Sunteți pe pagina 1din 16

BC80 Catalogue

Type Description/Technical Data Stock Code Picture Page

c 2005 Beijing Siemens Cerberus Electronics LTD. - Data subject to change without notice

1
BC80 Catalogue
Type Description/Technical Data Stock Code Picture

c 2005 Beijing Siemens Cerberus Electronics LTD. - Data subject to change without notice
TableBC80
of Contents
Catalogue
Type Description/Technical Data Stock Code Picture Page

1. BC8001 Series Fire Alarm Control Unit.....................................2

BC8001 Compact Control Unit with 1 line (127 Dev) ..................................2

BC8001P Compact Control Unit with 1 line, printer ..........................2


BC8001E Compact Control Unit with 2 line (254 Dev).......................3

BC8001PE Compact Control Unit with 2 line, printer.........................3

2. BDS Series Field Device.............................................................4


BDS051 Optical Smoke Detector.......................................................4

BDS031 Heat Detector (Rate of Rise and Fixed)...............................4

BDS000 Addressable Detector Base.........................................................4


OP520 Collective Optical Smoke Detector.........................................5

HI520 Collective Heat Detector (Rate of Rise and Fixed)..................5

SO520 Collective Detector Base........................................................5


BDS121 Manual Call Point.................................................................6

BDS132 Input Module........................................................................6

BDS221 Output Module......................................................................7


BDS331 Fire Alarm Display Panel......................................................7

BDS161 Collective Input Module........................................................8

BDS152 Isolation Module...................................................................9


3. BC80 Panels and Function Cards.............................................10

BC8013H Wall Mounted Extinguishing Panel...................................10

BCE8001 Extension Card.................................................................11


BC8001 Compact CPU Board...........................................................11

BC8001 Compact Main Board..........................................................11

TP8000 Printer................................................................................12

c 2005 Beijing Siemens Cerberus Electronics LTD. - Data subject to change without notice

1
BC80 Catalogue
Type Description/Technical Data Stock Code Picture

BC8001 Series Fire Alarm Control Unit

BC8001/e BC8001 Compact Control Unit with 1 line(127 Dev) A6C50000016

BC8001 is a control unit very suitable for small size projects


and constructions. It has the following features:

BDS series field devices compatible.


2 Wires and polarity free F-BUS, transmission distance is
up to 1000m.
Specialized BDS algorithm enhance immunity to
environment disturbances.
Menu driven person-machine interface, very easy to operate.
With optional extension card can be networked up to 31
other BC80 control units(BC8001/BC8002/BC8004).
With optional extension card, possible to connect up to 3
B-Bus equipment like interlocking and extinguishing panels.
Optional printer can be mounted in to the control unit.
System can be easily configured on the panel or via PC.
Configuration data can be uploaded to PC at any time.

Number of Detector Lines 1


Number of Field Devices 127
System Network -
Built-in Printer -
LCD Display 240 x 128, Backlit
Auto Mapping Yes
Event History 1000
Digital I/O's
- Nr. Of Dry contacts(24V/3A) 1
- Nr. Of OC outputs 1
- Nr. Of Monitored inputs 2

Operating Voltage 100 ~ 240VAC,


50 ~ 60Hz
Battery-Backup 24V, 6.5Ah
Download/Upload USB
Dimension 370 x 265 x 120mm
Weight(Without Batteries) 3.0kg

BC8001P/e BC8001P Compact Control Unit with 1 line, printer A6C50000018

One printer (TP8000 thermal sensitive printer) is built in with the


features above.

c 2005 Beijing Siemens Cerberus Electronics LTD. - Data subject to change without notice

2
BC80 Catalogue
Type Description/Technical Data Stock Code Picture

BC8001E/e BC8001E Compact Control Unit with 2 line (254 Dev) A6C50000017

An extension card is built-in additionally in the BC8001 which


can

Interconnect via A-Bus up to 31 controllers


(BC8001/BC8002/BC8004 Control Unit).
Interconnect up to 3 B-BUS equipments(BT8011/12
interlocking panel, BC8013 extinguishing panel).

BC8001PE/e BC8001PE Compact Control Unit with 2 line, printer A6C50000019

Same as BC8001, printer and extension card are built in


additionally.

c 2005 Beijing Siemens Cerberus Electronics LTD. - Data subject to change without notice

3
BC80 Catalogue
Type Description/Technical Data Stock Code Picture

BDS Series Field Devices

BDS051 BDS051 Optical Smoke Detector A6C50000002

The BDS051 is smoke detector which can be connected via


F-Bus to BC80 series control unit.

Patented labyrinth optical structure.


New built-in ASIC ensures the high reliability of data
processing.
Homogeneous response to different smoke.
High stability against dust, electromagnetic interference,
temperature fluctuation, humidity and corrosion.
Produced with SMT advanced technology.

Operating Voltage 16 ~ 32V DC


Operating Temperature -10 ~ +50℃
Storage Temperature -25 ~ +75℃
Relative Humidity ≤ 95%(40 ± 2℃)
Quiescent Current ≤ 1.0mA
Alarm Current ≤ 3.0mA
EMC 10V/m

BDS031 BDS031 Heat Detector (Rate of Rise and Fixed) A6C50000001

Newly developed circuit and sensor ensure high perfor-


mance of fixed and rate-of-rise temperature detection.
High stability against dust, electromagnetic interference,
temperature fluctuation, humidity and corrosion.
Produced with SMT advanced technology.

Operating Voltage 16 ~ 32V DC


Operating Temperature -10 ~ +50℃
Storage Temperature -25 ~ +75℃
Relative Humidity ≤ 95%(40 ± 2℃)
Quiescent Current ≤ 1.0mA
Alarm Current ≤ 3.0mA
EMC 10V/m

BDS000 BDS000 Detector Base A6C50000000

The detector base is for mounting the field devices BDS051


and BDS031.
The detector covers the whole base, the wiring capacity is 1.0
to 1.5 mm2 .

c 2005 Beijing Siemens Cerberus Electronics LTD. - Data subject to change without notice

4
BC80 Catalogue
Type Description/Technical Data Stock Code Picture

BDS Series Field Devices


OP520 OP520 Collective Optical Smoke Detector A6C50000010

The OP520 is an colletive detector can be connected in to S11


system and BC80 system via corresponding collective input
modules.

Patented optical structure and labyrinth.


Homogeneous sensitivity to different smokes.
High stability against dust, electromagnetic interference,
temperature fluctuation, humidity and corrosion.
Manufactured by advanced SMT technology.
Polarity detection and wrong connection fault-free.

Operating Voltage 21~ 29V DC


Output Voltage 5 ~ 13V
Quiescent Current ≤ 100 uA
Operating Temperature -10 ~ +50℃
Storage Temperature -30 ~ +75℃
Working Humidity ≤ 95%(40 ± 2℃)
EMC 10V/m
Alarm Indicator Current 1.5mA

HI520 HI520 Collective Heat Detector (Rate- of- Rise and Fixed) A6C50000009

Newly developed circuit and sensor ensure high perfor-


mance of fixed and rate of rise temperature detection.
High stability against dust, electromagnetic interference,
temperature fluctuation, humidity and corrosion.
Produced with SMT advanced technology.

Operating Voltage 21 ~ 29V DC


Output Voltage 5 ~ 13V
Operating Temperature -10 ~ +50℃
Storage Temperature -30 ~ +75℃
Relative Humidity ≤ 95%(40 ± 2℃)
Quiescent Current ≤ 100 uA
Alarm Current ≤ 1.5 mA
EMC 10V/m

SO520 SO520 Collective Detector Base A6C50000011

The detector base is for mounting the field devices HI520 and
OP520.

c 2005 Beijing Siemens Cerberus Electronics LTD. - Data subject to change without notice

5
BC80 Catalogue
Type Description/Technical Data Stock Code Picture

BDS Series Field Devices

BDS121/e BDS121 Manual Call Point A6C50000003

Manual call point can immediate trigger a fire alarm by


breaking the glass.

Direct connected on the BDS F-Bus, P,S polarity free.


Installed in the public area such as staircase, elevator
lobby.
Address can be set via Dip-switch.
A built-in dry contact can be used for activating other
equipment.
Mounted on the wall 1.5 meters above the ground.
Delivered electronic part and housing separately.

Operating Voltage 24VDC


Quiescent Current ≤ 1mA
Alarm Current ≤ 3mA
Working Temperature -20 ~ +55℃
Working Humidity ≤ 95%(40 ± 2℃)
Capacity of the dry contact 24VDC/ 0.1A
EMC 10V/m

BDS132/e BDS132 Input Module A6C50000004

The input module can be a interface to transmit the alarm or


technical signal from other equipment to Fire Alarm Control Unit.

Connect on the BDS F-Bus directly, address can be set


by a built-in Dip-switch.
Be used for interfacing the signals from flow switch,
pressure switch, etc and other parties to the fire alarm
system.
Input signal has to be a potential free digital signal. The
signal will be transmitted to controller and trigger
corresponding activations by preset logic expressions.
Fault will be automatic detected and displayed on the
controller.

Operating Voltage 24VDC


Quiescent Current ≤ 1mA
Activation Current ≤ 3mA
Working Temperature -10 ~ +50℃
Relative Humidity ≤ 95% (40 ± 2℃)
Wiring Capacity 1.0 ~ 1.5mm2

c 2005 Beijing Siemens Cerberus Electronics LTD. - Data subject to change without notice

6
BC80 Catalogue
Type Description/Technical Data Stock Code Picture

BDS Series Field Devices

BDS221/e BDS221 Output Module A6C50000007

The output module is to activate external equipments according


to the preset logic expressions and also expecting to receive a
confirmation of activation.

Connect on the F-Bus directly, address set via Dip-switch.


Can activate external devices by preset logic, the output
can be a pulse or steady signal according to Dip-switch
set up.
On the BDS detection line P , S can be connected with
polarity free.
The input signal is a potential free contact.
Can be used for activating high voltage devices via
connecting ZA2225 and ZA2226 in between.
It is not recommended to use this module for extinguishing
control directly.
Fault will be automatic detected and displayed on the
controller.

Operating Voltage 24VDC


Quiescent Current ≤ 1mA
Activation Current ≤ 3mA
Working Temperature -10 ~ +50℃
Relative Humidity ≤ 95% (40 ± 2℃)
Capacity of the output relay AC125V/0.6A, DC24V/2A
Confirmation LED Steady output Steady ON
Pulse Output Flashing

BDS331/e BDS331 Fire Alarm Display Panel A6C50000008

The panel is used for display alarm event on the floor.

1 BDS331 can display information of the devices on the


same F-BUS. Up to 127 devices can be displayed.
Can display fire alarm and control information.
The numbers of devices can be displayed on the LED
display.
Fault will be automatic detected and displayed on the
controller.
An relay output is built-in.
Additional power supply by 24-28VDC, is necessary.

Operating Voltage 24VDC


Monitoring Current ≤ 6mA
Alarm Current ≤ 60mA
Working Temperature -10 ~ +50℃
Working Humidity ≤ 95% (40 ± 2℃)
Relay Output 125VAC/1A, 24VDC/1.25A

c 2005 Beijing Siemens Cerberus Electronics LTD. - Data subject to change without notice

7
BC80 Catalogue
Type Description/Technical Data Stock Code Picture

BDS Series Field Devices

BDS161/e BDS161 Collective Input Module A6C50000006

This collective input module can connect collective detectors


to the F-Bus.

Directly connected on the F-Bus, address can be set by


Dip-switch, and the other 2 wires connect the collective
detectors.
Can be connected only in BC80 system.
One BDS161 can connect up to 25 collective detectors,
with the end of line element P6KE18CA.
Can transmit alarm, fault, normal danger level signal to
control unit and has also indication on the module.
On the BDS detection line P, S can be connected with
polarity free.
Collective detector's terminal "1,2 and 3,4 "connected to
BDS161 "D+ and D _ "correspondingly.
Alarm Indicator AI340 and AI300 can be connected on "L+, L_ ".
Fault will be automatic detected and displayed on the
controller.

