdatedtoreflectinstalledequipmentandotherinformation
describedintheGeneralRequirementsSection.Inaddition,theBeneficialOccupancyandAsBuilt
Deliverablesshallprovidethefollowingadditionalattributes:

ElecticalPanelName
ElectricalPanelCircut

20130312COBieGuidePublicv05

34


8.2.7 Fans
ThefollowingminimumsetofinformationshallbeprovidedinConstructionDocumentsstage
designdeliverablescheduleandreflectedintheCDStageCOBieDeliverableandsubsequent
constructiondeliverables.
Notethattheexpectednamingofthiscomponentshouldreflectthetypeandcomponents
specificuseinasystem.
Table10DesignMinimumFanScheduleHeadings

Heading
Name
Type
SpecificationSection
Location
Current
Voltage
Frequency
Service
FlowRate
Pressure
ControlType
Interlock
SpatialPlacement
BasisOfDesignManufacturer
BasisOfDesignModelNumber
BasisOfDesignNotes

TypicalUnit
FanTypeXXSpace#01
FanTypeXX
(asidentifiedinclientscontract)
(SpaceName)
Amps
Volts
Hz

L/s
Pa

(fromapprovedlistofplacementtypes)
(Iffoundondrawingschedules)
(Iffoundondrawingschedules)
(Iffoundondrawingschedules)

Constructiondeliverableswillbeupdatedtoreflectinstalledequipmentandotherinformation
describedintheGeneralRequirementsSection.Inaddition,theBeneficialOccupancyandAsBuilt
Deliverablesshallprovidethefollowingadditionalattributes:

ElecticalPanelName
ElectricalPanelCircut

20130312COBieGuidePublicv05

35


8.2.8 Motors
ThefollowingminimumsetofinformationshallbeprovidedinConstructionDocumentsstage
designdeliverablescheduleandreflectedintheCDStageCOBieDeliverableandsubsequent
constructiondeliverables.
Notethattheexpectednamingofthiscomponentshouldreflectthetypeandcomponents
specificuseinasystem.
Table11DesignMinimumMotorScheduleHeadings

Heading
Name
Type
SpecificationSection
Location
Current
Voltage
Frequency
Power
Phase
Efficiency
Drive
DriveControlType
SpatialPlacement
BasisOfDesignManufacturer
BasisOfDesignModelNumber
BasisOfDesignNotes

TypicalUnit
MotorTypeXXSpace#01
MotorTypeXX
(asidentifiedinclientscontract)
(SpaceName)
Amps
Volts
Hz
kW

(fromapprovedlistofplacementtypes)
(Iffoundondrawingschedules)
(Iffoundondrawingschedules)
(Iffoundondrawingschedules)

Constructiondeliverableswillbeupdatedtoreflectinstalledequipmentandotherinformation
describedintheGeneralRequirementsSection.Inaddition,theBeneficialOccupancyandAsBuilt
Deliverablesshallprovidethefollowingadditionalattributes:

ElecticalPanelName
ElectricalPanelCircut

20130312COBieGuidePublicv05

36


8.2.9 Compressors
ThefollowingminimumsetofinformationshallbeprovidedinConstructionDocumentsstage
designdeliverablescheduleandreflectedintheCDStageCOBieDeliverableandsubsequent
constructiondeliverables.
Notethattheexpectednamingofthiscomponentshouldreflectthetypeandcomponents
specificuseinasystem.
Table12DesignMinimumCompressorScheduleHeadings

Heading
Name
Type
SpecificationSection
Location
Current
Voltage
Frequency
RefrigerantType
Capacity
Speed
SpatialPlacement
BasisOfDesignManufacturer
BasisOfDesignModelNumber
BasisOfDesignNotes

TypicalUnit
CompressorTypeXXSpace#01
CompressorTypeXX
(asidentifiedinclientscontract)
(SpaceName)
Amps
Volts
Hz

%
RPM
(fromapprovedlistofplacementtypes)
(Iffoundondrawingschedules)
(Iffoundondrawingschedules)
(Iffoundondrawingschedules)

Constructiondeliverableswillbeupdatedtoreflectinstalledequipmentandotherinformation
describedintheGeneralRequirementsSection.Inaddition,theBeneficialOccupancyandAsBuilt
Deliverablesshallprovidethefollowingadditionalattributes:

ElecticalPanelName
ElectricalPanelCircut

20130312COBieGuidePublicv05

37


8.2.10 Variable Air Volume boxes
ThefollowingminimumsetofinformationshallbeprovidedinConstructionDocumentsstage
designdeliverablescheduleandreflectedintheCDStageCOBieDeliverableandsubsequent
constructiondeliverables.
Table13DesignMinimumVAVBoxScheduleHeadings

Heading
Name
Type
SpecificationSection
Location
Current
Voltage
Frequency
InletSize
AirFlowMinimum
AirFlowMaximum
PressureDrop
NCLevelDischarge
NCLevelRadiated
SpatialPlacement
BasisOfDesignManufacturer
BasisOfDesignModelNumber
BasisOfDesignNotes

TypicalUnit
VAVTypeXXSpace#01
VAVTypeXX
(asidentifiedinclientscontract)
(SpaceName)
Amps
Volts
Hz
mm
L/s
L/s
Pa
dB
dB
(fromapprovedlistofplacementtypes)
(Iffoundondrawingschedules)
(Iffoundondrawingschedules)
(Iffoundondrawingschedules)

Constructiondeliverableswillbeupdatedtoreflectinstalledequipmentandotherinformation
describedintheGeneralRequirementsSection.Inaddition,theBeneficialOccupancyandAsBuilt
Deliverablesshallprovidethefollowingadditionalattributes:

ElecticalPanelName
ElectricalPanelCircut

8.2.11 Valves
SchedulesforthistypeofdevicearenotrequiredforCOBieDesignDeliverables,butwillbe
requiredforCOBieBeneficialOccupancyandAsBuiltModels.Thesescheduleswillconsistofthe
followingparts.

OneCOBie.Typerecordforeachtypeofcomponent
OneCOBie.Componentforeachindividualcomponent,identifyingthecomponentsspace
NameofCOBie.Componentmustbeuniquelycreatedusingthefollowingrule
o Valve&COBie.SpaceName&&ItemCountinSpecificSpace
TwoCOBie.Attributerecordforeachcomponent
o OperatingPositionNormal(open/closed)
o OperatingPositionEmergency(open/closed)
OneCOBie.Connectionrecordforeachcomponentwhoseflowiscontrolledbythisdevice.

20130312COBieGuidePublicv05

38

8.2.12 Traps
SchedulesforthistypeofdevicearenotrequiredforCOBieDesignDeliverables,butwillbe
requiredforCOBieBeneficialOccupancyandAsBuiltModels.Thesescheduleswillconsistofthe
followingparts.

OneCOBie.Typerecordforeachtypeofcomponent
OneCOBie.Componentforeachindividualcomponent,identifyingthecomponentsspace
NameofCOBie.Componentmustbeuniquelycreatedusingthefollowingrule
o Trap&COBie.SpaceName&&ItemCountinSpecificSpace
PMSchedulesforthisCOBie.Typeshallidentifythefrequencyofinspection/maintenance
requiredforthistypeofcomponent.

8.2.13 Strainer
SchedulesforthistypeofdevicearenotrequiredforCOBieDesignDeliverables,butwillbe
requiredforCOBieBeneficialOccupancyandAsBuiltModels.Thesescheduleswillconsistofthe
followingparts.

OneCOBie.Typerecordforeachtypeofcomponent
OneCOBie.Componentforeachindividualcomponent,identifyingthecomponentsspace
NameofCOBie.Componentmustbeuniquelycreatedusingthefollowingrule
o Strainer&COBie.SpaceName&&ItemCountinSpecificSpace
PMSchedulesforthisCOBie.Typeshallidentifythefrequencyofinspection/maintenance
requiredforthistypeofcomponent.

20130312COBieGuidePublicv05

39

8.3 Required Plumbing System Assets


8.3.1 Water treatment Assemblies
WatertreatmentsystemsareanAssemblyofthreeprimaryComponenttypesthatshallbe
includedinCOBiedeliverables.ThesethreeTypesare

Pretreatmentequipment
Potablewatertreatmentequipment
Pressurevessels

IfawatertreatmentassemblyisaninternalpartofagivenfacilitythenthereshallbeoneType
objectforWaterTreatment.

ThefollowingminimumsetofinformationshallbeprovidedinConstructionDocumentsstage
designdeliverablescheduleandreflectedintheCDStageCOBieDeliverableandsubsequent
constructiondeliverables.
Table14DesignMinimumWaterTreatmentAssembliesScheduleHeadings

Heading

TypicalUnit

Name

WaterTreatmentAssemblyTypeXXSpace#01

Type

WaterTreatmentAssemblyTypeXX

SpecificationSection
Location

(asidentifiedinclientscontract)

SystemTypes

WaterSoftener

DesinfectionType

RejectionRatio

Capacity

cu.meters/day

SpatialPlacement
BasisOfDesignManufacturer

(fromapprovedlistofplacementtypes)
(Iffoundondrawingschedules)

BasisOfDesignModelNumber

(Iffoundondrawingschedules)

BasisOfDesignNotes

(Iffoundondrawingschedules)

(SpaceName)

Constructiondeliverableswillbeupdatedtoreflectinstalledequipmentandotherinformation
describedintheGeneralRequirementsSection.

20130312COBieGuidePublicv05

40

8.3.2 Valves
SchedulesforthistypeofdevicearenotrequiredforCOBieDesignDeliverables,butwillbe
requiredforCOBieBeneficialOccupancyandAsBuiltModels.Thesescheduleswillconsistofthe
followingparts.

OneCOBie.Typerecordforeachtypeofcomponent
OneCOBie.Componentforeachindividualcomponent,identifyingthecomponentsspace
NameofCOBie.Componentmustbeuniquelycreatedusingthefollowingrule
o Valve&COBie.SpaceName&&ItemCountinSpecificSpace
TwoCOBie.Attributerecordforeachcomponent
o OperatingPositionNormal(open/closed)
o OperatingPositionEmergency(open/closed)
OneCOBie.Connectionrecordforeachcomponentwhoseflowiscontrolledbythisdevice.

8.3.3 Plumbing Fixtures


Whiletherearemanydifferenttypesofplumbingfixtures,theycommonlyusethesametypeof
schedule,sinceeachtypeoffixtureperformsasimilarfunction.Thefollowingminimumsetof
informationshallbeprovidedinConstructionDocumentsstagedesigndeliverablescheduleand
reflectedintheCDStageCOBieDeliverableandsubsequentconstructiondeliverables.
Table15DesignMinimumPlumbingFixtureScheduleHeadings

Heading
Name
Type
SpecificationSection
Location
Waste
Vent
ColdWater
HotWater
SanitaryFixtureWater
MaximumFlowRate
SpatialPlacement
BasisOfDesignManufacturer
BasisOfDesignModelNumber
BasisOfDesignNotes

TypicalUnit
PlumbingFixtureTypeXXSpace#01
PlumbingFixtureTypeXX
(asidentifiedinclientscontract)
(SpaceName)
WSFU
WSFU
WSFU
WSFU
liter/flush
L/min
(fromapprovedlistofplacementtypes)
(Iffoundondrawingschedules)
(Iffoundondrawingschedules)
(Iffoundondrawingschedules)

Constructiondeliverableswillbeupdatedtoreflectinstalledequipmentandotherinformation
describedintheGeneralRequirementsSection.

20130312COBieGuidePublicv05

41

8.4 Required Fire Suppression System Assets


8.4.1 Pumps
ThefollowingminimumsetofinformationshallbeprovidedinConstructionDocumentsstage
designdeliverablescheduleandreflectedintheCDStageCOBieDeliverableandsubsequent
constructiondeliverables.
Notethattheexpectednamingofthiscomponentshouldreflectthetypeandcomponents
specificuseinasystem.
Table16DesignMinimumPumpScheduleHeadings

Heading
Name
Type
SpecificationSection
Location
Current
Voltage
Frequency
RatedFlow
ChurnPressure
ControllerType
SpatialPlacement
BasisOfDesignManufacturer
BasisOfDesignModelNumber
BasisOfDesignNotes

TypicalUnit
FireSurpressionPumpTypeXXSpace#01
FireSurpressionPumpTypeXX
(asidentifiedinclientscontract)
(SpaceName)
Amps
Volts
Hz
L/s
kPa

(fromapprovedlistofplacementtypes)
(Iffoundondrawingschedules)
(Iffoundondrawingschedules)
(Iffoundondrawingschedules)

Constructiondeliverableswillbeupdatedtoreflectinstalledequipmentandotherinformation
describedintheGeneralRequirementsSection.Inaddition,theBeneficialOccupancyandAsBuilt
Deliverablesshallprovidethefollowingadditionalattributes:

ElecticalPanelName
ElectricalPanelCircut

20130312COBieGuidePublicv05

42


8.4.2 Valves
SchedulesforthistypeofdevicearenotrequiredforCOBieDesignDeliverables,butwillbe
requiredforCOBieBeneficialOccupancyandAsBuiltModels.Thesescheduleswillconsistofthe
followingparts.

OneCOBie.Typerecordforeachtypeofcomponent
OneCOBie.Componentforeachindividualcomponent,identifyingthecomponentsspace
NameofCOBie.Componentmustbeuniquelycreatedusingthefollowingrule
o Valve&COBie.SpaceName&&ItemCountinSpecificSpace
TwoCOBie.Attributerecordforeachcomponent
o OperatingPositionNormal(open/closed)
o OperatingPositionEmergency(open/closed)
OneCOBie.Connectionrecordforeachcomponentwhoseflowiscontrolledbythisdevice.

8.4.3 Sprinkler heads


Designschedulesforthistypeofdeviceondesigndrawingsonlyidentifyeachtypeofcomponent.
Thelocationofeachcomponentistypicallyidentifiedbydrawingnote.AsaresultDesign
DeliverablesforthistypeofdeviceshallbecomprisedofthefollowingCOBieinformation:

OneCOBie.Typerecordforeachtypeofcomponent
OneCOBie.AttributerecordforeachType
o HeadType
OneCOBie.Componentforeachindividualcomponent,identifyingthecomponentsspace.

AtBeneficialOccupancyandAsBuiltdeliverables,designschedulesshallbeupdatedasnoted
below.

OneCOBie.Typerecordforeachtypeofcomponent
TwoCOBie.AttributerecordforeachType
o HeadType
o ThreadSize
OneCOBie.Componentforeachindividualcomponent,identifyingthecomponentsspace
NameofCOBie.Componentmustbeuniquelycreatedusingthefollowingrule
o SprinklerHead&COBie.SpaceName&&ItemCountinSpecificSpace

20130312COBieGuidePublicv05

43


8.4.4 Fire extinguishers
ThefollowingminimumsetofinformationshallbeprovidedinConstructionDocumentsstage
designdeliverablescheduleandreflectedintheCDStageCOBieDeliverable.
Table17ConstructionMinimumFireExtinguisherScheduleHeadings

Heading

TypicalUnit

Name

FireExtinguisherTypeXXSpace#01

Type

FireExtinguisherTypeXX

SpecificationSection
Location

(asidentifiedinclientscontract)

Capacity

Kg

(SpaceName)

Rating
SpatialPlacement
BasisOfDesignManufacturer

(fromapprovedlistofplacementtypes)
(Iffoundondrawingschedules)

BasisOfDesignModelNumber

(Iffoundondrawingschedules)

BasisOfDesignNotes

(Iffoundondrawingschedules)

Constructiondeliverableswillbeupdatedtoreflectinstalledequipmentandotherinformation
describedintheGeneralRequirementsSection.

8.5 Required Electrical System Assets


8.5.1 Light fixtures
Designschedulesforthistypeofdeviceondesigndrawingsonlyidentifyeachtypeofcomponent.
Thelocationofeachcomponentistypicallyidentifiedbydrawingnote.Thefollowingminimum
setofinformationshallbeprovidedinConstructionDocumentsstagedesigndeliverableschedule
andreflectedintheCDStageCOBieDeliverableandsubsequentconstructiondeliverables.
Notethattheexpectednamingofthiscomponentshouldreflectthetypeandcomponents
specificuseinasystem.
Table18DesignMinimumLightFixtureTypeScheduleHeadings

Heading

TypicalUnit

Name

LightFixtureTypeXXSpace#01

Type

LightFixtureTypeXX

SpecificationSection
Location

(asidentifiedinclientscontract)

Current

Amps

Voltage

Volts

Frequency

Hz

LensType

LampType

Mounting

20130312COBieGuidePublicv05

(SpaceName)

44


LampType

LampCount

Each

LampPower

Function

LightPath

SpatialPlacement
BasisOfDesignManufacturer

(fromapprovedlistofplacementtypes)
(Iffoundondrawingschedules)

BasisOfDesignModelNumber

(Iffoundondrawingschedules)

BasisOfDesignNotes

(Iffoundondrawingschedules)

AtBeneficialOccupancyandAsBuiltdeliverables,designschedulesshallbeupdatedasnoted
below.

OneCOBie.Componentforeachindividualcomponent,identifyingthecomponentsspace
TwoCOBie.Attributerecordforeachindividualcomponent
o ElecticalPanelName
o ElectricalPanelCircut
NameofCOBie.Componentmustbeuniquelycreatedusingthefollowingrule
o Outlet&COBie.SpaceName&&ItemCountinSpecificSpace

8.5.2 Outlets
Designschedulesforthistypeofdeviceondesigndrawingsonlyidentifyeachtypeofcomponent.
Thelocationofeachcomponentistypicallyidentifiedbydrawingnote.AsaresultDesign
DeliverablesforthistypeofdeviceshallbecomprisedofthefollowingCOBieinformation:

OneCOBie.Typerecordforeachtypeofcomponent
ThreeCOBie.AttributerecordforeachType
o Voltage
o Current
o Frequency
OneCOBie.Componentforeachindividualcomponent,identifyingthecomponentsspace
TwoCOBie.Attributerecordforeachindividualcomponent
o ElecticalPanelName
o ElectricalPanelCircut

AtBeneficialOccupancyandAsBuiltdeliverables,designschedulesshallbeupdatedasnoted
below.

OneCOBie.Typerecordforeachtypeofcomponent
ThreeCOBie.AttributerecordforeachType
o Voltage

20130312COBieGuidePublicv05

45

o Current
o Frequency
OneCOBie.Componentforeachindividualcomponent,identifyingthecomponentsspace
TwoCOBie.Attributerecordforeachindividualcomponent
o ElecticalPanelName
o ElectricalPanelCircut
NameofCOBie.Componentmustbeuniquelycreatedusingthefollowingrule
o Outlet&COBie.SpaceName&&ItemCountinSpecificSpace

20130312COBieGuidePublicv05

46


8.5.3 Switches
Designschedulesforthistypeofdeviceondesigndrawingsonlyidentifyeachtypeofcomponent.
Thelocationofeachcomponentistypicallyidentifiedbydrawingnote.AsaresultDesign
DeliverablesforthistypeofdeviceshallbecomprisedofthefollowingCOBieinformation:

OneCOBie.Typerecordforeachtypeofcomponent
ThreeCOBie.AttributerecordforeachType
o Voltage
o Current
o Frequency
OneCOBie.Componentforeachindividualcomponent,identifyingthecomponentsspace
TwoCOBie.Attributerecordforeachindividualcomponent
o ElecticalPanelName
o ElectricalPanelCircut

AtBeneficialOccupancyandAsBuiltdeliverables,designschedulesshallbeupdatedas
notedbelow.
OneCOBie.Typerecordforeachtypeofcomponent
TwoCOBie.AttributerecordforeachType
o Voltage
o Current
o Frequency
OneCOBie.Componentforeachindividualcomponent,identifyingthecomponentsspace
TwoCOBie.Attributerecordforeachindividualcomponent
o ElecticalPanelName
o ElectricalPanelCircut

NameofCOBie.Componentmustbeuniquelycreatedusingthefollowingrule
o Switch&COBie.SpaceName&&ItemCountinSpecificSpace
OneCOBie.Connectionrecordforeachfixture,outlet,orequipmentcontrolledbythis
component.

