Specifications
Inputcharacteristics
V/A/Hzdisplay
Inputimpedance
1M,20pF
Voltagerating
600Vrms,CATIII
Truermsvoltage
Ranges
5.000V,50.00V,500.0V,1250V1
Accuracy
(1%+10counts)
Ranges
50.00A,500.0A,5.000kA,50.00kA,1250kA
Accuracy
(1%+10counts)
Ranges
10.0to15.0kHz
Accuracy
([%ofreading]+[counts]):0.5%+2
Ranges
1.010.0
Accuracy
(5%+1count)
1phaseand3phase,3conductorbalancedloads
Ranges
250W1.56GW
Accuracy
(4%+4counts)FundamentalPower
(AC+DC)
Truermscurrent
(AC+DC)
Frequency
CFcrestfactor
Powerdisplay
Watts,VA,VAR
PFpowerfactor
DPFdisplacement
powerfactor,Cos.F
H2frequency
fundamental
Harmonicsdisplay
Voltage,current,
frequency
Fundamental
Accuracy
(2%+6counts)TotalPower
Range
01.0
Accuracy
0.04
Range
0.250.9
Accuracy
0.04
Range
0.901.0
Accuracy
0.03
Ranges
40.0to70.0Hz
Accuracy
([%ofreading]+[counts]):0.5%+2
Ranges
Fundamentalto51stharmonic
Accuracy
VA(3%+2counts)W(5%+2counts)
2to31st
VA(5%+3counts)W(10%+10counts)
harmonic
32to51st
VA(15%+5counts)W(30%+5counts)
harmonic
Frequency
fundamental
Phase
Ranges
40Hzto70Hz
Accuracy
0.25Hz
Range
V,A(Betweenfundamentalandharmonics)
Accuracy
3to15
Range
W(Betweenvoltagefundamentalandcurrent
harmonics)
Kfactor
(CurrentandPower)
THDtotalharmonic
distortion
Sagsandswells
Accuracy
5to15
Range
1.0to30.0
Accuracy
10%
Range
0.0099.99
Accuracy
(3%+8counts)
Recordingtimes
4minto16days(selectable)
Vrmsactual,vrms
Ranges
5.000V,50.00V,500.0V,1250V1
Accuracy
Readings(2%+10counts)Cursorreadings
max,min(AC+DC)
(2%+12counts)
Armsactual,arms
max,min(AC+DC)
Transientcapture
Ranges
50.00A,500.0A,5.000kA,50.00kA
Accuracy
(2%+10counts)
Minimumpulsewidth
40ns
Usefulbandwidth
DCto1MHz
input1
Numberoftransients
40
Voltagethreshold
20%,50%,100%,200%aboveorbelowreference
settings
Referencesignal
AfterSTART,theVrmsandfrequencyofthesignalaremeasured.
Fromthesedataapuresinewaveiscalculatedasreferencefor
thresholdsetting.
Vpeakmin,vpeakmax 10V,25V,50V,125V,250V,500V,1250VAccuracy:5%offull
R,C,diode,continuity
atcursor
scale
Resistanceranges
500.0,5.000k,50.00k,500.0k,5.000M,30.00M
Resistance
(0.6%+5counts)
accuracy
Capacitance
50.00nF,500.0nF,5.000F,50.00F,500.0F
ranges
Capacitanceaccuracy
Inrushcurrent
Inrushtimes
(2%+10counts)
DiodeRanges
0to3.000V
Diodevoltage
Accuracy
(2%+5counts)
Continuity
Beeperonat<305
Maxcurrent
0.5mA
Temperature
CorF
1s,5s,10s,50s,100s,5min
Currentranges
1A,5A,10A,50A,100A,500A,1000A
Cursorreadings Apeakmaxatcursor1andcursor2
Temperature
(withaccessory)
Scopedisplay
Measurements
Accuracy
5%offullscale
Timebetween
4to235pixels(1pixel=inrushtime/250)
cursors
Accuracy:(0.2%+2pixels)
Range
100C400C
Accuracy
(0.5%+5counts)
DC,AC,AC+DC,peak,peakpeak,frequency,
dutycycle,phase,pulsewidth,crestfactor
Timeranges
20ns/divto60s/div
Maxsampling
25MS/s
rate
Bandwidth
Voltagechannel 20MHzatinputs,1MHzwithTL24leads
[1]
Currentchannel
DCto15kHzatinputs,10kHzwithi400scurrent
[2]
clamp
Coupling
AC,DC(10Hz3dB)
Vertical
5mV/divto500V/div
sensitivity
Vertical
8bit(256levels)
resolution
Recordlength
512samplesperchannel
Baseranges
60S/divto20nS/div(0.4%+1pixel)
Timebase
Normal,roll,single
modes
Pretrigger
Upto10divisions
TriggerSource
Input1orinput2orautomaticselection
TriggerMode
AutomaticConnectandView,freeRun,and
singleShot
Connectandview
Advancedautomatictriggeringthatrecognizessignalpatterns
Automaticallyadjuststriggering,timebaseandamplitudeand
displaysstablepictures
Memories
20(screens,settings,data)
Recording
Recordingtimes
4minto16days(selectable)
Parameters
Chooseoneortwoparametersfromoneofthegroupsbelow
Volts/Ampres/Hertz
Power
Watts,VA,VAR,PF,DPF,frequency
Harmonics,THD,volts(Fund.andharmonic),ampres(F&H)
watts(F&H)
Frequency(H),%(H)oftotal,Phase(H),KF
Temperature
Resistance
Resistance,diode,continuity,capacitance
Scope
DCvoltage,DCcurrent,ACvoltage,ACcurrent,frequency,
Pulsewidth+or,phase,dutycycle+or,peakmax,peakmin,
peakminmax,crestfactor
Environmental
Operatingtemperature 0Cto+50C
specifications
Safetyspecifications
Electricalsafety
EN610101CATIII,600V.CSAlisted
Mechanicalandgeneral
Size
232x115x50mm
Weight
1.1kg
Warranty
3years
Batterylife
RechargeableNiMHpack(chargerincluded),6.5hrsextended
specifications
operatingtime(continuous)
Shockandvibration
Mil28800E,Type3,ClassIII,StyleB
Case
IP51(dust,drip,waterproof)
1.RatedEN610101600VCATIIICSA