Series 751
30.01
Series 751
European Trim
Certifications/Listings:
1026
104f/01
1026
See Victaulic Publication 10.01 for more details.
1026
1026
Product Description:
The Victaulic Series 751 alarm check valve works as
a check valve by preventing the reverse flow of water
from the system piping to the water supply. The valve is
trimmed with a water bypass line, which has an in-line
swing check valve. The bypass line allows pressure
surges to enter the system and to be trapped above the
alarm check valves clapper without the clapper lifting
and causing false alarms.
NOTE: The Series 751 FireLock Alarm Check Valve is also available as part of
the FireLock European Alarm Check Valve Station (Vds, CE, LCPB, GOST).
See page 11 for details.
Job/Owner
Engineer
System No.
Spec Section
Location
Paragraph
Contractor
Approved
Submitted By
Date
Date
Clapper
Seat
Alarm
Outlet
Alarm
Test
victaulic.com
A
B
H
C
Actual
Nominal Outside
Size
Diameter
inches
inches
mm
mm
11/2
1.900
40
48.3
2
2.375
50
60.3
21/2
2.875
65
73.0
3.000
76.1mm
76.1
3
3.500
80
88.9
4
4.500
100
114.3
6
6.625
150
168.3
6.500
165.1mm
165.1
8
8.625
200
219.1
Dimensions
E to E
A
inches
mm
9.00
228.60
9.00
228.60
12.61
320.29
12.61
320.29
12.61
320.29
15.03
381.76
16.00
406.40
16.00
406.40
17.50
444.50
victaulic.com
Approx.
Weight
Each
Height
B
inches
mm
18.50
470
18.50
470
22.50
572
22.50
572
22.50
572
23.50
597
24.00
610
24.00
610
26.00
660
Width
C
inches
mm
21.00
533
21.00
533
23.50
597
23.50
597
23.50
597
29.00
737
30.11
765
30.11
765
30.00
762
Depth
D
inches
mm
12.50
318
12.50
318
13.50
343
13.50
343
13.50
343
14.00
356
17.28
439
17.28
439
18.00
457
E
inches
mm
10.00
254
10.00
254
11.25
286
11.25
286
11.25
286
13.50
343
14.25
362
14.25
362
15.25
387
F
inches
mm
11.00
279
11.00
279
12.00
305
12.00
305
12.00
305
15.00
381
16.00
406
16.00
406
16.00
406
G
inches
mm
9.00
229
9.00
229
9.00
229
9.00
229
9.00
229
10.00
254
10.00
254
10.00
254
10.00
254
H
inches
mm
5.00
127
5.00
127
5.00
127
5.00
127
5.00
127
5.80
147
5.88
149
5.88
149
16.00
406
J
inches
mm
5.00
127
5.00
127
5.00
127
5.00
127
5.00
127
5.80
147
6.02
153
6.02
153
10.00
254
Without
Trim
lbs.
kg
14.2
6.4
14.6
6.6
34.4
15.6
34.4
15.6
35.3
16.0
49.0
22.2
69.0
31.3
69.0
31.3
142
64.4
With
Trim
lbs.
kg
31.0
14.1
31.0
14.1
52.0
23.6
52.0
23.6
52.0
23.6
80.0
36.3
91.0
41.3
95.0
43.1
182
82.6
165
.1m
8"/20
0mm
and
6"/
150
mm
m
0m
10
mm
an
d7
6.1
mm
4"/
1.0
0.9
0.8
0.7
0.6
0.5
0.4
3"/
80
2"/
50m
m
2
"
"/4
/65
mm
0m
m
2.0
3.0
6.0
5.0
4.0
0.3
0.2
0.1
10
20
30
40
60
80 100
200
300 400
600
1,000
2,000
800
4,000 6,000
3,000
Frictional Resistance
The chart below expresses the frictional resistance of
Victaulic Series 751 Alarm Check Valve in equivalent feet
of straight pipe.