20130312COBieGuidePublicv05

47


8.5.4 Distribution panel
ThefollowingminimumsetofinformationshallbeprovidedinConstructionDocumentsstage
designdeliverablescheduleandreflectedintheCDStageCOBieDeliverableandsubsequent
constructiondeliverables.
Notethattheexpectednamingofthiscomponentshouldreflectthetypeandcomponents
specificuseinasystem.
Table19DesignMinimumDistributionPanelTypeScheduleHeadings

Heading
Name
Type
SpecificationSection
Location
Current
Voltage
Frequency
Phase
NumberofWires
NumberofPoles
MainBreakerMounting
MainBusCurrent
NeutralBus
EquipGroundBus
IsolatedGroundBus
Mounting
AICRating
SpatialPlacement
BasisOfDesignManufacturer
BasisOfDesignModelNumber
BasisOfDesignNotes

TypicalUnit
DistributionPanelTypeXXSpace#01
DistributionPanelTypeXX
(asidentifiedinclientscontract)
(SpaceName)
Amps
Volts
Hz

Amps

(fromapprovedlistofplacementtypes)
(Iffoundondrawingschedules)
(Iffoundondrawingschedules)
(Iffoundondrawingschedules)

Constructiondeliverableswillbeupdatedtoreflectinstalledequipmentandotherinformation
describedintheGeneralRequirementsSection.Inaddition,theBeneficialOccupancyandAsBuilt
Deliverablesshallprovidethefollowingadditionalattributes:

ElecticalPanelName
ElectricalPanelCircut

Notethatthefullspecificationoftheelectricalsystemmaybedevelopedthroughuseofthe
COBie.ConnectionandCOBie.Assemblyworksheets.Unlessspecifiedbyclient,useofthese
worksheetsisnotrequiredtomeetthegenericCOBieGuide.

20130312COBieGuidePublicv05

48


8.5.5 Switchgear
ThefollowingminimumsetofinformationshallbeprovidedinConstructionDocumentsstage
designdeliverablescheduleandreflectedintheCDStageCOBieDeliverableandsubsequent
constructiondeliverables.
Notethattheexpectednamingofthiscomponentshouldreflectthetypeandcomponents
specificuseinasystem.
Table20DesignMinimumSwitchgearTypeScheduleHeadings

Heading
Name
Type
SpecificationSection
Location
Current
Voltage
Frequency
OperatingWeight
TypeofSupport
HorizontalBusCurrent
VerticalBusCurrent
ShortCircuitInterruptingRating
EnclosureRating
MinimumBusBracing
SpatialPlacement
BasisOfDesignManufacturer
BasisOfDesignModelNumber
BasisOfDesignNotes

TypicalUnit
SwitchgearTypeXXSpace#01
SwitchgearTypeXX
(asidentifiedinclientscontract)
(SpaceName)
Amps
Volts
Hz
Kg

Amps
Amps
KAIC

KAIC
(fromapprovedlistofplacementtypes)
(Iffoundondrawingschedules)
(Iffoundondrawingschedules)
(Iffoundondrawingschedules)

Constructiondeliverableswillbeupdatedtoreflectinstalledequipmentandotherinformation
describedintheGeneralRequirementsSection.Inaddition,theBeneficialOccupancyandAsBuilt
Deliverablesshallprovidethefollowingadditionalattributes:

ElecticalPanelName
ElectricalPanelCircut

20130312COBieGuidePublicv05

49


8.5.6 Generator
ThefollowingminimumsetofinformationshallbeprovidedinConstructionDocumentsstage
designdeliverablescheduleandreflectedintheCDStageCOBieDeliverableandsubsequent
constructiondeliverables.
Notethattheexpectednamingofthiscomponentshouldreflectthetypeandcomponents
specificuseinasystem.
Table21DesignMinimumGeneratorTypeScheduleHeadings

Heading
Name
Type
SpecificationSection
Location
Current
Voltage
Frequency
OperatingWeight
TypeofSupport
MaximumPowerOutput
FuelType
SpatialPlacement
BasisOfDesignManufacturer
BasisOfDesignModelNumber
BasisOfDesignNotes

TypicalUnit
GeneratorTypeXXSpace#01
GeneratorTypeXX
(asidentifiedinclientscontract)
(SpaceName)
Amps
Volts
Hz
Kg

kW

(fromapprovedlistofplacementtypes)
(Iffoundondrawingschedules)
(Iffoundondrawingschedules)
(Iffoundondrawingschedules)

Constructiondeliverableswillbeupdatedtoreflectinstalledequipmentandotherinformation
describedintheGeneralRequirementsSection.Inaddition,theBeneficialOccupancyandAsBuilt
Deliverablesshallprovidethefollowingadditionalattributes:

ElecticalPanelName
ElectricalPanelCircut

20130312COBieGuidePublicv05

50

8.6 Required Control System Assets


8.6.1 Sensors
ThefollowingminimumsetofinformationshallbeprovidedinConstructionDocumentsstage
designdeliverablescheduleandreflectedintheCDStageCOBieDeliverableandsubsequent
constructiondeliverables.
Notethattheexpectednamingofthiscomponentshouldreflectthetypeandcomponents
specificuseinasystem.
Table22DesignMinimumSensorsTypeScheduleHeadings

Heading

TypicalUnit

Name
Type
SpecificationSection
Location
Current
Voltage
Frequency
Mounting
SpatialPlacement
BasisOfDesignManufacturer
BasisOfDesignModelNumber
BasisOfDesignNotes

SensorTypeXXSpace#01
SensorTypeXX
(asidentifiedinclientscontract)
(SpaceName)
Amps
Volts
Hz

(fromapprovedlistofplacementtypes)
(Iffoundondrawingschedules)
(Iffoundondrawingschedules)
(Iffoundondrawingschedules)

Constructiondeliverableswillbeupdatedtoreflectinstalledequipmentandotherinformation
describedintheGeneralRequirementsSection.Inaddition,theBeneficialOccupancyandAsBuilt
Deliverablesshallprovidethefollowingadditionalattributes:

ElecticalPanelName
ElectricalPanelCircut

20130312COBieGuidePublicv05

51

8.6.2 Controllers
ThefollowingminimumsetofinformationshallbeprovidedinConstructionDocumentsstage
designdeliverablescheduleandreflectedintheCDStageCOBieDeliverableandsubsequent
constructiondeliverables..
Notethattheexpectednamingofthiscomponentshouldreflectthetypeandcomponents
specificuseinasystem.
Table23DesignMinimumControllerTypeScheduleHeadings

Heading
Name
Type
SpecificationSection
Location
Current
Voltage
Frequency
Mounting
SpatialPlacement
BasisOfDesignManufacturer
BasisOfDesignModelNumber
BasisOfDesignNotes

TypicalUnit
ControllerTypeXXSpace#01
ControllerTypeXX
(asidentifiedinclientscontract)
(SpaceName)
Amps
Volts
Hz

(fromapprovedlistofplacementtypes)
(Iffoundondrawingschedules)
(Iffoundondrawingschedules)
(Iffoundondrawingschedules)

Constructiondeliverableswillbeupdatedtoreflectinstalledequipmentandotherinformation
describedintheGeneralRequirementsSection.Inaddition,theBeneficialOccupancyandAsBuilt
Deliverablesshallprovidethefollowingadditionalattributes:

ElecticalPanelName
ElectricalPanelCircut

Controllerswillalsobeidentifiedwithonemoreattributetoallowoperatorstodeterminethe
primarycomponentthatiscontrolledbythisdevice.

ControlledDevice

20130312COBieGuidePublicv05

52

8.7 Required Elevator System Assets


8.7.1 Elevator
ThefollowingminimumsetofinformationshallbeprovidedinConstructionDocumentsstage
designdeliverablescheduleandreflectedintheCDStageCOBieDeliverableandsubsequent
constructiondeliverables..
Notethattheexpectednamingofthiscomponentshouldreflectthetypeandcomponents
specificuseinasystem.
Table24DesignMinimumElevatorTypeScheduleHeadings

Heading
Name
Type
SpecificationSection
Location
Current
Voltage
Frequency
Capacity
Speed
SCRHPRating
MGMotorPower
StartingAmps
AcceleratingAmps
Mach.RM
SpatialPlacement
BasisOfDesignManufacturer
BasisOfDesignModelNumber
BasisOfDesignNotes

TypicalUnit
ElevatorTypeXXSpace#01
ElevatorTypeXX
(asidentifiedinclientscontract)
(SpaceName)
Amps
Volts
Hz
Kg
m/s

KW
Amps
Amps
KCal/hr
(fromapprovedlistofplacementtypes)
(Iffoundondrawingschedules)
(Iffoundondrawingschedules)
(Iffoundondrawingschedules)

Constructiondeliverableswillbeupdatedtoreflectinstalledequipmentandotherinformation
describedintheGeneralRequirementsSection.Inaddition,theBeneficialOccupancyandAsBuilt
Deliverablesshallprovidethefollowingadditionalattributes:

ElecticalPanelName
ElectricalPanelCircut

20130312COBieGuidePublicv05

53

8.8 Required Food Service System Assets


8.8.1 Sinks
ThefollowingminimumsetofinformationshallbeprovidedinConstructionDocumentsstage
designdeliverablescheduleandreflectedintheCDStageCOBieDeliverableandsubsequent
constructiondeliverables.
Notethattheexpectednamingofthiscomponentshouldreflectthetypeandcomponents
specificuseinthissystem.
Table25DesignMinimumSinksTypeScheduleHeadings

Heading
Name
Type
SpecificationSection
Location
WaterInlet
Drain
SpatialPlacement
BasisOfDesignManufacturer
BasisOfDesignModelNumber
BasisOfDesignNotes

TypicalUnit
FoodServiceSinkTypeXXSpace#01
FoodServiceSinkTypeXX
(asidentifiedinclientscontract)
(SpaceName)

(fromapprovedlistofplacementtypes)
(Iffoundondrawingschedules)
(Iffoundondrawingschedules)
(Iffoundondrawingschedules)

Constructiondeliverableswillbeupdatedtoreflectinstalledequipmentandotherinformation
describedintheGeneralRequirementsSection.

20130312COBieGuidePublicv05

54


8.8.2 Waste Disposer
ThefollowingminimumsetofinformationshallbeprovidedinConstructionDocumentsstage
designdeliverablescheduleandreflectedintheCDStageCOBieDeliverableandsubsequent
constructiondeliverables.
Notethattheexpectednamingofthiscomponentshouldreflectthetypeandcomponents
specificuseinthissystem.
Table26DesignMinimumWasteDisposerTypeScheduleHeadings

Heading
Name
Type
SpecificationSection
Location
Current
Voltage
Frequency
Power
Connection
WaterInlet
Drain
SpatialPlacement
BasisOfDesignManufacturer
BasisOfDesignModelNumber
BasisOfDesignNotes

TypicalUnit
FoodServiceWasteDisposerTypeXXSpace#01
FoodServiceWasteDisposerTypeXX
(asidentifiedinclientscontract)
(SpaceName)
Amps
Volts
Hz
kW

(fromapprovedlistofplacementtypes)
(Iffoundondrawingschedules)
(Iffoundondrawingschedules)
(Iffoundondrawingschedules)

Constructiondeliverableswillbeupdatedtoreflectinstalledequipmentandotherinformation
describedintheGeneralRequirementsSection.Inaddition,theBeneficialOccupancyandAsBuilt
Deliverablesshallprovidethefollowingadditionalattribute:

ElecticalPanelName
ElectricalPanelCircut

20130312COBieGuidePublicv05

55


8.8.3 Dishwasher
ThefollowingminimumsetofinformationshallbeprovidedinConstructionDocumentsstage
designdeliverablescheduleandreflectedintheCDStageCOBieDeliverableandsubsequent
constructiondeliverables.
Notethattheexpectednamingofthiscomponentshouldreflectthetypeandcomponents
specificuseinthissystem.
Table27DesignMinimumDishwasherTypeScheduleHeadings

Heading
Name
Type
SpecificationSection
Location
Current
Voltage
Frequency
Power
Connection
WaterInlet
Drain
SpatialPlacement
BasisOfDesignManufacturer
BasisOfDesignModelNumber
BasisOfDesignNotes

TypicalUnit
FoodServiceDishwasherTypeXXSpace#01
FoodServiceDishwasherTypeXX
(asidentifiedinclientscontract)
(SpaceName)
Amps
Volts
Hz
kW

(fromapprovedlistofplacementtypes)
(Iffoundondrawingschedules)
(Iffoundondrawingschedules)
(Iffoundondrawingschedules)

Constructiondeliverableswillbeupdatedtoreflectinstalledequipmentandotherinformation
describedintheGeneralRequirementsSection.Inaddition,theBeneficialOccupancyandAsBuilt
Deliverablesshallprovidethefollowingadditionalattributes:

ElecticalPanelName
ElectricalPanelCircut

20130312COBieGuidePublicv05

56


8.8.4 Refrigerator
ThefollowingminimumsetofinformationshallbeprovidedinConstructionDocumentsstage
designdeliverablescheduleandreflectedintheCDStageCOBieDeliverableandsubsequent
constructiondeliverables.
Notethattheexpectednamingofthiscomponentshouldreflectthetypeandcomponents
specificuseinthissystem.
Table28DesignMinimumRefrigeratorTypeScheduleHeadings

Heading
Name
Type
SpecificationSection
Location
Current
Voltage
Frequency
Power
Connection
WaterInlet
Drain
SpatialPlacement
BasisOfDesignManufacturer
BasisOfDesignModelNumber
BasisOfDesignNotes

TypicalUnit
FoodServiceRefrigeratorTypeXXSpace#01
FoodServiceRefrigeratorTypeXX
(asidentifiedinclientscontract)
(SpaceName)
Amps
Volts
Hz
kW

(fromapprovedlistofplacementtypes)
(Iffoundondrawingschedules)
(Iffoundondrawingschedules)
(Iffoundondrawingschedules)

Constructiondeliverableswillbeupdatedtoreflectinstalledequipmentandotherinformation
describedintheGeneralRequirementsSection.Inaddition,theBeneficialOccupancyandAsBuilt
Deliverablesshallprovidethefollowingadditionalattributes:

ElecticalPanelName
ElectricalPanelCircut

20130312COBieGuidePublicv05

57


8.8.5 Icemaker
ThefollowingminimumsetofinformationshallbeprovidedinConstructionDocumentsstage
designdeliverablescheduleandreflectedintheCDStageCOBieDeliverableandsubsequent
constructiondeliverables.
Notethattheexpectednamingofthiscomponentshouldreflectthetypeandcomponents
specificuseinthissystem.
Table29DesignMinimumIcemakerTypeScheduleHeadings

Heading
Name

TypicalUnit
FoodServiceIcemakerTypeXXSpace#01

Type
SpecificationSection
Location
Current
Voltage
Frequency
Power
Connection
WaterInlet
Drain
SpatialPlacement
BasisOfDesignManufacturer
BasisOfDesignModelNumber
BasisOfDesignNotes

FoodServiceIcemakerTypeXX
(asidentifiedinclientscontract)
(SpaceName)
Amps
Volts
Hz
kW

(fromapprovedlistofplacementtypes)
(Iffoundondrawingschedules)
(Iffoundondrawingschedules)
(Iffoundondrawingschedules)

Constructiondeliverableswillbeupdatedtoreflectinstalledequipmentandotherinformation
describedintheGeneralRequirementsSection.Inaddition,theBeneficialOccupancyandAsBuilt
Deliverablesshallprovidethefollowingadditionalattributes:

ElecticalPanelName
ElectricalPanelCircut

20130312COBieGuidePublicv05

58


8.8.6 Range
ThefollowingminimumsetofinformationshallbeprovidedinConstructionDocumentsstage
designdeliverablescheduleandreflectedintheCDStageCOBieDeliverableandsubsequent
constructiondeliverables.
Notethattheexpectednamingofthiscomponentshouldreflectthetypeandcomponents
specificuseinthissystem.
Table30DesignMinimumRangeTypeScheduleHeadings

Heading
Name
Type
SpecificationSection
Location
Current
Voltage
Frequency
Power
Connection
Gas
SpatialPlacement
BasisOfDesignManufacturer
BasisOfDesignModelNumber
BasisOfDesignNotes

TypicalUnit
FoodServiceRangeTypeXXSpace#01
FoodServiceRangeTypeXX
(asidentifiedinclientscontract)
(SpaceName)
Amps
Volts
Hz
kW

Mbtu
(fromapprovedlistofplacementtypes)
(Iffoundondrawingschedules)
(Iffoundondrawingschedules)
(Iffoundondrawingschedules)

Constructiondeliverableswillbeupdatedtoreflectinstalledequipmentandotherinformation
describedintheGeneralRequirementsSection.Inaddition,theBeneficialOccupancyandAsBuilt
Deliverablesshallprovidethefollowingadditionalattributes:

ElecticalPanelName
ElectricalPanelCircut

20130312COBieGuidePublicv05

59


8.8.7 Fryer
ThefollowingminimumsetofinformationshallbeprovidedinConstructionDocumentsstage
designdeliverablescheduleandreflectedintheCDStageCOBieDeliverableandsubsequent
constructiondeliverables.
Table31DesignMinimumFryerTypeScheduleHeadings

Heading
Name
Type
SpecificationSection
Location
Current
Voltage
Frequency
Power
Connection
Gas
SpatialPlacement
BasisOfDesignManufacturer
BasisOfDesignModelNumber
BasisOfDesignNotes

TypicalUnit
FoodServiceFryerTypeXXSpace#01
FoodServiceFryerTypeXX
(asidentifiedinclientscontract)
(SpaceName)
Amps
Volts
Hz
kW

Mbtu
(fromapprovedlistofplacementtypes)
(Iffoundondrawingschedules)
(Iffoundondrawingschedules)
(Iffoundondrawingschedules)

Notethattheexpectednamingofthiscomponentshouldreflectthetypeandcomponents
specificuseinthissystem.
Constructiondeliverableswillbeupdatedtoreflectinstalledequipmentandotherinformation
describedintheGeneralRequirementsSection.Inaddition,theBeneficialOccupancyandAsBuilt
Deliverablesshallprovidethefollowingadditionalattributes:

ElecticalPanelName
ElectricalPanelCircut

20130312COBieGuidePublicv05

60


8.8.8 Freezer
ThefollowingminimumsetofinformationshallbeprovidedinConstructionDocumentsstage
designdeliverablescheduleandreflectedintheCDStageCOBieDeliverableandsubsequent
constructiondeliverables.
Notethattheexpectednamingofthiscomponentshouldreflectthetypeandcomponents
specificuseinthissystem.
Table32DesignMinimumFreezerTypeScheduleHeadings

Heading

SpecificationSection

TypicalUnit
FoodServiceFreezerTypeXXSpace#01
FoodServiceFreezerTypeXX
(asidentifiedinclientscontract)

Location
Current
Voltage
Frequency
Power
Connection
SpatialPlacement
BasisOfDesignManufacturer
BasisOfDesignModelNumber
BasisOfDesignNotes

(SpaceName)
Amps
Volts
Hz
kW

(fromapprovedlistofplacementtypes)
(Iffoundondrawingschedules)
(Iffoundondrawingschedules)
(Iffoundondrawingschedules)

Name
Type

Constructiondeliverableswillbeupdatedtoreflectinstalledequipmentandotherinformation
describedintheGeneralRequirementsSection.Inaddition,theBeneficialOccupancyandAsBuilt
Deliverablesshallprovidethefollowingadditionalattributes:

ElecticalPanelName
ElectricalPanelCircut

20130312COBieGuidePublicv05

61

8.9 Required Architectural Assets


8.9.1 Doors
ThefollowingminimumsetofinformationshallbeprovidedinConstructionDocumentsstage
designdeliverablescheduleandreflectedintheCDStageCOBieDeliverableandsubsequent
constructiondeliverables.
Notethatacommaseparatedlistoftwospacenamesisrequiredforinteriordoors.Thefirst
spacelisted(orifonlyonespaceisprovided)shallbethespaceintowhichthedooropens.
Table33DesignMinimumDoorTypeScheduleHeadings

Heading
Name
Type
SpecificationSection
Location
DoorWidth
DoorHeight
DoorThickness
DoorType
DoorMaterial
DoorFinish
GlazingType
SecurityCode
FrameType
FrameMaterial
FrameFinish
FrameHead
FrameJam
FrameSill
FireLabelClass
FireLabelRating
HardwareSet
Pressurization
EgressDoor
SpatialPlacement
BasisOfDesignManufacturer
BasisOfDesignModelNumber
BasisOfDesignNotes

TypicalUnit
DoorTypeXXSpace#01
DoorTypeXX
(asidentifiedinclientscontract)
(SpaceNames)
mm
mm
mm

(fromapprovedlistofplacementtypes)
(Iffoundondrawingschedules)
(Iffoundondrawingschedules)
(Iffoundondrawingschedules)

Constructiondeliverableswillbeupdatedtoreflectinstalledequipmentandotherinformation
describedintheGeneralRequirementsSection.

