Sunteți pe pagina 1din 200

4010 Fire Alarm

PC Programmer
Installation and Programming Instructions

574-187
Rev. C

Technical Manuals Online! - http://www.tech-man.com

Copyright and Trademarks

Copyright Simplex Time Recorder Co., 2000. All rights reserved.


Printed in the United States of America.
Information in this document is subject to change without notice. No part of this
document may be reproduced or transmitted in any form or by any means,
electronic or mechanical, for any purpose, without the express written consent of
Simplex Time Recorder Company.
Walk Test is protected by US Patent No. 4,725,818.
MAPNET addressable communications is protected by US Patent No.4,796,025.
IDNet is patent pending.
TrueAlarm Analog Detection is protected by US Patent No. 5,155,468.
TrueAlarm Detector Base is protected by US Patent No. 5,173, 683.

Cautions and Warnings

SYSTEM REACCEPTANCE TEST AFTER SOFTWARE CHANGES - To


ensure proper system operation, this product must be tested in accordance with
NFPA72-1996, Chapter 7 after any programming operation or change in sitespecific software. Reacceptance testing is required after any change, addition or
deletion of system components, or after any modification, repair or adjustment
to system hardware or wiring.
All components, circuits, system operations, or software functions known to be
affected by a change must be 100% tested. In addition, to ensure that other
operations are not inadvertently affected, at least 10% of initiating devices that
are not directly affected by the change, up to a maximum of 50 devices, must
also be tested and proper system operation verified.
READ AND SAVE THESE INSTRUCTIONS. Follow the instructions in the
installation, operating and programming manuals. These instructions must be
followed to avoid damage to the control panel and associated equipment. Fire
Alarm Control Panel (FACP) operation and reliability depend upon proper
installation.
DO NOT INSTALL ANY SIMPLEX PRODUCT THAT APPEARS
DAMAGED. Upon unpacking your Simplex product, inspect the contents of
the carton for shipping damage. If damage is apparent, immediately file a claim
with the carrier and notify Simplex.
ELECTRICAL HAZARD - Disconnect electrical power when making any
internal adjustments or repairs. Servicing should be performed by qualified
Simplex Representatives.
RADIO FREQUENCY ENERGY - This equipment generates, uses, and can
radiate radio frequency energy and if not installed and used in accordance with
the instruction manual, may cause interference to radio communications. It has
been tested and found to comply with the limits for a Class A computing device
pursuant to Subpart J of Part 15 of FCC Rules, which are designed to provide
reasonable protection against such interference when operated in a commercial
environment. Operation of this equipment in a residential area may cause
interference in which case the user at his own expense will be required to take
whatever measures may be required to correct the interference.

Technical Manuals Online! - http://www.tech-man.com

Codes and Standards

The 4010 is listed for the following.


UL 864 Listings for Type of System:

UL 864 Power-Limited Fire Alarm Control Unit.

Local (formerly NFPA 72A).


Requires the sounding of an alarm via listed notification appliance(s).

Auxiliary (formerly NFPA 72B).


Requires 4010-9809 City Circuit Module.

Remote Station - protected premise (formerly NFPA 72C).


Requires 4010-9809 City Circuit Module or the 4010-9810 or -9816 DACT.

Proprietary - protected premise (formerly NFPA 72D).


Requires 4010-9817 (with 4010-9818 or 4010-9819) or 4010-9821 Network
Interface Modules.

Central Station - protected premise (formerly NFPA 71).


Requires 4010-9810 or -9816 DACT.

Suppression Releasing Service.


Requires 4010-9814 Suppression Kit.

UL 864 Listings for Type of Service:

Automatic, Manual, Waterflow, and Sprinkler Supervisory.

UL 864 Listings for Type of Signaling:

Coded, Non-Coded, March-Time and DACT.


DACT requires the 4010-9810 or -9816.

Factory Mutual Approved:

Same as UL above.

Local Approvals:

CSFM
MEA
Continued on next page

Technical Manuals Online! - http://www.tech-man.com

Codes and Standards


(continued)

About this Manual

The installer should be familiar with the relevant codes listed below as well as
any other applicable local codes and standards, when installing a fire alarm
system.

NFPA 72
NFPA 11

NFPA 11A
NFPA 12
NFPA 12A
NFPA 13
NFPA 14
NFPA 15
NFPA 16

NFPA 16A

NFPA 17
NFPA 17A
NFPA 25

NFPA 70
NFPA 80
NFPA 90A

NFPA 90B

NFPA 92A
NFPA 92B

NFPA 101
NFPA 170
NFPA 231C
NFPA 1221

National Fire Alarm Code


Standard for Low-Expansion Foam and Combined Agent
Systems
Standard for Medium- and High-Expansion Foam Systems
Standard on Carbon Dioxide Extinguishing Systems
Standard on Halon 1301 Fire Extinguishing Systems
Standard for the Installation of Sprinkler Systems
Standard for the Installation of Standpipe and Hose Systems
Standard for Water Spray Fixed Systems for Fire Protection
Standard for the Installation of Deluge Foam-Water Sprinkler
and Foam-Water Spray Systems
Standard for the Installation of Closed-Head Foam-Water
Sprinkler Systems
Standard for Dry Chemical Extinguishing Systems
Standard for Wet Chemical Extinguishing Systems
Standard for Inspection, Testing, and Maintenance of
Water-Based Fire Protection Systems
National Electrical Code
Standard for Fire Doors and Fire Windows
Standard for the Installation of Air Conditioning and
Ventilation Systems
Standard for the Installation of Warm Air Heating and Air
Conditioning Systems
Recommended Practice for Smoke-Control Systems
Guide for Smoke Management Systems in Malls, Atria, and
Large Areas
Life Safety Code
Standard for Fire Safety Symbols
Standard for Rack Storage of Materials
Standard on the Installation, Maintenance, and Use of Public
Fire Service Communication Systems

Before you start using the 4010 Fire Alarm Installing, Operating, and
Programming Instructions, its important to understand the conventions used in
this publication.
The following conventions are used in this publication to identify special names
or text.

When a membrane panel key (located below the display) is referenced in


this manual, it is normally shown between left and right arrows. Examples
are <ALARM SILENCE> and <SYSTEM RESET>.

Italic type indicates important terms or titles of publications, such as the


4010 Fire Alarm - Programming Instructions.

Bulleted lists, such as this one, provide you with information. They are also
used to indicate alternatives in numbered procedural steps.

Numbered lists indicate procedures with steps that you must carry out
sequentially.

Technical Manuals Online! - http://www.tech-man.com

Table of Contents

Chapter 1. Overview
Overview................................................................................................... 1-1
Related Documents ................................................................................... 1-1
In this Chapter........................................................................................... 1-1
Programmer Overview.................................................................................. 1-2
Introduction............................................................................................... 1-2
Tabs........................................................................................................... 1-3
Icons.......................................................................................................... 1-4
Menu Structure ......................................................................................... 1-4
4010 FACP Version 2.x Feature Enhancements........................................... 1-6
Summary of Features ................................................................................ 1-6
4010 Upgrade Compatibility......................................................................... 1-8
Introduction............................................................................................... 1-8
Using the Version 2.x Programmer with Version 1.x Jobs ....................... 1-9

Chapter 2. Installing/Upgrading PC Programmer


Software
Overview................................................................................................... 2-1
Before You Begin ..................................................................................... 2-1
In this Chapter........................................................................................... 2-1
Before You Begin ......................................................................................... 2-2
System Requirements................................................................................ 2-2
Required Components............................................................................... 2-2
Step 1. Install the Software Key .................................................................. 2-3
Overview................................................................................................... 2-3
Installation ................................................................................................ 2-3
Step 2. Create Floppy Disks (If Necessary) ................................................. 2-4
Overview................................................................................................... 2-4
Procedure .................................................................................................. 2-4
Step 3. Install or Upgrade the PC Programmer Software ............................ 2-7
Overview................................................................................................... 2-7
Procedure .................................................................................................. 2-7

Chapter 3. Downloading a Bin File


Overview................................................................................................... 3-1
Before You Begin ..................................................................................... 3-1
In this Chapter........................................................................................... 3-1
Step 1. Connect Serial Cable and Set Serial Parameters.............................. 3-2
Overview................................................................................................... 3-2
Step 1. Connect the Serial Cable.............................................................. 3-2
Step 2. Set PC Programmer Communication Parameters ........................ 3-2
Step 3. Set 4010 FACP Baud Rate........................................................... 3-3
v

Technical Manuals Online! - http://www.tech-man.com

Step 2. Enable Panel for Download ............................................................. 3-4


Procedure .................................................................................................. 3-4
Step 3. Upload and Archive Version 1.x Job Files ...................................... 3-5
Upload, Backup, and Archive Existing Version 1.x Job........................... 3-5
Step 4. Download BIN File.......................................................................... 3-6
Overview................................................................................................... 3-6
Step 1. Copy BIN File from Floppy to PC Programmer Computer ......... 3-6
Step 2. Start Download on PC Programmer............................................. 3-6
Step 3. Warm Start the 4010 FACP ......................................................... 3-8

Chapter 4. Getting Started


Overview................................................................................................... 4-1
In this Chapter........................................................................................... 4-1
Using Quick CFIG to Autoconfigure a Panel ............................................... 4-2
Using Quick CFIG to Create a New Job................................................... 4-2
Quick CFIG Reconfigure All Hardware Option ....................................... 4-2
Upload the Job from the Panel to the Laptop............................................ 4-3
Starting the Programmer ............................................................................... 4-4
Using the Start Menu ................................................................................ 4-4
Creating a New Job....................................................................................... 4-5
Introduction............................................................................................... 4-5
Step 1. Invoke New System Dialog ......................................................... 4-5
Step 2. Specify Job Number..................................................................... 4-6
Step 3. Specify System Type ................................................................... 4-6
Step 4. Specify Standalone or Network System....................................... 4-6
Opening an Existing Job Stored on the PC ................................................... 4-7
Introduction............................................................................................... 4-7
Procedure .................................................................................................. 4-7
Uploading a Job from the Panel.................................................................... 4-8
Introduction............................................................................................... 4-8
Step 1. Set Panel and PC Baud Rates to 19, 200...................................... 4-8
Step 2. Connect Serial Cable between PC and Panel ............................... 4-9
Step 3. Enable Upload on Panel............................................................... 4-9
Step 4. Start Upload at PC ..................................................................... 4-10
Saving, Archiving, Backing Up, and Restoring Jobs.................................. 4-13
Introduction............................................................................................. 4-13
Saving a Job ............................................................................................ 4-13
Using Save As......................................................................................... 4-14
Archiving a Job....................................................................................... 4-14
Backing Up a Job.................................................................................... 4-15
Restoring a Backed Up or Archived Job................................................. 4-16

Chapter 5. Setting General Information, System


Options, Passcodes, and Access Levels
Introduction............................................................................................... 5-1
In this Chapter........................................................................................... 5-1
Entering General Information ....................................................................... 5-2
Entering General Information ................................................................... 5-2
vi

Technical Manuals Online! - http://www.tech-man.com

Enabling System Options.............................................................................. 5-3


Introduction............................................................................................... 5-3
Time Format ............................................................................................. 5-3
Depleted Battery ....................................................................................... 5-4
Alarm Silence / Inhibit.............................................................................. 5-4
Alarm Cutout Timer.................................................................................. 5-4
Door Drop on Alarm................................................................................. 5-5
Door Drop on AC Fail .............................................................................. 5-5
Air Handling Units (AHU) Stagger Start.................................................. 5-5
Suppression Release.................................................................................. 5-6
Active Status Reminder ............................................................................ 5-7
Signal Operation ....................................................................................... 5-7
Setting Passcodes and Access Levels ........................................................... 5-9
Overview................................................................................................... 5-9
Setting Passcodes .................................................................................... 5-10
Setting Access Levels ............................................................................. 5-10

Chapter 6. Programming Cards


Introduction............................................................................................... 6-1
In this Chapter........................................................................................... 6-1
Overview Card Tab.................................................................................... 6-2
Card Tab Screen Components................................................................... 6-2
Card Configuration Rules ......................................................................... 6-2
Using AutoFill .......................................................................................... 6-3
Adding / Deleting Cards ............................................................................... 6-4
Introduction............................................................................................... 6-4
Adding Cards ............................................................................................ 6-4
Deleting Cards .......................................................................................... 6-4
Programming Master Controller (SFIO) Card .............................................. 6-5
Introduction............................................................................................... 6-5
Programming User-Defined LEDs............................................................ 6-5
Programming User-Defined Function Keys.............................................. 6-7
Programming the NAC Card ........................................................................ 6-9
Introduction............................................................................................... 6-9
Step 1. Open the NAC Card..................................................................... 6-9
Step 2. Edit Device Types........................................................................ 6-9
Step 3. Edit Point Types......................................................................... 6-10
Step 4. Edit Custom Labels.................................................................... 6-10
Programming the AUX Relay Card ............................................................ 6-11
Introduction............................................................................................. 6-11
Step 1. Open the AUX Relay Card ........................................................ 6-11
Step 2. Edit the Point Type .................................................................... 6-12
Step 3. Edit Custom Label ..................................................................... 6-12
Programming the IDNet Card ..................................................................... 6-13
Introduction............................................................................................. 6-13
Step 1. Open the IDNet Card ................................................................. 6-13
Step 2. Edit Each Points Device Type .................................................. 6-14
Step 3. Edit Each Points Point Type ..................................................... 6-15
Step 4. Set Single Station Mode (Detectors with Sounder Bases Only) 6-15
Viewing and Programming Analog and Digital Pseudos............................ 6-16
Introduction............................................................................................. 6-16
vii

Technical Manuals Online! - http://www.tech-man.com

Viewing Card 18 Digital System Pseudos ........................................... 6-16


Card 19 User Digital Pseudos .............................................................. 6-17
Card 20 Analog System Pseudos ......................................................... 6-18
Card 21 Analog User Pseudos ............................................................. 6-19
Card 22 System Defined List Pseudos ................................................. 6-20
Card 23 User Definable List Pseudos .................................................. 6-21
Programming a Dual RS-232 Card ............................................................. 6-22
Introduction............................................................................................. 6-22
Step 1. Open the RS-232 Card Screen ................................................... 6-22
Step 2. Configure Communication Settings........................................... 6-22
Step 3. Select Events.............................................................................. 6-23
Programming an RS-232 Service Modem Card.......................................... 6-24
Introduction............................................................................................. 6-24
Step 1. Open the RS-232 Service Modem Card Screen ......................... 6-24
Step 2. Configure Communication Settings for Port B .......................... 6-24
Step 3. Select Events to Forward to Remote System ............................. 6-25
Service Modem Command Summary ..................................................... 6-26
Programming a 4120 Network Card ........................................................... 6-29
Introduction............................................................................................. 6-29
Step 1. Define Network Job Attributes (If Necessary)........................... 6-29
Step 2. Enter Description ....................................................................... 6-30
Step 3. Set Node / Loop Number and Comm Style ............................... 6-31
Step 4. Select Port Media (Modular Card Only) .................................... 6-31
Programming a 24 Point I/O Card .............................................................. 6-32
Introduction............................................................................................. 6-32
Programming an Input Device (Two- or Three-Position Switch) ........... 6-32
Programming an Output Point ................................................................ 6-36
Programming an LCD Annunciator Card ................................................... 6-37
Introduction............................................................................................. 6-37
Step 1. Open the LCD Annunciator Card Screen................................... 6-37
Step 2. Programming External Graphical LCD Annunciator Switches . 6-37
Step 3. Programming LEDs ................................................................... 6-39
Programming Events............................................................................... 6-40

Chapter 7. Programming Points


Overview................................................................................................... 7-1
In this Chapter........................................................................................... 7-1
Overview Point Tab ................................................................................... 7-2
Introduction............................................................................................... 7-2
Splitter Bar................................................................................................ 7-2
Site, Card, and Point Views ...................................................................... 7-2
Sort Order ................................................................................................. 7-2
Word Library ............................................................................................ 7-2
AutoFill..................................................................................................... 7-3
Custom Label Spell Check........................................................................ 7-3
Programming a Points Hardware Device Type ........................................... 7-5
Introduction............................................................................................... 7-5
Procedure .................................................................................................. 7-5
Programming a Points Software Point Type................................................ 7-8
Introduction............................................................................................... 7-8
Procedure .................................................................................................. 7-8
viii

Technical Manuals Online! - http://www.tech-man.com

Programming Custom Labels ..................................................................... 7-11


Introduction............................................................................................. 7-11
Procedure ................................................................................................ 7-11

Chapter 8. Programming Lists


Introduction............................................................................................... 8-1
In this Chapter........................................................................................... 8-1
Overview List Tab ..................................................................................... 8-2
Accessing the List Tab.............................................................................. 8-2
Icons used within the Screen..................................................................... 8-2
Sorting the Point Display .......................................................................... 8-3
Naming Lists and Adding/Deleting Points ................................................... 8-4
Naming a List............................................................................................ 8-4
Adding Points ........................................................................................... 8-4
Deleting Points.......................................................................................... 8-4

Chapter 9. Creating a Site Tree


Introduction............................................................................................... 9-1
In this Chapter........................................................................................... 9-1
Overview....................................................................................................... 9-2
Introduction............................................................................................... 9-2
Terms and Concepts.................................................................................. 9-2
The Site Tab.............................................................................................. 9-3
Building a Site Tree ...................................................................................... 9-5
Introduction............................................................................................... 9-5
Step 1. Add the Buildings ........................................................................ 9-5
Step 2. Add Floors ................................................................................... 9-5
Step 3. Add Floor Components................................................................ 9-6
Step 4. Add Points ................................................................................... 9-6

Chapter 10. Creating Custom Control Equations


Introduction............................................................................................. 10-1
In this Chapter......................................................................................... 10-1
Overview CC Tab .................................................................................... 10-2
CC Tab.................................................................................................... 10-2
Overview Components of a CC Equation................................................ 10-4
Introduction............................................................................................. 10-4
Input Statements ..................................................................................... 10-4
Output Statements................................................................................... 10-5
Step 1. Add a New Equation to the User Program..................................... 10-6
Procedure ................................................................................................ 10-6
Step 2. Add Additional Inputs and Outputs to an Equation ....................... 10-7
Introduction............................................................................................. 10-7
Adding Additional Inputs ....................................................................... 10-7
Adding Additional Outputs..................................................................... 10-7

Step 3. Edit Each Input Statements Properties ......................................... 10-8


Introduction............................................................................................. 10-8
ix

Technical Manuals Online! - http://www.tech-man.com

Associating Points with Input Statements............................................... 10-9


Input Opcodes and Qualifiers ............................................................... 10-10
Step 4. Edit Each Output Statements Properties..................................... 10-19
Procedure .............................................................................................. 10-19
Associating Points with Output Statements .......................................... 10-23

Chapter 11. Building and Downloading a Job


Introduction............................................................................................. 11-1
In this Chapter......................................................................................... 11-1
Building a Job ............................................................................................. 11-2
Introduction............................................................................................. 11-2
Using Job Builder ................................................................................... 11-2
Downloading a CFG File to the Panel ........................................................ 11-3
Introduction............................................................................................. 11-3
Step 1. Set Panel and PC Serial Communication Parameters ................ 11-3
Step 2. Connect Serial Cable between PC and Panel ............................. 11-4
Step 3. Enable Download on Panel........................................................ 11-4
Step 4. Start Download at PC................................................................. 11-5

Appendix A. Hardware Device Types, Software Point


Types, and Point Addresses
Appendix B. Conversion Table
Index

Technical Manuals Online! - http://www.tech-man.com

Chapter 1
Overview

The 4010 is a single-channel, addressable, modular FACP that monitors and


controls up to 250 IDNet addressable devices. The Standard Function
Input/Output (SFI/O) card, power supply, and cabinet provide a complete fire
alarm control panel for most applications. Optional modules mount to the
chassis to provide additional outputs, network communication, and additional
power. Additionally, the 4010 can automatically control supplementary
equipment such as fire doors and fans during an alarm condition using its
auxiliary relay outputs.
This chapter provides an overview of the PC Programmer application and
discusses 4010 FACP Version 2.x feature enhancements and Version 2.x
upgrade requirements.
The remainder of this publication discusses:

Related Documents

Installing or upgrading the PC Programmer


Using the PC Programmer to program a 4010 job

Additional information related to 4010 Version 2.x includes the following:


574-052 ....... 4010 Installation, Operation, and Front Panel Programming
Instructions
574-779 ....... 4010 SFIO Programmed IC Installation Instructions
574-499 ....... 4010 SFIO Board Installation Instructions
574-181 ....... 4009 IDNet NAC Extender Installation Instructions
574-182 ....... 4009 Fiber Optic Link Option Installation Instructions
574-325 ....... 4009-9807 NAC Option Card Installation Instructions
574-326 ....... 4009-9808 NAC Class A Adapter Option Card Installation
Instructions

In this Chapter

Refer to the following page for specific information on a topic.


Topic

See Page #

Programmer Overview

1-2

4010 FACP Version 2.x Feature Enhancements

1-6

4010 Upgrade Compatibility

1-8

1-1

Technical Manuals Online! - http://www.tech-man.com

Overview

Overview

Programmer Overview

Introduction

The Simplex Programmer application provides a graphical interface for


programming the 4010 FACP. This application contains the following major
components.

A set of Tabs corresponding to the major programmable components of the


4010 system. Clicking on a tab gains access to a window that allows you to
program a specific set of system attributes. Figure 1-1 shows the location
of the tabs. Refer to Tabs later in this section for specific information.

Icons that allow you to quickly perform routine tasks such as printing,
saving a job, etc. Refer to Figure 1-2 for a quick reference on each icons
function.

Menus containing groups of similar choices. All menu choices have a


counterpart on the Icon Bar.

Icons provide quick


access to common
tasks

Menus group similar


tasks

Tabs access related


programming options
and choices

Figure 1-1. Programmer Application, Showing Location of Tabs,


Icons, and Menus
Continued on next page

1-2

Technical Manuals Online! - http://www.tech-man.com

Programmer Overview, Continued

Each tab contains a group of related programming functions, as follows:

The Panel Tab allows you to do the following:

Edit general information such as network, panel, branch, and listing


information

Select and program system options, such as Alarm Silence Inhibit,


Alarm Cutout Timer, etc.

Define passcodes for access levels one through four


Set access levels for various system functions (Fire Alarm
Acknowledge, etc.)

The Card Tab allows you to do the following:

Add and delete cards


Program user-defined LEDs and function keys
Edit each points hardware device type, point type, and custom label on
a per-card basis

The Site Tab provides a means of creating a two-dimensional


representation of a job site. This involves creating and adding labels that
represent the building components -- floors, offices, hallways, etc. -- to the
site tree, and associating points with the correct label. (For example, if the
site tree contains a label named LOBBY, you would associate the points
located in the Lobby area with the LOBBY label.)

Use the Point Tab to do the following:

List points
Edit each points hardware device type, point type, or custom label
AutoFill a points custom label field
Search for a point, based on its name, device type, point type, or label
Spell check custom labels

The List Tab allows you to create and edit system lists.

Custom Control Tab provides a graphical interface for creating Custom


Control equations. A significant advantage of this interface is the ability to
display all of an equations operators and points.
Continued on next page

1-3

Technical Manuals Online! - http://www.tech-man.com

Overview

Tabs

Programmer Overview, Continued

Icons

The Icon Bar contains a set of icons that allow you to quickly perform basic
tasks, such as creating a new job or error checking a job. Figure 1-2 shows the
location of the Icon Bar and identifies the function of each icon.

Figure 1-2. Icon Bar


Menu Structure

Figure 1-3 shows the menu structure of the 4010 PC Programmer application.
Note that some of the options contained in the menu structure are not available
elsewhere in the application (i.e., there is no icon or tab for Preferences).

1-4

Technical Manuals Online! - http://www.tech-man.com

Technical Manuals Online! - http://www.tech-man.com

File Menu

Edit Menu

View Menu

Build Menu

Transfer
Menu

Window
Menu

Help Menu

New

Undo

Panel

Error Check

Settings

New Window

Help
Topics

Open

Cut

Cards

Build

Transfer

Cascade

About

Close

Copy

Site

Terminal

Tile

Save

Paste

Points

Save As

Preferences

Lists

Print Report

Custom Control

Preview Report

Revision
History

Print Setup

Flip View

Archive

Toolbar

Backup

Status Bar

Arrange Icons

Restore

Figure 1-3. 4010 Programmer Menu Structure

1-5

4010 FACP Version 2.x Feature Enhancements

Table 1-1 summarizes the Version 2.x feature enhancements. Refer to the next
section of this manual for a list of the hardware and software components
required to support these features.

Summary of Features

Table 1-1. Version 2.x Feature Enhancements


Feature

Description
Version 2.x provides the ability to connect the 4009 IDNet NAC Extender
to the 4010. Key features of the new 4009 include:

Support for 4009 IDNet


NAC Extender

Standard unit provides four Class B NACs (rated 2A @ 24 VDC),


power supply (8A) and charger.

IDNet Communication and Control. Provides status monitoring and


individual NAC control using a single IDNet address.

Option cards include:

Class A Adapter

IDNet Repeater permits additional 2500 cable run for IDNet


applications

IDNet Fiber Optic receiver card accepts IDNet transmission from


up to 3000 over fiber optic conductors.

Four-circuit NAC card provides four additional NACs, rated 1.5A


@ 24 VDC

TrueAlarm Utility
Temperature Sensing

TrueAlarm utility temperature sensing achieved by assigning the


UTILITY point type to a TrueAlarm heat sensor point allows you to
create Custom Control equations that monitor the heat sensor and trigger
output(s) when a threshold temperature is reached.

Day/Night Programming

The addition of Day/Night programming to Custom Control allows devices


to be controlled differently at different times of the day. A common
application for this type of programming is to decrease the sensitivity of a
TrueAlarm Photo sensor during the day and increase its sensitivity at
night.

60 Equation Custom
Control Capacity

The number of Custom Control equations allowed by the 4010 has been
increased from 40 to 60.

Discrete Battery Charger


Trouble

A discrete Battery Charger Trouble was added to Version 2.x, providing


more exact trouble reporting for charger-related problems. Version 1.x of
the system reported only a common trouble.

Faster Earth Fault


Search Diagnostics

Version 2.x incorporates a revised polling sequence for Earth Fault


Search Diagnostics, resulting in improved cycle times and faster location
of Earth faults.
Continued on next page

1-6

Technical Manuals Online! - http://www.tech-man.com

4010 FACP Version 2.x Feature Enhancements, Continued

Table 1-1. Version 2.x Feature Enhancements

Feature

Support for AHJ Alarm


City Circuit
Programming

Description
Version 2.x adds the ability to reset a City Circuit in the following situation:
If the device(s) in alarm is physically removed.

No other devices are in an alarm state.

System Reset is performed.


Enabling City Circuit reset is done via Custom Control.
Version 2.x includes support for TrueAlert Non-Addressable NAC devices.
With these devices, horn control occurs over the same two wires that
power and fire the strobe appliances, allowing horns and strobes to exist
on the same NAC and still be controlled separately (i.e., horns on until
silenced while strobes remain on until reset). Important points to
remember about TrueAlert Non-Addressable NAC devices include:
Hardware Device Type. TrueAlert Non-Addressable NACs use a
hardware device type of either SIGA (Class A NAC) or SIGB (Class B
NAC).
Software Device Types. Two separate software point types support
two distinct modes of operation:

QALERT device type has no automatic operation. All operations


for this type of device type must be programmed with Custom
Control.

TrueAlert NonAddressable Devices

SQALERT device type automatically turns on the designated


circuit on alarm detect (general alarm), issues the horn silence
command upon Alarm Silence, and turns off the circuit at the
completion of System Reset. Any point programmed with the
SQALERT point type is not available for use in Custom Control
programming.
Quick CFIG. TrueAlert Non-Addressable functionality is not
supported by the front panel Quick CFIG option. You must manually
program TrueAlert hardware and software device types, using either
the front panel interface or the PC Programmer.
Horn Operation. Operation of TrueAlert Non-Addressable Horns is
through the new TrueAlert Horn Operation system option. Possible
selections for this option are STEADY, TEMPORAL, and SLOW
MARCH.
Alarm Operation. In an alarm condition, any NAC programmed with
the SQALERT device type automatically activates. Horns operate as
defined by the TrueAlert Horn Operation system option, and strobes
activate. Pressing Alarm Silence turns off the horns, leaving the
strobes active. System reset automatically turns TrueAlert NACs off.
SMPL Programming. The QALERT point type provides Custom
Control capability for TrueAlert Non-Addressable devices. Existing
opcodes such as ON, OFF, S MARCH, F MARCH, and TEMPORAL
provide standard functionality, and a new opcode HORN OFF
provides specific control of TrueAlert Non-Addressable horns.

1-7

Technical Manuals Online! - http://www.tech-man.com

Overview

Summary of Features
(continued)

4010 Upgrade Compatibility

Introduction

Table 1-2 lists the 4010 FACPs features and indicates whether a specific
hardware or software component is required to support a specific feature or set
of features.
Keep the following in mind when reviewing this table:

4010 Phase 1 features are compatible with any mix of SFIO card, SFIO
firmware, BIN file, and programmer software (BIN and programmer
software must be same revision level).

The REV. C SFIO board provides improved overload protection for the U9
voltage regulator.

TrueAlert Non-Addressable functionality for the 4010 SFIOs NACs


requires the REV. C SFIO board, Version 2 SFIO firmware, and a Version
2 of the BIN file and programmer application.

Discrete battery trouble reporting requires the REV. C SFIO board, Version
2 SFIO firmware, and a Version 2 of the BIN file and programmer
application.

4009 IDNet NACs require either the REV. B or REV. C SFIO board,
Version 2 SFIO firmware, and Version 2 of the BIN file and programmer
application.

All other 4010 Version 2 features are supported by either version of the
SFIO card and SFIO firmware, but you must have Version 2 of the BIN file
and programmer application.

Table 1-2. Compatibility Matrix for Versions 1 and 2

Feature

Phase 1
Features
IDNet U9
Overload
Protection
4010 SFIO
TrueAlert NonAddressable
NACs
FM Battery
Charger TBL
4009 IDNet
Interface
Other Version 2
Features

SFIO Board
Rev. B
565-736

SFIO Board
Rev. C
565-736

SFIO FW
Version 1
742-147

SFIO FW
Version 2
742-147

Programmer
and BIN File
Version 1
741-108 &
107

Programmer
and BIN File
Version 2
741-108 &
107

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Continued on next page


1-8

Technical Manuals Online! - http://www.tech-man.com

4010 Upgrade Compatibility, Continued

Using the programmer to edit jobs on a panel containing older versions of the
SFIO chip and board has the following effect:

After saving the job, the panel tags the job as a Phase II job.
Subsequent editing of the job cannot take advantage of the full set of Phase
II features, despite the jobs Phase II designation.

Because this situation may become confusing, it is recommended that you


upgrade the panels SFIO card and SFIO firmware before editing its job with the
Phase II programmer.

1-9

Technical Manuals Online! - http://www.tech-man.com

Overview

Using the Version 2.x


Programmer with Version 1.x
Jobs

BLANK PAGE

Technical Manuals Online! - http://www.tech-man.com

Chapter 2
Installing/Upgrading
PC Programmer Software
Overview

This chapter lists the system requirements for the PC on which you intend to
install the PC Programmer software and describes installing or upgrading the
Version 2.x programmer software on your PC.

Before You Begin

Before getting started, make sure that you have the following:

In this Chapter

Software key (Simplex Part # 742-079)


Download cable (Simplex Part # 733-794)
Version 2.x PC Programmer CD-ROM (Simplex Part # 741-107)
Blank floppy disks (optional)
Floppy disk with Version 2.x BIN file (Simplex Part # 741-108)

Refer to the following page for specific information on a topic.