Alarm Voltage 3.7V ~ 16.4VDC


Fault Voltage(Short) 0V ~ 3.7VDC
Fault Voltage(open) 22.1VDC
Normal Voltage 16.4V ~ 22.1VDC
Quiescent Current < 4mA
Alarm Current < 16mA
Operating Voltage -10 ~ +50℃
Working Temperature ≤ 95% (40 ± 2℃)
Alarm Indicator 1.5mA
Wiring Capacity 1.0 ~ 1.5mm2

c 2005 Beijing Siemens Cerberus Electronics LTD. - Data subject to change without notice

8
BC80 Catalogue
Type Description/Technical Data Stock Code Picture

BDS Series Field Devices

BDS152/e BDS152 Isolation Module A6C50000005

The isolation module is used for isolating the short point on


the detection bus so that the devices which are connected to
the controller before the short point will not be influenced. It
will automatically recover to its normal status when the fault is
eliminated.

In case the short happens on the detection bus, the


isolation module activates so that the devices before the
short point can work normally.
Parallel connection on the first place of each branch or
stub.
No need to set address.
When one loop monitors several floors, on each floor
one Isolation module shall be installed.
One isolation module can connect up to 25 field devices.
P0, S0 on BDS152 connect to control unit P,S terminal
with polarity sensitive. The P,S terminal on BDS152 can
connect to the P,S of other field devices with polarity free.
Fault will be automatic detected and displayed on the
controller.

Working Temperature -20 ~ +50℃


Working Humidity ≤ 95% (40 ± 2℃)
Activation Current ≤ 0.5mA
Pass through Voltage ≤ 1V
Wiring Capacity 1.0 ~ 1.5mm2

c 2005 Beijing Siemens Cerberus Electronics LTD. - Data subject to change without notice

9
BC80 Catalogue
Type Description/Technical Data Stock Code Picture

BC80 Panels and Function Cards

BC8013H/e BC8013H Wall Mounted Extinguishing Panel A6C50000022

The extinguishing panel is used for controls of extinguishing


section.

One panel monitors 2 extinguishing section, for each


section 3 outputs and 3 confirmation signals for those
outputs are equipped for activation of extinguishing alert,
extinguishing section separation, gas release.
Can be connected via B-Bus, address set by Dip-switch,
Information of extinguishing section can be displayed on
the control unit.
Parameters can be configured on panel and via PC-Tool.
Can operate the controlled section on site or on the panel.
External control wires are monitored automatically
against the short.
Panel can be set in automatic mode and manual mode.
Auto mapping is possible.
Fault is automatically detected and displayed on the
panel.

Operating Voltage DC24V ~ 28V


Quiescent Current 40.0mA
Operating Current 200 mA
Nominal Output Current 80mA
Maximum Current per output 200mA
Working Temperature -20℃ ~ 40℃

c 2005 Beijing Siemens Cerberus Electronics LTD. - Data subject to change without notice

10
BC80 Catalogue
Type Description/Technical Data Stock Code Picture

BC80 Panels and Function Cards

BCE8001 BCE8001 Extension Card A6C50000024

It is the extension card for the BC8001 compact controller.

A-Bus interface can make the compact controller


networkable to 31 controllers.
B-Bus interface can make the controller connect up to 3
B-Bus equipments.
F-Bus interface can connect one detection bus
additionally which can connect up to 127 devices more.

BCC8010 BC8001 Compact CPU Board 80040600

Function of the CPU board is storing, loading the configuration


data.

BCC8001 BC8001 Compact Main Board 80010100

Function of the main board is to handle the data and event


received from field.

c 2005 Beijing Siemens Cerberus Electronics LTD. - Data subject to change without notice

11
BC80 Catalogue
Type Description/Technical Data Stock Code Picture

BC80 Panels and Function Cards

TP8000 TP8000 Printer A6C50000028

A thermal sensitive printer can print out the event on the


logger paper when event occurs.

c 2005 Beijing Siemens Cerberus Electronics LTD. - Data subject to change without notice

12
BC80 Catalogue
Type Description/Technical Data Stock Code Picture

c 2005 Beijing Siemens Cerberus Electronics LTD. - Data subject to change without notice
BC80 Catalogue
Type Description/Technical Data Stock Code Picture

c 2005 Beijing Siemens Cerberus Electronics LTD. - Data subject to change without notice

S-ar putea să vă placă și