Sunteți pe pagina 1din 6

World

UPS-Systems
Power Line 400
highest reliability combined with high
efficiency and ease of operation

Class

Power

Systems

BENNING World Class Power Systems

Power Line 400


safe and reliable
Economic advantages of the technology

More and more data centres and production facilities make


higher demands on UPS systems. Non-linear or unbalanced
loads have to be controlled as much as instantanuous load
changes, overloads and high inrush currents. Today UPS are
considered an integral part of any data centre and can mean
a high investment. Therefore compromising on the reliability
and efficiency of the UPS does not make sense.

The PL 400 uses IGBT power simiconductors and the latest


design in rectifiers and inverter technology. This means the
PL 400 operates without any mains feedback and does not
draw any reactive power from the mains (see figure).
Therefore, no complex or costly harmonic filters are required.

Input current

General

time
UPS with 6-puls
rectifier

UPS with 12-puls


rectifier

PL 400 with IGBT


rectifier

Power Line 400 with sinusoidal input current insured THD < 5%.

Reliability without any compromises

The advantages of the PL 400:

The Power Line 400 is a UPS complies with the highest standards for safety and reliability for power supplies without
compromising its efficiency. The combination of the 16 bit
micro-controller and the latest power electronic control and
monitoring design allow the user to access all the UPSs
functions. The Power Line 400 is a true on-line UPS with double voltage conversion and a constant voltage and frequency
output. In the event of mains failure the power is supplied
uninterrupted by the battery without a break in the output of
the UPS. Even at 100% unbalanced loads, a very high voltage
constant is maintained so as not to endanger the protected
load. Most EDP loads generate high peak currents, even with
three times the nominal current, the quality of the output is
not effected or the need to go to by-pass mode. In essence it
provides perfect UPS protection.

Increased reliability with lower component count


No additional costs for filters
No resonance effects due to wrongly balanced
filters
No interference problems with diesel generators
No harmonic problems at the input, unlike 6 or 12-pulse
UPS systems
Generators can be sized smaller because no reserve is
required to cope with harmonic oscillation

BENNING World Class Power Systems

Power Line 400


powerfull and compact
Space saving and compact

Parallel operation and redundency

Space and volume are critical factors for the total cost
calculation of a UPS. With this in mind the PL 400 is designed
in order to minimise its footprint. The design of the high performance heat sink allows us to concentrate the whole
power electronics on one sub-assembly. The system is also
designed to allow access to all vital components through the
front.

The PL 400 can be connected in parallel and requires no


external control (no master/slave operation). The system has
the option of up to eight systems in parallel to all the UPS to
grow with your requirements. The cabinets can be easily
configuered and repuire no special cables for parallel
operation.

UPS system Power Line 400

PL 400
operating unit
front view
side view (tilt out)
inside view

Easy operation

Guarantee of highest battery availability

All available intormation on the status of the PL 400 can be


accessed via the control panel. The control panel can be
tilted to allow the user a more comfortable reading position.

The battery is an essential part of the UPSs function. With the


PL 400 the status and condition of the battery is constantly
monitored. Temperature controlled charging maximises the
life of the battery.

Current condition through circuit diagram with LED


operating status
LCD with 80 characters given plain text information
Password protection against unintentional operation
User guidance with clear and easy instructions
Event monitor for the last 1200 events
Complete documentation of date, time and events in
plain text
User configuerable
Language selection
Selection of 100 different battery variations
Functional setting of parameters and remote control

Low voltage protection switches off the battery before an


under voltage state occurs.
Cyclic battery testing monitors the battery condition
Battery monitoring provides the user with information on
the batteries capacity and the battery back-up with the
current load.
Total discharge testing is available to test the battery capacity against predetermined levels.

BENNING World Class Power Systems

Power Line 400 online


diagnosis and monitoring
A complete system for the remote diagnostics and
monitoring

SNMP integration of the Power Line 400 into the


network management

The PL 400 allows remote access to the system for error


diagnosis and fault finding. Recall of system messages is
available from the event memory. All operating and system
messages such as change in status and main interruptions
are maintained with a date and time of the event. Recall of
real time data of voltage, frequency, current and power is
also available. The monitoring system can also be configured
to the users specific requirements, this includes updating of
the PL 400 software via modem and if required the system
can auto-dial a specified service provider in the event ot
system errors.

