Min.AcceptableSpecificationofCurrentTransformerforMetering:
Sr.
No
Particulars
11kV
33kV
132kV
220kV
HighestSystemVoltage
(kVrms)
12
36
145
245
CTratio.
20001000/11
800400/11
400/11
800/11
1600800/11
600300/11
1200600/11
400200/11
800400/11
300150/11
600300/11
10050/11
400200/11
300150/11
15075/11
Numberofmetering
cores
TwoNos
TwoNos
TwoNos
TwoNos
Ratedcontinuous
thermalcurrent.
120%of
rated
primary
current
120%of
rated
primary
current
120%of
rated
primary
current
120%of
rated
primary
current
Ratedshorttimethermal
currentofprimaryfor1
sec.(kA)
25
25
31.5
40
CTcharacteristics:a)
Ratedprimarycurrent
(Amps.)
20001000
800400
400
800
1600800
600300
1200600
400200
800400
300150
600300
10050
400200
300150
15075
(b)RatedSecondary
current(Amps.)
(c)Classofaccuracy.
0.2
0.2
0.2
0.2
(d)Max.instrument
securityfactor
(e)Ratedburden(VA).
30
30
30
40
IStowhichCTconforms.
IStowhichinsulatingoil
conforms.
Min.AcceptableSpecificationofVoltageTransformerforMetering:
Sr.
No
Particulars
245kV
CVTs
145kV
CVTs
HighestSystemVoltage
(kV)
245kV
145
kV
RatedCapacitance(pF)
4400pfwithtolerance+10%
and5%
Forlowvoltageterminal
overentirecarrier
frequencyrange.
(a)Straycapacitance
Shallnotexceed200pf
(b)Strayconductance
Shallnotexceed20us
(a)Highfrequency
capacitancefor
entirecarrierfrequency
range
within80%to150%ofrated
capacitance
(b)Equivalentseries
resistanceovertheentire
frequencyrange.
lessthan40Ohms
No.ofsecondary
windingsforpotential
device.
Two
Transformationratio:
(i)WindingI
20kV\/3/110\/3V
(ii)WindingII
20kV\/3/110\/3V
Ratedsecondaryburden
(i)WindingI(VA)
50VA
50VA
(ii)WindingII(VA)
50VA
50VA
AccuracyClass:
(i)WindingI(VA)
0.2formetering
(ii)WindingII(VA)
0.2formetering
Voltagefactorfor
windingIVoltage
factorforwindingII
1.2Cont.&1.5for30secs.1.2
Cont.&1.5for30secs.
10
IStowhichCVTs
conform.
IS3156withlatest
amendment
11
IStowhichInsulating
Oilconform.
IS335withlatest
amendment
Two
MinimumAcceptableSpecificationofSinglePhasePTforMetering:
Sr.No
Particulars
33kV
11kV
HighestSystemVoltage(kVrms)
36
12
Transformationratio.
33kV/
V3/110/
V3
11kV/110V
Numberofwindings.
Two
Two
Ratedoutput/burden(VA)per
winding/phase.
50
50
Accuracyclass.(At10to100%of
VAburden)
0.2
0.2
Ratedvoltagefactorand
duration.
1.2continuous&1.5for30
secs.
IStowhichPTconforms.
3156withlatest
amendment
YouMayLike
1.
FILEDUNDERUNCATEGORIZED
AboutJignesh.Parmar
JigneshParmarhascompletedM.Tech(PowerSystemControl),B.E(Electrical)fromGujaratUniversity.Hehasmorethan13years
experienceinPowerTransmissionPowerDistributionElectricalenergytheftdetectionElectricalMaintenanceElectrical
Projects(PlanningDesigningcoordinationExecution).HeisPresentlyassociatewithoneoftheleadingbusinessgroupasaDeputy
ManageratAhmedabad,India.HeisFreelancerProgrammerofAdvanceExcelanddesignusefulExcelSheetsofElectrical
EngineeringasperIS,NEC,IEC,IEEEcodes.HeistechnicalAuthorforElectricalMirrorandElectricalIndiaMagazines.Heis
TechnicalBloggerandFamiliarwithEnglish,Hindi,Gujarati,Frenchlanguages.HewantstoSharehisexperience&knowledgeand
helptechnicalenthusiaststofindsuitablesolutionsandupdatingthemselvesonvariousEngineeringTopics.
4ResponsestoMinimumAcceptableSpecificationofC.T&P.TforMetering
waqasahmedsays:
April2,2011at5:18am
dearsir!!
yourpostareveryinformative..irequestyoutopleaseguideusonrealytestingfordifferentschemesofcableandOHTL
protection..pleaseshareusyourpracticalknowledge..
Regards
WaqasAhmed
Reply
rajivpandeysays:
May10,2011at4:26am
Itisreallyinformative.Pleaseguidemeaboutthefollowing:
Wehaveanewsteelplantcomingupinthestateofwestbengal.Theplantisstillininstallation&commissioningstage.Wehave
erectedone220KVlinefromsupplyingutilitytothe220/33KVMainreceivingstationoftheplant.theCTratiointhelineis
400/1,0.2Class.Weneedabout1.5MVAatpresenttokeeptheMRSchargedandforcommissioningoffewoftheequipment.
However,supplyingutilityhastoldusthattheywillnotbeabletosupplylessthan5MVAinthe220KVline,assupplyofless
than5MVAmaycauseerrorinmetering.Kindlyguideuswhetherthestandofsupplyingutilityiscorrectornotwithreasoning.
Regards,
Rajiv
Reply
rcsays:
July30,2011at12:05pm
Verygood.keepitup
Reply
parijatsays:
December16,2014at5:46pm
inmaharastraitisrequiredtoputcheckmeterontheconsumersideforhighMDcosumer.pleasecouldutellmeitspossibleto
connectwithsamecoreofctorPTorwehavetoinsatallseparatemeteringtemple
Reply
CreateafreewebsiteorblogatWordPress.com.
TheEnterpriseTheme.
Follow
FollowElectricalNotes&Articles
BuildawebsitewithWordPress.com