Design Criteria
Environmental (Atmospheric, Geologic etc.) and Structural requirements apply to 230kV, 345kV,
and 500kV conductors, structures, and equipment; both for Lines and Substations. Electrical
requirements are Voltage Specific.
Line design
Flood Plain
Substations General
AC Station Service
DC supply
Ground grid resistance
3000A
40kA (X/R 25) DC time constant 60ms
450kV to 550kV 500kV nominal
(typical normal voltages range from 515kV to 550kV)
300uV @1MHz
1800kV
1550kV
1050kV
318kV MCOV Station Class (396kV duty cycle)
2.2 (i.e. closing resistors required & no restrikes, or line end
arresters used to clamp switching overvoltages.)
Effectively Grounded Neutral (always)
1/100years Keraunic level =40
1/40 years/breaker position
300uV @1MHz
990kV
1200kV
2145kV
1/100 miles (160km) per year Keraunic level=40
1/100 miles (160km) per year
300uV @1MHz
700kV
840kV
1440kV
1/100 miles (160km) per year Keraunic level=40
1/100 miles (160km) per year