Documente Academic
Documente Profesional
Documente Cultură
Compressors, Inc.
Number:
124
Application Bulletin
D00905
E27204
L00910
2/9/96
10/17/97
2/21/03
Application Bulletin
No. 124
Release E/N:
Date:
Revision E/N:
Date:
C18811
10/20/95
L00910
2/21/03
These are general guidelines only and in no way should they replace, contradict or otherwise take
precedence over any local, state or federal law or regulation pertaining to the recovery,
reclamation, and recycling of refrigerants.
With the phase-out of HCFCs, existing air conditioning/heat pump equipment will need to be
replaced with new equipment or retrofitted with new components (including the compressor) that
are approved for use with the new refrigerant and their lubricants. Using the procedures described
below, existing R22 systems can be retrofitted for use with R407C, allowing them to continue in
service for the remainder of their useful life. Bristol Compressors does not recommend the
changeover of HCFC refrigerants to HFCs in systems that are operating and have no leaks.
R407C is a zeotropic blend of refrigerants of the following composition:
R32
R125
R134a
23%
25%
52%
New High Temperature R407C Compressors are identified by the number 7 in the second digit
of the model number (example: H75B28QABC). These compressors are factory oil charged with
Polyol ester (POE) lubricant and employ an improved lubrication system which are required for
the new refrigerant .
For Bristols approved lubricant type and required oil charge amounts for use with R407C, refer to
the individual compressor model specification sheet. This information can be found on Bristols
website www.bristolcompressors.com. The use of any other lubricant may void the compressor
warranty.
SYSTEM DESIGN
1.0 Refrigerant Metering Devices
The performance of each system is very dependent on the proper operation of each metering
device. Devices such as solenoid valves, capillary tubes, fixed orifice valves, and expansion
valves can perform differently if they are not correctly adjusted or properly sized. For example,
the port size of a valve may not be correct for the new refrigerant density. Each valve and
metering device manufacturer should be consulted, along with the system's manufacturer, to
ensure all components will work properly in the presence of the new refrigerant and lubricant.
2.0 Filter Driers
The proper selection of a system's filter drier is very important. Some filter driers may not be
suitable for R407C refrigerant and polyol ester lubricant. Therefore, the original equipment
manufacturer should be contacted for the proper filter drier selection. It is important to replace the
filter drier any time the refrigerant or lubricant in a system is changed. Specifically, Bristol
Compressors requires a new suction line filter drier be installed during any compressor
replacement. Maintaining good system performance, reliability and cleanliness is closely linked
to proper filter drier operation.
3.0 Controls
The proper operation of many types of air conditioning/heat pump equipment requires that the
control systems function correctly. The control system could be pressure controls, temperature
controls, timing devices, or sophisticated electronic controls. Changing to R407C refrigerant and
polyol ester lubricant in a system could adversely affect these control systems. Each equipment
manufacturer should be consulted to ensure each control system will operate correctly with the
R407C refrigerant/polyol ester lubricant combination. Changes most likely will have to be made
for continued good equipment performance. These changes could involve adjusting temperature
or pressure set points to new values or replacing the control system with a newly designed unit.
4.0
a)
b)
When setting evaporator superheat, calculate it from the saturated vapor (or
dew point) temperature.
c)
When setting subcooling, calculate it from the saturated liquid (or bubble
point) temperature.
4.1.3.2
b)
c)
d)
PSIA
PRESSURE
PSIG
DEW POINT
F
MEAN TEMP
F
BUBBLE POINT
F
10
-4.7
-47.90
-54.48
-61.06
11
-3.7
-44.64
-51.18
-57.72
12
-2.7
-44.59
-49.61
-54.62
13
-1.7
-38.75
-45.24
-51.72
14
-0.7
-36.07
-42.53
-48.99
15