20130312COBieGuidePublicv05

62

8.9.2 Windows
ThefollowingminimumsetofinformationshallbeprovidedinConstructionDocumentsstage
designdeliverablescheduleandreflectedintheCDStageCOBieDeliverableandsubsequent
constructiondeliverables.
Notethatacommaseparatedlistoftwospacenamesisrequiredforinteriorwindows.
Table34DesignMinimumWindowTypeScheduleHeadings

Heading
Name
Type
SpecificationSection
Location
WindowNumber
SecurityCode
WindowRating
GlazingType
WindowSize
WindowSize
WindowSize
WindowOperation
FrameMaterial
UFactor
SpatialPlacement
BasisOfDesignManufacturer
BasisOfDesignModelNumber
BasisOfDesignNotes

TypicalUnit
WindowTypeXXSpace#01
WindowTypeXX
(asidentifiedinclientscontract)
(SpaceNames)

(fromapprovedlistofplacementtypes)
(Iffoundondrawingschedules)
(Iffoundondrawingschedules)
(Iffoundondrawingschedules)

Constructiondeliverableswillbeupdatedtoreflectinstalledequipmentandotherinformation
describedintheGeneralRequirementsSection.

20130312COBieGuidePublicv05

63


8.9.3 Finishes
ThefollowingminimumsetofinformationshallbeprovidedinConstructionDocumentsstage
designdeliverablescheduleandreflectedintheCDStageCOBieDeliverableandsubsequent
constructiondeliverables.
Table35DesignMinimumFinishScheduleHeadings

Heading
Name
Type
SpecificationSection
Location
Floor
Base
Walls
CeilingType
CeilingFinish
CeilingHeight
SpatialPlacement
BasisOfDesignManufacturer
BasisOfDesignModelNumber
BasisOfDesignNotes

TypicalUnit

(asidentifiedinclientscontract)
(SpaceName)

mm
(fromapprovedlistofplacementtypes)
(Iffoundondrawingschedules)
(Iffoundondrawingschedules)
(Iffoundondrawingschedules)

Constructiondeliverableswillbeupdatedtoreflectinstalledequipmentandotherinformation
describedintheGeneralRequirementsSection.

20130312COBieGuidePublicv05

64

8.10 Furnishing Assets


Whiletherearemanydifferenttypesoffurnishingassets,theycommonlyusethesametypeof
schedule.ThefollowingminimumsetofinformationshallbeprovidedinConstructionDocuments
stagedesigndeliverablescheduleandreflectedintheCDStageCOBieDeliverableandsubsequent
constructiondeliverables.
Table36DesignMinimumFurnishingAssetsScheduleHeadings

Heading

TypicalUnit
FurnishingAssetTypeXXSpace#01
FurnishingAssetTypeXX
(asidentifiedinclientscontract)
(SpaceName)

(fromapprovedlistofplacementtypes)
(Iffoundondrawingschedules)
(Iffoundondrawingschedules)
(Iffoundondrawingschedules)

Name
Type
SpecificationSection
Location
GFCI
GFGI
CFCI
SpatialPlacement
BasisOfDesignManufacturer
BasisOfDesignModelNumber
BasisOfDesignNotes

Constructiondeliverableswillbeupdatedtoreflectinstalledequipmentandotherinformation
describedintheGeneralRequirementsSection.

20130312COBieGuidePublicv05

65

8.11 Site Assets


8.11.1 Site Water Distribution System
8.11.1.1 Site Water Pumps
ThefollowingminimumsetofinformationshallbeprovidedinConstructionDocumentsstage
designdeliverablescheduleandreflectedintheCDStageCOBieDeliverableandsubsequent
constructiondeliverables.
Notethattheexpectednamingofthiscomponentshouldreflectthetypeandcomponents
specificuseinthissystem.
Table37DesignMinimumPumpScheduleHeadings

Heading

TypicalUnit
SiteWaterPumpTypeXXSpace#01
SiteWaterPumpTypeXX
(asidentifiedinclientscontract)
(SpaceName)
Amps
Volts
Hz
kW
L/s
L/s
kPa
(fromapprovedlistofplacementtypes)
(Iffoundondrawingschedules)
(Iffoundondrawingschedules)
(Iffoundondrawingschedules)

Name
Type
SpecificationSection
Location
Current
Voltage
Frequency
Power
FlowRateMin
FlowRateMax
PressureHead
SpatialPlacement
BasisOfDesignManufacturer
BasisOfDesignModelNumber
BasisOfDesignNotes

Constructiondeliverableswillbeupdatedtoreflectinstalledequipmentandotherinformation
describedintheGeneralRequirementsSection.Inaddition,theBeneficialOccupancyandAsBuilt
Deliverablesshallprovidethefollowingadditionalattributes:

ElecticalPanelName
ElectricalPanelCircut

20130312COBieGuidePublicv05

66

8.11.1.2 Site Water Valves


SchedulesforthistypeofdevicearenotrequiredforCOBieDesignDeliverables,butwillbe
requiredforCOBieBeneficialOccupancyandAsBuiltModels.Thesescheduleswillconsistofthe
followingparts.

OneCOBie.Typerecordforeachtypeofcomponent
OneCOBie.Componentforeachindividualcomponent,identifyingthecomponentsspace
NameofCOBie.Componentmustbeuniquelycreatedusingthefollowingrule
o Valve&COBie.SpaceName&&ItemCountinSpecificSpace
TwoCOBie.Attributerecordforeachcomponent
o OperatingPositionNormal(open/closed)
o OperatingPositionEmergency(open/closed)
OneCOBie.Connectionrecordforeachcomponentwhoseflowiscontrolledbythisdevice.

8.11.1.3 Site Water Tanks


ThefollowingminimumsetofinformationshallbeprovidedinConstructionDocumentsstage
designdeliverablescheduleandreflectedintheCDStageCOBieDeliverableandsubsequent
constructiondeliverables.
Notethattheexpectednamingofthiscomponentshouldreflectthetypeandcomponents
specificuseinthissystem.
Table38DesignMinimumTanksScheduleHeadings

Heading
Name
Type
SpecificationSection
Location
AccessType
StorageType
Capacity
SpatialPlacement
BasisOfDesignManufacturer
BasisOfDesignModelNumber
BasisOfDesignNotes

TypicalUnit
SiteWaterTankTypeXXSpace#01
SiteWaterTankTypeXX
(asidentifiedinclientscontract)
(SpaceName)

L
(fromapprovedlistofplacementtypes)
(Iffoundondrawingschedules)
(Iffoundondrawingschedules)
(Iffoundondrawingschedules)

Constructiondeliverableswillbeupdatedtoreflectinstalledequipmentandotherinformation
describedintheGeneralRequirementsSection.

20130312COBieGuidePublicv05

67

8.11.2 Site Fire Suppression System


8.11.2.1 Fire Suppression Hydrants
ThefollowingminimumsetofinformationshallbeprovidedinConstructionDocumentsstage
designdeliverablescheduleandreflectedintheCDStageCOBieDeliverableandsubsequent
constructiondeliverables.
Notethattheexpectednamingofthiscomponentshouldreflectthetypeandcomponents
specificuseinthissystem.
Table39DesignMinimumHydrantScheduleHeadings

Heading
Name
Type
SpecificationSection
Location
FlowRate
PressureRating
BodyColor
CapColor
SpatialPlacement
BasisOfDesignManufacturer
BasisOfDesignModelNumber
BasisOfDesignNotes

TypicalUnit
HydrantTypeXXSpace#01
HydrantTypeXX
(asidentifiedinclientscontract)
(SpaceName)

(fromapprovedlistofplacementtypes)
(Iffoundondrawingschedules)
(Iffoundondrawingschedules)
(Iffoundondrawingschedules)

Constructiondeliverableswillbeupdatedtoreflectinstalledequipmentandotherinformation
describedintheGeneralRequirementsSection.
8.11.2.2 Fire Suppression Valves
SchedulesforthistypeofdevicearenotrequiredforCOBieDesignDeliverables,butwillbe
requiredforCOBieBeneficialOccupancyandAsBuiltModels.Thesescheduleswillconsistofthe
followingparts.

OneCOBie.Typerecordforeachtypeofcomponent
OneCOBie.Componentforeachindividualcomponent,identifyingthecomponentsspace
NameofCOBie.Componentmustbeuniquelycreatedusingthefollowingrule
o Valve&COBie.SpaceName&&ItemCountinSpecificSpace
TwoCOBie.Attributerecordforeachcomponent
o OperatingPositionNormal(open/closed)
o OperatingPositionEmergency(open/closed)
OneCOBie.Connectionrecordforeachcomponentwhoseflowiscontrolledbythisdevice.

20130312COBieGuidePublicv05

68

8.11.2.3 Fire Suppression Pumps


ThefollowingminimumsetofinformationshallbeprovidedinConstructionDocumentsstage
designdeliverablescheduleandreflectedintheCDStageCOBieDeliverableandsubsequent
constructiondeliverables.
Notethattheexpectednamingofthiscomponentshouldreflectthetypeandcomponents
specificuseinthissystem.
Table40DesignMinimumPumpScheduleHeadings

Heading
Name
Type
SpecificationSection
Location
Current
Voltage
Frequency
Power
FlowRateMin
FlowRateMax
PressureHead
SpatialPlacement
BasisOfDesignManufacturer
BasisOfDesignModelNumber
BasisOfDesignNotes

TypicalUnit
FirePumpTypeXXSpace#01
FirePumpTypeXX
(asidentifiedinclientscontract)
(SpaceName)
Amps
Volts
Hz
kW
L/s
L/s
kPa
(fromapprovedlistofplacementtypes)
(Iffoundondrawingschedules)
(Iffoundondrawingschedules)
(Iffoundondrawingschedules)

Constructiondeliverableswillbeupdatedtoreflectinstalledequipmentandotherinformation
describedintheGeneralRequirementsSection.Inaddition,theBeneficialOccupancyandAsBuilt
Deliverablesshallprovidethefollowingadditionalattributes:

ElecticalPanelName
ElectricalPanelCircut

20130312COBieGuidePublicv05

69


8.11.3 Water Supply Wells
8.11.3.1 Water Pumps
ThefollowingminimumsetofinformationshallbeprovidedinConstructionDocumentsstage
designdeliverablescheduleandreflectedintheCDStageCOBieDeliverableandsubsequent
constructiondeliverables.
Notethattheexpectednamingofthiscomponentshouldreflectthetypeandcomponents
specificuseinthissystem.
Table41DesignMinimumPumpScheduleHeadings

Heading
Name
Type
SpecificationSection
Location
Current
Voltage
Frequency
Power
FlowRateMin
FlowRateMax
PressureHead
SpatialPlacement
BasisOfDesignManufacturer
BasisOfDesignModelNumber
BasisOfDesignNotes

TypicalUnit
WaterSupplyPumpTypeXXSpace#01
WaterSupplyPumpTypeXX
(asidentifiedinclientscontract)
(SpaceName)
Amps
Volts
Hz
kW
L/s
L/s
kPa
(fromapprovedlistofplacementtypes)
(Iffoundondrawingschedules)
(Iffoundondrawingschedules)
(Iffoundondrawingschedules)

Constructiondeliverableswillbeupdatedtoreflectinstalledequipmentandotherinformation
describedintheGeneralRequirementsSection.Inaddition,theBeneficialOccupancyandAsBuilt
Deliverablesshallprovidethefollowingadditionalattributes:

ElecticalPanelName
ElectricalPanelCircut

20130312COBieGuidePublicv05

70

8.11.3.2 Water Valves


SchedulesforthistypeofdevicearenotrequiredforCOBieDesignDeliverables,butwillbe
requiredforCOBieBeneficialOccupancyandAsBuiltModels.Thesescheduleswillconsistofthe
followingparts.

OneCOBie.Typerecordforeachtypeofcomponent
OneCOBie.Componentforeachindividualcomponent,identifyingthecomponentsspace
NameofCOBie.Componentmustbeuniquelycreatedusingthefollowingrule
o Valve&COBie.SpaceName&&ItemCountinSpecificSpace
TwoCOBie.Attributerecordforeachcomponent
o OperatingPositionNormal(open/closed)
o OperatingPositionEmergency(open/closed)
OneCOBie.Connectionrecordforeachcomponentwhoseflowiscontrolledbythisdevice.

8.11.4 Site Sanitary Sewer


8.11.4.1 Sewer Manholes
ThefollowingminimumsetofinformationshallbeprovidedinConstructionDocumentsstage
designdeliverablescheduleandreflectedintheCDStageCOBieDeliverableandsubsequent
constructiondeliverables.
Notethattheexpectednamingofthiscomponentshouldreflectthetypeandcomponents
specificuseinthissystem.
Table42DesignMinimumManholeScheduleHeadings

Heading
Name
Type
SpecificationSection
Location
NorthCoordinate(Y)
EastCoordinate(X)
Top
Inv.In
Inv.Out
SpatialPlacement
BasisOfDesignManufacturer
BasisOfDesignModelNumber
BasisOfDesignNotes

TypicalUnit
SewerManholeTypeXXSpace#01
SewerManholeTypeXX
(asidentifiedinclientscontract)
(SpaceName)

(fromapprovedlistofplacementtypes)
(Iffoundondrawingschedules)
(Iffoundondrawingschedules)
(Iffoundondrawingschedules)

Constructiondeliverableswillbeupdatedtoreflectinstalledequipmentandotherinformation
describedintheGeneralRequirementsSection.

20130312COBieGuidePublicv05

71


8.11.4.2 Sewer Pumps
ThefollowingminimumsetofinformationshallbeprovidedinConstructionDocumentsstage
designdeliverablescheduleandreflectedintheCDStageCOBieDeliverableandsubsequent
constructiondeliverables.
Notethattheexpectednamingofthiscomponentshouldreflectthetypeandcomponents
specificuseinthissystem.
Table43DesignMinimumPumpScheduleHeadings

Heading
Name
Type
SpecificationSection
Location
Current
Voltage
Frequency
RatedFlow
ChurnPressure
ControllerType
SpatialPlacement
BasisOfDesignManufacturer
BasisOfDesignModelNumber
BasisOfDesignNotes

TypicalUnit
SewerPumpTypeXXSpace#01
SewerPumpTypeXX
(asidentifiedinclientscontract)
(SpaceName)
Amps
Volts
Hz
L/s
kPa

(fromapprovedlistofplacementtypes)
(Iffoundondrawingschedules)
(Iffoundondrawingschedules)
(Iffoundondrawingschedules)

Constructiondeliverableswillbeupdatedtoreflectinstalledequipmentandotherinformation
describedintheGeneralRequirementsSection.Inaddition,theBeneficialOccupancyandAsBuilt
Deliverablesshallprovidethefollowingadditionalattributes:

ElecticalPanelName
ElectricalPanelCircut

8.11.4.3 Sewer Valves


SchedulesforthistypeofdevicearenotrequiredforCOBieDesignDeliverables,butwillbe
requiredforCOBieBeneficialOccupancyandAsBuiltModels.Thesescheduleswillconsistofthe
followingparts.

OneCOBie.Typerecordforeachtypeofcomponent
OneCOBie.Componentforeachindividualcomponent,identifyingthecomponentsspace
NameofCOBie.Componentmustbeuniquelycreatedusingthefollowingrule
o Valve&COBie.SpaceName&&ItemCountinSpecificSpace
TwoCOBie.Attributerecordforeachcomponent
o OperatingPositionNormal(open/closed)

20130312COBieGuidePublicv05

72

o OperatingPositionEmergency(open/closed)
OneCOBie.Connectionrecordforeachcomponentwhoseflowiscontrolledbythisdevice.

8.11.4.4 Sewer Tanks


ThefollowingminimumsetofinformationshallbeprovidedinConstructionDocumentsstage
designdeliverablescheduleandreflectedintheCDStageCOBieDeliverableandsubsequent
constructiondeliverables.
Notethattheexpectednamingofthiscomponentshouldreflectthetypeandcomponents
specificuseinthissystem.
Table44DesignMinimumTankScheduleHeadings

Heading
Name
Type
SpecificationSection
Location
AccessType
StorageType
Capacity
SpatialPlacement
BasisOfDesignManufacturer
BasisOfDesignModelNumber
BasisOfDesignNotes

TypicalUnit
SewerTankTypeXXSpace#01
SewerTankTypeXX
(asidentifiedinclientscontract)
(SpaceName)

L
(fromapprovedlistofplacementtypes)
(Iffoundondrawingschedules)
(Iffoundondrawingschedules)
(Iffoundondrawingschedules)

Constructiondeliverableswillbeupdatedtoreflectinstalledequipmentandotherinformation
describedintheGeneralRequirementsSection.

20130312COBieGuidePublicv05

73


8.11.5 Fuel Distribution
8.11.5.1 Fuel Distribution Pumps
ThefollowingminimumsetofinformationshallbeprovidedinConstructionDocumentsstage
designdeliverablescheduleandreflectedintheCDStageCOBieDeliverableandsubsequent
constructiondeliverables.
Notethattheexpectednamingofthiscomponentshouldreflectthetypeandcomponents
specificuseinthissystem.
Table45DesignMinimumFuelPumpScheduleHeadings

Heading

TypicalUnit
FuelPumpTypeXXSpace#01
FuelPumpTypeXX
(asidentifiedinclientscontract)
(SpaceName)
Amps
Volts
Hz

L/s
L/s
m
RPM
kW

(fromapprovedlistofplacementtypes)
(Iffoundondrawingschedules)
(Iffoundondrawingschedules)
(Iffoundondrawingschedules)

Name
Type
SpecificationSection
Location
Current
Voltage
Frequency
Service
FlowRateMin
FlowRateMax
TotalHead
RotationSpeed
Power
Phase
SpatialPlacement
BasisOfDesignManufacturer
BasisOfDesignModelNumber
BasisOfDesignNotes

Constructiondeliverableswillbeupdatedtoreflectinstalledequipmentandotherinformation
describedintheGeneralRequirementsSection.Inaddition,theBeneficialOccupancyandAsBuilt
Deliverablesshallprovidethefollowingadditionalattributes:

ElecticalPanelName
ElectricalPanelCircut

20130312COBieGuidePublicv05

74


8.11.5.2 Fuel Distribution Valves
SchedulesforthistypeofdevicearenotrequiredforCOBieDesignDeliverables,butwillbe
requiredforCOBieBeneficialOccupancyandAsBuiltModels.Thesescheduleswillconsistofthe
followingparts.

OneCOBie.Typerecordforeachtypeofcomponent
OneCOBie.Componentforeachindividualcomponent,identifyingthecomponentsspace
NameofCOBie.Componentmustbeuniquelycreatedusingthefollowingrule
o Valve&COBie.SpaceName&&ItemCountinSpecificSpace
TwoCOBie.Attributerecordforeachcomponent
o OperatingPositionNormal(open/closed)
o OperatingPositionEmergency(open/closed)
OneCOBie.Connectionrecordforeachcomponentwhoseflowiscontrolledbythisdevice.

