Documente Academic
Documente Profesional
Documente Cultură
Hong Kong Community College, The Hong Kong Polytechnic University, Hong Kong, China
Department of Building Services Engineering, The Hong Kong Polytechnic University, Hong Kong, China
A R T I C L E I N F O
A B S T R A C T
Article history:
Received 27 July 2009
Received in revised form 25 August 2009
Accepted 25 August 2009
A water-cooled chiller system in an air-conditioned hotel can take up about one-quarter of the total
electricity consumption and considerable amounts of water in the heat rejection process. This paper
evaluates operating cost savings of a chiller system integrated with optimal control of cooling towers and
condenser water pumps. A sophisticated chiller system model was used to ascertain how different
control methods inuence the annual electricity and water consumption of chillers operating for the
cooling load prole of a reference hotel. It is estimated that applying load-based speed control to the
cooling tower fans and condenser water pumps could reduce the annual system electricity use by 8.6%
and operating cost by 9.9% relative to the equivalent system using constant speed fans and pumps with a
xed set point of 29.4 8C for cooling water temperature control. The ways to implement this advanced
control for system optimization are discussed.
2009 Elsevier B.V. All rights reserved.
Keywords:
Water-cooled chiller
Cooling tower
Economic analysis
Optimum control
1. Introduction
Hotels play an important role in sustaining the economic
growth of Hong Kong. Yet they constitute one of the major energy
end users in the commercial sector because of their round-theclock operation. A previous survey [1] indicated that the overall
electricity consumption in the hotel segment increased from 443
to 921 GWh (a 108.2% increase) from 1988 to 2000. With the
increasing supply of local hotels, it was estimated that their
electricity demand could grow by 36.8 GWh per annum over the
period of 20012005 [2]. One possible way to moderate the
increasing electricity demand is to improve the energy performance of air-conditioning systems which account for around half
of the total electricity consumption. According to studies on the
electricity consumption of 16 local hotels [3,4], their energy use
intensity (EUIthe annual electricity consumption in kWh per unit
oor area of a building in m2) varied widely from 198 to 926 kWh/
m2 with an average of 406 kWh/m2. For hotels with central airconditioning plants, water-cooled chiller systems with cooling
towers are commonly used to provide cooling energy in the form of
chilled water to maintain the thermal conditions required for
indoor areas. The operation of chillers and cooling towers leads to
the peak electricity demand and accounts for about half of
electricity consumption for air conditioning. Moreover, cooling
204
made on the trade-off between the chiller power, tower fan power
and condenser water pump power under the reduced ow
conditions. Also no control regime was given on how the condenser
water ow should vary in response to the chiller load and wet-bulb
conditions. Variable speed control is increasingly applied to
cooling tower fans to reduce their cycling frequency and allow
better heat rejection control with decreased fan power [9]. The
dynamic characteristics of cooling towers with the varying heat
rejection airow impose more complications in system optimization. Lu et al. [10] presented a model-based optimization strategy
for the condenser water loop of a chiller system. The strategy
involved minimizing the total power of the chillers, condenser
water pumps and cooling tower fans, taking into account the
interaction between the varying air ow rate and condenser water
ow rate for a given heat rejection rate. The inuence of the
condenser water entering temperature on both the chiller power
and cooling tower performance was analysed. Yet they did not
explain the control logic of the condenser water pump and cooling
tower fan for system optimization.
Graves [11] reformulated the GordonNg model [7] in order to
optimize a system designed with two chiller-pump pairs and one
cooling tower. The chiller model was coupled with an Ntueffectiveness (Ntuno. of transfer units) model [12] for evaluating
the cooling tower performance. Drawing on the chillertower
interaction, the modied model was used to analyse how the
system COP varied with the changing condenser water ow. Yet
the tower model discounted the water loss due to evaporation, and
a single NTU value was assumed to represent the tower
performance at different water and airow rates. Two correlations
were identied to facilitate near-optimal system operation: one
was the linear relationship between the cooling water set point
and wet bulb (an analogy to the xed approach method); another
was the linear relationship between the tower fan speed and pump
speed. Benton et al. [13] developed a regression model to represent
the improved cooling tower simulation algorithm (CTSA). The
algorithm simply indicated the cooling tower approach (cooling
water leaving temperature subtracted from wet-bulb temperature) as a dependent variable of the wet-bulb temperature, range
(temperature difference of cooling water), condenser water ow
and fan power. It remains to be ascertained how to evaluate an
optimal set point for cooling water temperature or the optimal fan
Table 1
General information about the hotel and its air-conditioning systems.