Topic

See Page #

Before You Begin

2-2

Step 1. Install the Software Key

2-3

Step 2. Create Floppy Disks (If Necessary)

2-4

Step 3. Install or Upgrade the PC Programmer


Software

2-7

2-1

Technical Manuals Online! - http://www.tech-man.com

PC Programmer Software
Installation/Upgrade

Once you have done this, you must download the BIN file from the distribution
floppy disk to the panel. Refer to Chapter 3 for information on downloading the
Version 2.x BIN file to the 4010 FACP.

Before You Begin

System Requirements

The Panel Programmer is a Microsoft Windows 95 application. To install


and use the Panel Programmer, you must have the following:

Required Components

An IBM-compatible personal computer with a Pentium Processor and


a free serial communications port
Microsoft Windows 95 operating system software
Mouse (with at least two buttons)
16 Mb RAM (32Mb recommended)
850 Mb (or greater) hard drive
If a DACT is installed, you will need the SDACT Programmer software
(Part No. 553-807)

Other components that you may need include:

A 733-794 serial download cable


A 740-989 software key (see Field Service Bulletin FSB-549 for the
ordering procedure)
A 741-107 CD-ROM, containing 4010 Programmer software
If a DACT is installed, you will need the SDACT Programmer software
(Part No. 553-807)

2-2

Technical Manuals Online! - http://www.tech-man.com

Step 1. Install the Software Key

Overview

The Software Key (740-989) controls access to the Panel Programmer. When
the Panel Programmer is started, the software reads the parallel port on the PC
looking for a Software Key before the main programming window is displayed.
If the correct key is not detected, a message box is displayed noting that there is
either a missing or incorrect key and the Panel Programmer will terminate with
no further action.

Installation

Use the following procedure to install the key:

3.

Turn OFF power to your computer.


Remove your printer cable from your parallel port (if installed).
Connect the software key to your parallel port and reconnect your
printer cable to the software key. (See Figure 2-1.)
Turn ON power to your computer.

PARALLEL PORT LPT1

LAPTOP
COMPUTER
(REAR VIEW)

740-989 SOFTWARE KEY

PRINTER CABLE

Figure 2-1. Software Key Installation

2-3

Technical Manuals Online! - http://www.tech-man.com

PC Programmer Software
Installation/Upgrade

1.
2.

Step 2. Create Floppy Disks (If Necessary)

Overview

This section describes creating a set of floppy disks that contain the PC
Programmer software. This step is only necessary if the PC on which you
intend to install the PC Programmer does not contain a CD-ROM drive. Skip to
Step 3. Install or Upgrade the PC Programmer Software, if the system on
which you intend to install or upgrade the PC Programmer software contains a
CD-ROM drive.
Before creating disks, make sure you have the following:

Procedure

1.

A PC containing a CD-ROM drive on which the diskettes can be made.


Seven 3.5, high-density (1.44 MB) floppy diskettes. Ensure that the
diskettes are blank and virus free before using them.
Ensure that the software key is properly installed. The programmer
software will not install if the key is not properly connected to the system.
Insert the CD-ROM (741-107) in the drive of the PC on which the disks
will be made.
The initial screen shown in Figure 2-2 automatically appears after
approximately 10 to 20 seconds.

Figure 2-2. Initial Installation Screen


2.

Click on the DiskBuilder button.


A progress thermometer appears, showing the progress of the Install Wizard
installation. The next screen, shown in Figure 2-3, cautions you to exit all
Windows programs before continuing with the installation.
Continued on next page

2-4

Technical Manuals Online! - http://www.tech-man.com

Step 2. Create Floppy Disks (If Necessary), Continued

Procedure (continued)

3.

Click Next to continue.


The screen shown in Figure 2-4 appears, prompting you to insert a disk in
Drive A:\.

Figure 2-4. Prompt to Insert Disks


4.

Insert a disk in Drive A:\ and click Next.


Continued on next page

2-5

Technical Manuals Online! - http://www.tech-man.com

PC Programmer Software
Installation/Upgrade

Figure 2-3. Welcome Screen

Step 2. Create Floppy Disks (If Necessary), Continued

Procedure (continued)

A progress thermometer appears, showing the progress of the file copy


operation. A series of prompts, similar to the one shown in Figure 2-5 appear,
prompting you to insert each additional disk.

Figure 2-5. Prompt for Additional Disk


Disk Builder is complete when the Finished dialog, shown in the next figure,
appears.

Figure 2-6. Finished Dialog

2-6

Technical Manuals Online! - http://www.tech-man.com

Step 3. Install or Upgrade the PC Programmer Software

Overview

This section describes installing Version 2.x of the PC Programmer software. If


the PC on which you are installing the programmer already contains Version 1.x
software, make sure to overwrite the Version 1.x software with the Version 2.x
programmer software.

Procedure

1.

Do one of the following, depending on which type of media you are using:
If installing from CD-ROM, do the following:
Insert the CD in the drive. The initial screen shown in Figure 2-7
automatically appears after approximately 10 to 20 seconds.

Figure 2-7. Initial Installation Screen


b.

Click Simplex Programmer. The Welcome Screen, shown in Figure


2-8, appears.

If Installing from Floppy Disk, do the following:


a.
b.

Insert Disk 1 in the floppy drive.


Click the Start button and choose the Run option. The Run dialog
appears.
c. Click Browse. After the Browse dialog appears, click on the Look In
list box, and select the A:\ drive.
d. When the contents of the A:\ drive appear, click on Setup.
e. Click on the Open button. The Browse dialog closes and the Run
dialog becomes the active dialog.
f. Click OK.
A progress thermometer appears, showing the progress of the Install Shield
installation. This is followed by the Welcome Screen shown in Figure 2-8.
Continued on next page

2-7

Technical Manuals Online! - http://www.tech-man.com

PC Programmer Software
Installation/Upgrade

a.

Step 3. Install or Upgrade the PC Programmer Software, Continued

Procedure (continued)

Figure 2-8. Installation Welcome Screen


2.

Click Next.
The screen shown in Figure 2-9 appears. As shown in the figure, the
default installation directory is:
C:\Program Files\Simplex\Programmer\
In most cases, it is recommended that you install the software in this
directory. If necessary, use the Browse button to specify a different drive or
directory path.

Figure 2-9. Choose Destination Directory Dialog


Continued on next page

2-8

Technical Manuals Online! - http://www.tech-man.com

Step 3. Install or Upgrade the PC Programmer Software, Continued

Procedure (continued)

3.

Click Next.
A progress thermometer appears, indicating the progress of the file copy
operation. The next prompt, shown in Figure 2-10, indicates that the
installation is finished and that you need to reboot the machine.

PC Programmer Software
Installation/Upgrade

Figure 2-10. Reboot Prompt

2-9

Technical Manuals Online! - http://www.tech-man.com

This is Blank

Technical Manuals Online! - http://www.tech-man.com

Chapter 3
Downloading a Bin File

Overview

Before You Begin

This chapter describes downloading a BIN File from the PC on which the PC
Programmer software is installed to the 4010 FACP. You need to do this in the
following situations:

Following installation of the Version 2.x PC Programmer software, you


must download the Version 2.x BIN file that accompanied the programmer
software to the panel.

As revisions to the 4010 FACP are made, you may receive additional copies
of the BIN file to download.

Before getting started, make sure that you have the following:

Refer to the following page for specific information on a topic.


Topic

See Page #

Step 1. Connect Serial Cable and Set Serial


Parameters

3-2

Step 2. Enable Panel for Download

3-4

Step 3. Upload and Archive Version 1.x Jobs

3-5

Step 4. Download (BIN) File

3-6

3-1

Technical Manuals Online! - http://www.tech-man.com

Downloading a BIN File

In this Chapter

Download cable (Simplex Part # 733-794)


Floppy with Version 2.x BIN file (Simplex Part # 741-108)

Step 1. Connect Serial Cable and Set Serial Parameters

Overview

This section describes:

Step 1. Connect the Serial


Cable

Connecting the serial cable (733-794) between the PC on which the


programmer software is installed and the 4010 FACPs service port.
Setting PC Programmer serial communication parameters.
Setting the baud rate on the 4010 FACP.

Connect the 733-794 serial cable between a free serial port on the service PC
and the service port of the 4010 FACP, as follows:
1.

Locate the PC within 6 feet of the 4010 FACP and connect the end shown
in Figure 3-1 to the PC. Make sure that the red stripe is aligned to the left
as you connect the cable.

2.

Connect the other end to the service port on the 4010 FACP.

Align Red Stripe


to the Left
9-Pin Connector
goes to PC

Figure 3-1. Connecting Serial Cable


Step 2. Set PC Programmer
Communication Parameters

The PC Programmer software requires you to specify settings for the following
serial communication parameters.

Port = COMx
Baud = 9600 or 19200 (recommended)
Parity = None
Stop Bits = 1
Data Bits =8
Continued on next page

3-2

Technical Manuals Online! - http://www.tech-man.com

Step 1. Connect Serial Cable and Set Serial Parameters, Continued

Step 2. Set PC Programmer


Communication Parameters
(continued)

Click the Start button. Point to Programs and select Simplex. When the choices
appear, select Programmer.
1.

Click on the Programmer applications Transfer menu and select Settings.


A dialog similar to the one shown in Figure 3-2 appears.

2.

Set the parameters to the settings listed earlier in this section.

Figure 3-2. Serial Port Settings


Switches 2-1 and 2-2 on the 4010 FACP set the panels baud rate. Table 3-1
summarizes the possible settings for these switches, and Figure 3-3 shows their
location. Make sure that the baud rate you set on the 4010 FACP matches the
baud rate set for the PC Programmer software.
Table 3-1. 4010 Baud Rate Switch Settings
Baud Rate

SW 2-1

SW 2-2

OFF LINE

ON

ON

9600

OFF

ON

19,200

ON

OFF

Black indicates switch positio

OFF LINE
9600
19,200

Figure 3-3. Using Switches SW1 and SW2 to Set Panel Baud Rate

3-3

Technical Manuals Online! - http://www.tech-man.com

Downloading a BIN File

Step 3. Set 4010 FACP Baud


Rate

Step 2. Enable Panel for Download

Procedure

Follow the steps in this section to enable the 4010 FACP for downloads.
1.
2.
3.

Login to the 4010 at Access Level 4.


Press <MENU>.
Press <NEXT> until [UPLOAD/DOWNLOAD] is displayed.
<ENTER> to Accept
<NEXT/PREV to Scroll
Menu:
[Upload/Download]

4.

Press <ENTER>. A screen similar to the following appears.


<ENTER> to Accept
Prog. Interface:

5.

<NEXT/PREV> to Scroll
[Initialize Up/Dwnload]

Press the <NEXT> or <PREV> keys until [Initialize Up/Dwnload] is


displayed and press <ENTER>.

The 4010 displays the following message to indicate that the panel is ready to
accept a download.
***
***

File Transfer Initialized ***


Check Programming Unit **

3-4

Technical Manuals Online! - http://www.tech-man.com

Step 3. Upload and Archive Version 1.x Job Files

Upload, Backup, and Archive


Existing Version 1.x Job

If a Version 1.x job is currently loaded on the panel, make sure to upload,
backup, and archive this job before downloading the Version 2.x BIN file.
Downloading the Version 2.x BIN file erases the existing Version 1.x job from
the panel.
After uploading and restoring the Version 2.x BIN file, you can restore the
Version 1.x job, rebuild it as a Version 2.x job, and download it back to the
panel.
Refer to the following sections of this manual for information on uploading and
backing up a job.
Topic

Refer to

Uploading a Job

Chapter 4 Uploading a Job from


the Panel

Backing Up and Archiving a Job

Chapter 4 Saving, Archiving,


Backing Up, and Restoring Jobs

Downloading a BIN File

3-5

Technical Manuals Online! - http://www.tech-man.com

Step 4. Download BIN File

Overview

Downloading the BIN file is a three-step process:


1.

Copy the BIN file from the floppy to the PC Programmer computer.

2.

Start the download process on the PC.

3.

Perform a Warm Start on the 4010 FACP.

Follow the steps outlined below for specific instructions.


Step 1. Copy BIN File from
Floppy to PC Programmer
Computer

Use Windows Explorer to copy the BIN file from the floppy disk to a directory
on the PC Programmers hard drive. It is recommended that you copy the file to
the following directory. This is the default directory in which the programmer
looks for BIN files.
\PROGRAM FILES\SIMPLEX\PROGRAMMER

Step 2. Start Download on PC


Programmer

1.

Click on the Transfer menu. When the selections appear, choose Transfer.
A window similar to the one shown Figure 3-4 appears.

Figure 3-4. Upload/Download Window


2.

Select the following radio button options in the windows panels.

3.

Download
Direct
Panel EXEC

Click OK. The dialog shown in Figure 3-5 appears, warning you to backup
the system before continuing.
Continued on next page

3-6

Technical Manuals Online! - http://www.tech-man.com

Step 4. Download BIN File, Continued

Step 2. Start Download on PC


Programmer (continued)

Figure 3-5. Caution Dialog


4.

Click Yes.
A window similar to the following appears, prompting you for the location
of the EXEC (Bin) file.

Downloading a BIN File

Figure 3-6. Open Dialog


5.

Select the directory to which the file was copied, click on the name of the
EXEC file, and then select the Open button.
A dialog similar to the following displays.

Figure 3-7. Download Dialog


6.

Click the Start button.


A message appears in the Download Dialog (Figure 3-7), indicating that the
PC Programmer is waiting for the 4010 FACP to begin downloading the
file.
Continued on next page

3-7

Technical Manuals Online! - http://www.tech-man.com

Step 4. Download BIN File, Continued

Step 3. Warm Start the 4010


FACP

Performing a Warm Start of the 4010 FACP triggers the panel to download the
EXEC (Bin) file from the PC Programmer.
1.

Login to the 4010 at Access Level 4.

2.
3.

Press <MENU>.
Press <NEXT> until [PANEL RESTART] is displayed.
<ENTER> to Accept
<NEXT/PREV to Scroll
Menu:
[Panel Restart]

4.

Press <ENTER>. A screen similar to the following appears.


<ENTER> to Accept
<NEXT/PREV> to Scroll
Panel Restart: [Warm Start]

5.

Press the <NEXT> or <PREV> keys until [Warm Start] is displayed and
press <ENTER>

A warm start initiates the start of the download. At the PC Programmer, the
Download dialog (Figure 3-7) shows the progress of the download.
When the download is complete, you should restore and download the Version
1.x job (if necessary).

3-8

Technical Manuals Online! - http://www.tech-man.com

Chapter 4
Getting Started

Overview

This chapter describes the following tasks:

In this Chapter

Using Quick CFIG to autoconfigure a panel


Starting the programmer
Creating a new job
Opening an existing job
Uploading a job from the panel
Saving, archiving, backing up and restoring jobs

Refer to the following page for specific information on a topic.


Topic

See Page #

Using Quick CFIG to Autoconfigure a Panel

4-2

Starting the Programmer

4-4

Creating a New Job

4-5

Opening an Existing Job Stored on the PC

4-7

Uploading a Job from the Panel

4-8

Saving, Archiving, Backing Up, and Restoring Jobs

4-13

Getting Started

4-1

Technical Manuals Online! - http://www.tech-man.com

Using Quick CFIG to Autoconfigure a Panel

Using Quick CFIG to Create a


New Job

The 4010 FACP includes the Quick CFIG utility, an automatic configuration
tool that automatically detects 4010 points. For most new installations, it is
more efficient to run 4010 Quick CFIG from the front panel and then upload the
CFIG from the 4010 to the PC Programmer, where any changes to the point
types, custom labels, and system options can be made.
Using Quick CFIG on a new panel configures the panel for general alarm
operation as follows:

All initiating devices found by Quick CFIG are assigned a FIRE point type.
SIG1 and SIG2 are set to point type SSIGNAL. SIG3 and SIG4 are set to
RSIGNAL.
AUX1 is set to point type RRELAY. AUX2 is set to TRELAY.
Remote annunciators are detected at their set address.

Hardware that is not automatically configured includes:

Quick CFIG Reconfigure All


Hardware Option

Graphic annunciators
Suppression points
Network card
SDACT or CCDACT card

The Quick CFIG Reconfigure All Hardware option, described in this section,
creates a new 4010 configuration.
Note1: If a configuration exists and this option is selected, it clears the current
configuration and adds all currently connected devices to the CFIG.
Note 2: Quick CFIG terminates if duplicate IDNet devices are detected. If this
happens, run Quick CFIG again and watch the LCD. Before the
program terminates, it will list the first seven duplicate addresses
found.
1.
2.

Press <MENU>.
Press <NEXT> or <PREVIOUS> until [Quick CFIG] is displayed and
then press <ENTER>. A warning appears, indicating that the 4010 is no
longer in the Fire Alarm Operation mode.
Please Wait . . .
Fire Alarm Operation Suspended

3.
4.

Press <ENTER> to continue with the Quick-CFIG option.


Press <NEXT> or <PREVIOUS> until <RECONFIGURE ALL
HARDWARE> is displayed and then press <ENTER>. A warning
appears, indicating that this will delete the current configuration.
WARNING
<Enter> to Continue
WARNING
This will DELETE current configuration

Continued on next page


4-2

Technical Manuals Online! - http://www.tech-man.com

Using Quick CFIG to Autoconfigure a Panel, Continued

Quick CFIG Reconfigure All


Hardware Option (continued)

5.

Press <ENTER> to continue. Another warning appears, indicating that you


need to press <ENTER> to confirm the deletion.
WARNING
<Enter> to Continue
WARNING
Press <Enter> to confirm deletion

6.

A message appears indicating that Quick CFIG is reconfiguring the


hardware. This message is followed by another, which indicates that Quick
CFIG is scanning for IDNet devices. The Reconfigure ALL Hardware
function is complete when a message similar to the following appears.
** Automatic Hardware Detection Completed **
Total IDNet Devices Added: 128

Upload the Job from the


Panel to the Laptop

When Quick CFIG completes, you need to upload the job from the panel to the
laptop PC on which the programmer is installed. Once the job is uploaded, you
can open it and customize it as required by the customer, i.e., custom labels,
system options, etc.
See Uploading a Job from the Panel, later in this chapter for specific
information on doing this.

Getting Started

4-3

Technical Manuals Online! - http://www.tech-man.com

Starting the Programmer

Using the Start Menu

Click on the Start menu and point to Programs. When the choices appear, point
to Simplex and then choose Programmer.
A screen similar to the one shown in Figure 4-1 appears.

Figure 4-1. Initial Programmer Screen

4-4

Technical Manuals Online! - http://www.tech-man.com

Creating a New Job

Introduction

This section describes creating a new job with the PC programmer. Doing this
creates a job with limited definitions for the devices (i.e., no custom labels and
default device type or point types assigned to IDNet points). This is useful for
off-site configuration of a system.
After creating a job in this manner, refer to the subsequent chapters in this book
for information on adding option cards to the job, defining system options,
defining device and point types, and adding custom control equations.
Skip this section if you used Quick CFIG to create a new job and uploaded it to
the laptop.
Note:

Step 1. Invoke New System


Dialog

Each branch is responsible for assigning and archiving jobs. The


exception to this is a network job, in which case the network job
number must be assigned by Simplex Applications Engineering.

1.

Start the programmer, as described in the previous section.

2.

At the initial Programmer Screen (Figure 4-1), click on the File menu and
choose New.
The dialog shown in Figure 4-2 appears.

Continued on next page

4-5

Technical Manuals Online! - http://www.tech-man.com

Getting Started

Figure 4-2. New System Dialog

Creating a New Job, Continued

Step 2. Specify Job Number

Enter a name for the job in the Job Number field. It is recommended that you
use a seven-character number with the following format:
BBYMTJJ
BB = Branch Number (1296 possible numbers using the Base 36 numbering
system.) See Appendix B for a Base 36 conversion table.
Y = Year (0 = 1997; 1 = 1998;. . . A = 2007)
M = Month (1 = Jan; 2 = Feb; . . . C = Dec)
T = Panel Type (D = 4010)
JJ = Job number (1296 jobs per branch per month possible using the Base 36
numbering system.) See Appendix B for a Base 36 conversion table.
Example: Job 3004D01 translates to the following:
Branch Number: 108 (becomes 30 using the Base 36 numbering
system)
Year: 1997 (becomes 0)
Month: April (becomes 4)
Panel Type: 4010 (becomes D)
Job Number: 01 (still 01 using the Base 36 numbering system)
Note:

See Appendix B for the Base 10 to Base 36 Conversion Table.

If you enter a Job Name that does not conform to this convention, a warning
message box is presented reminding you of the Job Name format. However, a
non-conforming Job Name will be allowed as long as it follows the DOS filenaming conventions and only contains characters that are part of the 4010
character set. All alpha characters entered will be automatically converted to
upper-case.
When you create a new job file, the Programmer places the letter A at the end
of your seven-character job name. Each time you open this job and make a
revision, the revision letter is also upgraded.
Step 3. Specify System Type

Examine the entry for the System Type drop down list box. The selection must
read 4010. Click on this list box and change the currently selected system
type to 4010 if necessary.

Step 4. Specify Standalone or


Network System

The System Options panel, located at the bottom of Figure 4-2, allows you to
specify whether the 4010 system is operating as a standalone or networked
system. This panel contains the following three choices:

Standalone System specifies that the 4010 is not connected via a 4120
network to other panels.

New Network specifies that the 4010 is physically connected to other


panels, but no network job exists in the 4010s \NETJOBS folder. In this
case, you must specify a network job number in the Job Number field of
Figure 4-2. Make sure to specify only a job number supplied by Simplex
Applications Engineering.

Existing Network specifies that the 4010 is connected to other panels, and
the job has been previously programmed.

4-6

Technical Manuals Online! - http://www.tech-man.com

Opening an Existing Job Stored on the PC

Introduction

By default, previously programmed jobs are stored in either the \4010JOBS or


the \NETJOBS directory. If the job for the panel that you are currently
programming is stored on the PC, use the following procedure to open it for
additional editing.
You should only do this if you are sure that the job on the PC is exactly the same
as the programming (CFIG) currently in use on the panel. For example, if you
have made changes to the panels programming from the 4010 front panel, it
may be more desirable to upload the CFIG from the panel to the laptop PC
before performing additional programming. See the next section for details.

Procedure

1.

Click on the File menu.

2.

Select Open.
A window similar to the following appears.

Figure 4-3. Open Database Dialog


3.

Open the folder containing the job that corresponds to the panel you are
currently programming.

4.

Select the job name and click on the Open button. One of the following
occurs, depending on whether the job has been previously archived.

Non-Archived Jobs. A series of messages appear, indicating that the


programmer is loading the job and updating links. These messages are
followed by the main PC Programmer screen.

Archived Jobs. A prompt appears, indicating that the job has been
previously archived and changes will be saved to a new revision of the
job. Click OK to continue. The next screen displays the main PC
Programmer screen.

4-7

Technical Manuals Online! - http://www.tech-man.com

Getting Started

The name of the job (filename.sdb) appears.

Uploading a Job from the Panel

Introduction

This section describes uploading an existing job from a 4010 FACP to the
service PC for editing. An upload occurs over a serial link running between the
panel and the PC. Follow the steps outlined in the following sections to link the
PC and panel and upload the job.
Note:

Step 1. Set Panel and PC


Baud Rates to 19,200

1.

If the panel containing the job that you want to upload is on a network,
you can upload the job, but you cannot edit the jobs attributes (i.e.,
change system options, add points, etc.). Contact Simplex Service for
additional information.

Set switches SW1 and SW2 to the positions shown in Figure 4-4. These
positions enable a baud rate of 19,200 on the 4010 FACP.

Black indicates switch position

19,200

Figure 4-4. Switch Position for 19,200 Baud


2.

Start the 4010 Programmer application.


Click on the Transfer menu and select Settings.
A dialog similar to the one shown in Figure 4-5 appears.

Figure 4-5. Setting PC Transfer Rate to 19,200


3.

Set these parameters as follows:

Port. Set this radio button to the setting that corresponds to the serial
port to which the serial cable will be connected. In most cases, this will
be COM1.
Baud Rate. Set to 19,200.
Parity. Set to None.
Stop Bits. Set to 1.
Data Bits. Set to 8.
Continued on next page
4-8

Technical Manuals Online! - http://www.tech-man.com

Uploading a Job from the Panel, Continued

Step 2. Connect Serial Cable


between PC and Panel

Connect a 733-794 serial cable between a free serial port on the service PC and
the service port of the 4010 FACP.
1.

Locate the PC within 6 feet of the 4010 FACP and connect the end shown
in Figure 4-6 to the PC.

2.

Connect the other end to the service port on the 4010 FACP. Make sure that
the red stripe is aligned to the left as you connect the cable.

Align Red Stripe


to the Left
9-Pin Connector
goes to PC

Figure 4-6. Connecting Serial Cable


Step 3. Enable Upload on
Panel

1.
2.
3.

Login to the 4010 at Access Level 4.


Press <MENU>.
Press <NEXT> until [UPLOAD/DOWNLOAD] is displayed.

4.

Press <ENTER>. A screen similar to the following appears.


<ENTER> to Accept
Prog. Interface:

5.

<NEXT/PREV> to Scroll
[Initialize Up/Dwnload]

Press the <NEXT> or <PREV> keys until [Initialize Up/Dwnload] is


displayed and press <ENTER>.
Continued on next page

4-9

Technical Manuals Online! - http://www.tech-man.com

Getting Started

<ENTER> to Accept
<NEXT/PREV to Scroll
Menu:
[Upload/Download]

Uploading a Job from the Panel, Continued

Step 3. Enable Upload on


Panel (continued)

The 4010 displays the following message to indicate that the panel is ready to
upload a job.
***
***

Step 4. Start Upload at PC

1.

File Transfer Initialized ***


Check Programming Unit **

Click on the Transfer menu. When the selections appear, choose Transfer.
A window similar to the one shown in Figure 4-7 appears.

Figure 4-7. Upload/Download Dialog


2.

Select the following radio button options in the windows panels.

3.

Upload
Direct
Panel CFIG

Click OK.
The dialog shown in Figure 4-8 appears, prompting you to begin the upload.

Figure 4-8. Upload Dialog


4.

Click on the Start button to begin the upload. One of the following occurs,
depending on whether a job by the same name already exists in the PCs
\4010JOBS folder.
Continued on next page

4-10

Technical Manuals Online! - http://www.tech-man.com

Uploading a Job from the Panel, Continued

Step 4. Start Upload at PC


(continued)

If Job Name Already Exists on PC. If a job by the same name already
exists in the 4010JOBS folder on the PC, the programmer generates a
prompt asking whether you want to write over the existing file. If you do
not want to write over the existing file, click on No. Another dialog
appears, giving you the opportunity to rename the job. If you want to
overwrite the existing job, click on Yes button. A dialog similar to the one
shown in Figure 4-9 appears, indicating the progress of the file transfer.

If Job Name Does Not Exist on PC. If no job with this name exists on the
PC, the programmer begins the download after you click on the Start
button. A dialog similar to the one shown in Figure 4-9 appears, indicating
the progress of the file transfer.

Figure 4-9. Transfer in Progress


The following message appears when the upload is complete.

Figure 4-10. Upload Complete Message


5.

Click OK to continue.
The next message indicates that the programmer is unbuilding the job.

The programmer displays the next message to indicate that the job has been
successfully unbuilt and is now stored in the 4010JOBS folder.
Continued on next page

4-11

Technical Manuals Online! - http://www.tech-man.com

Getting Started

Figure 4-11. Unbuilding 4010 Job Message

Uploading a Job from the Panel, Continued

Step 4. Start Upload at PC


(continued)

Figure 4-12. Job Unbuild Complete Message


To open this job, refer to Opening an Existing Job Stored on the PC, earlier in
this chapter.

4-12

Technical Manuals Online! - http://www.tech-man.com

Saving, Archiving, Backing Up, and Restoring Jobs

Introduction

This section discusses the programmers file management tools Save, Archive,
Backup, and Restore. Refer to the appropriate section below for additional
information.
Always backup and archive a job following editing and successful download.
Doing this allows you to return to a known state should critical problems occur
with an edited job file.

Saving a Job

This option writes an editable version of the job using the job name specified
by the user, followed by the .MDB file extension to the PCs hard disk.
To save a job, do the following:
1.

Open the Save dialog, in either of the following ways:

Click on the Save icon, represented by a disk icon on the icon bar.
Click on the File menu and select the Save option.

A dialog similar to the following appears, allowing you to specify the name
of the file and list the modifications made to the file.

Getting Started

Figure 4-13. Save Dialog


2.
3.
4.

Enter the jobs file name in the Name field.


List any changes made to the job in the Enter Modifications field.
Click on OK to close the dialog.
Continued on next page

4-13

Technical Manuals Online! - http://www.tech-man.com

Saving, Archiving, Backing Up, and Restoring Jobs, Continued

Using Save As

To create a copy of the job currently being edited, use the Save As option. To
do this, click on the File menu and choose Save As.
A dialog similar to the one shown in Figure 4-14 appears, allowing you to
specify the new file name, the destination directory, and the destination drive.

Figure 4-14. Save As Dialog


Archiving a Job

Archive creates a compressed, permanent/non-writable copy of a job, and does


the following with it:

Saves the job to floppy, or a remote (networked) disk.


Saves the job to the hard disk, marking it Read-Only. (This copy can be
restored at a later date, using the Restore command, which is described
below.)

To archive a job, follow these steps:


1.
2.

Make sure the job has been saved before archiving.


Click on the File menu and select the Archive option.
A dialog similar to the following appears.

Figure 4-15. Archive Dialog


3.

Click on a destination drive. The Archive utility automatically names the


file and creates a \4010ARCH directory on the drive that you choose.
Continued on next page

4-14

Technical Manuals Online! - http://www.tech-man.com

Saving, Archiving, Backing Up, and Restoring Jobs, Continued

Archiving a Job (continued)

4.

5.

6.

7.

8.

Backing Up a Job

Click on the Archive button.


The system generates a prompt, asking whether you really want to archive
the job.
Click Yes to continue or No to exit.
If the 4010ARCH directory does not already exist on the target drive, the
system prompts you to create it. If the directory exists, this prompt does not
appear.
Choose Yes to create the directory.
The system displays a message indicating that the archive is complete and
the job can no longer be edited. (Use Restore to restore an archived job, if
necessary.)
Click OK.

When the Programmer Archive Utility dialog reappears, click Exit to close
the Archive utility.

Backup stores a read/writable version of the job on either a removable storage


medium or a remote disk. Follow these steps to backup a job.
1.

Click on the File menu and select the Backup option.


A dialog similar to the one shown in Figure 4-16 appears:
Continued on next page
Getting Started

4-15

Technical Manuals Online! - http://www.tech-man.com

Saving, Archiving, Backing Up, and Restoring Jobs, Continued

Backing Up a Job (continued)

2.

Select the destination directory and drive.

3.

Click on the Backup button.

Figure 4-16. Backup Dialog


A message appears, prompting whether to continue with the backup or
terminate the operation.
4.

Click Yes to continue.


The progress of the backup appears on the bottom of the Backup dialog.

5.
Restoring a Backed Up or
Archived Job

Click Exit to exit the application when the backup is complete.

Restore allows previously backed up or archived jobs to be retrieved for


subsequent viewing or editing.
To restore a backed up or archived job, follow these steps:
1.

Click on the File menu and select the Restore option.