8.11.5.3 Fuel Distribution Tanks


ThefollowingminimumsetofinformationshallbeprovidedinConstructionDocumentsstage
designdeliverablescheduleandreflectedintheCDStageCOBieDeliverableandsubsequent
constructiondeliverables.
Notethattheexpectednamingofthiscomponentshouldreflectthetypeandcomponents
specificuseinthissystem.
Table46DesignMinimumFuelTankScheduleHeadings

Heading
Name
Type
SpecificationSection
Location
AccessType
Service
FuelType
Capacity
DryWeight
WetWeight
SpatialPlacement
BasisOfDesignManufacturer
BasisOfDesignModelNumber
BasisOfDesignNotes

TypicalUnit
FuelTankTypeXXSpace#01
FuelTankTypeXX
(asidentifiedinclientscontract)
(SpaceName)

L
Kg
Kg
(fromapprovedlistofplacementtypes)
(Iffoundondrawingschedules)
(Iffoundondrawingschedules)
(Iffoundondrawingschedules)

Constructiondeliverableswillbeupdatedtoreflectinstalledequipmentandotherinformation
describedintheGeneralRequirementsSection.

20130312COBieGuidePublicv05

75

8.11.5.4 Fuel Distribution Switches


Designschedulesforthistypeofdeviceondesigndrawingsonlyidentifyeachtypeofcomponent.
Thelocationofeachcomponentistypicallyidentifiedbydrawingnote.AsaresultDesign
DeliverablesforthistypeofdeviceshallbecomprisedofthefollowingCOBieinformation:

OneCOBie.Typerecordforeachtypeofcomponent
ThreeCOBie.AttributerecordforeachType
o Voltage
o Current
o Frequency
OneCOBie.Componentforeachindividualcomponent,identifyingthecomponentsspace
TwoCOBie.Attributeforeachindividualcomponent
o PanelBoard
o Circuit

AtBeneficialOccupancyandAsBuiltdeliverables,designschedulesshallbeupdatedasnoted
below.

OneCOBie.Typerecordforeachtypeofcomponent
ThreeCOBie.AttributerecordforeachType
o Voltage
o Current
o Frequency
OneCOBie.Componentforeachindividualcomponent,identifyingthecomponentsspace
TwoCOBie.Attributeforeachindividualcomponent
o PanelBoard
o Circuit
NameofCOBie.Componentmustbeuniquelycreatedusingthefollowingrule
o Switch&COBie.SpaceName&&ItemCountinSpecificSpace
OneCOBie.Connectionrecordforeachfixture,outlet,orequipmentcontrolledbythis
component.

20130312COBieGuidePublicv05

76

9 PARTS & CONSUMABLES


Thefollowingtypesofpartsaretobeidentified:

1.Generalconsumables
2.Generalcustodial
3.Generalshopequipment
4.Equipment
5.Tools
6.Equipmentspecificmaterials

9.1 Common Facility Consumables


ThefollowingminimumsetofinformationshallbeprovidedintheBeneficialOccupancy
ConstructionCOBieDeliverableandreflectedintheAsBuiltConstructionDeliverable.
Table47MinimumAttributesforCommonFacilityConsumablesandCOBieMapping

Heading

COBieMapping
Sheet

Column

AttributeName

DataType

AttributeReference

PartNumber

Spare

PartNumber

IfcIdentifier

Description

Spare

Description

IfcText

Vendor

Spare

Suppliers

IfcText

UnitPrice

Attribute

UnitPrice

IfcMonetaryUnit

Spare

Unit

Attribute

UnitOfMeasure

IfcUnit

Spare

Quantity

Attribute

Quantity

IfcCountMeasure Spare

MaterialCost

Attribute

MaterialCost

IfcMonetaryUnit

Spare

ShippingCost

Attribute

ShippingCost

IfcMonetaryUnit

Spare

SubCost

Attribute

SubCost

IfcMonetaryUnit

Spare

LogisticsCategory1 Attribute

LogisticsCategory1 IfcText

Spare

LogisticsCategory2 Attribute

LogisticsCategory2 IfcText

Spare

Website

Attribute

Website

IfcText

Spare

Criticality

Attribute

Criticality

IfcText

Spare

20130312COBieGuidePublicv05

77

9.2 Equipment Specific Consumables


ThefollowingminimumsetofinformationshallbeprovidedintheBeneficialOccupancy
ConstructionCOBieDeliverableandreflectedintheAsBuiltConstructionDeliverable.
Table48MinimumAttributesforEquipmentSpecificConsumablesandCOBieMapping

Heading

COBieMapping
Sheet

Column

AttributeName

Attribute
Reference

DataType
PartNumber

Spare

PartNumber

IfcIdentifier

Description

Spare

Description

IfcText

Vendor

Spare

Suppliers

IfcText

SpecNumber

Attribute

IfcLabel

Spare

SpecSection

Attribute

SpecificationNumb
er
SpecificationSectio
n

IfcLabel

Spare

UnitPrice

Attribute

UnitPrice

IfcMonetaryUnit

Spare

Unit

Attribute

IfcUnit

Spare

InitialOrderQuantity

Attribute

UnitOfMeasure
InitialOrderQuantit
y

IfcCountMeasure

Spare

ReOrderQuantity
MinimumInventory
Level

Attribute

Attribute

Attic

IfcCountMeasure

Spare

ReOrderQuantity
MinimumInventor
yLevel

IfcCountMeasure

Spare

Attribute

Attic

IfcText

Spare

MaterialCost

Attribute

MaterialCost

IfcMonetaryUnit

Spare

ShippingCost

Attribute

ShippingCost

IfcMonetaryUnit

Spare

SubCost

Attribute

SubCost

IfcMonetaryUnit

Spare

LogisticsCategory1

Attribute

LogisticsCategory1

IfcText

Spare

LogisticsCategory2

Attribute

LogisticsCategory2

IfcText

Spare

Website

Attribute

Website

IfcText

Spare

Criticality

Attribute

Criticality

IfcText

Spare

20130312COBieGuidePublicv05

78

APPENDIX A OWNERS REQUIREMENTS


**********************************************************************************
NOTE:Priortotheuseofthisdocumentbyaspecificowner.Thissectionshouldbeupdatedtoreflect
theindividualproceduresandtechnologiesinplacebythatownertofacilitatetheproductionand
deliveryofCOBiedeliverables.
**********************************************************************************
ThisAppendixprovidestherequirementsforyourspecificAgencyasadditionsto,orclarificationof,the
generalrequirementsforCOBiedeliverablesidentifiedintheprevioussections.

1 Automated Tools
ItisrecommendedthattheAgencyutilizingthisguideidentifythenecessaryautomatedtoolstobeused
duringthedifferentprojectphases.

Design
TheAgencywillneedtoolstocapturethedesigninformationrequiredinCOBie.Thereareseveral
designtoolsavailabletoproduceadesignCOBiefile.Moreinformationrelatedtosuchtoolscanbe
foundontheCOBieMeansandMethodpage14.

Construction
TheAgencywillneedtoolstocaptureinformationduringconstructionthatisrequiredinCOBie.Tools
canbeusedtocaptureassetsserialnumbersortoelectronicallyproduceandtransmitsubmittals.
Thereareseveraltoolsavailabletoaccomplishthis.MoreinformationcanbefoundontheCOBieMeans
andMethodpage15.

Commissioning
TheAgencywillneedtoolstocaptureandupdateinformationduringthecommissioningphase.There
areseveralavailabletoolstoaidinthisprocess.Moreinformationrelatedtosuchtoolscanbefoundon
theCOBieMeansandMethodpage16.

2 Mandatory Classification
Inlieuoftheclientprovidingaspecificclassificationscheme,theprojectteamshallsubmit,tothe
ownerforapproval,theclassificationschemetobeused.Theidentificationofthe
COBie.Sheet.ClassificationcolumndatashallbeasingletextstringwiththeClassificationNumber,a
delimiter(typicallyacolon),andtheClassificationname,e.g.1112113400:NewFacility.Thebest

14

http://www.buildingsmartalliance.org/index.php/projects/cobie
http://www.buildingsmartalliance.org/index.php/projects/cobie
16
http://www.buildingsmartalliance.org/index.php/projects/cobie
15

20130312COBieGuidePublicv05

79


classificationfoundshallbeused.Ifthereisnotaspecificallyapplicablesubclassification,thehigher
levelclassificationshallbeselected.Spacesmaybeaddedtoclassificationrecordstoprovide
readability.

COBie.Contact Classification
TherequiredclassificationtobeusedforCOBie.Contactrecordsidentifiestheorganizationsroles.The
Agencyspecifictableforcontactclassificationshallbeinsertedinthissection.Ifnospecificagencytable
isavailableforthisclassification,OmniClassTable34OrganizationalRolesshallbeuseasdefault.

COBie.Facility Classification
TherequiredclassificationtobeusedforCOBie.Facilityrecordsidentifiesthefacilitysfunction.The
Agencyspecifictableforfacilityclassificationshallbeinsertedinthissection.Ifnospecificagencytable
isavailableforthisclassification,OmniClassTable11ConstructionEntitiesbyFunctionshallbeuseas
default.

COBie.Space Classification
TherequiredclassificationtobeusedforCOBie.Spacerecordsidentifiesthespacesfunction.The
Agencyspecifictableforspaceclassificationshallbeinsertedinthissection.Ifnospecificagencytableis
availableforthisclassification,OmniClassTable13SpacesbyFunctionshallbeuseasdefault.

COBie.Zone Classification
ThefollowingzonesarerecommendedtobeincludedinCOBiemodels,ifsuchzonesarerelevantinthe
specificfacilitybeingmodeled.Theseareprovidedinalphabeticalorder.

CirculationZone
FireAlarmZone
HistoricalPreservationZone
LightingZone
OccupancyZone
VentilationZone

COBie.Type Classification
TherequiredclassificationtobeusedforCOBie.Typerecordsidentifiestheassettype.TheAgency
specifictablefortypeclassificationshallbeinsertedinthissection.Ifnospecificagencytableisavailable
forthisclassification,OmniClassTable23Productsshallbeuseasdefault.

COBie.System Classification
TherequiredclassificationtobeusedforCOBie.Systemrecordsidentifiesthesystemtype.TheAgency
specifictablefortypeclassificationshallbeinsertedinthissection.Ifnospecificagencytableisavailable
forthisclassification,OmniClassTable21Elementsshallbeuseasdefault.

20130312COBieGuidePublicv05

80

APPENDIX B MAPPING FOR EQUIPMENT / ASSET SCHEDULE


REQUIREMENTS

1 Required HVAC System Assets


1.1 Chiller
ThefollowingminimumsetofinformationshallbeprovidedinConstructionDocumentsstagedesign
deliverablescheduleandreflectedintheCDStageCOBieDeliverable.COBiedatamappingisbasedon
COBieformatandcurrentSPietemplateChiller_AIRCOOLED_USTypeProduct17
Table49MappingforMinimumChillerScheduleHeadings

DesignSchedule
Heading
Unit
ChillerTypeXX
Name
Space#01

Sheet

COBieMapping
AttributeName
DataType

Column

Component

Name

IfcLabel

Component

TypeName

IfcText

Attribute

TypeName

Type

ChillerTypeXX

SpecificationSe
ction

Location

(SpaceName)

Component

SpaceName

Current

Amps

Attribute

Current

Voltage

Volts

Attribute

Voltage

Hz

Attribute

Frequency

kW

Attribute

NominalPower

Capacity

kW

Attribute

NominalCapacity

WaterFlow

m3/hr

Attribute

NominalFlowRate

AmbientTemp

Attribute

AmbientTempurat
ure

PressureDrop

kPa

Attribute

PressureDrop

EnteringWater
C
Temp

Attribute

WaterTempEnterin
g

LeavingWater

Attribute

WaterTempLeavin

Frequency

Power

AttributeReference

ifcText
IfcIdentifier

IfcElectricCurren
tMeasure
IfcElectricVoltag
eMeasure
IfcFrequencyMe
asure
IfcPowerMeasur
e
IfcPowerMeasur
e
IfcVolumetricFlo
wRateMeasure
IfcThermodynam
icTemperatureM
easure
IfcPressureMeas
ure
IfcThermodynam
icTemperatureM
easure
IfcThermodynam

Type

Type/Component
Type/Component
Type/Component
Type/Component
Type/Component
Type/Component
Type/Component
Type/Component
Type/Component
Type/Component

17

http://www.wbdg.org/references/spie/111201/Chiller_AIRCOOLED_US/Chiller_AIRCOOLED
_USTypeProduct.html

20130312COBieGuidePublicv05

81


Temp
Motor
Controller

Unloading
Steps
ChillerMedia

ChillerType

Refrigerant
Type
Energy
EfficiencyRatio
(EER)
Integrated
PartLoad
Value(IPLV)
HeatReclaim

SpatialPlaceme
nt
BasisOfDesign
Manufacturer
BasisOfDesign
ModelNumber
BasisOfDesign
Notes

icTemperatureM
easure

Attribute

MotorController

IfcIdentifier

Type/Component

Attribute

UnloadingSteps

IfcText

Type/Component

Attribute

ChillerMedia

IfcText

Type/Component

Attribute

ChillerType

IfcText

Type/Component

Attribute

RefrigerantType

IfcText

Type/Component

Btu/hrtokW

Attribute

EnergyEfficiency
Ratio

IfcRatioMeasure

Type/Component

Attribute

IntegratedPart
LoadValue

IfcText

Type/Component

Attribute

HeatReclaim

IfcBoolean

Type/Component

(FromList)

Attribute

Placement

IfcText

Component

(BasisofDesign)

Attribute

BODManufacturer

IfcLabel

Type

(BasisofDesign)

Attribute

BODModel

IfcLabel

Type

(IfRequired)

Attribute

BODNotes

IfcText

Type

1.2 Boiler
ThefollowingminimumsetofinformationshallbeprovidedinConstructionDocumentsstagedesign
deliverablescheduleandreflectedintheCDStageCOBieDeliverable.COBiedatamappingisbasedon
COBieformatandcurrentSPietemplateBoiler_Steam_US18
Table50MappingforMinimumBoilerScheduleHeadings

DesignSchedule
Heading
Name
Type

SpecificationS
ection

COBieMapping
Sheet

BoilerTypeXXSpace#
01

Component

Name

IfcLabel

Component

TypeName

IfcText

Attribute

TypeName

ifcText

Type

BoilerTypeXX

Column

AttributeName

Attribute
Reference

Unit

DataType

18

http://www.wbdg.org/references/spie/110901/Boiler_STEAM_US/Boiler_STEAM_USTypeProduct.html

20130312COBieGuidePublicv05

82


Location

(SpaceName)

Component

SpaceName

Current

Amps

Attribute

Current

Voltage

Volts

Attribute

Voltage

Frequency

Hz

Attribute

Frequency

InputPower

kW

Attribute

PowerInput

OutputPower

kW

Attribute

PowerOutput

WaterFlow

m3/hr

Attribute

NominalFlowRate

Entering
WaterTemp

Attribute

WaterTempEnterin
g

LeavingWater
Temp

Attribute

WaterTempLeavin
g

VentDiameter

mm

Attribute

VentDiameter

Passes

Attribute

Passes

IfcText

Type/Component

PressureDrop

kPa

Attribute

PressureDrop

IfcPressureMeas
ure

Type/Component

Attribute

EnergySource

IfcLabel

Type/Component

Attribute

FuelType

IfcText

Type/Component

Attribute

OutputMedia

IfcText

Type/Component

(FromList)

Attribute

Placement

IfcText

Component

Attribute

BODManufacturer

IfcLabel

Type

Attribute

BODModel

IfcLabel

Type

Attribute

BODNotes

IfcText

Type

EnergySource

FuelType

OutputMedia

SpatialPlacem
ent
BasisOfDesign
Manufacturer
BasisOfDesign
ModelNumber
BasisOfDesign
Notes

(BasisofDesign)
(BasisofDesign)
(IfRequired)

IfcIdentifier
IfcElectricCurren
tMeasure
IfcElectricVoltag
eMeasure
IfcFrequencyMe
asure
IfcPowerMeasur
e
IfcPowerMeasur
e
IfcVolumetricFlo
wRateMeasure
IfcThermodynam
icTemperatureM
easure
IfcThermodynam
icTemperatureM
easure
IfcPositiveLength
Measure

Type/Component
Type/Component
Type/Component
Type/Component
Type/Component
Type/Component
Type/Component

Type/Component
Type/Component

20130312COBieGuidePublicv05

83

1.3 Air Handling Units


ThefollowingminimumsetofinformationshallbeprovidedinConstructionDocumentsstagedesign
deliverablescheduleandreflectedintheCDStageCOBieDeliverable.COBiedatamappingisbasedon
COBieformatandcurrentSPietemplateUnitaryEquipment_AIRHANDLER_USTypeProduct19
Table51MappingforMinimumAirHandlingUnitScheduleHeadings

DesignSchedule
Heading

COBieMapping

Name

Component

Name

IfcLabel

Type

AHUTypeXX

Component

TypeName

IfcText

Attribute

TypeName

ifcText

Type

Component

SpaceName

IfcIdentifier
IfcElectricCurren
tMeasure
IfcElectricVoltag
eMeasure
IfcFrequencyMe
asure
IfcVolumetricFlo
wRateMeasure
IfcVolumetricFlo
wRateMeasure
IfcVolumetricFlo
wRateMeasure
IfcPressureMeas
ure
IfcPowerMeasur
e
IfcRotationalFre
quencyMeasure
IfcSoundPressur
eMeasure
IfcVolumetricFlo
wRateMeasure
IfcLinearVelocity
Measure
IfcPowerMeasur
e
IfcThermodynam
icTemperatureM
easure

SpecificationSection

(SpaceName)

Location

Sheet

Column

AttributeName

Attribute
Reference

Unit
AHUTypeXX
Space#01

Current

Amps

Attribute

Current

Voltage

Volts

Attribute

Voltage

Frequency
FanFlow
Maximum

Hz

Attribute

Frequency

L/s

Attribute

FanFlowRateMax

FanFlowNominal

L/s

Attribute

FanOutsideFlow
FanExtPressure
Drop

L/s

Attribute

FanFlowRateMin
FanFlowRateOutsid
e

kPa

Attribute

FanPressureDrop

FanMotorPower

kW

Attribute

FanMotorPower

FanSpeed

RPM

Attribute

FanSpeed

FanSoundLevel

dB

Attribute

FanSoundLevel

CoilFlow

L/s

Attribute

CoilFlow

CoilVelocity

m/min

Attribute

CoilVelocity

CoilCapacity

Attribute

CoilCapcity

EnteringAirTempDB

Attribute

EnteringAirTempD
B

DataType

Type/Component
Type/Component
Type/Component
Type/Component
Type/Component
Type/Component
Type/Component
Type/Component
Type/Component
Type/Component
Type/Component
Type/Component
Type/Component

Type/Component

19

http://www.wbdg.org/references/spie/111201/UnitaryEquipment_AIRHANDLER_US/UnitaryEquipment
_AIRHANDLER_USTypeProduct.html

20130312COBieGuidePublicv05

84

LeavingAirTempWB

Attribute

LeavingAirTempW
B

EnteringWater
Temp

Attribute

EnteringWaterTem
p

LeavingWater
Temp

Attribute

LeavingWaterTem
p

ChilledWaterRate

L/s

Attribute

ChilledWaterRate

RunoutInletSize

mm

Attribute

RunoutInletSize

RunoutOutletSize
CoilAirPressure
Drop
CoilWaterPressure
Drop

mm

Attribute

Pa

Attribute

kPa

Attribute

RunoutOutletSize
PressureDropCoilAi
r
PressureDropCoil
Water

IfcThermodynam
icTemperatureM
easure
IfcThermodynam
icTemperatureM
easure
IfcThermodynam
icTemperatureM
easure
IfcThermodynam
icTemperatureM
easure
IfcThermodynam
icTemperatureM
easure
IfcVolumetricFlo
wRateMeasure
IfcPositiveLength
Measure
IfcPositiveLength
Measure
IfcPressureMeas
ure
IfcPressureMeas
ure

SpatialPlacement
BasisOfDesign
Manufacturer
BasisOfDesign
ModelNumber
BasisOfDesign
Notes

(FromList)

Attribute

Placement

IfcText

Component

(BasisofDesign)

Attribute

BODManufacturer

IfcLabel

Type

(BasisofDesign)

Attribute

BODModel

IfcLabel

Type

(IfRequired)

Attribute

BODNotes

IfcText

Type

EnteringAirTempWB C

Attribute

EnteringAirTempW
B

LeavingAirTempDB

Attribute

LeavingAirTempDB

Type/Component

Type/Component

Type/Component

Type/Component

Type/Component
Type/Component
Type/Component
Type/Component
Type/Component
Type/Component

