ELECTRICAL 100% DD PEER REVIEW
GENERAL COMMENTS
1.
Please coordinate with GF&P the Lighting & Power layout for all floors with the
Architectural Plan.
2 BEDROOM TYPE C LIGHTING LAYOUT
2.
Provide additional recessed pinlight at the bathroom located at Gridline 6.
E3-05
3.

Provide porcelain receptacle outlet at the balcony.

2 BEDROOM TYPE D LIGHTING LAYOUT


4.
E3-05
Please verify: No lighting fixture connected to switch Sl.
2 BEDROOM TYPE F LIGHTING LAYOUT
5.
E3-06
Provide additional recessed pinlight at the bathroom located at Gridline C-10.
2 BEDROOM TYPE G LIGHTING LAYOUT
6.
E3-07
Provide porcelain receptacle outlet at the balcony.
2 BEDROOM TYPE H LIGHTING LAYOUT
7.
E3-07
Provide additional recessed pinlight at the bathroom entrance located at Gridline 2-3.
2 BEDROOM TYPE L LIGHTING LAYOUT
8.
Number of porcelain receptacle outlets located at dining and living room in conflict
E3-09
with the Architectural Plan.
3 BEDROOM TYPE C LIGHTING LAYOUT
9.
E3-12
Provide porcelain receptacle outlets at Gridline 1/A for the balcony.
3 BEDROOM TYPE H LIGHTING LAYOUT
10.
Provide wiring connection for the porcelain receptacle outlets located at Gridline 3E3-16
4/C.
GRAND VILLA LEVEL 1 TYPE Q LIGHTING LAYOUT
11.
E3-20
Provide porcelain receptacle outlets at Gridline H/3-4 for the balcony.
1 BEDROOM TYPE H POWER LAYOUT
12.
E3-27
Please provide an additional duplex receptacle outlet beside the bedroom.
1 BEDROOM TYPE N POWER LAYOUT
13.
Please check the position of the 2 duplex receptacle outlets at Gridline D/7-8.
14.

E3-28

Receptacle Outlet near the Water Heater reflected in the Architectural Plan but not in
the Electrical Plan.

Item
No.

Reference /
Sheet No.

Queries / Comments

2 BEDROOM TYPE A POWER LAYOUT


15.
Duplex receptacle outlet located at Gridline C/1-2 should be mounted on the wall.
E3-29
2 BEDROOM TYPE D POWER LAYOUT
16.
Please verify: duplex receptacle outlets located at Gridline 9-10 at the bathroom area
reflected
in the Architectural Plan but not in the Electrical Plan.
E3-30
17.
There is no duplex receptacle outlet provided for the Maids room at Gridline 9-10.
2 BEDROOM TYPE J POWER LAYOUT
18.
E3-33
Please verify: duplex receptacle outlets located at Gridline B-C/1 reflected in the
Architectural Plan but not in the Electrical Plan.
2 BEDROOM TYPE L POWER LAYOUT
19.
E3-34
Please verify: duplex receptacle outlet located at Gridline 9 near the door opening for
the bathroom reflected in the Architectural Plan but not in the Electrical Plan.
2 BEDROOM TYPE M POWER LAYOUT
20.
Please coordinate with GF&P about the positions of the power outlets.
E3-35
21.

Provide power outlet for the lamp fixture at the living room.

2 BEDROOM TYPE N POWER LAYOUT


22.
E3-35
Provide power outlet for the lamp fixture at the living room.
3 BEDROOM TYPE A POWER LAYOUT
23.
Please verify: duplex receptacle outlet located at Gridline C/8 reflected in the
E3-36
Architectural Plan but not in the Electrical Plan.
3 BEDROOM TYPE B POWER LAYOUT
24.
Please check: No water heater outlet at Gridline 6.
E3-37
25.
Please verify: duplex receptacle outlet located at Gridline 7-8 near the bathroom door
reflected in the Architectural Plan but not in the Electrical Plan.
3 BEDROOM TYPE C POWER LAYOUT
26.
Please coordinate with GF&P about the positions of the power outlets.
27.

E3-37

Please check if we still need to provide GFCI & CT outlets at the bathroom located at
Gridline 3-4.
28.
Please check if we still need to provide GFCI & CT outlets at the bathroom located at
Gridline 4-5.
3 BEDROOM TYPE D POWER LAYOUT
29.
Please check if we still need to provide GFCI & CT outlets at the bathroom located at
E3-38
Gridline A-B/3.
3 BEDROOM TYPE E (LEVEL 1) POWER LAYOUT
30.
E3-38
Please provide duplex receptacle outlet for the TV at Gridline A/3-4.
3 BEDROOM TYPE F (LEVEL 1) POWER LAYOUT
31.
E3-40
Please complete the power layout.
3 BEDROOM TYPE F (LEVEL 2) POWER LAYOUT

Item
Reference /
No.
Sheet No.
32.
E3-40

Queries / Comments
Please complete the power layout.

3 BEDROOM TYPE J POWER LAYOUT


33.
Please check if we still need to provide GFCI & CT outlets at the bathroom located at
E3-42
Gridline 7.
GRAND VILLA LEVEL 1 TYPE Q POWER LAYOUT
34.
Please check if we still need to provide GFCI & CT outlets at the bathrooms located
E3-45
at Gridline 3.
GRAND VILLA LEVEL 1 TYPE P POWER LAYOUT
35.
Provide Water Heater Outlet at Gridline 5-6.
E3-46
36.
Please check if we still need to provide GFCI & CT outlet at the bathroom located at
Gridline 5.
GRAND VILLA LEVEL 3 TYPE B POWER LAYOUT
37.
E3-49
Provide Microwave Outlet & Dryer Outlet at Gridline G/2-3.
GRAND VILLA LEVEL 4 TYPE B POWER LAYOUT
38.
Please check if we still need to provide GFCI & CT outlets at the bathroom located at
E3-49
Gridline G/2.
GRAND VILLA LEVEL 2 TYPE N POWER LAYOUT
39.
Please check if we still need to provide GFCI & CT outlets at the bathroom located at
E3-50
Gridline G-H/7-8.
Prepared by:

Noted By:

I.A Campbell & Associates, Inc.


Thadeo C. Pobocan
Project Architect

William L. Cabato, R.A., PMP, AIA


Project Manager