A dialog, similar to the one shown in Figure 4-17, appears.
Continued on next page

4-16

Technical Manuals Online! - http://www.tech-man.com

Saving, Archiving, Backing Up, and Restoring Jobs, Continued

Restoring a Backed Up or
Archived Job (continued)

Figure 4-17. Restore Dialog


2.

Select the drive and directory containing the Backup or Archive files.

3.

Choose the file to restore and click on the Restore button. Archived files
are listed with an SDA4010 file extension, and Backup files are listed with
an SDC4010 file extension.
A message similar to the following appears.

Getting Started

4.

Click Yes to continue. One of the following occurs, depending on whether


a copy of the job already exists on the PC.

If the job does not already exist on the PC, the progress of the Restore
operation displays at the bottom of the screen.

If the job already exists on the PC, Restore asks if you want to
overwrite the existing file. Click Yes to initiate the Restore or No to
exit.

4-17

Technical Manuals Online! - http://www.tech-man.com

White text

Technical Manuals Online! - http://www.tech-man.com

Introduction

This chapter describes setting the systems general information, system options,
passcodes, and access levels.

In this Chapter

Refer to the following page for specific information on a topic.


Topic

See Page #

Entering General Information

5-2

Enabling System Options

5-3

Setting Passcodes and Access Levels

5-9

5-1

Technical Manuals Online! - http://www.tech-man.com

Genl Info/System Options

Chapter 5
Setting General Information,
System Options, Passcodes, and Access Levels

Entering General Information

Entering General Information

1.
2.
3.

Select the Panel tab.


Select the General Information radio button.
A window similar to the following appears.
Enter the applicable information in the fields.

Figure 5-1. General Information

5-2

Technical Manuals Online! - http://www.tech-man.com

Enabling System Options

The following section describes setting the 4010s system options. Click on the
Panel tab and then choose the System Options radio button to gain access to the
options. Refer to the applicable section below for information on a specific
system option.

Figure 5-2. System Options


Time Format

The Time Format option allows you to display system time in 12- or 24-hour
format. That is, time is displayed in either a 12-hour format that uses an AM
(morning) or PM (afternoon) designation, or in 24-hour (military style) format.
The Time format directly affects how time is displayed on the 4010 not only at
the high-level status screen but in the Historical Logs.
Enable either 12- or 24-hour format by selecting the appropriate check box, as
shown below: Refer to Figure 5-2 for the location of this option.

Continued on next page

5-3

Technical Manuals Online! - http://www.tech-man.com

Genl Info/System Options

Introduction

Enabling System Options, Continued

Depleted Battery

This option selects the mode of operation for the 4010 FACP if an alarm occurs
during an AC power loss while a Depleted Battery trouble exists. The specific
operation of this option differs slightly, depending on whether you have a
domestic or Canadian system.
Domestic Operation. The default setting for the option is OFF and the depleted
battery threshold voltage is 19.4 VDC 5%. Operation of this option for a
domestic system is as follows:

If the system is in alarm and a depleted battery condition occurs, any NACs
that are active remain active.

If the system in not in alarm and a depleted battery condition occurs, the
NACs are prevented from activating.

Canadian Operation. The default setting for the option is OFF and the depleted
battery threshold voltage is 19.4 VDC 5%. Operation of this option for a
Canadian system is as follows:

When a depleted battery condition occurs, power is turned off to the 4010.
AC power must be restored to re-activate the 4010.

Enable this option by selecting the check box shown below. Refer to Figure 5-2
for the location of this option.

Alarm Silence/Inhibit

You can inhibit the Alarm Silence/System Reset on a 4010 FACP for a set
duration. The range for the Silence/Reset Inhibit timer is 0-60 minutes with zero
(No Inhibit) being the default setting.
Enable this option by selecting the following check box, as shown below. Refer
to Figure 5-2 for the location of this option.

Alarm Cutout Timer

The Alarm Signal Cutout timer allows you to set a duration for how long
signals sound after an alarm. In other words, when an alarm condition exists,
the signals sound until silenced. With this option set at two minutes, building
signals sound on alarm for two minutes and then stop sounding. However, the
alarm condition remains active in the panel. The default setting for this options
is No Cutout (meaning an Alarm Silence is required to shut off signals).
Enable this option by selecting the check box shown below. Refer to Figure 5-2
for the location of this option.

Continued on next page

5-4

Technical Manuals Online! - http://www.tech-man.com

Enabling System Options, Continued

The Door Drop on Alarm timer allows the 4010 to hold doors open for a set
duration during an alarm condition. After that duration has expired, the 4010
shuts off the door holder relays and the doors close. The range for the timer is
0-60 seconds with a default setting of zero seconds. To have door holders drop
the doors immediately, leave the timer set to zero seconds.
Enable this option by selecting the check box shown below. Refer to Figure 5-2
for the location of this option.

Note: To make a relay a door holder relay, you must assign it the DHOLDER
point type.
Door Drop on AC Fail

The Door Holder - AC Fail Door Drop Timer allows the 4010 to hold doors
open for a set duration during an AC power loss condition. After that duration
has expired, the 4010 shuts off the door holder devices and the doors close. The
range for the timer is 0-60 minutes, with a default setting of 5 minutes. To have
door holders drop the doors immediately upon AC power loss, set the timer to
zero minutes.
Enable this option by selecting the check box shown below. Refer to Figure 5-2
for the location of this option.

Air Handling Units (AHU)


Stagger Start

This option allows you to set the 4010 to stagger start any Air Handling Units
(point types AHUR, AHUO, and AHUF) in the 4010 FACP . This option
protects against power spikes that may cause the circuit breakers to trip when
AHUs start simultaneously. The range for stagger starting the AHUs is 0-60
seconds. The default setting for this option is 30 seconds. A setting of zero
allows all AHUs to start immediately.
The 4010 FACP displays an AHU Stagger Start message when the sequence
starts and an AHU Stagger Start Complete message when the sequence ends.
Enable this option by selecting the check box shown below. Refer to Figure 5-2
for the location of this option.

Continued on next page

5-5

Technical Manuals Online! - http://www.tech-man.com

Genl Info/System Options

Door Drop on Alarm

Enabling System Options, Continued

Suppression Release

The Suppression Release option contains three selections:

Dual Detector. When enabled, this option requires two points in L9


(Automatic Suppression Release Points List) to activate before the outputs
specified in L12 (Suppression Release Output Points List) activate.

Detector Delay. When enabled, this option allows you to specify a delay
between the time that a detector activates and the time that a point within
the L9 list triggers. The range is from 0 to 60 seconds (60 is the default).

Manual Delay. When enabled, this option allows you to specify a delay,
ranging from 0 to 30 seconds, between the time that a manual release point
is activated and the time that the suppression release points in L10 trigger.

L9 Automatic Suppression Release Points


L10 Suppression Manual Release Points
L11 Suppression Release Abort Points
L12 Suppression Release Output Points

For example: any points in L9 have a default delay of 60 seconds before L12
activates, any points in L10 have a default delay of 30 seconds before L12
activates. Once points in L10 are activated, L12 activates after the default 30second delay regardless of the state of abort switches in L11. When Dual
Detector operation is ON, this requires two points in L9 to activate before
suppression release operation is initiated.
WARNING:

When any points in L11 are activated during the


cycling of a delay function, the delay timers continue
to count down to zero. If you release the abort
switch that is in L11 after the timer has reached zero,
points in L12 activate immediately.

Note 1. Do not use the PC Programmer to change the point type of a


suppression release point; doing this causes the PC Programmer to change the
point type back to its default setting. To change the point type of a suppression
release point, you must use the front panel programmer.
Note 2. Set the Depleted Battery Cut Out Timer system option to ON for
suppression release systems. Refer to Depleted Battery earlier in this section
for information.
Continued on next page

5-6

Technical Manuals Online! - http://www.tech-man.com

Enabling System Options, Continued

The Active Status Reminder option allows you to set an interval and duration
during which the 4010 reminds operators that a FIRE, SUPV, or TBL condition
still exists in the panel.
Active Status Reminder consists of two parts. Refer to Figure 5-2 for the
location of these options.

Signal Operation

Reminder Interval. Enable the Reminder Interval by selecting the check


box shown below. Use the control on the right to set the interval. The
range can be from 1 to 12 hours, and the default is 8 hours.

Acknowledge Option. This option sets the duration of the acknowledge


signal. The range can be from 1 to 12 hours, and the default is 5 seconds.
For troubles, a setting of 0 sounds a continuous signal until acknowledged
from the front panel. For alarms, a setting of 0 sounds a continuous signal
until the alarm condition is cleared.

Audible and Visible ON til Silence Notification Appliance Circuits (NACs) can
be set to the choices shown in Table 5-1. The default setting for the Audible
NACs is Temporal; the default setting for the Visible NACs is Synchronous; and
the default setting for TrueAlert Non-Addressable Horns is TEMPORAL.

Continued on next page

5-7

Technical Manuals Online! - http://www.tech-man.com

Genl Info/System Options

Active Status Reminder

Enabling System Options, Continued

Signal Operation (continued)


Table 5-1. Signal Choices
Signal Type

Choices

Audible NAC
Operation

Temporal A three pulse coding pattern


consisting of three second pulses, each
separated by second silence. Each group of
three pulses is separated by 1.5 seconds of
silence.
Steady
March Time
Slow March Time

Visual NAC
Operation

Steady
March Time
Slow March Time
Temporal
Synchronous

TrueAlert NonAddressable Horn


Operation

5-8

Technical Manuals Online! - http://www.tech-man.com

Possible selections for this option are


Steady
Temporal
Slow March Time

Setting Passcodes and Access Levels

All operations in the 4010 are protected at a preset level with designated
passcodes to access these operations. The table below shows the basic
operations and menu choices for specific access levels. The default passcodes
are listed for Levels 2 through 4.
Table 5-2. Access Levels and Operations
ACCESS LEVEL

OPERATIONS

Ack
Silence
System Reset

2
Default
Passcode = 2000

3
Default
Passcode = 3000

All Level 1 Operations, plus:


Set Time/Date
Point Control
Enable/Disable Points
All Level 1 & 2 Operations,
plus:
Clear Logs
Clear Verification Tallies
Programming

Edit/Clear Point Label

Restore/Save CFIG
TrueTest
Walk Test
Reports

4
Default
Passcode = 4000

All Level 1,2, & 3 Operations,


plus:
Quick CFIG
Run Diagnostics
Upload/Download
Programming
Edit Cards
Edit SMPL Program
System Options
Restart Panel
Warm Start
Cold Start
Continued on next page

5-9

Technical Manuals Online! - http://www.tech-man.com

Genl Info/System Options

Overview

Setting Passcodes and Access Levels, Continued

Setting Passcodes

1.
2.
3.

Select the Panel tab, if it is not already selected.


Click on the Passcodes radio button. See Figure 5-3.
Edit the passcodes, as necessary.

Figure 5-3. Passcodes


Setting Access Levels

1.

Select the Panel tab, if it is not already selected.

2.

Click on the Access Levels radio button. See Figure 5-3.

3.

For each of the operations listed in Figure 5-4, use the controls to set an
access level of 1, 2, 3, or 4.

Figure 5-4. Access Levels

5-10

Technical Manuals Online! - http://www.tech-man.com

Chapter 6
Programming Cards

Introduction

The 4010 allows you to manually add and delete option cards, and to view and
program points and card options (user-defined LEDs and function keys) on a
per-card basis.

In this Chapter

Refer to the following page for specific information on a topic.


See Page #

Overview Card Tab

6-2

Adding / Deleting Cards

6-4

Programming Master Controller (SFIO) Card

6-5

Programming the NAC Card

6-9

Programming the AUX Relay Card

6-11

Programming the IDNet Card

6-13

Viewing and Programming Analog and Digital


Pseudos

6-16

Programming a Dual RS-232 Card

6-22

Programming an RS-232 Service Modem Card

6-24

Programming a 4120 Network Card

6-29

Programming a 24 Point I/O Card

6-32

Programming an LCD Annunciator Card

6-37

6-1

Technical Manuals Online! - http://www.tech-man.com

Programming Cards

Topic

Overview Card Tab

Card Tab Screen Components

The Card Tab, shown in Figure 6-1, provides a graphical means of adding,
deleting, and programming 4010 FACP cards. Components of the Card Tab
screen include:

Active Card List. The left-hand side of the screen lists all cards (hardware
and logical) installed on the 4010 FACP. Green cards represent hardware
components and blue cards represent logical groups of similar points. (For
example, Card 19 represents all Digital User Pseudo Points.)

Available Card List. The right-hand side of the screen lists available
option cards that can be added to the system.

Splitter Bar. The width of the Active Card and Available Card lists can be
changed by positioning the cursor directly over the splitter bar, clicking and
holding the left mouse button, dragging the bar to a new location, and then
releasing the bar.

Splitter Bar

Figure 6-1. Card Tab


Card Configuration Rules

The following card configuration rules apply to the 4010 FACP:

Cards 1 through 3 and 17 through 23 cannot be deleted.


One 4120 Network Card or One DACT is allowed.
One Dual RS232 Card or One RS232/Modem is allowed.
Continued on next page

6-2

Technical Manuals Online! - http://www.tech-man.com

Overview Card Tab, Continued

Using AutoFill

The programmer includes an AutoFill feature that allows you to automatically


add pre-selected text or selections to a points device type, point type, or custom
label fields.
Follow these steps to use AutoFill:
Open the card whose points you want to edit.

2.

Click on the point containing the text or selections you want to copy. The
points entry highlights to show it is selected.

3.

If you want to copy the highlighted text to a range of points, do one of the
following:

Range of Adjoining Points. If the points adjoin one and other, hold
down the SHIFT key and click the left mouse button on the topmost
point in the range. Continue to hold down the SHIFT key, move to the
bottom point in the range, and click and release the mouse button.

Range of Non-Adjoining Points. If the points do not adjoin one


another, hold down the CTRL key and select each point. Release the
CTRL key only after all points have been selected.

4.

Press the F4 key. The AutoFill dialog appears.

5.

Click on the check boxes (device type, point type, or custom label)
corresponding to the fields that you want to automatically fill. You can
select multiple fields (i.e. device type and custom label).

6.

Click on the appropriate radio button in the Selection panel, as follows:

7.

All Points. Automatically fills every point with the device type, point
type, or custom label of the point selected in Step 2 above.

Selected Points. Automatically fills every selected point (Step 3 above)


with the device type, point type, or custom label of the point selected in
Step 2 above.

Point Forward. Automatically fills every point forward of the point


selected in Step 2 above with that points device type, point type, or
custom label.

Click OK to AutoFill the selected fields.

6-3

Technical Manuals Online! - http://www.tech-man.com

Programming Cards

1.

Adding / Deleting Cards

Introduction

This section describes manually adding or deleting option cards. Each time you
add a card, the programmer specifies default values for card and point attributes.
After you add a card(s), refer to the appropriate section later in this chapter for
information on editing card-specific information. Refer to Chapter 7
Programming Points for information on programming a cards points and
options.

Adding Cards

1.

In the Available Cards List, select the card you want to add.

2.

Hold the left mouse button down, drag the card to the Active Card List, and
release the mouse button.

The programmer prevents you from adding cards that violate the card
configuration rules.
Deleting Cards

1.

In the Active Card List, click the right mouse button on the icon
representing the card you want to delete. A menu, containing the Delete
and Properties choices, appears. Refer to Figure 6-2.

2.

Select Delete.
The programmer prevents you from deleting cards 1 through 3 and 17
through 23.

3.

Select Yes when the programmer prompts you to confirm the delete
operation.

Figure 6-2. Delete Option

6-4

Technical Manuals Online! - http://www.tech-man.com

Programming Master Controller (SFIO) Card

Introduction

The Master Controller card icon, located at the top of the Active Cards List
(refer to Figure 6-1), represents the 4010s SFIO board. Double clicking on this
icon invokes the Master Controller (SFIO) Card Programming Screen shown in
Figure 6-3.
The top of the screen contains a list of the points associated with the SFIO card.
The point name, device type, and point type none of which is editable is
shown for each point.
Programmable components of the Master Controller card include:
User Defined LED1, LED2, and LED3. See Programming User-Defined
LEDs, later in this section for additional information.

User Defined Function Key 1 and User Defined Function Key 2. See
Programming User-Defined Function Keys later in this section for
additional information.

Figure 6-3. Master Controller (SFIO) Card Programming Screen


Programming User-Defined
LEDs

Each user defined LED allows you to monitor the state of a specific system
point, illuminating when the state of the point changes. For example, LED 1 can
be programmed to light RED when the state (mode) of list point L26 (Waterflow
points) changes to ALARM.
Follow these steps to program an LED.
1.

Choose the LED color by clicking on the radio button to the left of the
appropriate color.
NOTE: It is not possible to independently program the LEDs colors. In
other words, you cannot have the LED light RED when one state is true or
YELLOW when another state is true.
Continued on next page

6-5

Technical Manuals Online! - http://www.tech-man.com

Programming Cards

Programming Master Controller (SFIO) Card, Continued

Programming User-Defined
LEDs (continued)

2.

Click on the Mode drop down list box. Choose the mode (State) that must
be true to illuminate the LED. Refer to Table 6-1 for details on the
available modes.

3.

Click on the Ref Address list box and associate a point with the mode you
set in Step 2. The list that appears depends on the Mode selection. The Ref
Address list contains either physical points, pseudo points, list points, or no
entries.
Table 6-1. Modes for User-Defined LEDs
Mode

Meaning

Disable

LED illuminates when the state of the REF ADDR


(point) is DISABLED.

Fire

LED illuminates when the state of the REF ADDR


(point) goes into ALARM

LF

LED illuminates when the ALARM ACK button on the


panel is pushed.

LS

LED illuminates when the SUPV ACK button on the


panel is pushed.

LT

LED illuminates when the TROUBLE ACK button on


the panel is pushed.

OFF

LED illuminates when the state of the REF ADDR


(point) is OFF.

ON

LED illuminates when the state of the REF ADDR


(point) is ON

SMPL

LED illuminates when the state of a Custom Control


equation(s) is TRUE.

SUPERV

LED illuminates when the state of the REF ADDR


(point) goes into SUPERV.

TROUBLE

LED illuminates when the state of the REF ADDR


(point) goes into ALARM

User-Defined LED Examples. The following examples show typical ways in


which user-defined LEDs are used.
Waterflow Indicator. The following example monitors L26, a user-defined
list containing all Waterflow Points, and illuminates the RED LED if any point
within this list goes into an ALARM state.
1.
2.
3.

Click on the radio button to the left of the RED led.


Click on the Mode drop-down list box and select FIRE.
Click on the Ref. Address list box and select L26.
Continued on next page

6-6

Technical Manuals Online! - http://www.tech-man.com

Programming Master Controller (SFIO) Card, Continued

Programming User-Defined
LEDs (continued)

Earth Ground Detect. The following example tracks the state of P76, a userdefined pseudo point, and illuminates the Yellow LED if P76 turns ON.
P76 is, in turn, controlled by an SMPL equation, shown below, that monitors
power supply points 2-2 (+ Earth Ground) and 2-3 (Neg. Earth Ground). If
either point turns ON (i.e., indicates an Earth ground problem, either positive or
negative), the equation turns on P76, which illuminates the Yellow LED to
indicate the problem.
Click on the radio button to the left of the Yellow led.
Click on the Mode drop-down list box and select ON.
Click on the Ref. Address list box and select P76.

The SMPL equation for the Earth Ground Detect example is shown below.
INPUT
ON/CODE 2-2
or ON/CODE 2-3
OUTPUT
TRACK ON P76 PRI 9,9

Programming User-Defined
Function Keys

Function keys are a way to easily and repeatedly perform a specific function
(Mode) on a particular system point (Reference Address).
1.

Click on the Mode drop-down list box and choose the appropriate mode.
Refer to Table 6-2 for information on the modes.

2.

If the Mode allows, click on the Ref. Address drop-down list box and
choose the point to which the mode applies.
Continued on next page

6-7

Technical Manuals Online! - http://www.tech-man.com

Programming Cards

1.
2.
3.

Programming Master Controller (SFIO) Card, Continued

Programming User-Defined
Function Keys (continued)

Table 6-2. Modes for User-Defined Function Keys


Mode

Meaning

ACK

Function key acknowledges all alarms, troubles, and


supervisories.

DE

N/A with user-defined function keys.

LFACK

Function key acknowledges all fire alarms.

LSACK

Function key acknowledges all supervisory events.

LSR

Function key performs a system reset on the local


panel.

LSS

Function key performs a signal silence on the local


panel.

LTACK

Function key acknowledges all trouble events.

LTEST

Function key performs a lamp test.

ONOFF

N/A with user-defined function keys.

PBH

Pressing the function key turns the specified point


(Ref. Address) ON until the function key is released.

PBT

This mode allows the reference address to track the


state of the function key. The point turns ON if the
switch is active and turns OFF if the switch is not
active.

SMPL

Used to indicate that an SMPL equation is being


used to program the function key.

TDE

Function key toggles (reverses) the Disable/Enable


state of the specified point (Ref. Address).

TOF

Function key toggles (reverses) the ON/OFF state of


the specified point (Ref. Address).

6-8

Technical Manuals Online! - http://www.tech-man.com

Programming the NAC Card

Introduction

The 4010 FACP provides four Notification Appliance Circuits (NACs), each of
which connects one or more Notification Appliances (horns, strobes, bells, etc.)
to the 4010.
The PC Programmer represents the 4010s standard, hardwired NACs as the
NAC card. (Note: 4009 IDNet NACs are grouped and programmed under the
IDNet card.) Opening the NAC card allows you to view and program the device
type, point type, and custom label of the standard Notification Appliances.
The position of the NAC card within the Active Cards List is shown below.
Programming Cards

Figure 6-4. NAC Card Location within Active Cards List


Step 1. Open the NAC Card

Double click on the NAC icon shown in Figure 6-4. A window similar to the
following appears. This window displays all standard NACs.

Figure 6-5. Card Data Entry Window for NACs


Step 2. Edit Device Types

Edit a NACs Device Type, as follows:


1.

Move to the line corresponding to the NAC whose device type you want to
change.

2.

Double click on the NACs existing device type. A list box appears,
containing the following choices:

SIGA - Class A NAC. NAC contains multiple signal paths, allowing


circuit operation to continue if a single open circuit occurs. This option
requires installation of a Class A NAC adapter card.

SIGB - Class B NAC. NAC contains only a single circuit path.


Continued on next page
6-9

Technical Manuals Online! - http://www.tech-man.com

Programming the NAC Card, Continued

Step 3. Edit Point Types

Edit a NACs Point Type, as follows:


1.

Double click on the NACs existing Point Type. A list box appears,
containing NAC-specific point types.

2.

Select the appropriate Point Type. Refer to Table 6-3 for a quick reference
of point types, or refer to Appendix A for detailed point type descriptions.
Table 6-3. NAC Point Types Quick Reference
NAC Point Types
AHUF

AHU off relay dual relay control

AHUO

AHU on relay dual relay control

AHUR

AHU on/off relay signal relay

ALTERN

Elevator capture - alternate

BSIGNAL

Trouble/supervisory bell signal

DHOLDER

Door holder control

PRIMARY

Elevator capture - primary

QALERT

TrueAlert Non-Addressable signal

RELAY

Step 4. Edit Custom Labels

Application

Generic relay

RSIGNAL

Alarm signal on until reset

RVISUAL

Visual on until reset

RWATER

Waterflow signal on until reset

SIGNAL

Generic signal (no default operation)

SQALERT

TrueAlert Non-Addressable signal


on until silence

SSIGNAL

Alarm signal on until silence

SUPREL

Suppression release output

SUPV

Sprinkler supervisory signal

SVISUAL

Visual on until silence

SWATER

Waterflow signal on until silence

TSIGNAL

Trouble/supervisory signal

Edit a NACs Custom Label, as follows:


1.

Move to the line corresponding to the NAC whose custom label you want to
change.

2.

Double click on the NACs existing label and type the appropriate label.

Refer to Using AutoFill at the beginning of this chapter for information on


copying custom label text to a range of points.

6-10

Technical Manuals Online! - http://www.tech-man.com

Programming the AUX Relay Card

Introduction

The 4010 FACP includes two auxiliary relays commonly referred to as AUX
relays. Each relay provides one Form C contact, normally open or normally
closed, rated at 2A (24 VDC) or 0.5 A (120 VAC) with the optional auxiliary
relay kit.
The PC Programmer represents all AUX relays as the AUX Relay card.
Opening this card allows you to view and program the point type and custom
label for these relays. (Note: AUX Relays do not have a programmable device
type.)

Figure 6-6. AUX Relay Icon


Step 1. Open the AUX Relay
Card

Double click on the AUX Relay icon. A window similar to the following
appears.

Figure 6-7. Card Data Entry Window for AUX Relays


Continued on next page
6-11

Technical Manuals Online! - http://www.tech-man.com

Programming Cards

Figure 6-6 shows the location of the AUX Relay card within the Active Card
List.

Programming the AUX Relay Card, Continued

Step 2. Edit the Point Type

Edit an AUX Relays Point Type, as follows:


1.

Double click on the AUX Relays existing Point Type.

2.

Select the appropriate Point Type. Refer to Table 6-4 for a quick reference
of point types, or refer to Appendix A for detailed point type descriptions.
Table 6-4. AUX Relay Point Types Quick Reference
AUX Relay Point
Types

Step 3. Edit Custom Label

Application

AHUF

AHU off relay dual relay control

AHUO

AHU on relay dual relay control

AHUR

AHU on/off relay signal relay

ALTERN

Elevator capture - alternate

BSIGNAL

Trouble/supervisory bell signal

DHOLDER

Door holder control

PRIMARY

Elevator capture - primary

QALERT

TrueAlert Non-Addressable signal

RELAY

Generic relay

RSIGNAL

Alarm signal on until reset

RVISUAL

Visual on until reset

RWATER

Waterflow signal on until reset

SIGNAL

Generic signal (no default operation)

SQALERT

TrueAlert Non-Addressable signal on until


silence

SSIGNAL

Alarm signal on until silence

SUPREL

Not Applicable

SUPV

Sprinkler supervisory signal

SVISUAL

Visual on until silence

SWATER

Waterflow signal on until silence

TSIGNAL

Trouble/supervisory signal

Edit an AUX Relays Custom Label, as follows:


1.

Move to the line corresponding to the AUX Relay whose custom label you
want to change.

2.

Double click on the relays custom label field and enter the appropriate
label.

Refer to Using AutoFill at the beginning of this chapter for information on


copying custom label text to a range of points.

6-12

Technical Manuals Online! - http://www.tech-man.com

Programming the IDNet Card

Introduction

The 4010 FACP supports up to 250 IDNet points.


The PC Programmer represents all IDNet points as the IDNet card. Opening
this card allows you to view and program the device type, point type, custom
label, and mode (sounder base smoke detectors only) for each IDNet point.
Figure 6-8 shows the location of the IDNet card within the Active Card List.

Programming Cards

Figure 6-8. IDNet Card Icon


Step 1. Open the IDNet Card

Double click on the IDNet icon, shown in Figure 6-8. A window similar to the
following appears.

Figure 6-9. Card Data Entry Window for IDNet


Continued on next page

6-13

Technical Manuals Online! - http://www.tech-man.com

Programming the IDNet Card, Continued

Step 2. Edit Each Points


Device Type

Edit an IDNet points Device Type, as follows:


1.

Move to the line corresponding to the point whose device type you want to
change.

2.

Double click on the points device type field. A list box appears, containing
the IDNet-specific choices shown in Table 6-5. Refer to Appendix A for
detailed descriptions of these device types.
Table 6-5. IDNet Device Types
Device Type
4009A
4009A8
ADRPUL
CANPUL
HEAT
IAM
IHEAT
IION
IOHEAT
ION
IPHOTO
KACPULL
MAZAM
MBZAM
OHEAT
PHOTO
QIPHOTO
QPHOTO
QRPHOTO
QSPHOTO
R4009A
R4009A8
RHEAT
RIAM
RION
ROHEAT
RPHOTO
SHEAT
SION
SOHEAT
SPHOTO
XIPHOTO
XPHOTO
XRPHOTO
XSPHOTO

Application
4009A with 4 NACs
4009A with 8 NACs
Addressable Pull Station
Canadian Pull Station
TrueAlarm Heat Detector
Line Power Sup. IAM with TrueSense
TrueAlarm heat detector with isolator
TrueAlarm ion detector with isolator
TrueAlarm heat detector with ROR and Relay
TrueAlarm ionization detector
TrueAlarm photo detector with isolator base
KAC Pull Station
Class A Monitor ZAM (T-sense)
Class B Monitor ZAM (T-sense)
TrueAlarm Heat Detector with ROR
TrueAlarm Photoelectric Detector
Quick Connect Photo with Isolator
Quick Connect Photo
Quick Connect Photo with Relay
Quick Connect Photo with Sounder
4009A 4 NACs with Repeater
4009A 8 NACs with Repeater
TrueAlarm heat detector with relay
Relay IAM
TrueAlarm ion detector with relay
TrueAlarm heat detector with ROR and Relay
TrueAlarm photo detector with relay
TrueAlarm heat detector with sounder
TrueAlarm ion detector with sounder
TrueAlarm heat detector with ROR and Relay
TrueAlarm photo detector with sounder
Extra sensitive TrueAlarm photo detector with
isolator
Extra sensitive TrueAlarm photo detector
Extra sensitive TrueAlarm photo detector with
relay
Extra sensitive TrueAlarm photo detector with
sounder
Continued on next page

6-14

Technical Manuals Online! - http://www.tech-man.com

Programming the IDNet Card, Continued

Step 3. Edit Each Points


Point Type

Edit an IDNet points Point Type, as follows:


1.

Move to the line corresponding to the IDNet point whose point type you
want to change and double click on the Point Type field.

2.

Select the appropriate Point Type. Refer to the Monitor Point Type
descriptions in Appendix A for detailed information on IDNet point types.

Step 4. Set Single Station


Mode (Detectors with
Sounder Bases Only)

TrueAlarm devices with sounder bases default to Single Station mode. Single
station has the following effect.

Sounder activates when the associated sensor is above its alarm threshold.

Sounder silences when sensor is below its alarm threshold.

Alarm remains at panel until reset is performed.

Follow these steps to enable or disable Single Station mode for a specific point.
1.

Double click on the points Mode field.


Two choices appear. One choice is blank (disables Single Station mode)
and the other choice is Single Station (enables Single Station mode).

2.

Select the appropriate mode.

To globally disable Single Station mode, use the front panel programmer
interface (System Options menu).

6-15

Technical Manuals Online! - http://www.tech-man.com

Programming Cards

Note: Do not use the PC Programmer to change the point type of a suppression
release point; doing this causes the PC Programmer to change the point type
back to its default setting. To change the point type of a suppression release
point, you must use the front panel programmer.

Viewing and Programming Analog and Digital Pseudos

Introduction

The pseudo point cards, each of which represents a separate and distinct group
of pseudo points, are located at the bottom of the Active Cards List. Figure 6-10
shows the location of these cards.

Figure 6-10. Digital and Analog Pseudo Cards


Viewing Card 18 Digital
System Pseudos

Card 18 represents the Digital System Pseudos. These points store a value of
ON or OFF and are used by the system to monitor and control system
components and functions.
Double clicking on the Card 18 icon, shown in Figure 6-11, displays the
systems 75 digital pseudo points and their pre-assigned label. This is a viewonly screen and cannot be edited.

Figure 6-11. Card 18 Digital System Pseudos (View Only)


Continued on next page

6-16

Technical Manuals Online! - http://www.tech-man.com

Viewing and Programming Analog and Digital Pseudos, Continued

Card 19 User Digital


Pseudos

User-defined Digital Pseudo Points are used within Custom Control equations.
The function of a user-defined digital pseudo point is determined by the point
type that you assign it. Table 6-6 lists the point types for user-defined digital
pseudo points and explains their function.
To program the Point Type and Custom Label for each user-defined digital
pseudo point, follow these steps.
1.