0.3
-33.53
-39.97
-46.40
16
1.3
-31.13
-37.54
-43.95
17
2.3
-28.84
-35.23
-41.62
18
3.3
-26.65
-33.03
-39.40
19
4.3
-24.56
-30.91
-37.26
20
5.3
-22.55
-28.89
-35.22
21
6.3
-20.62
-26.94
-33.25
22
7.3
-18.76
-25.06
-31.35
23
8.3
-16.96
-23.25
-29.53
24
9.3
-15.23
-21.50
-27.76
25
10.3
-13.55
-19.80
-26.05
26
11.3
-11.92
-18.16
-24.39
27
12.3
-10.34
-16.56
-22.78
28
13.3
-8.0
-15.01
-21.21
29
14.3
-7.31
-13.50
-19.69
30
15.3
-5.85
-12.03
-18.21
31
16.3
-4.44
-10.60
-16.76
32
17.3
-3.05
-9.20
-15.35
33
18.3
-1.70
-7.84
-13.98
34
19.3
-0.38
-6.51
-12.64
35
20.3
0.90
-5.21
-11.32
36
21.3
2.16
-3.94
-10.04
37
22.3
3.40
-2.69
-8.78
38
23.3
4.61
-1.47
-7.55
39
24.3
5.79
-0.28
-6.34
40
25.3
6.95
0.90
-5.16
45
30.3
12.44
6.44
0.43
50
35.3
17.47
11.52
5.57
TABLE 1
Application Bulletin 124 - Page 5 of 13
Revision L00910
PSIA
PRESSURE
PSIG
DEW POINT
F
MEAN TEMP
F
BUBBLE POINT
F
55
40.3
22.14
16.23
10.32
60
45.3
26.48
20.62
14.76
65
50.3
30.56
24.74
18.92
70
55.3
34.40
28.63
22.85
75
60.3
38.04
32.31
26.57
80
65.3
41.50
35.80
30.10
85
70.3
44.79
39.13
33.47
90
75.3
47.94
42.32
36.69
95
80.3
50.96
45.37
39.78
100
85.3
53.85
48.30
42.75
105
90.3
56.64
51.13
45.61
110
95.3
59.33
53.85
48.37
115
100.3
61.93
56.49
51.04
120
105.3
64.44
59.03
53.62
125
110.3
66.87
61.50
56.12
130
115.3
69.23
63.89
58.54
135
120.3
71.52
66.21
60.90
140
125.3
73.74
68.47
63.19
145
130.3
75.91
70.67
65.42
150
135.3
78.02
72.81
67.59
155
140.3
80.07
74.89
69.71
160
145.3
82.08
76.93
71.78
170
155.3
85.95
80.87
75.78
180
165.3
89.64
84.62
79.60
190
175.3
93.19
88.23
83.27
200
185.3
96.59
91.70
86.80
210
195.3
99.86
95.03
90.20
220
205.3
103.01
98.25
93.48
230
215.3
106.05
101.35
96.65
240
225.3
109.00
104.36
99.71
250
235.3
111.84
107.27
102.69
260
245.3
114.60
110.09
105.58
270
255.3
117.28
112.83
108.38
280
265.3
119.88
115.50
111.11
290
275.3
122.41
118.09
113.77
TABLE 1
Application Bulletin 124 - Page 6 of 13
Revision L00910
PSIA
PRESSURE
PSIG
DEW POINT
F
MEAN TEMP
F
BUBBLE POINT
F
300
285.3
124.88
120.62
116.36
310
295.3
127.27
123.08
118.89
320
305.3
129.61
125.49
121.36
330
315.3
131.89
127.83
123.77
340
325.3
134.12
130.13
126.13
350
335.3
136.29
132.37
128.44
360
345.3
138.41
134.56
130.70
370
355.3
140.49
136.71
132.92
380
365.3
142.52
138.81
135.09
390
375.3
144.51
140.87
137.22
400
385.3
146.46
142.89
139.31
410
395.3
148.37
144.87
141.37
420
405.3
150.24
146.81
143.38
430
415.3
152.08
148.73
145.37
TABLE 1
R22
315
305
295
285
275
Pressure (Psia)
265
255
245
235
225
215
205
195
185
175
165
155
145
135
125
80
90
100
110
120
FIGURE # 1
130
Pressure (Psia)
80
60
40
20
0
-20
-10
10
20
30
40
FIGURE # 2
50
Plastics compatibility
Elastomers compatibility
Lubricant (viscosity, manufacturer, additives)
Solid core driers: Check with drier manufacturer for recommendation
6.2
6.3
6.4
Remove R22 charge. Remove refrigerant and collect in a recovery cylinder using a
recovery device capable of pulling 10 - 20 in. Hg vacuum. If the correct R22 charge
size for the system is not known, weigh the amount of refrigerant removed. The initial
quantity of R407C charged in the system will be determined from this weight.
6.5
Remove compressor. The compressor must be removed from system since it will not
be compatible with HFCs/POE lubricant.
6.6
Replace filter drier. Replace filter drier with one approved for use with R407C
refrigerant/polyol ester lubricant.
6.7
Install compressor. Using normal service practices, install compressor approved for
R407C refrigerant/polyol ester lubricant.
Application Bulletin 124 - Page 10 of 13
Revision L00910
Leak check system. Use normal service practices. If a leak detector is used, consult the
leak detector manufacturer for units sensitivity to R407C.
6.9
Evacuate. Use normal service practices to remove air and other non-condensables in
the system, evacuate to at least 200 microns.
6.10 Charge system with R407C. To ensure that the proper refrigerant composition is
charged in the system, it is important that liquid only be removed from the charging
cylinder. Once removed from the cylinder, R407C can be charged to the system as
vapor as long as all of the refrigerant removed from the cylinder is transferred to the
system.