1.4 Fan coil units


ThefollowingminimumsetofinformationshallbeprovidedinConstructionDocumentsstagedesign
deliverablescheduleandreflectedintheCDStageCOBieDeliverable.COBiedatamappingisbasedon
COBieformatandcurrentSPietemplateCoil_NOTDEFINED_US20.
Table52MappingforMinimumFanCoilUnitScheduleHeadings

COBieMapping

DesignSchedule
Sheet
Heading

Column

AttributeName

Attribute
Reference

Name

Unit
FanCoilTypeXX
Space#01

DataType
Component

Name

IfcLabel

Type

FanCoilTypeXX

Component

TypeName

IfcText

20

http://www.wbdg.org/references/spie/110901/Coil_NOTDEFINED_US/Coil_NOTDEFINED_USTypeProduct.html

20130312COBieGuidePublicv05

85

SpecificationSection

Attribute

TypeName

Location

(SpaceName)

Component

SpaceName

Current

Amps

Attribute

Current

Voltage

Volts

Attribute

Voltage

Frequency

Hz

Attribute

AirFlow

L/s

Attribute

Frequency
NominalAirFlowRat
e

FanSpeed

Attribute

FanSpeed

ExitStaticPressure

Pa

Attribute

ExitStaticPressure

EnteringAirTempDB

Attribute

EnteringAirTempD
B

EnteringAirTempWB C

Attribute

EnteringAirTempW
B

LeavingAirTempDB

Attribute

LeavingAirTempDB

LeavingAirTempWB

Attribute

LeavingAirTempW
B

TotalCapacity

KW

Attribute

SensibleCapacity

KW

Attribute

TotalCapacity
NominalSensibleCa
pacity

EnteringWater
Temp

Attribute

EnteringWaterTem
p

LeavingWater
Temp

Attribute

LeavingWaterTem
p

ChilledWaterFlow

L/s

Attribute

ChilledWaterFlow

CoolingCoilDeltaP

kPa

Attribute

CoolingCoilDeltaP

CoolingRows

Attribute

CoolingRows

FanMotorPower

KW

Attribute

Phase

Attribute

CabinetType

SpatialPlacement

(FromList)

ifcText

Type

IfcIdentifier
IfcElectricCurren
tMeasure
IfcElectricVoltag
eMeasure
IfcFrequencyMe
asure
IfcVolumetricFlo
wRateMeasure
IfcRotationalFre
quencyMeasure
IfcPressureMeas
ure
IfcThermodynam
icTemperatureM
easure
IfcThermodynam
icTemperatureM
easure
IfcThermodynam
icTemperatureM
easure
IfcThermodynam
icTemperatureM
easure
IfcPowerMeasur
e
IfcPowerMeasur
e
IfcThermodynam
icTemperatureM
easure
IfcThermodynam
icTemperatureM
easure
IfcVolumetricFlo
wRateMeasure
IfcPressureMeas
ure

Type/Component

Power

IfcReal
IfcPowerMeasur
e

PhaseReference

IfcLabel

Type/Component

Attribute

CabinetType

IfcText

Type/Component

Attribute

Placement

IfcText

Component

20130312COBieGuidePublicv05

Type/Component
Type/Component
Type/Component
Type/Component
Type/Component
Type/Component

Type/Component

Type/Component

Type/Component

Type/Component
Type/Component
Type/Component

Type/Component

Type/Component
Type/Component
Type/Component

Type/Component

86


BasisOfDesign
Manufacturer
BasisOfDesign
ModelNumber
BasisOfDesign
Notes

(BasisofDesign)

Attribute

BODManufacturer

IfcLabel

Type

(BasisofDesign)

Attribute

BODModel

IfcLabel

Type

(IfRequired)

Attribute

BODNotes

IfcText

Type

1.5 Filters
ThefollowingminimumsetofinformationshallbeprovidedinConstructionDocumentsstagedesign
deliverablescheduleandreflectedintheCDStageCOBieDeliverable.COBiedatamappingisbasedon
COBieformatandcurrentSPietemplateFilter_AIRPARTICLEFILTER_US21.AirFlowmaximumwas
includedinthistablesinceitwasfoundinanoteassociatedwitheachfilter.Theefficiencyrating
identifiedinthetableistoogeneralandshouldbeclarifiedaseitherNominalCountedEfficiencyor
NominalWeightedEfficiency.
Table53MappingforMinimumFilterScheduleHeadings

COBieMapping

DesignSchedule
Sheet
Heading

Column

AttributeName

Attribute
Reference

Name

Unit
FilterTypeXX
Space#01

DataType
Component

Name

IfcLabel

Type

FilterTypeXX

Component

TypeName

IfcText

SpecificationSection

Attribute

TypeName

ifcText

Type

Location

(SpaceName)

Component

SpaceName

Length

mm

Attribute

NominalLength

Width

mm

Attribute

NominalWidth

Height

mm

Attribute

NominalHeight

AirFlowMaximum

L/s

Attribute

AirFlowNominal

L/s

Attribute

NominalPressure
Drop

Pa

Attribute

MaxFlowRate
NominalFlowRat
e
NominalPressure
Drop

IfcIdentifier
IfcPositiveLength
Measure
IfcPositiveLength
Measure
IfcPositiveLength
Measure
IfcVolumetricFlo
wRateMeasure

EfficiencyRating

Attribute

ResidenceTime

Sec

Attribute

SpatialPlacement

(FromList)

Attribute

Type/Component
Type/Component
Type/Component
Type/Component

IfcVolumetricFlo
wRateMeasure

Type/Component

IfcPressureMeas
ure

Type/Component

Efficiency

IfcReal

Type/Component

ResidenceTime

IfcTimeMeasur
e

Type/Component

Placement

IfcText

Component

21

http://www.wbdg.org/references/spie/110901/Filter_AIRPARTICLEFILTER_US/Filter_AIRPARTICLEFILTER_
USTypeProduct.html

20130312COBieGuidePublicv05

87


BasisOfDesign
Manufacturer
BasisOfDesign
ModelNumber
BasisOfDesign
Notes

BODManufacture
r

IfcLabel

Type

(BasisofDesign)

Attribute

(BasisofDesign)

Attribute

BODModel

IfcLabel

Type

(IfRequired)

Attribute

BODNotes

IfcText

Type

1.6 Pumps
ThefollowingminimumsetofinformationshallbeprovidedinConstructionDocumentsstagedesign
deliverablescheduleandreflectedintheCDStageCOBieDeliverable.COBiedatamappingisbasedon
COBieformatandcurrentSPietemplatePump_CIRCULATOR_US22.
Table54MappingforMinimumPumpScheduleHeadings

DesignSchedule
Heading

COBieMapping
Unit

PumpTypeXX
Space#01

Name

Sheet

Column

AttributeName

Attribute
Reference

DataType

Component

Name

IfcLabel

Component

TypeName

IfcText

(SpaceName)

Attribute
Component

TypeName
SpaceName

Type

Current

Amps

Attribute

Current

Voltage

Volts

Attribute

Voltage

Frequency

Hz

Attribute

Frequency

RatedFlow

L/s

Attribute

FlowRateRange

ChurnPressure

kPa

Attribute

ChurnPressure

ifcText
IfcIdentifier
IfcElectricCurren
tMeasure
IfcElectricVoltag
eMeasure
IfcFrequencyMe
asure
IfcVolumetricFlo
wRateMeasure
IfcPressureMeas
ure

ControllerType

Attribute

ControllerType

IfcText

Type/Component

SpatialPlacement
BasisOfDesign
Manufacturer
BasisOfDesign
ModelNumber

(FromList)

Attribute

Placement

IfcText

Component

Attribute

BODManufacturer

IfcLabel

Type

Attribute

BODModel

IfcLabel

Type

Attribute

BODNotes

IfcText

Type

Type
SpecificationSection
Location

PumpTypeXX

(BasisofDesign)
(BasisofDesign)

BasisOfDesignNotes (IfRequired)

Type/Component
Type/Component
Type/Component
Type/Component
Type/Component

22

http://www.wbdg.org/references/spie/111201/Pump_CIRCULATOR_US/Pump_CIRCULATOR_
USTypeProduct.html

20130312COBieGuidePublicv05

88

1.7 Fans
ThefollowingminimumsetofinformationshallbeprovidedinConstructionDocumentsstagedesign
deliverablescheduleandreflectedintheCDStageCOBieDeliverable.COBiedatamappingisbasedon
COBieformatandcurrentSPietemplateFan_CENTRIFUGALAIRFOIL_US23
Table55MappingforMinimumFanScheduleHeadings

DesignSchedule
Heading

COBieMapping
Unit

Sheet

Column

AttributeName

Attribute
Reference

DataType

Name

FanTypeXX
Space#01

Component

Name

IfcLabel

Type

FanTypeXX

Component

TypeName

IfcText

SpecificationSection

Attribute

TypeName

ifcText

Type

Location

(SpaceName)

Component

SpaceName

IfcIdentifier

Current

Amps

Attribute

Current

Voltage

Volts

Attribute

Voltage

Frequency

Hz

Attribute

Frequency

Service

Attribute

TypeOfService

IfcText

FlowRate

L/s

Attribute

Pressure

Pa

Attribute

IfcVolumetricFlo
wRateMeasure
IfcPowerMeasur
e

ControlType

Attribute

NominalAirFlowRat
e
NominalTotalPress
ure
CapacityControlTy
pe

IfcLabel

Type/Component

Interlock

Attribute

Interlock

IfcText

Component

SpatialPlacement
BasisOfDesign
Manufacturer
BasisOfDesign
ModelNumber
BasisOfDesign
Notes

(FromList)

Attribute

Placement

IfcText

Component

(BasisofDesign)

Attribute

BODManufacturer

IfcLabel

Type

(BasisofDesign)

Attribute

BODModel

IfcLabel

Type

(IfRequired)

Attribute

BODNotes

IfcText

Type

IfcElectricCurren
tMeasure
IfcElectricVoltag
eMeasure
IfcFrequencyMe
asure

Type/Component
Type/Component
Type/Component
Type/Component
Type/Component
Type/Component

23

http://www.wbdg.org/references/spie/111201/Fan_CENTRIFUGALAIRFOIL_US/Fan_CENTRIFUGALAIRFOIL_
USTypeProduct.html

20130312COBieGuidePublicv05

89

1.8 Motors
ThefollowingminimumsetofinformationshallbeprovidedinConstructionDocumentsstagedesign
deliverablescheduleandreflectedintheCDStageCOBieDeliverable.COBiedatamappingisbasedon
COBieformatandcurrentSPietemplateElectricMotor_DC_US24.
Table56MappingforMinimumMotorScheduleHeadings

DesignSchedule
Heading

COBieMapping
Unit

Sheet

Column

AttributeName

Attribute
Reference

DataType

Name

MotorTypeXX
Space#01

Component

Name

IfcLabel

Type

MotorTypeXX

Component

TypeName

IfcText

SpecificationSection

Attribute

TypeName

ifcText

Type

Location

(SpaceName)

Component

SpaceName

IfcIdentifier

Current

Amps

Attribute

Current

Voltage

Volts

Attribute

Voltage

Frequency

Hz

Attribute

Frequency

Power

KW

Attribute

Power

Phase

Attribute

PhaseReference

IfcLabel

Type/Component

Efficiency

Attribute

ElectricMotorEffici
ency

IfcPowerMeasur
e

Type/Component

Drive

Attribute

Drive

IfcLabel

Type/Component

DriveControlType

Attribute

DriveControlType

IfcText

Type/Component

SpatialPlacement
BasisOfDesign
Manufacturer
BasisOfDesign
ModelNumber

(FromList)

Attribute

Placement

IfcText

Component

(BasisofDesign) Attribute

BODManufacturer

IfcLabel

Type

(BasisofDesign) Attribute

BODModel

IfcLabel

Type

BasisOfDesignNotes

(IfRequired)

BODNotes

IfcText

Type

Attribute

IfcElectricCurren
tMeasure
IfcElectricVoltag
eMeasure
IfcFrequencyMe
asure
IfcPowerMeasur
e

Type/Component
Type/Component
Type/Component
Type/Component

24

http://www.wbdg.org/references/spie/110901/ElectricMotor_DC_US/ElectricMotor_DC_USTypeProduct.html

20130312COBieGuidePublicv05

90

1.9 Compressors
ThefollowingminimumsetofinformationshallbeprovidedinConstructionDocumentsstagedesign
deliverablescheduleandreflectedintheCDStageCOBieDeliverable.COBiedatamappingisbasedon
COBieformatandcurrentSPietemplateCompressor_RECIPROCATING_US25.
Table57MappingforMinimumCompressorScheduleHeadings

COBieMapping

DesignSchedule
Sheet
Heading
Name
Type
SpecificationSecti
on

Unit
Compressor
TypeXXSpace#01
Compressor
TypeXX

Column

AttributeName

Attribute
Reference

DataType
Component

Name

IfcLabel

Component

TypeName

IfcText

Attribute

TypeName

ifcText

Type

Location

(SpaceName)

Component

SpaceName

Current

Amps

Attribute

Current

Voltage

Volts

Attribute

Voltage

Frequency

Hz

Attribute

Frequency

RefrigerantType

Attribute

RefrigerantClass

Capacity

Attribute

NominalCapacity

IfcIdentifier
IfcElectricCurren
tMeasure
IfcElectricVoltag
eMeasure
IfcFrequencyMe
asure
IfcMaterialDefini
tion
IfcPowerMeasur
e

Speed

RPM

Attribute

CompressorSpeed

IfcRotationalFre
quencyMeasure

Type/Component

SpatialPlacement
BasisOfDesign
Manufacturer
BasisOfDesign
ModelNumber
BasisOfDesign
Notes

(FromList)

Attribute

Placement

IfcText

Component

Attribute

BODManufacturer

IfcLabel

Type

Attribute

BODModel

IfcLabel

Type

Attribute

BODNotes

IfcText

Type

(BasisofDesign)
(BasisofDesign)
(IfRequired)

Type/Component
Type/Component
Type/Component
Type/Component
Type/Component

25

http://www.wbdg.org/references/spie/110901/Compressor_RECIPROCATING_US/Compressor_RECIPROCATING
_USTypeProduct.html

20130312COBieGuidePublicv05

91

1.10 Variable Air Volume boxes


ThefollowingminimumsetofinformationshallbeprovidedinConstructionDocumentsstagedesign
deliverablescheduleandreflectedintheCDStageCOBieDeliverable.COBiedatamappingisbasedon
COBieformatandcurrentSPietemplateAirTerminalBox_VARIABLEFLOWPRESSUREDEPENDANT_US26
Table58MappingforMinimumVAVBoxScheduleHeadings

DesignSchedule
Heading

COBieMapping

Unit

Sheet

Column

AttributeName

Attribute
Reference

DataType

Name

VAVTypeXX
Space#01

Component

Name

IfcLabel

Type

VAVTypeXX

Component

TypeName

IfcText

SpecificationSecti
on

Attribute

TypeName

ifcText

Type

Location

(SpaceName)

Component

SpaceName

IfcIdentifier

Current

Amps

Attribute

Current

Voltage

Volts

Attribute

Voltage

Frequency

Hz

Attribute

Frequency

InletSize

mm

Attribute

InletSize

L/s

Attribute

FlowRateRange

L/s

Attribute

FlowRateRange

Pa

Attribute

PressureDrop

dB

Attribute

NCLevelDischarge

dB

Attribute

NCLevelRadiated

(FromList)

Attribute

Placement

IfcText

Component

(BasisofDesign)

Attribute

BODManufacturer

IfcLabel

Type

(BasisofDesign)

Attribute

BODModel

IfcLabel

Type

(IfRequired)

Attribute

BODNotes

IfcText

Type

AirFlow
Minimum
AirFlow
Maximum
PressureDrop
NCLevel
Discharge
NCLevel
Radiated
SpatialPlacement
BasisOfDesign
Manufacturer
BasisOfDesign
ModelNumber
BasisOfDesign
Notes

IfcElectricCurren
tMeasure
IfcElectricVoltag
eMeasure
IfcFrequencyMe
asure
IfcPositiveLength
Measure
IfcVolumetricFlo
wRateMeasure
IfcVolumetricFlo
wRateMeasure
IfcPressureMeas
ure
IfcSoundPressur
eMeasure
IfcSoundPressur
eMeasure

Type/Component
Type/Component
Type/Component
Type/Component
Type/Component
Type/Component
Type/Component
Type/Component
Type/Component

26

http://www.wbdg.org/references/spie/110901/AirTerminalBox_VARIABLEFLOWPRESSUREDEPENDANT
_US/AirTerminalBox_VARIABLEFLOWPRESSUREDEPENDANT_USTypeProduct.html

20130312COBieGuidePublicv05

92

2 Required Plumbing System Assets


2.1 Water treatment Assemblies

ThefollowingminimumsetofinformationshallbeprovidedinConstructionDocumentsstagedesign
deliverablescheduleandreflectedintheCDStageCOBieDeliverable.

Table59MappingforMinimumWaterTreatmentAssembliesScheduleHeadings

DesignSchedule
Heading

Unit
WaterTreatmentAssem
blyTypeXXSpace#01
WaterTreatmentAssem
blyTypeXX

Name
Type

COBieMapping
Sheet

Column

Component

Name

Component

TypeName

Attribute

TypeName

SpecificationS
ection

Location

(SpaceName)

Component

SpaceName

SystemTypes

Attribute

Water
Softener
Disinfection
Type
Rejection
Ratio
Capacity
SpatialPlacem
ent
BasisOfDesign
Manufacturer
BasisOfDesign
ModelNumber
BasisOfDesign
Notes

AttributeName

Attribute
Reference

DataType
IfcLabel
IfcText

ifcText

Type

IfcIdentifier

SystemsType

IfcText

Type/Component

Attribute

WaterSoftener

IfcBoolean

Type/Component

Attribute

DesinfectionType

IfcText

Type/Component

Attribute

RejectionRatio

IfcRatioMeasure

Type/Component

cu.meters/day

Attribute

Capacity

IfcVolumetricFlo
wRateMeasure

Type/Component

(FromList)

Attribute

Placement

IfcText

Component

(BasisofDesign)

Attribute

BODManufacturer

(BasisofDesign)

Attribute

BODModel

(IfRequired)

Attribute

BODNotes

IfcLabel
IfcLabel
IfcText

Type
Type
Type

20130312COBieGuidePublicv05

93

2.1 Plumbing Fixtures


ThefollowingminimumsetofinformationshallbeprovidedinConstructionDocumentsstagedesign
deliverablescheduleandreflectedintheCDStageCOBieDeliverable.COBiedatamappingisbasedon
COBieformatandcurrentSPietemplateSanitaryTerminal_WASHHANDBASIN_PlumbingFixtures_US27,
SanitaryTerminal_TOILETPAN_PlumbingFixtures_US28,
SanitaryTerminal_URINAL_PlumbingFixtures_US29
Table60MappingforMinimumPlumbingFixtureScheduleHeadings

DesignSchedule
Heading

Unit
PlumbingFixture
TypeXXSpace#01
PlumbingFixture
TypeXX

Name
Type

COBieMapping
Sheet

Column

AttributeName

Attribute
Reference

DataType

Component

Name

IfcLabel

Component

TypeName

IfcText

Attribute

TypeName

ifcText

Type

IfcIdentifier

SpecificationS
ection

Location

(SpaceName)

Component

SpaceName

Waste

WSFU

Attribute

WasteWater

Vent

WSFU

Attribute

Vent

ColdWater

WSFU

Attribute

ColdWater

HotWater

WSFU

Attribute

HotWater

liter/flush

Attribute

SanitaryFixtureWat
er

IfcReal

Type/Component

L/min

Attribute

MaximumFlowRate

IfcVolumetricFlo
wRateMeasure

Type/Component

(FromList)

Attribute

Placement

IfcText

Component

(BasisofDesign)

Attribute

BODManufacturer

IfcLabel

Type

(BasisofDesign)

Attribute

BODModel

IfcLabel

Type

(IfRequired)

