DEFINITIONS
This is the safety alert symbol. It is used to alert you to potential personal
injury hazards. Obey all safety messages that follow this symbol to avoid
possible injury or death.
DANGERIndicates a hazardous situation which, if not avoided, will result in death
or serious injury.
WARNINGIndicates a hazardous situation which, if not avoided, could result in
death or serious injury.
CAUTIONIndicates a hazardous situation which, if not avoided, could result in
minor or moderate injury.
NOTICEIndicates a hazard that could result in property damage only (including
damage to the control).
IMPORTANTDesignates an operating tip or maintenance suggestion.
The engine, turbine, or other type of prime mover should be equipped with an
overspeed shutdown device to protect against runaway or damage to the prime
mover with possible personal injury, loss of life, or property damage.
The overspeed shutdown device must be totally independent of the prime mover
control system. An overtemperature or overpressure shutdown device may also
be needed for safety, as appropriate.
Read this entire manual and all other publications pertaining to the work to be performed before
installing, operating, or servicing this equipment. Practice all plant and safety instructions and
precautions. Failure to follow instructions can cause personal injury and/or property damage.
This publication may have been revised or updated since this copy was produced. To verify that
you have the latest revision, be sure to check the Woodward website:
www.woodward.com/pubs/current.pdf
The revision level is shown on the front cover after the publication number. The latest version of
most publications is available at:
www.woodward.com/publications
If your publication is not there, please contact your customer service representative to get the
latest copy.
Any unauthorized modifications to or use of this equipment outside its specified mechanical,
electrical, or other operating limits may cause personal injury and/or property damage, including
damage to the equipment. Any such unauthorized modifications: (i) constitute "misuse" and/or
"negligence" within the meaning of the product warranty thereby excluding warranty coverage
for any resulting damage, and (ii) invalidate product certifications or listings.
To prevent damage to a control system that uses an alternator or battery-charging
device, make sure the charging device is turned off before disconnecting the battery
from the system.
To prevent damage to electronic components caused by improper handling, read
and observe the precautions in Woodward manual 82715, Guide for Handling and
Protection of Electronic Controls, Printed Circuit Boards, and Modules.
Woodward Governor Company reserves the right to update any portion of this publication at any time. Information
provided by Woodward Governor Company is believed to be correct and reliable. However, no responsibility is
assumed by Woodward Governor Company unless otherwise expressly undertaken.
Woodward 2005
All Rights Reserved
Manual 91371
Contents
ELECTROSTATIC DISCHARGE AWARENESS ................................................ III
CHAPTER 1. GENERAL INFORMATION......................................................... 1
Introduction .......................................................................................................... 1
Application ........................................................................................................... 1
CHAPTER 2. 723PLUS DSC ..................................................................... 3
723PLUS Digital Control Declaration of Incorporation ........................................ 3
723PLUS Digital Speed Control Accessories ...................................................... 3
723PLUS Control Specifications ......................................................................... 3
CHAPTER 3. 723PLUS INSTALLATION ....................................................... 7
Scope ................................................................................................................... 7
Unpacking ............................................................................................................ 7
Power Requirements ........................................................................................... 7
Location Considerations ...................................................................................... 7
Electrical Connections ......................................................................................... 8
Internal Jumpers ................................................................................................ 14
Installation Checkout Procedure ........................................................................ 18
CHAPTER 4. SYSTEM DESCRIPTION ......................................................... 19
Engine Speed .................................................................................................... 19
Speed Control and Synchronizing ..................................................................... 20
Droop Control .................................................................................................... 21
Isochronous Load Sharing ................................................................................. 22
Load Sharing via LON ....................................................................................... 23
MW Control ........................................................................................................ 25
High/Low Frequency Protection ........................................................................ 26
Operating Modes ............................................................................................... 27
Limiters and Load Rejection .............................................................................. 27
PID Control and Actuator Output ....................................................................... 28
Run/Stop and Alarms......................................................................................... 29
Modbus Communications and Control .............................................................. 30
Analog Outputs .................................................................................................. 31
Control Options .................................................................................................. 31
Operator Interface.............................................................................................. 31
CHAPTER 5. TUNABLES ........................................................................... 32
General .............................................................................................................. 32
Configure Mode ................................................................................................. 32
Service Mode ..................................................................................................... 41
Configure Values List......................................................................................... 74
Service Values List ............................................................................................ 76
Modbus Communications Address List ............................................................. 83
CHAPTER 6. MODBUS COMMUNICATIONS ................................................. 85
CHAPTER 7. SET POINT PROGRAMMING................................................... 89
Introduction ........................................................................................................ 89
Hand-Held Programmer..................................................................................... 89
PC Interface ....................................................................................................... 92
Watch Window ................................................................................................... 93
Woodward
Manual 91371
Contents
CHAPTER 8. SERVICE OPTIONS ............................................................... 96
Product Service Options..................................................................................... 96
Woodward Factory Servicing Options ................................................................ 97
Returning Equipment for Repair ......................................................................... 97
Replacement Parts ............................................................................................. 98
Engineering Services ......................................................................................... 98
How to Contact Woodward................................................................................. 99
Technical Assistance .......................................................................................... 99
MANUAL REVISION HISTORY .................................................................. 101
ii
Woodward
Manual 91371
2.
Avoid the build-up of static electricity on your body by not wearing clothing
made of synthetic materials. Wear cotton or cotton-blend materials as
much as possible because these do not store static electric charges as
much as synthetics.
3.
4.
Do not remove the printed circuit board (PCB) from the control cabinet
unless absolutely necessary. If you must remove the PCB from the control
cabinet, follow these precautions:
When replacing a PCB, keep the new PCB in the plastic antistatic
protective bag it comes in until you are ready to install it. Immediately
after removing the old PCB from the control cabinet, place it in the
antistatic protective bag.
To prevent damage to electronic components caused by improper
handling, read and observe the precautions in Woodward manual
82715, Guide for Handling and Protection of Electronic Controls,
Printed Circuit Boards, and Modules.
Woodward
iii
iv
Manual 91371
Woodward
Manual 91371
Chapter 1.
General Information
Introduction
This manual describes the 723PLUS Generator Control, part numbers
8280-5000/5010 (High and Low Voltage Control, actuator output 0200 mA)
and 8280-5020/5030 (High and Low Voltage Control, actuator output 420 mA).
Application
The control is intended for use in a variety of generator applications; for
auxiliary generators and diesel electric propulsion in marine systems, and for
island mode operation and for base loading against an infinite bus in power
plant systems. From the revision B software, the LON * load sharing option is
added. This option provides load sharing by mean of LON bus, with a maximum
of 16 units, that can be split in maximum 3 different busses. The LON load
sharing provides diagnostics in case of failure of load sharing.
*LON is a trademark of Echelon Corporation.
The MW Control mode is especially useful for applications where the grid is
weak and large frequency excursions are expected. Under these
circumstances, operating in droop mode is not practical, as large variations in
load would be experienced, due to frequency shifts of the grid. In MW control,
the speed of the engine is maintained by the grid, and the load on the generator
remains constant throughout the frequency excursion.
The control provides closed loop speed control, with a torsional filter and a
notch (band-stop) filter to help to eliminate problems caused by low frequency
oscillations due to engine and generator inertias and flexible couplings.
Three modes of operation are available:
Start and maximum fuel limiters are provided, as well as a charge air pressure
limiter based on the 420 mA Charge Air Pressure input. A load limiter, enabled
during MW control, will provide load de-rating during frequency excursions.
Additional protection is offered to open the Grid Breaker or the Generator
Breaker, should the frequency excursion become too large.
The control can be adjusted/biased for synchronizing the generator to a bus by
means of the Increase/Decrease contacts, or by the input provided for a
Woodward Unit Synchronizer (SPM-A or DSLC - Digital Synchronizer and
Load Control).
The control can also be adjusted/biased for synchronizing across a bus tie
breaker, or to synchronies the bus to the grid, using a Woodward System
Synchronizer, common to the controls on the bus.
Woodward
Manual 91371
One serial port (J2) is configured for communications with the Woodward
Servlink Server, using RS-232 or RS-422. Then, using the Woodward Watch
Window, engine parameters can be monitored, and Service/Configure tunable
values adjusted.
One serial port (J3) is available for Modbus communications using RS-232,
RS-422 or RS-485. Engine parameters can be monitored, and certain control
functions sent to the control via the Modbus.
420 mA outputs are available for monitoring various control parameters.
Woodward
Manual 91371
Chapter 2.
723PLUS DSC
723PLUS Digital Control Declaration of Incorporation
In accordance with the EMC directive 89/336/EEC and its amendments, this
controlling device, manufactured by the Woodward Governor Company, is
applied solely as a component to be incorporated into an engine prime mover
system. Woodward Governor declares that this controlling device complies with
the requirements of EN50081-2 and EN50082-2 when put into service per the
installation and operating instructions outlined in the product manual.
This controlling device is intended to be put into service only upon
incorporation into an engine prime mover system that itself has met
the requirements of the above Directive and bears the CE mark.
Manual 91371
Woodward
Manuall 91371
723PLUS
7
Ge
enerator Co
ontrol for W
rtsil
Woodw
ward
723P
PLUS Genera
ator Control for Wrtsill
Manual 91371
W
Woodward
Manual 91371
Chapter 3.
723PLUS Installation
Scope
This chapter contains installation instructions for the 723PLUS control. Power
requirements, environmental precautions, and location considerations are
included to help you determine the best location for the control. Additional
information includes unpacking instructions, electrical connections, and
installation checkout procedures.
Unpacking
Before handling the control, read page iii, Electrostatic Discharge Awareness.
Be careful when unpacking the electronic control. Check the control for signs of
damage such as bent panels, scratches, and loose or broken parts. If any
damage is found, immediately notify the shipper.
Power Requirements
The high-voltage version of the 723PLUS Digital Speed Control requires a
voltage source of 90 to 150 Vdc. The low-voltage version requires a voltage
source of 18 to 40 Vdc. Maximum power consumption is 40 W for both high and
low voltage models.
To prevent damage to the control do not exceed the input voltage
range.
Location Considerations
Consider these requirements when selecting the mounting location:
Avoidance of vibration
Manual 91371
Electrical Connections
Shielded Wiring
All shielded cable must be twisted conductor pairs. Do not attempt to tin the
braided shield. All signal lines should be shielded to prevent picking up stray
signals from adjacent equipment. Connect the shields to the nearest chassis
ground. Wire exposed beyond the shield should be as short as possible, not
exceeding 50 mm (2 inches). The other end of the shields must be left open and
insulated from any other conductor. DO NOT run shielded signal wires along
with other wires carrying large currents. See Woodward application note 50532,
EMI Control in Electronic Governing Systems, for more information.
Where shielded cable is required, cut the cable to the desired length and
prepare the cable as instructed below.
1. Strip outer insulation from BOTH ENDS, exposing the braided or spiral
wrapped shield. DO NOT CUT THE SHIELD.
2. Using a sharp, pointed tool, carefully spread the strands of the shield.
3. Pull inner conductor(s) out of the shield. If the shield is the braided type,
twist it to prevent fraying.
4. Remove 6 mm (1/4 inch) of insulation from the inner conductors.
Installations with severe electromagnetic interference (EMI) may require
additional shielding precautions. Contact Woodward Governor Company for
more information.
Woodward
Manual 91371
Woodward
Manual 91371
Use shielded twisted-pair wires to connect to terminals 15(+) and 16(), 17(+)
and 18(), and 19(+) and 20(). For an electrically isolated input device such as
a 4 to 20 mA input analog meter, the shield should be grounded at the control
end of the cable. For input to other devices, use the recommendation of the
device manufacturer. The analog outputs will drive 420 mA at 600 ohms
maximum.
To prevent possible damage to the control or poor control
performance resulting from ground loop problems, we recommend
using current loop isolators if the 723PLUS controls analog inputs
and outputs are used with non-isolated devices (common ground
system). A number of manufacturers offer 20 mA loop isolators.
Consult Woodward Governor Company for further information.
10
Woodward
Manuall 91371
723PLUS
7
Ge
enerator Co
ontrol for W
rtsil
To prev
vent possible damage to
o the contro
ol or poor co
ontrol
perform
mance resultting from grround loop p
problems, we
w recomme
end
using current-loop isolators if the 723PLU
US control's analog inpu
uts
and outtputs are us
sed with non
n-isolated de
evices (com
mmon ground
system)). A numberr of manufac
cturers offerr 20 mA loop isolators.
Consultt Woodward
d Governor Company
C
fo
or further infformation.
Serial communications ports
S
J1Hand
dheld Progra
ammer
J2Servvlink Server, RS-232 and RS-422
J3Modb
bus, RS-232
2, RS-422, RS-485
T
Terminatio
on
For RS-422, termination
F
t
s
should
be loc
cated at the receiver
r
whe
en one or mo
ore
trransmitters are
a connected to a single receiver. When a single transmitter is
i
connected to one or more
e receivers, te
ermination should be at tthe receiver
fa
arthest from the transmittter. Figure 3--1 is an exam
mple.
Figure
e 3-1. RS-422
2 Terminatorr Locations
For RS-485, termination
F
t
s
should
be at each end of the cable. If termination can't
be located at the end of a cable, put itt as close as possible to tthe ends. Fig
gure
mple.
3-2 is an exam
Figure
e 3-2. RS-485
5 Terminatorr Locations
Woodw
ward
11
723P
PLUS Genera
ator Control for Wrtsill
Manual 91371
Comm
municating with
w a HMI (H
Human Mach
hine Interface
e) operator in
nterface is a
speciial case of Fiigure 3-1. Be
ecause the HMI
H master cannot
c
put itss transmitter
into a high-impedance state, and
a the bit ra
ate is less tha
an 90K bits/ssec,
termination is not needed at th
he slave. Termination is needed at th
he HMI
receivver, but beca
ause there iss no way to lo
ocate it there
e, it has to be
e put at the
altern
nate location.
If you
u don't know if a master can
c put its tra
ansmitter into
o a high-impedance state
e,
terminate the line
e as shown in
n Figure 3-1. It does not hurt
h to termin
nate the line
even when it's no
ot needed as in the case of
o the HMI operator interrface.
Term
mination is accomplished using a three
e-resistor volltage divider between a
positiive voltage and
a ground. The
T impedan
nce of the res
sistor networrk should be
equal to the chara
acteristic imp
pedance of th
he cable. This is usually about 100 to
o
120 ohms.
o
The pu
urpose is to maintain a voltage level between the two
differential lines so
s that the re
eceiver will be
e in a stable condition. The differentia
al
voltag
ge can range
e between 0..2 and 6 voltss; the maxim
mum voltage between the
e
receivver input and
d circuit grou
und must be less than 10 volts. There
e is one
termination resisttor network fo
or each J2 and J3 port lo
ocated on the
e 723PLUS.
Conn
nection to thiss resistor nettwork is mad
de through th
he 9-pin conn
nectors on
pins 6 and 9.
See Figures
F
3-3 through
t
3-6 for
f terminatio
on and cable connection examples.
12
2
Figurre 3-6. 723PLUS RS-422
Con
nnections with Optional
Terrmination at Transmitter
T
W
Woodward
Manuall 91371
723PLUS
7
Ge
enerator Co
ontrol for W
rtsil
G
Grounding
g and Shie
elding
The RS-422 and
T
a RS-485 specification
ns state that a ground wirre is needed if
th
here is no oth
her ground path
p
between
n units. The preferred
p
me
ethod to do th
his is
to
o include a separate wire
e in the cable
e that conneccts the circuitt grounds
to
ogether. Con
nnect the shie
eld to earth ground
g
at one point only. The alternate
w is to conn
way
nect all circuit grounds to
o the shield, and
a then con
nnect the shield to
earth ground at one point only. If the la
atter method
d is used, and
d there are nonn
issolated node
es on the partty line, conne
ect the shield
d to ground a
at a non-isola
ated
node, not an isolated node
e. Figures 3--7 and 3-8 illustrate these
e cabling
approaches.
Non-iso
olated nodes
s may not have a signa
al ground av
vailable. If signal
ground is not available, use th
he alternate wiring sche
eme in Figurre 3-8
with the
e signal ground connec
ction remove
ed on those
e nodes only
y.
F
Figure
3-7. Preferred
P
Mu
ultipoint Wirin
ng using Shie
elded Twisted-Pair Cable
e with
S
Separate
Sig
gnal Ground Wire
Figure 3-8
8. Alternate Multipoint
M
Wiring using Sh
hielded Twissted-Pair Cab
ble
witho
out a Separatte Signal Gro
ound Wire
The signal ground connection is not required if signa
al ground is
unavaila
able.
Woodw
ward
13
Manual 91371
Internal Jumpers
The 723PLUS control has ten, two-position internal jumpers (JPR1 through
JPR20) located on the top of the printed circuit board. If it is necessary to
change any jumper to match the control requirements, and suit the nature of the
software, read page iii, Electrostatic Discharge Awareness.
Ensure that the power to the control is switched off, before removing the cover.
Using a small pair of tweezers, carefully remove the appropriate jumper and
replace it securely over the proper two connectors (see Figure 3-9). The jumper
connections are listed:
JPR10
*JPR9
JPR12
*JPR11
JPR13 and JPR2
*JPR13 and JPR1
JPR14 and JPR2
**JPR15 and JPR3
***JPR15 and JPR4
JPR16 and JPR3
JPR5 and JPR17
*JPR6 and JPR18
JPR7 and JPR20
*JPR8 and JPR19
Analog output #1
Analog output #1
Analog output #2
Analog output #2
Analog output #3
Analog output #3
Analog output #3
Actuator output
Actuator output
Actuator output
Speed sensor #1
Speed sensor #1
Speed sensor #2
Speed sensor #2
0-1 mA
0-20 mA
0-1 mA
0-20 mA
0-200 mA, single
0-20 mA, single
0-160 mA, tandem
0-200 mA, single
0-20 mA, single
0-160 mA, tandem
Proximity switch
Magnetic pickup
Proximity switch
Magnetic pickup
14
Woodward
Manuall 91371
723PLUS
7
Ge
enerator Co
ontrol for W
rtsil
Woodw
ward
15
Manual 91371
16
Woodward
Manual 91371
Woodward
17
Manual 91371
Visual Inspection
A.
Check the linkage between the actuator and fuel metering device for
looseness or binding. Refer to the appropriate actuator manual, and
Manual 25070, Electronic Governor Installation Guide, for additional
information on linkage.
To prevent possible serious injury from an overspeeding engine, the
actuator lever or stroke should be near but not at the minimum
position when the fuel valve or fuel rack is at the minimum fuel
delivery position.
B.
Check for correct wiring in accordance with the plant wiring diagram.
C.
D.
Check the speed sensor(s) for visible damage. If the sensor is a magnetic
pickup, check the clearance between the gear and the sensor, and adjust
if necessary. Clearance should be between 0.25 and 1.25 mm (0.010 and
0.050 inch) at the closest point. Make sure the gear runout does not
exceed the pickup gap. Refer to manual 82510 Magnetic Pickups And
Proximity Switches For Electric Governors, for information.
