Documente Academic
Documente Profesional
Documente Cultură
Date: 21/11/2013
EDS 02-0031
Summary:
This standard describes the decision making process, methods and materials to be
used when cables and joints are required to be installed in air and need to be
protected from fire.
Originator:
Paul Williams
Date:
21/11/2013
Approved By:
Steve Mockford
Approved Date:
28/11/2013
Review Date:
28/11/2016
This document forms part of the Companys Integrated Business System and its requirements are mandatory throughout UK
Power Networks. Departure from these requirements may only be taken with the written approval of UK Power Networks
Director of Asset Management. If you have any queries about this document please contact the originator of the current issue.
Document History
(The document history notes below are intended as a guide only and may not cover all of the changes. If you wish to make use
of this document it should be read in full.)
Version
Date
Details
Originator
4.0
21/11/2013
Paul Williams
3.0
12/06/2012
Paul Williams
2.2
22/08/2011
Don Fossett
2.1
14/02/2011
Document rebranded
Don Fossett
2.0
23/06/2009
Paul Williams
1.0
13/01/2006
Original Issue
Paul Williams
THIS IS AN UNCONTROLLED DOCUMENT, THE READER MUST CONFIRM ITS VALIDITY BEFORE USE
Version: 4.0
Contents
1
Introduction ............................................................................................................. 3
Scope ....................................................................................................................... 3
Design Guidelines Flow Chart for Installing Cable and Joints in Air ................... 4
4.1
4.1.1
4.1.2
4.2
5.1
Transition Joints between Existing Solid PILC and new XLPE Cables ....................... 6
5.1.1
5.1.2
5.1.3
5.2
5.2.1
5.2.2
5.2.3
5.3
Transition Joints between Existing Fluid Filled and new XLPE Cables ...................... 8
5.4
5.5
2 of 8
Introduction
The purpose of this engineering design standard is to provide additional detailed guidelines
for the actions to be taken when considering, installing and commissioning the installation of
underground cables and cable joints in an in-air situation (i.e. cable tunnels, substations,
cable basements, underground pits, etc.)
Scope
Underground cables and cable joints are designed to be buried direct in the ground.
Installation in air should be avoided to limit the possible effects of a fire, caused by a failure
and its subsequent spread, unless no other engineering solution is possible.
However, it is accepted that operational constraints mean that cables and joints do
occasionally need to be installed in air.
This standard details the design guidelines, additional measures to be taken and materials to
be used, when cables and joints have to be installed in an in-air situation.
The flow chart in Section 3 illustrates the decision process that shall be undertaken when
deciding on the appropriate course of action to be employed when a project needs to
consider the requirements for cable and joints to be installed in air.
3 of 8
Design Guidelines Flow Chart for Installing Cable and Joints in Air
START
Yes
No
Does the project
require cable & joints to be
permanently installed
in air
No
Install cables as
required
No
Paint all exposed
cables with
intumescant paint
Yes
No
Yes
No
Yes
Yes
No
Yes
Is the Joint a
Heatshrink
Joint
Yes
No
No
Yes
Is an approved
flame retardent joint
shell available
Yes
Use flame retardent
joint shell and fill
with approved resin
No
No
Is the Joint a fluid filled
Cable or fluid filled to XLPE
transition joint
Yes
Yes
Paint exposed joint
and adjacent cables
with intumescant
paint
4 of 8
Cable Installation
4.1
4.1.1
Cable Types
All new install underground cables should have a flame retardant sheath, if they are to be
installed in an in-air situation (i.e. in a cable tunnel, substation, cable basement or a cable
pit), except where the exposed length is less than 3 metres when standard cables with either
PVC or polyethylene sheaths can be used.
If a cable type without a flame retardant sheath needs to be installed, because the
installation of a flame retardant cable is not practical or possible (i.e. there is no suitable
position for a joint between the two cables types). Any exposed length of cable in excess of
3 metres shall be protected by a suitable intumescant paint, applied in accordance with the
manufacturers instructions.
Tests have shown that three coats of Dulux Pyroshield Emulsion are sufficient to provide the
required level of flame resistance for all types of cable.
4.1.2
Cable Spacings
Based on the information contained within the BEWAG* report Special report on Fire
Resistant Cable Installation in Tunnels, all new cross linked polyethylene ( XLPE) low
smoke zero halogen (LSOH) cables shall be installed in trefoil formation.
*BEWAG Berlin Power Utility, now part of the Vattenfall Europe Group.
In order to limit damage should a cable failure occur and to provide clear access, the
minimum separation distances in Table 1 shall be observed:
Type of Spacing
200mm
Minimum 600mm
In these cases, where cables without a flame retardant sheath have already been installed in
an in-air situation, the normal risk assessment process shall be carried out. If it is decided
that additional precautions are required, the circuit(s) in question shall be switched out and
the methods detailed in Section 4.1 of document shall be employed.