Attribute

BODNotes

IfcText

Type

Sanitary
FixtureWater
Maximum
FlowRate
SpatialPlacem
ent
BasisOfDesign
Manufacturer
BasisOfDesign
ModelNumber
BasisOfDesign
Notes

IfcVolumetricFlo
wRateMeasure
IfcVolumetricFlo
wRateMeasure
IfcVolumetricFlo
wRateMeasure
IfcVolumetricFlo
wRateMeasure

Type/Component
Type/Component
Type/Component
Type/Component

27

http://www.wbdg.org/references/spie/110901/SanitaryTerminal_WASHHANDBASIN_PlumbingFixtures_US/Sanit
aryTerminal_WASHHANDBASIN_PlumbingFixtures_USTypeProduct.html
28
http://www.wbdg.org/references/spie/111201/SanitaryTerminal_TOILETPAN_PlumbingFixtures
_US/SanitaryTerminal_TOILETPAN_PlumbingFixtures_USTypeProduct.html
29
http://www.wbdg.org/references/spie/111201/SanitaryTerminal_URINAL_PlumbingFixtures
_US/SanitaryTerminal_URINAL_PlumbingFixtures_USTypeProduct.html

20130312COBieGuidePublicv05

94

3 Required Fire Suppression System Assets


3.1 Pumps
ThefollowingminimumsetofinformationshallbeprovidedinConstructionDocumentsstagedesign
deliverablescheduleandreflectedintheCDStageCOBieDeliverable.COBiedatamappingisbasedon
COBieformatandcurrentSPietemplatePump_CIRCULATOR_US30.
Table61MappingforMinimumPumpScheduleHeadings

DesignSchedule
Heading

COBieMapping
Unit

PumpTypeXX
Space#01

Name

Sheet

Column

AttributeName

Attribute
Reference

DataType

Component

Name

IfcLabel

Component

TypeName

IfcText

(SpaceName)

Attribute
Component

TypeName
SpaceName

Type

Current

Amps

Attribute

Current

Voltage

Volts

Attribute

Voltage

Frequency

Hz

Attribute

Frequency

RatedFlow

L/s

Attribute

FlowRateRange

ChurnPressure

kPa

Attribute

ChurnPressure

ifcText
IfcIdentifier
IfcElectricCurren
tMeasure
IfcElectricVoltag
eMeasure
IfcFrequencyMe
asure
IfcVolumetricFlo
wRateMeasure
IfcPressureMeas
ure

ControllerType

Attribute

ControllerType

IfcText

Type/Component

SpatialPlacement
BasisOfDesign
Manufacturer
BasisOfDesign
ModelNumber

(FromList)

Attribute

Placement

IfcText

Component

Attribute

BODManufacturer

IfcLabel

Type

Attribute

BODModel

IfcLabel

Type

Attribute

BODNotes

IfcText

Type

Type
SpecificationSection
Location

PumpTypeXX

(BasisofDesign)
(BasisofDesign)

BasisOfDesignNotes (IfRequired)

Type/Component
Type/Component
Type/Component
Type/Component
Type/Component

30

http://www.wbdg.org/references/spie/111201/Pump_CIRCULATOR_US/Pump_CIRCULATOR_
USTypeProduct.html

20130312COBieGuidePublicv05

95

3.2 Fire extinguishers


Designschedulesforthistypeofdeviceondesigndrawingsonlyidentifyeachtypeofcomponent.The
locationofeachcomponentistypicallyidentifiedbydrawingnote.AsaresultDesignDeliverablesfor
thistypeofdeviceshallbecomprisedofthefollowingCOBieinformation:

OneCOBie.Typerecordforeachtypeofcomponent
TwoCOBie.AttributerecordforeachType
o Capacity(Kg)
o Rating
OneCOBie.Componentforeachindividualcomponent,identifyingthecomponentsspace

SchedulesforthistypeofdevicearenotrequiredforCOBieDesignDeliverables,butwillberequiredfor
COBieBeneficialOccupancyandAsBuiltModels.Thesescheduleswillconsistofthefollowingparts.
Table62MappingforMinimumFireExtinguisherScheduleHeadings

DesignSchedule
Heading
Name
Type

Unit
FireExtinguisher
TypeXXSpace#01
FireExtinguisher
TypeXX

COBieMapping
Sheet

Column

AttributeName

DataType

AttributeReference

Component

Name

IfcLabel

Component

TypeName

IfcText

Attribute

TypeName

ifcText

Type

SpecificationS
ection

Location

(SpaceName)

Component

SpaceName

IfcIdentifier

Capacity

Kg

Attribute

Capacity

IfcMassMeasure

Component

Rating

Attribute

Rating

IfcText

Component

SpatialPlacem
ent

(FromList)

Attribute

Placement

IfcText

Component

Attribute

BODManufacture
r

IfcLabel

Type

Attribute

BODModel

IfcLabel

Type

Attribute

BODNotes

IfcText

Type

BasisOfDesign (BasisofDesign)
Manufacturer
BasisOfDesign
(BasisofDesign)
ModelNumber
BasisOfDesign
(IfRequired)
Notes

20130312COBieGuidePublicv05

96

4 Required Electrical System Assets


4.1 Light fixtures
ThefollowingminimumsetofinformationshallbeprovidedConstructionDocumentstagedesign
deliverablescheduleandreflectedintheCDStageCOBieDeliverable.COBiedatamappingisbasedon
COBieformatandcurrentSPietemplateLightFixture_DIRECTIONSOURCE_LightFixture_US31
Table63MappingforMinimumLightFixtureTypeScheduleHeadings

DesignSchedule
Heading
Name
Type
SpecificationS
ection

Unit
LightFixture
TypeXXSpace#01
LightFixtureTypeXX

COBieMapping
Sheet

Column

AttributeName

Attribute
Reference

DataType

Component

Name

IfcLabel

Component

TypeName

IfcText

Attribute

TypeName

ifcText

Type

IfcIdentifier

Location

(SpaceName)

Component

SpaceName

Current

Amps

Attribute

Current

Voltage

Volts

Attribute

Voltage

Frequency

Hz

Attribute

Frequency

LensType

Attribute

LensType

IfcLabel

Type/Component

LampType

Attribute

LampType

IfcLabel

Type/Component

Mounting

Attribute

IfcLabel

Type/Component

LampCount

Each

Attribute

LightFixtureMounti
ngType
LampCount

IfcCountMeasure

Type/Component

LampPower

Attribute

LampPower

IfcPowerMeasure

Type/Component

Function

Attribute

Function

IfcText

Type/Component

LightPath

Attribute

LightPath

IfcTaxt

Type/Component

(FromList)

Attribute

Placement

IfcText

Component

(BasisofDesign)

Attribute

BODManufacturer

IfcLabel

Type

(BasisofDesign)

Attribute

BODModel

IfcLabel

Type

(IfRequired)

Attribute

BODNotes

IfcText

Type

SpatialPlacem
ent
BasisOfDesign
Manufacturer
BasisOfDesign
ModelNumber
BasisOfDesign
Notes

IfcElectricCurrent
Measure
IfcElectricVoltageM
easure
IfcFrequencyMeas
ure

Type/Component
Type/Component
Type/Component

31

http://www.wbdg.org/references/spie/111201/LightFixture_DIRECTIONSOURCE_LightFixture_US/
LightFixture_DIRECTIONSOURCE_LightFixture_USTypeProduct.html

20130312COBieGuidePublicv05

97

4.2 Distribution panel


ThefollowingminimumsetofinformationshallbeprovidedinConstructionDocumentsstagedesign
deliverablescheduleandreflectedintheCDStageCOBieDeliverable.COBiedatamappingisbasedon
COBieformatandcurrentSPietemplate
ElectricDistributionBoard_DISTRIBUTIONBOARD_DistributionPanel_US32.
Table64MappingforMinimumDistributionPanelTypeScheduleHeadings

COBieMapping

DesignSchedule
Heading
Name
Type
SpecificationS
ection

Unit
DistributionPanel
TypeXXSpace#01
DistributionPanel
TypeXX

(SpaceName)

Location

Sheet

Column

AttributeName

DataType

AttributeReference

Component

Name

IfcLabel

Component

TypeName

IfcText

Attribute

TypeName

ifcText

Type

Component

SpaceName

IfcIdentifier
IfcElectricCurren
tMeasure
IfcElectricVoltag
eMeasure
IfcFrequencyMe
asure

IfcLabel
IfcCountMeasur
e

Type/Component

IfcInteger

Type/Component
Type/Component

Current

Amps

Attribute

Current

Voltage

Volts

Attribute

Voltage

Frequency

Hz

Attribute

Frequency

Phase
Numberof
Wires
Numberof
Poles
MainBreaker
Mounting
MainBus
Current

Attribute

PhaseReference

Attribute

NumberOfWires

Attribute

Attribute

NumberOfPoles
MainBreakerMoun
ting

Amps

Attribute

BusCurrent

IfcText
IfcElectricCurren
tMeasure

NeutralBus
EquipGround
Bus
Isolated
GroundBus

Attribute

NeutralBus

IfcBoolean

Type/Component

Attribute

EquipGroundBus

IfcBoolean

Type/Component

Attribute

IsolatedGroundBus IfcBoolean

Type/Component

Mounting

Attribute

MountingType

IfcText

Type/Component

AICRating
SpatialPlacem
ent
BasisOfDesign
Manufacturer
BasisOfDesign
ModelNumber

Attribute

AICRating

IfcText

Type/Component

(FromList)

Attribute

Placement

IfcText

Component

Attribute

BODManufacturer

IfcLabel

Type

Attribute

BODModel

IfcLabel

Type

(BasisofDesign)
(BasisofDesign)

Type/Component
Type/Component
Type/Component

Type/Component

Type/Component

32

http://www.wbdg.org/references/spie/111201/ElectricDistributionBoard_DISTRIBUTIONBOARD_DistributionPan
el_US/ElectricDistributionBoard_DISTRIBUTIONBOARD_DistributionPanel_USTypeProduct.html

20130312COBieGuidePublicv05

98


BasisOfDesign
Notes

(IfRequired)

Attribute

BODNotes

IfcText

Type

20130312COBieGuidePublicv05

99

4.3 Switchgear
ThefollowingminimumsetofinformationshallbeprovidedinConstructionDocumentsstagedesign
deliverablescheduleandreflectedintheCDStageCOBieDeliverable.
Table65MappingforMinimumSwitchgearTypeScheduleHeadings

COBieMapping

DesignSchedule
Sheet
Heading

Column

AttributeName

Attribute
Reference

Unit
SwitchgearTypeXX
Space#01

Component Name

IfcLabel

Type
SpecificationSectio
n

SwitchgearTypeXX

Component TypeName

IfcText

ifcText

Type

Location

(SpaceName)

Component SpaceName

Current

Amps

Attribute

Current

Voltage

Volts

Attribute

Voltage

Frequency

Hz

Attribute

Frequency

OperatingWeight

Kg

Attribute

OperatingWeight

IfcIdentifier
IfcElectricCurre
ntMeasure
IfcElectricVoltag
eMeasure
IfcFrequencyM
easure
IfcMassMeasur
e

TypeofSupport
HorizontalBus
Current
VerticalBus
Current
ShortCircuit
InterruptingRating

Attribute

Amps

Attribute

SupportType
HorizontalBusCurr
ent

Amps

Attribute

KAIC

Attribute

EnclosureRating
MinimumBus
Bracing

Attribute

KAIC

Attribute

(FromList)

Name

SpatialPlacement
BasisOfDesign
Manufacturer
BasisOfDesign
ModelNumber
BasisOfDesign
Notes

(BasisofDesign)
(BasisofDesign)
(IfRequired)

DataType

Attribute

TypeName

Type/Component
Type/Component
Type/Component
Type/Component

IfcText
IfcElectricCurre
ntMeasure
IfcElectricCurre
VerticalBusCurrent ntMeasure
ShortCircuitInterru IfcElectricCurre
ptingRating
ntMeasure

Type/Component

IfcText
IfcElectricCurre
ntMeasure

Type/Component

EnclosureRating
MinimumBusBraci
ng

Attribute

Placement

IfcText

Component

Attribute

BODManufacturer

IfcLabel

Type

Attribute

BODModel

IfcLabel

Type

Attribute

BODNotes

IfcText

Type

Type/Component
Type/Component
Type/Component

Type/Component

20130312COBieGuidePublicv05

100

4.4 Generator
ThefollowingminimumsetofinformationshallbeprovidedinConstructionDocumentsstagedesign
deliverablescheduleandreflectedintheCDStageCOBieDeliverable.COBiedatamappingisbasedon
COBieformatandcurrentSPietemplateElectricGenerator_STANDALONE_US33
Table66MappingforMinimumGeneratorTypeScheduleHeadings

COBieMapping

DesignSchedule
Sheet
Heading
Name
Type
SpecificationS
ection

Unit
GeneratorTypeXX
Space#01
GeneratorTypeXX

Column

AttributeName

Attribute
Reference

DataType
Component Name

IfcLabel

Component TypeName

IfcText

ifcText

Type

IfcIdentifier
IfcElectricCurrent
Measure
IfcElectricVoltageM
easure
IfcFrequencyMeas
ure

Attribute

TypeName

Location

(SpaceName)

Component SpaceName

Current

Amps

Attribute

Current

Voltage

Volts

Attribute

Voltage

Frequency
Operating
Weight
Typeof
Support
Maximum
PowerOutput

Hz

Attribute

Frequency

Kg

Attribute

OperatingWeight

Attribute

IfcText

Type/Component

KW

Attribute

SupportType
MaximumPowerOut
put

IfcPowerMeasure

Type/Component

FuelType
SpatialPlacem
ent
BasisOfDesign
Manufacturer
BasisOfDesign
ModelNumber
BasisOfDesign
Notes

Attribute

FuelType

IfcText

Type/Component

(FromList)

Attribute

Placement

IfcText

Component

Attribute

BODManufacturer

IfcLabel

Type

Attribute

BODModel

IfcLabel

Type

Attribute

BODNotes

IfcText

Type

(BasisofDesign)
(BasisofDesign)
(IfRequired)

IfcMassMeasure

Type/Component
Type/Component
Type/Component
Type/Component

33

http://www.wbdg.org/references/spie/110901/ElectricGenerator_STANDALONE_US/ElectricGenerator_STANDA
LONE_USTypeProduct.html

20130312COBieGuidePublicv05

101

5 Required Control System Assets


5.1 Sensors
ThefollowingminimumsetofinformationshallbeprovidedinConstructionDocumentsstagedesign
deliverablescheduleandreflectedintheCDStageCOBieDeliverable.COBiedatamappingisbasedon
COBieformatandcurrentSPietemplatesSensor_MOVEMENTSENSOR_US34and
Sensor_LIGHTSENSOR_US35.
Table67MappingforMinimumSensorsTypeScheduleHeadings

COBie Mapping

DesignSchedule
Heading

Unit

Sheet

Column

AttributeName

Attribute
Reference

DataType

SensorTypeXX
Space#01

Component Name

IfcLabel

Type
SpecificationS
ection

SensorTypeXX

Component TypeName

IfcText

ifcText

Type

Location

(SpaceName)

Component SpaceName

Current

Amps

Attribute

Current

Voltage

Volts

Attribute

Voltage

Frequency

Hz

Attribute

Frequency

IfcIdentifier
IfcElectricCurrent
Measure
IfcElectricVoltageM
easure
IfcFrequencyMeas
ure

Mounting
SpatialPlacem
ent
BasisOfDesign
Manufacturer
BasisOfDesign
ModelNumber
BasisOfDesign
Notes

Attribute

Mounting

IfcText

Type/Component

(FromList)

Attribute

Placement

IfcText

Component

Attribute

BODManufacturer

IfcLabel

Type

Attribute

BODModel

IfcLabel

Type

Attribute

BODNotes

IfcText

Type

Name

(BasisofDesign)
(BasisofDesign)
(IfRequired)

Attribute

TypeName

Type/Component
Type/Component
Type/Component

34

http://www.wbdg.org/references/spie/110901/Sensor_MOVEMENTSENSOR_US/Sensor_MOVEMENTSENSOR_U
STypeProduct.html
35
http://www.wbdg.org/references/spie/110901/Sensor_LIGHTSENSOR_US/Sensor_LIGHTSENSOR_USTypeProduct
.html

20130312COBieGuidePublicv05

102

5.2 Controllers
ThefollowingminimumsetofinformationshallbeprovidedinConstructionDocumentsstagedesign
deliverablescheduleandreflectedintheCDStageCOBieDeliverable.COBiedatamappingisbasedon
COBieformatandcurrentSPietemplateController_PROGRAMMABLE_US36.
Table68MappingforMinimumControllerTypeScheduleHeadings

COBieMapping

DesignSchedule
Sheet
Heading

Column

AttributeName

Attribute
Reference

Unit
ControllerTypeXX
Space#01

Component Name

IfcLabel

Type
SpecificationS
ection

ControllerTypeXX

Component TypeName

IfcText

ifcText

Type

Location

(SpaceName)

Component SpaceName

Current

Amps

Attribute

Current

Voltage

Volts

Attribute

Voltage

Frequency

Hz

Attribute

Frequency

IfcIdentifier
IfcElectricCurrent
Measure
IfcElectricVoltageM
easure
IfcFrequencyMeas
ure

Mounting
SpatialPlacem
ent
BasisOfDesign
Manufacturer
BasisOfDesign
ModelNumber
BasisOfDesign
Notes

Attribute

Mouting

IfcText

Type/Component

(FromList)

Attribute

Placement

IfcText

Component

Attribute

BODManufacturer

IfcLabel

Type

Attribute

BODModel

IfcLabel

Type

Attribute

BODNotes

IfcText

Type

Name

(BasisofDesign)
(BasisofDesign)
(IfRequired)

DataType

Attribute

TypeName

Type/Component
Type/Component
Type/Component

36

http://www.wbdg.org/references/spie/110901/Controller_PROGRAMMABLE_US/Controller_PROGRAMMABLE_
USTypeProduct.html

20130312COBieGuidePublicv05

103

6 Required Elevator System Assets


6.1 Elevator
ThefollowingminimumsetofinformationshallbeprovidedinConstructionDocumentsstagedesign
deliverablescheduleandreflectedintheCDStageCOBieDeliverable.COBiedatamappingisbasedon
COBieformatandcurrentSPietemplateTransportElement_ELEVATOR_US37.
Table69MappingforMinimumElevatorTypeScheduleHeadings

COBieMapping

DesignSchedule
Sheet
Heading

Column

AttributeName

Attribute
Reference

Unit
ElevatorTypeXX
Space#01

Component Name

IfcLabel

Type
SpecificationS
ection

ElevatorTypeXX

Component TypeName

IfcText

ifcText

Type

Location

(SpaceName)

Component SpaceName

Current

Amps

Attribute

Current

Voltage

Volts

Attribute

Voltage

Frequency

Hz

Attribute

Frequency

IfcIdentifier
IfcElectricCurrent
Measure
IfcElectricVoltageM
easure
IfcFrequencyMeas
ure

Capacity

Kg

Attribute

Capacity

IfcMassMeasure

Type/Component
Type/Component

Name

DataType

Attribute

TypeName

Type/Component
Type/Component
Type/Component

Speed

m/s

Attribute

Speed

IfcLinearVelocityM
easure

SCRHPRating
MGMotor
Power

Attribute

SCRHPRating

IfcText

Type/Component

KW

Attribute

Power

Type/Component

StartingAmps
Accelerating
Amps

Amps

Attribute

StartingAmps

Amps

Attribute

AcceleratingAmps

IfcPowerMeasure
IfcElectricCurrent
Measure
IfcElectricCurrent
Measure

Mach.RM
SpatialPlacem
ent
BasisOfDesign
Manufacturer
BasisOfDesign
ModelNumber
BasisOfDesign
Notes

KCal/hr

Attribute

MachRM

IfcPowerMeasure

Type/Component

(FromList)

Attribute

Placement

IfcText

Component

Attribute

BODManufacturer

IfcLabel

Type

Attribute

BODModel

IfcLabel

Type

Attribute

BODNotes

IfcText

Type

(BasisofDesign)
(BasisofDesign)
(IfRequired)