Double click on the Card 19 icon within the Active Cards List. A window
similar to the following appears.
Programming Cards

Figure 6-12. Card 19 User-Defined Digital Pseudos


2.

3.

Edit a pseudo points point type, as follows:


a.

Move to the line corresponding to the pseudo point whose point type
you want to change.

b.

Double click on the points existing point type. A list box appears,
containing the choices shown in Table 6-6. Click on the appropriate
choice.

Double click on a points Custom Label field to edit its custom label.
Continued on next page

6-17

Technical Manuals Online! - http://www.tech-man.com

Viewing and Programming Analog and Digital Pseudos, Continued

Card 19 User Digital


Pseudos (continued)

Table 6-6. Point Types for User-Defined Digital Pseudo Points


Point Type

Application

ALARM

Turning ON a digital pseudo point with this point type


causes an Alarm condition.

SUPV

Turning ON a digital pseudo point with this point type


causes a Supervisory condition.

TROUBLE

Turning ON a digital pseudo point with this point type


causes a Trouble condition.

UTILITY

A UTILITY digital pseudo point can hold a value of


ON or OFF, and is typically used as an ON/OFF
switch within a custom control equation.
Example. In the following Custom Control equation,
P76 turns ON only when the state of point 2-2 or 2-3
is ON. P76 can then be monitored by other system
components, triggering other actions when it turns
ON.
INPUT
ON/CODE 2-2
or ON/CODE 2-3
OUTPUT
TRACK ON P76 PRI 9,9

Card 20 Analog System


Pseudos

Card 20 represents the systems Analog Pseudo Points. These type of pseudo
points store analog values (the number 128, for example), and can be used as a
threshold value within a Custom Control equation. (For example, perform some
action when the value of the Trouble Count analog pseudo point [A2] reaches a
specific value).
Double click on the Card 20 icon, shown in Figure 6-10, to display the systems
analog pseudo points and their pre-assigned labels. This is a view-only screen
and cannot be edited. Refer to Figure 6-13 for an example of this screen.
Continued on next page

6-18

Technical Manuals Online! - http://www.tech-man.com

Viewing and Programming Analog and Digital Pseudos, Continued

Card 20 Analog System


Pseudos (continued)

Programming Cards

Figure 6-13. Card 20 System Analog Pseudo Points (View Only)


Card 21 Analog User
Pseudos

Analog User Pseudos store analog values that can be used in Custom Control
equations. The exact function of an analog user pseudo depends on its point
type counter, timer, or analog value.
Double clicking on the Card 21 icon within the Active Cards List displays the
systems user Analog Pseudo points. Refer to Figure 6-14 for an example of
this screen.

Figure 6-14. Card 21 Analog User Pseudos


Continued on next page

6-19

Technical Manuals Online! - http://www.tech-man.com

Viewing and Programming Analog and Digital Pseudos, Continued

Card 21 Analog User


Pseudos (continued)

Follow the steps below to program an analog user pseudos point type or custom
label.
1.

Edit the point type of a user analog pseudo point, as follows:


a.

Move to the line corresponding to the pseudo point whose point type
you want to change.

b.

Double click on the points existing point type. A list box appears,
containing the choices shown in the following table. Click on the
appropriate choice.
Table 6-7. Analog Psuedo Point Types

Point Type
ANALOG

Stores a static, analog value between 0 and 65,535.

COUNTER

Allows the points analog value to be incremented by


Custom Control equations. Typically used to track
the number of some system condition and trigger
some action when a threshold is reached.

TIMER

Allows you to set an analog value between 0 and


65, 535 that can be used as a countdown timer. A
timer can be used to delay some action until a
specified amount of time passes.

2.
Card 22 System Defined List
Pseudos

Application

Double click in the Custom Label field to edit the points custom label.

List Pseudos provide a means of monitoring a range of similar devices. (All


Waterflow Alarm Monitor Zones, for example.)
Double clicking on the Card 22 icon within the Active Cards List displays the
System List Pseudo points and their pre-assigned label. This is a view-only
screen and cannot be edited.

Figure 6-15. System List Pseudo Points


Continued on next page
6-20

Technical Manuals Online! - http://www.tech-man.com

Viewing and Programming Analog and Digital Pseudos, Continued

Card 23 User Definable List


Pseudos

User Definable List Pseudos allow you to create a list of similar points for use in
Custom Control equations, user-defined LEDs, user-defined function keys, etc.
The list point turns ON if one of the points referenced in the list turns ON. You
can only edit a lists custom label from the Card Tab.
Follow the steps below to program a user-defined list pseudos custom label.
1.

Double click on the Card 23 icon. A screen similar to the one shown in
Figure 6-16 appears.

Programming Cards

Figure 6-16. User Defined List Pseudos


2.

Move to the line corresponding to the point whose custom label you want to
change. Double click on the line and edit the points label.

6-21

Technical Manuals Online! - http://www.tech-man.com

Programming a Dual RS-232 Card

Introduction

The Dual RS-232 card allows one or two printers to be attached to the 4010
panel. Programming a dual RS-232 card involves setting the communication
parameters and selecting which events are annunciated to the printer(s).

Step 1. Open the RS-232 Card


Screen

Double click on the icon that represents the RS-232 card. (If the card is not
already in the Active Cards List, you first need to drag it from the Available
Cards list into the Active Cards List.) A screen similar to the one shown in
Figure 6-17 appears.

Figure 6-17. RS-232 Card Screen


Step 2. Configure
Communication Settings

Configure the settings for the printer attached to Port A or Port B, as follows:
1.

Click on the Port A or Port B radio button.

2.

Click on the drop-down list box beneath the radio button and specify the
type of printer attached to the port. If no printer is attached to the port,
select Unused. Do not select Command when configuring a printer.
Table 6-8. Supported Printer Types
Option

Application

Unused

Unused port

Print80U

80 character, unsupervised printer

Print80S

80 character, supervised printer

Print40U

40 character, unsupervised printer

Print40S

80 character, supervised printer

Command

Used only when a service modem is


connected to an RS-232 Service Modem
Card. See next section of this manual for
details.
Continued on next page
6-22

Technical Manuals Online! - http://www.tech-man.com

Programming a Dual RS-232 Card, Continued

Step 2. Configure
Communication Settings
(continued)

Click on the Port Label field, shown below, and specify the location of the
printer.

4.

Use the drop down list boxes under Communication Settings to specify the
Baud Rate, number of Data Bits and Stop Bits, and the Parity setting in use
on the printer.

1.

Move to the Event Reporting panel and select the check boxes that
correspond to the types of events you want annunciated at the printer.
Refer to Table 6-9 for information on these checkboxes.

Programming Cards

Step 3. Select Events

3.

Table 6-9. Event Choices


Checkbox

Application

Fire Alarm Events

Prints an event when an ALARM condition


occurs.

Trouble Events

Prints an event when a TROUBLE condition


occurs.

Supervisory Events

Prints an event when a SUPERVISORY


condition occurs.

Walk Test Events

Prints an event when a WALKTEST occurs.

Silence/Reset Events

Prints an event when a System Reset or


Alarm Silence is performed.

SMPL Print Statements


Events

Allows SMPL Print statements to print at the


printer.

Control Events

Prints an event when a control point (signal or


relay) turns ON or OFF.

Utility Events

Prints an event when a point with the Utility


point type turns ON or OFF.

Pseudo Events

Prints an event when a pseudo point changes


state, either from ON to OFF or vice versa.

Reports Events

Specifies whether the printer prints a report


when a report is generated at the panel.

2.

Click OK to close the screen.

6-23

Technical Manuals Online! - http://www.tech-man.com

Programming an RS-232 Service Modem Card

Introduction

The RS-232 Service Modem card allows the following:

Service personnel can dial into the 4010 FACP through the RS-232 Service
Modem card and perform basic control and monitoring of the panel, and
request system reports.

System status and reports can be sent out the service modem port and
displayed on a remote terminal or computer.

This section describes programming the RS-232 Service Modem Card and
provides a brief description of the remote commands used to monitor/control the
4010 FACP.
Step 1. Open the RS-232
Service Modem Card Screen

Double click on the icon that represents the RS-232 Service Modem card. (If
the card is not already in the Active Cards List, you first need to drag it from the
Available Cards list into the Active Cards List.)
A screen similar to the one shown in Figure 6-18 appears.

Figure 6-18. RS-232 Service Modem Card Screen


Step 2. Configure
Communication Settings for
Port B

1.

Click on the Port B radio button.

2.

Click on the drop-down list box beneath the Port B radio button and select
the Command option.
Continued on next page

6-24

Technical Manuals Online! - http://www.tech-man.com

Programming an RS-232 Service Modem Card, Continued

Step 2. Configure
Communication Settings for
Port B (continued)

Click on the Port Label field, shown below, and specify the location of the
control device.

4.

Use the drop down list boxes under Communication Settings to specify the
modems Baud Rate, number of Data Bits and Stop Bits, and the Parity.

Move to the Event Reporting panel and select the check boxes that correspond
to the types of events you want annunciated at the remote system. Refer to
Table 6-10 for information on these checkboxes.
Table 6-10. Event Choices
Checkbox

Application

Fire Alarm Events

Displays an event when an ALARM condition


occurs.

Trouble Events

Displays an event when a TROUBLE


condition occurs.

Supervisory Events

Displays an event when a SUPERVISORY


condition occurs.

Walk Test Events

Displays an event when a WALKTEST occurs.

Silence/Reset Events

Displays an event when a System Reset or


Alarm Silence is performed.

SMPL Print Statements


Events

Displays SMPL Print statements at the remote


system.

Control Events

Displays an event when a control point (signal


or relay) turns ON or OFF.

Utility Events

Displays an event when a point with the Utility


type turns ON or OFF.

Pseudo Events

Displays an event when a pseudo point


changes state, either from ON to OFF or vice
versa.

Reports Events

Specifies whether the system displays a


report when one is generated at the panel.
Continued on next page

6-25

Technical Manuals Online! - http://www.tech-man.com

Programming Cards

Step 3. Select Events to


Forward to Remote System

3.

Programming an RS-232 Service Modem Card, Continued

Service Modem Command


Summary

Service modem commands are either query type commands that request
information or action type commands that direct the panel to perform some
function. The asterisk shown within each command denotes the minimum
number of characters that you must type. For example, to use the TIME
command, you need to type, at a minimum, the T character. In the examples,
the character represents the prompt.

Table 6-11. Service Modem Commands


Command

Explanation / Examples
Sets and displays the system time and date.
Viewing Current Time and Date. Type T at the prompt as shown below:
-T

T*IME

The system responds by displaying the time and date, similar to the following:
8:00:05 am Wed 25-DEC-98

Changing Current Time and Date. Type a T followed by the time and date.
-T 9:00 am 25-DEC-98

Returns the current logical point status (ON, OFF, FIRE, etc.) for the requested point.
Viewing Status for a Specific Point. Enter the LIST command, followed by the points
address (see Appendix A for a list of point addresses). For example:
-LIST P260

L*IST

Viewing List of Current Alarms, Troubles, or Supervisories. Enter the LIST command,
followed by an F (current list of alarms), T (current list of Troubles), or S (current list of
Supervisories). For example:
-LIST F

Viewing Alarm, Trouble, or Supervisory Counts. Enter the List command, followed by
COUNT.
-LIST COUNT

Allows the user to manipulate the status of a control point or digital pseudo point.
Turning a Point ON. Enter the SET command, followed by the points address (see
Appendix A for a list of point addresses), and the ON qualifier. For example:
-SET P260 ON

S*ET

Turning a Point OFF. Enter the SET command, followed by the points address (see
Appendix A for a list of point addresses), and the OFF qualifier. For example:
-SET P260 OFF

Clearing an Override Trouble. Enter the SET command, followed by the points address
(see Appendix A for a list of point addresses), and the AUTO qualifier. For example:
-SET P260 AUTO

Continued on next page


6-26

Technical Manuals Online! - http://www.tech-man.com

Programming an RS-232 Service Modem Card, Continued

Service Modem Command


Summary (continued)
Table 6-12. Service Modem Commands (continued)
Command

Explanation / Examples
Displays the revision of the 4010s system software and the revision and name of the CFIG
(job) executing on the panel. For example:

REV*ISION

-REVISION

Help on Parameters. Enter HELP without a parameter to see a list of available


parameters. To see a short text description of a parameter, type HELP, followed by a
parameter.
HELP

Help on Commands. Enter HELP, followed by a command to see a short text description
for one of the service modem commands. Applicable commands are: TIME, LIST
REVISION, SET, DISABLE, HELP, LOGIN, RESTART, ACK, PRINT, CLEAR, TYPE. For
example:
-HELP TYPE

Allows the user to perform a cold or warm restart.


Performing a Warm Start. Enter RESTART, followed by the qualifier WARM. A warm
start re-initializes the hardware, but does not affect the logs, time and date, verification
tallys, and disable states. For example:
RES*TART

-RESTART WARM

Performing a Cold Start. Enter RESTART, followed by the qualifier COLD. A cold start
performs a complete re-initialization of the panel.
-RESTART COLD

Acknowledging the Highest Priority Abnormal Point. Enter the ACK command with no
qualifiers. For example:
-ACK

ACK

Acknowledging All Points in the Active Alarm (fire), Trouble, or Supervisory List.
Enter the ACK command, followed by F, T, or S. For example:
-ACK F

Logging in to a Remote System. Enter LOGIN at the prompt and wait for the prompt to
reappear. When it does, enter the 4 digit passcode that corresponds to the desired login
level. For example:
LOG*IN

-LOGIN
-4000

Logging Out of a Remote System. Enter LOGIN at the prompt and wait for the prompt to
reappear. When it does, enter a carriage return.
Continued on next page

6-27

Technical Manuals Online! - http://www.tech-man.com

Programming Cards

SYS REV: 2.01 CFIG FORMAT: 71 JOB 92A1004A REV:7 24-NOV-99

Programming an RS-232 Service Modem Card, Continued

Service Modem Command


Summary (continued)
Table 6-13. Service Modem Commands (continued)
Command

Explanation / Examples
Sends a report to the report printer. The PRINT command must be followed by one of the
following qualifiers:

PRINT

ALOG
TLOG
SLOG
CLOG
TASERV
TASTAT

Prints the alarm log


Prints the trouble log
Prints the supervisory log
Prints the combined log
Prints a TrueAlarm service report
Prints a TrueAlarm status report

The command allows the user to clear the alarm log, trouble log, supervisory log, or
combined log. Type CLEAR, followed by one of the following:
CLEAR

ALOG
TLOG
SLOG
CLOG

Prints the alarm log


Prints the trouble log
Prints the supervisory log
Prints the combined log

Sends a report to the terminal (PC) from which the command was issued. The TYPE
command must be followed by one of the following qualifiers:
TYPE

ALOG
TLOG
SLOG
CLOG
TASERV
TASTAT

Prints the alarm log


Prints the trouble log
Prints the supervisory log
Prints the combined log
Prints a TrueAlarm service report
Prints a TrueAlarm status report

Allows the user to disable/enable points.


Disabling a Point. Enter the DISABLE command, followed by a point and the ON
qualifier. For example:
DIS*ABLE

-DISABLE P260 ON

Enabling a Point. Enter the DISABLE command, followed by a point and the OFF
qualifier. For example:
-DISABLE P260 OFF

Three control key commands are supported:


CTRL+A
CTRL+S
CTRL+D

CTRL+A
CTRL+S
CTRL+D

Acknowledges the highest priority abnormal point


Alarm Silence
System Reset

6-28

Technical Manuals Online! - http://www.tech-man.com

Programming a 4120 Network Card

Introduction

This section describes programming a 4120 network card -- either an RS485


card (also known as a Wired Media card) or a modular card with either RS485
or Fiber.
Be aware of the following before beginning:
You cannot create a network of only 4010 panels. You must connect the
4010 to a network containing either a 4100, GCC, or NPU.

Use the PC Programmers Network Tab to create public points.

If you are adding a network card to a non-networked job (i.e., you selected
Standalone Panel when you originally created the job), the programmer presents
the following screen, which allows you to specify the network job number,
description, and network file. Once a standalone job is changed to a network
job, you can no longer upload the job to the laptop. Make sure you backup the
job before proceeding.

Figure 6-19. New Network Job Dialog


1.

Select the appropriate radio button New Network or Existing Network


as required.

2.

If the network job is new, you must specify the Network File number and
Network Description for the job. Refer to Simplex Applications
engineering for information on specifying a network file number.
Continued on next page

6-29

Technical Manuals Online! - http://www.tech-man.com

Programming Cards

Step 1. Define Network Job


Attributes (If Necessary)

Programming a 4120 Network Card, Continued

Step 1. Define Network Job


Attributes (If Necessary)
(continued)

3.

Double click on the icon that represents the 4120 Network card. (If the card
is not already in the Active Cards List, you first need to drag it from the
Available Cards list into the Active Cards List.)
A screen similar to the one shown in Figure 6-20 appears.

Figure 6-20. 4120 Network Card Screen


Step 2. Enter Description

The Description field specifies what appears in the DBN Node Listing
Description, shown at the bottom of Figure 6-20.
Continued on next page

6-30

Technical Manuals Online! - http://www.tech-man.com

Programming a 4120 Network Card, Continued

Step 3. Set Node / Loop


Number and Comm Style

Choose the appropriate selections for Node Number, Loop Number, and Comm
Style, as follows:
Node Number. The Node Number is a unique number used to identify the 4010
panel on the 4120 network. The range for this number is between 1 and 99. If
necessary, first use the Simplex Network Programmer or the network
diagnostics to view the other nodes on the network. Review the node numbers
already in use and select a unique number for this node.

Comm Style. Style 4 networks represent a single line or star topology. With
these types of networks a single short, ground fault, or open circuit on the
network communications channel reports a trouble and all nodes beyond the
fault operate in local (standalone) mode.
Style 7 networks represent a closed loop ring. With these types of networks, any
single open, short, or ground fault on the network communications channel will
not interrupt communications between nodes on the network.
Step 4. Select Port Media
(Modular Card Only)

Modular versions of the 4120 card allow the use of either Wired Media (RS485)
or fiber for the cards left and right ports.
1.

Click the drop down list box underneath Left Port and select the choice that
represents the type of module used on the cards left port.

2.

Click the drop down list box underneath Right Port and select the choice
that represents the type of module used on the cards right port.

6-31

Technical Manuals Online! - http://www.tech-man.com

Programming Cards

Loop Number. A 4120 network can support up to 4 separate loops, with no


physical bridging or routing of information between loops. Make sure that the
loop number you choose is the same as all other nodes on the loop.

Programming a 24 Point I/O Card

Introduction

A 24 Point I/O card allows 24 additional input (either two or three position
switches) or output devices (lamp, piezo, relay, or on until reset relay) to be
connected to the 4010 FACP.
Double click on the icon that represents the 24 Point I/O card. (If the card is not
already in the Active Cards List, you first need to drag it from the Available
Cards list into the Active Cards List.)
A screen similar to the one shown in Figure 6-21 appears.

Figure 6-21. 24 Point I/O Card Screen


Programming an Input Device
(Two- or Three-Position
Switch)

1.

Click on the Device Type field and select GRAPHIN device type.

2.

Click on the point type field and select one of the following:

OSWITCH. Specifies a two-position switch, supervised for open


circuits. Requires an EOL resistor.

SSWITCH. Specifies a two-position switch, supervised for open and


short circuits. Requires EOL and current limited (up leg) resistors.

TSWITCH. Three position (SPDT) switch, supervised for open


circuits. Requires EOL and current limited resistors.

USWITCH. Two-position switch, unsupervised. Assumes that no


EOL or current limited resistor is used. For this type of switch,
SHORT = ON and OPEN = OFF.

3.

Select the mode (operation) of the switch. Refer to Table 6-11 for specific
information on the modes.

4.

Click on the Ref. Addr field and select the point affected by the mode.
Continued on next page

6-32

Technical Manuals Online! - http://www.tech-man.com

Programming a 24 Point I/O Card, Continued

Programming an Input Device


(Two- or Three-Position
Switch) (continued)
Table 6-14. Input Modes
Mode

Switch Type
USWITCH

ACK Programs the switch to


acknowledge all alarms and
troubles

SSWITCH

TSWITCH

USWITCH
DE -- Programs the switch to
disable or enable a specific point.
This mode is typically used with a 2position maintained or a 3-position
switch, and is not intended to be
used with a 2-position momentary
switch. Use TDE (toggle
disable/enable) with a 2-position
momentary.

OSWITCH
SSWITCH

TSWITCH

USWITCH
LFACK Programs the switch to
acknowledge Fire Alarms.
LSR Programs the switch to
perform a system reset.
LSS Programs the switch to
perform a signal silence.

OSWITCH

SSWITCH

Open

Acknowledges all alarms and troubles

Normal

Mode OFF

Short

Acknowledges all alarms and troubles

Normal

Mode OFF.

Limited

Acknowledges all alarms and troubles

Normal

Mode OFF

Normal

Mode OFF

Short

Acknowledges all alarms and troubles

Limited

Acknowledges all alarms and troubles

Open

Enables the referenced point.

Normal

Disables the referenced point.

Short

Enables the referenced point.

Normal

Disables the referenced point.

Limited

Enables the referenced point.

Normal

Disables the referenced point.

Normal

Mode OFF

Short

Disables the referenced point

Limited

Enables the referenced point

Open

Performs the modes action i.e.,


acknowledges alarms, performs reset, etc.

Normal

Mode OFF

Short

Performs the modes action i.e.,


acknowledges alarms, performs reset, etc.

Normal

Mode OFF

Limited

Performs the modes action i.e.,


acknowledges alarms, performs reset, etc.

Normal

Mode OFF

LTACKPrograms the switch to


acknowledge troubles.

Normal

Mode OFF

LTEST Programs the switch to


perform a lamp test.

Short

Performs the modes action i.e.,


acknowledges alarms, performs system
reset, etc.

Limited

Performs the modes action i.e.,


acknowledges alarms, performs reset, etc.

TSWITCH

Continued on next page


6-33

Technical Manuals Online! - http://www.tech-man.com

Programming Cards

OSWITCH

Circuit State and Result

Programming a 24 Point I/O Card, Continued

Programming an Input Device


(Two- or Three-Position
Switch) (continued)
Table 6-11. Input Modes (continued)
Mode

Switch Type
USWITCH

ONOFF Programs the switch to


turn the referenced point ON or
OFF. This mode is typically used
with a 2-position maintained or a 3position switch, and is not intended
to be used with a 2-position
momentary switch.

OSWITCH

SSWITCH

TSWITCH

USWITCH
PBH Push Button Hold. This
mode programs the switch to turn a
point ON and hold it ON. Point
must be turned OFF by Custom
Control or system reset.

OSWITCH
SSWITCH

TSWITCH

USWITCH
PBT Push Button Track. This
mode allows the reference address
to track the state of the switch. The
point turns ON if the switch is active
and turns OFF if the switch is not
active. This mode is intended for
use with a 2 position momentary or
push button switch.

OSWITCH
SSWITCH

TSWITCH

Circuit State and Result


Open

Turns point ON

Normal

Turns point OFF

Short

Turns point ON

Normal

Turns point OFF

Limited

Turns point ON

Normal

Turns point OFF

Normal

Mode OFF

Short

Turns point ON

Limited

Turns point OFF

Open

Turns point ON and holds it ON.

Normal

Mode OFF

Short

Turns point ON and holds it ON.

Normal

Mode OFF

Limited

Turns point ON and holds it ON.

Normal

Mode OFF

Normal

Mode OFF

Short

Turns point ON and holds it ON.

Limited

Turns point ON and holds it ON.

Open

Turns referenced point ON.

Normal

Turns referenced point OFF

Short

Turns referenced point ON.

Normal

Turns referenced point OFF

Limited

Turns referenced point ON.

Normal

Turns referenced point OFF

Normal

Turns referenced point OFF.

Short

Turns referenced point ON.

Limited

Turns referenced point ON.


Continued on next page

6-34

Technical Manuals Online! - http://www.tech-man.com

Programming a 24 Point I/O Card, Continued

Programming an Input Device


(Two- or Three-Position
Switch) (continued)
Table 6-11. Input Modes (continued)
Mode

USWITCH

Not Applicable

OSWITCH

Not Applicable

SSWITCH

Not Applicable

TSWITCH

Not Applicable

USWITCH
TDE Programs the switch to
toggle (reverse) the disable/enable
state of the point. This mode is
intended for use with a 2-position
momentary switch.

OSWITCH
SSWITCH

TSWITCH

USWITCH
TOF -- Programs the switch to
toggle (reverse) the ON/OFF state
of the point. This mode is intended
for use with a 2-position momentary
switch.

Circuit State and Result

OSWITCH
SSWITCH

TSWITCH

Programming Cards

SMPL Mode indicates that an


SMPL equation is being used to
program the switch.

Switch Type

Open

Toggles the disable/enable state of point

Normal

Mode OFF.

Short

Toggles the disable/enable state of point.

Normal

Mode OFF.

Limited

Toggles the disable/enable state of point.

Normal

Mode OFF

Normal

Mode OFF

Short

Toggles the disable/enable state of point.

Limited

Toggles the disable/enable state of point.

Open

Toggles the ON/OFF state of the point.

Normal

Mode OFF

Short

Toggles the ON/OFF state of the point.

Normal

Mode OFF

Limited

Toggles the ON/OFF state of the point.

Normal

Mode OFF

Normal

Mode OFF

Short

Toggles the ON/OFF state of the point.

Limited

Toggles the ON/OFF state of the point.


Continued on next page

6-35

Technical Manuals Online! - http://www.tech-man.com

Programming a 24 Point I/O Card, Continued

Programming an Output Point

1.

Click on the Device Type field and select the GRAPHOUT device type.

2.

Click on the point type field and select one of the following:

LAMP. Specifies that the output is an LED.

PIEZO. Specifies that the output is an audible piezo device. Piezo


beeps to indicate an alarm, and sounds a steady tone to indicate a
trouble or supervisory condition.

RELAY. Specifies that the output is a generic relay.

RRELAY. Specifies that the output is a relay that activates upon


ALARM and turns OFF upon reset.

3.

Select the mode (operation) of the output. Refer to Table 6-15 for specific
information on the modes.

4.

Click on the Ref Addr field and select the point used to trigger the output.
Table 6-15. Output Device Modes
Mode

Application

DISABLE

Output activates when the referenced point is


Disabled.

FIRE

Output activates when the state of the referenced


point is in an ALARM condition.

LF

Output activates when any ALARM condition occurs.

LS

Output activates when a Supervisory condition occurs.

LT

Output activates when a Trouble condition occurs.

OFF

Output activates when the state of the referenced


point is OFF.

ON

Output activates when the state of the referenced


point is OFF.

SMPL

Output activates when a Custom Control equation


executes.

SUPERV

Output activates when a Supervisory condition occurs


to the referenced point.

TROUBLE

Output activates when a Trouble condition occurs to


the referenced point.

6-36

Technical Manuals Online! - http://www.tech-man.com

Programming an LCD Annunciator Card

Introduction

External Graphical LCD Annunciator contains LEDs that can be


programmed to monitor the state of specific points. This product is
available for international systems only.

LCD Annunciator contains LEDs that can be programmed to monitor the


state of specific points.

Double click on the card icon that represents the annunciator. A screen similar
to the following appears. The names of the points differ if you are programming
an External LCD Annunciator.

Figure 6-22. LCD Annunciator


Step 2. Programming
External Graphical LCD
Annunciator Switches

The External LCD Annunciator contains push button switches that can be used
to control outputs. Programming these switches involves setting a device type,
point type, mode (operation for the switch), and reference point (the point
affected by the switches mode).
1.

Click on the Device Type column to the right of the switch that you want to
program and select the LCDIN choice.
Continued on next page

6-37

Technical Manuals Online! - http://www.tech-man.com

Programming Cards

Step 1. Open the LCD


Annunciator Card Screen

The 4010 can use either of the following annunciators:

Programming an LCD Annunciator Card, Continued

Step 2. Programming
External Graphical LCD
Annunciator Switches
(continued)

2.

Click on the Point Type column and select USWITCH (2-position,


unsupervised switch.

3.

Click on the Mode and select the operation of the switch.


Table 6-16. Modes for External LCD Switches
Mode

Application

ACK

Programs the switch to acknowledge all alarms and


troubles.

DE

Programs one switch position to disable the point and


another switch position to enable the point.

LFACK

Programs the switch to acknowledge Fire Alarms.

LSR

Programs the switch to perform a system reset.

LSS

Programs the switch to perform a signal silence.

LTACK

Programs the switch to acknowledge troubles.

LTEST

Programs the switch to perform a lamp test.

ONOFF

Programs one position of the switch to turn the point ON


and another switch position to turn the point OFF.

PBH

Programs the switch to turn the point ON and hold it ON.


Point must be turned off by Custom Control or system
reset.

PBT

Programs the referenced address to track the state of


the switch, turning ON when the switch is active and
turning OFF when the switch is inactive.

SMPL

Indicates that an SMPL equation is being used to


program the switch.

TDE

Programs the switch to toggle the Disable/Enable state


of the point.

TOF

Programs the switch to toggle the ON/OFF state of the


point.

4.

Click on the Ref. Addr field and select the point affected by the switch.

5.

Use the Keyswitch checkboxes, located in the Access Levels panel of


Figure 6-22, if you want to require the use of a key to acknowledge Alarms,
Fire Alarms, Supervisory events, Trouble events, or System events.
Continued on next page

6-38

Technical Manuals Online! - http://www.tech-man.com

Programming an LCD Annunciator Card, Continued

Step 3. Programming LEDs

Both the External Graphical LCD Annunciator and the LCD Annuciator contain
LEDs that can be used to monitor the state of a point, illuminating a specific
color when the state of the point is equal to a specific condition.
1.

Click on the Device Type field corresponding to the LED that you want to
program and choose Multicolor.

2.

Click on the Point Type field and choose one of the following. Note that
LED1 and LED2 illuminate Yellow or Red, whereas LED3 illuminates
either Yellow or Green.

3.

Available Point Types

LED 1

Select Yellow for a Yellow LED


Select Non Yellow for a Red LED

LED 2

Select Yellow for a Yellow LED


Select Non Yellow for a Red LED

LED 3

Select Yellow for a Yellow LED


Select Non Yellow for a Green LED

Click on the Mode drop down list box. Choose the mode (State) that must
be true to illuminate the LED. Refer to the following table for details on the
available modes.
Table 6-17. Modes for User-Defined LEDs
Mode

Meaning

Disable

LED illuminates when the state of the REF ADDR


(point) is DISABLED.

Fire

LED illuminates when the state of the REF ADDR


(point) goes into ALARM

LF

LED illuminates when the ALARM ACK button on the


panel is pushed.

LS

LED illuminates when the SUPV ACK button on the


panel is pushed.

LT

LED illuminates when the TROUBLE ACK button on


the panel is pushed.

OFF

LED illuminates when the state of the REF ADDR


(point) is OFF.

ON

LED illuminates when the state of the REF ADDR


(point) is ON

SMPL

LED illuminates when the state of a Custom Control


equation(s) is TRUE.

SUPERV

LED illuminates when the state of the REF ADDR


(point) goes into SUPERV.

TROUBLE

LED illuminates when the state of the REF ADDR


(point) goes into ALARM
Continued on next page
6-39

Technical Manuals Online! - http://www.tech-man.com

Programming Cards

LED

Programming an LCD Annunciator Card, Continued

Step 3. Programming LEDs


(continued)

Programming Events

The Event Reporting panel of the LCD Annunciator card programming screen
allows you to select which events are reported at the annunciator.

