PN 16 DN 25 - 125
Water 150 C
Pneumatic spring
Closes at increasing pressure at the outlet
R8
Advantages
Setting of outlet pressure from 0 to 16 bar without
any spring change.
High accuracy.
Low noise operation.
Very long life of diaphragm, because it always works
with low differential pressure of approx. 20 kPa.
Maximal security. In case of diaphragm rupture the
auxiliary spring instantly tightly closes the valve.
Wrong adjustment of safety valve is not possible if
connected to the same pressure vessel as reducing
valve.
Function
The regulator consists of a valve (1), an actuator (3) and a
pressure vessel (8). The fluid pressure at valve's outlet acts
through the impulse pipe (2) to the top side of the diaphragm (5),
and attempts to close the valve together with the force of the
auxiliary spring (4). The pressure of compressed air (9) in the
pressure vessel acts through the connection pipe (6) to the
bottom side of diaphragm, and attempts to open the valve. As
long as the forces on the diaphragm are balanced, the valve's
plug stands still. If the fluid pressure increases, the valve closes
until the new balance is reached. In case of diaphragm rupture,
pressure of fluid on top side and compressed air on the bottom
side of the diaphragm are equalized, and auxiliary spring
instantly tightly closes the valve. The force of the auxiliary spring
corresponds to the pressure of approx. 20 kPa.
Installation
Install the valve into a horizontal pipeline with the actuator body
below. The direction of flow is shown with an arrow on the valve
body. Installation of a strainer in front of the valve is
recommended. At the first filling, vent actuator body a couple of
times by vent screw (12). If the regulated fluid is steam, or the
temperature exceeds 130 C, a cooling vessel (OH 150) must
be installed in the impulse pipe (2). Prior to operation, fill the
cooling vessel with cold water and vent it. For impulse pipe (2)
and connection pipe (6) use copper pipe 10x1.
TA-Regulator Orlika 13, Breice, Slovenia Phone: +386 7 496 14 17 Fax: +386 7 496 20 40 www.ta-regulator.com
2/06
R8
Specifications
Nominal pressure
PN 16
Maximal differential pressure in valve
16 bar
Maximal pressure at outlet
16 bar
Maximal water temperature
150 C
Accuracy approx.
kPa
Flanges
DIN 2501
Valve body
PN 16
cast iron (GG-25)
PN 16
ductile iron (GGG-40.3)
Actuator body
cast iron (GG-25)
Diaphragm
NBR
Valve seat
stainless steel
Valve plug
stainless steel with EPDM insert
Dimensions
Nominal size
KVS
Length
Height
Height
Diameter
Diameter
Weight
DN
L
H
h
D
F
M
mm
m3/h
mm
mm
mm
mm
mm
kg
25
9
160
435
80
330
115
38
32
17
180
450
95
330
140
39
40
19
200
450
95
330
150
40
50
32
230
460
105
330
165
46
65
50
290
545
125
375
185
68
80
80
310
555
135
375
200
78
100
110
350
600
165
375
220
98
125
120
400
610
175
375
250
106
TA-Regulator Orlika 13, Breice, Slovenia Phone: +386 7 496 14 17 Fax: +386 7 496 20 40 www.taregulator.com