CONTENTS
1. What is ATW heat pump?.......................................................2
2. Heat pump unit_General information ...................................4
3. System design ......................................................................15
4. Interface (I/F) ........................................................................23
5. Flow temp. controller (FTC) .................................................55
6. Requirements........................................................................90
7. System example ...................................................................91
1-2-2. Defrost
Note: Occasionally, vapor that is made by the defrost operation may seem as if smoke come up from the outdoor unit.
5
1.7
20
20.9
25
31.4
30
43.8
10
15
20
25
30
5
1.0
20
12.5
25
18.8
30
26.2
10
15
20
25
30
15
1.3
60
19.3
75
29.9
90
42.8
30
45
60
75
90
2-1. Line-up
2-1-1. Outdoor unit for Air to water
(1) Packaged type: The Air to Water outdoor unit with a plate HEX (refrigerant-water) inside
Connectable models
Capacity
( HP )
2
3
4
5
Packaged models
1-phase
3-phase
PUHZ-W50VHA
PUHZ-W85VHA
ZUBADAN-Packaged models
1-phase
3-phase
PUHZ-HW112YHA
PUHZ-HW140VHA
PUHZ-HW140YHA
(2) Split type: The standard outdoor unit without a plate HEX (refrigerant-water) inside
Connectable models
Capacity
( HP )
2.5
3
4
5
6
PUHZ-RP71VHA3#1
PUHZ-RP100VHA3#1
PUHZ-RP100YHA3#1
PUHZ-RP125VHA2#2
PUHZ-RP125YHA2#2
PUHZ-RP140VHA2#2
PUHZ-RP140YHA2#2
PUHZ-HRP71VHA(2)
PUHZ-HRP100VHA(2)
PUHZ-HRP100YHA(2)
PUHZ-HRP125YHA(2)
* Outdoor units (PUHZ-RP or PUHZ-P) other than the above-mentioned become possible by connecting TH5 ( 2-phase refrigerant temp. thermistor ) with the interface only for Air to Air use.
35
VHA3
VA
35
VHA3
50
VHA3
VA
50
VHA3
60
VHA3
VA
60
VHA3
PAC-IF011B-E / PAC-IF010-E
71
100
125
140
VHA(2) V/YHA(2) YHA(2)
VHA3
V/YHA3 V/YHA2 V/YHA2
VHA2
VHA2
VHA2
VA
V/YHA
V/YHA
YHA
YHA
71
100
125
140
VHA
V(Y)HA
YHA
VHA3
V/YHA3 V/YHA2 V/YHA2
200
YHA2
YHA
MYA
200
YHA2
250
YHA2
YHA
MYA
250
YHA2
MANUAL STEP MODE is New function of INTER FACE (Fixed capacity = Compressor frequency (Hz) fixed mode) .
2 Phase (Gas/Liquid) pipe thermistor is required (TH5).
Also, Interface P.C.B. SW2-6 need to be set "OFF (No LEV self control mode)" .
<Old models : The models that are not described in the table above.>
*1: With(Auto-mode)+(SW2-6 is OFF)+(2phase thermistor), all A-control outdoor units are able to connect to PAC-IF010/
011B-E only for Air to Air use.
*2: With(Manual-mode)+(SW2-6 is OFF)+(2phase thermistor), from following RP type outdoor units are able to connect to
PAC-IF010/011B-E only for Air to Air use.
PUHZ-RP35V, 50V, 60V, 71V,100V/Y,125V/Y,140V/YHA2
PUHZ-RP200Y, 250YHA
Service
manual
Parts catalog
I/F
FTC
OCH439
OCB439
OC374
OC374
OCH425
OCB425
Type
cased
PCB only
cased
PCB only
2-2. Data
2-2-1. Packaged type
Refer to each model's service manual.