General
Gross oor area (GFA) (m2)
Total air-conditioned area (m2)
U-values of wall/window/roof (W/m2 8C)
Shading coefcient of glass
52,020
45,540 (87.5% GFA)
1.9/5.4/0.7
0.55
Area
Area per oor (m2)
Air-conditioned area per oor (m2)
Number of oors
Cooling temperature set point (8C)
Relative humidity (%)
Ventilation rate (L/s/person)
Occupancy (m2/person)
Equipment power density (W/m2)
Lighting power density (W/m2)
Guestrooms
2,010
2,010
18
24
50
7.5
18
12
18
01002400
01002400
01002400
08002300
08002300
08002300
2-way valve
01002400
2-way valve
4800
Centrifugal
R134a
1600
280.7
5.7
7/12.5
72
33/38
87
2004
34.4/29.4
87
63
22.8
0.2
0.53
28
28
21.6
205
cooling capacity of 1600 kW each. This multiple-chiller arrangement is commonly used to enhance exibility and back up capacity
at part load operation. The capacity modulation of each centrifugal
chiller is done by varying the opening of the inlet guide vanes. Each
chiller is coupled with a constant speed chilled water pump to
deliver the rated ow rate to the chiller evaporator. There is a
differential pressure by-pass pipe in the single-loop pumping
system to balance the ow of chilled water supplied by the staged
chillers against the demand of chilled water required by the airside
system coils.
Chiller sequencing was implemented under which all the
running chillers carried the same part load, and no additional
chillers in the chiller arrangement started to operate until each of
the operating chillers was running at full load. Following this
strategy for staging chillers, two and three chillers operated when
the building cooling load exceeded 1600 and 3200 kW, respectively. Each chiller operating was interlocked with one chilled
water pump, one condenser water pump and one cooling tower.
3.2. Calculation of the annual electricity consumption of the chiller
system
A sophisticated chiller system model was developed using
TRNSYS 15 in order to compute the annual electricity consumption
of chillers, pumps and cooling tower fans. The model considered
the real process phenomena, including the capacity control of
compressors and mechanistic relations between chiller components. In simulating the operation of a chiller of any given size, the
compressors and the condenser satised the mass balance of
refrigerant and the energy balance at the evaporator. The cooling
towers were modelled using the Ntu-effectiveness approach with
which a change in the heat transfer effectiveness of the tower at
various combinations of airow and water ow is taken into
account. An algorithm was included in the cooling tower module to
compute the operating variables of the cooling towers based on a
given set point of cooling water leaving temperature. Details about
the development of the model and its validation were given
elsewhere [15].
The hourly chiller power was computed by using the chiller
system model based on the hourly weather data and the load
which each operating chiller carried. The electricity consumption
of the chilled water pumps varied step by step, depending on the
number of chillers operating. The fan power of each cooling tower
operating depends on whether it is on/off or variable speed control
is used and on the set point of the temperature of cooling water
leaving the cooling tower. The overall annual electricity consumption of the chiller plant is the sum of all chiller power, pump
power and cooling tower fan power for all operating hours.
3.3. Prediction of water consumption costs and electricity costs
The make-up water of a cooling tower serves to compensate for
three parts of water loss: evaporation, drift and bleed-off. The
cooling tower module within the system model considered the
overall mass and energy balance of cooling water and air to
estimate the evaporation loss. The drift rate and bleed-off rate
were assumed to be 0.2% and 0.6%, respectively, of the cooling
water circulation rate, with regard to the use of the traditional
chlorination water treatment technology. The make-up water cost
of HK$4.58/m3 and the sewage charge of HK$1.2/m3 from bleed-off
were used to calculate the overall water consumption and
discharge cost for the operation of cooling towers, based on the
guidelines stated in the pilot scheme for the wider use of fresh
water in evaporative cooling towers for energy-efcient airconditioning systems [16]. The calculation of the electricity cost of
the chiller plant was based on the maximum demand tariff of a
206
helps offer fan power savings when the chiller load could drop with
the ambient wet-bulb temperature (Tawb) and that this control
provides more energy savings compared with the xed set point
control [9]. For Schemes 4 and 8, the algorithm of simulating tower
fan control searched for an optimal Tctwl to minimize the sum of
compressor power, condenser water pump power and cooling
tower fan power for any given operating condition. The optimal fan
speed for maximum system performance was determined along
with the optimal Tctwl. Scheme 1 is regarded as the baseline
because it is conventionally applied to existing chiller systems.
Schemes 28 represent individual and mixed uses of the energyefcient technologies.
