Checked?
Y
Building Shell/Envelope
Y
Y
Y
Y
Y
Y
Y
Thermal Zones
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Other
Check BEPS and SS-R reports
for unmet load hours
Check peak loads reports to
make sure they make sense
Check SV-A reports to make
sure they make sense
Compare results to rules of
thumb
Comments
A couple of spaces labeled "core" are EXT space types,
spaces below atriums?
NA for baseline
NA
Values look reasonable but should follow method
outlined in G3.1.2.9.
None present per 90.1 for CZ 4A
Okay accept for big turn down for heating with no
morning warm up modeled.
Reset schedule has 10 dT but 90.1 Appendix G
G3.1.3.12 states a 5 dT.
input value is consistent with 90.1 specified value of
0.4 CFM/ft2.
Night cycle control is off
None modeled. Should include to avoid overcooling
and reheating during cool conditions.
NA
NA
Second boiler is on for a~ 400 hours during the year.
Second chiller is on for 45 hours per year. The sizing /
staging of the plant equipment should be improved.
Overall efficiencies are not bad though.
1.25
Not all loads met ~ 12% of the time most likely due to
the plenum zones being considered to be conditioned
or if these really are conditions, their supply design
flow needs to be increased. Sometimes not having a
central heating coil can cause this too.
20
Window Calcs
Window
Description
New - All
ASHRAE
New - All
ASHRAE
* Excludes outside air-film coefficient
Data
Center of Glass
Overall Window + Fram
U-value
U-value
Btu/hr ft SHGC
Tvis Btu/hr ft
0.72
0.4
0.72
0.5
Data
Overall Window + Frame
SHGC
0.4
0.4
Weather
Metrics
Heating (kBTU/SF)
Cooling (kWh/SF)
Total All Energy (kBtu/SF)
Model
*DOE
see units
MJ/m2 MJ/m2
27.6
313.5
70.1
3.8
137.0
110.9
102.4 1162.4
586.3
13.9
157.4
139.1
23.0
261.0
181.0
* Published values for Large Office in DC based on reference building models developed
Rule of Thumb
Heating capacity (Mbtu/hr)
Heating capacity (Btu/ SF)
Cooling capacity (tons)
Cooling capacity (SF/ton)
Chilled water flow (GPM)
Chilled water flow (GPM/ton)
Condenser water flow (GPM)
Condenser water flow (GPM/t
Air flow Collections (CFM)
Air flow Collections (CFM/ft2)
Air flow Public (CFM)
Air flow Public (CFM/ft2)
Air flow Non Public (CFM)
Air flow Non Public (CFM/ft2)
Air flow total (CFM)
Air flow total (CFM/ft2)
9.9
30.0
1,836.7
179.1
3,599.0
20.1
5,100.0
2.8
### 298602
0.6
### 196117
1.0
55,832.0 196117
0.3
###
1.3
15-20
400
2.5
2.5
3
<1
<1
<1
<1