Documente Academic
Documente Profesional
Documente Cultură
a r t i c l e
i n f o
Article history:
Received 30 November 2007
Accepted 5 August 2008
Available online 12 August 2008
Keywords:
Water-cooled chiller
Simulation
Variable speed
Electricity and water consumption
a b s t r a c t
There are increasing views on implementing all-variable speed chiller plants in place of conventional
constant speed plants. Supporters of these views claim that all-variable speed chiller systems can operate
much more efciently at part load in response to changes in building cooling load. This paper introduces
load-based speed control for all-variable speed plants to optimize their environmental performance.
Thermodynamic-behaviour chiller system models were developed to perform environmental assessment
(in terms of annual electricity and water consumption) for typical constant speed and all-variable speed
chiller systems operating for the cooling load prole of a local ofce building. Operating cost differences
between the two systems were calculated and compared in an economic analysis. Applying load-based
speed control to the variable speed chiller plant can decrease the annual total electricity use by 19.7%
and annual water use by 15.9% relative to the corresponding constant speed plant. The signicance of this
study is to provide more insights into how to make chiller systems more sustainable.
2008 Elsevier Ltd. All rights reserved.
1. Introduction
Central chiller plants have long been used to provide cooling energy for comfort air conditioning at the expense of considerable
electricity. Where water-cooled heat rejection systems are concerned, each plant contains multiple chillers, chilled water distribution pumps, condenser water pumps and cooling towers. For
many existing chiller plants, variable speed applications are limited to the tower fans and secondary-loop chilled water pumps if
the plant employs a primary/secondary pumping system. It is
worth widening the use of variable speed drives (VSD) for all the
components in order to make chiller systems operate as efciently
as possible. According to Crowther and Furlongs study [1], applying VSD to cooling tower fans with optimized control could make a
58% improvement in system energy performance, relative to the
equivalent system but with on/off fan control and a xed condenser water temperature set point. They addressed challenges
of varying the ow of condenser pumps during part load conditions
and indicated that the increased condenser water temperature
range under the reduced ow conditions could inuence the chiller
work, tower heat transfer effectiveness, and the system as a whole.
There are some studies focusing on applying VSD individually to
the chillers, chilled water pumps and condenser water pumps.
Qureshi and Tassou [2] made a review on the use of VSD for chiller
systems. They conrmed that VSD has been applied successfully to
perform capacity modulation for chiller compressors. The VSD
* Corresponding author. Tel.: +852 3746 0416; fax: +852 2364 7375.
E-mail address: ccyufw@hkcc-polyu.edu.hk (F.W. Yu).
1359-4311/$ - see front matter 2008 Elsevier Ltd. All rights reserved.
doi:10.1016/j.applthermaleng.2008.08.003
1722
optimize the control sequence of chilled water plants using VSD for
the chillers, condenser water pumps and cooling tower fans. Based
on simulation results of an example chiller plant, they demonstrated that the speed of the condenser pumps and tower fans
should be adjusted in response to the chiller load in order to
achieve optimized plant performance.
Gordon et al. [7] highlighted that the condenser water ow rate
could be a control variable in improving the energy performance of
chiller systems. They established an analytic semi-empirical chiller
model to study variations of chiller COP (coefcient of performance) at different condenser water ow rates. No analysis was
made on the system level involving the interaction between the
compressor power, pump power and tower fan power. The model
serves well for fault detection and diagnosis purposes, but is incapable of accounting the varying operating characteristics of cooling
towers. No control regime was generalized on how the condenser
water ow should be varied in response to various chiller load
and wet-bulb temperature conditions in order to achieve optimal
energy performance of the system.
Hartman is a pioneer promoting all-variable speed chiller plants
where all the chillers, condenser pumps and tower fans are driven
by VSD [8]. He explained criteria for designing such plants, selecting the equipment and operating the equipment in order to
achieve the highest overall plant performance at part load conditions. Based on his simulation analyses, the annual energy use of
all-variable speed chiller plants with optimized controls would
be on average 28% lower than the corresponding conventional constant speed plants with equipment of the same nominal efciency
at design conditions. He also developed the equal marginal performance principle (EMPP) for designing efcient air-conditioning
systems [9]. The EMPP involves understanding the power relationships between the system components and formulating the powerbased speed control algorithms to operate the variable speed
equipment.