Due to the liquid density difference of R407C versus R22, the refrigeration system will
requires less weight of R407C than R22. The optimum charge will vary depending on
the operating conditions, size of the evaporator and condenser, size of receiver (if
present), and length of pipe or tubing runs in the system. For most systems, the
optimum charge will be 85 - 90% by weight of the original R22 charge. It is
recommended that the system be initially charged with about 85% by weight of the
original R22 charge (refer to section 6.4).
Add the initial charge to the liquid line of the system with the compressor not running.
When the system and cylinder pressures are equal, start the compressor and meter the
remainder of the refrigerant into the suction line of the system. Since some
compressors may be damaged if liquid refrigerant enters the suction side of the
compressor, it is important to charge the refrigerant slowly into the suction line to
allow it to vaporize before it enters the compressor. A throttling valve can be used to
ensure that the liquid is converted to vapor prior to entering the system.
6.11 Charge adjustment. Allow the system to run until conditions stabilize. Add additional
R407C in small amounts until the system conditions reach the desired levels (refer to
data recorded in step 6.3). Be sure to charge by evaporator/condenser temperatures
since the pressures will be higher at the temperatures equal to R22. Total charge
should not exceed original R22 charge levels.
6.12 Label components and system. After completion of retrofit, label the system and the
converted components to identify the type of refrigerant and lubricant, so proper
service will be performed in the future.
Attached is a Retrofit Checklist (Appendix 1) for R407C to assist you in the retrofit
process and a System Data Sheet (Appendix 2) to record the system operating
conditions for your records.
Appendix 1
Checklist for R407C Retrofit
1. Consult the original equipment manufacturer of the system components for their
recommendation concerning compatibility and their retrofit procedures in order to
sustain warranty
2. If compressor is operable, run high flow condition (highest suction pressure for 10 - 15
minutes to maximize oil return to compressor).
3. Remove R22 charge from system (need 10-20 in. Hg vacuum to remove charge). Use
recovery cylinder --Do not vent to atmosphere-4. Replace filter drier with new filter drier approved for use with R407C.
- Loose fill driers: Use XH7 or XH9 desiccant or equivalent.
- Solid core driers: Check with drier manufacturer for recommendation.
5. Replace compressor with one approved for usage with R407C.
- Measure and record oil remaining in old compressor
- Residual lubricant should be less than 5% by weight of the total lubricant used in
system
6. Leak check system.
7. Evacuate with vacuum pump using normal service practices (200 microns minimum).
8. Charge system with R407C.
- Initially charge 85% by weight of original equipment manufacturer specified R22
charge.
- Amount of refrigerant charged: _______
9. Start up equipment and adjust charge until desired operating conditions are achieved.
- If low on charge, add in increments of 2 - 3% of original R22 charge.
- Amount of refrigerant charged:
_______
10. Total Refrigerant Charged (add 8 and 9)
_______
- Should not exceed original R22 charge level
11. Label components and system for type of refrigerant (R407C) and lubricant (polyol ester
oil).
12. Conversion is complete!!
Appendix 2
SYSTEM DATA SHEET
Type of System/Location:
Equipment Mfg.:
Compressor Mfg.:
Model No.:
Model No.:
Serial No.:
Serial No.:
Original Lubricant:
Type/Mfg.:
Charge Size:
New Lubricant:
Type/Mfg.:
1st Charge Size:
2nd Charge Size:
Additional Charge Size:
Drier Mfg.:
Model No.:
Loose Fill:
Solid Core:
Capillary Tube:
Expansion Valve:
If Expansion Valve:
Manufacturer:
Model No.:
Control/Set Point:
Location of Sensor:
Other System Controls (e.g.: head press control); Describe:
(circle units used where applicable)
R22 Data
R407 Data
Date/Time
Refrigerant
Charge Size Lb.
Ambient Temperature (F/C)
Relative Humidity
Compressor:
Suction Temperature (F/C)
Suction Pressure psig
DischargeTemperature (F/C)
Discharge Pressure psig
Indoor Temperature (F/C)
Evaporator:
Refrigerant Inlet Temperature (F/C)
Refrigerant Outlet Temperature (F/C)
Coil Air/H 2O In Temperature (F/C)
Coil Air/H 2O Out Temperature (F/C)
Refrigerant Temperature @ Superht. Ctl. Pt. (F/C)
Condenser:
Refrigerant Inlet Temperature (F/C)
Refrigerant Outlet Temperature (F/C)
Coil Air/H 2O In Temperature (F/C)
Coil Air/H 2O Out Temperature (F/C)
Exp. Device Inlet Temperature (F/C)
Motor Amps
Run/Cycle Time
Comments: