Documente Academic
Documente Profesional
Documente Cultură
Metropolitan Express
Railway
Evacuation and ventilation
November 2009
COWI A/S
Parallelvej 2
DK-2800 Kongens Lyngby
Denmark
Tel +45 45 97 22 11
Fax +45 45 97 22 12
www.cowi.com
Document no.
72156-2
Version
1.0
Date of issue
2009-11-23
Prepared
JK/MF
Checked
PON
Approved
PON
Table of Contents
1
Introduction
4
4.1
4.2
4.3
4.4
4.5
10
10
11
11
12
15
5
5.1
17
17
6
6.1
6.2
6.3
Basic option
Description of the option
Tunnel ventilation
Safety consideration incl. evacuation
19
19
20
22
26
26
27
29
31
31
32
34
7.1
7.2
7.3
8
8.1
8.2
8.3
P:\57050Z\188 (Korea deep railway tunnel)\Report Evac and Vent\72156-2 Evacuation and ventilation.docx
9
9.1
9.2
9.3
37
37
39
41
10
Comparison
44
11
References
48
P:\57050Z\188 (Korea deep railway tunnel)\Report Evac and Vent\72156-2 Evacuation and ventilation.docx
Introduction
Dividing wall
In this concept it is assumed that the two railway tracks are separated by a
fire proof dividing wall. The dividing wall has emergency doors at close
P:\57050Z\188 (Korea deep railway tunnel)\Report Evac and Vent\72156-2 Evacuation and ventilation.docx
distance. This concept will require a larger tunnel diameter than in the other options.
The basic option and the modifications are considered in sections 6, 7, 8 and 9,
respectively covering:
Ventilation
P:\57050Z\188 (Korea deep railway tunnel)\Report Evac and Vent\72156-2 Evacuation and ventilation.docx
COWI has regarding safety and ventilation considered the basic option as
well as some modified options for the Seoul Metropolitan Express Railway.
The accident considered is a train on fire stopped in the tunnel. The conclusion
is, that the concept is not so much governed by considerations of ventilation
system capacity, as by considerations of safe passenger evacuation and safe
access for the fire brigade.
The basic option with a two track tunnel has been considered. This option
can in theory, with a distance of maximum 500 m between entrances to safe
spaces in shelters, fulfill international standards. This concept is however depending on a satisfactory detailing of the access to the shelters and of the shelters themselves (they need to accommodate a lot of passengers and the width of
the access seems to be limited to less than required in international standards).
In addition to the shelters we have considered a distance of 2500 m between
shafts for fire brigade access (and evacuation of passengers not going to the
shelters) and 1250 between ventilation shafts. This is deemed a satisfactory solution for fire brigade safety and safety of other trains in the tunnel even
though the more shafts the better.
According to the information we have received, the passenger density in the
system is very high. This means that evacuation time may be too long even
though the width of the walkways in the tunnel fulfills normal standard requirements. The evacuation time should be studied using appropriate models
such as EXODUS, as opposed to the very rough estimates that could be included in this report.
In order to suggest on some improvements to the basic concept we have considered three modified options:
Emergency corridor
We think that the use of an emergency corridor below the tracks rather than
shelters is a better solution, as it allows the passengers to evacuate completely
from the tunnel rather than having so many passengers waiting in a relatively
P:\57050Z\188 (Korea deep railway tunnel)\Report Evac and Vent\72156-2 Evacuation and ventilation.docx
P:\57050Z\188 (Korea deep railway tunnel)\Report Evac and Vent\72156-2 Evacuation and ventilation.docx
costs are larger, this option should be preferred, as long as the additional costs
are not disproportionate with the value of the reduction in risk.
We hope that the description and evaluation of ventilation concept and evacuation facilities provided in this report for the "basic option" and three modified
options will provide a valuable basis for the feasibility study for Seoul Metropolitan Express Railway.
P:\57050Z\188 (Korea deep railway tunnel)\Report Evac and Vent\72156-2 Evacuation and ventilation.docx
There are several proposals for the alignment of the Seoul Metropolitan Express Railway. For the purpose of this report we have been looking at the
alignment from Song-do (new development area at Incheon) to Cheong-ryangri (North of the Seoul City Centre), please see the illustration on the next page.
The information on the considered system has been received through drawings,
sketches, questions and answers exchanged in e-mail correspondence with
SUNJIN.
Alignment and stations
The planned express railway system is all underground and with underground
stations. Distance between stations varies between 2.9 km and 9.3 km. The stations are closest in the city centre and more distant around Incheon. On the
Cheong-ryang-ri to Song-do express railway line, which is approximately 50
km long, there are 9 stations. The stations will be highest standard and
equipped with platform screen doors.
The tunnels are typically located at a depth of 30 50 meters below ground surface.
Rolling stock
The trains for the express railway system are expected to be electrical trains
with overhead catenary.
Pressure tightness coefficient =15 sec corresponding to a train with excellent sealing.