All the past studies have brought individual contributions to
promoting VSD applications in chiller systems. Yet there is a lack
of simple but generic approach to controlling all-variable speed
chiller plants. More track records of using all-variable speed chiller
systems with advanced control are considered necessary, considering the use of variable speed technology will continue to grow to
sustain highly efcient chiller systems. The aim of this paper is
to investigate how load-based speed control should be applied to
all-variable speed chiller plants to enhance their environmental
and economic benets. This paper rst describes an all-variable
speed chiller plant and a conventional constant speed plant considered in the simulation study. Optimal regions of constant and variable speed chillers will be presented to illustrate how to
determine optimum chiller sequencing. Based on the chiller system models developed, the annual electricity and water consumption will be predicted for the two systems operating for the cooling
load prole of an ofce building. Operating cost differences between the two systems will be calculated and compared in an economic analysis. Discussion will be given on how the pumps and
tower fans should operate based on the simple load-speed relationship in order to achieve near optimal system control. After that,
some remarks will be made on using the EMPP and power-based
speed control for system optimization. The signicance of this
study is to provide more solid data which helps widen the use of
all-variable speed chiller systems for greener buildings.
2. Methods of study
2.1. Equipment and plant arrangement
Figs. 1 and 2 show two systems with the conventional and allvariable speed congurations considered in the simulation study.
CT 1
CT2
CT 3
Chiller 1
(2130 kW)
Chiller 2
(2130 kW)
Condenser
water pumps
Chiller 3
(2130 kW)
Primary chilled
water pumps
Decoupling bypass
VSD
VSD
Variable speed secondary
chilled water pumps
1723
CT 1 VSD
CT 2 VSD
VSD
CT 3 VSD
Chiller 1 VSD
(2130 kW)
VSD
VSD
VSD
Condenser
water pumps
Chiller 2
(2130 kW)
VSD
Chiller 3
(2130 kW)
VSD
VSD
VSD
Primary chilled
water pumps
Table 1
Physical data of two chiller systems
System
Conventional
All-variable
speed
6390
6390
R134a
2130
350
6.1
7.0
7/12.5
R134a
2130
350
6.1
9.8
7/12.5
92.4
30/35.5
92.4
30/35.5
107.6
107.6
Cross-ow
2480
30/35.5
107.6
Axial, two
speed
84
100.8
30.4
0.2
0.53
Cross-ow
2480
30/35.5
107.6
Axial,
variable
speed
84
100.8
30.4
0.2
0.53
26
26.1
26
62.7
54.9
28.8
28.8
30
800
25
700
600
500
15
400
300
10
200
100
0
20
.9-1
9
ECWT (oC)
Chiller COP
900
1724
18.3
23.9
29.4
7
6
Optimal region
5
4
3
0
0.2
evaluation are given elsewhere [11]. The building had a peak load
of 6389 kW with annual cooling hours of 2834 h (90.5% of the
buildings annual opening hours). The hourly cooling loads of the
building were modelled in the subtropical Hong Kong climate
using an example weather year. The annual cooling energy was
7,423,883 kWh. Fig. 3 shows the load-frequency distribution of
the building along with the average outdoor wet-bulb temperature
at each load bin. The hourly building cooling load data are expressed as ratios to the peak level of 6389 kW. It is undesirable
to have a single chiller system operating for the building load prole as the rst bar at the load bin of 0.10.2 in Fig. 3 illustrates, the
chiller needs to work at a part load ratio of 0.2 or below with very
low COP for 28% of the total cooling hours. Given this situation,
three identical chillers were considered for the two systems serving the building. It is possible to ensure that each of the three chillers carries a part load ratio (PLR) of at least 0.28 which is well
above its minimum allowable capacity step. The minimum PLR of
0.28 refers to a situation where one of the three chillers rated at
2130 kW operates for the lowest building load of 596 kW.