18
Woodward
Manual 91371
Chapter 4.
System Description
Engine Speed
Speed Sensing
The control has two speed sensing inputs, and may be configured for torsional
filtering, for smoother operation with soft couplings, or high signal select, giving
speed sensing redundancy should one signal fail. If the torsional filter has been
selected, the speed sensors should be positioned on either side of the coupling;
sensor #1 on the engine side, and sensor #2 on the generator side. If the high
signal select is utilized, then both speed sensing devices should be located on
the same speed sensing disc.
Each speed sensor input has a failed speed detection device, with an override
function which is active during engine start-up. The Failed Spd Sensor #1 and
Failed Spd Sensor #2 LEDs located on the 723PLUS control, give indication
when either input has failed. If a speed sensor fails, it will be switched out until
the fault is rectified, and then reset during the next engine start .
When the torsional filter is selected, failure of either speed sensor will result in
the activation of the Minor Alarm, and control will continue with one speed
signal. If the Generator CB Aux contact input is closed, the Propgain Multiplier
will be switched in to decrease the Prop Gain value. If high signal select is
chosen, failure of a speed sensor will also give continued control with one
speed signal, and the Minor Alarm will be activated.
The option is available to disable the Minor Alarm if one speed sensor fails, for
situations where only one speed sensor is utilized. The Failed Spd Sensor LED
on the front panel of the 723PLUS will still illuminate if no speed signal is
sensed, but the Minor Alarm will not activate.
Failure of both speed sensors will initiate a shutdown, whereby the control will
drive the actuator output to zero if forward acting, or maximum if reverse acting,
and the Major Alarm will be activated.
If the engine has been shut down by the 723PLUS control due to both
speed sensors failing, do NOT attempt to start the engine until the
faults have been located and rectified. Failure of the pickups can
only be detected whilst the engine is running, i.e. the signal must
already exist for the failure detection to operate. If the 723PLUS
cannot detect engine speed during start-up, the actuator output will
go to maximum, possibly driving the engine into an overspeed
condition. The engine should be equipped with an additional
overspeed shutdown device that operates totally independently of
this control, to protect against runaway or damage to the engine,
with possible personal injury or loss of life.
Electronic overspeed detection and shutdown is integral to the control. The
control will drive the actuator output to zero fuel, if the Overspeed Trip is
exceeded.
The engine should be equipped with an additional overspeed
shutdown device, that operates totally independently of this control,
to protect against runaway or damage to the engine, with possible
personal injury or loss of life, should this control fail.
Woodward
19
723P
PLUS Genera
ator Control for Wrtsill
Manual 91371
Spee
ed Filterin
ng
The following
f
diag
gram shows the arrangem
ment of the speed
s
filters and torsiona
al
filter / HSS (High Signal Selecct):
Sp
peed Control and
d Synchrronizing
Engine Start
When
n the Run/Stop contact iss closed (or opened
o
if the
e Open DI#1 To Run
config
gurable is se
elected true), the speed reference is at
a Idle Speed
d. The
refere
ence will then remain at idle,
i
until the
e engine spee
ed exceeds the
t Idle/Rate
ed
Switcch speed, at which
w
time th
he speed refference will ramp
r
to Rate
ed Speed at
the Accel/Decel
A
R
Rate.
This ramp to rated may
m be interrrupted by mo
omentarily
closin
ng Decrease
e contact (so freezing the ramp).
If the Idle/Rated select
s
contactt is required, the Enable I//R Select parrameter
shoulld be set true
e. When the Run/Stop
R
con
ntact is put in
n the run possition, the
speed
d reference will
w be initiallyy at Idle Spee
ed. Once the engine has started, the
contro
ol will remain
n at idle, if the
e contact is in
n the idle pos
sition, or will ramp to Rate
ed
Spee
ed, at the Acccel/Decel Ratte, if/when the
e contact is closed.
c
If the engine is
starte
ed with the Id
dle/Rated sele
ect contact on,
o the speed reference will
w stay at idle
e
speed
d and will nott ramp to Ratted Speed. Closing
C
the Id
dle/Rated con
ntact after the
e
RUN command, will
w start the ramp
r
to Rated
d Speed at th
he Accel/Deccel Rate. The
e
idle-to
o-rated ramp
p may be inte
errupted by eiither opening
g the Rated/Id
dle contact
(and so returning the reference
e back to Idle
e Speed at th
he Accel/Deccel Rate), or b
by
mome
entarily closing the Decre
ease contact (so freezing the ramp).
20
W
Woodward
Manual 91371
The rated-to-idle ramp may be interrupted similarly by either closing the Rated/Idle
contact (and so returning the reference back to Rated Speed, at the Accel/Decel
Rate), or by momentarily closing the Increase contact (so freezing the ramp).
The Idle/Rated contact input is only functional, whilst the Generator CB Aux
contact input is open.
Synchronizing to a Bus
When the engine reaches Rated Speed, and has remained within the Ready to
Synch Limits for the Sync OK Delay Time, the Ready to Synchronies status
communicated via the Modbus will become TRUE.
The Unit Synchronizer Input will bias the speed reference, based on the value
of the bipolar voltage input. Once the Generator CB Aux contact is closed, the
bias is either:
Last value locked in until the Generator CB Aux input is opened, if droop
mode is enabled.
Alternatively, the unit can be synchronized to the bus using the
Increase/Decrease contacts, which will cause the speed reference to change at
the Inc/Dec Rate #1. The Maximum Speed determines the limit to which the
reference may be increased, and the Minimum Speed is the limit to which the
reference may be decreased.
Opening the Generator CB Aux contact input will set the speed reference
instantly to Rated Speed.
Droop Control
To operate in Droop mode, the Isochronous/Droop contact input must be open,
and the Generator CB Aux contact closed.
The speed droop value is calculated based on the Droop percentage, and the
load on the engine. The engine load will be derived from the MW Transducer
input. Should this signal fail, the load will be determined based on the position
of the actuator output. Failure of the load signal input will activate the Minor
Alarm, which will be reset once the signal is healthy. The speed droop will
always be zero, whilst the CB Aux is open.
Woodward
21
Manual 91371
A Droop Pulse function is provided to help prevent an engine being driven into
reverse power, when connected to a bus in droop mode. When the Generator CB
Aux contact is closed, the speed reference is immediately increased by the Ref
Bias Pulse. This will cause the generator to immediately take on load from the
other sets. This is a permanent bias, whilst the control remains in droop mode.
This function can be disabled by tuning the Ref Bias Pulse parameter to zero.
Closure of the Increase contact will cause the speed reference to increase at
the Inc/Dec Rate #2, therefore causing the engine to take on load (if available).
Closure of the Decrease contact will cause the speed reference to decrease at
the Inc/Dec Rate #2, therefore causing the engine to shed load (if possible).
Woodward
Manual 91371
If it is necessary that a machine is required on-line more quickly than usual (i.e.
during an emergency situation), the contact should be closed, and once the
Generator CB Aux contact is closed, the control will load the engine at the
Emergency Load Rate, rather than the Auto Load Rate.
If the Unload function is used whilst the Emergency Load Rate contact is
closed, the engine will be unloaded at the Emergency Unload Rate.
The Emergency Load/Unload Rates may be disabled at any time, by opening
the contact.
If the MW Transducer input signal should fail whilst in isochronous load sharing,
the control will switch back into droop control, with load based on the actuator
output. Once the fault is rectified, and the signal fault reset (either automatically
or by using the Modbus Reset), the control will load/unload back into
isochronous load sharing.
Whilst the control is operating in isochronous load sharing, the droop reference
is continuously tracking, so that if the control is switched into droop mode, the
transfer will be bumpless.
Switching into MW Control mode will also be bumpless.
Woodward
23
Manual 91371
Bus Interconnection
Closing the bus tie breaker causes all the units to share equal load. When, upon
closing of the tie breaker, a load difference exists between the buses that is larger
than the preset value, the two buses are soft-loaded towards each other.
The load difference is set in service menu *MW LOAD LON* under BUS LOAD
DIFF (%), the load rate is set in BUS CONNECT RATE (%/sec). It should be
noted that these values have to be the same on all engine controls.
The Tie breaker feedback must be given to all units as given below:
Load Sharing
The load sharing is set in service menu *LOAD SHARING (LON)*, with a
negative deadband % and a positive deadband % setting a deadband wherein
there is no biasing out, outside this deadband the negative window % and
positive window % which set the window for the load difference where the bias
in positive window and bias in negative window will give a biasing to the speed
controller. The max negative bias and max positive bias set the maximum bias
in rpm to the speed controller.
Woodward
Manual 91371
When the LON failure comes from an engine which was off-line (Circuit Breaker
is open) then the other engines on that bus section will keep running in
isochronous load sharing mode.
If now a reset to the LON alarm is given and the LON alarm is still active then
the bus will switch to droop mode.
A reset can be given by forcing the engine in droop mode (Discrete input F) and
then switch back to Isochronous mode. NOTE: You will have to do this for each
engine on that bus section!
The LON alarm logic also gets a reset when the CB contact (Circuit breaker
feedback) is switched.
The engine will switch to droop mode when the kW-sensor fails.
MW Control
To operate in MW Control, the Generator CB Aux, Parallel With Grid (if used)
and MW Control contact inputs must be closed, and the MW load input must not
be disabled.
Switching into MW Control from Isochronous Load Sharing or Droop mode will
be bumpless. Once in MW Control, the MW reference can be adjusted by use of
the Increase/Decrease contact inputs. Closing the Increase contact raises the
MW reference towards the Maximum Load at the Raise Load Rate. Closing the
Decrease contact lowers the MW reference towards the Minimum Load at the
Lower Load Rate.
If the Select Int MW Ref parameter has been selected true in Configure, and the
control switches into MW Control mode when the generator breaker closes, the
MW reference will automatically ramp to the Internal MW Ref at the Int MW Ref
Rate. If the control is in digital MW setting mode (use of increase/decrease
contacts to set MW reference), it will then remain at this level until the
Increase/Decrease contact inputs are used to adjust the load. If the control is in
analog MW setting mode, then the parameter Enbl Int Ref Analog must be
selected true to utilize the internal MW reference function. In this case, once the
internal MW reference is reached, the reference will be ramped to the analog
reference level.
The ramp to Internal MW Ref is not utilized when switching into MW
Control when the breaker is closed.
If both the Increase and Decrease contacts are closed (or Remote Reference
selected via the Modbus), the MW reference will ramp to the level determined
by the 420 mA Remote Reference input, at the Auto Load Rate. Once this
level has been reached, the reference will continue to follow the input, at the
Raise/Lower Load Rates. If the remote reference input should fail (i.e. <2 mA,
>22 mA), the MW reference will lock in the last healthy value. The control will
then respond to the Increase/Decrease contacts, once the remote MW
reference is de-selected.
If both the Increase and Decrease contacts are closed to select the remote
reference, opening only one of the contacts will NOT de-select the remote
reference. Both contacts must be opened to de-select the remote reference.
This is to prevent the reference being driven high or low in the event of a single
wire break.
Woodward
25
Manual 91371
Closing the Unload contact (momentarily) will cause the control to decrease the
MW reference until the Unload Trip Level is reached, at which time the control will
issue a Generator Breaker Open Command. This output will remain active until
the Generator CB Aux contact is opened, indicating that the breaker has opened.
The unloading sequence can be interrupted by momentarily closing the Increase
contact input. The load will then remain at the level it was interrupted at, if in local
mode, or will ramp back to the remote reference level, if in remote mode.
Failure of the 420 mA MW Transducer input (i.e. <1 mA, >22 mA) will switch
the control into droop mode, with load calculated based on the actuator output.
Once the fault is rectified, and the signal fault reset (either automatically or by
using the Modbus Reset), the control will load/unload back into MW Control.
During normal operation, transferring to droop or isochronous modes will be
bumpless.
When going from MW-Control to Isoch mode, by opening the Parallel With Grid
contact, the load sharing lines relay K4 is closed immediately, to ensure that all
units will switch instantly to isochronous load sharing. In this case, the transfer
may not be completely bumpless, depending on the imported/exported load and
distribution of load between engines, before the grid breaker was opened.
Depending on which method of MW Control is preferred, either Direct MW
Control or MW Deadband Control may be chosen.
Direct MW Control:
The PID compares the measured MW to the MW reference, and adjusts the
actuator output accordingly.
MW Deadband Control (Compensated MW Control):
The control is effectively in Droop mode. A deadband controller compares the
measured MW with the MW reference, and then will increase/decrease the
speed reference ramp, and hence increase/decrease the load on the engine.
Opening the Parallel With Grid contact input, when the control is selected to
Droop mode, resets the speed reference instantly to Rated Speed.
26
Woodward
Manual 91371
If En MW Ovrd Autorst is configured true, then the control will automatically reselect MW control mode, once the grid frequency is back within the trip limits,
and the MW Ovrd Autorst Dly has expired.
The Freq HH Trip & Freq LL Trip parameters, set the high and low frequency
window, outside of which the control will give the command to open the
generator breaker, after a time delay LL/HH Trip Delay.
Operating Modes
Whether the control is in Droop, Isochronous or MW Control mode, is
dependent on the status of certain contact inputs, and whether or not certain
analog inputs are healthy. The table below indicates which mode of operation
the control will select, based on the status of the relevant digital and analog
inputs.
MODE
I/O
Gen CB (DI)
Grid CB (DI)
Isoch/Droop (DI)
MW Control (DI)
MW Load (AI)
MW Reference
(AI)
Isoch
Droop
Droop
Droop
Droop
1
0
1
IRR
H
IRR
1
0
0
IRR
IRR
IRR
1
1
IRR
0
IRR
IRR
1
0
1
IRR
F
IRR
1
1
IRR
1
F
IRR
DI
1 = CLOSED
0 = OPEN
IRR = STATUS IRRELEVANT
MW Control
Analog/Remote
1
1
IRR
1
H
H
MW Control
Digital/Inc-Dec
1
1
IRR
1
H
IRR
AI
F = FAILED
H = HEALTHY
IRR = STATUS IRRELEVANT
27
Manual 91371
28
Woodward
Manual 91371
Window #1
0.1
GAIN RATIO
MW PROP GAIN
Gain Ratio = 1
Generator
Breaker
Old Gain
Slope Logic
SPEED ERROR
Window #2
Generator
Breaker
GAIN RATIO
Gain Ratio = *2(0,10)
*
Multiply
Prop Gain #1
/
Prop Gain #2
Load
MW CONTROL
Gain Ratio = 1
GEN
CB
PID
SPEED ERROR
MW INT GAIN
INT GAIN #1
INT GAIN
#2
MW S.D.R.
S.D.R. #1
S.D.R. #2
Direct MW Control
A single set of dynamics (Proportional Gain, Integral Gain and S.D.R.) for
operation in MW Control mode.
Actuator Hit
An Actuator Hit function is provided for testing the dynamics of the control
during commissioning of the system. This function can be enabled in Configure
mode, and once the control has reset itself, the function is only available for a
30 minute period. When the appropriate parameter is toggled true using the
Operator Interface (HHT or PC-based), a tunable value is subtracted from the
actuator output, for a tunable period of time. This will enable the operator to
check that the dynamic settings are suitable. This is a better alternative to
physically disturbing the fuel rack to check the response of an engine, as it will
provide a consistent means of test.
29
Manual 91371
Major Alarm
The Major Alarm will be activated:
if the Charge Air Pressure/Reactive Power input fails - below 2 mA, above
22 mA
30
Woodward
Manual 91371
Analog Outputs
Through the 723PLUS 420 mA analog outputs, it is possible to monitor any
three of the following:
Actuator Position (0100%)
Engine Speed (rpm4 mA and 20 mA set points configurable)
Engine Load (0-100%)
MW Reference (MW4 mA and 20 mA set points configurable)
Speed Input #1 (rpm4 mA and 20 mA set points configurable)
Speed Input #2 (rpm4 mA and 20 mA set points configurable)
The analog outputs are configured under the *ANALOG O/P CONFIG* menu in
Service.
Control Options
The following options are available with the 723PLUS Generator Control:
Digital O/P #2 configurable for Minor Alarm (default) or Grid Breaker Open
Command - Configured using Operator Interface.
Ability to enable the Unload contact input for Idle/Rated selection whilst
breaker is open - Configured using Operator Interface.
The Run/Stop contact input may be configured such that the contact is
opened to Run, and closed to Stop, instead of the default, close to Run,
open to Stop.
Operator Interface
The parameters within the control may be configured and monitored using
either a Hand Held Programmer, or using the Servlink Server and Graphical
User Interface (more details of this can be found in Chapter 7, Set Point
Programming).
The serial port J2 is configured for use with Servlink server, and port J1 is
configured for use with the handheld programmer. Port J1 can also be changed
to Servlink mode, which is necessary when software has to be downloaded.
Woodward
31
Manual 91371
Chapter 5.
Tunables
General
This chapter describes the parameters that can be tuned or monitored. The
Configure Mode section below describes the values that can be adjusted in
Configure Mode. The Service Mode section describes the values that can be
configured in Service Mode.
See the Configure Values List and Service Values List sections later in this
chapter for the Configure and Service values lists.
Where applicable, the nominal setting for each tunable is listed (the nominal
values are provided only as a guideline). The actual settings are obtained from
the engine manufacturer or determined during commissioning and should be
noted in the Actual column for future reference.
Failure to save set points prior to removing power from the control
will cause them to revert to the previously saved settings.
Configure Mode
Refer to Chapter 7, Set Point Programming. On the Hand-held Programmer,
press the . key. The display will show 'To Enable CONFIGURE Press
*ENTER*'. Press the ENTER key and the display will show 'To Shutdown I/O,
Press *ENTER*'. Press the ENTER key to enter the Configure menus.
The configure mode consists of the following menus:
1. PASSCODE
2. SPEED SENSORS
3. ENGINE SPEED
4. MW CONTROL
5. FINAL DRIVER
6. ENGINE LOAD
7. MODBUS PORT SETUP
8. CONFIGURE
9. CONF MODBUS I/PS
10. CONTROL OPTIONS
11. SET LON ALARMS
12. LON COM
PASSCODE
Description
ENABLE CONFIGURE
ENABLE SERVICE
Range
0 to 32767
0 to 32767
Nominal
723
723
Actual
ENABLE CONFIGURE
This parameter must be set to the correct passcode value, in order to enable
the Configure menus. If the value is incorrect, then no configure values are
displayed, and therefore cannot be altered.
To obtain the passcode value, please contact Wrtsil.
32
Woodward
Manual 91371
ENABLE SERVICE
This parameter must be set to the correct passcode value, in order to enable
the Service menus. If the value is incorrect, then only following menus are
displayed:
SERVICE MODE, Display Menu
SERVICE MODE, Minor Alarm Menu (in case of Minor Alarm)
SERVICE MODE, Major Alarm Menu (in case of Major Alarm)
The values in these menus are only monitoring values and cannot be altered.
To obtain the passcode value, please contact Wrtsil.