Click on the Ref Address field and associate a point with the mode you set
in Step 3. The list that appears depends on the Mode selection. The Ref
Address list contains either physical points, pseudo points, list points, or no
entries.

Click on the check boxes that correspond to the events that should be routed to
the annunciator. The list is as follows:

Silence / Reset Events


SMPL Print Statements
Walk Test Events
Fire Alarm Events
Trouble Events
Supervisory Events

6-40

Technical Manuals Online! - http://www.tech-man.com

Chapter 7
Programming Points
Blank Page

Overview

This chapter provides instructions for programming each points device type,
point type, and custom label.

In this Chapter

Refer to the following page for specific information on a topic.


Topic

See Page #

Overview Point Tab

7-2

Programming a Points Hardware Device Type

7-5

Programming a Points Software Point Type

7-8

Programming Custom Labels

7-11

Programming Points

7-1

Technical Manuals Online! - http://www.tech-man.com

Overview Point Tab

Introduction

The Point Tab, shown in Figure 7-1, allows you to view all points in the system,
and to add and edit point information. This section describes the general
features AutoFill, Word Library, etc. of the Point Tab screen.

Splitter
Bar

Figure 7-1. Point Tab


Splitter Bar

Use the Splitter Bar to adjust the size of the window containing points. Position
the cursor over the Splitter Bar, click and hold the mouse button, drag the bar to
its new position and release the mouse button.

Site, Card, and Point Views

The View panel allows you to view points in three ways. Each view is selected
by clicking on the corresponding radio button in the View panel (top right
Figure 7-1).

Site View uses the site tree to display the points.


Card View breaks down the points by card, listing each cards points
beneath an icon that represents the card.
Point View allows you to see a listing of all points in the system, arranged
numerically.

Sort Order

The Sort Order panel, located in the top right of Figure 7-1, allows you to
display points in ascending or descending numerical order. Use the two radio
buttons Ascending and Descending to set the sort order.

Word Library

The Custom Label Suggestion box displays suggestions from the programmers
word library as you create custom labels. If you wish to insert the word
displayed in this box, press CTRL + F and the word is inserted in the correct
position in the custom label.
Continued on next page
7-2

Technical Manuals Online! - http://www.tech-man.com

Overview Point Tab, Continued

AutoFill

1.

Enter the text that you want to automatically enter in the Custom Label
AutoFill text entry box.

2.

Choose the points to which the text will be added, as follows:

Single Point. Click on the point to highlight it. Next, click on the
AutoFill button. The text is added to the Custom Label field of the
selected point.

Range of Adjoining points. Click on the first point in the range. Hold
down the shift key and click on the last point in the range. Click on the
AutoFill button. The text is added to the Custom Label field for the
range of points.

Range of Non-Adjoining Points. Hold down the CTRL key and click
on the points. Each point highlights to show it is selected. When all
points have been selected, release the CTRL key and click on the
AutoFill button. The text is added to the Custom Label field for all of
the selected points.

Spell check allows you to validate the spelling of custom labels, and can be used
to check either selected points or all points.
1.

Make sure Point View is selected.

2.

Select the points to check as follows:

Single Point. Click on the Selected Points button in the Custom Label
Spell Check panel and click on the point to highlight it. Next, click on
the AutoFill button. The text is added to the Custom Label field of the
selected point.

Range of Adjoining Points. Click on the Selected Points button in the


Custom Label Spell Check panel and click on the first point in the
range. Hold down the shift key and click on the last point in the range.
Click on the AutoFill button. The text is added to the Custom Label
field for the range of points.

Range of Non-Adjoining Points. Click on the Selected Points button


in the Custom Label Spell Check panel and hold down the CTRL key
and click on the points. Each point highlights to show it is selected.
When all points have been selected, release the CTRL key and click on
the AutoFill button. The text is added to the Custom Label field for all
of the selected points.

All Points. Click on the All Points button in the Custom Label Spell
Check panel.
Continued on next page

7-3

Technical Manuals Online! - http://www.tech-man.com

Programming Points

Custom Label Spell Check

AutoFill allows you to automatically add text to the Custom Label field. It is
possible to select either a single point, a range of adjoining points within the list,
or a group of non-adjoining points.

Overview Point Tab, Continued

Custom Label Spell Check


(continued)

3.

Click on the rectangular Check button, located in the Custom Label Spell
Check panel.
Words that are not contained in the programmers dictionary are flagged by
the following dialog.

Figure 7-2. Spell Check Correction Dialog


4.

Choose an option, as follows:

Change. Changes spelling of the highlighted word to the suggestion.


Ignore. Treats the word as correct for the one highlighted occurrence.
Change All. Changes all occurrences of the misspelled word to the
suggestion.
Ignore All. Treats all occurrences of the word as correctly spelled.
Add to User Dict. Inserts the word into the dictionary.

7-4

Technical Manuals Online! - http://www.tech-man.com

Programming a Points Hardware Device Type

Introduction

A points hardware device type identifies the specific hardware device being
programmed. The programmer supports the following general categories of
hardware device type.
Each hardware device type corresponds to a specific Product ID (PID).
Appendix A of this manual lists the PIDs that apply to each device type.

Procedure

1.

Move to the points device type field and double click with the left mouse
button.
A context-sensitive list of device types appears, meaning the list that
appears for an IDNet point is different from the list that appears for a NAC
point.

2.

Click on the device type that is appropriate for the point being programmed.
Refer to Table 7-1 for quick reference information, or refer to Appendix A
for detailed information on the hardware device types.
Table 7-1. Device Types Quick Reference
Class

Device Type

NAC

SIGA
SIGB

Class A signal (1&2, 3&4 in pairs)


Class B signal (1&2, 3&4 in pairs)

Input

INPUT
GRAPHIN

Input
Graphic I/O input

Output

GRAPHOUT
OUTPUT

Graphic I/O output


Output

Relay

RELAY
RIAM

Unsupervised Relay
Relay IAM
Continued on next page

7-5

Technical Manuals Online! - http://www.tech-man.com

Programming Points

MAZAM
MBZAM

Addressable Detector Base


Addressable Pull Station
Canadian 2-stage Pull Station
Communicating Line Powered
ISO
Class A Monitor ZAM (T-sense)
Class B Monitor ZAM (T-sense)

Monitor

ADRDET
ADRPUL
CANPUL
ISO

Application

Programming a Points Hardware Device Type, Continued

Procedure (continued)
Table 7-1. Device Types Quick Reference (continued)
Class
SSD
(Simplex
Smoke
Detector)

IDNet

Device Type
Heat
IHEAT
IION
IOHEAT
ION
IPHOTO
OHEAT
PHOTO
RHEAT
RION
ROHEAT
RPHOTO
SHEAT
SION
SOHEAT
SPHOTO
4009A
4009A8
R4009A
R4009A8
ADRPUL
CANPUL
HEAT
IAM
IHEAT
IION
IOHEAT
ION
IPHOTO
KACPULL
MAZAM
MBZAM
OHEAT
PHOTO
QIPHOTO
QPHOTO
QRPHOTO

Application
Heat
Heat with Isolator base
Ion with Isolator base
Rate of rise heat with isolator base
ION
Photo with Isolator
Rate of rise heat
Photo
Heat with relay
ION with relay
Rate of rise heat with relay
Photo with relay
Heat with sounder
ION with sounder
Rate of rise heat with sounder
Photo with sounder
4009A with 4 NACs
4009A with 8 NACs
4009A 4 NACs with Repeater
4009A 8 NACs with Repeater
Addressable Pull Station
Canadian 2-stage pull station
Heat Detector
Line Power Sup. IAM with
TrueSense
Heat Detector with Isolator
ION Detector with Isolator
TureAlarm Heat Detector with ROR
and Isolator
Ionization Detector
Photo with Isolator Base
KAC Pull Station
Class A Monitor ZAM (TrueSense)
Class B Monitor ZAM (TrueSense)
Heat Detector with ROR
Photoelectric Detector
Quick Connect Photo with Isolator
Quick Connect Photo
Quick Connect Photo with relay
Continued on next page

7-6

Technical Manuals Online! - http://www.tech-man.com

Programming a Points Hardware Device Type, Continued

Procedure (continued)
Table 7-1. Device Types (continued)
Class
IDNet

Device Type
QSPHOTO
RHEAT
RIAM
RION
ROHEAT
RPHOTO
SHEAT
SION
SOHEAT
SPHOTO
XIPHOTO
XPHOTO
XRPHOTO
XSPHOTO

ANALOG
COMNTBL
DIGTAL
DTMASTERIN
DTMASTEROUT1
DTMASTEROUT2
LIST
STATUS

7-7

Technical Manuals Online! - http://www.tech-man.com

Quick Connect Photo with sounder


Heat detector with relay
Relay IAM
ION Detector with Relay
Heat Detector with ROR and Relay
Photo with Relay
Heat Detector with sounder
Ion Detector with sounder
Heat Detector with ROR and
Sounder
Photo with sounder
Extra-sensitive Photo ISO
Extra-sensitive Photo
Extra-sensitive Photo with Relay
Extra-sensitive Photo with
Sounder
Analog Pseudo
Network Common Trouble
Digital Pseudo
Master Switch Input
Master LED Output Red/Yellow
Master LED Output Red/Green
List
Status

Programming Points

Misc.
Device
Types

Application

Programming a Points Software Point Type

Introduction

A point type determines the following:

The message displayed on the 4010s LCD when changes occur to the state
of the points circuit.

The way in which the system operates (for example, initiate an Alarm,
Trouble, or Supervisory action) when changes occur to the state of the
points circuit.

Example. Compare the FIRE Point type with the SO (normally open sprinkler
monitor) point type. When the circuit state of a point programmed with either type
is Normal, the system operates normally (i.e., no Alarm/Trouble/Supervisory
messages and no system action occurs).
Notice, however, that the operation of the system is different if a Current Limited
condition occurs. When a current limited condition occurs for a device associated
with the FIRE point type, the system displays Fire Monitor Zone on the LCD,
illuminates the FIRE LED, and triggers any automatic and custom Alarm response
(i.e., activate NACs, etc.). Contrast this with what happens when a current limited
condition occurs for a device associated with the SO point type. In this case, an
abnormal physical state exists. To have actions occur as a result of the sprinkler
monitors change in state, you would need to write a Custom Control equation that
monitors the point for this circuit state and then executes specific output actions if
an abnormal physical state occurs.
Circuit
Status
FIRE

SO

Procedure

LCD Text

System Operation

Normal
Limited
Open
Short

Fire Monitor Zone


Fire Monitor Zone
Fire Monitor Zone

Normal
Fire Alarm
Open Trouble
Fire Alarm

Normal
Limited
Open
Short

Sprinkler Monitor
Sprinkler Monitor
Sprinkler Monitor

Normal
Abnormal
Open Trouble
Abnormal

Follow these steps to define a points software point type.


Note: Do not use the PC Programmer to change the point type of a suppression
release point; doing this causes the PC Programmer to change the point type
back to its default setting. To change the point type of a suppression release
point, you must use the front panel programmer.
1.

Click on the point whose point type you want to program.

2.

Move to the points Point Type field and double click with the left mouse
button.

3.

Click on the appropriate point type. Refer to Table 7-2 for a quick
reference of the point types; refer to Appendix A for detailed descriptions of
the point types.
Continued on next page
7-8

Technical Manuals Online! - http://www.tech-man.com

Programming a Points Software Point Type, Continued

Procedure (continued)
Table 7-2. Point Types
Category

Point Type
ABORT
DAMPER
DUCT
EMERG
FIRE
FLAME
FPUMP
GENMON
GVMON
HEAT
LATSUPV
PULL
S2STAGE

SUPABRT
SUPDET
SUPDUMP
SUPPRES
SUPV
TROUBLE
UTILITY
VSFIRE
VSMOKE
VSPULL
WATER
WSO

Continued on next page

7-9

Technical Manuals Online! - http://www.tech-man.com

Programming Cards

Monitor

SDUCT
SFIRE
SFPUMP
SGENMON
SMOKE
SO
SPULL
STYLEC

Application
Abort zone (pre-signal)
Damper Monitor (open/closed)
Duct Detector
Combination Fire/Emergency Alarm
Fire Alarm (Generic)
Flame Detector
Fire Pump Monitor
Generator Monitor
Generic verified Monitor
Heat Detector
Latching Supervisory
Manual Pull Station
2-stage Monitor (abn=presignal;
short=alarm)
Supervisory Duct Detector
Combination Smoke Fire Zone
Supervisory Fire Pump Monitor
Supervisory Generator Monitor
Smoke detector
Sprinkler supervisory (normally open)
Combination Smoke/Pull Zone
Style C Monitor Point (current
limit=fire alarm; short/open=trouble)
Suppression release abort zone
Suppression release detector zone
Suppression release manual dump
Suppression release pressure monitor
Supervisory (generic)
Trouble Monitor
Non-alarm utility with Tri-state ability
Verified Smoke/Fire Zone
Verified Smoke Zone
Verified combination Smoke/Pull
Zone
Waterflow Switch
Waterflow Switch/Sprinkler
supervision (Normally Open)

Programming a Points Software Point Type, Continued

Procedure (continued)
Table 7-2. Point Types (continued)
Category

Point Type
AHUF
AHUO
AHUR
ALTERN
BSIGNAL

Control

DHOLDER
PRIMARY
RELAY
RSIGNAL
RVISUAL
RWATER
SIGNAL
SSIGNAL
SUPREL
SUPV

LAMP
OSWITCH

24 Point I/O

PIEZO
RELAY
RRELAY
SSWITCH
TSWITCH
USWITCH

7-10

Technical Manuals Online! - http://www.tech-man.com

Application
AHU OFF Relay (Dual Relay
Control)
AHU ON Relay (Dual Relay
Control)
AHU ON/OFF Relay (Signal
Relay control)
Alternate Elevator Capture
Trouble/Supervisory Bell Signal
(on until ACK)
Door Holder Control
Primary Elevator Capture
Generic Relay
Alarm Signal (on until reset)
Visual (on until reset)
Waterflow Signal (on until reset)
Generic Signal (no default
operation)
Alarm Signal (on until silence)
Suppression (Agent Discharge)
Release Output
Sprinkler Supervisory Signal (on
until ACK)
Lamp Output
2-position switch (open,
supervised)
Piezo output
Generic Relay
Relay (on until reset)
2-position switch (open/short
supervised)
3-position switch (open,
supervised)
2-position switch (unsupervised)

Programming Custom Labels

Introduction

Custom Labels provide a means of adding custom text descriptions to a points


Custom Label field.

Procedure

1.

Click on the point whose label you want to program.

2.

Move to the points Custom Label field and double click with the left
mouse button.
A flashing cursor appears, indicating that you should enter text.

3.

Edit the label. Refer to Overview at the beginning of this chapter for
information on using the AutoFill feature to automatically add text to the
Custom Label field.

Programming Points

7-11

Technical Manuals Online! - http://www.tech-man.com

This page blank

Technical Manuals Online! - http://www.tech-man.com

Chapter 8
Programming Lists
Introduction

This chapter describes editing the name of a list, and adding or deleting points
from a list.

In this Chapter

Refer to the following page for specific information on a topic.


Topic

See Page #

Overview List Tab

8-2

Naming Lists and Adding/Deleting Points

8-4

Programming Lists

8-1

Technical Manuals Online! - http://www.tech-man.com

Overview List Tab

Accessing the List Tab

The List Tab allows you to build or edit lists. Click on the List Tab at the top of
the screen to display the list-editing window.

Figure 8-1. List Tab, Showing List Editing Window


The system maintains the following lists:

Icons used within the Screen

Lists 1 through 3 use a pre-assigned label and are auto-generated by the


programmer.

Lists 4 through 7 use a pre-assigned label but are not auto-generated.

Lists 8 through 12. These are lists containing suppression release points.

Lists 26 through 50 are available for user-defined requirements.

Three icons are used to show the status of a list. These icons appear to the left
of the lists number.

A page represents a list that contains no points.


A book represents a list containing points.
An open book represents an open list, and displays the contents of the list
immediately below the open book icon.
Continued on next page

8-2

Technical Manuals Online! - http://www.tech-man.com

Overview List Tab, Continued

Sorting the Point Display

The right side of the List window contains the points that can be added to
system and user-defined lists. You can sort and filter this list as follows:
1.

Click on the View button. A dialog similar to the following appears.

Figure 8-2. Point Display Filter


2.

Select the Sort/Filter options as follows:


Change the view to a Site-, Card-, or Point-specific view by clicking on
the appropriate radio button in the View panel. Site View shows a list
of the points grouped by site information. Card View organizes the
points according to which card they are associated with. Point View is
the default view. It displays a numerical list of all points.

b.

Choose Ascending or Descending order. Ascending order lists the


points from highest number to lowest and descending lists the points
from lowest to highest.

c.

Click on the Device drop down list box. This selection allows you to
display only points with a specific device type. Choose All to see all
points.

d.

Click on the Point drop down list box. This selection allows you to
display only points with a specific point type. Choose All to see all
points.

8-3

Technical Manuals Online! - http://www.tech-man.com

Programming Lists

a.

Naming Lists and Adding/Deleting Points

Naming a List

Adding Points

Use the following procedure to edit the name of any user-defined list. (Note that
you cannot change the name of system-defined lists.)
1.

Double click on the Description field to the right of the list number that you
want to define.

2.

Edit the text as appropriate.

Points contained on the right hand side of the List window are added to a list as
follows:
1.

2.

Deleting Points

Highlight the points that you want to add to the list.

Single Point. Click on the point to highlight it.

Range of Adjoining points. Click on the first point in the range. Hold
down the shift key and click on the last point in the range.

Range of Non-Adjoining Points. Hold down the CTRL key while


clicking on each point. Each point highlights to show it is selected.
When all points have been selected, release the CTRL key.

Hold down the left mouse button and drag the points into the list area.
While continuing to hold down the mouse button, position the cursor
directly over the list to which you want to add the points and release the
mouse button.

Delete points from a list, as follows:


1.

Click on the + sign in the box to the left of the book that represents the list
from which you want to delete points.

2.

Select the points to delete, as follows:

3.

Single Point. Click on the point to highlight it.

Range of Adjoining points. Click on the first point in the range. Hold
down the shift key and click on the last point in the range.

Range of Non-Adjoining Points. Hold down the CTRL key while


clicking on each point. Each point highlights to show it is selected.
When all points have been selected, release the CTRL key.

Press the Delete key, or hold down the right mouse button and select the
Delete option.

8-4

Technical Manuals Online! - http://www.tech-man.com

Chapter 9
Creating a Site Tree

This chapter describes creating a site tree, which is a tree-like representation of


your building and its fire alarm points.

In this Chapter

The remainder of this chapter discusses the following topics:


Topic

See Page #

Overview

9-2

Building a Site Tree

9-5

9-1

Technical Manuals Online! - http://www.tech-man.com

Creating a Site Tree

Introduction

Overview

Introduction

A site tree allows you to create labels for specific, physical areas of a building
and assign fire alarm points to these labels. When complete, a site tree
graphically depicts the layout of the site and gives an indication of every points
location within the site.
A site tree reads from left to right, with general divisions of the site (such as
Building A or West Wing) listed on the left side and specific areas of the site
(such as R&D lab or Boiler) listed on the right side. Points are listed on the far
right of the tree and are the smallest unit that can be added to a site tree.
Figure 9-1 shows a typical site tree.

Figure 9-1. Typical Site Tree


Terms and Concepts

Important terms and concepts related to a site tree include:

Book icons represents element of the tree that contain subordinate elements.
In Figure 9-1, for example, the 1ST FLOOR book indicates that some
number of building components (either points or smaller divisions of the
building) are contained within it. A plus (+) sign to the left of a closed book
indicates that the contents of the element are not currently displayed.
Conversely, a minus (-) sign to the left of an open book indicates that the
contents of the element are currently displayed.

A page icon represents an element of the tree that contains no subordinate


elements. Points, which are the smallest division of a site tree, are always
represented by a page.
Continued on next page

9-2

Technical Manuals Online! - http://www.tech-man.com

Overview, Continued

The Site Tab

Selecting the Site Tab displays a window similar to the one shown in Figure 9-2.
The left side of the window is the area in which the site tree is created. The
right side of the window lists the points that can be added to the site tree.

The terms Level and Leaf are used when inserting components into the site
tree. These are relative terms used to indicate where an element will be
inserted in relation to the currently highlighted element. A level indicates
that the new element will be added at a level equal to the selected element,
whereas leaf indicates that the new element is subordinate to the highlighted
element. In Figure 9-1, for example, the highlight is on OFFICE 2.
Inserting a Level would add an element equal to OFFICE 2. Inserting a
Leaf would add an element that is subordinate to OFFICE 2.

Figure 9-2. Site Tab Window


Use the View button shown at the top of the points list to change, filter,
and sort the way in which points are displayed in the list. You can sort and filter
the Points list as follows:
1.

Click on the View button. A dialog similar to the one shown in Figure 9-3
appears.
Continued on next page

9-3

Technical Manuals Online! - http://www.tech-man.com

Creating a Site Tree

Terms and Concepts


(continued)

Overview, Continued

The Site Tab (continued)

Figure 9-3
2.

Select the Sort/Filter options as follows:


a.

Change the view to a Site-, Card-, or Point-specific view by clicking on


the appropriate radio button in the View panel. Site view shows a list
of the points grouped by the Site information. Card View organizes the
points according to which card they are associated with. Point View is
the default view. It displays a numerical list of all points.

b.

Choose Ascending or Descending order. Ascending order lists the


points from highest number to lowest and descending lists the points
from lowest to highest.

c.

Click on the Device drop down list box. This selection allows you to
display only points with a specific device type. Choose All to see all
points.

d.

Click on the Point drop down list box. This selection allows you to
display only points with a specific point type. Choose All to see all
points.

9-4

Technical Manuals Online! - http://www.tech-man.com

Building a Site Tree

Step 1. Add the Buildings

It is helpful to identify the major components of the site before you begin to
create the site tree. At a minimum, you probably want to include entries for
each of the following in the tree.

Each building
Each floor within the building
Each component (office, lab, hallway, duct, etc.) of each floor that contains
points

1.

Right click on the blank portion of the Site screen. When the list of choices
appears, select Insert Level.
An entry, containing a Page icon and the word *Level*, appears.

2.

Double click on *Level* and type the building name in the text entry box.
The name must be 10 characters or less.

3.

To add an additional building, right click on the entry that you just added
(the building ) and select Insert Level.
Insert Level adds an element to the tree that is equal to the currently
selected element. In this case, another entry that is equal to the building.

4.
Step 2. Add Floors

Double click on *Level* and type a building name.

Add floors to the building, as follows:


1.

Right click on the entry that represents a building. When the list of choices
appears, click on Insert Leaf.
An entry, containing a Page icon and the word *Leaf*, appears. This entry
is indented to the right of the building entry.

2.

Double click on *Leaf* and enter the name of the floor. The text
description must be 10 characters or less.

Repeat Steps 3 and 4, highlighting the icons for other buildings as necessary, to
add all other floors.
Continued on next page

9-5

Technical Manuals Online! - http://www.tech-man.com

Creating a Site Tree

Introduction

Building a Site Tree, Continued

Step 3. Add Floor


Components

Floor components such as offices, hallways, ducts, etc. are added by first
selecting the floor to which you want to add the components and then selecting
Insert Leaf, as follows:
1.

Double click on the floor to which you want to add components. A menu of
options appears.

2.

Choose Insert Leaf.


A line containing a page icon, followed by the label *Leaf*, appears. This
line is beneath and to the right of the highlighted floor.

3.

Double click on *Leaf*. Enter a name for the floor in the text entry box.
The name must be 10 characters or less.

Repeat these steps, choosing different floors as required, to add other floor
components.
Step 4. Add Points

Points are added to the tree as follows:


1.

Move to the list of points on the right side of the screen. Click on the point.
A page icon, containing a + sign appears.

2.

Drag the point into the site tree, positioning it over the floor component to
which it should be added.

3.

Release the mouse button. The point is added to the floor component.

Repeat these steps until all points are added to the site tree.

9-6

Technical Manuals Online! - http://www.tech-man.com

Chapter 10
Creating Custom Control Equations
Introduction

This chapter provides an overview of the Simplex Multi-functional


Programming Language (SMPL), also known as Custom Control, and describes
using the PC Programmer application to program Custom Control equations.

In this Chapter

The remainder of this chapter discusses the following topics:


Topic

See Page #
10-2

Overview Components of a CC Equation

10-4

Step 1. Add a New Equation to the User Program

10-6

Step 2. Add Additional Inputs and Outputs to an


Equation

10-7

Step 3. Edit Each Input Statements Properties

10-8

Step 4. Edit an Output Statements Properties

10-19

10-1

Technical Manuals Online! - http://www.tech-man.com

Custom Control

Overview CC Tab

Overview CC Tab

CC Tab

The CC Tab, shown in Figure 10-1, provides a graphical means of adding and
editing custom control equations. Points appear in a list on the right side of the
CC window and equations appear on the left side of the window.

Figure 10-1. CC Tab


Use the View button shown at the top of the points list to change, filter,
and sort the way in which points are displayed in the list. You can sort and filter
the Points list as follows:
1.

Click on the View button. A dialog similar to the one shown in Figure 10-2
appears.

Figure 10-2. Point Display Filter


Continued on next page

10-2

Technical Manuals Online! - http://www.tech-man.com

Overview CC Tab, Continued

CC Tab (continued)

2.

Select the Sort/Filter options as follows:


Change the view to a Site-, Card-, or Point-specific view by clicking on
the appropriate radio button in the View panel. Site View shows a list
of the points grouped by the site information. Card View organizes the
points according to which card they are associated with. Point View is
the default view. It displays a numerical list of all points.

b.

Choose Ascending or Descending order. Ascending order lists the


points from highest number to lowest and descending lists the points
from lowest to highest.

c.

Click on the Device drop down list box. This selection allows you to
display only points with a specific device type. Choose All to see all
points.

d.

Click on the Point drop down list box. This selection allows you to
display only points with a specific point type. Choose All to see all
points.

10-3

Technical Manuals Online! - http://www.tech-man.com

Custom Control

a.

Overview Components of a CC Equation

Introduction

Up to 60 Custom Control equations can be programmed for the 4010. Each


equation consists of two sides: an INPUT SIDE, containing one or more Input
Statements and an OUTPUT SIDE, containing one or more Output Statements.
The total number of statements, both input and output must be 6 or less.
An equation can be better understood as an IF/THEN command. IF the
INPUT SIDE is true, THEN execute the OUTPUT SIDE.

Input Statement
Input Statement
End of Inputs

Equation

Output Statement
Output Statement
End of Outputs

Figure 10-3. Example Equation


Input Statements

Input Statements can do either of the following:

Monitor the status of a point, set of points, or list.

Perform a function, such as Delay, Cycle, Compare two values, or


Save/Recall values.

Multiple input statements, located within the same equation, must be separated
by a logical operator (AND or OR). These operators function as follows:

AND Operator. Use the AND Logical operator to link the current input
statement in Series with all previous input statements in an equation. In the
example below, IF the condition of M1-1 is Fire AND the condition of M12 is Fire, then the INPUT SIDE is true and the Output statements (not
shown) execute. If, however, only M1-1 or M1-2 (not both) is in a Fire
state, the INPUT side is not true and the output statements do not execute.

Continued on next page

10-4

Technical Manuals Online! - http://www.tech-man.com

Overview Components of a CC Equation, Continued

Input Statements (continued)

Output Statements

Output statements are the actions that occur when the INPUT Side of an
equation is true. An output consists of an Opcode, the point associated with the
Opcode, and a priority.

OR Operator. The OR Logical operator links the current statement in


Parallel with all previous statements in an equation. In the example below,
IF the condition of M1-1 is Fire OR the condition of M1-2 is Fire, then the
INPUT SIDE is true. In other words, when the status of either M1-1 or M12 becomes Fire, the output statements execute.

Technical Manuals Online! - http://www.tech-man.com

Custom Control

10-5

Step 1. Add a New Equation to the User Program

Procedure

All user-defined CC equations are stored within the User Program, which is
represented by an icon on the left side of the screen. Follow these steps to add a
new equation to the User Program.
1.

Right click on the User icon. See Figure 10-4 for its location.

2.

Highlight Add Equation and click the left mouse button.


An entry similar to the following appears beneath the user program.

Figure 10-4. Adding an Equation

10-6

Technical Manuals Online! - http://www.tech-man.com

Step 2. Add Additional Inputs and Outputs to an Equation

Introduction

Each equation can have up to 6 inputs or outputs in it. Follow these steps to add
additional inputs/outputs to the equation. If the equation appears as a book with
a plus (+) sign to the left of it, click on the + sign to expand the equation.

Adding Additional Inputs

1.

Highlight one of the equations existing input statements and click the right
mouse button.

2.

Click on Add Input.

Adding Additional Outputs

1.

Highlight one of the equations existing output statements and click the
right mouse button.

2.

Click on Add Output.

An additional output appears beneath the highlighted output statement.

10-7

Technical Manuals Online! - http://www.tech-man.com

Custom Control

An additional input appears beneath the highlighted input statement.

Step 3. Edit Each Input Statements Properties

Introduction

An inputs properties specify the behavior of the input (i.e. what operation or
function does the input perform). Properties also define how inputs function in
relation to other inputs. Input Properties are set through the Custom Control
Input dialog. Follow these steps to open this dialog.
1.

Highlight one of the equations input qualifiers and click the right mouse
button. A menu of choices appears.

2.

Click on Properties. A dialog similar to Figure 10-5 appears.

Figure 10-5. Custom Control Input Dialog


3.

Use the AND / OR logical operators to specify whether the input is in series
(AND radio button) or parallel (OR radio button) with all other inputs. If
the Equation has only a single input, skip this step.

4.

Use the NOT Operator to specify that the condition must not be true for the
output to execute. In the following example, the input side of the equation
is true if the condition of M1-1 is Fire and the condition of M1-2 is NOT
fire.

5.

Click on the Opcode and Qualifier list boxes and choose an Opcode and
qualifier. Refer to Table 10-1 for a list of Opcodes and qualifiers.
Continued on next page

10-8

Technical Manuals Online! - http://www.tech-man.com

Step 3. Edit Each Input Statements Properties, Continued

Associating Points with Input


Statements

After defining the Opcode and Qualifier for an input statement, you need to
associate a point with the statement. To do this, follow these steps.
1.

In the list on the right side of the screen, click on the name of the point.

2.

Hold down the left mouse button and drag the highlighted point from the
list to the appropriate Input Statement.

3.

Release the mouse button.

10-9

Technical Manuals Online! - http://www.tech-man.com

Custom Control

Continued on next page

Step 3. Edit Each Input Statements Properties, Continued

Input Opcodes and Qualifiers

Table 10-1 lists the opcodes and their qualifiers and explains their use.
Table 10-1. Input Opcodes and Qualifiers

Opcode

Qualifier

Fire Detect

Application
When the referenced point (for example a smoke, flame,
heat detector) enters an alarm condition, the input condition
is TRUE for approximately second. Any NACs triggered
on the output side of the equation sound until signal
silence. Should another detector then sound, it would
trigger its NACs, allowing the fire condition to be tracked
from one area to another. This functionality is known as
resound.
Refer to the ANY opcode later in this table for information
on using Fire Detect with lists.

Point Status
Allows the status of
a specific point to be
tested for a specific
condition.

Fire

When the referenced point (either a pull station or detector


type device) enters an alarm condition, the input condition
is TRUE until a System Reset is performed.

Fire Ack

When the referenced point enters an alarm condition, the


input condition is TRUE until the alarm is acknowledged.

Trouble

When the referenced point enters a trouble condition, the


input condition is TRUE until the trouble condition is
acknowledged.
When the referenced point enters a supervisory condition,
the input condition is TRUE until the problem condition is
fixed.

Supervisory

Supervisory Ack

For example, turning a sprinkler system OS&Y valve


changes the state of the contacts being monitored and
triggers a Supervisory condition. Although this condition
can be acknowledged, the supervisory condition cannot be
cleared until the OS&Y is restored to its original position.
When the referenced point enters a supervisory condition,
the input condition is TRUE until the supervisory condition
is acknowledged. One way this qualifier might be used
would be to sound a bell in a control room when a point (a
list containing all waterflow points for example) enters a
supervisory condition. In this case, the bell would connect
to a relay that would be referenced on the output side of the
equation, and the input side of the equation would monitor
the list with the Supervisory ACK qualifier. The output (bell)
would turn off only when the supervisory condition is
acknowledged.
Continued on next page

10-10

Technical Manuals Online! - http://www.tech-man.com

Step 3. Edit Each Input Statements Properties, Continued

Input Opcodes and Qualifiers


(continued)
Opcode

Qualifier

Application

Trouble Ack

When the referenced point enters a trouble condition, the


input condition is TRUE until the trouble condition is
acknowledged. Typically used in a similar way to the
Supervisory ACK qualifier.

Physical Normal

The input condition is TRUE when the physical state of the


referenced point is normal.

Physical Abnormal

The input condition is TRUE when the physical state of the


referenced point is abnormal (current limited). One typical
use for this qualifier is to verify the physical location of a fire
in high-rise building. Once the location of the fire is
determined (i.e., locate the detectors with a Physical
Abnormal state), the output side of the equation can be
used to pressurize only the floor(s) with detectors in this
state, and ignore any pull stations (which may or may not
be on the fire floor).

Physical Open

The input condition is TRUE when the physical state of the


referenced point (or its wiring) is open.

Physical Short

The input condition is TRUE when the physical state of the


referenced point (or its wiring) is short.

Disable

The input condition is TRUE when the state of the


referenced point is disabled.

Class A Trouble

The input condition is TRUE when the state of the


referenced point is a Class A Trouble.

ON / Coding

The input condition is TRUE when a signal circuit (NAC) or


relay is ON or coding (i.e., sounding/flashing in march time,
temporal, etc.). A typical use for this qualifier is to use the
relay or NAC as a switch for some other action.

OFF

The input condition is TRUE when a signal circuit (NAC) or


relay is OFF. Also used as a switch for some other action.

Control On

The input condition is TRUE when an IDNet sounder or


relay base is ON.

Control Off

The input condition is TRUE when an IDNet sounder or


relay base is OFF.

Dirty

Input condition is TRUE when the average value for the


referenced point exceeds the fixed threshold (120 analog
units).

Empty

Input condition is TRUE if the referenced point is a list and


it is empty.
Continued on next page

10-11

Technical Manuals Online! - http://www.tech-man.com

Custom Control

Point Status
Allows the status of
a specific point to be
tested for a specific
condition.

Table 10-1. Input Opcodes and Qualifiers

Step 3. Edit Each Input Statements Properties, Continued

Input Opcodes and Qualifiers


(continued)
Table 10-1. Input Opcodes and Qualifiers
Opcode

Point Status
Allows the status of
a specific point to be
tested for a specific
condition.

Qualifier

Application

Abnormal Detect

When the referenced point enters an abnormal condition,


the input condition is TRUE for approximately second.
Any NACs triggered on the output side of the equation
sound until signal silence.

Open Detect

When an open condition occurs to the referenced point, or


its circuit, the input condition is TRUE for approximately
second. Any NACs triggered on the output side of the
equation sound until signal silence.

Short Detect

When a short condition occurs to the referenced point, or its


circuit, the input condition is TRUE for approximately
second. Any NACs triggered on the output side of the
equation sound until signal silence.

ANY Opcode. Input condition is TRUE for second if any


point within the list enters an alarm condition. Any NACs
triggered on the output side of the equation sound until
system silence. Should another detector then sound, it
would trigger its NACs, allowing the fire condition to be
tracked from one area to another. This functionality is
known as resound.
ANY/ALL Used
only with Lists. Note
that with the ANY
Opcode you can
specify how many
points within the list
must meet the
criteria for the input
condition to be true.

Fire Detect

Using a list to implement resound allows a large number of


devices to be monitored by a limited number of equations.
Since the maximum number of equations is limited to 60,
lists provide an efficient way of implementing many system
features.
ALL Opcode. Input condition is TRUE for second only if
ALL points within the list are in alarm.
ANY Opcode. When any point within the list (pull stations
or detector type device) enters an alarm condition, the input
condition is TRUE until a System Reset is performed.

Fire

ALL Opcode. All devices within the list must enter an


alarm condition for the input condition to be TRUE. If this
occurs, the condition is TRUE until a System Reset is
performed.
Continued on next page

10-12

Technical Manuals Online! - http://www.tech-man.com

Step 3. Edit Each Input Statements Properties, Continued

Input Opcodes and Qualifiers


(continued)
Table 10-1. Input Opcodes and Qualifiers
Opcode

Qualifier

Application
ANY Opcode. When any point with the list enters a
supervisory condition, the input condition is TRUE until the
problem condition is fixed.

Supervisory

ANY/ALL Used
only with Lists. Note
that with the ANY
Opcode you can
specify how many
points within the list
must meet the
criteria for the input
condition to be true.

ALL Opcode. All devices within the list must enter an


alarm condition for the input condition to be TRUE. If this
occurs, the condition is TRUE until the alarms are
acknowledged.
ANY Opcode. When any point with the list enters a
supervisory condition, the input condition is TRUE until the
problem condition is fixed.

Supervisory

ALL Opcode. All devices within the list must enter an


supervisory condition for the input condition to be TRUE. If
this occurs, the input condition is TRUE until all problem
conditions are fixed.
ANY Opcode. When any point within the list enters a
trouble condition, the input condition is TRUE until the
trouble condition is fixed.

Trouble

ALL Opcode. All devices within the list must enter a


trouble condition for the input condition to be TRUE. If this
occurs, the condition is TRUE until all trouble conditions are
fixed.
ANY Opcode. When any point within the list enters a
supervisory condition, the input condition is TRUE until the
supervisory condition is acknowledged.

Supervisory Ack

ALL Opcode. All devices within the list must enter a


supervisory condition for the input condition to be TRUE. If
this occurs, the condition is TRUE until all alarms are
acknowledged.
Continued on next page

10-13

Technical Manuals Online! - http://www.tech-man.com

Custom Control

Fire Ack

ALL Opcode. All devices within the list must enter an


supervisory condition for the input condition to be TRUE. If
this occurs, the input condition is TRUE until all problem
conditions are fixed.
ANY Opcode. When any point within the list enters an
alarm condition, the input condition is TRUE until the alarm
is acknowledged.

Step 3. Edit Each Input Statements Properties, Continued

Input Opcodes and Qualifiers


(continued)
Table 10-1. Input Opcodes and Qualifiers
Opcode

Qualifier

Application
ANY Opcode. When any point within the list enters a
trouble condition, the input condition is TRUE until the
troubles are acknowledged.

Trouble Ack

ALL Opcode. All devices within the list must enter a


trouble condition for the input condition to be TRUE. If this
occurs, the condition is TRUE until all troubles are
acknowledged.
ANY Opcode. The input condition is TRUE when the
physical state of any point within the list is normal.

Physical Normal
ALL Opcode. The input condition is TRUE when the
physical state of all points within the list is normal.
ANY/ALL Used
only with Lists. Note
that with the ANY
Opcode you can
specify how many
points within the list
must meet the
criteria for the input
condition to be true.

Physical Abnormal

ANY Opcode. The input condition is TRUE when the


physical state of any point within the list is abnormal
(current limited). One typical use for this qualifier is to
verify the physical location of a fire in high-rise building.
Once the location of the fire is determined (i.e., locate the
detectors with a Physical Abnormal state), the output side
of the equation can be used to pressurize only the floor(s)
with detectors in this state, and ignore any pull stations that
may have been pulled (and may or may not be on the fire
floor).
ALL Opcode. The state of all devices within the list must
be Physical Abnormal for the input condition to be TRUE.

Physical Open

ANY Opcode. The input condition is TRUE when the


physical state of any point within the list (or any points
wiring) is open.
ALL Opcode. The circuit state of all devices within the list
must be open for the input condition to be TRUE

Physical Short

ANY Opcode. The input condition is TRUE when the


physical state of any point within the list (or any points
wiring) is shorted.
ALL Opcode. The circuit state of all devices within the list
must be shorted for the input condition to be TRUE
Continued on next page

10-14

Technical Manuals Online! - http://www.tech-man.com

Step 3. Edit Each Input Statements Properties, Continued

Input Opcodes and Qualifiers


(continued)
Table 10-1. Input Opcodes and Qualifiers
Opcode

Qualifier

Disable

ANY / ALL Used


only with Lists. Note
that with the ANY
Opcode you can
specify how many
points within the list
must meet the
criteria for the input
condition to be true.

ANY Opcode. The input condition is TRUE when any point


within the list is disabled.
ALL Opcode. All points within the list must be disabled for
the input condition to be TRUE.
ANY Opcode. The input condition is TRUE when any
signal circuit (NAC) or relay within a list is ON or coding
(i.e., sounding/flashing in march time, temporal, etc.). A
typical use for this qualifier is to use the relay or NAC as a
switch for some other action.
ALL Opcode. All signal circuits or NACs within the list
must be ON or coding for the input condition to be TRUE.

On Input

ANY Opcode. Used to override any programming in the


system. Typically used by inspectors to override
programming that triggers signals, elevator capture, door
drop, etc. The input condition is TRUE if any point within
the list is ON.
All Opcode. Used to override any programming in the
system. Typically used by inspectors to override
programming that triggers signals, elevator capture, door
drop, etc. The input condition is TRUE if all points within
the list are ON.
Any Opcode. The input is TRUE if any point within the list
has been manually overridden (i.e., controlled from the
panel).

Manual Override
All Opcode. The input is TRUE if all points within the list
have been manually overridden (i.e., controlled from the
panel).

Delay

Constant

Allows the Custom Control input condition to set a delay


equal to a constant value.

Variable

Allows the Custom Control input condition to reference a


value contained in an analog pseudo point. This value can
periodically change, allowing the amount of delay to
change as required by the application.
Continued on next page

10-15

Technical Manuals Online! - http://www.tech-man.com

Custom Control

On/Coding

Application

Step 3. Edit Each Input Statements Properties, Continued

Input Opcodes and Qualifiers


(continued)
Opcode

Table 10-1. Input Opcodes and Qualifiers


Qualifier

Application

Constant

Allows the Custom Control output condition to periodically


execute. The frequency at which the statement executes is
determined by the value of the constant. For example, the
output side of the equation could periodically (every 15
minutes for example) turn a heat pump on if necessary.

Variable

Allows the Custom Control input condition to periodically


execute. The frequency at which the statement executes is
determined by the value of an analog pseudo point. This
analog value can periodically change, allowing the
frequency of the cycle to change as required by the
application.

Seconds (constant)

Allows a time value (for example, an analog pseudo point


timer) to be compared against a constant value (threshold).
This allows some output to be executed as the threshold is
approached (less than), met (equal to), or exceeded
(greater than).

Counts (constant)

Allows a counter (for example, an analog pseudo point


counter) to be compared against a constant value
(threshold). This allows some output to be executed as the
threshold is approached (less than), met (equal to), or
exceeded (greater than).

Counts (variable)

Allows a variable counter (an analog pseudo point counter)


to be compared against another variable counter (another
analog pseudo point counter used as a threshold). This
allows some output to be executed as the threshold is
approached (less than), met (equal to), or exceeded
(greater than).

Cycle

Compare

SAVE. Allows an input condition to be evaluated and its


result stored in a register as a 1 (true) or 0 (false). There
are six registers available for use.
Save/Recall

Save/Recall
Register #

RECALL. Allows an input to recall the value of a register


and use it beside other input conditions. If the recalled
value is false, it prevents the input from being TRUE. If the
recalled value is true (and all other parts of the input are
TRUE), the input condition is TRUE.
Continued on next page

10-16

Technical Manuals Online! - http://www.tech-man.com

Step 3. Edit Each Input Statements Properties, Continued

Input Opcodes and Qualifiers


(continued)
Opcode

ION Smoke Level

XPHOTO Smoke
Level

Qualifier

Application

Smoke level 0.5

Input condition is TRUE when the smoke level for the


referenced photo smoke detector exceeds 0.5 %.

Smoke level 1.0

Input condition is TRUE when the smoke level for the


referenced photo smoke detector exceeds 1.0 %.

Smoke level 1.5

Input condition is TRUE when the smoke level for the


referenced photo smoke detector exceeds 1.5 %.

Smoke level 2.0

Input condition is TRUE when the smoke level for the


referenced photo smoke detector exceeds 2.0 %.

Smoke level 2.5

Input condition is TRUE when the smoke level for the


referenced photo smoke detector exceeds 2.5 %.

Smoke level 3.0

Input condition is TRUE when the smoke level for the


referenced photo smoke detector exceeds 3.0 %.

Smoke level 3.7

Input condition is TRUE when the smoke level for the


referenced photo smoke detector exceeds 3.7 %.

Smoke level 0.5

Input statement is TRUE when the smoke level for the


referenced ion smoke detector exceeds 0.5 %.

Smoke level 0.9

Input statement is TRUE when the smoke level for the


referenced ion smoke detector exceeds 0.9 %.

Smoke level 1.3

Input statement is TRUE when the smoke level for the


referenced ion smoke detector exceeds 1.3 %.

Smoke level 1.7

Input statement is TRUE when the smoke level for the


referenced ion smoke detector exceeds 1.7 %.

Smoke level 0.2

Input statement is TRUE when the smoke level for the


referenced extra-sensitive photo smoke detector exceeds
0.2 %.

Smoke level 0.5

Input statement is TRUE when the smoke level for the


referenced extra-sensitive photo smoke detector exceeds
0.5 %.

Smoke level 1.0

Input statement is TRUE when the smoke level for the


referenced extra-sensitive photo smoke detector exceeds
1.0 %.

Smoke level 1.5

Input statement is TRUE when the smoke level for the


referenced extra-sensitive photo smoke detector exceeds
1.5 %.
Continued on next page

10-17

Technical Manuals Online! - http://www.tech-man.com

Custom Control

PHOTO Smoke
Level

Table 10-1. Input Opcodes and Qualifiers

Step 3. Edit Each Input Statements Properties, Continued

Input Opcodes and Qualifiers


(continued)
Table 10-1. Input Opcodes and Qualifiers
Opcode

XPHOTO Smoke
Level

Qualifier

Application

Smoke level 2.0

Input statement is TRUE when the smoke level for the


referenced extra-sensitive photo smoke detector exceeds
2.0 %.

Smoke level 2.5

Input statement is TRUE when the smoke level for the


referenced extra-sensitive photo smoke detector exceeds
2.5 %.

Smoke level 3.7

Input statement is TRUE when the smoke level for the


referenced extra-sensitive photo smoke detector exceeds
3.7 %.

10-18

Technical Manuals Online! - http://www.tech-man.com

Step 4. Edit Each Output Statements Properties

Procedure

An outputs properties specify what occurs (for example, a limited set of


strobes/horns activate) when the Input Side of the CC Equation is True. Output
Properties are set through the Custom Control output dialog. Follow these steps
to open this dialog.
1.

Highlight one of the equations output qualifiers and click the right mouse
button. A menu of choices appears.

2.

Click on Properties. A dialog similar to the following appears.


Custom Control

Figure 10-6. Custom Control Output Dialog


3.

Use Table 10-2 to set the Opcode and Qualifier.

Table 10-2. Output Opcodes and Qualifiers


Opcode

Qualifier

Application

ON

When the input side of the equation is true, Hold ON turns


the referenced output point ON. The output remains ON
until another equation turns the output OFF or the system is
reset. List L7 (Control Points, Off with Reset) is useful for
turning OFF a number of points simultaneously.

OFF

When the input side of the equation is true, Hold OFF turns
the referenced output point OFF. The output point remains
OFF until another equation turns the output point ON or the
system is reset.

Hold

Continued on next page

10-19

Technical Manuals Online! - http://www.tech-man.com

Step 4. Edit Each Output Statements Properties, Continued

Procedure (continued)
Table 10-2. Output Opcodes and Qualifiers (continued)
Opcode

Qualifier
PRI

Hold

When the input side of the equation is true, the priority is


reset to the value specified until a system reset is
performed.

Slow March Time

When the input side of the equation is true, the output


cycles at 20 beats per minute (bpm) until a system reset is
performed.

Fast March Time

When the input side of the equation is true, the output


cycles at 120 beats per minute (bpm) until a system reset is
performed.

Temporal

When the input side of the equation is true, the output


pattern consists of three second pulses, each separated
by second of silence. Each group of three cycles is
separated by 1.5 seconds of silence. The output cycles
until a system reset is performed.

ON

When the input side of the equation is true, the output turns
ON. When the input is false, the output turns OFF.

OFF

When the input side of the equation is true, the output turns
OFF. When the input is false, the output turns ON.

PRI

When the input side of the equation is true, the priority is


changed to a value that you specify. When the input is
false, the priority returns to its original value.

On

When the input side of the equation is True, Set turns the
point referenced on the output side of the equation ON.
The point stays ON until a Set OFF command occurs.

OFF

When the input side of the equation is True, Set turns the
point referenced on the output side of the equation OFF.
The point stays OFF until a Set ON command occurs.

PRI

When the input side of the equation is True, Set turns the
point referenced on the output side of the equation ON.
The point stays ON until a Set OFF command occurs.

On

When the input side of the equation is true, the


enable/disable state of the point is set to ON, which
disables the point.

OFF

When the input side of the equation is true, the


enable/disable state of the point is set to OFF, which
enables the point.

Track

Set

Enable/Disable

Application

Continued on next page

10-20

Technical Manuals Online! - http://www.tech-man.com

Step 4. Edit Each Output Statements Properties, Continued

Procedure (continued)
Table 10-2. Output Opcodes and Qualifiers (continued)
Opcode

Qualifier

When the input side of the equation is true, the value of an


analog pseudo point is set to a constant value.

Variable

When the input side of the equation is true, the value of an


analog pseudo point is set to a variable value.

Constant

When the input side of the equation is true, the referenced


point pulses for the specified amount of time (constant
value).

Variable

When the input side of the equation is true, the referenced


point pulses for the specified amount of time (variable).

ON

When the input side of the equation is true, the referenced


LED is turned ON. Note you must use LED OFF to turn the
LED OFF.

OFF

When the input side of the equation is true, the referenced


LED is turned OFF.

Slow

When the input side of the equation is true, the referenced


LED flashes Slow.

Fast

When the input side of the equation is true, the referenced


LED flashes Fast.

Pulse

Print

Channel Code

All Ports / Displays

Prints a message to the referenced ports/displays.

ON

When the input side of the equation is true, all devices on


the IDNet channel are turned ON. Note that this includes
all relays, door holders, etc.

OFF

When the input side of the equation is true, all devices on


the IDNet channel are turned OFF. Note that this includes
all relays, door holders, etc.

Fast March Time

When the input side of the equation is true, all devices on


the IDNet channel turn on and off in fast march time.

Temporal

When the input side of the equation is true, all devices on


the IDNet channel turn on and off in a temporal pattern.

March Time

When the input side of the equation is true, all devices on


the IDNet channel turn on and off in standard march time.
Continued on next page

10-21

Technical Manuals Online! - http://www.tech-man.com

Custom Control

Constant
Set Analog Value

LED

Application

Step 4. Edit Each Output Statements Properties, Continued

Procedure (continued)
Table 10-2. Output Opcodes and Qualifiers (continued)
Opcode

Set Photo
Threshold

Set Heat Threshold

Set ROR

Set ION Threshold

Qualifier

Application

Smoke Level 0.5

When the input side of the equation is true, the threshold


level for the photo smoke detector is set to 0.5.

Smoke Level 1.0

When the input side of the equation is true, the threshold


level for the photo smoke detector is set to 1.0.

Smoke Level 1.5

When the input side of the equation is true, the threshold


level for the photo smoke detector is set to 1.5.

Smoke Level 2.0

When the input side of the equation is true, the threshold


level for the photo smoke detector is set to 2.0.

Smoke Level 2.5

When the input side of the equation is true, the threshold


level for the photo smoke detector is set to 2.5.

117 Fahrenheit

When the input side of the equation is true, the threshold


level for the heat detector is set to 117 degrees F.

135 Fahrenheit

When the input side of the equation is true, the threshold


level for the heat detector is set to 135 degrees F.

155 Fahrenheit

When the input side of the equation is true, the threshold


level for the heat detector is set to 155 degrees F.

3 C / minute

When the input side of the equation is true, the threshold


level for the ROR heat detector is set to 3 C / minute.

15 F / minute

When the input side of the equation is true, the threshold


level for the ROR heat detector is set to 15 C / minute.

20 F / minute

When the input side of the equation is true, the threshold


level for the ROR heat detector is set to 20 C / minute.

Smoke Level 0.5

When the input side of the equation is true, the threshold


level for the ION smoke detector is set to 0.5.

Smoke Level 0.9

When the input side of the equation is true, the threshold


level for the ION smoke detector is set to 0.9.

Smoke Level 1.3

When the input side of the equation is true, the threshold


level for the ION smoke detector is set to 1.3.

Smoke Level 1.7

When the input side of the equation is true, the threshold


level for the ION smoke detector is set to 1.7.
Continued on next page

10-22

Technical Manuals Online! - http://www.tech-man.com

Step 4. Edit Each Output Statements Properties, Continued

Procedure (continued)
(continued)
Opcode

Qualifier
Smoke Level 0.2

When the input side of the equation is true, the threshold


level for the extra-sensitive photo smoke detector is set to
0.2.

Smoke Level 0.5

When the input side of the equation is true, the threshold


level for the extra-sensitive photo smoke detector is set to
0.5.

Smoke Level 1.0

When the input side of the equation is true, the threshold


level for the extra-sensitive photo smoke detector is set to
1.0.

Smoke Level 1.5

When the input side of the equation is true, the threshold


level for the extra-sensitive photo smoke detector is set to
1.5.

Smoke Level 2.0

When the input side of the equation is true, the threshold


level for the extra-sensitive photo smoke detector is set to
2.0.
Used with TrueAlert Non-Addressable Horns. When the
input side of the equation is true, Horn OFF turns TrueAlert
Non-Addressable horns off.

HORN OFF

Associating Points with


Output Statements

Application

After defining the Opcode and Qualifier for an output statement, you need to
associate a point with the statement. To do this, follow these steps.
1.

In the list on the right side of the screen, click on the name of the point.

2.

Hold down the left mouse button and drag the highlighted point from the
list to the appropriate output Statement.

3.

Release the mouse button.

10-23

Technical Manuals Online! - http://www.tech-man.com

Custom Control

Set XPHOTO
Threshold

Table 10-2. Output Opcodes and Qualifiers (continued)

White text

Technical Manuals Online! - http://www.tech-man.com

Chapter 11
Building and Downloading a Job
Introduction

This chapter describes building a 4010 job and downloading it to the 4010 panel.

In this Chapter

The remainder of this chapter discusses the following topics:


Topic

See Page #

Building a Job

11-2

Downloading a CFG File to the Panel

11-3

Building/Downloading Jobs

11-1

Technical Manuals Online! - http://www.tech-man.com

Building a Job

Introduction

This section describes using the PC Programmers Job Builder utility to create a
Configuration Data file (CFIG), and download it to the 4010 FACP.

Using Job Builder

The Job Builder utility does the following:

Automatically saves the job being built.


Verifies that the hardware and the configured points are accurate.
Produce the CFG file.

To build a job, follow these steps:


1.

Click on the Build menu and choose the Build option.


The Job Builder dialog appears, displaying the progress of the job build in
the window.

2.

Click on OK when the job is finished building.

Figure 11-1. Job Builder Dialog

11-2

Technical Manuals Online! - http://www.tech-man.com

Downloading a CFG File to the Panel

Introduction

This section describes downloading a CFG file (built job file) from a service PC
to the 4010 FACP. A download occurs over a serial link running between the
panel and the PC. Follow the steps outlined in the following sections to link the
PC to the panel and download the job.

Step 1. Set Panel and PC


Serial Communication
Parameters

1.

Set switches SW1 and SW2 to the positions shown in Figure 11-2. These
positions enable a baud rate of 19,200 on the 4010 FACP.

Black indicates switch position

19,200

Figure 11-2. Switch Position for 19,200 Baud


Start the 4010 Programmer application.
Click on the Transfer menu and select Settings.
A dialog similar to the one shown in Figure 11-3 appears.

Figure 11-3. Setting PC Transfer Rate to 19,200


3.

Set the parameters in this dialog as follows:

Port. Set this radio button to the setting that corresponds to the serial
port on the PC to which the serial cable will be connected. In most
cases, this will be COM1.
Baud Rate. Set to 19,200.
Parity. Set to None.
Stop Bits. Set to 1.
Data Bits. Set to 8.
Continued on next page

11-3

Technical Manuals Online! - http://www.tech-man.com

Building/Downloading Jobs

2.

Downloading a CFG File to the Panel, Continued

Step 2. Connect Serial Cable


between PC and Panel

Connect a 733-794 serial cable between a free serial port on the service PC and
the service port of the 4010 FACP.
1.

Locate the PC within 6 feet of the 4010 FACP and connect the end shown
in Figure 11-4 to the PC.

2.

Connect the other end to the service port on the 4010 FACP. Make sure that
the red stripe is aligned to the left as you connect the cable.

Align Red Stripe


to the Left
9-Pin Connector
goes to PC

Figure 11-4. Connecting Serial Cable


Step 3. Enable Download on
Panel

1.
2.
3.

Login to the 4010 at Access Level 4.


Press <MENU>.
Press <NEXT> until [UPLOAD/DOWNLOAD] is displayed.
<ENTER> to Accept
<NEXT/PREV to Scroll
Menu:
[Upload/Download]

4.

Press <ENTER>. A screen similar to the following appears.


<ENTER> to Accept
Prog. Interface:

5.

<NEXT/PREV> to Scroll
[Initialize Up/Dwnload]

Press the <NEXT> or <PREV> keys until [Initialize Up/Dwnload] is


displayed and press <ENTER>.
Continued on next page

11-4

Technical Manuals Online! - http://www.tech-man.com

Downloading a CFG File to the Panel, Continued

Step 3. Enable Download on


Panel (continued)

The 4010 displays the following message to indicate that the panel is ready to
accept a download.
***
***

Step 4. Start Download at PC

1.

File Transfer Initialized ***


Check Programming Unit **

Click on the Transfer menu. When the selections appear, choose Transfer.
A window similar to the one shown in Figure 11-5 appears.

2.

Select the following radio button options in the windows panels.

3.

Download
Direct
Panel CFIG

Click OK.
The dialog shown in Figure 11-6 appears, prompting you to begin the
download.

Figure 11-6. Download Dialog


4.

Click on the Start button to begin the download.


A progress thermometer appears, tracking the progress of the download.
Continued on next page

11-5

Technical Manuals Online! - http://www.tech-man.com

Building/Downloading Jobs

Figure 11-5. Upload/Download Dialog

Downloading a CFG File to the Panel, Continued

Step 4. Start Download at PC


(continued)

Figure 11-7. Transfer in Progress


7.

When the following prompt appears, choose Yes to restart the panel.
Note: You must restart the panel from the PC, not the panel. Pressing the
panels warm start button causes all downloaded information to be lost.

Figure 11-8. Restart Panel Prompt

11-6

Technical Manuals Online! - http://www.tech-man.com

Appendix A
Hardware Device Types,
Software Point Types, and Point Addresses

Introduction

This appendix lists and explains the following:

Hardware Device Types. 4010 hardware device types are listed with their
corresponding PIDs, allowing you to exactly match the equipment used
with the available device types.

Software Point Types. 4010 point types are grouped into two general
categories:

In this Chapter

Monitor point types are used with monitoring devices, such as smoke
detectors, pull stations, heat detectors, fire pump monitors, etc.

Control point types are used with signal (notification appliance) and
relay devices.

Point Addresses and definitions. Each 4010 point has a point address, such
as 1-1 (NAC card signal 1 address). A point address and an understanding
of when the point turns ON and OFF are necessary for referencing points in
Custom Control equations.

This appendix discusses the following topics:


Topic

See Page #
A-2

Control Point Types

A-3

Monitor Point Types

A-9

24-Point I/O Point Types

A-17

Addresses for Hardware Points

A-18

Addresses for Pseudo Points

A-25

A-1

Technical Manuals Online! - http://www.tech-man.com

Device Types/Point Types

Device Types

Device Types

Sensor/Base Device Types

The hardware device type used for a specific sensor/base combination depends
on the combination. The following table summarizes which point types can be
used with the various combinations of sensor and base.
To use this table, first identify the exact sensor/base combination in use for each
IDNet point. The point at which the column (base) and row (sensor) intersect
contains the device type that you should use for that sensor/base combination.

Standard
Base
4098-9792

Photo
Sensor
4098-9714
Ion
Sensor
4098-9717
Heat
Sensor
4098-9733

LED
Base
4098-9789

Sounder
Base

Isolator
Base
4098-9793

External
Duct Base
4098-9750
4098-9751

Internal
Duct Base
4098-9752
4098-9753

Relay
Base
4098-9791

PHOTO
XPHOTO

SPHOTO
XSPHOTO

IPHOTO
XIPHOTO

PHOTO
RPHOTO
XPHOTO?

PHOTO
RPHOTO
XPHOTO?

RPHOTO
XRPHOTO

ION

SION

IION

N/A

N/A

RION

HEAT
OHEAT

SHEAT
SOHEAT

IHEAT
IOHEAT

N/A

N/A

RHEAT
ROHEAT

IAMs / ZAMs / IDNet


Addressable Device Types

The following table lists the PIDs and corresponding device types for IAMs,
ZAMS, and IDNet Addressable devices.

Device
IDNet Class A Monitor ZAM
IDNet Class B Monitor ZAM
International Pull Station
Canadian Pull Station
IDNet Single Action Pull Station

IDNet Supervised IAM


IDNet Relay IAM
4009A IDNet Addressable NAC Device with 4 NACs
4009A IDNet Addressable NAC Device with 8 NACs
4009A IDNet Addressable NAC Device with 4 NACs
and a Repeater
4009A IDNet Addressable and a Repeater NAC
Device with 4 NACs

A-2

Technical Manuals Online! - http://www.tech-man.com

PID

Device Type

4090-9106

MAZAM

4090-9101
International Only
Canadian Only
Standard -- 4090-9001
Break Glass -- 4090-9002
Double Action -- 4090-9003
4090-9001
4090-9002
4009-9201
4009-9201 and 4009 9807
4009-9201 and 4009-9809

MBZAM
KACPUL
CANPUL
ADRPUL

4009-9201 and 4009 9807


and 4009-9809

R4009A8

IAM
RIAM
4009A
4009A8
R4009A

Control Point Types

AHUF

AHU off relay dual relay control. This point type is used with applications
that use two auxiliary relays for AHU control one relay for ON and one relay
for OFF. Use this point type for the OFF relay. See AHUO also. If you have a
single relay that performs both ON and OFF functions, see AHUR.
Circuit Status

AHUO

LCD Display

System Status

ON

AHU OFF Relay

ON

OFF

AHU OFF Relay

OFF

AHU OFF Relay

CODING

Disabled TBL

AHU OFF Relay

TROUBLE

OFF AUTO TBL

AHU OFF Relay

TROUBLE

AHU on relay dual relay control. This point type is used with applications that
use two auxiliary relays for AHU control one relay for ON and one relay for
OFF. Use this point type for the ON relay. Points assigned with this type
operate on general alarm. See AHUF also. If you have a single relay that
performs both ON and OFF functions, see AHUR.
Circuit Status

AHUR

LCD Display

System Status

ON

AHU ON Relay

ON

OFF

AHU ON Relay

OFF

AHU ON Relay

CODING

Disabled TBL

AHU ON Relay

TROUBLE

OFF AUTO TBL

AHU ON Relay

TROUBLE

LCD Display

System Status

ON

AHU Relay

ON

OFF

AHU Relay

OFF

AHU Relay

CODING

Disabled TBL

AHU Relay

TROUBLE

OFF AUTO TBL

AHU Relay

TROUBLE

Circuit Status

Continued on next page

A-3

Technical Manuals Online! - http://www.tech-man.com

Device Types/Point Types

AHU on/off relay single relay control. This point type is used with
applications in which a single relay performs AHU ON and OFF control. Points
assigned with this type operate on general alarm.