2-2-2. Split
[1] Specifications(Reference data(connect to plate heat exchanger))
Rating conditions
Nominal operating condition
Heating (A2/W35)
Outside air temperature (Dry-bulb)
Outside air temperature (Wet-bulb)
Water temperature (inlet/outlet)
Heating (A7/W35)
Outside air temperature (Dry-bulb)
Outside air temperature (Wet-bulb)
Water temperature (inlet/outlet)
Heating (A7/W45)
Outside air temperature (Dry-bulb)
Outside air temperature (Wet-bulb)
Water temperature (inlet/outlet)
+2:
+1:
+30/+35:
+7:
+6:
+30/+35:
+7:
+6:
+40/+45:
Model name
PAC-IF011B-E
PAC-IF010-E
PAC-IF021B-E
PAC-IF020-E
Parts catalog
OCB427
OCB427
PUHZ-HRP71VHA2
Power supply
(Phase, Voltage, Frequency)
Breaker size
Nominal water flow
Capacity
Heating
COP
(A2/W35)
Power input
Capacity
Heating
COP
(A7/W35)
Power input
Capacity
Heating
COP
(A7/W45)
Power input
A: 50 mm
B: 466 mm
32
22.9
8.00
3.24
2.47
8.00
4.40
1.82
8.00
3.24
2.47
kW
kW
Model name
Power supply
(Phase, Voltage, Frequency)
40 / 16
32.1
11.20
3.02
3.71
11.20
4.26
2.63
11.20
3.24
3.46
11.20
2.40
4.67
kW
kW
kW
Outdoor unit
Model name
Power supply
(Phase, Voltage, Frequency)
Breaker size
Nominal water flow
Heating
Capacity
COP
(A2/W35)
Power input
Heating
Capacity
COP
(A7/W35)
Power input
Heating
Capacity
COP
(A7/W45)
Power input
A
L/min
kW
kW
:
:
Water IN
60
55
50
45
40
-25
-20
-15
-10
-5
10
PUHZ-HRP125YHA2
3[, 400V, 50Hz
A
Ref.OUT
(Heating)
16
40.1
14.00
2.70
5.19
14.00
4.22
3.32
14.00
3.20
4.38
kW
PUHZ-HRP100VHA2 /
PUHZ-HRP100YHA2
Water OUT
Ref.IN
(Heating)
W: 112 mm
H: 526 mm
D: 130 mm
50 plates
Outdoor unit
Breaker size
Nominal water flow
Heating
Capacity
COP
(A2/W35)
Power input
Heating
Capacity
COP
(A7/W35)
Power input
Heating
Capacity
COP
(A7/W45)
Power input
Heating
Capacity
COP
(A7/W55)
Power input
-25 ~ +35
-5 ~ +46
PUHZ-RP60VHA3#1
Power supply
(Phase, Voltage, Frequency)
Breaker size
Nominal water flow
Capacity
Heating
COP
(A2/W35)
Power input
Capacity
Heating
COP
(A7/W35)
Power input
Capacity
Heating
COP
(A7/W45)
Power input
A
L/min
kW
A: 50 mm
B: 466 mm
25
20.1
6.80
2.94
2.31
7.00
4.29
1.63
7.00
3.27
2.14
kW
kW
kW
kW
kW
Model name
W:112 mm
H: 526 mm
D: 82 mm
30 plates
kW
kW
kW
A
Ref.OUT
(Heating)
Water IN
25
22.9
7.50
2.92
2.57
8.00
4.21
1.90
8.00
3.20
2.50
kW
kW
Water OUT
Ref.IN
(Heating)
PUHZ-RP71VHA3#1
Power supply
(Phase, Voltage, Frequency)
Heating
Cooling
Outdoor unit
Breaker size
Nominal water flow
Capacity
Heating
COP
(A2/W35)
Power input
Capacity
Heating
COP
(A7/W35)
Power input
Capacity
Heating
COP
(A7/W45)
Power input
60
55
50
45
-11 ~ +35
-5 ~ +46
-10
-5
10
Outdoor unit
PUHZ-RP100VHA3#1 /
PUHZ-RP100YHA3#1
Model name
Power supply
(Phase, Voltage, Frequency)
Breaker size
Nominal water flow
Capacity
Heating
COP
(A2/W35)
Power input
Capacity
Heating
COP
(A7/W35)
Power input
Capacity
Heating
COP
(A7/W45)
Power input
A: 50 mm
B: 466 mm
32 / 16
32.1
10.50
2.90
3.62
11.20
4.21
2.66
11.20
3.20
3.50
kW
kW
kW
kW
kW
65
32/16
40.1
11.50
2.70
4.26
14.00
4.15
3.37
14.00
3.10
4.51
kW
kW
kW
kW
kW
Outdoor unit
Power supply
(Phase, Voltage, Frequency)
Breaker size
Nominal water flow
Capacity
Heating
COP
(A2/W35)
Power input
Capacity
Heating
COP
(A7/W35)
Power input
Capacity
Heating
COP
(A7/W45)
Power input
kW
kW
kW
:
:
50
45
-15
-10
-5
10
40/16
45.9
11.70
2.69
4.35
16.00
3.90
4.10
16.00
3.00
5.34
kW
kW
55
60
40
-20
PUHZ-RP140VHA2#2 /
PUHZ-RP140YHA2#2
Model name
Water IN
A
Ref.OUT
(Heating)
Breaker size
Nominal water flow
Capacity
Heating
COP
(A2/W35)
Power input
Capacity
Heating
COP
(A7/W35)
Power input
Capacity
Heating
COP
(A7/W45)
Power input
PUHZ-RP125VHA2#2 /
PUHZ-RP125YHA2#2
Power supply
(Phase, Voltage, Frequency)
Water OUT
Ref.IN
(Heating)
W:112 mm
H: 526 mm
D: 130 mm
50 plates
Outdoor unit
Model name
-20 ~ +35
-5 ~ +46
Capacity
Cooling
(A35/W7)
7,100
Input
kW
2.20
Outdoor
Water
conditions conditions
Refrigerant circuit
Mode
Outdoor unit
Heating
(A7/W35)
8,000
1.82
3.67
2.61
Cooling
(A35/W7)
12,500
Heating
(A7/W35)
14,000
4.80
3.50
PUHZ-HRP100VHA2/
PUHZ-HRP100YHA2
PUHZ-HRP125YHA2
1, 50
1/3, 50
3, 50
230
230 / 400
400
PUHZ-HRP71VHA2
Phase, Hz
ACH50-50 plates
Cooling
Heating
(A35/W7)
(A7/W35)
10,000
11,200
Voltage
Current
9.9
8.2
16.5/5.6
11.7/4.0
7.3
5.3
Discharge pressure
MPa
2.4
2.0
2.6
2.1
2.8
2.3
Suction pressure
MPa
0.8
0.7
0.8
0.7
0.8
0.7
Discharge temperature
70
60
78
63
84
70
Condensing temperature
42
35
46
36
47
39
Suction temperature
12
11
10
Evaporating temperature
55
60
65
33
31
30
L/min
20.4
22.9
28.7
34.4
35.8
40.1
35
35
35
D.B.
35
35
35
W.B.
24
24
24
Flow volume
Outlet water temperature
The unit of pressure has been changed to MPa based on international SI system.
The conversion factor is : 1(MPa)=10.2(kgf/F)
Capacity
Cooling
(A35/W7)
6,000
Input
kW
2.31
Outdoor
Water
conditions conditions
Refrigerant circuit
Mode
Outdoor unit
ACH50-30 plates
Heating
Cooling
(A7/W35) (A35/W7)
7,000
6,600
1.63
Heating
(A7/W35)
8,000
2.59
1.90
ACH50-50 plates
Cooling
Heating
(A35/W7)
(A7/W35)
9,100
11,200
3.31
2.66
PUHZ-RP60VHA3#1
PUHZ-RP71VHA3#1
PUHZ-RP100VHA3#1/
PUHZ-RP100YHA3#1
1, 50
1, 50
1/3, 50
230
230
230 / 400
Phase, Hz
Voltage
Current
10.3
7.2
11.4
8.4
14.5 / 5.1
11.8 / 4.1
Discharge pressure
MPa
2.7
2.1
2.7
2.2
2.6
2.1
Suction pressure
MPa
0.8
0.7
0.8
0.7
0.8
0.7
Discharge temperature
70
65
70
66
74
65
Condensing temperature
45
36
45
36
44
36
Suction temperature
Evaporating temperature
56
57
58
34
33
35
L/min
17.2
20.1
18.9
22.9
26.1
32.1
35
35
35
D.B.
35
35
35
W.B.
24
24
24
Flow volume
Outlet water temperature
The unit of pressure has been changed to MPa based on international SI system.
The conversion factor is : 1(MPa)=10.2(kgf/F)
10
Outdoor
Water
conditions conditions
Refrigerant circuit
Electrical
circuit
Total
Mode
Capacity
Input
W
kW
Outdoor unit
Phase, Hz
Voltage
Current
Discharge pressure
Suction pressure
Discharge temperature
Condensing temperature
Suction temperature
Evaporating temperature
Evaporator inlet temperature
Evaporator outlet temperature
Condenser inlet temperature
Condenser outlet temperature
Flow volume
V
A
MPa
MPa
:
:
:
:
:
:
:
:
Cooling
(A35/W7)
12,000
5.10
ACH50-50 plates
Heating
Cooling
(A7/W35) (A35/W7)
14,000
12,500
3.37
5.38
Heating
(A7/W35)
16,000
4.10
PUHZ-RP125VHA2#2/
PUHZ-RP125YHA2#2
PUHZ-RP140VHA2#2/
PUHZ-RP140YHA2#2
1 / 3, 50
230 / 400
22.4 / 7.6 15.0 / 5.2
2.8
2.1
0.7
0.7
80
69
46
36
3
4
5
-1
6
63
35
1 / 3, 50
230 / 400
23.6 / 8.1 18.2 / 6.2
2.8
2.2
0.7
0.7
81
67
46
36
3
1
5
-1
6
61
34
L/min
34.4
40.1
35.8
45.9
35
35
D.B.
35
35
W.B.
24
24
The unit of pressure has been changed to MPa based on international SI system.
The conversion factor is : 1(MPa)=10.2(kgf/F)
11
100
Heating
95
Cooling 60 models
90
Cooling 71 model
85
Cooling 100 model
80
75
Note: The permitted pipe length is up to 55m for RP 60, 71 model.
The permitted pipe length is up to 80m for HRP71 and 100~ 140 model.
70
10
15
20
25
30
35
40
45
50
55
60
65
70
75
80
Thermistor TH1
(Outlet water)
Refrigerant
GAS pipe
connection
(5/8 inch)
Thermistor
TH6
(Outdoor
2-phase pipe)
Solenoid valve
(Four-way valve)
Ball valve
Strainer
#50
Charge plug
(High pressure)
Charge plug
(Low pressure)
Muffler
Water OUT
Low pressure
switch 63L
Plate HEX
Thermistor TH3
(Outdoor pipe)
High pressure
switch 63H
Thermistor
TH32
(Outdoor pipe)
Strainer
#100
Strainer
#100
Thermistor TH2
(Liquid pipe)
Strainer
#100
Stop valve
(with service port)
Thermistor TH33
(Outdoor pipe)
Strainer
#100
Compressor
Linear
expansion valve C
Bypass
valve
Strainer
#100
Power
receiver
Refrigerant
LIQUID pipe
connection
(3/8 inch)
Distributor
Thermistor TH4
(Discharge)
Linear
expansion valve B
Water IN
Thermistor TH7
(Outdoor)
Injection port
Replace
filter
Restrictor
Strainer
valve
#100
12
[6] Notification to design/select HEX (Refrigerant - Water) Warranty for SPILIT solution
Specifications of AHU and compatibility with regulations must be confirmed by your company.
Selection of an apporopriate AHU (with appropriate specifications to match those of units
connected to the AHU such as configuration, dimension, life-span, vibration, noise level,
or features) must be made by your company.
Mitsubishi Electric shall not be liable for any damage to the entire system or the AHU main
body caused by connected AHU with wrong specification or wrong usage of AHU.
Mitsubishi Electric shall not be liable for any damage to the outdoor units caused by AHU damage.
( AHU : hydro box or refrigerant - water HEX )
Heat exchanger
(1) Withstanding pressure
Designed pressure of outdoor unit is 4.15 MPa. Following must be satisfied for burst pressure of connecting application.
Burst pressure : More than 12.45 MPa (3 times more than designed pressure)
(2) Performance
Secure the heat exchanger capacity which meets the following conditions. If the conditions are not met, it may result in
malfunction caused by the protection operation or the outdoor unit may be turned off due to the operation of protection
system.
1. Evaporate temperature is more than 4: in max. frequency operation under *1 the cooling rated conditions.
2. In case of hot water supply, condense temperature is less than 58: in max. frequency operation with the outside temperature 7:D.B./6:W.B.
*1. Outdoor: 35:D.B./24:W.B.
(3) Heat exchanger internal capacity
Heat exchanger internal capacity must be within the capacity range shown below. If the heat exchanger below the minimum capacity is connected, it may result in the back flow of liquid or the failure of the compressor.
If the heat exchanger above the maximum capacity is connected, it may result in the deficiency in performance due to lack
of refrigerant or overheating of the compressor.
Minimum capacity : 10 Model capacity [J] / Maximum capacity : 30 Model capacity [J]
e.g. When connecting to PUHZ-HRP100 VHA2
Minimum capacity : 10 100 =1000 J
Maximum capacity : 30 100 =3000 J
Model capacity
60(2.5HP)
71(3HP)
100(4HP)
125(5HP)
140(6HP)
1800
2130
3000
3750
4200
600
710
1000
1250
1400
13
The water velocity in pipes should be kept within certain limits of material to avoid erosion,corrosion and excessive
noise generation.
Be aware, and take care of , that local velocities in small pipes, bends and similar obstructions can exceed the values
of previous page.
e.g.) Copper : 1.5m/s
Warning
Use clean enough water which meets water quality standards. The deterioration of water quality may result in the system breakdown or the water leakage.
Never use anything other than water as a medium. It may cause a fire or an explosion.
Do not use heated or cooled water that is produced by the air to water heat pump directly for drinking or cooking.
There is a risk to damage your health. There is also a risk that installing the water heat exchanger may corrode if the
necessary water quality for air to water heat pump system cannot be maintained. If you wish to use the heated or
cooled water from the heated pump for these purposes, take measure such as to the second heat exchanger within
the water piping system.
Reference data
Required specification and performance of Plate Heat Exchanger.
Required specification
Refrigerant side
Water side
Burst pressure
Frozen performance
Heat cycle
Endurance pressure
Refrigerant type
R410A
Normal (designed) pressure
4.15MPa
Operating temperature
-20~100:
Refrigerant type
Clean water
Normal (designed) pressure
1.5MPa
Operating temperature
-20~90: (No freezing)
12.45MPa (4.15MPa 3) or more
Satisfy an initial performance since 5 times or more of deep freezing.
70,000 times or moreTemperature difference: about 50K
72,000 times or morePressure difference: 3.3MPa (0 3.3MPa)
Required performance
< For 2.5~3 HP >
Required performance of Plate Heat Exchanger
Inlet temperature
Refrigerant side Condensing temperature
(R410A)
Subcool
Max. pressure loss
Inlet temperature
Outlet temperature
Water side
Water flow volume
Max. pressure loss
kW
degC
degC
degC
kPa
degC
degC
L/min
kPa
9.0
75
39.5
2
50
30
35
25.8
50
9.0
100
63.5
2
50
55
60
25.8
50
* For heating mode, used at counter flow direction between refrigerant flow and water one.
< For 4~6 HP >
Required performance of Plate Heat Exchanger
Inlet temperature
Refrigerant side Condensing temperature
(R410A)
Subcool
Max. pressure loss
Inlet temperature
Outlet temperature
Water side
Water flow volume
Max. pressure loss
kW
degC
degC
degC
kPa
degC
degC
L/min
kPa
14.0
75
39.5
2
50
30
35
40.1
50
14.0
100
63.5
2
50
55
60
40.1
50
* For heating mode, used at counter flow direction between refrigerant flow and water one.
14
System design
by digital/analog signals
simple/basic/analog temp.
Capacity control
For
Manufacturer
Individual installer
Manufacturer
Individual installer
Manufacturer
Individual installer
Manufacturer
Individual installer
Local controller
Air to Air
I/F
Local controller
Air to Water
FTC
Model name
PAC-IF010-E *
PAC-IF011B-E
PAC-IF010-E *
PAC-IF011B-E
PAC-IF010-E *
PAC-IF011B-E
PAC-IF020-E *
PAC-IF021B-E
Type
PCB only
Cased
PCB only
Cased
PCB only
Cased
PCB only
Cased with R/C
STEP I/F
FTC
Connected object
PAR-21MAA
(Standard)
PAR-W21MAA
PAR-20MAA
(Old )
(Standard)
I/F
FTC
I/F
FTC
I/F
FTC
Connectability
OK
NG (Continue to indicate PLEASE WAIT)
NG (Continue to indicate PLEASE WAIT)
OK
NG (Continue to indicate PLEASE WAIT)
NG (Continue to indicate PLEASE WAIT)
start
IF
Variable capacity
request signals for
Heat Pump is
calculated...
capacity
signals
protocol is...