SPEED SENSORS
Description
PULSE/REV #1
MAXIMUM HZ #1
PULSE/REV #1 DIG
PULSE/REV #2
MAXIMUM HZ #2
PULSE/REV #2 DIG
SPD ANA=F / DIG=T?
LOW SET POINT #1 (RPM)
OVERRIDE SPEED #1 (RPM)
MINIMUM SPEED #1 (RPM)
LOW SET POINT #2 (RPM)
OVERRIDE SPEED #2 (RPM)
MINIMUM SPEED #2 (RPM)
Range
30 to 360
500 to 10000
30 to 360
30 to 360
500 to 10000
30 to 360
False to True
0 to 1500
0 to 1500
0 to 1500
0 to 1500
0 to 1500
0 to 1500
Nominal
155
2519
155
155
2519
155
TRUE
95
135
400
95
135
400
Actual
PULSE/REV #1
This is the number of teeth (or holes) on the speed sensing disc, for the speed
sensors connected to the 723PLUS. Speed Sensor #1 should be located on the
engine side of the coupling. This value is needed for the analog speed sensing
in the software and must be set the same as the PULSES/REV #1 DIG value.
MAXIMUM HZ #1
This parameter allows tuning of the speed sensing algorithm, to obtain the
optimum resolution for sensing speed. It is important that the following
instructions for tuning these parameters is adhered to. The Maximum Hz should
be calculated based on both the minimum and maximum controlling speeds:
(Maximum Speed x Pulse/Rev x 1.3)/60 = A
(Minimum Speed x Pulse/Rev x 4)/60 = B
If B > A then use A as the Maximum Hz. If B < A then use B as the Maximum
Hz, provided that B is greater than 1.1 x Overspeed Trip Frequency. If not, then
contact Woodward Governor for further assistance.
Calculate separately for each speed sensor input, if Pulses/Rev #1 and
Pulses/Rev #2 are different.
PULSES/REV #1 DIG
This is the number of teeth (or holes) on the speed sensing disc, for the speed
sensor connected to the 723PLUS, Speed Sensor Input #1 . Speed sensor #1
should be located on the engine side of the coupling. This value is needed for
the digital speed sensing in the software and must be set the same as the
PULSES/REV #1 value.
PULSE/REV #2
This is the number of teeth (or holes) on the speed sensing disc, for the speed
sensors connected to the 723PLUS. Speed Sensor #2 should be located on the
generator/gearbox side of the coupling, if the torsional filter is used, otherwise, it
should be located on the same speed sensing disc as sensor #1. This value is
needed for the analog speed sensing in the software and must be set the same
as the PULSES/REV #2 DIG value.
Woodward
33
Manual 91371
MAXIMUM HZ #2
This parameter allows tuning of the speed sensing algorithm, to obtain the
optimum resolution for sensing speed. It is important that the following
instructions for tuning these parameters is adhered to. The Maximum Hz should
be calculated based on both the minimum and maximum controlling speeds:
(Maximum Speed x Pulse/Rev x 1.3)/60 = A
(Minimum Speed x Pulse/Rev x 4)/60 = B
If B > A then use A as the Maximum Hz. If B < A then use B as the Maximum
Hz, provided that B is greater then 1.1 x Overspeed Trip Frequency. If not, then
contact Woodward Governor for further assistance.
Calculate separately for each speed sensor input, if Pulses/Rev #1 and
Pulses/Rev #2 are different.
PULSES/REV #2 DIG
This is the number of teeth (or holes) on the speed sensing disc, for the speed
sensor connected to the 723PLUS, Speed Sensor Input #2. Speed sensor #2
should be located on the generator/gearbox side of the coupling, if the torsional
filter is used, otherwise, it should be located on the same speed sensing disc as
sensor #1. This value is needed for the digital speed sensing in the software
and must be set the same as the PULSES/REV #2 value.
SPD ANA=F / DIG=T
This parameter allows the selection between analog and digital speed sensing.
TRUE means the digital speed sensing blocks in the software are processed to
the software logic. FALSE means the analog speed sensing blocks are
processed to the software logic.
Default the digital speed sensing is active (TRUE).
Changing between the different speed blocks can have influence on
the dynamic settings.
LOW SET POINT #1
This is the speed at and below which the failed speed function operates, for
speed sensor #1. This parameter should always be set lower than the Override
Speed set point.
OVERRIDE SPEED #1
This is the speed below which the failed speed detection is overridden during
the engine start and stop sequence, for speed sensor #1. This parameter
should always be set higher than the Low Set Point parameter.
This set point must be tuned with caution. If the value is set too high,
it is possible that a failed speed signal would be overridden during
normal engine operation, giving a potentially dangerous situation.
Principle of speed failure detection:
During engine start, the actual speed first exceeds the LOW SET POINT, but
the speed fault override is still on. If the speed increases, the OVERRIDE
SPEED set point will be passed and the override speed fault will be switched
off, so no speed sensor failure will occur.
During engine stop, the OVERRIDE SPEED set point will be passed first and
with a delay of 0.3 seconds, the override speed fault will be activated. If the
speed drops faster than this 0.3 seconds below the LOW SET POINT, a speed
failure will be recognized and the speed failure alarm will be activated. In case
of a real speed sensor failure, the speed drops almost instantly to zero rpm, so
the speed failure will be activated directly. During a normal stop, the engine
speed will slowly come down due to the inertia of the engine. In this way the 0.3
seconds are long enough for not activating the speed failure because the
override will be on in case the actual speed pass the LOW SET POINT.
34
Woodward
Manual 91371
In most of the cases the default settings are correct. In case of problems with
speed sensor failures during stopping of the engine, the values need to be
tuned. Be aware that the set point must not be to close to each other because
of the 0.3 seconds that is needed for activating the speed fault override logic.
MINIMUM SPEED #1
This is the speed of speed sensor #1 below which the torsional filter is disabled,
and should be tuned to a setting, equivalent to 400 rpm.
LOW SET POINT #2
This is the speed at and below which the failed speed function operates, for
speed sensor #2. This parameter should always be set lower than the Override
Speed set point.
OVERRIDE SPEED #2
This is the speed below which the failed speed detection is overridden during
the engine start and stop sequence, for speed sensor #2. This parameter
should always be set higher than the Low Set point parameter.
This set point must be tuned with caution. If the value is set too high,
it is possible that a failed speed signal would be overridden during
normal engine operation, giving a potentially dangerous situation.
MINIMUM SPEED #2
This is the speed of speed sensor #2 below which the torsional filter is disabled,
and should be tuned to a setting, equivalent to 400 rpm.
ENGINE SPEED
Description
IDLE SPEED (RPM)
RATED SPEED (RPM)
OVERSPEED TRIP (RPM)
TORSIONAL FILTER?
Range
0.0 to 2000.0
0.0 to 2000.0
0.0 to 2500.0
False to True
Nominal
550.0
750.0
863.0
FALSE
Actual
MW CONTROL
Description
REMOTE REF @ 4 mA (MW)
REMOTE REF @ 20 mA (MW)
SELECT INT MW REF
ENBL INT REF ANALOG
Range
-10.0 to 60.0
0.0 to 60.0
False to True
False to True
Nominal
0.0
8.0
FALSE
FALSE
Actual
35
Manual 91371
FINAL DRIVER
Description
REVERSE ACTING?
ACT O/P @ 0 mA (%)
ACT O/P @ 20/200 mA (%)
ENABLE ACTUATOR HIT
CHARGE AIR @ 20 mA (bar)
STROKE ACTUATOR
Range
False to True
-25.0 to 200.0
-25.0 to 200.0
False to True
0.0 to 10.0
False to True
Nominal
FALSE
0.0
100.0
FALSE
6.0
FALSE
Actual
REVERSE ACTING?
If selected true, will reverse the actuator output signal to 200-0 mA/20-4 mA for
0-100%.
ACT O/P @ 0 mA (%)
Sets the % actuator output at 0 mA. See Table 5-1.
ACT O/P @ 20/200 mA (%)
Sets the % actuator output at 20 or 200 mA. See Table 5-1.
Table 5-1. Actuator Output
Actuator range Act O/P @ mA
0-200 ma
420 mA
20160 mA
10-180 mA
20-200 mA
0
-25
-14
-6
-11
Act O/P @
20/100 mA
100
100
129
112
100
36
Woodward
Manual 91371
ENGINE LOAD
Description
RATED LOAD (MW)
MW SENSOR @ 4 mA (MW)
MW SENSOR @ 20 mA (MW)
MVAR @ 4 mA
MVAR @ 20 mA
Range
0.0 to 60.0
-60.0 to 60.0
0.0 to 60.0
-60.0 to 60.0
-60.0 to 60.0
Nominal
6.52
0.0
8.0
-10.0
10.0
Actual
Range
1 to 2
1 to 247
Nominal
2
1
Actual
MODE (ASCII/RTU)
Sets the communications protocol of the J3 port. 1=ASCII, 2=RTU.
SLAVE ADDRESS
Sets the network address of the control. This will always be set to 1 for Point-toPoint communications.
CONFIGURE
Description
ENABLE CALIBRATION
Range
False to True
Nominal
FALSE
Actual
ENABLE CALIBRATION
If selected true, the *CALIBRATION* menu will be displayed under Service.
The parameters within this menu should only be adjusted by or under the
guidance of, Woodward Governor personnel.
Range
False to True
False to True
False to True
False to True
False to True
False to True
False to True
False to True
Nominal
FALSE
FALSE
FALSE
FALSE
FALSE
FALSE
FALSE
FALSE
Actual
START/STOP
If selected true, the control input for starting/stopping the engine is received via
the Modbus. If false, then the input is hardwired.
Woodward
37
Manual 91371
INC/DEC/SEL REMOTE
If selected true, the control inputs for Increase/Decrease Speed/Load, and
select remote MW reference, are received via the Modbus. If false, then the
inputs are hardwired.
UNLOAD & IDLE/RATED
If selected true, the control input for unloading, and idle/rated selection, is
received via the Modbus. If false, then the input is hardwired.
DROOP/ISOCHRONOUS
If selected true, the control input for droop/isochronous mode selection is
received via the Modbus. If false, then the input is hardwired.
SELECT MW CONTROL
If selected true, the control input for selecting MW Control is received via the
Modbus. If false, then the input is hardwired.
EMERGENCY LOAD RATE
If selected true, the control input for selecting the Emergency Loading Rate is
received via the Modbus. If false, then the input is hardwired.
RESET
If selected true, the reset command can be sent via Modbus. All faults which are
normally self-resetting will instead remain latched until a reset is received
(provided that the fault has been cleared). If false, then speed sensor faults are
reset when the Run/Stop contact input is closed, and all other faults are selfresetting, i.e. reset automatically when the fault is cleared.
REMOTE MW REFERENCE
If selected true, the remote MW reference input is received via the Modbus. If
false, then the input is hardwired.
CONTROL OPTIONS
Description
GRID CB OPEN CMD?
ENABLE MW OVERRIDE?
EN MW OVRD AUTORST?
MW DEADBAND CONTROL
ENABLE I/R SELECT
AI#4 - CHARGE AIR?
OPEN DI#1 TO RUN?
ENABLE AI#1
ENABLE AI#2
ENABLE AI#4
DO#1 NC?
DO#2 NC?
DO#3 NC?
kW Control I/O Ch (0=NA)
Tie#1 I/O Ch (0=NA)
Tie#2 I/O Ch (0=NA)
Par Grid I/O Ch (0=NA)
Emerg Loading I/O Ch (0=NA)
Use Fuel #2 I/O Ch (0=NA)
Range
False to True
False to True
False to True
False to True
False to True
False to True
False to True
False to True
False to True
False to True
False to True
False to True
False to True
0 to 9
0 to 9
0 to 9
0 to 9
0 to 9
0 to 9
Nominal
TRUE
FALSE
FALSE
FALSE
FALSE
FALSE
FALSE
TRUE
TRUE
FALSE
TRUE
FALSE
FALSE
7
0
0
8
0
0
Actual
Woodward
Manual 91371
EN MW OVRD AUTORST?
If selected true, if the MW Override function is used, this will allow automatic reselection of MW Control mode, once the grid frequency is back within the predefined limits, and a certain period of time has expired.
MW DEADBAND CONTROL
If selected true, MW control will be as compensated droop via the speed
reference (see description in system description text).
ENABLE I/R SELECT
If selected true, allows the Unload contact input to be utilized as an Idle/Rated
contact whilst the CB Aux input is open. In case the CB Aux contact is closed,
the unload function still can be activated by a pulse command. If the CB Aux is
open again and idle speed is wanted, the Idle/Rated contact must be toggled
again from 1 to 0.
AI#4 - CHARGE AIR?
If selected true, analog input #4 will be configured for measuring Charge Air
Pressure. If selected false, the input will be configured for the MVAR
transducer.
OPEN DI#1 TO RUN?
If true, digital input #1 is configured Open to Run, Close to Stop.
ENABLE AI#1
If false, (input disabled), the minor alarm for this input is overridden, and the
control will use the actuator position to determine engine load.
ENABLE AI#2
If false (input disabled), the minor alarm for this input is overridden.
ENABLE AI#4
If false, (input disabled), the minor alarm for this input is overridden, and the
charge air pressure limiter is disabled.
DO#1 NC?
If true, digital output #1 will be normally closed, i.e. contact will open when a
major alarm occurs.
DO#2 NC?
If true, digital output #2 will be normally closed, i.e. contact will open when a
minor alarm occurs/grid breaker open command is issued.
DO#3 NC?
If true, digital output #3 will be normally closed, i.e. contact will open when a
generator breaker open command is issued.
USE LSL (F) OR LON (T) ?
If false, the load sharing is done by means of load sharing lines.
If true, the load sharing is done by means of LON bus.
When LON is selected, also the LON specific service mode menus will be
activated.
KW CONTROL I/O CH (0=NA)
Maps & multiplexes the kW Control function to a 723PLUS input channel.
Set to 7 to use this function at discrete input #7.
Set to 0 when not used, so the discrete input is available for a different function.
Check all multiplexed discrete inputs to be used only once!
Woodward
39
Manual 91371
Range
False to True
Nominal
TRUE
Actual
Woodward
Manual 91371
LON COM
Description
LON Address
Is LON 2 Used ?
Is LON 3 Used ?
Is LON 4 Used ?
Is LON 5 Used ?
Is LON 6 Used ?
Is LON 7 Used ?
Is LON 8 Used ?
Is LON 9 Used ?
Is LON 10 Used ?
Is LON 11 Used ?
Is LON 12 Used ?
Is LON 13 Used ?
Is LON 14 Used ?
Is LON 15 Used ?
Is LON 16 Used ?
Range
1 to 16
False to True
False to True
False to True
False to True
False to True
False to True
False to True
False to True
False to True
False to True
False to True
False to True
False to True
False to True
False to True
Nominal
1
TRUE
TRUE
TRUE
TRUE
TRUE
TRUE
TRUE
TRUE
TRUE
TRUE
TRUE
TRUE
TRUE
TRUE
TRUE
Actual
LON Address
With help of this field, you set the LON address number for the particular unit.
The first bus bar, A or 1, LON Address 1 - 5.
The second bus bar, B or 2, LON Address 6 - 10.
The third bus bar C or 3, LON Address 11 16.
Is LON 2 Used ? Is LON 16 Used
This parameter must be tuned to true to let this particular unit know which other
units are to be expected. This must be done correctly, otherwise the alarming
and switching to droop will be incorrect!
FALSE This LON address is not used
TRUE This LON address is used and expects to communicate with this unit.
Service Mode
Refer to Chapter 7, Set Point Programming. On the Hand-held Programmer,
press the key. To move between menus, and to move through set-points
within menus, follow the instructions given for the Configure menus.
The service mode consist of several used to adjust and/or monitor various
parameters. The following service menus are available in service mode:
1. DISPLAY MENU
2. DYNAMICS #1
3. DYNAMICS #2
4. MW DYNAMICS
5. VARIABLE GAIN
6. ENGINE SPEED
7. SPEED REFERENCE
8. START/STOP
9. SYNCHRONIZING
10. LOAD SHARING (kW)
11. MW REFERENCE (kW)
12. ENGINE LOAD
13. FREQUENCY LIMITER
14. START FUEL LIMIT
15. CHARGE AIR LIMIT
16. MW LIMIT
17. FINAL DRIVER
18. GEN CB LOAD REJ
19. GRID CB LOAD REF
20. CALIBRATION
21. MODBUS PORT SETUP
Woodward
41
Manual 91371
SERVLINK J2 SETUP
ANALOG O/P CONFIG
MAJOR ALARM
MINOR ALARM
KICKDOWN
LOAD SHARING (LON)
LON COM FAILURE
MONITOR LON
MW LOAD LON
J1 PORT SETUP
DISPLAY MENU
Description
ENGINE SPEED (RPM)
SPEED REFERENCE (RPM)
MW LOAD (MW)
ACTUATOR POSITION (%)
FUEL LIMIT (%)
PID OUTPUT (%)
ENGINE STOPPED
ENGINE RUNNING
READY TO SYNC
UNIT SYNC BIAS (RPM)
SYS SYNC BIAS (RPM)
DROOP BIAS (RPM)
REF BEFORE BIAS (RPM)
GEN CB CLOSED
ISOCHRONOUS MODE
% LOAD
LS LINES %
LOAD SHARE ERROR
MW CONTROL MODE
MW OVERRIDE ACTIVE
LOAD REFERENCE (MW)
REMOTE REF SELECTED
REMOTE REFERENCE (MW)
MW LIMIT
REACTIVE POWER (MVAR)
CHARGE AIR PRESSURE (bar)
AI#1 mA
AI#2 mA
AI#4 mA
Range
Nominal
(Monitor)
(Monitor)
(Monitor)
(Monitor)
(Monitor)
(Monitor)
(Monitor)
(Monitor)
(Monitor)
(Monitor)
(Monitor)
(Monitor)
(Monitor)
(Monitor)
(Monitor)
(Monitor)
(Monitor)
(Monitor)
(Monitor)
(Monitor)
(Monitor)
(Monitor)
(Monitor)
(Monitor)
(Monitor)
(Monitor)
(Monitor)
(Monitor)
(Monitor)
Actual
42
Woodward
Manual 91371
ENGINE STOPPED
Indicates that the engine speed is below the override speed set point
ENGINE RUNNING
Indicates that the engine speed is above the Engine Running speed switch.
READY TO SYNC
Indicates that the engine has reached Rated Speed and has remained within
the window for the required time.
UNIT SYNC BIAS (RPM)
This is the rpm bias from the unit synchronizer input.
SYS SYNC BIAS (RPM)
This is the rpm bias from the system synchronizer input.
DROOP BIAS (RPM)
This is the rpm bias calculated for droop.
REF BEFORE BIAS (RPM)
This is the rpm speed reference before any biases (synch or droop) are taken
into account.
GEN CB CLOSED
Indicates that the Generator CB Aux input is closed.
ISOCHRONOUS MODE
Displays the status of the load sharing lines relay, which connects the unit load
sharing lines to the system load sharing lines. If true is displayed, the control is
in Isochronous mode.
% LOAD
This is the engine load, expressed as a % of the Rated Load.
LS LINES %
This is the % load represented on the load sharing lines.
LOAD SHARE ERROR
This is the error calculated between the % load on the load sharing lines, and
the % unit load.
MW CONTROL MODE
Indicates that the control is in MW Control mode.
MW OVERRIDE ACTIVE
Indicates that the control is in MW Override mode, i.e. switched into droop
mode, instead of opening the grid breaker, due to the defined frequency limits
being exceeded.
LOAD REFERENCE (MW)
This is the MW reference value.
REMOTE REF SELECTED
Indicates that the remote MW reference has been selected.
REMOTE REFERENCE (MW)
This is the MW reference demanded by the remote reference input.
MW LIMIT
This is the MW limit as determined by the frequency limiter curve.
Woodward
43
Manual 91371
DYNAMICS #1
Description
PROP GAIN #1
INTEGRAL GAIN #1 (1/s)
SDR #1
DYN SELECT DELAY (s)
Range
0.01 to 10.0
0.01 to 5.0
0.01 to 100.0
0.0 to 10.0
Nominal
0.25
0.5
10.0
2.5
Actual
PROP GAIN #1
PID proportional gain adjustment for the dynamics gain, when the Generator CB
Aux input is open. Increasing the P term increases the gain, a value for P that is
too large will cause oscillation, if P is too small the offset from a transient will be
too large.
INTEGRAL GAIN #1 (1/s)
PID integrator rate adjustment for the dynamics, affects recovery rate after a
transient, when the Generator CB Aux input is open. A value for I that is too
small will change the actuator current slowly and speed will take a long time to
return to set speed after a transient, giving overdamped response. If I is too
large the actuator current will move too fast and speed will overshoot and
response will be underdamped.
SDR #1
PID derivative ratio adjustment for the dynamics, when the Generator CB Aux
input is open. Set the amount of derivative (or lead) action the control will have.
Increasing the derivative ratio value above 1 will decrease the derivative
function giving the control a PI type action. A value too large will make the
system less responsive. A value too small will make the system oscillate, and
cannot be compensated for with the proportional gain or the integrator rate.
DYN SELECT DELAY (s)
This is the delay period for switching from Dynamics #2 to Dynamics #1, after
the Generator CB Aux contact input is opened.
DYNAMICS #2
Description
PROP GAIN #2
INTEGRAL GAIN #2 (1/s)
SDR #2
PROPGAIN MULTIPLIER
Range
0.01 to 10.0
0.01 to 5.0
0.01 to 100.0
0.01 to 1.0
Nominal
0.35
0.63
14.55
1.0
Actual
PROP GAIN #2
PID proportional gain adjustment for the dynamics gain, when the Generator CB
Aux input is closed. Increasing the P term increases the gain, a value for P that
is too large will cause oscillation, if P is too small the offset from a transient will
be too large.
44
Woodward
Manual 91371
MW DYNAMICS
Description
PROPORTIONAL GAIN
INTEGRAL GAIN
SDR
USE LOWER PROP BAND
Range
0.01 to 10.0
0.01 to 5.0
0.01 to 100.0
False to True
Nominal
0.01
0.3
20.0
FALSE
Actual
PROPORTIONAL GAIN
PID proportional gain adjustment for the dynamics gain, when in MW Control
mode. Increasing the P term increases the gain, a value for P that is too large
will cause oscillation, if P is too small the offset from a transient will be too large.
INTEGRAL GAIN
PID integrator rate adjustment for the dynamics, affects recovery rate after a
transient, when in MW Control mode. A value for I that is too small will change
the actuator current slowly and speed will take a long time to return to set speed
after a transient, giving overdamped response. If I is too large, the actuator
current will move too fast and speed will overshoot and response will be
underdamped.
SDR
PID derivative ratio adjustment for the dynamics when in MW Control mode. Set
the amount of derivative (or lead) action the control will have. Increasing the
derivative ratio value above 1 will decrease the derivative function giving the
control a PI type action. A value too large will make the system less responsive.
A value too small will make the system oscillate, and cannot be compensated
for with the proportional gain or the integrator rate.
USE LOWER PROP BAND
If selected true, the Proportional Gain value will be multiplied by a factor of 0.1.
Woodward
45
Manual 91371
VARIABLE GAIN
Description
LOW SPEED ERROR WIN#1
HIGH SPEED ERROR WIN#1
SPEED GAIN RATIO #1
LOW SPEED ERROR WIN#2
HIGH SPEED ERROR WIN#2
SPEED GAIN RATIO #2
LOAD LEVEL (GAIN) #1
LOAD GAIN RATIO #1
LOAD LEVEL (GAIN) #2
LOAD GAIN RATIO #2
LOAD LEVEL (INT) #1
LOAD INT GAIN RATIO #1
LOAD LEVEL (INT) #2
LOAD INT GAIN RATIO #2
Range
0.0 to 1000.0
0.0 to 1000.0
0.0 to 10.0
0.0 to 1000.0
0.0 to 1000.0
0.0 to 10.0
0.0 to 110.0
0.01 to 10.0
0.0 to 110.0
0.01 to 10.0
0.0 to 110.0
0.01 to 10.0
0.0 to 110.0
0.01 to 10.0
Nominal
20.0
100.0
1.0
20.0
100.0
1.0
0.0
1.0
100.0
1.0
0.0
1.0
100.0
1.0
Actual
Window #1
GAIN RATIO
Gain Ratio = *2(0,10)
Gain Ratio = 1
Generator
Breaker
Old Gain
Slope Logic
SPEED ERROR
Window #2
Generator
Breaker
GAIN RATIO
Gain Ratio = *2(0,10)
Prop Gain #1
/
Prop Gain #2
*
Multiply
Load
Gain Ratio = 1
SPEED ERROR
Instead of the normal switch for Fast Gain window logic, a linear multiplier is
selected so that the gain multiplier is increased when the speed error is
increasing. In this way a smoother switching is created and no rough switching
between low and high gain values.
LOW SPEED ERROR WIN#1
This value corresponds with the maximum absolute error between actual speed
and speed reference that the normal gain value is still used. The multiplier is
until this range set to 1. In case the error is increasing, the multiplier will be
linearly increased till the SPEED GAIN RATIO #1 until the HIGH SPEED
ERROR WIN #1 is reached. In this way, the normal gain will be slowly
increased for faster response of the engine. This logic is active whilst the
Generator CB Aux input is open. The control uses the absolute value of speed
error. The unfiltered speed is used for this calculation.
46
Woodward
Manual 91371
Woodward
47
Manual 91371
ENGINE SPEED
Description
SPEED FILTER (Hz)
FILTER 1 FREQUENCY (Hz)
FILTER 1 Q FACTOR
FILTER 2 FREQUENCY (Hz)
FILTER 2 Q FACTOR
SENSOR WEIGHT
ENGINE RUNNING (RPM)
TWO SPEED SENSORS?
ENABLE NOTCH FILTER 1
ENABLE NOTCH FILTER 2
Range
0.01 to 16.0
0.01 to 16.0
0.707 to 25.0
0.01 to 16.0
0.707 to 25.0
0.0 to 1.0
0.0 to 2500.0
False to True
False to True
False to True
Nominal
12.0
3.5
0.707
3.5
0.707
0.5
150.0
TRUE
FALSE
FALSE
Actual
48
Woodward
Manual 91371
FILTER 2 Q FACTOR
Adjusts the attenuation of the signal frequency, filtered by the band-stop filter
#2. The minimum value of 0.707 results in zero attenuation, and as the value is
increased, the attenuation is increased, and the range of frequencies affected
broadens.
SENSOR WEIGHT
When using the torsional filter, it is possible to weight one speed sensor input
more heavily than the other. If this value is set between 0.5 and 1, sensor #1
will be weighted more heavily then sensor #2. Between 0 and 0.5, sensor #2 will
be more heavily weighted.
ENGINE RUNNING (RPM)
This is the speed above which the engine is assumed to be running, for
monitoring purposes.
TWO SPEED SENSORS?
If selected false, the minor alarm relay will not be activated, should a speed
sensor input fail. The Failed Spd Sensor LED on the front of the 723PLUS
however, will still illuminate, as the failure is continuously detected. The purpose
of this parameter, is to prevent the minor alarm activating, when only one speed
pickup is used.
ENABLE NOTCH FILTER 1
If selected true will enable the Notch Filter #1.
ENABLE NOTCH FILTER 2
If selected true will enable the Notch Filter #2.
SPEED REFERENCE
Description
MINIMUM SPEED (RPM)
MAXIMUM SPEED (RPM)
ACCEL/DECEL RATE (RPM/s)
IDLE/RATED SWITCH (RPM)
INC/DEC RATE #1 (RPM/s)
INC/DEC RATE #2 (RPM/s)
Range
0.0 to 2000.0
0.0 to 2000.0
0.0 to 2000.0
0.0 to 2500.0
0.0 to 2000.0
0.0 to 2000.0
Nominal
690.0
810.0
25.0
450.0
2.0
1.0
Actual
49
Manual 91371
START/STOP
Description
RUNDOWN TIME (s)
PULSE/CONT ALARM?
ALARM PULSE TIME (s)
MINOR ALM PULSE (s)
Range
0.0 to 300.0
False to True
1.0 to 30.0
0.0 to 30.0
Nominal
10.0
FALSE
1.0
2.0
Actual
SYNCHRONIZING
Description
RDY TO SYNC LIMITS (RPM)
SYNC OK DLY TIME (s)
UNIT SYNCH GAIN
ENABLE UNIT SYNCH
SYNC FILTER
SYS SYNCH GAIN
ENABLE SYS SYNCH
SYS SYNCH DELAY
Range
0.0 to 20.0
0.0 to 30.0
0.0 to 100.0
False to True
0.01 to 16.0
0.0 to 100.0
False to True
0.0 to 30.0
Nominal
4.0
2.0
2.0
TRUE
10.0
2.0
FALSE
1.0
Actual
50
Woodward
Manual 91371
Range
1.0 to 100.0
0.01 to 100.0
0.0 to 30000.0
0.0 to 30000.0
0.0 to 30000.0
0.0 to 30000.0
False to True
False to True
0.0 To 9.0
False to True
0.0 to 9.0
0.0 to 9.0E+20
Nominal
2.0
5.0
30.0
50.0
50.0
100.0
TRUE
TRUE
0.5
TRUE
0.5
1.0
Actual
LS ERROR %
When soft loading/unloading into isochronous load sharing, the control will not
establish isochronous load sharing, until the load share error is within the limits
determined by this parameter.
LOAD GAIN
Sets the sensitivity to the load share error.
AUTO LOAD RATE (kW/s)
This is the rate at which load is increased when soft loading into isochronous
load sharing.
EMERGENCY LOAD RATE(kW/s)
This is the rate at which load is increased when soft loading into isochronous
load sharing, with the Emergency Loading Rate contact closed.
AUTO UNLOAD RATE (kW/s)
This is the rate at which load is decreased when soft unloading into isochronous
load sharing, from droop control. Also when using the Unload feature to shed
load and open the generator breaker.
EMRGNCY UNLOAD RATE (kW/s)
This is the rate at which load is decreased when soft unloading into isochronous
load sharing, from droop control, with the Emergency Loading Rate contact
closed. Also using the Unload feature to shed load, with the Emergency
Loading Rate contact closed.
RE-LOAD TO ISOC?
When operating in Isochronous Load Sharing mode, if the Raise/Lower contacts
are momentarily closed following the Unload command (to abort the unload
sequence), the setting of this value determines the course of action. If it is set
true, the control re-loads back into Isochronous mode. If it is set false, the
control remains at the load level it was aborted at, and remain in Droop mode.
Woodward
51
Manual 91371
MW REFERENCE (kW)
Description
AUTO LOAD RATE (kW/s)
AUTO UNLOAD RATE (kW/s)
RAISE LOAD RATE (kW/s)
LOWER LOAD RATE (kW/s)
ENABLE INSTANT RATE
INSTANT RATE WINDOW (kW)
DEADBAND WINDOW (kW)
D/B CTRL RAMP RATE (kW/s)
INTERNAL MW REF (%)
INT MW REF RATE (kW/s)
D/B MW FILTER (s)
MW REF FILTER (Hz)
Range
0.0 to 30000.0
0.0 to 30000.0
0.0 to 30000.0
0.0 to 30000.0
False to True
0.0 to 30000.0
0.0 to 30000.0
0.0 to 30000.0
0.0 to 110.0
0.0 to 30000.0
0.04 to 15.0
0.0 to 100.0
Nominal
30.0
50.0
30.0
30.0
FALSE
300.0
150.0
15.0
3.0
1000.0
3.5
50.0
Actual
52
Woodward
Manual 91371
ENGINE LOAD
This menu is mainly used when load sharing is selected to be performed by
means of load sharing lines. Some parameters are for general use
Description
DROOP(%)
FULL LOAD ACT %
MW FILTER (Hz)
DRP/ISOCH MW FILTER (Hz)
LOAD FILTER (Hz)
UNLOAD TRIP LEVEL (kW)
MAXIMUM FUEL LIMIT (%)
REF BIAS PULSE (RPM)
Range
0.0 to 15.0
0.0 to 100.0
0.01 to 10.0
0.01 to 10.0
0.01 to 10.0
-1000.0 to
30000.0
0.0 to 100.0
0.0 to 10.0
Nominal
5.0
70.0
1.0
1.0
1.0
200.0
Actual
100.0
1.0
DROOP (%)
This is the % of rated speed by which the speed reference is drooped at zero to
full load.
FULL LOAD ACT %
This is the actuator % output at full load.
MW FILTER (Hz)
This is the load filter value used, when the control is in MW Control mode. This
value should not need to be adjusted, but can be used to filter any undesirable
frequencies picked up by the MW transducer.
Woodward
53
Manual 91371
FREQUENCY LIMITER
Description
BUS FREQUENCY (Hz)
MW LIMITER HZ #1
MW LIMITER HZ #2
MAXIMUM LOAD (1) (MW)
MW LIMITER HZ #3
MAXIMUM LOAD (2) (MW)
MW LIMITER HZ #4
FREQ LL TRIP (Hz)
FREQ L TRIP (Hz)
FREQ H TRIP (Hz)
FREQ HH TRIP (Hz)
LL/HH TRIP DELAY (s)
L/H TRIP DELAY (s)
MW OVRD AUTORST DLY (s)
Range
45.0 to 65.0
0.0 to 60.0
10.0 to 60.0
0.0 to 100.0
0.0 to 100.0
0.0 to 100.0
50.0 to 100.0
40.0 to 60.0
40.0 to 60.0
50.0 to 70.0
50.0 to 70.0
0.0 to 3.0
0.0 to 3.0
0.0 to 1800.0
Nominal
50.0
48.0
49.0
6.52
51.0
6.52
52.0
46.0
47.0
51.0
53.0
0.1
0.1
300.0
Actual
54
Woodward
Manual 91371
Limiter Hz#4 must be greater than #3 which must be greater than #2,
which must be greater than #1. It may be necessary to tune #4 first,
and then #3, then #2, then #1 to achieve the desired settings.
FREQ LL TRIP (Hz)
If the grid frequency falls below this level, when the control is in MW control
mode, the generator breaker open command is issued.
FREQ L TRIP (Hz)
If the grid frequency falls below this level, when the control is in MW control
mode, the grid breaker open command is issued, or the control switched into
droop mode (MW Override).
FREQ H TRIP (Hz)
If the grid frequency exceeds this level, when the control is in MW control mode,
the grid breaker open command is issued, or the control switched into droop
mode (MW Override).
FREQ HH TRIP (Hz)
If the grid frequency exceeds this level, when the control is in MW control mode,
the generator breaker open command is issued.
LL/HH TRIP DELAY (s)
This sets the delay period, before the generator breaker open command is
issued, when the grid frequency exceeds the limits defined by the Freq HH & LL
Trip levels.
Woodward
55
Manual 91371
Range
0.0 to 2000.0
0.0 to 100.0
0.0 to 2000.0
0.0 to 100.0
0.0 to 2000.0
0.0 to 100.0
0.0 to 2000.0
0.0 to 100.0
Nominal
0.0
30.0
120.0
50.0
530.0
50.0
530.0
50.0
Actual
Example:
X1,Y1
X2,Y2
80%
Fuel Limit
Level
X3,Y3
40%
100rpm
X4,Y4
250rpm
Engine Speed
56
Woodward
Manual 91371
Range
0.0 to 2000.0
0.0 to 100.0
0.0 to 2000.0
0.0 to 100.0
0.0 to 2000.0
0.0 to 100.0
0.0 to 2000.0
0.0 to 100.0
Nominal
0.0
30.0
120.0
50.0
530.0
50.0
530.0
50.0
Actual
Start Fuel 2 Limit will be used when the Use Fuel #2 contact is closed.
X4 must be > X3 which must be > X2 which must be >X1.
57
Manual 91371
Range
0.0 to 6.0
0.0 to 100.0
0.0 to 6.0
0.0 to 100.0
0.0 to 6.0
0.0 to 100.0
0.0 to 6.0
0.0 to 100.0
Nominal
0.0
100.0
1.0
100.0
3.0
100.0
4.0
100.0
Actual
Load Limit
Level (%)
Chg Air Press D must be > Chg Air Press C which must be > Chg Air
Press B which must be greater than Chg Air Press A. The curve
extrapolates automatically outside the set points.
58
Woodward
Manual 91371
MW LIMIT
Description
MW LOAD A (MW)
ACTUATOR % A
MW LOAD B (MW)
ACTUATOR % B
MW LOAD C (MW)
ACTUATOR % C
MW LOAD D (MW)
ACTUATOR % D
Range
0.0 to 20.0
0.0 to 100.0
0.0 to 20.0
0.0 to 100.0
0.0 to 20.0
0.0 to 100.0
0.0 to 20.0
0.0 to 100.0
Nominal
0.0
100.0
2.0
100.0
4.0
100.0
8.0
100.0
Actual
Load Limit
Level (%)
MW LOAD (MW)
59
Manual 91371
MW LOAD A (MW)
This parameter configures the MW LOAD for point A, of the MW LOAD fuel
limiter curve. (MW)
ACTUATOR % A
This parameter configures the load % for point A, of the MW LOAD fuel limiter
curve.
MW LOAD B (MW)
This parameter configures the MW LOAD for point B, of the MW LOAD fuel
limiter curve. (MW)
ACTUATOR % B
This parameter configures the load % for point B, of the MW LOAD fuel limiter
curve.
MW LOAD C (MW)
This parameter configures the MW LOAD for point C, of the MW LOAD fuel
limiter curve. (MW)
ACTUATOR % C
This parameter configures the load % for point C, of the MW LOAD fuel limiter
curve.
MW LOAD D (MW)
This parameter configures the MW LOAD for point D, of the MW LOAD fuel
limiter curve. (MW)
ACTUATOR % D
This parameter configures the load % for point D, of the charge air fuel limiter
curve.
