Documente Academic
Documente Profesional
Documente Cultură
I. I NTRODUCTION
Responses of an electric power network after disturbances
portray the dynamic behavior of the system. Understanding
dynamic responses is crucial in evaluating the systems characteristics. Once these characteristics have been well-understood,
the response of the system to disturbances may be anticipated,
and unwanted behavior can be alleviated by the design and
implementation of power system controls and protections.
Stability of a power system is dependent on the set of
parameters describing the dynamic properties of each of
its elements. Of particular importance are those parameters belonging to machines, e.g. generators, turbines, and/or
governors. They play a major role in rotor angle stability
which is classied into two types: small-signal stability and
transient stability [1]. These two types of stability are widely
and intensively employed for stability security assessment at
network control centers and for planning purposes.
To correctly forecast dynamic responses and assess system
stability, accurate modelling of power systems is highly important. The system model should be capable of representing the
Manuscript submitted to the IEEE PES General Meeting Conference,
2012.
Y. Chompoobutrgool, W. Li, and L. Vanfretti are with the Electric Power
Systems Division, School of Electrical Engineering, Royal Institute of Technology (KTH), Teknikringen 33, SE-100 44, Stockholm, Sweden. E-mail:
yuwa@kth.se, liwei.emma@gmail.com, luigiv@kth.se
Y. Chompoobutrgool is supported by Elforsk, Sweden.
W. Li was supported in part by EIT InnoEnergy Collocation Center Sweden
within the Smart Power thematic area.
L. Vanfretti is supported by the STandUP for Energy collaboration initiative
and the KTH School of Electrical Engineering.
B. System Characteristics
The KTH-NORDIC32 system is depicted in Fig. 1. The
overall topology is longitudinal; two large regions are connected through considerably weak transmission lines. The rst
region is formed by the North and the Equivalent areas located
in the upper part, while the second region is formed by the
Central and the South areas located in the bottom part. The
system has 52 buses, 52 transmission lines, 28 transformers
and 20 generators, 12 of which are hydro generators located
in the North and the Equivalent areas, whereas the rest are
thermal generators located in the Central and the South areas.
There is more generation in the upper areas while more loads
congregate in the bottom areas, resulting in a heavy power
transfer from the northern area to the southern area through
weak tie-lines.
1 Free
G19
G9
51
EQUIV.
G2
SL
34
21
23
35
22
24
52
G10
G20
G4
G3
G1
G11
G5
25
26
37
36
NORTH
G12
G8
33
32
38
39
G14
G13
41
40
CENTRAL
43
G7
42
45
48
29
30
G6
G17
27
28
31
G15
44
49
G16
50
46
47
G18
400 kV
220 kV
130 kV
15 kV
SOUTH
Fig. 1.
C. Dynamic Modelling
Dynamic models of synchronous generators, exciters, turbines, and governors for the improved Nordic power system
are implemented in PSAT. All models used are documented in
the PSAT Manual. Parameter data for the machines, exciters,
and turbine and governors are referred to [18], [19] and
provided in Appendix B.
1) Generator Models: Two synchronous machine models
are used in the system: three-rotor windings for the salientpole machines of hydro power plants and four-rotor windings
for the round-rotor machines of thermal plants. According to
Fig. 1, thermal generators are denoted by G6 , G7 and G13
to G18 whereas hydro generators are denoted by G1 to G5 ,
G8 to G12 , G19 and G20 . These two types of generators are
described by ve and six state variables, respectively: , ,
eq , eq , ed , and with an additional state ed for the six-statevariables machine. All generators have no mechanical damping
and saturation effects are neglected.
2) Automatic Voltage Regulator and Over Excitation Limiter Models: The same model of AVR, as shown in Fig. 2, is
used for all generators but with different parameters. The eld
voltage vf is subject to an anti-windup limiter.
1
v0
s0
1
Tr s 1
v fmax
vm -
K0
+
vref
Fig. 2.
T1s 1
T2s 1
1
TFs 1
+
+
v f0
vref
v fmin
Exciter Model
i flim
1
T0s
if
Fig. 3.
vOXL
vref
AVR
Generator
Network
(pg , q g , vg )
if
PILOT
VALVE
6
+
1
Tg (1 Tps )
RATE
LIMIT
%G +
1
s
DISTRIBUTOR POSITION
VALVE AND
LIMIT
GATE
SERVOMOTOR
Pm
Pref Gref
PERMANENT DROOP
COMPENSATION
ETr s
1 Tr s
TRANSIENT DROOP
COMPENSATION
Pref
+
+
1
1 Tgs
1 T3s
1 T4s
1 Tcs
1 T5s
Fig. 6.
