Wye Start/Delta Run 101

Ask the How to hook up this increasingly


experts popular motor connection
Q: I have a 12 lead
dual voltage motor
As motor manufactures become
more aggressive to capture a grow-
ing global market, connection
schemes in polyphase induction
required on a single voltage Wye
Start/Delta Run Motor, however,
most motor manufactures have stan-
dardized with dual voltage motors
showing both a "Y" (Wye) motors are becoming more univer- (230/460), which requires the 12
Start and a Delta Run sal. One method called Wye/Delta, or leads to accommodate Wye
commonly referred to as Wye Start/Delta Run on both high and low
connection. Which one do Start/Delta Run, is becoming popular voltage. A 12-lead Wye Start/Delta
I use? with domestic manufacturers selling Run Motor has the ability to meet
abroad. This technique of starting several starting criteria, such as:

A: If wiring the motor


to a single 3 pole contactor
the motor wired in a Wye connection,
and later switching to a Delta Run
connection, will dramatically reduce
the current demand on a power dis-
Across the Line Starting - On
the Delta Run connection where the
full winding is energized at either
high or low voltage.
for “Across The Line tribution system. In areas where util- Wye Start/Delta Run - Initially
Starting,” use the Delta Run ity power is limited or over bur- the motor will start monetarily on the
Connection for the correct dened, this system can reduce brown Wye connection and then switch to
outs and severe voltage drops when the Delta Run for continuous opera-
high (460V) or low (230V) a motor is started. tion on either high or low voltage.
supply voltage. The motor The Wye Start/Delta Run method is This can be accomplished with a spe-
will start and run not new to the industry. It is used on cial Wye Delta Starter or by a series
continuously on the Delta a limited basis in the US, and more of contactors in a control circuit.
widely used in European countries. Reduced Voltage - Sometimes
Run connection. When using Sometimes the method is mandatory referred to as transformer starting,
reduced current starting, on large motors. In the United this method requires the motor con-
the motor is connected States, the fire pump industry has nected for Across the Line on the
momentarily in the “Wye adopted this starting system on UL Delta Run connection.
Listed fire pump motors. By using Soft Start or Variable Frequen-
Start” configuration and the Wye Start/Delta Run method, cy Drive - requires motor connected
must switch to the “Delta customers can achieve lower starting for Across the Line on the Delta Run
Run” for continuous current demand when the sprinkler connection.
operation. This can be system motor is started in a building Part Winding Start - This method
that is in distress or experiencing an
accomplished by a series of electrical fire. This starting method continued on back >
contactors in a control will minimize current demand during
circuit or by a special starting and reduce the impact on
Wye/Delta Starter. the power system, therefore, reduc-
ing the chance of the motor tripping
Have a question for the
off-line in a distressed power sys-
tem. Some of the fire pump motors
experts? Contact us
are also offered with the capability of
at jim.bryan@emotors.com
part winding starting on low voltage.
Typically, only six leads are
product service BULLETIN

< continued from page one


WYE START - DELTA RUN PART WINDING START
is only associated with low voltage, DUAL VOLTAGE 12 LEAD MOTOR DUAL VOLTAGE 12 LEAD MOTOR

on dual voltage Wye/Delta motors. LOW VOLTAGE HIGH VOLTAGE LOW VOLTAGE ONLY
This method energizes a portion of
6 4 5 7 8 9 12 10 11
the winding initially, and then after a
couple of seconds, will connect the 12 10 11 4 5 6 7 8 9
complete winding of the motor for START START
7 8 9 12 10 11 6 4 5
continuous operation.
Most motor repair and service facil- 1 2 3 1 2 3 1 2 3
ities throughout the industry are L1 L2 L3 L1 L2 L3 L1 L2 L3
knowledgeable of a Wye Start/Delta
7 8 9 7 8 9 12 10 11
Run motor. Confusion often occurs
when a motor is configured in this 6 4 5 4 5 6 7 8 9
RUN RUN
arrangement, but does not use the
12 10 11 12 10 11 6 4 5
Wye Start method, and instead will
use an Across the Line starting con- 1 2 3 1 2 3 1 2 3
nection. Some motor installers who L1 L2 L3 L1 L2 L3 L1 L2 L3
wire a motor configured in this man- USE RUN CONNECTION FOR ACROSS THE LINE STARTING
ner become confused. They can’t dis-
tinguish between the Wye Starting
connection and the Delta Run Con-
nection. They try to associate the
distribution voltage of a transformer
supplying 3-phase power in a Wye
configuration to the Wye Start con-
nection. Unfortunately, if the motor
is continuously operated at full load,
high current will result. And if over-
loads do not trip, damage to the
motor will result.
Per NEMA MG1 1998-1.76, a Wye
Start, Delta Run motor is one
arranged for starting by connecting
to the supply with the primary wind-
ing initially connected in Wye, then
reconnected in Delta for continuous
run operation. This is accomplished
by a special Wye-Delta starter con-
figuration using six leads from the
motor and is intended to limit the
inrush current required to start the
motor. STANDARDS AND METHODS FOR STARTING
NOTE: Damage will occur if the SQUIRREL CAGE INDUCTION MOTORS
motor is operated with load for motor
than 30 seconds on the Wye Start Wye Start – Delta Run: This method is actually reduced voltage, bit is accomplished by changing
the motor phase connections such that a winding that is designed to run with phase voltage equal
connection without transition to to line voltage on delta connection is wye connected for starting to put less than line voltage on
Delta Run. each phase. Effectively, the voltage is reduced by 1.732 factor. The impedence seen by the power
The information in the accompany- system is 3 times the impedance of the delta run connection.
ing charts addresses some of the Starting Characteristics:
technical advantages of Wye Start/ 1. Starting current is
Delta Run motors, the performance approximately 30% of normal.
2. Starting torque is
characteristics and the control sys- approximately 25-30% of
tem required to accommodate the normal.
various starting arrangements. Applications:
For additional information about 1. Where load torque during
Wye Start/Delta Run, please contact acceleration is very low.
2. May be used for partial
the Product Service Department at acceleration.
Emerson Motor Technologies, at 1- 3. Used more often for
800-566-1418. European motors.