FINAL DRIVER
Description
HIT ACTUATOR
ACTUATOR HIT PULSE (s)
ACTUATOR HIT VALUE (-%)
STROKE ACTUATOR (%)
Range
False to True
0.0 to 2.0
0.0 to 100.0
0.0 to 100.0
Nominal
FALSE
0.1
0.0
0.0
Actual
HIT ACTUATOR
If the Actuator Hit has been enabled, when the Hit Actuator parameter is tuned
TRUE, the Actuator Hit Value is subtracted from the % actuator output, for a
period of time (Actuator Hit Pulse). This function is available for the purpose of
testing and proving dynamic set-up.
ACTUATOR HIT PULSE (s)
See above.
ACTUATOR HIT VALUE (-%)
See above.
STROKE ACTUATOR (%)
If the configurable Stroke Actuator has been selected true, the engine is
stopped, and the Run/Stop contact is in the Stop position, by adjusting this
value, the actuator output can be increased and decreased in order to calibrate
an electric actuator.
60
Woodward
Manual 91371
Range
0.0 to 100.0
0.0 to 100.0
0.0 to 5000.0
0.0 to 100.0
0.0 to 5000.0
Nominal
30.0
30.0
10.0
100.0
10.0
Actual
Rejection
Period 1
Load
Level 1
Load
Level 2
Range
0.0 to 110.0
0.0 to 100.0
0.0 to 5000.0
0.0 to 100.0
0.0 to 5000.0
Nominal
50.0
50.0
10.0
100.0
10.0
Actual
Rejection
Period 1
Load
Level 1
Woodward
Load
Level 2
61
Manual 91371
CALIBRATION
Description
AI#1 OFFSET
AI#1 GAIN
AI#2 OFFSET
AI#2 GAIN
AI#4 OFFSET
AI#4 GAIN
LS LINES OFFSET
LS LINES GAIN
LS LOAD OFFSET
LS LOAD GAIN
AN I/P #1 mA
AN I/P #2 mA
AN I/P #4 mA
AN O/P #1 OFFSET
AN O/P #1 GAIN
AN O/P #2 OFFSET
AN O/P #2 GAIN
AN O/P #3 OFFSET
AN O/P #3 GAIN
AN O/P CALIBRATION
Range
-10.0 to 10.0
0.0 to 10.0
-10.0 to 10.0
0.0 to 10.0
-10.0 to 10.0
0.0 to 10.0
0 to 32767
0 to 32767
0 to 32767
0 to 32767
Nominal
0.0
1.0
0.0
1.0
0.0
1.0
0
21845
2028
8083
(Monitor)
(Monitor)
(Monitor)
-1000.0 to 1000.0 0.0
0.5 to 1.5
1.0
-1000.0 to 1000.0 0.0
0.5 to 1.5
1.0
-1000.0 to 1000.0 0.0
0.5 to 1.5
1.0
0.0 to 20.0
4.0
Actual
AI#1 OFFSET
If it is necessary to calibrate Analog Input #1, adjustment of this parameter
alters the offset.
To calibrate the input, set the mA to zero, and ensure that the control is
measuring zero. If not, adjust the offset until it does. Then set the mA input to
20 mA. Ensure that the control is measuring 20. If not, adjust the gain until it
does. Return the mA input to zero, and check that the control is still measuring
zero. If not, repeat the calibration process.
AI#1 GAIN
If it is necessary to calibrate the Analog Input #1, adjustment of this parameter
alters the gain.
AI#2 OFFSET
If it is necessary to calibrate Analog Input #2, adjustment of this parameter
alters the offset.
To calibrate the input, set the mA to zero, and ensure that the control is
measuring zero. If not, adjust the offset until it does. Then set the mA input to
20 mA. Ensure that the control is measuring 20. If not, adjust the gain until it
does. Return the mA input to zero, and check that the control is still measuring
zero. If not, repeat the calibration process.
AI#2 GAIN
If it is necessary to calibrate the Analog Input #2, adjustment of this parameter
alters the gain.
AI#4 OFFSET
If it is necessary to calibrate Analog Input #4, adjustment of this parameter
alters the offset.
To calibrate the input, set the mA to zero, and ensure that the control is
measuring zero. If not, adjust the offset until it does. Then set the mA input to
20 mA. Ensure that the control is measuring 20. If not, adjust the gain until it
does. Return the mA input to zero, and check that the control is still measuring
zero. If not, repeat the calibration process.
AI#4 GAIN
If it is necessary to calibrate the Analog Input #4, adjustment of this parameter
alters the gain.
62
Woodward
Manual 91371
LS LINES OFFSET
If it is necessary to calibrate Load Share Lines input, adjustment of this
parameter alters the offset.
To calibrate the load sharing lines, contact Woodward Governor for further
information.
LS LINES GAIN
If it is necessary to calibrate the Load Share Lines input, adjustment of this
parameter alters the gain.
LS LOAD OFFSET
If it is necessary to calibrate load output to the load sharing lines, adjustment of
this parameter alters the offset.
To calibrate the load output to the load sharing lines, contact Woodward
Governor for further information.
LS LOAD GAIN
If it is necessary to calibrate the load output to the load sharing lines,
adjustment of this parameter alters the gain.
AN I/P #1 mA
Displays the mA value of analog input #1.
AN I/P #2 mA
Displays the mA value of analog input #2.
AN I/P #4 mA
Displays the mA value of analog input #4.
AN O/P #1 OFFSET
This parameter is the offset term, for calibration of analog output #1 (terminals
15 and 16).
If it is necessary to calibrate the output, set the parameter Analog Output #1 (in
menu *ANALOG O/P CONFIG*) to 8. Then adjust the An O/P Calibration term
to zero, and measure the current from output #1. If it is not zero, then adjust the
offset term. Then adjust the An O/P Calibration term to 20, and check the
current again. If it does not read 20, then adjust the gain term. Return to zero,
and check again, and work through the calibration process again if necessary.
AN O/P #1 GAIN
This parameter is the gain term, for calibration of analog output #1 (terminals 15
and 16).
AN O/P #2 OFFSET
This parameter is the offset term, for calibration of analog output #2 (terminals
17 and 18).
If it is necessary to calibrate the output, set the parameter Analog Output #2 (in
menu *ANALOG O/P CONFIG*) to 8. Then adjust the An O/P Calibration term
to zero, and measure the current from output #2. If it is not zero, then adjust the
offset term. Then adjust the An O/P Calibration term to 20, and check the
current again. If it does not read 20, then adjust the gain term. Return to zero,
and check again, and work through the calibration process again if necessary.
AN O/P #2 GAIN
This parameter is the gain term, for calibration of analog output #2 (terminals 17
and 18).
Woodward
63
Manual 91371
AN O/P #3 OFFSET
This parameter is the offset term, for calibration of analog output #3 (terminals
19 and 20).
If it is necessary to calibrate the output, set the parameter Analog Output #3 (in
menu *ANALOG O/P CONFIG*) to 8. Then adjust the An O/P Calibration term
to zero, and measure the current from output #3. If it is not zero, then adjust the
offset term. Then adjust the An O/P Calibration term to 20, and check the
current again. If it does not read 20, then adjust the gain term. Return to zero,
and check again, and work through the calibration process again if necessary.
AN O/P #3 GAIN
This parameter is the gain term, for calibration of analog output #3 (terminals 19
and 20).
AN O/P CALIBRATION
For any analog output selected to Option 8 (calibration), adjustment of this
value between 0 and 20 allows checking and adjustment of the calibration of the
output/metering device, between 0 and 20 mA.
Range
1 to 3
1 to 7
1 to 3
1 to 3
0.0 to 10.0
False to True
Nominal
1
6
1
1
1.0
FALSE
Actual
HARDWARE CONFIG
Sets the communications hardware configuration, 1=RS-232, 2=RS-422,
3=RS-485
BAUD RATE
Sets the desired baud rate, an integer number in the range 1 to 7 is to be used
representing: 1=1200, 2=1800, 3=2400, 4=4800, 5=9600, 6=19200, 7=38400.
The preferred baud rate is 9600. If the chosen baud rate is 38400, then both J2
and J3 must be set identical.
STOP BITS
Sets the desired number of stop bits, an integer number in the range 1 to 3 is to
be used representing: 1=1, 2=1.5, 3=2
PARITY
Sets the desired parity, an integer number in the range 1 to 3 is to be used
representing: 1=OFF, 2=ODD, 3=EVEN
TIMEOUT
If no communication is received within the Timeout period, a communications
error occurs.
ENABLE MODBUS ALMS
If set false, communications errors are ignored by the control.
64
Woodward
Manual 91371
SERVLINK J2 SETUP
Description
HARDWARE CONFIG J2
BAUD RATE J2
SLAVE ADDRESS J2
Range
1 to 2
1 to 12
0 to 15
Nominal
1
9
1
Actual
HARDWARE CONFIG J2
Sets the communications hardware configuration, 1=RS-232, 2=RS-422, 3=RS485
BAUD RATE J2
Sets the desired baud rate, an integer number in the range 1 to 10 is to be used
representing: 1=110, 2=300, 3=600, 4=1200, 5=1800, 6=2400, 7=4800,
8=9600, 9=19200, 10=38400. The preferred baud rates are 9600 and 19200.
SLAVE ADDRESS J2
Sets the slave address. In case of multidrop communication, this parameter
needs to be adapted to define each control with a different slave address. For
normal point to point communication, this value must stay at 1.
Range
1 to 8
1 to 8
1 to 8
0.0 to 2000.0
0.0 to 2000.0
0.0 to 60.0
0.0 to 60.0
0.0 to 2000.0
0.0 to 2000.0
0.0 to 2000.0
0.0 to 2000.0
-100.0 to 100.0
0.0 to 200.0
Nominal
2
3
4
0.0
1000.0
0.0
8.0
0.0
1000.0
0.0
1000.0
0.0
100.0
Actual
AO#1
This selects the analog value required through output #1, terminals 15 and 16.
Output scanned/updated every 20 ms.
1=Actuator Position (%)
2=Engine Speed (rpm)
3=Percentage Load (%)
4=MW Reference (MW)
5=Unfiltered Speed #1 (rpm)
6=Unfiltered Speed #2 (rpm)
7=Calibration Output
AO#2
This selects the analog value required through output #2, terminals 17 and 18.
See above for selection numbers. Output scanned/updated every 80 ms.
AO#3
This selects the analog value required through output #3, terminals 19 and 20.
See above for selection numbers. Output scanned/updated every 80 ms.
ENG SPEED AO @4 mA (RPM)
This sets the analog output level at 4 mA representing engine speed (filtered).
This value is scanned/updated every 80 ms.
Woodward
65
Manual 91371
MAJOR ALARM
Description
OVERSPEED
BOTH SPD SEN FAILED
Range
Nominal
(Monitor)
(Monitor)
Actual
OVERSPEED
If true, the engine speed has reached the Overspeed Trip level.
BOTH SPD SEN FAILED
If true, both speed sensors have failed, i.e. below 250 Hz.
MINOR ALARM
This menu will only be displayed, if a Minor Alarm has occurred.
Description
AI#1 FAILURE
AI#2 FAILURE
SPEED SENSOR FAULT
MODBUS COMMS
MW LIMITING
REM SEL WIRE BREAK
AI#4 FAILURE
LON ALARM
TIE BREAKER #1 FAIL
TIE BREAKER #2 FAIL
66
Range
Nominal
(Monitor)
(Monitor)
(Monitor)
(Monitor)
(Monitor)
(Monitor)
(Monitor)
(Monitor)
(Monitor)
(Monitor)
Actual
Woodward
Manual 91371
AI#1 FAILURE
If true, the analog load input has failed, i.e. below 1 mA, above 22 mA.
AI#2 FAILURE
If true, the analog remote reference input has failed, below 2 mA, above 22 mA
SPEED SENSOR FAULT
If true, a speed sensor has failed, i.e. below the 250 Hz
MODBUS COMMS
If true, a communications failure has occurred with Modbus.
MW LIMITING
If true, the MW reference is being limited by the frequency limiter curve.
REM SEL WIRE BREAK
If true, following the selection of remote MW reference (closure of both Increase
and Decrease contacts), a single wire has been disconnected or broken. Both
contacts must be opened to de-select remote MW reference.
AI#4 FAILURE
If true, analog input #4 has failed, below 2 mA, above 22 mA
LON Alarm
If true, this indicates that a LON Alarm is active. This means that an unit is
switched of or LON line is broken.
If false, the LON network does not generate an alarm.
TIE BREAKER #1 FAIL
If true, this indicates that one of the Tie Breaker #1 feedbacks to the active units
with LON address 1-5 is failing. This results in a switch to droop mode situation
for that particular bus part!
If false, the Tie Breaker Feedback #1 is OK for all active units with LON address
1-5.
TIE BREAKER #2 FAIL
If true, this indicates that one of the Tie Breaker #2 feedbacks to the active units
with LON address 11-16 is failing. This results in a switch to droop mode
situation for that particular bus part!
If false, the Tie Breaker Feedback #1 is OK for all active units with LON address
11-16.
KICKDOWN
This menu is meant for test purposes only. The purpose of the logic is to reduce
the speed increase during a load rejection.
Three different possibilities are implemented in this software version all based
on the derivative of the difference between actual speed and speed reference.
Different possibilities are:
Actuator will be set to zero in case the derivative is within a certain window
The speed reference will jump down instantly and slowly ramped back to
the original level. In this case a bigger error is created on the PID so the
PID will show a fast reaction.
The Integrator factor will be changed when inside the derivative window.
All three different options can be tested independent from each other. This
service menu is added for this purpose in order to activate and tune the
different possibilities.
Woodward
67
Range
False to True
-1000 to 1000
-1000 to 1000
0 to 101
False to True
-1000 to 0
0 to 1000
0 to 1000
False to True
0.01 to 5.0
False to True
0.01 to 10.0
Manual 91371
Nominal
FALSE
-200
-50
0
FALSE
-40
500
10
FALSE
0.8
FALSE
0.05
Actual
KICKDOWN ACTIVE?
This parameter enables and disables the logic.
TRUE Kickdown Logic is active. When derivative of error between actual
speed and speed reference is exceeding a certain level, the logic is activated.
FALSE Kickdown Logic is disabled.
KICKDOWN ON LEVEL
This is the ON level of the kickdown logic. When the derivative is exceeding this
level, the kickdown logic is active. The logic IS deactivated when the
KICKDOWN OFF LEVEL has been reached.
KICKDOWN OFF LEVEL
This is the OFF level of the kickdown logic. When the derivative is reduced to
this level, the kickdown logic is deactivated.
ACT JMP DWN LVL
In case the kickdown logic is activated, and the ACT SPD REF DOWN?
Parameter is set to FALSE, this is the actuator jump down value the actuator is
forced to. When set to zero, the actuator is forced to zero position during the
time the logic is active. Once the KICKDOWN OFF LEVEL has been reached,
the PID takes over control of the actuator again.
ACT SPD REF DOWN?
With this parameter, the speed reference jump down logic is activated in case
the kickdown logic is active.
TRUE Speed reference jump down logic is active. In this case, the actuator
is forced down by the PID.
FALSE Speed reference jump down logic is NOT active. In this situation the
actuator is forced down by switching to the Act Jmp Dwn Lvl on the LSS Bus
after the PID.
SPD REF DWN JMP
This parameter sets the actual speed amount that the speed reference is
reduced by means of the Spd Ref Down Rate: in case the Act Spd Ref Down?,
the Kickdown Active? are set to TRUE and the kickdown levels are reached.
The value is in rpm.
SPD REF DOWN RATE
This sets the speed reference ramp down rate in rpm/Second in case the speed
reference jump down logic is active.
SPD REF BACK RATE
This sets the speed reference ramp up rate in rpm/Second in case the speed
reference jump down logic is active. With this rate the speed reference is
ramped back to its original value, once the KICKDOWN OFF LEVEL has been
reached.
68
Woodward
Manual 91371
Range
-100 to 0.10
0.10 to 100
-10 to 0.10
-100 to 0.10
0.10 to 100
0.10 to 100
-1 to 0.10
0.10 to 1
Nominal
-15
15
-10
-4
10
4
-0.50
0.50
Actual
Woodward
69
Manual 91371
NEG WINDOW %
Normal negative operation window (Load %)
BIAS IN NEG WINDOW
Bias, in rpm, at maximum negative operation window.
POS WINDOW %
Normal positive operation window (Load %)
BIAS IN POS WINDOW
Bias, in rpm, at maximum positive operation window.
NEG DEADBAND (%)
Negative load % level where no more speed bias will be set when within this
range.
POS DEADBAND (%)
Positive load % level where no more speed bias will be set when within this
range.
Range
MONITOR
MONITOR
MONITOR
MONITOR
MONITOR
MONITOR
MONITOR
MONITOR
MONITOR
MONITOR
MONITOR
MONITOR
MONITOR
MONITOR
MONITOR
MONITOR
Nominal
Actual
MONITOR LON
This menu is only visible when the LON Load sharing is activated.
The menu can be used to monitor following parameters of each engine:
The units generator kW load in %
The status of the generator circuit breaker
The status of the bus tie breakers
Description
AVERAGE LOAD %
CB IN LON 1?
Isoch Active LON 1?
LOAD % LON 1?
Load MW LON 1
Act Speed LON 1
Act Speed Ref LON 1
CB IN LON 2?
70
Range
MONITOR
MONITOR
MONITOR
MONITOR
MONITOR
MONITOR
MONITOR
MONITOR
Nominal
Actual
Woodward
Manual 91371
Description
Isoch Active LON 2?
LOAD % LON 2?
Load MW LON 2
Act Speed LON 2
Act Speed Ref LON 2
CB IN LON 3?
Isoch Active LON 3?
LOAD % LON 3?
Load MW LON 3
Act Speed LON 3
Act Speed Ref LON 3
CB IN LON 4?
Isoch Active LON 4?
LOAD % LON 4?
Load MW LON 4
Act Speed LON 4
Act Speed Ref LON 4
CB IN LON 5?
Isoch Active LON 5?
LOAD % LON 5?
Load MW LON 5
Act Speed LON 5
Act Speed Ref LON 5
CB IN LON 6?
Isoch Active LON 6?
LOAD % LON 6?
Load MW LON 6
Act Speed LON 6
Act Speed Ref LON 6
CB IN LON 7?
Isoch Active LON 7?
LOAD % LON 7?
Load MW LON 7
Act Speed LON 7
Act Speed Ref LON 7
CB IN LON 8?
Isoch Active LON 8?
LOAD % LON 8?
Load MW LON 8
Act Speed LON 8
Act Speed Ref LON 8
CB IN LON 9?
Isoch Active LON 9?
LOAD % LON 9?
Load MW LON 9
Act Speed LON 9
Act Speed Ref LON 9
CB IN LON 10?
Isoch Active LON 10?
LOAD % LON 10?
Load MW LON 10
Act Speed LON 10
Act Speed Ref LON 10
CB IN LON 11?
Isoch Active LON 11?
LOAD % LON 11?
Load MW LON 11
Act Speed LON 11
Act Speed Ref LON 11
CB IN LON 12?