Type/Component
Type/Component

37

http://www.wbdg.org/references/spie/110901/TransportElement_ELEVATOR_US/TransportElement_ELEVATOR
_USTypeProduct.html

20130312COBieGuidePublicv05

104

7 Required Food Service System Assets


7.1 Sinks
ThefollowingminimumsetofinformationshallbeprovidedinConstructionDocumentsstagedesign
deliverablescheduleandreflectedintheCDStageCOBieDeliverable.COBiedatamappingisbasedon
COBieformatandcurrentSPietemplateSanitaryTerminal_SINK_PlumbingFixtures_US38.
Table70MappingforMinimumSinksTypeScheduleHeadings

COBieMapping

DesignSchedule
Sheet
Heading

Column

AttributeName

Attribute
Reference

Name

Unit
SinkTypeXX
Space#01

Component Name

IfcLabel

Type

SinkTypeXX

Component TypeName

IfcText

ifcText

Type

SpecificationSection

DataType

Attribute

TypeName

Location

(SpaceName)

Component SpaceName

IfcIdentifier

WaterInlet

Attribute

WaterInlet

IfcText

Type/Component

Drain

Attribute

Drain

IfcText

Type/Component

SpatialPlacement
BasisOfDesign
Manufacturer
BasisOfDesign
ModelNumber
BasisOfDesign
Notes

(FromList)

Attribute

Placement

IfcText

Component

Attribute

BODManufacturer

IfcLabel

Type

Attribute

BODModel

IfcLabel

Type

Attribute

BODNotes

IfcText

Type

(BasisofDesign)
(BasisofDesign)
(IfRequired)

38

http://www.wbdg.org/references/spie/111201/SanitaryTerminal_SINK_PlumbingFixtures_US/SanitaryTerminal_
SINK_PlumbingFixtures_USTypeProduct.html

20130312COBieGuidePublicv05

105

7.2 Waste Disposer


ThefollowingminimumsetofinformationshallbeprovidedinConstructionDocumentsstagedesign
deliverablescheduleandreflectedintheCDStageCOBieDeliverable.COBiedatamappingisbasedon
COBieformatandcurrentSPietemplateElectricAppliance_USERDEFINED_FoodServiceEquipment_US39.
Table71MappingforMinimumWasteDisposerTypeScheduleHeadings

COBieMapping

DesignSchedule
Sheet
Heading
Name
Type
SpecificationS
ection

Unit
WasteDisposer
TypeXXSpace#01
WasteDisposer
TypeXX

Column

AttributeName

Attribute
Reference

DataType
Component Name

IfcLabel

Component TypeName

IfcText

ifcText

Type

Attribute

TypeName

Location

(SpaceName)

Component SpaceName

Current

Amps

Attribute

Current

Voltage

Volts

Attribute

Voltage

Frequency

Hz

Attribute

Frequency

IfcIdentifier
IfcElectricCurrent
Measure
IfcElectricVoltageM
easure
IfcFrequencyMeas
ure

Power

kW

Attribute

Power

IfcPowerMeasure

Type/Component

Connection

Attribute

Connection

IfcText

Type/Component

WaterInlet

Attribute

WaterInlet

IfcText

Type/Component

Drain
SpatialPlacem
ent
BasisOfDesign
Manufacturer
BasisOfDesign
ModelNumber
BasisOfDesign
Notes

Attribute

Drain

IfcText

Type/Component

(FromList)

Attribute

Placement

IfcText

Component

Attribute

BODManufacturer

IfcLabel

Type

Attribute

BODModel

IfcLabel

Type

Attribute

BODNotes

IfcText

Type

(BasisofDesign)
(BasisofDesign)
(IfRequired)

Type/Component
Type/Component
Type/Component

39

http://www.wbdg.org/references/spie/110901/ElectricAppliance_USERDEFINED_FoodserviceEquipment_US/Ele
ctricAppliance_USERDEFINED_FoodserviceEquipment_USTypeProduct.html

20130312COBieGuidePublicv05

106

7.3 Dishwasher
ThefollowingminimumsetofinformationshallbeprovidedinConstructionDocumentsstagedesign
deliverablescheduleandreflectedintheCDStageCOBieDeliverable.COBiedatamappingisbasedon
COBieformatandcurrentSPietemplateElectricAppliance_DISHWASHER_US40.
Table72MappingforMinimumDishwasherTypeScheduleHeadings

COBieMapping

DesignSchedule
Sheet
Heading

Column

AttributeName

Attribute
Reference

Unit
DishwasherTypeXX
Space#01

Component Name

IfcLabel

Type
SpecificationS
ection

DishwasherTypeXX

Component TypeName

IfcText

ifcText

Type

Location

(SpaceName)

Component SpaceName

Current

Amps

Attribute

Current

Voltage

Volts

Attribute

Voltage

Frequency

Hz

Attribute

Frequency

IfcIdentifier
IfcElectricCurrent
Measure
IfcElectricVoltageM
easure
IfcFrequencyMeas
ure

Power

KW

Attribute

Power

IfcPowerMeasure

Type/Component

Connection

Attribute

Connection

IfcText

Type/Component

WaterInlet

Attribute

WaterInlet

IfcText

Type/Component

Drain
SpatialPlacem
ent
BasisOfDesign
Manufacturer
BasisOfDesign
ModelNumber
BasisOfDesign
Notes

Attribute

Drain

IfcText

Type/Component

(FromList)

Attribute

Placement

IfcText

Component

Attribute

BODManufacturer

IfcLabel

Type

Attribute

BODModel

IfcLabel

Type

Attribute

BODNotes

IfcText

Type

Name

(BasisofDesign)
(BasisofDesign)
(IfRequired)

DataType

Attribute

TypeName

Type/Component
Type/Component
Type/Component

40

http://www.wbdg.org/references/spie/110901/ElectricAppliance_DISHWASHER_US/ElectricAppliance_DISHWAS
HER_USTypeProduct.html

20130312COBieGuidePublicv05

107

7.4 Refrigerator
ThefollowingminimumsetofinformationshallbeprovidedinConstructionDocumentsstagedesign
deliverablescheduleandreflectedintheCDStageCOBieDeliverable.COBiedatamappingisbasedon
COBieformatandcurrentSPietemplateElectricAppliance_REFRIGERATOR_US41.
Table73MappingforMinimumRefrigeratorTypeScheduleHeadings

COBieMapping

DesignSchedule
Sheet
Heading
Name
Type
SpecificationSe
ction

Unit
Refrigerator
TypeXXSpace#01
Refrigerator
TypeXX

Column

AttributeName

Attribute
Reference

DataType
Component Name

IfcLabel

Component TypeName

IfcText

ifcText

Type

Attribute

TypeName

Location

(SpaceName)

Component SpaceName

Current

Amps

Attribute

Current

Voltage

Volts

Attribute

Voltage

Frequency

Hz

Attribute

Frequency

IfcIdentifier
IfcElectricCurrent
Measure
IfcElectricVoltageM
easure
IfcFrequencyMeas
ure

Power

KW

Attribute

Power

IfcPowerMeasure

Type/Component

Connection

Attribute

Connection

IfcText

Type/Component

WaterInlet

Attribute

WaterInlet

IfcText

Type/Component

Drain
SpatialPlaceme
nt
BasisOfDesign
Manufacturer
BasisOfDesign
ModelNumber
BasisOfDesign
Notes

Attribute

Drain

IfcText

Type/Component

(FromList)

Attribute

Placement

IfcText

Component

Attribute

BODManufacturer

IfcLabel

Type

Attribute

BODModel

IfcLabel

Type

Attribute

BODNotes

IfcText

Type

(BasisofDesign)
(BasisofDesign)
(IfRequired)

Type/Component
Type/Component
Type/Component

41

http://www.wbdg.org/references/spie/110901/ElectricAppliance_REFRIGERATOR_US/ElectricAppliance_REFRIGE
RATOR_USTypeProduct.html

20130312COBieGuidePublicv05

108

7.5 Icemaker
ThefollowingminimumsetofinformationshallbeprovidedinConstructionDocumentsstagedesign
deliverablescheduleandreflectedintheCDStageCOBieDeliverable.COBiedatamappingisbasedon
COBieformatandcurrentSPietemplateElectricAppliance_USERDEFINED_FoodServiceEquipment_US42.
Table74MappingforMinimumIcemakerTypeScheduleHeadings

COBieMapping

DesignSchedule
Sheet
Heading

Column

AttributeName

Attribute
Reference

Unit
IcemakerTypeXX
Space#01

Component Name

IfcLabel

Type
SpecificationSec
tion

IcemakerTypeXX

Component TypeName

IfcText

ifcText

Type

Location

(SpaceName)

Component SpaceName

Current

Amps

Attribute

Current

Voltage

Volts

Attribute

Voltage

Frequency

Hz

Attribute

Frequency

IfcIdentifier
IfcElectricCurrent
Measure
IfcElectricVoltageM
easure
IfcFrequencyMeas
ure

Power

KW

Attribute

Power

IfcPowerMeasure

Type/Component

Connection

Attribute

Connection

IfcText

Type/Component

WaterInlet

Attribute

WaterInlet

IfcText

Type/Component

Drain
SpatialPlaceme
nt
BasisOfDesign
Manufacturer
BasisOfDesign
ModelNumber
BasisOfDesign
Notes

Attribute

Drain

IfcText

Type/Component

(FromList)

Attribute

Placement

IfcText

Component

Attribute

BODManufacturer

IfcLabel

Type

Attribute

BODModel

IfcLabel

Type

Attribute

BODNotes

IfcText

Type

Name

(BasisofDesign)
(BasisofDesign)
(IfRequired)

DataType

Attribute

TypeName

Type/Component
Type/Component
Type/Component

42

http://www.wbdg.org/references/spie/110901/ElectricAppliance_USERDEFINED_FoodserviceEquipment_US/Ele
ctricAppliance_USERDEFINED_FoodserviceEquipment_USTypeProduct.html

20130312COBieGuidePublicv05

109

7.6 Range
ThefollowingminimumsetofinformationshallbeprovidedinConstructionDocumentsstagedesign
deliverablescheduleandreflectedintheCDStageCOBieDeliverable.COBiedatamappingisbasedon
COBieformatandcurrentSPietemplateElectricAppliance_ELECTRICCOOKER_US43.
Table75MappingforMinimumRangeTypeScheduleHeadings

COBieMapping

DesignSchedule
Sheet
Heading

Column

AttributeName

Attribute
Reference

Unit
RangeTypeXX
Space#01

Component Name

IfcLabel

Type
SpecificationSec
tion

RangeTypeXX

Component TypeName

IfcText

ifcText

Type

Location

(SpaceName)

Component SpaceName

Current

Amps

Attribute

Current

Voltage

Volts

Attribute

Voltage

Frequency

Hz

Attribute

Frequency

IfcIdentifier
IfcElectricCurrent
Measure
IfcElectricVoltageM
easure
IfcFrequencyMeas
ure

Power

kW

Attribute

Power

IfcPowerMeasure

Type/Component

Connection

Attribute

Connection

IfcText

Type/Component

Gas
SpatialPlaceme
nt
BasisOfDesign
Manufacturer
BasisOfDesign
ModelNumber
BasisOfDesign
Notes

Mbtu

Attribute

Gas

IfcEnergyMeasure

Type/Component

(FromList)

Attribute

Placement

IfcText

Component

Attribute

BODManufacturer

IfcLabel

Type

Attribute

BODModel

IfcLabel

Type

Attribute

BODNotes

IfcText

Type

Name

(BasisofDesign)
(BasisofDesign)
(IfRequired)

DataType

Attribute

TypeName

Type/Component
Type/Component
Type/Component

43

http://www.wbdg.org/references/spie/110901/ElectricAppliance_ELECTRICCOOKER_US/ElectricAppliance_ELECT
RICCOOKER_USTypeProduct.html

20130312COBieGuidePublicv05

110

7.7 Fryer
ThefollowingminimumsetofinformationshallbeprovidedinConstructionDocumentsstagedesign
deliverablescheduleandreflectedintheCDStageCOBieDeliverable.COBiedatamappingisbasedon
COBieformatandcurrentSPietemplateElectricAppliance_ELECTRICCOOKER_US44.
Table76MappingforMinimumFryerTypeScheduleHeadings

COBieMapping

DesignSchedule
Sheet
Heading

Column

AttributeName

Attribute
Reference

Unit
FryerTypeXX
Space#01

Component Name

IfcLabel

Type
SpecificationSec
tion

FryerTypeXX

Component TypeName

IfcText

ifcText

Type

Location

(SpaceName)

Component SpaceName

Current

Amps

Attribute

Current

Voltage

Volts

Attribute

Voltage

Frequency

Hz

Attribute

Frequency

IfcIdentifier
IfcElectricCurrent
Measure
IfcElectricVoltageM
easure
IfcFrequencyMeas
ure

Power

KW

Attribute

Power

IfcPowerMeasure

Type/Component

Connection

Attribute

Connection

IfcText

Type/Component

Gas
SpatialPlacemen
t
BasisOfDesign
Manufacturer
BasisOfDesign
ModelNumber
BasisOfDesign
Notes

Mbtu

Attribute

Gas

IfcEnergyMeasure

Type/Component

(FromList)

Attribute

Placement

IfcText

Component

Attribute

BODManufacturer

IfcLabel

Type

Attribute

BODModel

IfcLabel

Type

Attribute

BODNotes

IfcText

Type

Name

(BasisofDesign)
(BasisofDesign)
(IfRequired)

DataType

Attribute

TypeName

Type/Component
Type/Component
Type/Component

44

http://www.wbdg.org/references/spie/110901/ElectricAppliance_ELECTRICCOOKER_US/ElectricAppliance_ELECT
RICCOOKER_USTypeProduct.html

20130312COBieGuidePublicv05

111

7.8 Freezer
ThefollowingminimumsetofinformationshallbeprovidedinConstructionDocumentsstagedesign
deliverablescheduleandreflectedintheCDStageCOBieDeliverable.COBiedatamappingisbasedon
COBieformatandcurrentSPietemplateElectricAppliance_FREEZER_US45.
Table77MappingforMinimumFreezerTypeScheduleHeadings

COBieMapping

DesignSchedule
Sheet
Heading

Column

AttributeName

Attribute
Reference

Unit
FreezerTypeXX
Space#01

Component Name

IfcLabel

Type
SpecificationSec
tion

FreezerTypeXX

Component TypeName

IfcText

ifcText

Type

Location

(SpaceName)

Component SpaceName

Current

Amps

Attribute

Current

Voltage

Volts

Attribute

Voltage

Frequency

Hz

Attribute

Frequency

IfcIdentifier
IfcElectricCurrent
Measure
IfcElectricVoltageM
easure
IfcFrequencyMeas
ure

Power

kW

Attribute

Power

IfcPowerMeasure

Type/Component

Connection
SpatialPlacemen
t
BasisOfDesign
Manufacturer
BasisOfDesign
ModelNumber
BasisOfDesign
Notes

Attribute

Connection

IfcText

Type/Component

(FromList)

Attribute

Placement

IfcText

Component

Attribute

BODManufacturer

IfcLabel

Type

Attribute

BODModel

IfcLabel

Type

Attribute

BODNotes

IfcText

Type

Name

(BasisofDesign)
(BasisofDesign)
(IfRequired)

DataType

Attribute

TypeName

Type/Component
Type/Component
Type/Component

45

http://www.wbdg.org/references/spie/110901/ElectricAppliance_FREEZER_US/ElectricAppliance_FREEZER_USTy
peProduct.html

20130312COBieGuidePublicv05

112

8 Required Architectural Assets


8.1 Doors
ThefollowingminimumsetofinformationshallbeprovidedinConstructionDocumentsstagedesign
deliverablescheduleandreflectedintheCDStageCOBieDeliverable.COBiedatamappingisbasedon
COBieformatandcurrentSPietemplateWindowDoor_DOOR_SecurityDoorsandFrames_US46
Table78MappingforMinimumDoorTypeScheduleHeadings

COBieMapping

DesignSchedule
Sheet
Heading

Column

AttributeName

Attribute
Reference

Unit
DoorTypeXX
Space#01

Component Name

IfcLabel

Type
SpecificationSec
tion

DoorTypeXX

Component TypeName

IfcText

ifcText

Type

Location

(SpaceName)

DoorWidth

mm

DoorHeight

mm

DoorThickness

Name

DataType

Attribute

TypeName

mm

Component SpaceName
NominalLen
Type
gth
NominalHei
Type
ght
NominalThic
Type
kness

IfcIdentifier
IfcPositiveLengthM
easure
IfcPositiveLengthM
easure
IfcPositiveLengthM
easure

DoorType

Type

Name

IfcLabel

DoorMaterial

Type

Material

IfcLabel

DoorFinish

Type

Finish

IfcText

GlazingType

Attribute

Glazing

IfcText

Type

SecurityCode

Attribute

SecurityCode

IfcText

Type

FrameType

Attribute

FrameType

IfcText

Type/Component

FrameMaterial

Attribute

FrameMaterial

IfcText

Type/Component

FrameFinish

Attribute

FrameFinish

IfcText

Type/Component

FrameHead

Attribute

Head

IfcText

Type/Component

FrameJam

Attribute

Jam

IfcText

Type/Component

FrameSill

Attribute

Sill

IfcText

Type/Component

FireLabelClass

Attribute

Class

IfcLabel

Type

46

http://www.wbdg.org/references/spie/110901/Door_DOOR_SecurityDoorsandFrames_US/Door_DOOR_Security
DoorsandFrames_USTypeProduct.html

20130312COBieGuidePublicv05

113


FireLabel
Rating

Attribute

FireRating

IfcLabel

Type

HardwareSet

Attribute

HardwareSet

IfcText

Type/Component

Pressurization

Attribute

Pressurization

IfcBoolean

Type/Component

EgressDoor
SpatialPlaceme
nt
BasisOfDesign
Manufacturer
BasisOfDesign
ModelNumber
BasisOfDesign
Notes

Attribute

Egress

IfcBoolean

Type/Component

Attribute

IfcText

Component

Attribute

BODManufacturer

IfcLabel

Type

Attribute

BODModel

IfcLabel

Type

Attribute

BODNotes

IfcText

Type

(FromList)
(BasisofDesign)
(BasisofDesign)
(IfRequired)

8.2 Windows
ThefollowingminimumsetofinformationshallbeprovidedinConstructionDocumentsstagedesign
deliverablescheduleandreflectedintheCDStageCOBieDeliverable.COBiedatamappingisbasedon
COBieformatandcurrentSPietemplateWindow_WINDOW_SecurityWindows_US47
Table79MappingforMinimumWindowTypeScheduleHeadings

COBieMapping

DesignSchedule
Sheet
Heading

Column

AttributeName

Attribute
Reference

Unit
WindowTypeXX
Space#01

Component Name

IfcLabel

Type
SpecificationSec
tion

WindowTypeXX

Component TypeName

IfcText

ifcText

Type

Location
Window
Number

(SpaceName)

Component SpaceName

IfcIdentifier

Attribute

Name

IfcIdentifier

Type

SecurityCode

Attribute

SecurityCode

IfcText

Type

WindowRating

Attribute

Rating

IfcText

Type

GlazingType

Attribute

Glazing

Type

Type

NominalLength NominalLength

Type

NominalHeight NominalHeight

Type

NominalWidth

IfcText
IfcPositiveLength
Measure
IfcPositiveLength
Measure
IfcPositiveLength
Measure

Name

WindowSize
WindowSize
WindowSize

DataType

Attribute

TypeName

NominalThickness

Type
Type
Type

47

http://www.wbdg.org/references/spie/110901/Window_WINDOW_SecurityWindows_US/Window_WINDOW_S
ecurityWindows_USTypeProduct.html

20130312COBieGuidePublicv05

114


Window
Operation

Attribute

WindowOperation IfcText

Type/Component

FrameMaterial

Attribute

FrameMaterial

IfcText

Type/Component

UFactor

Attribute

Ufactor

IfcText

Type/Component

Attribute

Placement

IfcText

Component

Attribute

BODManufacturer IfcLabel

Type

Attribute

BODModel

IfcLabel

Type

Attribute

BODNotes

IfcText

Type

SpatialPlaceme
nt
BasisOfDesign
Manufacturer
BasisOfDesign
ModelNumber
BasisOfDesign
Notes