5 of 8
In general, the installation of permanent cable joints in an in-air situation should be avoided
unless no other economic engineering solution is possible, especially as experience shows
that cable joints are more prone to in service failure.
Joints to be in service for a period of less than two years can be installed but are subject to
the same installation requirements.
There are three main types of cable joints and each should be considered based upon the
known reliability of each type:
5.1
Transition Joints between Existing Solid PILC and new XLPE Cables
Experience has shown that this particular type of joint is more prone to an electrical failure
than other types due to a mix of old and new technology and particularly the condition of the
existing PILC cables. Therefore, the use of such joints in an in-air situation should be
avoided unless no other economic engineering solution is achievable.
5.1.1
Heatshrink Joints
When a standard commonly used heatshrink joint is to be used in an in-air environment. The
surface of the each complete joint shall be painted with three coats of intumescant paint,
applied in accordance with the manufacturers instructions.
Tests have shown that three coats of Dulux Pyroshield Emulsion are sufficient to provide the
required level of flame resistance for all types of joint.
5.1.2
When a standard commonly used resin-filled joint is to be used in an in-air environment, the
black plastic joint shell, supplied in the kit shall be replaced with a new clear plastic flameretardant shell. Table 2 details the current available range of 11kV flame retardant joints
shells available from UK Power Networks Logistics or the manufacturer TE Connectivity,
currently these are only shells available at all voltages between LV and 132kV.
11kV Joint
kit Stores
Code
Flame
Retardant
Joint Shell
Stores
Code
04120S
04118M
13.0 Litres
13.0 Litres
Joint Description
Resin
Volume
Each flame retardant joint shell is installed in the same manner as the existing shells
supplied in each of the above kits, using the components in the kits and filled with the same
volume of jointing resin.
6 of 8
5.1.3
For all other types of joint the surface of each complete joint shall be painted with three coats
of intumescant paint, applied in accordance with the manufacturers instructions.
Tests have shown that three coats of Dulux Pyroshield Emulsion are sufficient to provide the
required level of flame resistance for all types of joint.
5.2
Experience has shown that this particular type of joint is less prone to an electrical failure
than other types. Therefore, the use of such joints in an in-air situation is acceptable as long
as the following engineering solutions are applied.
5.2.1
Heatshrink Joints
When a standard commonly used heatshrink joint is to be used in an in-air environment. The
surface of the each complete joint shall be painted with three coats of intumescant paint,
applied in accordance with the manufacturers instructions.
Tests have shown that three coats of Dulux Pyroshield Emulsion are sufficient to provide the
required level of flame resistance for all types of joint.
5.2.2
When a standard commonly used resin-filled joint is to be used in an in-air environment, the
black plastic joint shell, supplied in the kit shall be replaced with a new clear plastic flameretardant shell. Table 3 details the current available range of 11kV flame retardant joints
shells available from UK Power Networks Logistics or the manufacturer TE Connectivity,
currently these are only shells available at all voltages between LV and 132kV.
11kV Joint
kit Stores
Code
Flame
Retardant
Joint Shell
Stores
Code
04102U
04099J
6.0 Litres
6.0 Litres
Joint Description
Resin
Volume
Each flame retardant joint shell is installed in the same manner as the existing shells
supplied in each of the above kits, using the components in the kits and filled with the same
volume of jointing resin.
5.2.3
For all other types of new joint the surface of each complete joint shall be painted with three
coats of intumescant paint, applied in accordance with the manufacturers instructions.
Tests have shown that three coats of Dulux Pyroshield Emulsion are sufficient to provide the
required level of flame resistance for all types of joint.
7 of 8
5.3
Transition Joints between Existing Fluid Filled and new XLPE Cables
Experience has shown that this particular type of joint is less prone to an electrical failure
than other types and as the pressure within the joint is continuously monitored the chance of
failure is lower. Therefore, the use of such joints in an in-air situation is acceptable as long
as the following engineering solutions are applied.
All joints of this type contain large volumes of potentially flammable cable fluid; therefore any
joints of this type shall be installed in a suitably sized bunded area, large enough to capture
the volume of oil contained in the joint and the fluid filled cable connected to it.
To prevent the spread of fire the surface of the each complete joint shall be painted with
three coats of intumescant paint, applied in accordance with the manufacturers instructions.
Tests have shown that three coats of Dulux Pyroshield Emulsion are sufficient to provide the
required level of flame resistance for all types of joint.
5.4
Joint Spacings
In order to limit damage should a joint failure occur and to provide clear access, the
minimum separation distances in Table 4 shall be observed:
Type of Spacing
200mm
Minimum 600mm
Minimum 600mm
In these cases, where joints have already been installed in an in-air situation, the normal risk
assessment process shall be carried out. If it is decided that additional precautions are
required, the circuit(s) in question shall be switched out and the methods detailed in Sections
4.1 and 4.2 of this document shall be employed.
8 of 8