Isoch Active LON 12?
LOAD % LON 12?
Woodward
Nominal
Actual
71
Range
MONITOR
MONITOR
MONITOR
MONITOR
MONITOR
MONITOR
MONITOR
MONITOR
MONITOR
MONITOR
MONITOR
MONITOR
MONITOR
MONITOR
MONITOR
MONITOR
MONITOR
MONITOR
MONITOR
MONITOR
MONITOR
MONITOR
MONITOR
MONITOR
MONITOR
MONITOR
MONITOR
MONITOR
MONITOR
Manual 91371
Nominal
Actual
AVERAGE LOAD %
This value displays the average load % on the bus when in Isochronous load
sharing on the LON bus.
CB IN LON 1? CB IN LON 16?
These values show if the Circuit breaker on the specific LON address is in or
out.
TRUE Breaker is in.
FALSE Breaker is not in.
Isoch Active LON 1? Isoch Active LON 16?
These values show if the Isochronous Mode on the specific LON address is
active or not.
TRUE Isoch Mode is Active.
FALSE Isoch Mode is not active. Droop mode or MW mode will be.
LOAD % LON 1? LOAD % LON 16?
These values show if the Load in % of each unit online.
LOAD MW LON 1? LOAD MW LON 16?
These values show if the Load in MW of each unit online.
Act Speed LON 1? Act Speed LON 16?
These values show if the actual speed in rpm of each unit online.
Act Speed Ref LON 1? Act Speed Ref LON 16?
These values show if the actual speed reference in rpm of each unit online.
TIE BREAKER #1 IN?
This value shows if the Tie Breaker #1 is in or not.
TRUE TIE Breaker #1 is in.
FALSE TIE Breaker #1 is not in.
72
Woodward
Manual 91371
MW LOAD LON
This menu is only visible when the LON Load sharing is activated.
The menu must be used to set the LON load share parameters that are
important for the correct functionality as wanted.
Description
LOAD RATE (%/sec)
UNLOAD RATE (%/sec)
BUS CONNECT RATE (%/sec)
BUS LOAD DIFF (%)
Range
0.0 to 100.0
0.0 to 100.0
0.01 to 100.0
0.0 to 100.0
Nominal
1.0
3.0
1.0
10.0
Actual
J1 PORT SETUP
Description
1=SERVLINK, 2=HHT
BAUD RATE J1
Range
1, 2
1 - 10
Nominal
2
9
Actual
1=SERVLINK, 2=HHT
For downloading software into the 723PLUS it is necessary to switch the J1 port
to Servlink so that the PC can communicate with the control.
Once a mode is selected by changing the parameter, there is a delay of 30
seconds before the control will actually switch over. If Servlink is selected by
error, and the user cannot communicate with Servlink to switch it back to HHT,
switching the power off then on again will automatically reselect HHT.
BAUD RATE J1
This sets the baud rate for Servlink communications via the J1 port:
1=110, 2=300. 3=600, 4=1200, 5=1800, 6=2400, 7=4800, 8=9600, 9-19200,
10=38400
Woodward
73
Manual 91371
Final
Prompt
Default
Range
Value
____________________________________________________________________________
PASSCODE
ENABLE CONFIGURE
723
0 to 32767
__________
ENABLE SERVICE
723
0 to 32767
__________
SPEED SENSORS
PULSE/REV #1
MAXIMUM HZ #1
PULSE/REV #1 DIG
PULSE/REV #2
MAXIMUM HZ #2
PULSE/REV #2 DIG
SPD ANA=F / DIG=T?
LOW SET POINT #1 (rpm)
OVERRIDE SPEED #1 (rpm)
MINIMUM SPEED #1 (rpm)
LOW SET POINT #2 (rpm)
OVERRIDE SPEED #2 (rpm)
MINIMUM SPEED #2 (rpm)
155
2519
155
155
2519
155
TRUE
95
135
400
95
135
400
30 to 360
500 to 10000
30 to 360
30 to 360
500 to 10000
30 to 360
False to True
0 to 1500
0 to 1500
0 to 1500
0 to 1500
0 to 1500
0 to 1500
__________
__________
__________
__________
__________
__________
__________
__________
__________
__________
__________
__________
__________
ENGINE SPEED
IDLE SPEED (rpm)
RATED SPEED (rpm)
OVERSPEED TRIP (rpm)
TORSIONAL FILTER?
550.0
750.0
863.0
FALSE
0.0 to 2000.0
0.0 to 2000.0
0.0 to 2500.0
False to True
__________
__________
__________
__________
MW CONTROL
REMOTE REF @ 4 mA (MW)
REMOTE REF @ 20 mA (MW)
SELECT INT MW REF
ENBL INT REF ANALOG
0.0
8.0
FALSE
FALSE
-10.0 to 60.0
0.0 to 60.0
False to True
False to True
__________
__________
__________
__________
FINAL DRIVER
REVERSE ACTING?
ACT O/P @ 0 mA (%)
ACT O/P @ 20/200 mA (%)
ENABLE ACTUATOR HIT
CHARGE AIR @ 20 mA (bar)
STROKE ACTUATOR
FALSE
0.0
100.0
FALSE
6.0
FALSE
False to True
-25.0 to 200.0
-25.0 to 200.0
False to True
0.0 to 10.0
False to True
__________
__________
__________
__________
__________
__________
ENGINE LOAD
RATED LOAD (MW)
MW SENSOR @ 4 mA (MW)
MW SENSOR @ 20 mA (MW)
MVAR @ 4 mA
MVAR @ 20 mA
6.52
0.0
8.0
-10.0
10.0
0.0 to 60.0
-60.0 to 60.0
0.0 to 60.0
-60.0 to 60.0
-60.0 to 60.0
__________
__________
__________
__________
__________
2
1
1 to 2
1 to 247
__________
__________
CONFIGURE
ENABLE CALIBRATION
FALSE
False to True
__________
FALSE
FALSE
FALSE
FALSE
FALSE
FALSE
FALSE
FALSE
False to True
False to True
False to True
False to True
False to True
False to True
False to True
False to True
__________
__________
__________
__________
__________
__________
__________
__________
74
Woodward
Manual 91371
Heading
Final
Prompt
Default
Range
Value
____________________________________________________________________________
CONTROL OPTIONS
GRID CB OPEN CMD?
TRUE
False to True
__________
ENABLE MW OVERRIDE?
FALSE
False to True
__________
EN MW OVRD AUTORST?
FALSE
False to True
__________
MW DEADBAND CONTROL
FALSE
False to True
__________
ENABLE I/R SELECT
FALSE
False to True
__________
AI#4 - CHARGE AIR?
FALSE
False to True
__________
OPEN DI#1 TO RUN?
FALSE
False to True
__________
ENABLE AI#1
TRUE
False to True
__________
ENABLE AI#2
TRUE
False to True
__________
ENABLE AI#4
FALSE
False to True
__________
DO#1 NC?
TRUE
False to True
__________
DO#2 NC?
FALSE
False to True
__________
DO#3 NC?
FALSE
False to True
__________
USE LSL (F) OR LON (T) ?
FALSE
False to True
__________
KW CONTROL I/O CH (0=NA)
7
0 to 9
__________
TIE#1 I/O CH (0=NA)
0
0 to 9
__________
TIE#2 I/O CH (0=NA)
0
0 to 9
__________
PAR GRID I/O CH (0=NA)
8
0 to 9
__________
EMERG LOADING I/O CH (0=NA) 0
0 to 9
__________
USE FUEL #2 I/O CH (0=NA)
0
0 to 9
__________
SET LON ALARMS
SHOW ALARM LON TO ALL?
TRUE
False to True
__________
LON COM
LON Address
Is LON 2 Used ?
Is LON 3 Used ?
Is LON 4 Used ?
Is LON 5 Used ?
Is LON 6 Used ?
Is LON 7 Used ?
Is LON 8 Used ?
Is LON 9 Used ?
Is LON 10 Used ?
Is LON 11 Used ?
Is LON 12 Used ?
Is LON 13 Used ?
Is LON 14 Used ?
Is LON 15 Used ?
Is LON 16 Used ?
1
TRUE
TRUE
TRUE
TRUE
TRUE
TRUE
TRUE
TRUE
TRUE
TRUE
TRUE
TRUE
TRUE
TRUE
TRUE
1 to 16
False to True
False to True
False to True
False to True
False to True
False to True
False to True
False to True
False to True
False to True
False to True
False to True
False to True
False to True
False to True
__________
__________
__________
__________
__________
__________
__________
__________
__________
__________
__________
__________
__________
__________
__________
__________
Woodward
75
Manual 91371
Final
Prompt
Default
Range
Value
____________________________________________________________________________
DISPLAY MENU
ENGINE SPEED (rpm)
(Monitor)
SPEED REFERENCE (rpm)
(Monitor)
MW LOAD (MW)
(Monitor)
ACTUATOR POSITION (%)
(Monitor)
FUEL LIMIT (%)
(Monitor)
PID OUTPUT (%)
(Monitor)
ENGINE STOPPED
(Monitor)
ENGINE RUNNING
(Monitor)
READY TO SYNC
(Monitor)
UNIT SYNC BIAS (rpm)
(Monitor)
SYS SYNC BIAS (rpm)
(Monitor)
DROOP BIAS (rpm)
(Monitor)
REF BEFORE BIAS (rpm)
(Monitor)
GEN CB CLOSED
(Monitor)
ISOCHRONOUS MODE
(Monitor)
% LOAD
(Monitor)
LS LINES %
(Monitor)
LOAD SHARE ERROR
(Monitor)
MW CONTROL MODE
(Monitor)
MW OVERRIDE ACTIVE
(Monitor)
LOAD REFERENCE (MW)
(Monitor)
REMOTE REF SELECTED
(Monitor)
REMOTE REFERENCE (MW)
(Monitor)
MW LIMIT
(Monitor)
REACTIVE POWER (MVAR)
(Monitor)
CHARGE AIR PRESSURE (bar)
(Monitor)
AI#1 mA
(Monitor)
AI#2 mA
(Monitor)
AI#4 mA
(Monitor)
DYNAMICS #1
PROP GAIN #1
INTEGRAL GAIN #1 (1/s)
SDR #1
DYN SELECT DELAY (s)
0.25
0.5
10.0
2.5
0.01 to 10.0
0.01 to 5.0
0.01 to 100.0
0.0 to 10.0
__________
__________
__________
__________
DYNAMICS #2
PROP GAIN #2
INTEGRAL GAIN #2 (1/s)
SDR #2
PROPGAIN MULTIPLIER
0.35
0.63
14.55
1.0
0.01 to 10.0
0.01 to 5.0
0.01 to 100.0
0.01 to 1.0
__________
__________
__________
__________
MW DYNAMICS
PROPORTIONAL GAIN
INTEGRAL GAIN
SDR
USE LOWER PROP BAND
0.01
0.3
20.0
FALSE
0.01 to 10.0
0.01 to 5.0
0.01 to 100.0
False to True
__________
__________
__________
__________
76
Woodward
Manual 91371
Heading
Final
Prompt
Default
Range
Value
____________________________________________________________________________
VARIABLE GAIN
LOW SPEED ERROR WIN#1
20.0
0.0 to 1000.0
__________
HIGH SPEED ERROR WIN#1
100.0
0.0 to 1000.0
__________
SPEED GAIN RATIO #1
1.0
0.0 to 10.0
__________
LOW SPEED ERROR WIN#2
20.0
0.0 to 1000.0
__________
HIGH SPEED ERROR WIN#2
100.0
0.0 to 1000.0
__________
SPEED GAIN RATIO #2
1.0
0.0 to 10.0
__________
LOAD LEVEL (GAIN) #1
0.0
0.0 to 110.0
__________
LOAD GAIN RATIO #1
1.0
0.01 to 10.0
__________
LOAD LEVEL (GAIN) #2
100.0
0.0 to 110.0
__________
LOAD GAIN RATIO #2
1.0
0.01 to 10.0
__________
LOAD LEVEL (INT) #1
0.0
0.0 to 110.0
__________
LOAD INT GAIN RATIO #1
1.0
0.01 to 10.0
__________
LOAD LEVEL (INT) #2
100.0
0.0 to 110.0
__________
LOAD INT GAIN RATIO #2
1.0
0.01 to 10.0
__________
ENGINE SPEED
SPEED FILTER (Hz)
FILTER 1 FREQUENCY (Hz)
FILTER 1 Q FACTOR
FILTER 2 FREQUENCY (Hz)
FILTER 2 Q FACTOR
SENSOR WEIGHT
ENGINE RUNNING (rpm)
TWO SPEED SENSORS?
ENABLE NOTCH FILTER 1
ENABLE NOTCH FILTER 2
12.0
3.5
0.707
3.5
0.707
0.5
150.0
TRUE
FALSE
FALSE
0.01 to 16.0
0.01 to 16.0
0.707 to 25.0
0.01 to 16.0
0.707 to 25.0
0.0 to 1.0
0.0 to 2500.0
False to True
False to True
False to True
__________
__________
__________
__________
__________
__________
__________
__________
__________
__________
SPEED REFERENCE
MINIMUM SPEED (rpm)
MAXIMUM SPEED (rpm)
ACCEL/DECEL RATE (rpm/s)
IDLE/RATED SWITCH (rpm)
INC/DEC RATE #1 (rpm/s)
INC/DEC RATE #2 (rpm/s)
690.0
810.0
25.0
450.0
2.0
1.0
0.0 to 2000.0
0.0 to 2000.0
0.0 to 2000.0
0.0 to 2500.0
0.0 to 2000.0
0.0 to 2000.0
__________
__________
__________
__________
__________
__________
START/STOP
RUNDOWN TIME (s)
PULSE/CONT ALARM?
ALARM PULSE TIME (s)
MINOR ALM PULSE (s)
10.0
FALSE
1.0
2.0
0.0 to 300.0
False to True
1.0 to 30.0
0.0 to 30.0
__________
__________
__________
__________
SYNCHRONIZING
RDY TO SYNC LIMITS (rpm)
SYNC OK DLY TIME (s)
UNIT SYNCH GAIN
ENABLE UNIT SYNCH
SYNC FILTER
SYS SYNCH GAIN
ENABLE SYS SYNCH
SYS SYNCH DELAY
4.0
2.0
2.0
TRUE
10.0
2.0
FALSE
1.0
0.0 to 20.0
0.0 to 30.0
0.0 to 100.0
False to True
0.01 to 16.0
0.0 to 100.0
False to True
0.0 to 30.0
__________
__________
__________
__________
__________
__________
__________
__________
2.0
5.0
30.0
50.0
50.0
100.0
TRUE
TRUE
0.5
TRUE
0.5
1.0
1.0 to 100.0
0.01 to 100.0
0.0 to 30000.0
0.0 to 30000.0
0.0 to 30000.0
0.0 to 30000.0
False to True
False to True
0.0 TO 9.0
False to True
0.0 TO 9.0
0.0 TO 9.0E+20
__________
__________
__________
__________
__________
__________
__________
__________
__________
__________
__________
__________
Woodward
77
Manual 91371
Heading
Final
Prompt
Default
Range
Value
____________________________________________________________________________
MW REFERENCE (kW)
AUTO LOAD RATE (kW/s)
30.0
0.0 to 30000.0
__________
AUTO UNLOAD RATE (kW/s)
50.0
0.0 to 30000.0
__________
RAISE LOAD RATE (kW/s)
30.0
0.0 to 30000.0
__________
LOWER LOAD RATE (kW/s)
30.0
0.0 to 30000.0
__________
ENABLE INSTANT RATE
FALSE
False to True
__________
INSTANT RATE WINDOW (kW)
300.0
0.0 to 30000.0
__________
DEADBAND WINDOW (kW)
150.0
0.0 to 30000.0
__________
D/B CTRL RAMP RATE (kW/s)
15.0
0.0 to 30000.0
__________
INTERNAL MW REF (%)
3.0
0.0 to 110.0
__________
INT MW REF RATE (kW/s)
1000.0
0.0 to 30000.0
__________
D/B MW FILTER (s)
3.5
0.04 to 15.0
__________
MW REF FILTER (s)
50.0
0.0 to 100.0
__________
ENGINE LOAD
DROOP (%)
FULL LOAD ACT %
MW FILTER (Hz)
DRP/ISOCH MW FILTER (Hz)
LOAD FILTER (Hz)
UNLOAD TRIP LEVEL (kW)
MAXIMUM FUEL LIMIT (%)
REF BIAS PULSE (rpm)
5.0
70.0
1.0
1.0
1.0
200.0
100.0
1.0
0.0 to 15.0
__________
0.0 to 100.0
__________
0.01 to 10.0
__________
0.01 to 10.0
__________
0.01 to 10.0
__________
-1000.0 to 30000.0 __________
0.0 to 100.0
__________
0.0 to 10.0
__________
FREQUENCY LIMITER
BUS FREQUENCY (Hz)
MW LIMITER HZ #1
MW LIMITER HZ #2
MAXIMUM LOAD (1) (MW)
MW LIMITER HZ #3
MAXIMUM LOAD (2) (MW)
MW LIMITER HZ #4
FREQ LL TRIP (Hz)
FREQ L TRIP (Hz)
FREQ H TRIP (Hz)
FREQ HH TRIP (Hz)
LL/HH TRIP DELAY (s)
L/H TRIP DELAY (s)
MW OVRD AUTORST DLY (s)
50.0
48.0
49.0
6.52
51.0
6.52
52.0
46.0
47.0
51.0
53.0
0.1
0.1
300.0
45.0 to 65.0
0.0 to 60.0
10.0 to 60.0
0.0 to 100.0
0.0 to 100.0
0.0 to 100.0
50.0 to 100.0
40.0 to 60.0
40.0 to 60.0
50.0 to 70.0
50.0 to 70.0
0.0 to 3.0
0.0 to 3.0
0.0 to 1800.0
__________
__________
__________
__________
__________
__________
__________
__________
__________
__________
__________
__________
__________
__________
0.0
30.0
120.0
50.0
530.0
50.0
530.0
50.0
0.0 to 2000.0
0.0 to 100.0
0.0 to 2000.0
0.0 to 100.0
0.0 to 2000.0
0.0 to 100.0
0.0 to 2000.0
0.0 to 100.0
__________
__________
__________
__________
__________
__________
__________
__________
0.0
30.0
120.0
50.0
530.0
50.0
530.0
50.0
0.0 to 2000.0
0.0 to 100.0
0.0 to 2000.0
0.0 to 100.0
0.0 to 2000.0
0.0 to 100.0
0.0 to 2000.0
0.0 to 100.0
__________
__________
__________
__________
__________
__________
__________
__________
78
Woodward
Manual 91371
Heading
Final
Prompt
Default
Range
Value
____________________________________________________________________________
CHARGE AIR LIMIT
MANIFOLD PRESSURE A (bar)
0.0
0.0 to 6.0
__________
ACTUATOR % A
100.0
0.0 to 100.0
__________
MANIFOLD PRESSURE B (bar)
1.0
0.0 to 6.0
__________
ACTUATOR % B
100.0
0.0 to 100.0
__________
MANIFOLD PRESSURE C (bar)
3.0
0.0 to 6.0
__________
ACTUATOR % C
100.0
0.0 to 100.0
__________
MANIFOLD PRESSURE D (bar)
4.0
0.0 to 6.0
__________
ACTUATOR % D
100.0
0.0 to 100.0
__________
MW LIMIT
MW LOAD A (MW)
ACTUATOR % A
MW LOAD B (MW)
ACTUATOR % B
MW LOAD C (MW)
ACTUATOR % C
MW LOAD D (MW)
ACTUATOR % D
0.0
100.0
2.0
100.0
4.0
100.0
8.0
100.0
0.0 to 20.0
0.0 to 100.0
0.0 to 20.0
0.0 to 100.0
0.0 to 20.0
0.0 to 100.0
0.0 to 20.0
0.0 to 100.0
__________
__________
__________
__________
__________
__________
__________
__________
FINAL DRIVER
HIT ACTUATOR
ACTUATOR HIT PULSE (s)
ACTUATOR HIT VALUE (-%)
STROKE ACTUATOR (%)
FALSE
0.1
0.0
0.0
False to True
0.0 to 2.0
0.0 to 100.0
0.0 to 100.0
__________
__________
__________
__________
30.0
30.0
10.0
100.0
10.0
0.0 to 100.0
0.0 to 100.0
0.0 to 5000.0
0.0 to 100.0
0.0 to 5000.0
__________
__________
__________
__________
__________
50.0
50.0
10.0
100.0
10.0
0.0 to 110.0
0.0 to 100.0
0.0 to 5000.0
0.0 to 100.0
0.0 to 5000.0
__________
__________
__________
__________
__________
CALIBRATION
AI#1 OFFSET
AI#1 GAIN
AI#2 OFFSET
AI#2 GAIN
AI#4 OFFSET
AI#4 GAIN
LS LINES OFFSET
LS LINES GAIN
LS LOAD OFFSET
LS LOAD GAIN
AN I/P #1 mA
AN I/P #2 mA
AN I/P #4 mA
AN O/P #1 OFFSET
AN O/P #1 GAIN
AN O/P #2 OFFSET
AN O/P #2 GAIN
AN O/P #3 OFFSET
AN O/P #3 GAIN
AN O/P CALIBRATION
0.0
1.0
0.0
1.0
0.0
1.0
0
21845
2028
8083
(Monitor)
(Monitor)
(Monitor)
0.0
1.0
0.0
1.0
0.0
1.0
4.0
-10.0 to 10.0
0.0 to 10.0
-10.0 to 10.0
0.0 to 10.0
-10.0 to 10.0
0.0 to 10.0
0 to 32767
0 to 32767
0 to 32767
0 to 32767
__________
__________
__________
__________
__________
__________
__________
__________
__________
__________
-1000.0 to 1000.0
0.5 to 1.5
-1000.0 to 1000.0
0.5 to 1.5
-1000.0 to 1000.0
0.5 to 1.5
0.0 to 20.0
__________
__________
__________
__________
__________
__________
__________
Woodward
79
Manual 91371
Heading
Final
Prompt
Default
Range
Value
____________________________________________________________________________
MODBUS PORT SETUP
HARDWARE CONFIG
1
1 to 3
__________
BAUD RATE
6
1 to 7
__________
STOP BITS
1
1 to 3
__________
PARITY
1
1 to 3
__________
TIMEOUT
1.0
0.0 to 10.0
__________
ENABLE MODBUS ALMS
FALSE
False to True
__________
SERVLINK J2 SETUP
HARDWARE CONFIG J2
BAUD RATE J2
SLAVE ADDRESS J2
1
9
1
1 to 2
1 to 12
0 to 15
__________
__________
__________
2
3
4
0.0
1000.0
0.0
8.0
0.0
1000.0
0.0
1000.0
0.0
100.0
1 to 8
1 to 8
1 to 8
0.0 to 2000.0
0.0 to 2000.0
0.0 to 60.0
0.0 to 60.0
0.0 to 2000.0
0.0 to 2000.0
0.0 to 2000.0
0.0 to 2000.0
-100.0 to 100.0
0.0 to 200.0
__________
__________
__________
__________
__________
__________
__________
__________
__________
__________
__________
__________
__________
MAJOR ALARM
OVERSPEED
BOTH SPD SEN FAILED
(Monitor)
(Monitor)
MINOR ALARM
AI#1 FAILURE
AI#2 FAILURE
SPEED SENSOR FAULT
MODBUS COMMS
MW LIMITING
REM SEL WIRE BREAK
AI#4 FAILURE
LON ALARM
TIE BREAKER #1 FAIL
TIE BREAKER #2 FAIL
(Monitor)
(Monitor)
(Monitor)
(Monitor)
(Monitor)
(Monitor)
(Monitor)
(Monitor)
(Monitor)
(Monitor)
KICKDOWN
KICKDOWN ACTIVE?