Nominal
Size
inches
mm
11/2
40
2
50
21/2
65
76.1mm
3
80
4
100
6
150
165.1mm
8
200
Actual
Outside
Diameter
inches
mm
1.900
48.3
2.875
60.3
2.875
73.0
3.000
76.1
3.500
88.9
4.500
114.3
6.625
168.3
6.500
165.1
8.625
219.1
victaulic.com
Equivalent
Length of
Pipe
feet
meters
3
0.910
9
2.740
8.00
2.438
8.00
2.438
17.00
5.182
21.00
6.401
22.00
6.706
22.00
6.706
50.00
15.240
10,000
8,000
20,000
victaulic.com
4 - 6"
2
1 - 3 & 8"
10
4
10
8
7
5
6
11
14
13
12
Bill of Materials
1 Valve Body
1 Valve Body
2
3
4
5
15
BILL OF MATERIALS
9 Clapper Spring
2 Clapper
10 Spacers (Qty. 2)
Clapper 3 Clapper Seal
4 Seal Ring
11 Clapper Shaft
Clapper Seal
5 Seal Washer (Not Used on 1 - 2" [40 - 50-mm] Valves)
12 Clapper Shaft Retaining Plug (Qty.
Seal Ring6 Seal-Retaining Ring
7 Seal-Assembly Bolt
13 Cover Plate
Seal Washer
8 Bolt Seal
6 Seal-Retaining Ring
7 Seal-Assembly Bolt
8 Bolt Seal
victaulic.com
9
10
11
12
13
14
2)
15
Clapper Spring
Spacers (Qty. 2)
Clapper Shaft
Clapper Shaft Retaining Plug (Qty. 2)
Cover Plate
Cover Plate Gasket
Cover Plate Bolts (Qty. 7)
victaulic.com
10
15
13
2
To Water Motor
Alarm or Optional
Series 752V Retard
Vent Kit
15
Optional Location
for Item 13
To
System
Pipe to
Open Drain
5
14
Bill of Materials
1
Series 751 FireLock Alarm Check Valve
2
Water Supply Pressure Gauge
(0-300 psi/0-2068 kPa)
3
Swing Check Valve
4
System Pressure Gauge
(0-300 psi/0-2068 kPa)
5
Alarm Line Ball Valve (Normally Open)
6
Alarm Test Line Ball Valve
(Normally Closed)
7
Alarm Line Drain Restrictor (116-inch)
8
System Main Drain Valve
9
Series 752 Retard Chamber Assembly
(Optional/Sold Separately)
10
Series 760 Water Motor Alarm
(Optional/Sold Separately)
11
Water Supply Main Control Valve
(Optional/Sold Separately)
12
FireLock Rigid Coupling (Optional/Sold
Separately)
13
Alarm Pressure Switch (Optional/Sold
Separately)
14
Series 752V Retard Vent Kit (Optional/Sold
Separately) *
15
Gauge Valve
6
8
12
To Drain
To Drain
11
From Water
Supply
Bill of Materials
15 Gauge Valve
victaulic.com
From Excess
Pressure Pump
ill of Materials
1
Series 751 FireLock Alarm Check Valve
2
Water Supply Pressure Gauge
(0-300 psi/0-2068 kPa)
3
Swing Check Valve
4
System Pressure Gauge
(0-300 psi/0-2068 kPa)
5
Alarm Line Ball Valve (Normally Open)
6
Alarm Test Line Ball Valve
(Normally Closed)
7
Alarm Line Drain Restrictor (1/16-inch)
8
System Main Drain Valve
9
Series 760 Water Motor Alarm
(Optional/Sold Separately)
0
Water Supply Main Control Valve
(Optional/Sold Separately Comes
Standard when VQR Assembly is Ordered)
1
FireLock Rigid Coupling (Optional/Sold
Separately Comes Standard when VQR
Assembly is Ordered)
2
Alarm Pressure Switch (Optional/Sold
Separately)
3
Excess Pressure Pump Pressure Switch
(Sold Separately/Not Provided by Victaulic)
4
Excess Pressure Pump Isolation Ball Valve
(Normally Open)
5
Excess Pressure Pump Pressure Switch
Isolation Ball Valve (Normally Open)
Optional Location
for Item 12
To
System
To Excess
Pressure Pump
To Drain
To Drain
From Water
Supply
Bill of Materials
10 Water Supply Main Control Valve (Optional/Sold
Separately Comes Standard when VQR Assembly
is Ordered)
victaulic.com
Clapper
Alarm
Outlet
Seat
victaulic.com
10
B1
A
A1
G
E
F
Dimensions
A1
B1
cm
cm
cm
cm
cm
cm
cm
cm
cm
cm
cm
cm
cm
Approx.