By local
controller
(your side)
Analog
(0-10v/4-20mA)
Your system is
ANALOG STEP
SYSTEM
(IF)
digital step
(non-voltage contact)
Your system is
DIGITAL STEP
SYSTEM
(IF)
ANALOG STEP
SYSTEM
DIGITAL STEP
SYSTEM
By Non-voltage
Contact signals
By Non-voltage
Contact signals
IF PCB
ON/OF
System controller
(locally supplied)
Operation
mode
-Heating
-Cooling
Capacity
steps
Remote
By Non-voltage
Contact signals
for maintenance
- to check error code
IF PCB
ON/OF
Operation
mode
-Heating
-Cooling
Remote
System
controller
(locally supplied)
End user interface
Capacity
steps
By Analog signal
4-20mA / 1-5V / 0-10V
By our FTC
15
By our FTC
FTC
Heat Pump switch ON/OFF
and the operation mode
change is done
By remote controller
Your system is
SIMPLE SYSTEM.
(FTC)
By remote controller
Your system is
BASIC SYSTEM.
(FTC)
SIMPLE SYSTEM
BASIC SYSTEM
ON/OFF
Operation mode
- Heating
- Heating ECO
- Hot water
- Anti freeze
- Cooling
ON/OFF
By Non-voltage
Contact signals
System controller
(locally supplied)
ON/OFF
Operation mode
- Heating +
- Cooling
System controller
(locally supplied)
End user interface
Operation mode
Target flow temp.
Target flow temp.
Remote controller
Remote controller
Remote controller
End user interface
To preset
- target temp. for each mode
- target temp. parameters
To preset
- analog signal parameters
16
ATA
application
start
IF
Variable capacity
request signals for
Heat Pump is
calculated...
By local
controller
(your side)
capacity
signals
protocol is...
Analog
(0-10v/4-20mA)
digital step
(non-voltage contact)
Your system is
ANALOG STEP
SYSTEM
(IF)
Your system is
DIGITAL STEP
SYSTEM
(IF)
By our IF
Your system is
AUTO STEP
SYSTEM
(IF)
By Non-voltage
Contact signals
IF PCB
IF
PCB
ON/OF
Operation
mode
-Heating
-Cooling
ON/OFF
Operation mode
Target retern air temp.
Remote controller
Remote
controller
for
maintenance
- to check
error code
Capacity
steps
By Non-voltage
Contact signals
17
System
controller
(locally
suppliied)
IF
PCB
ON/OF
Operation
mode
-Heating
-Cooling
End user
interface
Remote
controller
For
maintenance
purpose
- analog signal
System
controller
(locally
suppliied)
End user
interface
Capacity
steps
By Analog
signal
4-20mA / 1-5V / 0-10V
18
TB141
1-2
3-4
5-6
7-8
9-10
11-12
13-14
TB142
10-12
(COM-IN6)
OFF
OFF
ON
ON
OFF
OFF
ON
ON
OFF
TB142
10-11
(COM-IN5)
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
table 3
OFF
ON
ON
ON
ON
OFF
OFF
OFF
OFF
TB142
10-13
(COM-IN7)
ON
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
DSA
SW3
TB6
TB6
0%
{
TB142
Step1
Step4
Step7
AUTO
Auto
Step7
Step4
Step1
OFF
10
11
12
13
14
[ON]
[OFF]
At site
100%
80%
70%
50%
30%
20%
10%
TypeB
Remark
(Comp. ON)
(Defrosting)
(Cooling)
(Heating)
ON
S1 S2 S3
L N
I/F
Auto
Step7
Step6
Step5
Step4
Step3
Step2
Step1
OFF
S1 S2 S3
L N
At site
[ON]
[OFF]
TypeA
FUSE
ZNR01
CNS2
(RED) 1 2
*2 Remove the
short-circuited connector
CNS2.
ON
Error
ON
ON
ON
ON
TB141
ON
4bit8 switch
OFF~AUTO
TB142
10-14
(COM-IN8)
Normal
Cooling
OFF
OFF
Normal
OFF(Comp. OFF)
OFF
OFF
OFF
OFF
1 2 3 4 5 6 7 8 9 10 11 12 13 14
X1 X2 X3 X4 X5 X6
Operation Output
Error Output
Comp. Output
Defrost Output
Mode(Cool)
Output
Mode(Heat)
Output
Item
1-2 (IN1)
3-4 (IN2)
X1
X2
X3
X4
X5
X6
ZNR02
Refer to table 1.