Pref
Xref X
Fig. 5.
Linearized
Turbine
Typical Tubine
Governor
Pm
1
R
1 T1s
1 T2s
Pm
0.4
0.3
0.3
0.2
0.2
0.1
0
0.1
0.2
0.4
1.5
0.2
0.3
1
0.5
0
0.5
Real Axis
(a) Model 2
Fig. 7.
0.1
0.1
0.3
Pole-Zero Map
0.4
Imaginary Axis
Fig. 4.
1
R
Imaginary Axis
Xref X
1.5
0.4
1.5
0.5
0
0.5
Real Axis
(b) Model 3
1.5
4
22.6
21.345
22
21.8
21.6
21.335
21.33
21.325
21.4
10
12
14
16
18
20
21.32
0
time (s)
10
12
14
16
18
20
time (s)
having low frequency of oscillations. These types of oscillations, namely low-frequency inter-area oscillations (LFIO),
occur in large power systems interconnected by weak transmission lines [25] that transfer heavy power ows. The system
of study, KTH-NORDIC32, has the characteristics of bearing
heavy power ow from the northern region supplying the load
in the southern region through loosely connected transmission
lines. Consequently, the system exhibits lightly damped low
frequency inter-area oscillations. Table I provides the two
lowest damping modes, their corresponding frequencies and
damping ratios, and the most associated state variables for both
cases. As shown in the table, the damping ratios obtained from
the two models bear a signicant difference. This discrepancy
is due to the incorrect modelling of the HTGs using Model 2,
for which damping ratios are larger than when using Model
3 for HTG representation. This model error might inuence
the design of damping controllers to be less effective; this
precisely illustrates why HTG modelling is important.
15
15
10
10
Imag
22.2
10
10
15
30
25
20
15
Real
10
15
30
25
(a) Model 2
10
10
1.5
Real
0.5
0.5
15
Real
10
10
2.5
20
(b) Model 3
Imag
21.34
Imag
Model 3
Model 3
Imag
Model 2
22.4
10
2.5
1.5
Real
0.5
0.5
TABLE I
L INEAR ANALYSIS RESULTS OF THE TWO LOWEST DAMPING MODES IN KTH-NORDIC32
Model
System with Model 2
System with Model 3
Eigenvalues
-0.11043 j3.1331
-0.14637 j4.6004
-0.0061875 j3.1015
-0.039918 j4.8658
Frequency (Hz)
0.49866
0.73218
0.49362
0.77442
Damping ratio
0.035223
0.031801
0.0019950
0.0082036
Syn 1
Syn 2
1.0006
Mode 1
Mode 2
90
0.002
60
120
0.005
60
120
Z1
30
210
330
Z1
Syn
Syn
Syn
10
0.0025
150
30
Z5
Z6
Z6
Z7
Z7
Z8
Z
1.0002
Z4
Z5
180
Syn 11
Z8
Syn 12
Z9
Z10
Z10
Z11
Z11
Z12
Syn 13
0.9998
Syn 14
Syn
12
210
Z13
330
Z13
Syn 16
Z15
240
Z16
300
270
Z18
Z18
Machine Speed
Z19
Z19
Z20
Z20
0.9994
Z17
20
40
60
80
100 120
time (s)
140
160
180
200
120
Mode 2
0.002
60
1.0008
1.0006
1.0002
90
120
Z1
30
180
0.01
60
240
300
270
Machine Speed
Z1
20
Syn
Syn
Syn
Syn
Syn
Syn
Syn
Syn
Syn
Syn
10
Z3
Syn
11
Syn
12
Syn
13
Syn
14
Syn
15
Syn
16
Syn
17
Syn
18
Syn
19
Syn
20
0.005
150
30
Z5
Z6
Z6
Z7
Z7
Z8
Z8
Z9
180
Z10
Z11
Z11
Z15
Z15
Z18
0.9992
300
240
270
Machine Speed
0.999
0
Z13
Z14
Z17
0.9994
Z12
330
210
Z14
Z16
0.9996
Z9
Z10
Z13
0.9998
Z4
Z5
Z12
330
19
Syn
Z2
210
18
Syn
Z2
3
0.001
150
17
Syn
1.0004
90
Syn
Mode 1
15
0.9996
Z14
Z17
270
Z3
Z16
Machine Speed
Z15
300
Syn
Syn
Z14
240
1.0004
Z4
180
Syn 3
Syn
Z2
3
0.001
150
90
Syn
Z16
50
100
time (s)
150
200
Z17
Z18
Z19
Z20
19
20
Fig. 12.
to apply a fault at a node and observe the corresponding responses. To allow for a proper comparison of the performance
of the two models of turbine and governor, the fault should be
applied at a bus in such way that the nonlinear behavior of the
model can be evaluated. As such, a three-phase fault is applied
at Bus 1011 at t = 5 s and removed after 20 ms in this study.
The generator speed responses of the two models, Model 2 and
Model 3, are displayed in Fig. 12a and 12b, respectively. Note
that during approximately the rst 10 s of the simulation, the
responses of the system using Model 3 exhibit the nonlinear
characteristics of the model.
Comparing the two simulations, the two responses behave
considerably different; those of Model 2 converge to steady
state while those of Model 3 show larger damped oscillations.
This is due to the systems damping related to the inter-area
swings [26], [27], [28]. Note that with this disturbance, both
Mode 1 and Mode 2, discussed in the previous section, are
excited.
1.0086
1.0086
1.0086
X= 0.77515
Y= 5.5684
X= 0.49438
Y= 5.5338
V (p.u.)
1.0085
SingleSided Amplitude Spectrum of Syn6 speed for KTHNORDIC32 system with Model 1&3
6
1.0084
1.0084
1.0084
|Y(f)|
1.0083
1.0082
1.0082
X= 0.057983
Y= 1.3138
10
time (s)
12
14
16
18
20
0.1
0.2
0.3
0.4
0.5
0.6
Frequency (Hz)
0.7
0.8
0.9
(a) FFT on 6
SingleSided Amplitude Spectrum of Syn18 speed for KTHNORDIC32 system with Model 1&3
12
1.0308
10
X= 0.49438
Y= 10.5394
1.0307
V (p.u.)
|Y(f)|
1.0307
4
1.0306
X= 0.057983
Y= 1.2773
X= 0.77515
Y= 0.36492
1.0306
0.1
0.2
0.3
0.4
0.5
0.6
Frequency (Hz)
0.7
0.8
0.9
(b) FFT on 18
Fig. 13.
system.
1.0305
10
time (s)
12
14
16
18
20
18
A PPENDIX B
DATA
TABLE II
G ENERATOR MODEL PARAMETERS
10.601
Nonlinear
Linear
10.6
10.599
10.598
10.597
10.596
10.595
10.594
Fig. 15.
10
time (s)
12
14
16
18
20
Parameter
xd [p.u.]
xd [p.u.]
x
d [p.u.]
[p.u.]
Td0
[p.u.]
Td0
xq [p.u.]
xq [p.u.]
x
q [p.u.]
[p.u.]
Tq0
[p.u.]
Tq0
2H [kWs/kVA]
Thermal
2.2
0.3
0.2
7
0.05
2
0.4
0.2
1.5
0.05
12
Hydro
1.1
0.25
0.2
5
0.05
0.7
0
0.2
0
0.1
6
Parameter
K0 [p.u.]
T2 [s]
T1 [s]
Te [s]
Tr [s]
vfmax [p.u.]
vfmin [p.u.]
vf0 [p.u.]
Thermal
120
50
5
0.1
0.001
5
0
0
Hydro
50
20
4
0.1
0.001
4
0
0
TABLE IV
OVER EXCITATION LIMITER MODEL PARAMETERS
Parameter
T0 [p.u.]
ilim
[p.u.]
f
max [p.u.]
vOXL
Value
10
3.0-22.0
1.1
TABLE V
T URBINE GOVERNOR SYSTEM MODEL PARAMETERS : M ODEL 1
Parameter
R [p.u.]
Tg [s]
Tc [s]
T3 [s]
T4 [s]
T5 [s]
Pmax [p.u.]
Pmin [p.u.]
Value
0.04
5
0.2
5
0.01
6
0.95
0, -0.5 for G13
TABLE VI
T URBINE GOVERNOR SYSTEM MODEL PARAMETERS : M ODEL 2
Parameter
R [p.u.]
T1 [s]
T2 [s]
Pmax [p.u.]
Pmin [p.u.]
Value
0.04, 0.08 (for G19 , G20 )
3
0.5
1
0
TABLE VII
T URBINE GOVERNOR SYSTEM MODEL PARAMETERS : M ODEL 3
Gmax
Gmin
Parameter
Tg [s]
Tp [s]
Tr [s]
Tw [s]
[p.u.]
[p.u.]
a11 [p.u.]
a13 [p.u.]
a21 [p.u.]
a23 [p.u.]
(Maximum gate opening) [p.u.]
(Minimum gate opening) [p.u.]
Value
0.2
0.04
5
1
0.04
0.3
0.5
1
1.5
1
1
0
R EFERENCES
[1] P. Kundur, J. Paserba, V. Ajjarapu, G. Andersson, A. Bose, C. Canizares,
N. Hatziargyriou, D. Hill, A. Stankovic, C. Taylor, T. Van Cutsem,
and V. Vittal, Denition and Classication of Power System Stability
IEEE/CIGRE Joint Task Force on Stability Terms and Denitions, IEEE
Transactions on Power Systems, vol. 19, no. 3, pp. 1387 1401, aug.
2004.
[2] Y. Chompoobutrgool and L. Vanfretti, Linear Analysis of the KTHNORDIC32 System, KTH Royal Institute of Technology, Tech. Rep.
Smarts-Lab-2011-001, March 2011.
R
E, 2011. [Online]. Available: http://www.
[3] SIEMENS, PSS
energy.siemens.com/us/en/services/power-transmission-distribution/
power-technologies-international/software-solutions/pss-e.htm
[4] CEPEL, PacDyn, 2011. [Online]. Available: http://www.pacdyn.cepel.
br/
[5] STRI, SIMPOW, 2011. [Online]. Available: http://www.stri.se/simpow
[6] P. Korba and K. Uhlen, Wide-area monitoring of electromechanical
oscillations in the nordic power system: practical experience, IET
Generation, Transmission Distribution, vol. 4, no. 10, pp. 1116 1126,
October 2010.
[7] K. Uhlen, L. Warland, J. Gjerde, O. Breidablik, M. Uusitalo, A. Leirbukt,
and P. Korba, Monitoring Amplitude, Frequency and Damping of Power
System Oscillations with PMU Measurements, IEEE PES General
Meeting, 2008.
[8] J. Turunen, M. Larsson, P. Korba, J. Jyrinsalo, and L. Haarla, Experiences and future plans in monitoring the inter-area power oscillation
damping, IEEE PES General Meeting, 2008.
[9] N. Chaudhuri, A. Domahidi, R. Majumder, B. Chaudhuri, P. Korba,
S. Ray, and K. Uhlen, Wide-area power oscillation damping control in
nordic equivalent system, IET Generation, Transmission Distribution,
vol. 4, no. 10, pp. 1139 1150, October 2010.
[10] E. Johansson, K. Uhlen, A. Leirbukt, P. Korba, J. Gjerde, and
L. Vormedal, Coordinating power oscillation damping control using
wide area measurements, IEEE/PES Power Systems Conference and
Exposition, pp. 18, 2009.
[11] K. Uhlen, S. Elenius, I. Norheim, J. Jyrinsalo, J. Elovaara, and E. Lakervi, Application of Linear Analysis for Stability Improvements in the
Nordic Power Transmission System, IEEE PES General Meeting, pp.
20972103, 2003.
[12] R. M. Stallman, Free Software, Free Society: Selected Essays of Richard
M. Stallman, 2nd ed. Free Software Foundation, Inc., 2010.
[13] F. Milano, L. Vanfretti, and J. Morataya, An Open Source Power
System Virtual Laboratory: The PSAT Case and Experience, IEEE
Transactions on Education, vol. 51, no. 1, pp. 1723, February 2008.
[14] S. Chopra and D. S. D., Decoding Liberation: The Promise of Free and
Open Source Software. Routledge, 2010.
[15] F. Milano, PSAT, Matlab-based Power System Analysis Toolbox,
2002. [Online]. Available: http://www.power.uwaterloo.ca/fmilano/
downloads.htm
[16] , An Open Source Power System Analysis Toolbox, IEEE Trans.
Power Syst., vol. 20, no. 3, pp. 11991206, August 2005.
[17] W. Li and L. Vanfretti, Development and Implementation of Hydro
Turbine and Governor Models for Small-Signal and Transient Stability
Analysis of Power Systems, KTH Royal Institute of Technology,
Electric Power Systems Department, Report for: EIT InnoEnergy Smart
Power Thematic Area, WP3.1: Smart Transmission Grids Real-Time
Simulation Platform Smarts-Lab-2011-005, September 2011.