2.3. Optimal region of chiller
Given that chiller power dominates the system power, it is
worth determining how to stage chillers for their most efcient
operation. Running chillers at full load as far as possible is a conventional way to minimize system power, considering that most
existing chillers with constant speed compressors have maximum
COP at full load and that pumping energy per unit cooling capacity
is lowest at full load conditions. However, prolonging the full load
operation of chillers cannot achieve the least power consumption if
they have superior COP at part load instead of at full load. It should
be noted that in absence of storage devices, operating the chiller at
part load in order not to dissipate surplus cooling energy is convenient, although the COP could result in a lower level. To meet the
actual cooling load, it is essential to look for minimum power consumption of the whole plant rather than maximum chiller COP. A
more generic approach to operating chillers with maximum efciency is based on the optimal loading points or region at which
the maximum COP takes place for any given condenser water
entering/leaving temperature.
Figs. 4 and 5 show the part load performance curves of the constant speed and variable speed chillers together with their optimal
region at different entering condenser water temperatures (ECWT).
With regard to the constant speed chiller, the COP drops considerably at low part load ratios and the local maxima are situated in a
at region of the curve (PLR of 0.81) with a slight variation of 5%
in COP, regardless of the condenser water temperatures. For the
variable speed chiller, the COP increases considerably, taking into
0.6
0.8
Fig. 4. Part load performance curves for the constant speed centrifugal chiller.
15
Chiller COP
Fig. 3. Frequency distribution of hourly building load ratios with average wet-bulb
temperature at each load bin.
0.4
10
ECWT ( o C)
18.3
23.9
29.4
5
Optimal region
0.2
0.4
0.6
0.8
account the condenser temperature relief under part load conditions. The maximum COP occurs at lower chiller loads when ECWT
drops, resulting in the optimal region leaning towards the low load
conditions. ECWT could be considered as a parameter other than
COP used to adjust the optimal chiller load region.
The schedules of chiller sequencing shown in Tables 2 and 3
were formulated for the two systems in order to maximize the
chiller performance. Regarding the conventional system, the traditional principle of chiller sequencing is still applicable as the optimal region of the chillers is quite close to the full load for all
condenser water entering temperatures. The least number of chillers operating is still used to meet the changing building cooling
load. While for the all-variable speed system, all the three chillers
would be staged starting from a building load ratio of 0.63, instead
of 0.67, in order to allow them to run as closely as possible to the
optimal region. The start-up frequencies of the three chillers in the
two systems are roughly the same.
3. Simulation of electricity and water use for the chiller system
The chilled water plant simulation was performed with the use
of component models for the chillers, pumps and cooling towers
developed under the TRNSYS 15 environment [12]. Fig. 6 shows a
ow diagram of the modelling the chiller under TRNSYS 15. Please
refer to Ref. [13] for details of the model and equations used. Input
variables of the model comprise the chiller load (Qcl), dry-bulb
temperature (Tadb), wet-bulb temperature (Tawb), chilled water
supply temperature (Tchws), chilled water mass ow rate (mw), condenser water ow rate (mcdw) and condenser water entering temperature (Tcdwe). Given these input variables, the model computes
over 30 operating variables, the power-related variables and chiller
1725
Table 2
Schedule of staging chillers for the conventional system
Building load
ratio (BLR)
No. of
total
cooling
hours
No. of
operating
chillers
Total
capacity of
operating
chillers
1171
1086
577
1
2
3
2130
4260
6390
0.28
0.5
0.67
Minimum
1
1
1
Table 3
Schedule of staging chillers for the all-variable speed system
Building load
ratio (BLR)
No. of
total
cooling
hours
No. of
operating
chillers
Total
capacity of
operating
chillers
Maximum
1171
969
694
1
2
3
2130
4260
6390
0.28
0.5
0.63
1
0.95
1
Data file of
operating conditions
Data reader
Constant
parameters
Input variables:
Qcl, Tadb, Tawb , Tchws, mw, mcdw, Tcdwe
Maximum
Equations for
evaluating refrigerant
properties
for Va 6 0:5Var ;
Compressor
Condenser
Printer
Operating variables in
each operating condition
Control
algorithm of
cooling towers
4
5
1726
Table 4
Annual plant electricity and water consumption per unit of air-conditioned oor area
of the building
System
Conventional
(1)
All-variable
speed (2)
80.6
(9.0%)
(48.5%)
(61.8%)
(10.3%)
(19.7%)
(15.9%)
the condenser water pumps, chillers and tower fans. This suggests
that reducing the ow rate of chilled water and condenser water is
a viable means to decrease greatly the system power during part
load operation, though it may give a diminishing return on the
reduction of chiller power resulting from a moderate increase in
the COP. With regard to the variable speed system, there was little
difference in the chiller COP between the nominal and reduced
chilled water ow conditions. However, when the condenser water
ow rate decreased with the chiller load or the wet-bulb temperature, the extent to which the chiller COP can increase would diminish in various degrees because the reduced condenser water ow
tempered the condensing temperature relief to save the compressor power. Indeed, the average chiller COPthe annual cooling energy of 7,423,883 kWh over the annual chiller electricity
consumptionincreased moderately to 6.7 even when the variable
speed chillers with a high IPLV of 9.8 were used. Given the reduced
condenser water ow conditions, the water consumption of the
cooling towers could drop by 15.9% in the all-variable speed case
in relation to the conventional case.