(External Output)
TB141
DC311~
339V
LED1
RECTIFICATION
2 4 6 8 10 12 14
1 3 5 7 9 11 13
(External Input)
SW2
SW1
TB142
Item
(OUT1)
(OUT2)
(OUT3)
(OUT4)
(OUT5)
(OUT6)
(OUT7)
LED4
SW6
OFF/ON
1
2
LED2
LED3 LED5
2 4 6 8 10 12 14
1 3 5 7 9 11 13
TB142
table 2
TB142
TB61
1 TB62
2
3 +
4
5
6
1 2 3 4 5 6 7 8 9 10 11 12 13 14
table 1
At site
I/F
4-20mA/1-5V/0-10V
Refer to table 2, 3.
TH5
Adjustable resistor
TH2
1
2
3
4
5
6
POWER SUPPLY
~/N
0%
OFF
Auto mode
Fixed capacity
(Hz fixed)
mode
TB142
10
11
12
13
14
I/F
100%
50%
10%
Remark
TO OUTDOOR UNIT
*1(Fig.1)
TO OUTDOOR UNIT
TH1
Interface controller
NAME
OFF
OFF
ON
ON
ON
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
OFF
OFF
OFF
OFF
OFF
ON
ON
OFF
OFF
Input
TypeA(4bit-8 setting)
TypeB(1bit-1 setting)
4-20mA
1-5V
0-10V
0-10k
No input(Auto mode)
OFF
OFF
ON
ON
OFF
ON
OFF
ON
Details
[Cooling]FIX
[Heating]FIX
External input(Depending on TB142-3,4)
OFF
ON
ON
OFF
ON
ON
ON
ON
OFF
OFF
OFF
OFF
SW2-5
28 C FIX
26 C FIX
24 C FIX
22 C FIX
20 C FIX
Details
Connect TH5
OFF
ON
Details
SW2-6
ON
OFF
OFF
ON
ON
ON
OFF
OFF
SW2-4
ON
OFF
ON
OFF
SW2-3
SW2-2
SW2-1
ON
ON
ON
OFF
ON
ON
OFF
OFF
ON
ON
OFF
OFF
INTERFACE CONTROLLER
TB6
TERMINAL BLOCK(INTERFACE/OUTDOOR CONNECTING LINE)
TB141
TERMINAL BLOCK (External Output)
TB142
TERMINAL BLOCK (External Input REMOTE SWITCH)
TB62
TERMINAL BLOCK (External Input)
TB61
THERMISTOR(TARGET, PIPE)
LED1
POWER SUPPLY(I/F)
LED2~5
OPERATION INDICATION
FUSE
FUSE(T3.15AL250V)
SW1
SWITCH(Input selection of inverter capacity setting) *See table 4.
SW2
SWITCH(Function switch)*See table 5 and 6.
SW3
SWITCH(LED2~5 Display setting)
SW6
SWITCH(4-20mA/1-5V/0-10V switch)*See table 4.
ZNR01,02
VARISTOR
DSA
SURGE ABSORBER
RELAY
X1~X6
TARGET TEMP. THERMISTOR
TH1
(0/15k, 25/5.2k DETECT)
PIPE TEMP. THERMISTOR/LIQUID
TH2
(0/15k, 25/5.2k DETECT)
PIPE TEMP. THERMISTOR/2-PHASE
TH5
(0/15k, 25/5.2k DETECT)
SYMBOL
(1) PAC-IF011B-E(I/F)
TB142
1
2
3
4
5
6
7
8
9
10
11
12
13
14
FTC
TB61
LED1
At site
SW3
1 2 3 4 5 6 7 8 9 10 11121314
X1 X2 X3 X4 X5 X6 X7
ZNR01
DSA
TB141
TB6
S1 S2 S3
L N
TB6
*2 Remove the
short-circuited
connector CNS2.
S1 S2 S3
L N
CNS2
(RED) 1 2
ZNR02 FUSE
Refer to Table 2.
2 4 6 8 10 12 14
1 3 5 7 9 11 13
DC311
339V
(External Output)
FTC
RECTIFICATION
2 4 6 8 10 12 14
1 3 5 7 9 11 13
Refer to
Table 1.