Weight
Each
kg
DN80
32.03
42.24
71.86
14.48
21.21
22.11
27.56
4.67
18.64
26.93
27.97
24.0
DN100
38.18
50.66
57.88
75.97
16.13
22.33
24.45
26.68
2.14
19.33
27.14
30.37
7.22
54.0
DN150
40.64
56.32
64.44
79.38
18.60
25.77
26.93
31.79
20.30
28.11
31.08
8.12
69.0
DN200
44.45
58.65
85.80
16.66
28.34
26.81
34.39
23.85
30.87
34.56
83.0
Size
1 The A dimension is the measurement from the top of the valve body to the bottom of the valve body (takeout dimension).
NOTE: Overall height B is greatest height if optional retard chamber is not installed.
victaulic.com
11
DN
150
N2 0
6"/
8"/D
0.1
0.01
00
DN
1
80
DN
3"/
4"/
100
1,000
10,000
100,000
Frictional Resistance
The chart below expresses the frictional resistance of
Victaulic Series 751 Alarm Check Valve in equivalent
meters of straight pipe.
Nominal
Size
Equivalent
Length of
Pipe
mm
meters
80
5.18
100
6.40
150
6.70
200
15.24
victaulic.com
12
Trim Packages:
victaulic.com
13
Bill of Materials
victaulic.com | Alarm
Check
Valve | Series 751 | Publication 830.01
1 Valve
Body
Bolt Seal
2
5
6
7
Clapper Spring
Clapper Seal
Seal Retaining Ring
9
10
11
12
13
14
Seal-Assembly Bolt
Cover Plate Gasket
Cover Plate
Cover Plate Bolt (Qty. 7)
Seal Ring
Seal Washer
2
3
5
10
11
12
7
8
9
14
13
7
8
9
Bill of Materials
1 Valve Body
8 Bolt Seal
9 Seal-Assembly Bolt
3 Clapper Shaft
4 Clapper
11 Cover Plate
5 Clapper Spring
6 Clapper Seal
13 Seal Ring
14 Seal Washer
victaulic.com
14
10
To Water Motor
Alarm or Optional
Series 752V Retard
Vent Kit
Optional Series 752V
Retard Vent Kit
Pipe to
Open Drain
14
15
4
Bill of Materials
1 Series 751 FireLock European Alarm
Check Valve
2 FireLock Rigid Coupling
3 Water Supply Main Control Valve
4 Gauge Valve
5 Water Supply Pressure Gauge (0-25 Bar)
6 Drain Swing Check Valve
7 Restricted Orifice/Alarm Line Drain
8 System Main Drain Valve
9 Series 752 VdS Retarding Chamber
Assembly (Optional/Sold Separately)
10 Alarm Pressure Switch
11 Alarm Line Ball Valve
(Lockable - Normally Open)
12 Series 760 European Water Motor Alarm
Assembly (Optional/Sold Separately)
13 System Test Valve
14 System Pressure Gauge (0-25 Bar)
15 Series 752V Retard Vent Kit *
(Optional/Sold Separately)
Normally
Open
(Lockable)
11
To
System
5
7
6
13
To
Drain
1
8
To
Drain
Bill
Materials
* Theof
Series
752V Retard Vent Kit is required any time an
Chamber
Assembly.
In addition,
the Series
752V Retard Alarm Check Valve
1
Series
751
FireLock
European
Vent Kit is required if multiple valves are tied into one water
motor alarm and a check valve isolates each line.
From Water
Supply
4 Gauge Valve
5 Water Supply Pressure Gauge (0-25 Bar)
2 The Series 752V Retard Vent Kit is required any time an air break is
needed above the Series 752 VdS Retarding Chamber Assembly. In
addition, the Series 752V Retard Vent Kit is required if multiple valves
are tied into one water motor alarm and a check valve isolates each
line.
victaulic.com
15
Installation
Reference should always be made to the appropriate Installation, Maintenance, and
Testing Manual included with each shipment of Victaulic products. These manuals are also
available in PDF format on our website at victaulic.com
Note
This product shall be manufactured by Victaulic or to Victaulic specifications. All products
to be installed in accordance with current Victaulic installation/assembly instructions.
Victaulic reserves the right to change product specifications, designs and standard
equipment without notice and without incurring obligations.
Warranty
Refer to the Warranty section of the current Price List or contact Victaulic for details.
victaulic.com
Trademarks
Victaulic and FireLock are registered trademarks of Victaulic Company.
16