(FromList)
(BasisofDesign)
(BasisofDesign)
(IfRequired)

8.3 Finishes
ThefollowingminimumsetofinformationshallbeprovidedinConstructionDocumentsstagedesign
deliverablescheduleandreflectedintheCDStageCOBieDeliverable.
Table80MappingforMinimumFinishScheduleHeadings

COBieMapping

DesignSchedule
Sheet
Heading

Column

AttributeName

Unit

Attribute
Reference

DataType

Name

Type
SpecificationSec
tion

Attribute

TypeName

ifcText

Type

Location

(SpaceName)

Space

Name

IfcIdentifier

Space

Floor

Attribute

CoveringFloor

IfcLabel]

Space

Base

Attribute

CoveringBase

IfcLabel

Space

Walls

Attribute

IfcLabel

Space

CeilingType

Attribute

IfcLabel

Space

CeilingFinish

Attribute

CoveringWalls
ConveringCeilingT
ype
CoveringCeilingFi
nish

Space

CeilingHeight
SpatialPlaceme
nt
BasisOfDesign
Manufacturer
BasisOfDesign
ModelNumber
BasisOfDesign
Notes

mm

Attribute

CeilingHeight

IfcText
IfcPositiveLengthM
easure

Attribute

Placement

IfcText

Component

Attribute

BODManufacturer IfcLabel

Space

Attribute

BODModel

IfcLabel

Space

Attribute

BODNotes

IfcText

Type

(FromList)
(BasisofDesign)
(BasisofDesign)
(IfRequired)

Space

20130312COBieGuidePublicv05

115

9 Furnishing Assets
Whiletherearemanydifferenttypesoffurnishingassets,theycommonlyusethesametypeof
schedule.ThefollowingminimumsetofinformationshallbeprovidedinConstructionDocumentsstage
designdeliverablescheduleandreflectedintheCDStageCOBieDeliverable.COBiedatamappingis
basedonCOBieformatandcurrentSPietemplatesFurniture_SHELF_US48andFurniture_TABLE_US49.
Table81MappingforMinimumFurnishingAssetsScheduleHeadings

COBieMapping

DesignSchedule
Sheet
Heading
Name
Type
SpecificationSection

Unit
FurnishingAsset
TypeXXSpace#01
FurnishingAsset
TypeXX

(SpaceName)

Location

Column

AttributeName

Attribute
Reference

DataType
Component Name

IfcLabel

Component TypeName

IfcText

ifcText

Type

Attribute

TypeName

Component SpaceName

IfcIdentifier

GFCI

Attribute

GFCI

IfcBoolean

Type/Component

GFGI

Attribute

GFGI

IfcBoolean

Type/Component

CFCI

Attribute

CFCI

IfcBoolean

Type/Component

SpatialPlacement
BasisOfDesign
Manufacturer
BasisOfDesign
ModelNumber
BasisOfDesign
Notes

(FromList)

Attribute

Placement

IfcText

Component

Attribute

BODManufacturer IfcLabel

Type

Attribute

BODModel

IfcLabel

Type

Attribute

BODNotes

IfcText

Type

(BasisofDesign)
(BasisofDesign)
(IfRequired)

48
49

http://www.wbdg.org/references/spie/110901/Furniture_SHELF_US/Furniture_SHELF_USTypeProduct.html
http://www.wbdg.org/references/spie/110901/Furniture_TABLE_US/Furniture_TABLE_USTypeProduct.html

20130312COBieGuidePublicv05

116

10 Site Assets
10.1 Site Water Distribution System
10.1.1 Pumps
ThefollowingminimumsetofinformationshallbeprovidedinConstructionDocumentsstagedesign
deliverablescheduleandreflectedintheCDStageCOBieDeliverable.COBiedatamappingisbasedon
COBieformatandcurrentSPietemplatePump_CIRCULATOR_US50.
Table82MappingforMinimumPumpScheduleHeadings

DesignSchedule
Heading

Unit
PumpTypeXX
Space#01

Name
Type

PumpTypeXX

COBieMapping
Sheet

Column

AttributeName

Attribute
Reference

DataType

Component Name

IfcLabel

Component TypeName

IfcText

ifcText

Type

IfcIdentifier

SpecificationSec
tion

Location

(SpaceName)

Component SpaceName

Current

Amps

Attribute

Current

Voltage

Volts

Attribute

Voltage

Frequency

Hz

Attribute

Frequency

RatedFlow

L/s

Attribute

FlowRateRange

ChurnPressure kPa

Attribute

ChurnPressure

IfcElectricCurrentMea
sure
IfcElectricVoltageMea
sure
IfcFrequencyMeasure
IfcVolumetricFlowRate
Measure
IfcPressureMeasure

ControllerType

Attribute

ControllerType

IfcText

Type/Component

Attribute

Placement

IfcText

Component

Attribute

BODManufacturer IfcLabel

Type

Attribute

BODModel

IfcLabel

Type

Attribute

BODNotes

IfcText

Type

SpatialPlaceme
nt
BasisOfDesign
Manufacturer
BasisOfDesign
ModelNumber
BasisOfDesign
Notes

(FromList)
(BasisofDesign)
(BasisofDesign)
(IfRequired)

Attribute

TypeName

Type/Component
Type/Component
Type/Component
Type/Component
Type/Component

50

http://www.wbdg.org/references/spie/111201/Pump_CIRCULATOR_US/Pump_CIRCULATOR_USTypeProduct.ht
ml

20130312COBieGuidePublicv05

117


10.1.2 Tanks
ThefollowingminimumsetofinformationshallbeprovidedinConstructionDocumentsstagedesign
deliverablescheduleandreflectedintheCDStageCOBieDeliverable.COBiedatamappingisbasedon
COBieformatandcurrentSPietemplateTank_STORAGE_US51.
Table83MappingforMinimumTanksScheduleHeadings

COBieMapping

DesignSchedule
Sheet
Heading

Column

AttributeName

Attribute
Reference

Name

Unit
TankTypeXX
Space#01

Component Name

IfcLabel

Type

TankTypeXX

Component TypeName

IfcText

ifcText

Type

SpecificationSection

DataType

Attribute

TypeName

Location

(SpaceName)

Component SpaceName

IfcIdentifier

AccessType

Attribute

AccessType

IfcLabel

Type/Component

StorageType

Attribute

StorageType

IfcLabel

Type/Component

Capacity

Attribute

NominalCapacity

IfcVolumeMeasure

Type/Component

SpatialPlacement
BasisOfDesign
Manufacturer
BasisOfDesign
ModelNumber
BasisOfDesign
Notes

(FromList)

Attribute

Placement

IfcText

Component

Attribute

BODManufacturer IfcLabel

Type

Attribute

BODModel

IfcLabel

Type

Attribute

BODNotes

IfcText

Type

(BasisofDesign)
(BasisofDesign)
(IfRequired)

51

http://www.wbdg.org/references/spie/110901/Tank_STORAGE_US/Tank_STORAGE_USTypeProduct.html

20130312COBieGuidePublicv05

118

10.2 Site Fire Suppression System


10.2.1 Hydrants
ThefollowingminimumsetofinformationshallbeprovidedinConstructionDocumentsstagedesign
deliverablescheduleandreflectedintheCDStageCOBieDeliverable.COBiedatamappingisbasedon
COBieformatandcurrentSPietemplateFireSuppressionTerminal_FIREHYDRANT_US52.
Table84MappingforMinimumHydrantScheduleHeadings

COBieMapping

DesignSchedule
Sheet
Heading
Name
Type
SpecificationS
ection

AttributeName

Attribute
Reference

Component Name

IfcLabel

HydrantTypeXX

Component TypeName

IfcText

ifcText

Type

(SpaceName)

Location

Column

Unit
HydrantTypeXX
Space#01

DataType

Attribute

TypeName

FlowRate
Pressure
Rating

Attribute

IfcIdentifier
IfcVolumetricFlowRate
DischargeFlowRate Measure

Attribute

PressureRating

IfcPressureMeasure

Type/Component

BodyColor

Attribute

BodyColor

IfcText

Type/Component

CapColor
SpatialPlacem
ent
BasisOfDesign
Manufacturer
BasisOfDesign
ModelNumber
BasisOfDesign
Notes

Attribute

CapColor

IfcText

Type/Component

(FromList)

Attribute

Placement

IfcText

Component

Attribute

BODManufacturer

IfcLabel

Type

Attribute

BODModel

IfcLabel

Type

Attribute

BODNotes

IfcText

Type

(BasisofDesign)
(BasisofDesign)
(IfRequired)

Component SpaceName

Type/Component

52

http://www.wbdg.org/references/spie/110901/FireSuppressionTerminal_FIREHYDRANT_US/FireSuppressionTer
minal_FIREHYDRANT_USTypeProduct.html

20130312COBieGuidePublicv05

119

10.3 Water Supply Wells


10.3.1 Pumps
ThefollowingminimumsetofinformationshallbeprovidedinConstructionDocumentsstagedesign
deliverablescheduleandreflectedintheCDStageCOBieDeliverable.COBiedatamappingisbasedon
COBieformatandcurrentSPietemplatePump_CIRCULATOR_US53.
Table85MappingforMinimumPumpScheduleHeadings

DesignSchedule
Heading

Unit
PumpTypeXX
Space#01

Name
Type

PumpTypeXX

COBieMapping
Sheet

Column

AttributeName

Attribute
Reference

DataType

Component Name

IfcLabel

Component TypeName

IfcText

ifcText

Type

IfcIdentifier

SpecificationSec
tion

Location

(SpaceName)

Component SpaceName

Current

Amps

Attribute

Current

Voltage

Volts

Attribute

Voltage

Frequency

Hz

Attribute

Frequency

RatedFlow

L/s

Attribute

FlowRateRange

ChurnPressure kPa

Attribute

ChurnPressure

IfcElectricCurrentMea
sure
IfcElectricVoltageMea
sure
IfcFrequencyMeasure
IfcVolumetricFlowRate
Measure
IfcPressureMeasure

ControllerType

Attribute

ControllerType

IfcText

Type/Component

Attribute

Placement

IfcText

Component

Attribute

BODManufacturer IfcLabel

Type

Attribute

BODModel

IfcLabel

Type

Attribute

BODNotes

IfcText

Type

SpatialPlaceme
nt
BasisOfDesign
Manufacturer
BasisOfDesign
ModelNumber
BasisOfDesign
Notes

(FromList)
(BasisofDesign)
(BasisofDesign)
(IfRequired)

Attribute

TypeName

Type/Component
Type/Component
Type/Component
Type/Component
Type/Component

53

http://www.wbdg.org/references/spie/111201/Pump_CIRCULATOR_US/Pump_CIRCULATOR_USTypeProduct.ht
ml

20130312COBieGuidePublicv05

120

10.4 Site Sanitary Sewer


10.4.1 Manholes
ThefollowingminimumsetofinformationshallbeprovidedinConstructionDocumentsstagedesign
deliverablescheduleandreflectedintheCDStageCOBieDeliverable.COBiedatamappingisbasedon
COBieformatandcurrentSPietemplateDistributionChamberElement_MANHOLE_US54.
Table86MappingforMinimumManholeScheduleHeadings

COBieMapping

DesignSchedule
Sheet
Heading

Column

AttributeName

Attribute
Reference

Name

Unit
ManholeTypeXX
Space#01

Component Name

IfcLabel

Type

ManholeTypeXX

Component TypeName

IfcText

ifcText

Type

SpecificationSection

DataType

Attribute

TypeName

Location
NorthCoordinate
(Y)

(SpaceName)

Component SpaceName

IfcIdentifier

Attribute

NorthCoordinate

IfcIdentifier

Type/Component

EastCoordinate(X)

Attribute

EastCoordinate

IfcIdentifier

Type/Component

Top

Attribute

Top

IfcReal

Type/Component

Inv.In

Attribute

InvIn

IfcReal

Type/Component

Inv.Out

Attribute

InvOut

IfcReal

Type/Component

SpatialPlacement
BasisOfDesign
Manufacturer
BasisOfDesign
ModelNumber
BasisOfDesign
Notes

(FromList)

Attribute

Placement

IfcText

Component

Attribute

BODManufacturer IfcLabel

Type

Attribute

BODModel

IfcLabel

Type

Attribute

BODNotes

IfcText

Type

(BasisofDesign)
(BasisofDesign)
(IfRequired)

54

http://www.wbdg.org/references/spie/110901/DistributionChamberElement_MANHOLE_US/DistributionChamb
erElement_MANHOLE_USTypeProduct.html

20130312COBieGuidePublicv05

121


10.4.2 Pumps
ThefollowingminimumsetofinformationshallbeprovidedinConstructionDocumentsstagedesign
deliverablescheduleandreflectedintheCDStageCOBieDeliverable.COBiedatamappingisbasedon
COBieformatandcurrentSPietemplatePump_CIRCULATOR_US55.
Table87MappingforMinimumPumpScheduleHeadings

DesignSchedule
Heading

Unit
PumpTypeXX
Space#01

Name
Type

PumpTypeXX

COBieMapping
Sheet

Column

AttributeName

Attribute
Reference

DataType

Component Name

IfcLabel

Component TypeName

IfcText

ifcText

Type

IfcIdentifier

SpecificationSec
tion

Location

(SpaceName)

Component SpaceName

Current

Amps

Attribute

Current

Voltage

Volts

Attribute

Voltage

Frequency

Hz

Attribute

Frequency

RatedFlow

L/s

Attribute

FlowRateRange

ChurnPressure kPa

Attribute

ChurnPressure

IfcElectricCurrentMea
sure
IfcElectricVoltageMea
sure
IfcFrequencyMeasure
IfcVolumetricFlowRate
Measure
IfcPressureMeasure

ControllerType

Attribute

ControllerType

IfcText

Type/Component

Attribute

Placement

IfcText

Component

Attribute

BODManufacturer IfcLabel

Type

Attribute

BODModel

IfcLabel

Type

Attribute

BODNotes

IfcText

Type

SpatialPlaceme
nt
BasisOfDesign
Manufacturer
BasisOfDesign
ModelNumber
BasisOfDesign
Notes

(FromList)
(BasisofDesign)
(BasisofDesign)
(IfRequired)

Attribute

TypeName

Type/Component
Type/Component
Type/Component
Type/Component
Type/Component

55

http://www.wbdg.org/references/spie/111201/Pump_CIRCULATOR_US/Pump_CIRCULATOR_USTypeProduct.ht
ml

20130312COBieGuidePublicv05

122


10.4.3 Tanks
ThefollowingminimumsetofinformationshallbeprovidedinConstructionDocumentsstagedesign
deliverablescheduleandreflectedintheCDStageCOBieDeliverable.COBiedatamappingisbasedon
COBieformatandcurrentSPietemplateTank_STORAGE_US56.
Table88MappingforMinimumTankScheduleHeadings

COBieMapping

DesignSchedule
Sheet
Heading

Column

AttributeName

Attribute
Reference

Name

Unit
TankTypeXX
Space#01

Component Name

IfcLabel

Type

TankTypeXX

Component TypeName

IfcText

ifcText

Type

SpecificationSection

DataType

Attribute

TypeName

Location

(SpaceName)

Component SpaceName

IfcIdentifier

AccessType

Attribute

AccessType

IfcLabel

Type/Component

StorageType

Attribute

StorageType

IfcLabel

Type/Component

Capacity

Attribute

NominalCapacity

IfcVolumeMeasure

Type/Component

SpatialPlacement
BasisOfDesign
Manufacturer
BasisOfDesign
ModelNumber
BasisOfDesign
Notes

(FromList)

Attribute

Placement

IfcText

Component

Attribute

BODManufacturer IfcLabel

Type

Attribute

BODModel

IfcLabel

Type

Attribute

BODNotes

IfcText

Type

(BasisofDesign)
(BasisofDesign)
(IfRequired)

56

http://www.wbdg.org/references/spie/110901/Tank_STORAGE_US/Tank_STORAGE_USTypeProduct.html

20130312COBieGuidePublicv05

123

10.5 Fuel Distribution


10.5.1 Fuel Pumps
ThefollowingminimumsetofinformationshallbeprovidedinConstructionDocumentsstagedesign
deliverablescheduleandreflectedintheCDStageCOBieDeliverable.COBiedatamappingisbasedon
COBieformatandcurrentSPietemplatePump_SUBMERSIBLEPUMP_US57.
Table89MappingforMinimumFuelPumpScheduleHeadings

COBieMapping

DesignSchedule
Sheet
Heading

Column

AttributeName

Attribute
Reference

Unit
FuelPumpTypeXX
Space#01

Component Name

IfcLabel

Type
SpecificationS
ection

FuelPumpTypeXX

Component TypeName

IfcText

ifcText

Type

Location

(SpaceName)

Component SpaceName

Current

Amps

Attribute

Current

Voltage

Volts

Attribute

Voltage

IfcIdentifier
IfcElectricCurrentMea
sure
IfcElectricVoltageMea
sure

Frequency

Hz

Attribute

Frequency

IfcFrequencyMeasure

Type/Component

Service

Attribute

Service

Type/Component

FlowRateMin

L/s

Attribute

FlowRateRange

FlowRateMax L/s

Attribute

FlowRateRange

IfcText
IfcVolumetricFloeRate
Measure
IfcVolumetricFloeRate
Measure

TotalHead
Rotation
Speed

Attribute

Attribute

IfcLengthMeasure
IfcRotationalFrequenc
yMeasure

Type/Component

RPM

TotalHead
NominalRotationS
peed

Power

kW

Attribute

Power

IfcPowerMeasure

Type/Component

Phase
SpatialPlacem
ent
BasisOfDesign
Manufacturer
BasisOfDesign
ModelNumber
BasisOfDesign
Notes

Attribute

PhaseReference

IfcLabel

Type/Component

(FromList)

Attribute

Placement

IfcText

Component

Attribute

BODManufacturer IfcLabel

Type

Attribute

BODModel

IfcLabel

Type

Attribute

BODNotes

IfcText

Type

Name

(BasisofDesign)
(BasisofDesign)
(IfRequired)

DataType

Attribute

TypeName

Type/Component
Type/Component

Type/Component
Type/Component

Type/Component

57

http://www.wbdg.org/references/spie/110901/Pump_SUBMERSIBLEPUMP_US/Pump_SUBMERSIBLEPUMP_UST
ypeProduct.html

20130312COBieGuidePublicv05

124


10.5.2 Fuel Tanks
ThefollowingminimumsetofinformationshallbeprovidedinConstructionDocumentsstagedesign
deliverablescheduleandreflectedintheCDStageCOBieDeliverable.COBiedatamappingisbasedon
COBieformatandcurrentSPietemplateTank_STORAGE_US58.
Table90MappingforMinimumFuelTankScheduleHeadings

COBieMapping

DesignSchedule
Sheet
Heading

Column

AttributeName

Attribute
Reference

Name

Unit
FuelTankTypeXX
Space#01

Component Name

IfcLabel

Type

FuelTankTypeXX

Component TypeName

IfcText

ifcText

Type

SpecificationSection

DataType

Attribute

TypeName

Location

(SpaceName)

Component SpaceName

IfcIdentifier

AccessType

Attribute

AccessType

IfcLabel

Type/Component

Service

Attribute

StorageType

IfcLabel

Type/Component

FuelType

Attribute

FuelType

IfcText

Type/Component

Capacity

Attribute

NominalCapacity

IfcVolumeMeasure

Type/Component

DryWeight

Kg

Attribute

DryWeight

IfcMassMeasure

Type/Component

WetWeight

Kg

Attribute

WetWeight

IfcMassMeasure

Type/Component

SpatialPlacement
BasisOfDesign
Manufacturer
BasisOfDesign
ModelNumber
BasisOfDesign
Notes

(FromList)

Attribute

Placement

IfcText

Component

Attribute

BODManufacturer IfcLabel

Type

Attribute

BODModel

IfcLabel

Type

Attribute

BODNotes

IfcText

Type

(BasisofDesign)
(BasisofDesign)
(IfRequired)

58

http://www.wbdg.org/references/spie/110901/Tank_STORAGE_US/Tank_STORAGE_USTypeProduct.html

20130312COBieGuidePublicv05

125