The "Simple Network Management Protocol" (SNMP) is a


standardized and worldwide used network protocol which
allows easy monitoring of all network components. Therefore,
the PL 400 can be very easily integrated into existing
network management systems such as e.g. HP-Openview,
IBM-Netview, Novell NMS and other SNMP-compatible
systems.

PL 400 Cabinet
inside view with and without safety guard

UPSMAN automatic power shut-down and


monitoring software

UPSMON central operating data acquisition and


monitoring

Systematic shut-down of individual work stations or entire


networks. UPSMAN is available for all common operating
systems, e.g. Windows 9.X / NT / 2000, OS/2, Novell
Netware, UNIX, Linux.

UPSMON is a complete information software for the monitoring of either individual or multiple power systems either
through a serial interface, modem or network. It allows realtime monitoring of all system events in a graphical format.
This information can be copied over to databases and spreadsheets for further analysis.

Simple remote diagnosis and


monitoring via modem

BENNING World Class Power Systems

Power Line 400


60, 80, 120, 160, 200 kVA
Technical data of Power Line 400
Type
Nominal power
Input
Nominal voltage
Harmonic distortion factor
Power factor
Output
Nominal voltage
Voltage tolerance

Settling time
Nominal frequency
Voltage harmonic
distortion factor
Crest factor
Overload
By-pass
Overload
General data
Overall efficiency
Battery
Cell number
Power
EMC
Permissible
ambient temperature
Relative air humidity
Installation height
System of protection
Colour
Dimensions H x W x E
Weight

kVA
kW

PL 400/60
60
48

PL 400/80
80
64

PL 400/120
120
96

PL 400/160
160
128

PL 400/200
200
160

400 15 %, 50 Hz 5 %
5%
0,97

400
< 1 % static
< 1 % at 100 % out-of balance load
< 5 % at 100 % load bounce
10
50 0,1%
< 1 % at linear load
< 5 % at nonlinear load acc. to EN 50091-1-1
3
150 % for 10 sec., 125 % for 10 min. at 3-phase load
220 % for 10 sec., 180 % for 10 min. at single-phase load

ms
Hz

1000 % for 150 ms., 150 % for 10 min.


%

91

92

kW

192
49,3

192
65,6

mm
kg

900

92

92

192
2 x 198
98,5
131,5
EN50091-2 standard class A
0 - 40

93
2 x 198
164,1

5 % - 95 % not condensing
< 1000 m above sea level without performance reduction
IP 21
RAL 7035 structured
1400 x 750 x 880
1800 x 1000 x 800
900
1100
850
850

Additional technical information:


High reliability combined with high efficiency and ease
of operation
Capable of supporting out of balance loads
Ability to operate in parallel
High efficiency
No feedback on the mains
Features
Internal manual by-pass
Key pad with mimetic circuit diagram and LC display
Memory for the last 1200 events
I/O board (12-digit input, 6-digit output, 6 relays)
Interface board (RS 232, RS 485, PCMCIA)
Options
Parallel operation of up to 8 systems
I/O board (12-digit input, 6-digit output, 6 relays)
Interface board (RS 232, RS 485, PCMCIA)
External service by-pass
Battery cabinet

Economic advantages of IGBT technology


Sinusoidal input current
-> no harmonic oscillation on the mains side
No reactive power consumption
-> saves energy and provides higher efficiency
No filters
-> increased reliability
No expensive filter balancing
No resonance effects due to badly or wrongly balanced
filters
Management interfaces:
PL-CONNECT modem remote diagnosis
PL-NET SNMP adapter and shut-down software
UPS-MON central remote control via PC
RCP remote control panel
ZLT mod bus

BENNING World Class Power Systems

www.benning.de

India
Benning SMC Power Systems (P) Ltd.
10, Electronic City, Sec.-18,
IND-Gurgaon -122015, Haryana
Tel. 0124 / 6 45 52 03 09
Fax 0124 / 6 45 52 12, 6 34 64 65
E-Mail: smcel@del2.vsnl.net.in

Russian Federation
OOO Benning Power Electronics
Schtscholkovskoje Chaussee, 5
RF-105122 Moscow
Tel. 0 95 / 9 67 68 50
Fax 0 95 / 9 67 68 51
E-Mail: benning@mtu-net.ru

Belgium
Benning Belgium
Power Electronics
Z. 2 Essenestraat 16
B-1740 Ternat
Tel. 02 / 58 287 84 (85)
Fax 02 / 58 287 69
E-Mail: info@benning.be

