Dimensions
22 x 22
22 x 25
22 x 25
22 x 25
22 x 50
6 x 97
Design
Occupancy #
2
2
2
2
20
0
Comfort Level:
3.
Zone
1
2
3
4
4.
Select or compute heat transfer coefficients for outside walls, roof, doors, windows, etc.
(Given in problem statement)
Component
Walls
Roof
Doors
Windows
5.
Component
Roof
N. Wall
E. Wall
S. Wall
W. Wall
N. Window
E. Window
S. Window
W. Window
N. Door
E. Door
S. Door
W. Door
6.
Per site plans
Rooms
1
2,3
4
Conf. , halls
U (BTU/hr-ft2-F)
0.128
0.112
0.470
0.580
Determine corresponding areas for outside walls, roofs, doors, windows, etc.
Office #1 (ft2)
484
170
170
0
0
50
50
0
0
0
0
0
0
Office #2 (ft2)
550
0
170
200
0
0
50
50
0
0
0
0
0
Office #3 (ft2)
550
0
0
200
0
0
0
50
0
0
0
0
0
Office #4 (ft2)
550
0
0
200
170
0
0
50
50
0
0
0
0
Halls (ft2)
582
18
18
0
60
0
0
0
0
42
42
0
0
7.
Obtain schedule of lighting, occupants, internal equipment, appliances, and processes that would
contribute to the internal loads.
Calculate peak cooling load due to conductive and solar effects (rooms 1st, zones 2nd, total last) .
Calculate conductive heat gains through walls, roof, glazing, etc.
Calculate solar gains through glazing (windows).
Component
Roof
Walls
Windows
Doors
Equation
Q = Uroof * Aroof * ETDt
Q = Uwall * Awall * ETDt
Q = Uwindow * Awindow * TD (conductive)
Q = SC * Aglass * SF (solar)
Q = Udoor * Adoor * TD
These loads must be calculated for each hour of occupancy in order to determine the peak load for the building. See
spreadsheet (MET 465 Cool Load Example Calcs.) for summary of calculations
9.
Infiltration:
Ventilation:
Note: Use largest of these two values (reference pg. 203 of text).
See spreadsheet (MET 465 Cool Load Example Calcs.) for summary of calculations
10. Calculate internal heat gains due to people, equipment, lights, etc.
Gain
People
Equipment
Lights
Equation
Qsensible = # Occupants * BTUH for activity level (p. 216)
Qlatent = # Occupants * BTUH for activity level (p. 216)
Per manufacturers specifications
Per building plans or
Estimate per table on page 216 of text
See spreadsheet (MET 465 Cool Load Example Calcs.) for summary of calculations
11. Sum all heat gains for peak zone loads.
Zone
Room
1
2
3
4
1
2,3
4
Conf.,
hall
Peak
Time
8:00 am
10:00am
4:00 pm
4:00 pm
Sensible Load
(BTU/hr)
13151
26067
16280
35542
Latent Load
(BTU/hr)
626
1342
671
6237
Total Load
(BTU/hr)
13778
27409
16951
41779
These loads represent the peak loads for each zone. Notice that the peak time varies. See spreadsheet (MET 465
Cool Load Example Calcs.) for summary of calculations.
8:00
Qsensible
(BTU/hr)
1282
2765
434
3190
25798
2948
7000
18023
1100
62540
8876
71416
10:00
Qsensible
(BTU/hr)
6411
2860
434
3190
25436
2948
7000
18023
1100
67402
8876
76278
12:00
Qsensible
(BTU/hr)
11540
2859
434
3190
21866
2948
7000
18023
1100
68960
8876
77837
2:00
Qsensible
(BTU/hr)
15386
3149
434
3190
25680
2948
7000
18023
1100
76912
8876
85788
4:00
Qsensible
(BTU/hr)
15386
3021
434
3190
24087
2948
7000
18023
1100
75190
8876
84066
6:00
Qsensible
(BTU/hr)
11540
3021
434
3190
16150
2948
7000
18023
1100
63407
8876
72282
8:00
Qsensible
(BTU/hr)
162
2765
434
3190
0
2948
7000
18023
1100
35623
8876
44499