4.2. Economic analysis
In order to judge the cost-effectiveness of the variable speed
chiller system, it is necessary to predict the capital cost investment
and how much operating cost this system can save. Local tariff
structures were considered to evaluate the operating costs associated with the annual electricity and water consumption of the chiller systems. The maximum demand tariff of one of the local power
companies was used to calculate the annual electricity consumption. This tariff involves monthly demand charges of HK$42.1/
kVA for the rst 400 kVA and HK$41.1/kVA for the next additional
kVA, and monthly energy charges of HK$1.023/kWh for the rst
200 units (i.e. kWh) supplied per month per kVA of maximum demand and of HK$0.962/kWh for each additional unit supplied.
Regarding the water charge tariff, the make-up water cost of
HK$4.58/m3 and the sewage charge of HK$1.2/m3 from bleed-off
were used, based on guidelines stated in the pilot scheme for the
wider use of fresh water in evaporative cooling towers for energy-efcient air-conditioning systems [15].
Assuming that the variable speed system does not incur any
additional recurrent costs (such as repair and maintenance costs),
its cost-effectiveness can be analysed by using a simple payback,
net present value, and the internal rate of return which is a measure of return in percentage to be expected on a capital investment.
The life cycle operating cost was also considered, which is the sum
of the discounted value of the annual electricity and water costs
over the lifespan of the system. A 15-year economic life was used
for the chillers with reference to the economic analysis for
mechanical equipment in ASHRAE 90.1 [16]. During this 15-year
lifespan, it was assumed that no major alternation of the chiller
Table 5
Operating costs comparison for the two chiller systems
System
Conventional
(1)
180
Capital cost (HK$/m2)
Annual operating cost (HK$/m2)
Electricity
46.4
Water
2.7
Total
49.1
Simple payback (yr)
All-variable
speed (2)
198
18
39.4
2.2
41.6
2.4 (=18/7.5)
41.5
299.8
16.7
316.5
514.5
7.0
0.5
7.5
53.2
3.5
56.7
38.6
system would take place. Based on the current bank loan interest
rate and the perception of the future monetary value, a discount
rate of 10% was used in the calculation of the life cycle operating
cost [17]. The 15-year economic life was considered in the calculation of the internal rate of return.
Table 5 gives the economic indicators of the two systems. All
the cost gures are presented as HK$ per unit of the total air-conditioned oor area in m2 of the building. For the two systems, the
annual electricity cost accounts for around 95% of the annual total
operating cost. Given this, the operating cost saving is virtually
proportional to the annual electricity saving. Considering that the
capital investment of the conventional chiller system is HK$180/
m2 (assuming HK$1200 per kW of plant cooling capacity an
indicative gure from informal consultation with local chiller suppliers), the simple payback could be 2.4 years based on the
assumption that the variable speed drives and the associated control system of the all-variable speed system could cause an additional cost by up to HK$18/m2 or 10% of the capital cost of the
conventional system. In this situation, the building owner who
purchases the variable speed chiller system instead of the conventional ones can enjoy a net savings of HK$38.6/m2 when operating
the chiller system throughout the 15-year lifespan. The internal
rate of return was identied to be 41.5% which is much higher than
the assumed discount rate of 10%. This suggests that the variable
speed system is a better-paying investment. It will be more economically attractive to adopt such an all-variable speed chiller
plant if there is a cost premium to balance the additional cost
resulting from the use of VSD and a demand side management programme which provides a rebate for electricity savings by use of
energy-efcient measures.