Control Point Types, Continued

ALTERN

Elevator capture alternate. Used for a relay connected to the elevator controls
to provide alternate floor elevator recall.
Circuit Status

BSIGNAL

LCD Display

System Status

ON

ALT Elevator Recall

ON

OFF

ALT Elevator Recall

OFF

ALT Elevator Recall

CODING

Disabled TBL

ALT Elevator Recall

TROUBLE

OFF AUTO TBL

ALT Elevator Recall

TROUBLE

Trouble/supervisory bell signal. Used when an audible signal should activate


on any supervisory or trouble condition and remain ON until the condition has
been acknowledged.
Circuit Status

DHOLDER

LCD Display

System Status

ON

Trouble Signal

ON

OFF

Trouble Signal

OFF

Trouble Signal

CODING

Disable TBL

Trouble Signal

TROUBLE

OFF AUTO TBL

Trouble Signal

TROUBLE

Door holder control (normally off). Used when the auxiliary relay is connected
to door holders. The relay energizes on alarm, loss of AC Power, or when
programmed.
Circuit Status
ON
OFF

LCD Display

System Status

Door Holder

ON

Door Holder

OFF

Door Holder

CODING

Disable TBL

Door Holder

TROUBLE

OFF AUTO TBL

Door Holder

TROUBLE
Continued on next page

A-4

Technical Manuals Online! - http://www.tech-man.com

Control Point Types, Continued

PRIMARY

Elevator capture primary. Used for any relay connected to the elevator
controls to provide primary floor elevator recall. By default, these relays pick
on any alarm.
Circuit Status

LCD Display

System Status

ON

Pri Elevator Capture

ON

OFF

Pri Elevator Capture

OFF

Pri Elevator Capture

CODING

Disable TBL

Pri Elevator Capture

TROUBLE

OFF AUTO TBL

Pri Elevator Capture

TROUBLE

QALERT

TrueAlert Non-Addressable signal. QALERT device type has no automatic


operation. All operations for this type of device type must be programmed with
Custom Control.

SQALERT

SQALERT device type automatically turns on the designated circuit on alarm


detect (general alarm), issues the horn silence command upon Alarm Silence,
and turns off the circuit at the completion of System Reset. Any point
programmed with the SQALERT point type is not available for use in Custom
Control programming.

RELAY

Generic relay no default operation. Used for any relay application that is not
defined by a specific point type.
Circuit Status

System Status

ON

Auxiliary Relay

ON

OFF

Auxiliary Relay

OFF

Auxiliary Relay

CODING

Disable TBL

Auxiliary Relay

TROUBLE

OFF AUTO TBL

Auxiliary Relay

TROUBLE

Alarm signal on until reset. Used for any signaling device (such as an audible
or visible notification appliance) that is required to be on until a system reset is
performed. Points assigned with this type operate on general alarm.
Circuit Status

LCD Display

System Status

ON

Signal Circuit

ON

OFF

Signal Circuit

OFF

Signal Circuit

CODING

Disable TBL

Signal Circuit

TROUBLE

OFF AUTO TBLE

Signal Circuit

TROUBLE
Continued on next page

A-5

Technical Manuals Online! - http://www.tech-man.com

Device Types/Point Types

RSIGNAL

LCD Display

Control Point Types, Continued

RVISUAL

Used only with visual notification appliances that must be ON until a system
reset is performed. Points assigned with this type operate on general alarm.
Circuit Status

RWATER

LCD Display

System Status

ON

Visual

ON

OFF

Visual

OFF

Visual

CODING

Disable TBL

Visual

TROUBLE

Off Auto TBL

Visual

TROUBLE

Waterflow signal on until reset.


Circuit Status

SIGNAL

LCD Display

System Status

ON

Signal Circuit

ON

OFF

Signal Circuit

OFF

Signal Circuit

CODING

Disable TBL

Signal Circuit

TROUBLE

Off Auto TBL

Visual

TROUBLE

Generic Alarm Signal on until reset. Used for any signaling device (such as an
audible or visible notification appliance) that is required to be on until reset.
Points assigned with this type operate on general alarm.
Circuit Status

LCD Display

System Status

ON

Signal Circuit

ON

OFF

Signal Circuit

OFF

Signal Circuit

CODING

Disable TBL

Signal Circuit

TROUBLE

OFF AUTO TBLE

Signal Circuit

TROUBLE
Continued on next page

A-6

Technical Manuals Online! - http://www.tech-man.com

Control Point Types, Continued

SSIGNAL

Alarm signal on until silence. Used for any signaling device (such as an
audible or visible notification appliance) that is required to be on until reset.
Points assigned with this type operate on general alarm.
Circuit Status

SUPREL

LCD Display

System Status

Normal

Signal Circuit

ON

Normal

Signal Circuit

OFF

Signal Circuit

CODING

Disable TBL

Signal Circuit

TROUBLE

OFF AUTO TBLE

Signal Circuit

TROUBLE

LCD Display

System Status

Suppression release output.


Circuit Status
Normal

Signal Circuit

ON

Normal

Signal Circuit

OFF

Signal Circuit

CODING

Signal Circuit

TROUBLE

Disable TBL

SUPV

Sprinkler supervisory signal. Turns ON with a SO or WSO supervisory alarm.


Turns OFF on ACK or when the supervisory clears. Example: Have a relay and
its point type is SUPV, used to set off a bell when a tamper is triggered or a gate
valve is opened.
Circuit Status

System Status

Normal

Signal Circuit

ON

Normal

Signal Circuit

OFF

Disable TBL

SVISUAL

Signal Circuit

CODING

Signal Circuit

TROUBLE

Visual on until silence. Used only with visual notification appliances that
must remain ON until an Alarm Silence is performed.
Circuit Status

LCD Display

System Status

Normal

Visual

ON

Normal

Visual

OFF

Visual

CODING

Disable TBL

Visual

TROUBLE

OFF AUTO TBL

Visual

TROUBLE
Continued on next page

A-7

Technical Manuals Online! - http://www.tech-man.com

Device Types/Point Types

LCD Display

Control Point Types, Continued

SWATER

Waterflow signal on until silence. Used in applications where a waterflow


signal circuit is required to remain activated until the Alarm Silence key is
pressed.
Circuit Status

TSIGNAL

LCD Display

System Status

ON

Signal Circuit

ON

OFF

Signal Circuit

OFF

Signal Circuit

CODING

Disable TBL

Signal Circuit

TROUBLE

Disable TBL

Signal Circuit

TROUBLE

LCD Display

System Status

Trouble/supervisory signal.
Circuit Status
ON

Signal Circuit

ON

ON

Signal Circuit

OFF

Signal Circuit

CODING

Disable TBL

Signal Circuit

TROUBLE

Disable TBL

Signal Circuit

TROUBLE

A-8

Technical Manuals Online! - http://www.tech-man.com

Monitor Point Types

FIRE

This is a generic fire alarm point type. A typical application for this point type
is a fire alarm zone containing more than one type of device. For example,
when a combination of smoke detectors, pull stations, waterflow monitors, and
heat detectors is connected to an IAM or ZAM, this point type allows alarms to
report as originating from a zone.
Circuit Status
Normal
Limited
Open
Short

LCD Text
Fire Monitor Zone
Fire Monitor Zone
Fire Monitor Zone

Status
Normal
Fire Alarm
Open Trouble
Fire Alarm

When an Alarm or Trouble condition occurs, press Enter to view specific


information for the Fire Monitor Zone
WATER

Used to define the operation of a waterflow monitor for all possible circuit
states.
Circuit Status
Normal
Limited
Open
Short

DUCT

LCD Text
Waterflow Monitor
Waterflow Monitor
Waterflow Monitor

Used to define the operation of a duct detector for all possible circuit states.
LCD Text

Circuit Status
Normal
Limited
Open
Short

Duct Detector
Duct Detector
Duct Detector

Status
Normal
Fire Alarm
Open Trouble
Fire Alarm

Defines the operation of a duct detector for all possible circuit states.
Circuit Status
Normal
Limited
Open
Short

LCD Text
Heat Detector
Heat Detector
Heat Detector

Status
Normal
Fire Alarm
Open Trouble
Fire Alarm
Continued on next page

A-9

Technical Manuals Online! - http://www.tech-man.com

Device Types/Point Types

HEAT

Status
Normal
Fire Alarm
Open Trouble
Fire Alarm

Monitor Point Types, Continued

FLAME

Use for flame detectors.


LCD Text

Circuit Status
Normal
Limited
Open
Short
PULL

Flame Detector
Flame Detector
Flame Detector

Use with manual pull stations.


Circuit Status
Normal
Limited
Open
Short

SMOKE

LCD Text
Manual Pull Station
Manual Pull Station
Manual Pull Station

LCD Text
Smoke Detector
Smoke Detector
Smoke Detector

Status
Normal
Fire Alarm
Open Trouble
Fire Alarm

Use for an emergency monitor zone in which two types of alarm devices for
example, emergency alarm devices such as Nurse Call and fire alarm devices -are connected to an IAM or ZAM. Emergency devices require the use of a
current limiting resistor. These devices generate an Emergency Alarm condition
at the panel.
Circuit Status
Normal
Limited
Open
Short

SFIRE

Status
Normal
Fire Alarm
Open Trouble
Fire Alarm

Use for 2- and 4-wire smoke detectors.


Circuit Status
Normal
Limited
Open
Short

EMERG

Status
Normal
Fire Alarm
Open Trouble
Fire Alarm

LCD Text
Monitor Zone
Monitor Zone
Monitor Zone

Status
Normal
Emergency Alarm
Open Trouble
Fire Alarm

Used when smoke detectors and shorting type devices are connected to an IAM
or ZAM.
Circuit Status
Normal
Limited
Open
Short

LCD Text
Fire Monitor Zone
Fire Monitor Zone
Fire Monitor Zone

Status
Normal
Smoke Alarm
Open Trouble
Fire Alarm
Continued on next page

A-10

Technical Manuals Online! - http://www.tech-man.com

Monitor Point Types, Continued

VFIRE

Used to activate the alarm verification software for all smoke detectors
connected to an IAM or ZAM. Shorting type devices cause an immediate alarm.
LCD Text

Circuit Status
Normal
Limited
Open
Short
SPULL

Fire Monitor Zone


Fire Monitor Zone
Fire Monitor Zone

Used when smoke detectors and pull stations are connected to an IAM or ZAM.
LCD Text

Circuit Status
Normal
Limited
Open
Short
VSPULL

Fire Monitor Zone


Fire Monitor Zone
Fire Monitor Zone

LCD Text
Fire Monitor Zone
Fire Monitor Zone
Fire Monitor Zone

Status
Normal
Verified Alarm
Open Trouble
Manual Alarm

LCD Text
Generator Monitor
Generator Monitor
Generator Monitor

Status
Normal
Running
Open Trouble
Abnormal

Same operation as the GENMON point type, but the generator running condition
automatically displays and requires operator acknowledgment.
Circuit Status
Normal
Limited
Open
Short

LCD Text
Generator Monitor
Generator Monitor
Generator Monitor

Status
Normal
Running
Open Trouble
Abnormal
Continued on next page

A-11

Technical Manuals Online! - http://www.tech-man.com

Device Types/Point Types

Used when emergency generator monitoring is required. The shorted condition


of the circuit indicates an abnormal status and is indicated by the Supervisory
Service LED. The current limited condition of the circuit indicates that the
generator is running, and can be tracked with an LED (must be programmed). A
current limiting resistor must be installed for this to happen.
Circuit Status
Normal
Limited
Open
Short

SGENMON

Status
Normal
Smoke Alarm
Open Trouble
Manual Alarm

Used when smoke detectors that must be verified and pull stations are connected
to an IAM or ZAM.
Circuit Status
Normal
Limited
Open
Short

GENMON

Status
Normal
Verified Alarm
Open Trouble
Fire Alarm

Monitor Point Types, Continued

FPUMP

Used to monitor fire pump conditions. The shorted condition indicates that the
fire pump is abnormal. The current limited condition indicates that the fire
pump is running.
Circuit Status
Normal
Limited
Open
Short

SFPUMP

LCD Text
Fire Pump Monitor
Fire Pump Monitor
Fire Pump Monitor

Same as the FPUMP point type, except that the fire pump running condition
requires operator acknowledgment.
Circuit Status
Normal
Limited
Open
Short

S2STAGE

LCD Text
Fire Pump Monitor
Fire Pump Monitor
Fire Pump Monitor

Status
Normal
Running
Open Trouble
Abnormal

Used for 2-stage alarms. The current limited operation of any device indicate a
Stage 1 Alarm. A short on the points circuit, such as a key switch operation,
causes a Stage 2 Alarm.
Circuit Status
Normal
Limited
Open
Short

SO

Status
Normal
Running
Open Trouble
Abnormal

LCD Text
2 Stage Monitor
2 Stage Monitor
2 Stage Monitor

Status
Normal
Stage 1 Alarm
Open Trouble
Stage 2 Alarm

Used to indicate abnormal sprinkler conditions, such as the opening of a PIV or


OS&Y tamper switch. This point type must be used with normally open
contacts only.
Circuit Status
Normal
Limited
Open
Short

LCD Text
Sprinkler Monitor
Sprinkler Monitor
Sprinkler Monitor

Status
Normal
Abnormal
Open Trouble
Abnormal
Continued on next page

A-12

Technical Manuals Online! - http://www.tech-man.com

Monitor Point Types, Continued

WSO

Combination Waterflow/Sprinkler Monitor (NO). Where permitted by the AHJ,


this circuit operates both waterflow monitors and PIV/OS&Y tampers on the
same circuit. All tamper switches (N.O. contacts) must be connected with a
current limiting resistor. Refer to the 4010 field wiring diagrams. A short
condition indicates waterflow alarms.
Circuit Status
Normal
Limited
Open
Short

SUPDET

LCD Text
Sprinkler Monitor
Sprinkler Monitor
Sprinkler Monitor

Suppression (Agent Discharge) Monitor.


Circuit Status
Normal
Limited
Open
Short

SUPABRT

LCD Text
Suppression Detector
Suppression Detector
Suppression Detector

LCD Text
Suppression Abort
Suppression Abort
Suppression Abort

Status
Normal
Activated
Open Trouble
Short Trouble

Manual suppression agent discharge .


LCD Text
Suppression Manual Dump
Suppression Manual Dump
Suppression Manual Dump

Status
Normal
Activated
Open Trouble
Short Trouble

Suppression agent pressure switch monitor.


LCD Text

Circuit Status
Normal
Limited
Open
Short

Suppression Pressure
Suppression Pressure
Suppression Pressure

Status
Normal
Discharge
Open Trouble
Short Trouble
Continued on next page

A-13

Technical Manuals Online! - http://www.tech-man.com

Device Types/Point Types

Circuit Status
Normal
Limited
Open
Short
SUPPRES

Status
Normal
Fire Alarm
Open Trouble
Fire Alarm

Suppression Abort (supervised).


Circuit Status
Normal
Limited
Open
Short

SUPDUMP

Status
Normal
Abnormal
Open Trouble
Waterflow Alarm

Monitor Point Types, Continued

SUPV

Used to monitor any supervisory type device where operator acknowledgment is


required.
LCD Text

Circuit Status
Normal
Limited
Open
Short
UTIL

Supervisory Monitor
Supervisory Monitor
Supervisory Monitor

Used to monitor and supervise any condition; operator acknowledgment is not


required. No alarm is generated by this point type.
Circuit Status
Normal
Limited
Open
Short

TROUBLE

LCD Text
Utility Monitor
Utility Monitor
Utility Monitor

LCD Text
Trouble Monitor
Trouble Monitor
Trouble Monitor

Status
Normal
Abnormal
Open Trouble
Abnormal

Used with smoke detectors whose alarm status must be verified.


Circuit Status
Normal
Limited
Open
Short

GVMON

Status
Normal
Abnormal
Open Trouble
Abnormal

Used for trouble monitoring only. No alarm is generated by this point type.
Circuit Status
Normal
Limited
Open
Short

VSMOKE

Status
Normal
Abnormal
Open Trouble
Abnormal

LCD Text
Smoke Detector
Smoke Detector
Smoke Detector

Status
Normal
Verified Alarm
Open Trouble
Fire Alarm

Used when the abnormal condition of the circuit must be verified.


LCD Text

Circuit Status
Normal
Limited
Open
Short

Fire Monitor
Fire Monitor
Fire Monitor

Status
Normal
Verified Alarm
Open Trouble
Fire Alarm
Continued on next page

A-14

Technical Manuals Online! - http://www.tech-man.com

Monitor Point Types, Continued

LATSUPV

Supervisory Monitor latch until reset. Used for generic supervisory alarm.
LCD Text

Circuit Status
Normal
Limited
Open
Short
STYLEC

Supervisory Alarm
Supervisory Alarm
Supervisory Alarm

Style-C Fire Alarm Monitor. Used when only current limited devices are
connected to the zone. A short circuit is reported as a Trouble.
Circuit Status
Normal
Limited
Open
Short

SDUCT

LCD Text
Fire Monitor Zone
Fire Monitor Zone
Fire Monitor Zone

LCD Text
Flame Detector
Flame Detector
Flame Detector

Status
Normal
Abnormal
Open Trouble
Abnormal

Abort zone.
LCD Text
Fire Alarm Abort
Fire Alarm Abort
Fire Alarm Abort

Status
Normal
Abnormal
Open Trouble
Abnormal

Damper Monitor.
Circuit Status
Normal
Limited
Open
Short

LCD Text
Damper Monitor
Damper Monitor
Damper Monitor

Status
Normal
Abnormal
Open Trouble
Abnormal
Continued on next page

A-15

Technical Manuals Online! - http://www.tech-man.com

Device Types/Point Types

Circuit Status
Normal
Limited
Open
Short
DAMPER

Status
Normal
Fire Alarm
Open Trouble
Short Trouble

Supervisory Duct Detector.


Circuit Status
Normal
Limited
Open
Short

ABORT

Status
Normal
Abnormal
Open Trouble
Abnormal

Monitor Point Types, Continued

4009A

4009A Point Type.


LCD Text

Circuit Status
Normal
Limited
Open
Short

4009A
4009A
4009A

A-16

Technical Manuals Online! - http://www.tech-man.com

Status
Normal
Abnormal
Open Trouble
Abnormal

24 Point I/O Point Types

USWITCH

2-position switch, unsupervised. Used for a 2-position switch without an EOL


or current limited resistor.
LCD Text

Circuit Status
Normal
Limited
Open
Disable TBL
OSWITCH

2-Position Switch
2-Position Switch
2-Position Switch

2-position switch, supervised for opens. Requires an EOL resistor.


LCD Text

Circuit Status
Normal
Limited
Open
Short
Disable TBL
SSWITCH

2-Position Switch
2-Position Switch
2-Position Switch
2-Position Switch

Status
OFF
Invalid State TBL
Open CKT TBL
ON
Disable TBL

2-position switch, supervised for opens and shorts. Requires EOL and current
limited resistors.
Circuit Status
Normal
Limited
Open
Short
Disable TBL

TSWITCH

Status
OFF
Invalid State TBL
ON
Disable TBL

LCD Text
2-Position Switch
2-Position Switch
2-Position Switch
2-Position Switch

Status
OFF
ON
Open CKT TBL
SHORT CKT TBL
Disable TBL

3-position (SPDT) switch, supervised for opens. Requires EOL and series
current limiting resistors (up leg).
LCD Text
3-Position Switch
3-Position Switch
3-Position Switch
3-Position Switch

A-17

Technical Manuals Online! - http://www.tech-man.com

Status
CENTER
UP
Open CKT TBL
DOWN
Disable TBL

Device Types/Point Types

Circuit Status
Normal
Limited
Open
Short
Disable TBL

Addresses for Hardware Points


The 4010 FACP contains many different types of points -- including read-only
system points, IDNet channel points, points on optional cards, digital and analog
pseudo points, list points, and card status (trouble) points. Many of these points
may be referenced , using the points address, in Custom Control equations.
This section provides a card-by-card description of the 4010s hardware, pseudo,
and list points. Card Status points, which may only be viewed from the Active
Trouble List, the Historical Logs, or on an RS-232 port (if available), are not
discussed in this section.
Master Controller (SFIO)
Hardware Points

The Master Controller (SFIO) card resides at card address 0 and contains 13
hardware points. In the table, each point has a type of R or U. Points listed with
a type of R are reserved system points. Points with a type of U are userconfigurable.
Point
0-1

Type
R

Label
Front Panel
Piezo
External N2
Disconnect
Relay

0-2

0-3
0-4

R
R

0-5

0-6

0-7

0-8

Fire LED
Supervisory
LED
Trouble
LED
Alarm
Silence LED
AC Power
LED
User LED 1

0-9

User LED 2

0-10

User LED 3

0-11

0-12

0-13

User
Defined Key
1
User
Defined Key
2
LCD
Backlight

Description
Indicates the status of the piezo sounder on
the 4010 Master.
Indicates the status of the External N2
Disconnect Relay. Turns on when no slaves
are communicating; turns off on System
Reset.
Status of the front panel Alarm LED.
Status of the front panel Supervisory LED.
Status of the front panel Trouble LED.
Status of the front panel Alarm Silence LED.
Status of the front panel AC Power LED.
This point indicates the status and
configuration of the first user programmable
LED on the front panel.
This point indicates the status and
configuration of the second user
programmable LED on the front panel.
This point indicates the status and
configuration of the third user programmable
LED on the front panel.
This point indicates the status and
configuration of the first user programmable
key (in the function menu).
This point indicates the status and
configuration of the second user
programmable key (in the function menu).
Indicates the status of the LCD backlight on
the front panel.
Continued on next page

A-18

Technical Manuals Online! - http://www.tech-man.com

Addresses for Hardware Points, Continued

NAC Card Hardware Points

Power Supply Card

The NAC has 7 hardware points associated with it. Of the 7 hardware points, 6
are points which may be programmed by the user. The other point is the City
Circuit point which is not available for programming or viewing by the user.
The following table is a list of the points on the NAC card. The type field
denotes which class the point falls into (S=System point that is not available to
the user for viewing or programming , U=User Configurable Points).
Point

Type

1-1

1-2

1-3

1-4

1-5

1-6

1-7

Label
(default)
NAC
Circuit: SIG
1
NAC
Circuit: SIG
2
NAC
Circuit: SIG
3
NAC
Circuit: SIG
4
AUX
Circuit:
AUX 1
AUX
Circuit:
AUX 2
City Circuit

Description
NAC card Signal 1 status and configuration.

NAC card Signal 2 status and configuration.

NAC card Signal 3 status and configuration.

NAC card Signal 4 status and configuration.

NAC card Relay 1 status and configuration.

NAC card Relay 2 status and configuration.

Interface 4004 / 4005 / 4010 City Module.

Point
2-1

Label
AC Power

2-2

Positive Earth
Ground
Negative Earth
Ground
Expansion Power
Supply

2-3
2-4

2-5

Expansion Power
Supply Battery

Description
This trouble point will indicate that the AC
line voltage is too low for proper system
operation.
This trouble point indicates that there is a
fault condition between +24V and earth.
This trouble point indicates that there is a
fault condition between 0V and earth.
This trouble point indicates Expansion Power
Supply trouble. Only occurs if expansion
supply is configured.
This trouble point indicates Expansion Power
Supply AUX Power trouble. Only occurs if
expansion supply is configured.
Continued on next page

A-19

Technical Manuals Online! - http://www.tech-man.com

Device Types/Point Types

The Power Supply Card is required for all 4010 configurations, and is located at
card address 2. There are 9 hardware points associated with the Power Supply
card, all of which are system points that cannot be modified by the user. The
following table is a list of the points on the Power Supply card.

Addresses for Hardware Points, Continued

Power Supply Card


(continued)

Point
2-6

Label
Battery Low

2-7

Battery
Depleted/Disconnected
Battery Low Cutout

2-8

IDNet Card

2-9

Battery Charger
Trouble

2-10

Battery Charger

Description
This trouble point indicates that the battery
has a voltage less than 22.8V.
This trouble point indicates that the battery
has a voltage less than 19.5V.
This trouble point indicates that the
batteries have reached a depleted state, and
the system will shut itself off.
This trouble point indicates that the battery
charger has failed. Set if hardware
indicates trouble and AC fail has not
occurred in the previous 24 hours.
This output point controls the status of the
battery charger (on/off).

The IDNet Card is required for all 4010 configurations, and is located at card
address 3. The IDNet Card defaults to a configuration with no hardware points
(devices). However, up to 250 devices may be programmed for the IDNet Card.
The IDNet Card also includes eight card status points.
The IDNet card can have up to 250 devices configured. All of the IDNet
devices can be modified by the user. How the point is configured (i.e. software
point type) will determine what action will be taken (trouble, alarm, etc.) when
the point changes state. The following table is a list of the points that may be
included on the IDNet card. The labels indicated for the points are the default
labels assigned when the point is added from the front panel.
Point
3-1

Label (default)
IDNet Device: M1-1

3-2

IDNet Device: M1-2

3-3

IDNet Device: M1-3

3-249

IDNet Device: M1249


IDNet Device: M1250

3-250

RS232\Modem Card

Description
The point on the IDNet card configured for
address 1.
The point on the IDNet card configured for
address 2.
The point on the IDNet card configured for
address 3.
The point on the IDNet card configured for
address 249.
The point on the IDNet card configured for
address 250.

Either an RS232 Card or Modem Card may be added to the 4010 system. Even
though these cards are optional, if an RS232 or Modem card is configured, it
must reside at card address 4. There are two hardware points associated with
them. Both of the RS232/Modem points are user configurable. However, the
points have no labels associated with them, because they cannot be viewed on
the front panel. The following table is a list of the points on the RS232/Modem
cards.
Continued on next page

A-20

Technical Manuals Online! - http://www.tech-man.com

Addresses for Hardware Points, Continued

RS232\Modem Card
(continued)

SDACT Card

Point
4-1

Label
None

4-2

None

The SDACT card is an optional card that may be added to the 4010 system. The
SDACT card is mutually exclusive with the Network card, and if configured,
must reside at address 8. There is one hardware point associated with the
SDACT card. The point does not have a label, and cannot be viewed from the
front panel.
Point
8-1

Network Card

Description
Port A point. Default to unsupervised 80
character Printer port.
Port B point. Default to command line port.

Label
None

Description
SDACT Port.

The Network card is an optional card that may be added to the 4010 system.
The Network card is mutually exclusive with the SDACT card, and if
configured, must reside at address 8. The network card allows the 4010 to serve
as a network node for a 4120 network. Points on the 4010 may be declared
public to the 4120 network. These points are the Network Status points, and
will be described in this section.
The Network card can have up to 511 Network points configured. The
following table is a list of the points that may be configured on the Network
card. The Common Trouble Point is the only default point for the Network card.
Label
None

NetPt2

None

NetPt3

None

NetPt510

None

NetPt511

None

Description
This point is the Network Common Trouble
Point. This point is public on the network.
This point contains the Network Type, Class,
Destination, and Reference for the second
network public point.
This point contains the Network Type, Class,
Destination, and Reference for the third
network public point.
This point contains the Network Type, Class,
Destination, and Reference for the 510th
network public point.
This point contains the Network Type, Class,
Destination, and Reference for the 511th
network public point.
Continued on next page

A-21

Technical Manuals Online! - http://www.tech-man.com

Device Types/Point Types

Point
NetPt1

Addresses for Hardware Points, Continued

24 Point I/O Card

The 4010 can have up to six annunciator cards added to the system. One of
these cards is the 24IO card. The 24IO card can reside at addresses 9 through
14.
Each 24I/O card has 24 hardware points associated with it. The user can
program all hardware points on the 24I/O card. The functionality of the point
depends on the device type (Input or Output), the point type, and modes
programmed against it. The labels for the points on the 24I/O card are default
labels, and cannot be changed by the user. The following table describes the
organization of points on the 24I/O card. In this table, card represents the card
address (9-14) of the 24 I/O card.

Point
card-1
card-2
card-3
card-23
card-24
LCD Card

Label
I/O Card #, Point 1
I/O Card #, Point 2
I/O Card #, Point 3
I/O Card #, Point 23
I/O Card #, Point 24

Description
The 1st point on the 24IO card.
The 2nd point on the 24IO card.
The 3rd point on the 24IO card.
The 23rd point on the 24IO card.
The 24th point on the 24IO card.