KICKDOWN ON LEVEL
KICKDOWN OFF LEVEL
ACT JMP DWN LVL
ACT SPD REF DOWN?
SPD REF DWN JMP:
SPD REF DOWN RATE:
SPD REF BACK RATE:
ENABLE I-FACTOR SWITCH
I-FACTOR DURING KICK
ENABLE CB REF KICKDOWN
CB REF DWN TIME (s)
FALSE
-200
-50
0
FALSE
-40
500
10
FALSE
0.8
FALSE
0.05
False to True
-1000 to 1000
-1000 to 1000
0 to 101
False to True
-1000 to 0
0 to 1000
0 to 1000
False to True
0.01 to 5.0
False to True
0.0 to 10.0
__________
__________
__________
__________
__________
__________
__________
__________
__________
__________
__________
__________
-15
15
-10
-4
10
4
-0.5
0.5
-100 to 0.10
0.10 to 100
-10 to 0.10
-100 to 0.10
0.10 to 100
0.10 to 100
-1 to 0.10
0.10 to 1
__________
__________
__________
__________
__________
__________
__________
__________
80
Woodward
Manual 91371
Heading
Final
Prompt
Default
Range
Value
____________________________________________________________________________
LON COM FAILURE
FAIL TO COM LON 1?
(MONITOR)
FAIL TO COM LON 2?
(MONITOR)
FAIL TO COM LON 3?
(MONITOR)
FAIL TO COM LON 4?
(MONITOR)
FAIL TO COM LON 5?
(MONITOR)
FAIL TO COM LON 6?
(MONITOR)
FAIL TO COM LON 7?
(MONITOR)
FAIL TO COM LON 8?
(MONITOR)
FAIL TO COM LON 9?
(MONITOR)
FAIL TO COM LON 10?
(MONITOR)
FAIL TO COM LON 11?
(MONITOR)
FAIL TO COM LON 12?
(MONITOR)
FAIL TO COM LON 13?
(MONITOR)
FAIL TO COM LON 14?
(MONITOR)
FAIL TO COM LON 15?
(MONITOR)
FAIL TO COM LON 16?
(MONITOR)
MONITOR LON
AVERAGE LOAD %
CB IN LON 1?
Isoch Active LON 1?
LOAD % LON 1?
Load MW LON 1
Act Speed LON 1
Act Speed Ref LON 1
CB IN LON 2?
Isoch Active LON 2?
LOAD % LON 2?
Load MW LON 2
Act Speed LON 2
Act Speed Ref LON 2
CB IN LON 3?
Isoch Active LON 3?
LOAD % LON 3?
Load MW LON 3
Act Speed LON 3
Act Speed Ref LON 3
CB IN LON 4?
Isoch Active LON 4?
LOAD % LON 4?
Load MW LON 4
Act Speed LON 4
Act Speed Ref LON 4
CB IN LON 5?
Isoch Active LON 5?
LOAD % LON 5?
Load MW LON 5
Act Speed LON 5
Act Speed Ref LON 5
CB IN LON 6?
Isoch Active LON 6?
LOAD % LON 6?
Load MW LON 6
Act Speed LON 6
Act Speed Ref LON 6
CB IN LON 7?
Isoch Active LON 7?
LOAD % LON 7?
Load MW LON 7
Act Speed LON 7
Act Speed Ref LON 7
CB IN LON 8?
Isoch Active LON 8?
LOAD % LON 8?
Load MW LON 8
Act Speed LON 8
Woodward
(MONITOR)
(MONITOR)
(MONITOR)
(MONITOR)
(MONITOR)
(MONITOR)
(MONITOR)
(MONITOR)
(MONITOR)
(MONITOR)
(MONITOR)
(MONITOR)
(MONITOR)
(MONITOR)
(MONITOR)
(MONITOR)
(MONITOR)
(MONITOR)
(MONITOR)
(MONITOR)
(MONITOR)
(MONITOR)
(MONITOR)
(MONITOR)
(MONITOR)
(MONITOR)
(MONITOR)
(MONITOR)
(MONITOR)
(MONITOR)
(MONITOR)
(MONITOR)
(MONITOR)
(MONITOR)
(MONITOR)
(MONITOR)
(MONITOR)
(MONITOR)
(MONITOR)
(MONITOR)
(MONITOR)
(MONITOR)
(MONITOR)
(MONITOR)
(MONITOR)
(MONITOR)
(MONITOR)
(MONITOR)
81
Manual 91371
(MONITOR)
(MONITOR)
(MONITOR)
(MONITOR)
(MONITOR)
(MONITOR)
(MONITOR)
(MONITOR)
(MONITOR)
(MONITOR)
(MONITOR)
(MONITOR)
(MONITOR)
(MONITOR)
(MONITOR)
(MONITOR)
(MONITOR)
(MONITOR)
(MONITOR)
(MONITOR)
(MONITOR)
(MONITOR)
(MONITOR)
(MONITOR)
(MONITOR)
(MONITOR)
(MONITOR)
(MONITOR)
(MONITOR)
(MONITOR)
(MONITOR)
(MONITOR)
(MONITOR)
(MONITOR)
(MONITOR)
(MONITOR)
(MONITOR)
(MONITOR)
(MONITOR)
(MONITOR)
(MONITOR)
(MONITOR)
(MONITOR)
(MONITOR)
(MONITOR)
(MONITOR)
(MONITOR)
(MONITOR)
(MONITOR)
(MONITOR)
(MONITOR)
MW LOAD LON
LOAD RATE (%/sec)
UNLOAD RATE (%/sec)
BUS CONNECT RATE (%/sec)
BUS LOAD DIFF (%)
0.0 to 100.0
0.0 to 100.0
0.01 to 100.0
0.0 to 100.0
1.0
3.0
1.0
10.0
J1 PORT SETUP
1=SERVLINK, 2=HHT
BAUD RATE J1
2
9
1, 2
1 - 10
82
__________
__________
Woodward
Manual 91371
Description
Run/Start Engine
Stop Engine
Increase Speed/Load
Decrease Speed/Load
Select Remote Reference
Unload
Droop
Isochronous
Emergency Loading Rate
Reset
Select KW Control
Select Rated Speed
Select Idle Speed
Boolean Reads
Address
1:0001
1:0002
1:0003
1:0004
1:0005
1:0006
1:0007
1:0008
1:0009
1:0010
1:0011
1:0012
1:0013
1:0014
1:0015
1:0016
1:0017
1:0018
1:0019
1:0020
1:0021
1:0022
1:0023
1:0024
1:0025
1:0026
1:0027
1:0028
1:0029
1:0030
1:0031
1:0032
1:0033
1:0034
1:0035
1:0036
1:0037
1:0038
1:0039
1:0040
1:0041
1:0042
1:0043
Woodward
Description
*MAJOR/SHUTDOWN ALARM*
*MINOR ALARM*
OVERSPEED - SD
BOTH SPEED SENSORS FAILED - SD
ANALOG INPUT #1 FAILURE - MINOR
ANALOG INPUT #2 FAILURE - MINOR
SPEED SENSOR FAILURE - MINOR
MW LIMITING - MINOR
REMOTE SELECT, WIRE BREAK - MINOR
ANALOG INPUT #4 FAILURE - MINOR
LON FAILURE
ENGINE STOPPED
ENGINE RUNNING
READY TO SYNCHRONIES
GENERATOR BREAKER CLOSED
ISOCHRONOUS MODE
MW CONTROL MODE
REMOTE REFERENCE SELECTED
MW OVERRIDE ACTIVE
TB1 Failure (LON LS)
TB2 Failure (LON LS)
LON #1 FAIL
LON #2 FAIL
LON #3 FAIL
LON #4 FAIL
LON #5 FAIL
LON #6 FAIL
LON #7 FAIL
LON #8 FAIL
LON #9 FAIL
LON #10 FAIL
LON #11 FAIL
LON #12 FAIL
LON #13 FAIL
LON #14 FAIL
83
Manual 91371
Description
LON #15 FAIL
LON #16 FAIL
Analog Reads
Address
3:0001
3:0002
3:0003
3:0004
3:0005
3:0006
3:0007
3:0008
3:0009
3:0010
3:0011
3:0012
3:0013
3:0014
3:0015
3:0016
3:0017
3:0018
3:0019
3:0020
Description
ENGINE SPEED (RPM)
ENGINE SPEED #1 (RPM)
ENGINE SPEED #2 (RPM)
SPEED REFERENCE (RPM)
MW LOAD
ACTUATOR POSITION (%)
FUEL LIMIT
PID OUTPUT
% LOAD
LS LINES %
LOAD SHARE ERROR
LOAD REFERENCE (MW)
REMOTE REFERENCE (MW)
MW LIMIT
UNIT SYNCH BIAS (RPM)
SYSTEM SYNCH BIAS (RPM)
DROOP BIAS (RPM)
SPEED REFERENCE BEFORE BIASES
REACTIVE POWER (MVAR)
CHARGE AIR PRESSURE (bar)
Analog Writes
Address
4:0001
84
Description
Remote MW Reference (MW)
Woodward
Manual 91371
Chapter 6.
Modbus Communications
The 723PLUS Digital Control utilizes AEG-Modicon Incs Modbus protocol.
The Modbus protocol determines how the master and slaves establish and
break off contact, how the sender and receiver are identified, how messages
are exchanged in an orderly manner, and how errors are detected. The protocol
also controls the query and response cycle which takes place between the
master and slave devices.
The protocol provides for one master and up to 247 slaves on a common line.
Each slave is assigned a fixed unique device address in the range of 1 to 247.
Only the master can initiate a transaction. A transaction consists of a message
from the master to one of the slaves and a response from that slave to the
master.
The control supports two modes of transmission for Modbus. The mode defines
the individual units of information within a message, and the numbering system
used to transmit the data. Only one mode of transmission may be used per
Modbus system; mixing of modes is not possible. The two transmission modes
are ASCII (American Standard Code for Information Interchange) and RTU
(Remote Terminal Unit). The modes are defined in Table 6-1. The 723PLUS
DCS uses either the ASCII or the RTU transmission mode.
Table 6-1. Modbus Transmission Modes
ASCII
CODING SYSTEM
HEXADECIMAL
BITS PER CHARACTER
7
PARITY
EVEN, ODD, NONE
STOP BITS
1 OR 2
DATA TRANSMITTED PER
4 BITS
CHARACTER
LRC
ERROR CHECKING
(LONGITUDINAL
REDUNDANCY CHECK)
RTU
8 BIT BINARY
8
EVEN, ODD, NONE
1 OR 2
8 BITS
CRC
(CYCLICAL REDUNDANCY
CHECK)
In RTU mode, the data is sent in 8-bit binary characters. In ASCII mode, each
RTU character is first divided into two 4-bit parts (high order and low order) and
then represented by their hexadecimal equivalent. The ASCII characters
representing the hexadecimal characters are used to construct the message.
ASCII mode uses twice as many characters as RTU mode. Additionally, in RTU
mode, message characters must be transmitted in a continuous stream. In
ASCII mode, breaks of up to 1 second can occur between characters.
There are two communication ports available in the 723PLUS. Both ports may
be configured for RS-232, RS-422 or RS-485 communications. If the
communication utilizes an RS-232 link, the distance between devices is limited
to a maximum distance of 15 meters (50 feet). It should be noted that the J3
port can communicate using either ASCII or RTU mode, whereas the J2 port is
only able to communicate using ASCII.
The 723PLUS can be programmed as either a master or slave unit. When
programmed as a slave unit, it responds only after being asked for a set of
parameters. Typically the 723PLUS communicates as a slave with a Modbus
Master device utilizing a separate link to each device. However, if multidropping
is used, one or two 723PLUSs can be connected to one Master device on a
single link.
Woodward
85
Manual 91371
The data is passed between the Master and the 723PLUS in the form of
message frames (see Table 6-2). On any single multidrop link, each slave
address must be unique.
Table 6-2. Modbus Frame Definition
BEGINNING
OF FRAME
:
3-CHAR
DEAD TIME
SLAVE
ADDRESS
2 CHARS
8 BITS
1 CHAR
8 BITS
FUNCTION
CODE
2 CHARS
8 BITS
1 CHAR
8 BITS
DATA
4 BITS DATA
PER CHAR
8 BITS DATA
PER CHAR
ERROR
CHECK CODE
2 CHAR
8 BITS
2 CHAR
16 BITS
END OF
FRAME
CR LF
3 CHAR
DEAD TIME
The function code portion of the message frame tells the addressed slave what
function to perform. Table 6-3 and Figure 6-1 define and list the function codes
supported by the 723PLUS.
Table 6-3. Modbus Function Codes
Code
1
2
3
4
5
6
8
15
16
Description
Read digital outputs
Read digital inputs
Read analog outputs
Read analog inputs
Write single digital output
Write single analog input
Loopback test - returns the query
(sub-function 0 only)
Write digital outputs
Write analog outputs
MODBUS
ADDRESS
0000
FFFF
FUNCTION
CODES
0XXXX
1XXXX
3XXXX
4XXXX
DIGITAL
OUTPUTS
DIGITAL
INPUTS
ANALOG
INPUTS
ANALOG
OUTPUTS
1, 5 & 15
3, 6 & 16
86
Woodward
Manual 91371
Name
Illegal Function
Checksum Error
10
Garbled Message
Meaning
The message function is not an
allowable action
The message start address is not
allowable address
The received message had an
incorrect error check code
The received message could not
be decoded
Name
Illegal Function
Checksum Error
10
Garbled Message
20
Unsolicited Message
21
Function Mismatch
22
23
No Response
Meaning
This exception response received
from a slave
This exception response received
from a slave
The received message had an
incorrect error check code
The received message could not
be decoded
A message was received without
being requested
Received message had a function
code different from the command
Received message had an
address different from the
command
The slave did not respond within
1.5 seconds
Function
Code
Message
Type
1,2,3,4
Query
NUMBER
OF
POINTS
1,2,3,4
Response
SLAVE FUNCTION
ADDRESS
CODE
ANALOG OR DIGITAL
DATA
ERROR
CHECK
5,6
Query
or
Response
SLAVE FUNCTION
DATA
ANALOG OR DIGITAL
ADDRESS
CODE
ADDRESS
VALUE
ERROR
CHECK
15,16
Query
NUMBER
ANALOG OR DIGITAL
SLAVE FUNCTION START
DATA
ADDRESS
CODE
ADDRESS OF POINTS
15,16
Response
NUMBER
SLAVE FUNCTION START
ADDRESS
CODE
ADDRESS OF POINTS
ALL
Response
SLAVE FUNCTION
ADDRESS
CODE
BYTE
COUNT
ERROR
CODE
ERROR
CHECK
ERROR
CHECK
ERROR
CHECK
Woodward
87
ERROR
CHECK
Manual 91371
Typical Value
9600
None
1
Adjustment Range
1200 to 38400
None, Odd, Even
1, 1.5, 2
The Modbus communication ports in the 723PLUS are custom programmed for
each application, and have unique Modbus addresses. The Modbus address
listing consists of Boolean Writes, Boolean Reads, Analog Reads, and Analog
Writes. The Boolean reads and writes are also referred to as input and holding
coils. The analog reads and writes are also referred to as input registers and
holding registers.