4.3. Load-based speed control for all-variable speed chiller system
All the equipment in a variable speed chiller system should be
provided with proper speed control in order to effectively operate
the system with minimum power consumption. Each chiller makes
use of its own microprocessor with proprietary control to adjust
the compressor speed in response to the changing chiller load
while controlling the chilled water supply temperature at its set
point. The minimization of energy use for the system, therefore, refers to optimizing the operation of chilled water pumps, condenser
water pumps and cooling tower fans for all ambient and chiller
load conditions. Given the variable primary ow conditions, it is
worth ascertaining how to control the speed of the chilled water
pumps which deliver the ow required to meet the chiller load
while allowing the chillers to run closely at their optimal region
in order to minimize the total power consumption. Based on the
1727
RPMchp
A generic form for the direct fan speed control would be: RPMctf = c1
PLR + c2, where c1 and c2 are constants to be determined based on
the performance characteristics and power rating of cooling towers.
Such kind of simplied tower fan control has been given in a study
on a generic control algorithm for cooling towers [18]. Referring to
traditional cooling water temperature control, the approach (condenser water entering temperature minus ambient wet bulb) may
be xed irrespective of operating conditions to enhance chiller
tower control. Yet based on the graphical analysis shown in Fig. 8,
the optimal approach with minimum power consumption varied
between 3.6 and 4.9 C in response to the chiller load, but the approach-load relationship is very vague when the chiller operated
at above half load. This suggests that it is not feasible to use a cooling water temperature (with varying values at a given chiller load)
to control the tower fan speed in order to achieve minimum power
consumption.
Another chiller system simulation was carried out to identify
the likely implications of using load-based speed control on the
environmental performance of the variable speed system. It is
found that the control brought about no appreciable difference in
the annual water consumption, but only caused a slight increase
of 2.8% in the annual electricity consumption of the chillers and
tower fans. The load-based speed control for cooling tower fans, indeed, eliminates the need of using high quality temperature or relative humidity sensor to measure the wet-bulb temperature. This,
in turn, helps minimize the noisy control signal resulting from the
measurement errors, and at the same time, to provide more stable
fan speed control because the wet-bulb temperature tends to vary
often compared to the chiller load.
It is essential to equip variable speed chiller plants with proper
instruments to perform real-time measurement and verication of
5.0
100
80
60
40
20
R = 0.9509
0
0.0
0.2
0.4
0.6
0.8
1.0
4.5
4.0
3.5
3.0
0.0
0.2
0.4
0.6
0.8
1.0
1728
the building cooling load and the chiller load in order to implement
load-based speed control for the pumps and tower fans. The monitoring of these loads is crucial for ascertaining whether the chillers
are staged according to their optimal region and for allocating the
system load evenly to the operating chillers. Under the variable
ow conditions, neither the ow rate nor temperature difference
of chilled water can serve to indicate the actual chiller load. The
load which each operating chiller carries should be computed
directly from the measured ow rate and temperatures of the
chilled water. Based on the chiller load calculated, the speeds of
the pumps and tower fans associated with the chillers operating
can be readily determined for optimized operation.
4.4. Remarks on usingequal marginal performance principle (EMPP) to
achieve system optimization
The results of this study indicate that the energy performance of
a chiller system can be improved considerably by using all-variable
speed congurations. To achieve such improvement, it is important
to minimize the aggregate power of all the system components for
all operating conditions. The load-based speed control has been
introduced as one of the means to achieve minimum power consumption of all-variable speed chiller plants. Hartman, on the other
hand, has demonstrated the EMPP as a theoretical approach to
understanding the power relationships between the components
for optimizing all-variable speed chiller plants [8,9]. One criterion
for applying EMPP is to express the system output (cooling capacity, Q) as a function of components power inputs in the form:
Q = f(Component 1 power, Component 2 power . . . Component n
power). When the mathematical expression of this formula is identied, the optimum system COP can be determined by equating all
marginal COPs of the power components, where marginal COP for
component x is given by o Q/oComponent x power.