The 4010 can have up to six annunciator cards added to the system. One of
these cards is the LCD card. The LCD card can reside at addresses 9 through
14. The LCD card has five hardware points associated with it. Only the first
three hardware points (user LEDs) on the LCD card can be programmed by the
user. The labels for the points on the LCD card are default labels, and cannot be
changed by the user. The following table describes the points included on the
LCD card. In this table, card represents the card address (9-14) of the LCD
Annunciator card.
Point
card-1

Label
LCD Card #, Point 1

card-2

LCD Card #, Point 2

card-3

LCD Card #, Point 3

card-4

LCD Card #, Point 4

card-5

LCD Card #, Point 5

Description
The status of the First User LED on the LCD
card. Programmable for color and mode.
The status of the Second User LED on the
LCD card. Programmable for color and
mode.
The status of the Third User LED on the
LCD card. Programmable for color and
mode.
The status of the Alarm Silence LED on the
LCD card.
The status of the Piezo sounder on the LCD
card.
Continued on next page

A-22

Technical Manuals Online! - http://www.tech-man.com

Addresses for Hardware Points, Continued

4009A Card

The 4009A Card, which always resides at card address 17, is a very unique card
in the 4010 system. The 4009A card itself is a pseudo card, which means that
an actual hardware card does not exist at address 17. However, unlike other
pseudo cards in the system, the points on the 4009A pseudo card track the status
of actual hardware points. The points on the 4009A Card are used to control and
track the status of the NAC circuits found on all of the 4009A devices
configured in the system. Therefore, the number of configured points on the
4009A Card may vary, depending on the number of 4009A devices configured
in the system. The 4010 can have up to five 4009A devices programmed into
the system, with each 4009A device having up to 8 NAC points, and 8 card
status points associated with it. An overview of how the 4009A points are
configured, and how these points are associated with a specific 4009A device, is
provided in the following sections.
The 4009A card can have up to five 4009A devices associated with it. Each
of the 4009A devices can be configured to have 4 or 8 NACs. Regardless of the
configuration of the 4009A device, the 4009A card always has room provided
for 8 NACs per device. The labels shown for the points on the 4009A card are
default labels. However, these labels may be changed by the user. The
following table describes the points included on the 4009A card. (S=System
point that is not available to the user for viewing or programming , U=User
Configurable Points.)
Type

Label
(default)
IDNet M1#: 4009A
NAC 1

17-1

17-2

IDNet M1#: 4009A


NAC 2

17-3

IDNet M1#: 4009A


NAC 3

17-4

IDNet M1#: 4009A


NAC 4

17-5

IDNet M1#: 4009A


NAC 5

17-6

IDNet M1#: 4009A


NAC 6

Description
The status of the first NAC on the first
4009A device configured in the system. The
device is indicated by the IDNet address
provided.
The status of the second NAC on the first
4009A device configured in the system. The
device is indicated by the IDNet address
provided.
The status of the third NAC on the first
4009A device configured in the system. The
device is indicated by the IDNet address
provided.
The status of the fourth NAC on the first
4009A device configured in the system. The
device is indicated by the IDNet address
provided.
The status of the fifth NAC on the first
4009A device configured in the system. The
device is indicated by the IDNet address
provided.
The status of the sixth NAC on the first
4009A device configured in the system. The
device is indicated by the IDNet address
provided.
Continued on next page

A-23

Technical Manuals Online! - http://www.tech-man.com

Device Types/Point Types

Point

Addresses for Hardware Points, Continued

4009A Card (continued)


Point

Type

Label
(default)
IDNet M1#: 4009A
NAC 8

17-8

17-9

IDNet M1#: 4009A


NAC 1

17-33

IDNet M1#: 4009A


NAC 1

17-34

IDNet M1#: 4009A


NAC 2

17-35

IDNet M1#: 4009A


NAC 3

17-36

IDNet M1#: 4009A


NAC 4

17-37

IDNet M1#: 4009A


NAC 5

17-38

IDNet M1#: 4009A


NAC 6

17-39

IDNet M1#: 4009A


NAC 7

17-40

IDNet M1#: 4009A


NAC 8

A-24

Technical Manuals Online! - http://www.tech-man.com

Description
The status of the eighth NAC on the first
4009A device configured in the system. The
device is indicated by the IDNet address
provided.
The status of the first NAC on the second
4009A device configured in the system. The
device is indicated by the IDNet address
provided.
The status of the first NAC on the fifth
4009A device configured in the system. The
device is indicated by the IDNet address
provided.
The status of the second NAC on the fifth
4009A device configured in the system. The
device is indicated by the IDNet address
provided.
The status of the third NAC on the fifth
4009A device configured in the system. The
device is indicated by the IDNet address
provided.
The status of the fourth NAC on the fifth
4009A device configured in the system. The
device is indicated by the IDNet address
provided.
The status of the fifth NAC on the fifth
4009A device configured in the system. The
device is indicated by the IDNet address
provided.
The status of the sixth NAC on the fifth
4009A device configured in the system. The
device is indicated by the IDNet address
provided
The status of the seventh NAC on the fifth
4009A device configured in the system. The
device is indicated by the IDNet address
provided.
The status of the eighth NAC on the fifth
4009A device configured in the system. The
device is indicated by the IDNet address
provided.

Addresses for Pseudo Points

Introduction

There are three types of pseudo points that exist in every system. They include
digital, analog, and list pseudo. Each of these types may be referenced in
Custom Control in both the input and output sides of an equation. Reserved
system pseudo points are used to indicate system trouble or alarm indications,
control diagnostics or other system functions, and to communicate information
between the 4010 Master and SMPL. Some pseudos are set by the system and
are read only to the user. Other pseudos are either set from SMPL or from the
front panel as a cue for the system to perform some operation.

Digital Pseudo Points

Every 4010 system has two Digital Pseudo cards at addresses 18 and 19. The
first card is reserved for system pseudo points while the second is available to
the user. Each contains 75 digital pseudo points which may be programmed as
follows:
Type

Description

UTILITY

Utility point (ON/OFF - no acknowledge required)

ALARM

Fire alarm point. Turning the point on causes an ALARM


condition.

SUPV

Supervisory point.

TROUBLE

Trouble point.

Each system digital pseudo point falls into one of the following categories:
Class

Description
Point is controlled by the 4010 master and is read only to the
end user.

RW

Point is controlled by the 4010 master, but may also be


controlled by the end user (front panel or SMPL).

Point is controlled by the end user and is read by the 4010


Master in order to accomplish some function or operation.

The system digital pseudo card in the 4010 system is located at address 18. It
contains a total of 75 reserved system pseudo points that cannot be edited. The
following table list the system pseudo points. The type field denotes which class
(see above) the point falls into, and what its type is (U=UTIL, F=FIRE,
T=TROUBLE, S=SUPERVISORY).
Continued on next page

A-25

Technical Manuals Online! - http://www.tech-man.com

Device Types/Point Types

Addresses for Pseudo Points, Continued

Digital Pseudo Points


(continued)

Point
D1

Type
R U

D2

R U

D3

R U

D4

R T

D5

R T

External N2
Trouble

D6
D7

RW
U
R T

User SMPL
Program
Cold Start

D8

R T

D9
D10

RW
F
R T

D11

R T

D12

RW
U

D13

R T

Warm Start /
Check Time
and Date
Manual
Evacuation
System
Time and
Date
Simplex
Service
Mode
Keypad
Inactivity
Timer
Disable
Active List
Overflow

D14

RW
T
R T

D15
D16

RW
U

Label
Unacked
Fire in
System
Unacked
Supervisory
in System
Unacked
Trouble in
System
Extra N2
Card

City
Disconnect
City Circuit
Trouble
AHJ City
Reset

Description
On if unacked fire exists in system.

On if unacked supervisory exists in system.

On if unacked trouble exists in system.

Turned on at panel startup if an


unprogrammed N2 slave card is detected.
Only clears on panel restart.
Turns on when panel is no longer
communicating with ALL slave cards. Turns
off on a System Reset.
On when User SMPL program is active.
Indicates that panel has performed a cold start.
Turns of when acknowledged.
Indicates that panel has performed a warm
start. Turns off when acknowledged.
Turns on when Manual Evacuation is selected.
Turns off on a System Reset.
Indicates that the time and date is incorrect.
Turns off when time and date is updated.
Indicates that the panel is in Service Mode.
Turns off only on a panel restart.
Disables Keypad Inactivity timer.

Turns on when the number of alarms,


supervisories, or troubles is greater than the
system active list size (50 fires, 50 supv, 100
troubles). Turns off on a panel restart.
On if city circuit is disconnected.
On if city circuit is in trouble.
During a system reset, if this pseudo is On, a
point will reset unless it is in an ALARM
state. A point has to be in a NORMAL state
to reset, when the AHJ pseudo is off.
Continued on next page

A-26

Technical Manuals Online! - http://www.tech-man.com

Addresses for Pseudo Points, Continued

Digital Pseudo Points


(continued)

Point
D17

Type
RW
T

D18

RW
T
RW
T
RW
T

D19
D20

R T

D22

R U

D23

R T

D24

R T

D25

RW
U

D26

RW
U

D27D30

D31

R U

D32D35

D36

R U

D37D44

Description
On if control points are bypassed.

On if elevator recall points are bypassed.


On if doorholder points are bypassed.
On when any verified points tally limit
exceeds 10. Off when all points tally limit is
below 10.
On when Walk Test is active.

On when Earth Fault Latch diagnostic is


active.
On when TrueTest is active.

On when Programming or Quick-CFIG is


entered. Panel is no longer operational.

This point is turned on when a system reset is


initiated. The point may be turned off using
SMPL.
This point is turned on when an alarm silence
is initiated. The point may be turned off using
SMPL.
unused

On if network is in running in degraded Style4.


unused

On if no set-host session is active on network


card.
unused

Continued on next page

A-27

Technical Manuals Online! - http://www.tech-man.com

Device Types/Point Types

D21

Label
Control
Point
Bypass
Elevator
Bypass
Doorholder
Bypass
Verification
Tally Limit
Exceeded
Walk Test
Active in
System
Earth Fault
Latch
TrueTest
Active in
System
Programmin
g Mode System
Disabled
System
Reset
Activated
Alarm
Silence
Activated
Reserved
System
Pseudo
Point
Network
Style 7
Abnormal
Reserved
System
Pseudo
Point
No CRT
Connected
Reserved
System
Pseudo
Point

Addresses for Pseudo Points, Continued

Digital Pseudo Points


(continued)

Point
D45

Type
W T

D46

WT

D47

R T

D48

W T

D49
D50

W U
W U

D51

W U

D52

R U

D53

R U

D54D57

D58

R U

D59

R U

D60
D75

Label
Duplicate
IDNet
Device
Detection
Active
IDNet Weak
Answer
Detection
Active
Event Queue
Overflow
LCD
Annunciator
Sounder
Disable
IDNet Boost
Device
Almost
Dirty
Peak Log
Enable
RS232 Port
A
Disconnecte
d
RS232 Port
B
Disconnecte
d
Reserved
System
Pseudo
Point
Network
System
Reset
Network
Signal
Silence
Digital: P60
Digital: P75

Description
When on (either through front panel or
SMPL) it enables the duplicate device
detection diagnostic on the IDNet card.

When on (either through front panel or


SMPL) it enables the weak answer detection
diagnostic on the IDNet card.
On when the RS232/LCD annunciator event
queue is overflowed and events have been
missed. Panel restart clears the trouble.
When on the panel tells all LCD Annunciators
to disable their local sounder. Turning pseudo
off will enable the sounders. Controllable
from front panel only - not SMPL.
When on it boosts the IDNet levels.
When active it forces IDNet almost dirty
troubles to report.
When on any peak value change recorded on
IDNet devices is sent to the Trouble Log.
On whenever nothing is connected to Port A
on the RS232 or RS232/Modem card.

On whenever nothing is connected to Port B


on the RS232 or RS232/Modem card.

unused

Used in 4120 Network programming to


perform a 4010 System Reset from another
node.
Used in 4120 Network programming to
perform a 4010 Alarm Silence from another
node.
unused
unused
Continued on next page

A-28

Technical Manuals Online! - http://www.tech-man.com

Addresses for Pseudo Points, Continued

4010 User Digital Pseudos

The user digital pseudo card in the 4010 is at address 19. It has 75 points
available for specialized applications programming. Any point may be
programmed as one of the four types of digital pseudos (i.e. UTILITY, FIRE,
etc.), and each may be assigned a 40 character custom label.
Note that any user pseudo points defined as FIRE type are not auto-generated in
the General Alarm List (L1), and SUPERVISORY points are not generated into
the Supervisory Monitor List (L8).

Analog Pseudo Points

Analog pseudo points exist as counters or timers in the 4010 system. SMPL
delay and cycle equations may be written referencing the user Analog pseudo
points on the output side (for delay/cycle operations). Each analog point may
contain a value from 0-65,535 and the point is considered ON when the value is
non-zero. For delay and cycle purposes, the maximum allowable value gives a
real-time range of just over 18 hours. There are two analog pseudo cards in the
4010 system - one reserved for system analogs, and one reserved for user points.

4010 System Analog Pseudos

The 4010 system has one analog pseudo card reserved for system use at address
20. It contains a total of 25 points. At present, only the first 12 are used but the
remainder are reserved for future expansion.
Point
A1
A2
A3
A4
A5
A6
A7
A8

Excessively Dirty
Device Count
Current Year

A9

Current Month

A10

Current Day

A11
A12

Current Hour
Current Minute

Description
Number of fire alarms active in system.
Number of supervisory alarms active in system.
Number of troubles active in system.
Pulsed for one poll cycle during system startup.
Total number of devices that have an almost
dirty status (not necessarily a trouble).
Total number of devices that are in Dirty
Trouble.
Total number of devices that are in Excessively
Dirty Trouble.
Numeric representation of the current calendar
year. (Example: the year 1998 is shown as 98).
Numeric representation of the current calendar
month (1 - 12).
Numeric representation of the current calendar
day.
Current hour (0 - 23).
Current minute (0 - 59).

The user analog pseudo card in the 4010 is at address 21. It has 25 points
available for specialized applications programming. The analog user pseudos
can have custom labels assigned to them.
Continued on next page

A-29

Technical Manuals Online! - http://www.tech-man.com

Device Types/Point Types

4010 User Analog Pseudos

Label
Fire Count
Supervisory Count
Trouble Count
System Startup
Almost Dirty
Device Count
Dirty Device Count

Addresses for Pseudo Points, Continued

List Pseudo Points

List psuedo points provide a convenient way to group points in any manner the
user desires. The 4010 contains two list pseudo cards - one reserved for the
system and one for the user. The status of the list is determined by counts which
are maintained for the following states:

Fire Count
Trouble Count
Supervisory Count
Normal
Open
Limited
Short
Fire Ack
Trouble Ack
Supervisory Ack
Disable
On/Input
On/Coding
Manual Control

The 4010 restricts the total number of points in any one list to 255. It also
restricts the total number of points available on any one list card to 500 (the total
number of points in all lists on one list card cannot exceed 500).
4010 System Lists

The 4010 system reserves one list card at address 22 for system use. Currently,
12 of the 25 system lists are used by the 4010 application. All of these lists
control application specific operation of the 4010 panel. Some are autogenerated by the system as points are added and may not be edited, while the
remainder are filled by the user to activate pre-defined applications. The system
lists are shown below:
Point
L1

Label
General Alarm
Monitor Points

L2

Waterflow Alarm
Monitor Zones

L3

Sprinkler Supervisory
Monitor Zones

L4

Primary Elevator
Recall Monitors
Alternate Elevator
Recall Monitors

L5

Description
Auto-generated by the panel and not
editable. Contains all fire-alarm monitor
points in the system plus the Manual Evac
pseudo. User FIRE digital pseudos are not
auto-generated here.
Auto-generated by the panel and not
editable. Contains all waterflow-type
monitor points (WSO)
Auto-generated by the panel and not
editable. Contains all sprinkler-type monitor
points (SO)
Filled by the user. When in fire state, will
activate the primary elevator recall function.
Filled by the user. When in fire state, will
activate the alternate elevator recall function.
Continued on next page

A-30

Technical Manuals Online! - http://www.tech-man.com

Addresses for Pseudo Points, Continued

4010 System Lists (continued)


Point
L6
L7

4010 User Lists

Label
Control Points, Off
With Silence
Control Points, Off
With Reset

L8

Supervisory Monitor
Points

L9

Automatic
Suppression Release
Points

L10

Suppression Manual
Release Points

L11

Suppression Release
Abort Points

L12

Suppression Release
Output Points

Description
Filled by the user. Turns on when L1 is in
FIRE detect, turns off with alarm silence.
Filled by the user. Turns on when L1 is in
FIRE detect, turns off with completed system
reset.
Auto-generated by the system - may be
edited. Contains all Supervisory type
monitor points.
Auto-generated by the system - may be
edited. When in fire state, causes L12 to
activate after automatic release delay timer
expires.
Auto-generated by the system - may be
edited. When in the fire state, causes L12 to
activate after manual release delay timer
expires.
Auto-generated by the system - may be
edited. When in the supervisory state, causes
the suppression release sequence to abort.
Auto-generated by the system - may be
edited. Activated by the panel when the
suppression release algorithm completes.

The user list pseudo card in the 4010 is at address 23. It has 25 points available
that may be filled by the user for specialized applications. The user lists may
have custom labels assigned to them.

Device Types/Point Types

A-31

Technical Manuals Online! - http://www.tech-man.com

This page intentionally blank

Technical Manuals Online! - http://www.tech-man.com

Introduction

How to Use the Table

This appendix contains the Base 10 to Base 36 Conversion Table. Use this table
to convert your Base 10 branch and job numbers to the Base 36 format required
by the Programmer (see Chapter 2).

Use the following procedure to convert your Base 10 number to the equivalent
Base 36 number:
1. Find the number in the Base 10 column of the table.
2. Look in the adjacent Base 36 column to see the corresponding Base 36
number.

B-1

Technical Manuals Online! - http://www.tech-man.com

Conversion Table

Appendix B
Conversion Table

Base 10 to Base 36 Conversion Table


Base 10 Base 36 Base 10 Base 36 Base 10 Base 36 Base 10 Base 36 Base 10 Base 36
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49

0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
Q
R
S
T
U
V
W
X
Y
Z
10
11
12
13
14
15
16
17
18
19
1A
1B
1C
1D

50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
81
82
83
84
85
86
87
88
89
90
91
92
93
94
95
96
97
98
99

1E
1F
1G
1H
1I
1J
1K
1L
1M
1N
1O
1P
1Q
1R
1S
1T
1U
1V
1W
1X
1Y
1Z
20
21
22
23
24
25
26
27
28
29
2A
2B
2C
2D
2E
2F
2G
2H
2I
2J
2K
2L
2M
2N
2O
2P
2Q
2R

100
101
102
103
104
105
106
107
108
109
110
111
112
113
114
115
116
117
118
119
120
121
122
123
124
125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
140
141
142
143
144
145
146
147
148
149

2S
2T
2U
2V
2W
2X
2Y
2Z
30
31
32
33
34
35
36
37
38
39
3A
3B
3C
3D
3E
3F
3G
3H
3I
3J
3K
3L
3M
3N
3O
3P
3Q
3R
3S
3T
3U
3V
3W
3X
3Y
3Z
40
41
42
43
44
45

151
152
153
154
155
156
157
158
159
160
161
162
163
164
165
166
167
168
169
170
171
172
173
174
175
176
177
178
179
180
181
182
183
184
185
186
187
188
189
190
191
192
193
194
195
196
197
198
199
200

47
48
49
4A
4B
4C
4D
4E
4F
4G
4H
4I
4J
4K
4L
4M
4N
4O
4P
4Q
4R
4S
4T
4U
4V
4W
4X
4Y
4Z
50
51
52
53
54
55
56
57
58
59
5A
5B
5C
5D
5E
5F
5G
5H
5I
5J
5K

201
202
203
204
205
206
207
208
209
210
211
212
213
214
215
216
217
218
219
220
221
222
223
224
225
226
227
228
229
230
231
232
233
234
235
236
237
238
239
240
241
242
243
244
245
246
247
248
249
250

5L
5M
5N
5O
5P
5Q
5R
5S
5T
5U
5V
5W
5X
5Y
5Z
60
61
62
63
64
65
66
67
68
69
6A
6B
6C
6D
6E
6F
6G
6H
6I
6J
6K
6L
6M
6N
6O
6P
6Q
6R
6S
6T
6U
6V
6W
6X
6Y

Continued on next page

B-2

Technical Manuals Online! - http://www.tech-man.com

Base 10 Base 36 Base 10 Base 36 Base 10 Base 36 Base 10 Base 36 Base 10 Base 36
251
252
253
254
255
256
257
258
259
260
261
262
263
264
265
266
267
268
269
270
271
272
273
274
275
276
277
278
279
280
281
282
283
284
285
286
287
288
289
290
291
292
293
294
295
296
297
298
299
300

6Z
70
71
72
73
74
75
76
77
78
79
7A
7B
7C
7D
7E
7F
7G
7H
7I
7J
7K
7L
7M
7N
7O
7P
7Q
7R
7S
7T
7U
7V
7W
7X
7Y
7Z
80
81
82
83
84
85
86
87
88
89
8A
8B
8C

301
302
303
304
305
306
307
308
309
310
311
312
313
314
315
316
317
318
319
320
321
322
323
324
325
326
327
328
329
330
331
332
333
334
335
336
337
338
339
340
341
342
343
344
345
346
347
348
349
350

8D
8E
8F
8G
8H
8I
8J
8K
8L
8M
8N
8O
8P
8Q
8R
8S
8T
8U
8V
8W
8X
8Y
8Z
90
91
92
93
94
95
96
97
98
99
9A
9B
9C
9D
9E
9F
9G
9H
9I
9J
9K
9L
9M
9N
9O
9P
9Q

351
352
353
354
355
356
357
358
359
360
361
362
363
364
365
366
367
368
369
370
371
372
373
374
375
376
377
378
379
380
381
382
383
384
385
386
387
388
389
390
391
392
393
394
395
396
397
398
399
400

9R
9S
9T
9U
9V
9W
9X
9Y
9Z
A0
A1
A2
A3
A4
A5
A6
A7
A8
A9
AA
AB
AC
AD
AE
AF
AG
AH
AI
AJ
AK
AL
AM
AN
AO
AP
AQ
AR
AS
AT
AU
AV
AW
AX
AY
AZ
B0
B1
B2
B3
B4

401
402
403
404
405
406
407
408
409
410
411
412
413
414
415
416
417
418
419
420
421
422
423
424
425
426
427
428
429
430
431
432
433
434
435
436
437
438
439
440
441
442
443
444
445
446
447
448
449
450

B5
B6
B7
B8
B9
BA
BB
BC
BD
BE
BF
BG
BH
BI
BJ
BK
BL
BM
BN
BO
BP
BQ
BR
BS
BT
BU
BV
BW
BX
BY
BZ
C0
C1
C2
C3
C4
C5
C6
C7
C8
C9
CA
CB
CC
CD
CE
CF
CG
CH
CI

451
452
453
454
455
456
457
458
459
460
461
462
463
464
465
466
467
468
469
470
471
472
473
474
475
476
477
478
479
480
481
482
483
484
485
486
487
488
489
490
491
492
493
494
495
496
497
498
499
500

CJ
CK
CL
CM
CN
CO
CP
CQ
CR
CS
CT
CU
CV
CW
CX
CY
CZ
D0
D1
D2
D3
D4
D5
D6
D7
D8
D9
DA
DB
DC
DD
DE
DF
DG
DH
DI
DJ
DK
DL
DM
DN
DO
DP
DQ
DR
DS
DT
DU
DV
DW

Continued on next page

B-3

Technical Manuals Online! - http://www.tech-man.com

Conversion Table

Base 10 to Base 36 Conversion Table, Continued

Base 10 to Base 36 Conversion Table, Continued

Base 10 Base 36 Base 10 Base 36 Base 10 Base 36 Base 10 Base 36 Base 10 Base 36
501
502
503
504
505
506
507
508
509
510
511
512
513
514
515
516
517
518
519
520
521
522
523
524
525
526
527
528
529
530
531
532
533
534
535
536
537
538
539
540
541
542
543
544
545
546
547
548
549
550

DX
DY
DZ
E0
E1
E2
E3
E4
E5
E6
E7
E8
E9
EA
EB
EC
ED
EE
EF
EG
EH
EI
EJ
EK
EL
EM
EN
EO
EP
EQ
ER
ES
ET
EU
EV
EW
EX
EY
EZ
F0
F1
F2
F3
F4
F5
F6
F7
F8
F9
FA

551
552
553
554
555
556
557
558
559
560
561
562
563
564
565
566
567
568
569
570
571
572
573
574
575
576
577
578
579
580
581
582
583
584
585
586
587
588
589
590
591
592
593
594
595
596
597
598
599
600

FB
FC
FD
FE
FF
FG
FH
FI
FJ
FK
FL
FM
FN
FO
FP
FQ
FR
FS
FT
FU
FV
FW
FX
FY
FZ
G0
G1
G2
G3
G4
G5
G6
G7
G8
G9
GA
GB
GC
GD
GE
GF
GG
GH
GI
GJ
GK
GL
GM
GN
GO

601
602
603
604
605
606
607
608
609
610
611
612
613
614
615
616
617
618
619
620
621
622
623
624
625
626
627
628
629
630
631
632
633
634
635
636
637
638
639
640
641
642
643
644
645
646
647
648
649
650

B-4

Technical Manuals Online! - http://www.tech-man.com

GP
GQ
GR
GS
GT
GU
GV
GW
GX
GY
GZ
H0
H1
H2
H3
H4
H5
H6
H7
H8
H9
HA
HB
HC
HD
HE
HF
HG
HH
HI
HJ
HK
HL
HM
HN
HO
HP
HQ
HR
HS
HT
HU
HV
HW
HX
HY
HZ
I0
I1
I2

Index
programming, 6-1
programming 24 point I/O, 6-32
programming AUX relay, 6-11
programming IDNet, 6-13
programming master controller, 6-5
programming NAC card, 6-9
programming pseudo point cards, 6-16
CD-ROM
installing on a system without, 2-4
installing programmer from CD-ROM, 2-7
CFIG
building, 11-2
downloading to panel, 11-3
class A NACs, 6-9
class B NACs, 6-9
communication parameters
setting, 3-2
custom control
adding an equation, 10-6
adding inputs and outputs, 10-7
editing input properties, 10-8
editing output properties, 10-19
input opcodes, 10-10
output opcodes, 10-19
overview of equation, 10-4
custom control tab, 1-3
overview, 10-2
custom labels, 7-11
for AUX relays, 6-12
for NACs, 6-10
spell check for, 7-3

Misc.
24 point I/O card, 6-32
24 point I/O cards
output points, 6-36
4009 IDNet NAC Extender, 1-6
4120 network card
programming, 6-29

A
access levels, 5-9
active status reminder system option, 5-7
adding cards, 6-4
AHJ alarm city circuit programming, 1-7
AHU stagger start system option, 5-5
alarm cutout timer system option, 5-4
alarm pseudo point, 6-18
alarm silence/inhibit system option, 5-4
analog system pseudos, 6-18
analog user pseudos, 6-19
point types for, 6-20
AND operator, 10-4
archiving jobs, 4-13
AutoFill
and card tab, 6-3
and point tab, 7-3
AUX relay
custom labels for, 6-12
point types for, 6-12
programming, 6-11

D
B

day/night programming, 1-6


deleting cards, 6-4
depleted battery system option, 5-4
and suppression release, 5-6
device types, 7-5
for IDNet points, 6-14
NAC, 6-9
summary of, 1
digital system pseudos, 6-16
door drop on AC fail system option, 5-5
door drop on alarm system option, 5-5
download
and warm start, 3-8
BIN file, 3-1
communication parameters, 3-2
connecting cable, 3-2
connecting cable for, 11-4
enabling on panel, 11-4
enabling panel for, 3-4
procedure for, 3-6
required cable, 3-2
warning about backup and archive, 3-5
downloading a CFIG

backing up jobs, 4-13


Base 36 conversion, 4-6
battery charger trouble, 1-6
baud rate, 3-3
BIN file, 3-1
connecting download cable, 3-2
default directory for, 3-6
downloading to panel, 3-1
required download components, 3-1
when to download. See
building a job, 11-2

C
card tab, 1-3
and AutoFill, 6-3
overview, 6-2
cards
4120 network, 6-29
adding and deleting, 6-4
dual RS-232 card, 6-22
LCD annunciator, 6-37

IN-1

Technical Manuals Online! - http://www.tech-man.com

downloading to panel, 11-3

defined, 9-3
list tab, 1-3
overview, 8-2
sorting points within, 8-3
lists
adding/deleting points, 8-4
naming, 8-4

E
Earth ground detect
user-defined LED example, 6-7
EXEC. See BIN file
existing jobs
opening, 4-7

M
master controller card, 6-5
menu structure, 1-4
menus, 1-2

F
F4 key, 6-3
firmware
and compatibility, 1-8
floppy disks, 2-4
installing programmer from, 2-7
function keys
programming user-defined, 6-7

N
NACs
and signal operation system option, 5-7
custom labels for, 6-10
device types for, 6-9
point types for, 6-10
programming NAC card, 6-9

G
general information
setting, 5-2

O
OR operator, 10-5
oswitch point type, 6-32
overview, 1-1
programmer components, 1-2

I
icons, 1-2
summary of functions, 1-4
IDNet card
device types for, 6-14
point types for, 6-15
programming, 6-13
installation, 2-1
creating floppy disks, 2-4
installing programmer from CD-ROM, 2-7
required components, 2-1
system requirements, 2-2

P
panel
and Quick CFIG, 4-2
setting baud rate, 3-3
panel tab, 1-3
and general information, 5-3
and system options, 5-3
passcodes, 5-9
point addresses
summary of, 1
point tab, 1-3
overview of, 7-2
point types
24 point I/O input types, 6-32
24 point I/O output types, 6-36
defined, 7-8
for 24 point I/O, 6-32
for analog user pseudos, 6-20
for AUX relay, 6-12
for IDNet points, 6-15
for user digital pseudos, 6-18
NAC, 6-10
summary of, 1
programmer
features of each version, 1-8
starting, 4-4
warning about suppression point types, 5-6
pseudo points, 6-16
analog system pseudos, 6-18
analog user pseudos, 6-19

J
job number format, 4-6
jobs
and older SFIO components, 1-9
archiving, 4-13
backing up, 4-13
building and downloading, 11-2
creating a new job, 4-5
downloading to panel, 11-3
format of job number, 4-6
opening an existing, 4-7
restoring, 4-13
saving, 4-13
uploading from panel, 4-8

L
LCD annunciator, 6-37
leaf
defined, 9-3
level

IN-2

Technical Manuals Online! - http://www.tech-man.com

digital system pseudos, 6-16


system defined list pseudos, 6-20
user digital pseudos, 6-17
user-defined list pseudo points, 6-21

system defined list pseudos, 6-20


system options, 5-3
active status reminder, 5-7
AHU stagger start, 5-5
alarm cutout timer, 5-4
alarm silence inhibit, 5-4
depleted battery, 5-4
door drop on AC fail, 5-5
door drop on alarm, 5-5
signal operation, 5-7
suppression release, 5-6
time format, 5-3

Q
QALERT device type, 1-7
Quick CFIG, 1-7
procedure for new panels, 4-2
TrueAlert Non-Addressable NAC devices, 1-7
alarm operation, 1-7
and Quick CFIG, 1-7
and signal operation system option, 5-7
horn operation for, 1-7
SMPL programming of, 1-7

T
tabs, 1-2
overview of, 1-3
time format system option, 5-3
trouble pseudo point, 6-18
tswitch point type, 6-32

R
related documents, 1-1
restoring jobs, 4-13
RS-232 card
configuring, 6-22
RS-232 service modem card
programming, 6-24
service modem commands for, 6-26

U
upgrade, 2-1, 2-7
compatibility, 1-8
uploading jobs, 4-8
and baud rate, 4-8
communication parameters, 4-8
procedure for, 4-8
user digital pseudos, 6-17
point types for, 6-18
user-defined function keys, 6-7
user-defined LED
Earth ground detect example, 6-7
waterflow indicator example, 6-6
user-defined LEDs, 6-5
user-defined list pseudos, 6-21
uswitch point type, 6-32
utility pseudo point, 6-18
utility temperature sensing, 1-6

S
saving jobs, 4-13
setting baud rate, 3-3
SFIO board
and compatibility, 1-8
SFIO card, 6-5
programming user-defined function keys, 6-7
programming user-defined LEDs on, 6-5
signal operation system option, 5-7
single station
setting, 6-15
site tab, 1-3
overview, 9-3
site tree
building, 9-5
overview, 9-2
SMPL programming
QALERT device type, 1-7
software key, 2-3
SQALERT device type, 1-7
sswitch point type, 6-32
stagger start system option, 5-5
starting the programmer, 4-4
supervisory pseudo point, 6-18
suppression release system option, 5-6

V
Version 2.x features, 1-6

W
warm start
and download, 3-8
waterflow indicator
user-defined LED example, 6-6

IN-3

Technical Manuals Online! - http://www.tech-man.com

This page intentionally blank

Technical Manuals Online! - http://www.tech-man.com

This page intentionally blank

Technical Manuals Online! - http://www.tech-man.com

Rev. C

Simplex Time Recorder Co., Simplex Plaza Westminster, Massachusetts 01441-0001 U.S.A.
Simplex International Time Equipment, Co., LTD. Mississauga, Ontario, Canada

Technical Manuals Online! - http://www.tech-man.com

574-187

S-ar putea să vă placă și