SW2
1
SW1
(External Input)
OFF/ON
SW6
TB141
1
2
LED2 LED4
LED3 LED5
TB142
1 TB62
2
3 +
4
5
6
1
2
3
4
5
6
19
NAME
SYMBOL
FLOW TEMP. CONTROLLER(FTC)
TB6
TERMINAL BLOCK(FTC/OUTDOOR UNIT CONNECTING LINE)
TB141
TERMINAL BLOCK (External Output)
TB142
TERMINAL BLOCK (External Input Contact signal)
TB62
TERMINAL BLOCK (External Input Analog signal)
TB61
TERMINAL BLOCK (Thermistor)
LED1
POWER SUPPLY(FTC)
LED2
POWER SUPPLY(WIRED REMOTE CONTROLLER)
LED3
TRANSMISSION(FTC-OUTDOOR UNIT)
LED4, 5
NOT IN USE
FUSE
FUSE(T3.15AL250V)
SW1
SWITCH *See Table 3, 4 and 6.
SW2
SWITCH
SW3
SWITCH *See Table 5.
SW6
SWITCH(4-20mA/1-5V/0-10V switch) *See Table 3.
ZNR01,02
VARISTOR
DSA
SURGE ABSORBER
X1X7
RELAY
ACTUAL FLOW WATER TEMP. THERMISTOR (Water piping)
TH1
(0/15k, 25/5.2k DETECT)
PIPE TEMP. THERMISTOR/LIQUID (Refrigerant piping)
TH2
(0/15k, 25/5.2k DETECT)
TO OUTDOOR UNIT
POWER SUPPLY
/N
TO OUTDOOR UNIT
*1(Fig.1)
Heating
HeatingECO
Hot Water
Anti-Freeze
Cooling
At site
TH2
4-20mA/1-5V/0-10V
*6
TH1
(IN4)
(COM-IN5)
(COM-IN6)
(COM-IN7)
(COM-IN8)
7-8
10-11
10-12
10-13
10-14
(OUT7)
13-14
X7
X1
X2
X3
X4
X5
X6
Outdoor unit *6
SPLIT type
PACKAGED type
SPLIT type
PACKAGED type
4-20mA
SPLIT type
PACKAGED type
1-5V
SPLIT type
PACKAGED type
0-10V
SPLIT type
PACKAGED type
DIP switch on PCB
SPLIT type
SW2-18, SW3-13 PACKAGED type
Wired remote controller SPLIT type
PACKAGED type
Wired remote controller SPLIT type
PACKAGED type
Change TEMP.Input
DIP switch on PCB
SW2-18, SW3-13
Wired remote controller
SW1-1
ON
ON
ON
ON
OFF
OFF
OFF
OFF
ON
ON
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
Normal
OFF
OFF
OFF
OFF
SW1-2
OFF
OFF
OFF
OFF
ON
ON
ON
ON
ON
ON
OFF
OFF
OFF
OFF
OFF
OFF
SW1-5
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
ON
ON
Error
ON
ON
ON
ON
Remark
Not in use
Not in use
SW3-6=OFF
SW3-6=ON
SW1-6
ON
ON
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
ON
OFF
OFF
OFF
OFF
Operation mode
Heating/Heating ECO/Hot water/Anti-freeze/Cooling
Heating/Heating ECO/Hot water/Anti-freeze
Item
Normal
Forced Comp. OFF
Forced Comp. OFF
Normal
*7. Don
t use this setting when using the SPLIT type outdoor unit.
*8. Refer to installation manual.
SW6-2
OFF
OFF
OFF
OFF
ON
ON
ON
ON
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
BH79L347H01
SW1-6=OFF
Set temperature range with wired remote controller
SW1-6=ON
Set temperature table with DIP switch of FTC
SW1-6 SW1-7 SW1-8 Temperature range with wired remote controller
Cooling
Heating/HeatingECO/Hot Water Anti-Freeze
OFF
OFF
OFF
Upper 45 / lower 5 Upper 25 / lower 5
Upper 55 / lower 20
OFF
ON
OFF
Upper 45 / lower 5 Upper 25 / lower 5
Upper 60 / lower 20 *7
OFF
OFF
ON
Upper 45 / lower 5 Upper 25 / lower 5
Upper 50 / lower 20
OFF
ON
ON
ON
OFF
OFF
ON
ON
OFF
ON
OFF
ON
ON
ON
ON
Table 6 SW1-6,7,8
ON
OFF
SW3-6
Table 5 SW3-6 Logic of Forced comp. OFF external signal (TB142 5-6)
SW1-3
OFF
ON
SW6-1
OFF
OFF
OFF
OFF
ON
ON
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
Temperature table
SW2-18, SW3-13
Table