Comparisons were made on how the system COP varied under
Schemes 28 in relation to the baseline. The system COP means the
chiller load output divided by the total input power of the chiller,
condenser water pump and cooling tower fan. All the schemes had
the same power of chilled water pumps and so it was excluded
from the calculation of system COP. As Fig. 2 illustrates, lowering
Tctwl to 18.3 8C could not bring about an absolute increase in the
system COP, though the compressor power was lowest for most
operating conditions among the other operating schemes. Indeed,
the system COP could drop by up to 11% when the chiller load
reduced to a part load ratio of 0.2. This is because the tower fans
operated at full speed continuously and the increase of the fan
power exceeded the reduction of the compressor power. Except
the 18.3 8C Tctwl control, the system COP could be improved by
applying variable speed control to the condenser water pump. This
implies that modulating the condenser water ow in direct
proportion to the chiller load is a viable means to optimize the
trade-off between the compressor power and condenser water
pump power.
The system COP could increase by various degrees for all
operating conditions when using the 4 8C approach or implementing the optimal Tctwl, regardless of whether the on/off or variable
speed control was used for the tower fans and condenser water
pumps. When the wet-bulb temperature was below 28 8C, the
percentage increase in the system COP was more noticeable at
higher chiller loads under the 4 8C approach control. The system
COP increased by 1.416.1% by using the optimum Tctwl and
variable speed control for both the fans and pumps. Such an
increase tends to be signicant at the minimum and maximum
loading conditions and be moderate at a part load ratio of around
0.5 with a wet-bulb temperature of below 28 8C.
5. Economic benets of the energy-efcient technologies
Table 3
Operating schemes of different controls of condenser water pump and cooling
tower.
Scheme
Notation
Description
1 (baseline)
Tctwl29.4CS
Tctwl18.3CS
App4CS
Tctwl,opCS
Tctwl29.4VS
Tctwl18.3VS
App4VS
Tctwl,opVS
207
Fig. 2. Percentage change of system COP in Schemes 28 in relation to the baseline. (a) Wet-bulb temperature = 16 8C, (b) wet-bulb temperature = 20 8C, (c) wet bulb
temperature = 24 8C, (d) wet bulb temperature = 28 8C.
trade-off between the chiller power, pump power and fan power
was optimized, resulting in an 8.6% decrease in the annual system
electricity consumption. Furthermore, the optimal control in
Scheme 8 could bring about a 14.8% reduction in the annual
water consumption.
To investigate the economic benets of the energy-efcient
technologies for the chiller system, the annual operating costs and
life cycle costs were calculated and compared. Operating costs
(such as repair and maintenance costs) other than the electricity
and water charges were assumed to be the same value for all the
schemes and they were excluded in this cost analysis. Regarding
the calculation of the life cycle operating costs, a life span of 15
years was assumed for the chiller system and a discount rate of 10%
was considered throughout the lifespan. Table 5 gives the
calculation results. The annual electricity cost dictates the overall
operating cost based on its overwhelming proportion and so
reducing electricity use is an effective means to lower the
operating cost.
Table 4
Annual chiller plant electricity and water consumption per unit of air-conditioned oor area of the hotel.
3
Scheme
1 (baseline)
66.6
9.4
7.2
4.7
87.9
63.2
9.4
7.2
5.2
85.0
70.9
9.4
3.3
1.2
84.7
66.7
9.4
3.3
7.2
86.6
69.1
9.4
3.3
1.5
83.2
67.0 (2.24%)
9.4 (0%)
3.3 (54.17%)
1.6 (58.84%)
81.3 (8.63%)
341.7
353.0
245.6
316.0
258.4
266.9 (14.81%)
380.6
208
Table 5
Annual operating costs and life cycle costs per unit of air-conditioned oor area of the hotel for the chiller system with eight operating schemes.
Scheme
1 (baseline)
94.2
6.2
100.4
91.0
6.4
97.4
89.5
4.6
94.1
91.4
5.8
97.2
87.9
4.8
92.7
86.1 (9.57%)
5.0 (15.91%)
91.1 (9.94%)
716.7
47.0
763.7
692.1
48.6
740.7
680.4
35.1
715.4
695.5
43.9
739.3
668.5
36.7
705.2
655.1 (9.57%)
37.9 (15.91%)
693.0 (9.94%)
pumps and the associated control system. After the operating cost
savings fully recoup the implementation cost, the building owner
can enjoy a prot of around HK$3,025,722 due to the optimal
control throughout the rest of the functional life of the system. It is
envisaged that the implementation of optimal control would be
more economically attractive if there is a subsidized scheme or
rebate for purchasing energy-efcient equipment.
6. Implementation of load-based speed control for system
optimization
PLRSpump;full
0:5S pum p; full
(1)
(2)
The load-based speed control for the tower fans brings about a
slight increase of 0.4 kWh/m2 from 81.3 kWh/m2, the lowest
annual electricity consumption of the chiller system in Scheme 8.
