Sunteți pe pagina 1din 4

O-BBS 24-1080 and 48-540

Outdoor Battery Backup System

Key Features
High capacity passive hydrogen
ventilation system reliable
ventilation capacity exceeding
industry standards to minimize risk
of hydrogen build up
Two separate compartments,
battery and electronics no
risk for arcs or sparks to ignite
hydrogen gas as electronics
compartment is located below
batteries
Outer skin made of 1/8" thick
powder coated aluminum
corrosion resistant and shot gun
resistant
Heavy duty foil backed
insulation in battery
compartment minimizes
environmental impact and cooling
requirement
Multiple and flexible cable inlet
positions simple adaptability to
site conditions

Outside Plant for


Business-Critical Continuity

Description
The system includes innovative temperature control for the ultimate in reliability and long
life time. The O-BBS is state of the art engineering with extensive software analysis as well
as extensive agency testing and verification to the highest industry standards. Further
engineering focus was on installability/serviceability and cost.
DC Power
+24VDC or 48VDC configurations flexibility to connect to all common DC power
voltages
Integrated Battery Breaker Module, BBM flexibility to choose up to four feeds with
circuit breakers up to 200A each
Cooling and Heating
Thermoelectrical cooling/heating
(Peltier) high reliability and low maintenance cost
No refrigerants used environmental friendly and no requirement for specialized
refrigerant service technicians
DC operated cooling/heating, i.e. no AC power routing required saves site
installation cost and time
Low Voltage Disconnect device automatic disconnect and reconnect of Peltier unit
maximizes backup time and minimizes recharge time
Thermostatically controlled by solid state circuit high reliability and precise control

Application
Emerson Energy Systems O-BBS is a high
performance battery backup system for
outdoor applications. Usage can be for, but
not limited to:
Extended RBS/BTS/data/telecom outdoor
battery backup
Replacement of diesel generator sets
Replacement of existing battery backup
solution to increase system reliability and
battery life
Outdoor enclosure and shelter sites


OSPDS-124100 / 0207

O-BBS 24-1080 and 48-540 Outdoor Battery Backup System

Specifications
System Characteristics
Nominal system voltage

+24VDC or -48VDC

Backup capacity
Up to 4h at 6kW and 1.75V/cell

Up to 1080Ah (+24VDC version)*


Up to 540Ah (-48VDC version)*

Agency approvals

Telcordia GR-487-CORE and UL 50

Grounding, single point

2-hole lug for 1/4" screw and 5/8" spacing

Environmental Classification
Operating temperature (nominal)

Maximum: 115F (46C) with 753 W/m2 solar load


Minimum: -40F (-40C)

Sound level

55 dB(A) at 5 (1.5m)

Hydrogen outgassing capacity

500 cc/min (less than 2% H2 concentration)

Degree of protection

NEMA 4 (electronics compartment)


NEMA 3R (battery compartment)

Earthquake

Telcordia GR-63-CORE, Zone 4

Environmental Control Unit, ECU


Technology

Thermoelectrical (TE) modules (Peltier), forced air, closed loop, filterless, non-refrigerant

Cooling and heating capacity

Cooling 200W, heating 250W

Thermostat control (solid state)


Cooling, set point 77F (25C), +/- 3.5F (2C)


Heating, set point 50F (10C), +/- 3.5F (2C)

Low Voltage Disconnect (LVD)


with disconnect/reconnect of ECU

25.0 / 26.0V, +/- 0.5V (+24VDC version)


50.1 / 51.0V, +/- 0.5V (-48VDC version)

Repair time

< 10 minutes (non-specialist)

Power consumption 11.2A (+24VDC version)



5.6A (-48VDC version)
Enclosure
Dimensions (H x W x D)

57" x 36" x 30" (1448 x 914 x 762mm)

Weight

880 lbs / 400 kg (excluding batteries)


2700 lbs / 1200 kg (including batteries)

Lock system

3-point, padlockable

Alarms

Open door (NC)


High/low temperature (NO or NC)
Circuit breaker tripped (NO or NC)

Access

Front access (rear access not required)

Bug screens (on all openings)

0.1" (2.5mm) mesh hole size

External material

Aluminum 5052-H32, 1/8" thick

External color, powder coating

Medium gray, polyester semi gloss hytex

Cable inlets
Exchangeable cable inlet plates

Conduit connections, 11/4", 2", 4" etc.


Cable grommets and glands, various sizes
Roxtec, CF16

Safety Compliance
UL

UL50

CSA

C22.2 60950-00

Telcordia

GR-487-CORE

NEMA

NEMA 4 for electronics compartment and NEMA 3R for battery compartment


OSPDS-124100 / 0207

O-BBS 24-1080 and 48-540 Outdoor Battery Backup System

Battery Specifications
Optional Equipment *
Top terminal type

GNB

Front terminal type, 22" deep






GNB
M12V155FT
C&D
FA 12-150
EnerSys 12V165F
Fiamm 12 FAT 155
East Penn-Deka 12AVR-150ET
Northstar
NSB170FT

M12V90F

Installation

Factory installed and pre-wired

Battery acid drip prevention

Plastic tray for each battery

Battery Breaker Module (BBM)


Circuit Breakers (CB)

Up to 4 CBs, 100 to 200A each

Lug size (external side)

Up to 4/0, 2-hole lug for 3/8" screw and 1" spacing

Interrupt current

50 kAIC

Safety Compliance
Telcordia

GR-487-CORE

* Additional equipment types can be fitted.


OSPDS-124100 / 0207

O-BBS 24-1080 and 48-540 Outdoor Battery Backup System

State of the art engineering with extensive software analysis,


testing and verification

Emerson Network Power.


The global leader in enabling businesscritical continuity.

Emerson Network Power


Energy Systems
701 N. Glenville Drive, Richardson, TX
Telephone: 866-851-2565 Fax: 972-367-0066
www.EmersonNetworkPower.com/EnergySystems

AC Power
Connectivity
DC Power
Embedded Computing

Embedded Power
Monitoring
Outside Plant
Power Switching & Controls

Precision Cooling
Racks & Integrated Cabinets
Services
Surge Protection

2007 Emerson Network Power Energy Systems,


North America, Inc. All rights reserved.
The Emerson logo is a trademark and a service mark
of Emerson Electric Co. Emerson Network Power is a division
of Emerson Electric Co.
Printed in USA
OSPDS-124100 / 0207

S-ar putea să vă placă și