Creating a cooling output expression for a multiple-chiller system is a complicated and even difcult process, which is not the
scope of this study. Yet some remarks are presented below on
using the EMPP to implement system optimization. There are a total of 12 power components with regard to a variable speed system
with three pairs of chillers, chilled water pumps, condenser water
pumps and cooling tower fans. Due to the sequencing of chillers,
each component power varies in discrete steps at certain loading
points over the entire range of building cooling loads. This discrete
power variation can cause difculty in evaluating the marginal
COPs for each power component. To counter this, it may be necessary to create a set of system output expressions, each of which
caters for a certain building cooling load range handled by a given
number of operating chillers. The time and effort to create the system output expressions and to determine the marginal COPs would
be highly intensied if the chiller system is on a large scale with
many sequencing (or staging) patterns of the power components.
While there is a generic form for expressing the system output,
the coefcients and mathematical formula for representing each
power component are specic, given that each chiller system
should have its own design and power requirements. At present
no analytic tool has been developed for using EMPP to determine
the mathematical expression of cooling outputs for any given system design with respect to the number and size of chillers. Under
this circumstance, the power relationships in mathematical form
may be identied by using curve tting techniques in cases where
an ample set of power-related operating data is collected for a system with various cooling outputs. This suggests that the EMPP is
viable for use after the system is working in the post-operation
stage. It is more desirable, however, to apply the EMPP in the system design stage to facilitate optimum equipment selection and
power-based control development. It remains to be seen how the
evaluation of system design alternatives with the use of EMPP be-
5. Conclusions
This study examines how all-variable speed chiller systems
with load-based speed control yield economic benets and superior environmental performance with reduced electricity and
water consumption relative to the conventional constant speed
systems. Given the superior performance of variable speed devices
at part load operation, the basic principles of designing an all-variable speed chiller plant are using fewer and equally sized chillers
and considering a single-loop chilled water circuit with variable
ow. The variable speed chillers should be staged based on their
optimal region with maximum COP. With regard to an all-variable
speed chiller system operating for the cooling load prole of an
ofce building, the annual electricity consumption could decrease
the annual total electricity use by 19.7% and annual water use by
15.9% relative to the corresponding constant speed plant. Loadbased speed control is introduced as a simple and direct means
1729
[6] M. Hydeman, G. Zhou, Optimizing chilled water plant control, ASHRAE J. 49 (6)
(2007) 4454.
[7] J.M. Gordon, K.C. Ng, H.T. Chua, C.K. Lim, How varying condenser coolant ow
rate affects chiller performance: thermodynamic modeling and experimental
conrmation, Appl. Therm. Eng. 20 (2000) 11491159.
[8] T. Hartman, All-variable speed centrifugal chiller plants, ASHRAE J. 43 (9)
(2001) 4352.
[9] T. Hartman, Designing efcient systems with the equal marginal performance
principle, ASHRAE J. 47 (7) (2005) 6470.
[10] Air-conditioning and Refrigeration Institute (ARI), Standard 550/590:
performance rating of water-chilling packages using vapour compression
cycle, Arlington, VA, 2003.
[11] F.W. Yu, K.T. Chan, Life cycle analysis of enhanced condenser features for aircooled chillers serving air-conditioned buildings, Bldg. Environ. 41 (2006)
981991.
[12] Solar Energy Laboratory, TRNSYS 15: a transient system simulation program
(Reference manual), Madison, WI, University of WisconsinMadison Press,
2000.
[13] F.W. Yu, K.T. Chan, Optimization of water-cooled chiller system with loadbased speed control, Appl. Energy 85 (10) (2008) 931950.
[14] Braun JE. Methodologies for the design and control of chilled water systems,
PhD thesis, University of Wisconsin/Madison, Madison, WI, 1988.
[15] Electrical and Mechanical Services Department (EMSD), Pilot scheme for wider
use of fresh water in evaporative cooling towers for energy-efcient air
conditioning systems, Author Press, Hong Kong, 2000.
[16] ASHRAE, ASHRAE standard 90.1: energy standard for building except low-rise
residential buildings, American Society of Heating, Refrigerating and AirConditioning Engineers, Atlanta, GA, 2004.
[17] W.L. Lee, F.W.H. Yik, Framework for formulating a performance-based
incentive-rebate scale for demand-side-energy management scheme for
commercial buildings in Hong Kong, Appl. Energy 73 (2002) 139166.
[18] J.E. Braun, A generic control algorithm for cooling towers in cooling plants with
electric and/or gas-driven chillers, Int. J. HVAC&R Res. 13 (4) (2007) 581598.