The proposed control eliminates the need to determine the
optimum cooling water temperature based on the ambient wetbulb temperature which is likely to be suffered from imprecise
measurement. Furthermore, the optimal control of the whole
system can be highly simplied. This is because the sequencing of
chillers, pumps and tower fans and their individual speed controls
can be based entirely on the chiller load conditions only.
7. Conclusions
This paper presents the economic benets of a water-cooled
chiller system with the individual and mixed uses of energyefcient technologies: variable speed congurations for condenser
water pumps and cooling tower fans; improved cooling water
control methods (constant set point of 18.3 8C, a xed approach of
4 8C to wet-bulb temperature and optimized method to minimize
the overall power). Drawing on a sophisticated model, the
characteristics of improved chiller system COP with various
energy-efcient technologies were identied. Load-based speed
control is introduced for the tower fans and condenser water
pumps to achieve system optimization with minimum power
consumption. Implementing the optimum control to a chiller
system could bring about a saving of HK$10.1/m2 in the annual
operating cost per unit of the total air-conditioned oor area of a
reference hotel in Hong Kong. It is expected that load-based speed
control is generic for all types of multiple-chiller systems with full
or partial use of variable speed drives for the system components.
The economic analysis reported here can help hotel owners realize
the likely reduction in operating costs and decide which
technology is cost-effective or even prot-making with respect
to their budget for implementing chiller system improvement
programmes.
Acknowledgement
References
[1] W.W. Chan, J.C. Lam, Prediction of pollutant emission through electricity consumption by the hotel industry in Hong Kong, International Journal of Hospitality
Management 21 (2002) 381391.
[2] F.W. Yu, K.T. Chan, Electricity end-use characteristics of air-cooled chillers in
hotels in Hong Kong, Building and Environment 40 (2005) 143151.
[3] S. Deng, J. Burnett, A study of energy performance of hotel buildings in Hong Kong,
Energy and Buildings 31 (2000) 712.
[4] F.W.H. Yik, J. Burnett, I. Prescott, Predicting air-conditioning energy consumption
of a group of buildings using different heat rejection methods, Energy and
Buildings 33 (2001) 151166.
[5] T. Hartman, All-variable speed centrifugal chiller plants, ASHRAE Journal 43 (9)
(2001) 4353.
[6] W.P. Bahneth, E.B. Peyer, Varying views on variable-primary ow, HeatPiping
Air Conditioning Engineering 76 (3) (2004) S59.
[7] J.M. Gordon, K.C. Ng, H.T. Chua, C.K. Lim, How varying condenser coolant ow rate
affects chiller performance: thermodynamic modeling and experimental conrmation, Applied Thermal Engineering 20 (2000) 11491159.
[8] M. Hydeman, P. Sreedharan, N. Webb, S. Blanc, Development and testing of a
reformulated regression-based electric chiller model, ASHRAE Transaction 108 (2)
(2002), paper no. HI-02-18-2.
209
[9] H. Crowther, J. Furlong, Optimizing chillers and towers, ASHRAE Journal 46 (7)
(2004) 3440.
[10] L. Lu, W. Cai, Y.C. Soh, L. Xie, S. Li, HVAC system optimizationcondenser water
loop, Energy Conversion and Management 45 (2004) 613630.
[11] R.D. Graves, Thermodynamic modeling and optimization of a screw compressor
chiller and cooling tower system, Msc Thesis, The Ofce of Graduate Studies of
Texas A&M University, 2003.
[12] J.E. Braun, G.T. Diderrich, Near-optimal control of cooling towers for chilled water
systems, ASHRAE Transaction (1990), SL-90-13-3.
[13] D.J. Benton, M. Hydeman, C.F. Bowman, P. Miller, An improved cooling tower
algorithm for the CoolToolsTM simulation model, ASHRAE Transaction 108 (1)
(2002), paper no. AC-02-9-4.
[14] Solar Energy Laboratory, TRNSYS: A Transient System Simulation Program (Reference Manual), University of Wisconsin/Madison Press, Madison, WI, 2000.
[15] F.W. Yu, K.T. Chan, Optimization of water-cooled chiller system with load-based
speed control, Applied Energy 85 (2008) 931950.
[16] Electrical, Mechanical Services Department, Pilot Scheme for Wider Use of Fresh
Water in Evaporative Cooling Towers for Energy-efcient Air Conditioning
Systems, Author Press, Hong Kong, 2000.
[17] Air-Conditioning & Refrigeration Institute, Standard 550/590: Performance Rating of Water Chilling Packages Using the Vapor Compression Cycle, Author Press,
Arlington, Virginia, 2003.