Ireland
Theo Benning GmbH
North Industrial Estate
Whitemill North
IRE-Wexford / Rep. Ireland
Tel. 0 53 / 41 79 5
Fax 0 53 / 41 84 1
E-Mail: benning@benning.ie

South East Asia


Benning Power Electronics Pte Ltd
1, Kaki Bukit View
# 05-03/04 Techview
SGP-Singapore 415941
Tel. (65) 6844 3133
Fax (65) 6844 3279
E-Mail: benning@singnet.com.sg

Czech Republic
Benning CR s.r.o.
Zahradn ul. 894
CZ-293 06 Kosmonosy
(Mlad Boleslav)
Tel. 03 26 / 72 10 03
Fax 03 26 / 72 25 33
E-Mail: benning@benning.cz

Israel
Laor Energy ltd.
P.O.B. 570
IL-Nazereth Elite 17105
Tel. 03 / 6 87 25 51
Fax 03 / 6 87 11 10
E-Mail: URI@Laor-Energy.com

Sweden
Eldaco AB
Box 990, Hovslagarev. 3B
S-19129 Sollentuna
Tel. 08 / 6239500
Fax 08 / 969772
E-Mail: power@eldaco.se

France
Benning Conversion dnergie
43, avenue Winston Churchill
B.P. 418
F-27404 Louviers Cedex
Tl. 02 / 32 25 23 94
Fax 02 / 32 25 08 64
E-Mail: info@benning.fr

Italy
Benning Conversione di Energia S.r.l.
Via E. Mattei, 7
I-40138 Bologna
Tel. 0 51 / 53 19 55
Fax 0 51 / 53 09 23
E-Mail: benning.energia@libero.it

Switzerland
Benning Power Electronics GmbH
Industriestrasse 6
CH-8305 Dietlikon
Tel. 01/ 8057575
Fax 01/ 8057580
E-Mail: info@benning.ch

Germany
Theo Benning
Elektrotechnik und Elektronik GmbH & Co.KG
Mnsterstr. 135-137
D-46397 Bocholt
Tel. 0 28 71/ 93-0
Fax 0 28 71/ 9 32 97
E-Mail: info@benning.de

Netherlands
Benning NL
Power Electronics
Peppelkade 42
NL-3992 AK Houten
Tel. 0 30 / 6 34 60 10
Fax 0 30 / 6 34 60 20
E-Mail: info@benning.nl

Spain
Benning Conversin de Energa S.A.
C/Pico de Santa Catalina 2
Pol. Ind. Los Linares
E-28970 Humanes, Madrid
Tel. 91/ 6048110
Fax 91/ 6048402
E-Mail: benningcde@retemail.es

Great-Britain
Benning Power Electronics (UK) Ltd.
Oakley House
Hogwood Lane
Finchampstead
GB-Berkshire
RG 40 4QW
Tel. 0118 9731506
Fax 0118 9731508
E-Mail: info@benninguk.com

Poland
Benning Power Electronics Sp.z.o.o.
Korczunkowa 30
PL-05-503 Gloskw
Tel. 0 22 / 7 57 84 53 / 7 57 36 68-70
Fax 0 22 / 7 57 84 52
E-Mail: benning@medianet.pl

Ukraine
Benning
ul. Solomenskaja, 3B
UA-252110 Kiew
Tel. 044 / 246 10 25
Fax 044 / 248 92 36
E-Mail: benning@ukrpack.net

Hungary
Benning Kft.
Power Electronics
Rkczi t 262
H-2541 Lbatlan
Tel. 033 / 50 76 00
Fax 033 / 50 76 01
E-Mail: benning@mail.uti.hu

P. R. of China
Benning V. GmbH
Shanghai Repr. Office
1233 Si Ping Rd., Rm. 006
PRC-200 092 Shanghai
Tel. 021 5557 0609
Fax 021 6504 1878
E-Mail: benning@public8.sta.net.cn

U.S.A.
Lucas-Benning
Power Electronics, Inc.
11120 Grader Street
USA-Dallas, TX 75238
Tel. 214 5531444
Fax 214 5531355
E-Mail: sales@lucasbenning.com

784195.00 03/2002 paus Design & Medien, Bocholt Subject to alterations. Printed on chlorine free paper.

Austria
Benning GmbH Elektrotechnik und Elektronik
Eduard-Klinger-Str. 9
A-3423 St. Andr-Wrdern
Tel. 0 22 42 / 3 24 16-0
Fax 0 22 42 / 3 24 23
E-Mail: info@benning.at

ISO 14001