All values that can be addressed by Modbus are considered to be discrete and
numeric. The discretes are a 1 bit binary, on or off value and the numerics are
16 bit values. Registers are interpreted by the 723PLUS as signed 16 bit
integers. The maximum number of analogs in a single message is 59 for ASCII
mode and 118 for RTU mode. The maximum number of digitals in a single
message is 944 for ASCII mode and 1888 for RTU mode.
Boolean Writes (Holding Coils)
Holding coils are logical signals that are both readable from and writable to the
723PLUS. An example of a Boolean write value would be raise or lower
commands. A logical true denoted by the value 1 will cause the command listed
in the description to be executed. The 723PLUS control supports function codes
1, 5 and 15. These correspond to reading selected holding coils, writing to a
single holding coil, and writing to a multiple holding coils, respectively.
Boolean Reads (Input Coils)
Input Coils are logical signals that are readable from, but not writable to, the
723PLUS. An example of a Boolean read value would be an alarm indication.
The 1: term in the address identifies an input coil. The 723PLUS supports
Modbus function code 2, which involves reading selected input coils.
Analog Reads (Input Registers)
Input registers are analog values that are readable from, but not writable to, the
723PLUS. An example of an analog read value would be engine speed. The
value of the input registers are stored internal to the control as floating point
numbers representing engineering units (i.e. rpm or Hz). The values that are
transmitted are integer values ranging from -32767 to +32767. Since Modbus
can only handle integers, values that have a decimal point should be multiplied
by a constant before being sent by Modbus. The 723PLUS supports Modbus
function code 4, which involves reading selected input registers.
Analog Writes (Holding Registers)
Holding registers are analog values that are writable to, but not readable from,
the 723PLUS. An example of an analog write value would be a kW load
reference. The value of the holding registers are also stored in the control as
numbers representing engineering units. The 723PLUS supports Modbus
function codes 3, 6 and 16. These correspond to reading selected holding
registers, writing to a single holding register, and writing to multiple holding
registers, respectively.
88
Woodward
Manuall 91371
723PLUS
7
Ge
enerator Co
ontrol for W
rtsil
Chapter 7.
Set Point
P
Program
P
mming
g
Intro
oduction
Due to the diffferences bettween installations, plus system and component
D
to
olerances, th
he 723PLUS control mustt be tuned to
o each system
m for optimum
performance.
This chapter contains
T
c
info
ormation on how
h
to enter control set p
points, using
either a Hand
d Held Progra
ammer or a PC
P Interface, (whicheverr is provided for
th
he application).
An imprroperly calib
brated contrrol could ca
ause an engine overspe
eed or
other da
amage to th
he engine. To
o prevent possible seriious injury from
f
an overrspeeding en
ngine, read this entire p
procedure before
b
starting
the engine.
The 723PLUS
T
S has two typ
pes of tunablle; the Servicce tunable an
nd the Config
gure
tu
unable. The Service
S
tuna
able allow tun
ning while the
e engine is rrunning. The
C
Configure
tun
nable may on
nly be adjuste
ed if the conttrol (and hen
nce the I/O) is
s
shutdown, and therefore, the engine stopped.
s
The System Description
T
D
fo
or each type of 723PLUS
S control will contain a lis
st of
each tunable parameter, with
w its default value and
d range of ad
djustment. A
second list will provide an individual description off each tunable.
Ha
and-Held
d Program
mmer
H
Hand-held
Programm
mer and Menus
M
The Hand-held Programm
T
mer is a hand
d-held compu
uter terminal that gets its
power from th
he 723PLUS Digital Conttrol. The term
minal connects to the RS--422
communicatio
on serial portt on the control.
The programm
T
mer does a power-up
p
sellf-test whene
ever it is plug
gged into the
control. When
n the self-tesst is complete
e, the screen
n displays two
o lines of
nformation. This
T
is inform
mation relating to the appllication. Presssing the 'ID' key
in
changes the display
d
to show the Wood
dward logo with
w the coun
ntry name
(""Woodward (NL)")
(
and ap
pplication na
ame of the syystem. Presss "ID" again for
f the
software part number.
The programm
T
mer screen iss a four-line, back lighted
d LCD displa
ay. The displa
ay
le
ets you look at
a two separrate functions
s or menu ite
ems at the sa
ame time. Us
se the
Up/Down Arrow
A
key to
o toggle betw
ween the two
o displayed ittems (an @
@
in
ndicates the item in the active
a
menu).. Use the BK
KSP and SPA
ACE keys to scroll
th
hrough the display to sho
ow the remainder of a pro
ompt if it is lo
onger than th
he
display screen's 18 characters.
The 723PLUS
T
S Digital Con
ntrol has thre
ee sets of me
enus: the Serrvice menus,, the
C
Configure
me
enus and the Debug menus. The Servvice menus a
allow easy ac
ccess
and tuning wh
hile the engin
ne is running
g. The Config
gure menus m
may only be
entered if the I/O is shutdo
own, and hence the engine stopped. The Debug menu
allows accesss to the GAP
P software.
Woodw
ward
89
723P
PLUS Genera
ator Control for Wrtsill
Manual 91371
Con
nfigure Me
enus
To acccess the Co
onfigure men
nus, the engin
ne must be shutdown.
s
Prress the . keyy.
The display
d
will show, 'To Ena
able CONFIG
GURE Press
s *ENTER*'. Press
P
the
ENTE
ER key and the
t display will
w show, 'To
o Shutdown I//O, Press *E
ENTER*'.
Presss the ENTER
R key and this will allow you
y to get into the Configure menus.
If the engin
ne is running
g during this
s process, it will be shu
utdown due
to the shuttting down of
o the I/O of the
t control.
To move between
n the menus use the
pointss within a me
enu use the
and
key to
o return to th
he menu hea
ader.
a
and
keys. To move thrrough the set
ke
eys,. Once in
n a menu, pre
ess the ESC
Serv
vice Menu
us
To acccess the Se
ervice menuss press the
key. To mo
ove between menus, and
d
to mo
ove through set
s points within menus, follow the instructions ass for the
Confiigure menus. Also to retu
urn to the me
enu header, or
o to leave Service,
S
follow
w
the Configure
C
insttructions.
Debug Menus
s
To acccess the De
ebug first pre
ess
(solid square) afterr which the
key should
d
be prressed. To move
m
between
n category menus
m
use th
he
and
keys, once iin
keys.
the right categoryy move through the GAP blocks by us
sing the
and
Within a GAP block every outtput and tuna
able (*) input can been se
een by using
the
and
keyys.
A Tun
nable (*) can
n be changed
d by using the
e Up or the
Turtle
Rabbitt
Up keys
k
to increa
ase the value
e, and the
Turtle Do
own or
Rabbit
Down
n keys to de
ecrease the value
v
(see also adjusting set points).
To re
eturn to the menu
m
headerr press the
Confiigure instructtions.
key, or to le
eave Service
e, follow the
Adju
usting Sett Points
To ad
djust a set po
oint, use the
increa
ase the value
e, and the
decre
ease the valu
ue. The
turtle up
u or the
turtle dow
wn or
rabbit up and
a
rabbit up keys to
rabbit down keys to
turtle do
the ra
ate of change
e faster than
n the
turrtle up and
own keys.
This is useful during initial sett-up where a value may need
n
to be ch
hanged
signifficantly. Whe
ere necessarry, to select TRUE,
T
use either the
the
rabbit up
p keys, and to select FA
ALSE, use the
e
rabb
bit down keyys.
90
turtle up o
or
turtle down or
W
Woodward
Manuall 91371
723PLUS
7
Ge
enerator Co
ontrol for W
rtsil
To obtain an exact
T
e
value, press the =
= key. Key in
n the required
d figure and press
E
ENTER.
This ma
ay only be done
d
if the fiigure is with
hin 10% of th
he existing
value.
To save set points
T
p
at any time, use the
e SAVE key.. This transfe
ers all new se
et
point values into EEPROM
M memory. The
T EEPROM
M retains all set points when
power is remo
oved from the control.
To prev
vent possible damage to
o the engine
e resulting from
f
improp
per
control settings, make sure yo
ou save the set points before
b
removing
power from
f
the con
ntrol. Failure
e to save the set points
s before
removin
ng power fro
om the conttrol causes tthem to revert to the
previou
usly saved settings.
s
H
Hand-Held
d Programmer Keys
T programm
The
mer keys havve the follow
wing functionss (see Figure
e 7-1):
(left arrow)
(righ
ht arrow)
(up/d
down arrow)
(up arrow)
a
(dow
wn arrow)
(tturtle up)
(tturtle down)
(rrabbit up)
(rrabbit down)
(minu
us)
+ (plus)
(solid
d square)
ID
ESC
SAVE
BKSP
SPACE
ENTER
= (equals)
. (decim
mal)
Woodw
ward
91
Manual 91371
PC Interface
A PC Interface may be provided for tuning parameters, instead of the Hand
Held Programmer. This will consist of the Servlink Server, which acts as the
interface between the PC and the 723PLUS. The J2 port hardware
communication link is configurable for RS-232 or RS-422, and the
communications protocol is the Woodward developed Servlink. The J1 port is
only RS-422.
The Woodward Watch Window can be used to interface with the Servlink
Server, as a means for displaying the Service and Configure tunable/monitors,
with the ability for tuning the parameters. Watch Window also offers the ability
to upload the tunable parameters from the control, into a file, and also to
download the parameters stored in the file, into a control (of the same
type/application).
With each application manual. a list of each of the tunable parameters will be
provided along with a description of each. Also, a listing of each of the tunable
with the default values and the range of adjustment will be included.
The PC Interface should be installed on a PC running a Windows 32 bit
operating system.
92
Woodward
Manual 91371
Watch Window
The Watch Window is a tool for viewing and adjusting the parameters of the
723PLUS Control. An application can be quickly and easily developed by the
user, by assembling a number of tabbed sheets, onto which are dropped, the
parameters that are required for monitoring/adjusting. The Watch Window is
made up of three types of window; Main Window, Servlink Explorer and Servlink
Inspector.
The following is an example of the Watch Window:
Main Window
The Main Window is the application controlling window, and provides the
standard menus for opening/closing/saving files, Cut/Copy/Paste of parameters,
and also for adding/removing/renaming tabbed sheets to the application.
Woodward
93
Manual 91371
Servlink Explorer
The Explorer is used to browse the set of variables available through the
Servlink Server. The Explorer is composed a set of tabbed sheets. Each sheet
is associated with a single control from a Servlink network. The sheets tab is
labeled with the associated controls identifier.
Each sheet contains a tree view. The tree view displays the names of the
categories and blocks in a controls application program in a hierarchical
structure. The names at each level in the tree are listed in alphabetical order.
The Watch Window which is normally supplied will display the Configure and
Service menus only.
Selected variables can be used in Copy and Paste or Drag and Drop operations
in order to add a variable to an Inspector. Variables can be selected using the
mouse (left click) or keyboard (arrow keys). Selecting categories or blocks
selects all of the fields underneath them.
94
Woodward
Manual 91371
Servlink Inspector
The Inspector is used to monitor and edit variables available through the
Servlink Server. The Inspector is composed of a set of tabbed sheets. Each
sheet contains a grid (the grid shown in the following example is reduced - other
fields headers are available to define which control a variable relates to, and if
relevant, which category and block name. Each sheets tab is labeled with a
user-definable name. The user has the ability to add and remove sheets using
menu items and/or tool bar buttons in the Main Window.
An icon to the left of the variable defines whether it is a monitor value, configure
tunable or service tunable (or debug tunable if relevant):
Service Tunable
Monitor Value
Configure Tunable
One or more variables can be selected using the mouse (left click) or keyboard
(arrow keys). If the user wishes to select multiple variables, they can do so by
performing one of these sequences:
Select a variable, hold down the shift key, and arrow up or down until all of
the variables are selected.
Click on a variable, hold down the shift key, and click on the last variable in
the series that the user wishes to select.
Selected variables can be used in Cut, Copy and Paste or Drag and Drop
operations in order to add a variable to an Inspector. If the selected variable is
tunable or configurable the status bar will display the minimum and maximum
value for that variable. If multiple variables are selected, the minimum and
maximum will not be displayed for any of the selected variables.
The Inspector can have its configuration saved and restored. The Inspector can be
closed by using the Main Window or by clicking the standard windows close button.
Woodward
95
Manual 91371
Chapter 8.
Service Options
Product Service Options
If you are experiencing problems with the installation, or unsatisfactory
performance of a Woodward product, the following options are available:
Consult the troubleshooting guide in the manual.
Contact the manufacturer or packager of your system.
Contact the Woodward Full Service Distributor serving your area.
Contact Woodward technical assistance (see How to Contact Woodward
later in this chapter) and discuss your problem. In many cases, your
problem can be resolved over the phone. If not, you can select which
course of action to pursue based on the available services listed in this
chapter.
OEM and Packager Support: Many Woodward controls and control devices are
installed into the equipment system and programmed by an Original Equipment
Manufacturer (OEM) or Equipment Packager at their factory. In some cases, the
programming is password-protected by the OEM or packager, and they are the
best source for product service and support. Warranty service for Woodward
products shipped with an equipment system should also be handled through the
OEM or Packager. Please review your equipment system documentation for
details.
Woodward Business Partner Support: Woodward works with and supports a
global network of independent business partners whose mission is to serve the
users of Woodward controls, as described here:
A Full Service Distributor has the primary responsibility for sales, service,
system integration solutions, technical desk support, and aftermarket
marketing of standard Woodward products within a specific geographic area
and market segment.
96
Woodward
Manual 91371
Woodward
97
Manual 91371
Packing a Control
Use the following materials when returning a complete control:
packing materials that will not damage the surface of the unit;
a strong tape around the outside of the carton for increased strength.
To prevent damage to electronic components caused by improper
handling, read and observe the precautions in Woodward manual
82715, Guide for Handling and Protection of Electronic Controls,
Printed Circuit Boards, and Modules.
Replacement Parts
When ordering replacement parts for controls, include the following information:
Engineering Services
Woodward offers various Engineering Services for our products. For these services,
you can contact us by telephone, by email, or through the Woodward website.
Technical Support
Product Training
Field Service
Technical Support is available from your equipment system supplier, your local
Full-Service Distributor, or from many of Woodwards worldwide locations,
depending upon the product and application. This service can assist you with
technical questions or problem solving during the normal business hours of the
Woodward location you contact. Emergency assistance is also available during
non-business hours by phoning Woodward and stating the urgency of your
problem.
Product Training is available as standard classes at many of our worldwide
locations. We also offer customized classes, which can be tailored to your
needs and can be held at one of our locations or at your site. This training,
conducted by experienced personnel, will assure that you will be able to
maintain system reliability and availability.
Field Service engineering on-site support is available, depending on the
product and location, from many of our worldwide locations or from one of our
Full-Service Distributors. The field engineers are experienced both on
Woodward products as well as on much of the non-Woodward equipment with
which our products interface.
For information on these services, please contact us via telephone, email us, or
use our website: www.woodward.com/support.
98
Woodward
Manual 91371
Engine Systems
Turbine Systems
Facility
Phone Number
Brazil
+55 (19) 3708 4800
China
+86 (512) 6762 6727
Germany:
Kempen --- +49 (0) 21 52 14 51
Stuttgart ----- +49 (711) 78954-0
India
+91 (129) 4097100
Japan
+81 (43) 213-2191
Korea
+82 (51) 636-7080
Poland
+48 12 295 13 00
United States ---- +1 (970) 482-5811
Facility
Phone Number
Brazil
+55 (19) 3708 4800
China
+86 (512) 6762 6727
Germany:
Stuttgart ----- +49 (711) 78954-0
India
+91 (129) 4097100
Japan
+81 (43) 213-2191
Korea
+82 (51) 636-7080
The Netherlands - +31 (23) 5661111
United States ---- +1 (970) 482-5811
Facility
Phone Number
Brazil
+55 (19) 3708 4800
China
+86 (512) 6762 6727
India
+91 (129) 4097100
Japan
+81 (43) 213-2191
Korea
+82 (51) 636-7080
The Netherlands - +31 (23) 5661111
Poland
+48 12 295 13 00
United States ---- +1 (970) 482-5811
You can also contact the Woodward Customer Service Department or consult our
worldwide directory (www.woodward.com/support/directory.cfm) for the name
of your nearest Woodward distributor or service facility.
Technical Assistance
If you need to telephone for technical assistance, you will need to provide the following information.
Please write it down here before phoning:
Your Name
Site Location
Phone Number
Fax Number
Engine/Turbine Model Number
Manufacturer
Number of Cylinders (if applicable)
Type of Fuel (gas, gaseous, steam, etc)
Rating
Application
Control/Governor #1
Woodward Part Number & Rev. Letter
Control Description or Governor Type
Serial Number
Control/Governor #2
Woodward Part Number & Rev. Letter
Control Description or Governor Type
Serial Number
Control/Governor #3
Woodward Part Number & Rev. Letter
Control Description or Governor Type
Serial Number
If you have an electronic or programmable control, please have the adjustment setting positions or
the menu settings written down and with you at the time of the call.
Woodward
99
100
Manual 91371
Woodward
Activation of kickdown if the generator or grid breaker is opened. This Woodward made for the
Diamond / Sapphire Princess special software.
Individual engine running parameters communication over LON for service purposes. As in
propulsion control (other engine speed, load, etc.)
The adjustable range for the parameters INC/DEC RATE #1 (rpm/s) and INC/DEC RATE #2
(rpm/sec) are changed from 02000 rpm/s into 050 rpm/s.
Revision B documents the changes as implemented in the 5413-8520 Rev C software.
Removal of all not allowed special characters from GAP software blocks
All functions for discrete inputs #7 and #8 are using multiplexers now, allowing simple addition
of new functions.
New discrete input contact Use Fuel2 added, plus switchable Start Fuel2 Limiter.
Revision "C" changes:
Addition of a "PID Freeze" functionThis function can be enabled to suppress any transient
effects on the speed reference, PID control, and actuator output, when switching from Droop
to Isochronous and vice versa.