P:\57050Z\188 (Korea deep railway tunnel)\Report Evac and Vent\72156-2 Evacuation and ventilation.docx
P:\57050Z\188 (Korea deep railway tunnel)\Report Evac and Vent\72156-2 Evacuation and ventilation.docx
10
4.1
As part of the basis of the design of an underground railway system, the risk to
the passengers shall be identified, such that appropriate precautions can be taken against these risks. A brief identification is carried out here, pointing on the
following risks to the passengers of the Metropolitan Express Railway:
Risk in the trains not related to train accidents (e.g. stumbling when moving in the train or falling as the train brakes)
Train collision
Train derailment
Train fire
Collapse of structures
P:\57050Z\188 (Korea deep railway tunnel)\Report Evac and Vent\72156-2 Evacuation and ventilation.docx
11
For the design of evacuation and rescue facilities the fire accidents are of most
concern, as the time aspects here are very important. These accidents will also
be a major contribution to the overall risk of the train passengers. Hence train
fires are the focus of this report.
Train fires following accidents can have even larger consequences than train
fires not caused by such other accidents, as passengers may be injured in the
initial accidents and therefore not able to escape from the fire. Furthermore in
train collisions there will be two trains involved, such that number of passengers having to escape will be approximately doubled. However, it follows from
the list of tunnel fires presented in Ref. /4/ that there are recorded very few of
such fires (since 1980 only the derailment 13. Jan. 1982 in the Washington DC
underground railway/metro; some more in the earlier records).
Hence only a fire in a single train, stopped in the tunnel between stations, is
considered in this report. This accident is further discussed in section 4.3.
4.2
Risk acceptance
Risk reduction is implemented according to the ALARP principle, see section 4.5.
4.3
International standards
A brief review of major international standards for railway tunnels has been
carried out regarding requirements to escape routes and access of the fire brigade. The standards covered are:
P:\57050Z\188 (Korea deep railway tunnel)\Report Evac and Vent\72156-2 Evacuation and ventilation.docx
12
The results are shown in the table below. It is noted that if cross passages are
provided, then it is not required also to have exits to open air. It is further noted
that UIC 779-9 indicates that the requirements for width of access routes is only
for single bore tunnels (one or two tracks). In UIC 779-9 it is indicated that the
safety measures are to be seen as guidelines but not as strict rules.
Width of walkways
Paragraph
Height of walkways
Paragraph
Distance between cross passages
Paragraph
Distance between exits
Paragraph
Width of escape doors
Paragraph
Height of escape doors
Paragraph
Width of cross passages
Paragraph
Height of cross passages
Paragraph
Width of escape stairs
Paragraph
Width of access routes
Paragraph
Table 4-1
4.4
4.2.2.7
I-40
2.25
4.2.2.7
244
500
500
6.2.2.3
4.2.2.6.4
I-43
762
1000
1000
6.2.2.2
4.2.2.6.3
I-43
1.4
4.2.2.2.6.3&4
2.0
4.2.2.2.6.3&4
1.12
1.5
2.25
6.2.2.3.2
4.2.2.2.6.4
I-46
2.1
2.25
2.25
6.2.2.3.2
4.2.2.2.6.4
I-46
1.2
I-44
2.25
2.25
4.2.2.11
I-45
Train fires
The risk from train fires is generally reduced by the following measures:
The trains will be equipped with fire extinguishers, such that minor fires
inside the train may be extinguished. (Our assumption in accordance with
current practice).
P:\57050Z\188 (Korea deep railway tunnel)\Report Evac and Vent\72156-2 Evacuation and ventilation.docx
13
Any train on fire will attempt to drive to the next station if at all possible,
as the risk to the passengers will be much less, when the train is stopped
here, than if the train should stop in the tunnel. (Our assumption in accordance with current practice).
There will be fire detectors on the trains, such that a fire will be detected
early. This will improve the possibilities of the train on fire reaching a station. (Our assumption in accordance with current practice).
In spite of these precautions, a train on fire may stop in the tunnel between stations. This is the situation which is considered further in this report, as this accident scenario will be governing for the safety design of the tunnels.
The critical issues in the event of such an accident are:
The passengers shall be able to escape from the burning train to a safe location (self rescue of the passengers). Here the capacity of the evacuation
routes and the distance to the safe location is of concern.
Passengers of other trains in the same tunnel shall be protected against the
smoke from the burning train, either by the train driving out of the tunnel
or by the ventilation system ensuring fresh air to these other trains. A situation where passengers from other trains than the burning train will have to
evacuate in a smoke-filled tunnel should be avoided.
The fire brigade has good access to the accident location, such that they
can rescue passengers not able to escape and fight the fire.
The fire accidents scenario is established including the number of passengers in the train, the fire curve, how far the fire is developed, when the
train stops, the time from train stop till evacuation of the passengers is established and the envisaged operation of the emergency ventilation.
The smoke spread and resulting temperatures in the tunnel are established.
This work is part of the risk analysis work mentioned in section 4.2.
P:\57050Z\188 (Korea deep railway tunnel)\Report Evac and Vent\72156-2 Evacuation and ventilation.docx
14
Here a very rough and simplistic calculation of evacuation time has been carried out using the method prescribed in NFPA 130, Ref. /1/, for documenting
the adequacy of escape routes from station platforms. In order to be able to use
this method in the tunnel the following simplifications have been made:
The escape from the train to the walkway along the train has not been considered.
The prescribed deduction of 300 mm sidewalls and 460 mm at open platform edges has not been taken into account, as this would reduce the width
of the walkway to be used in the calculation to close to zero.
The numbers from NFPA used in the very rough calculation of evacuation time
are:
Other trains
A train ahead of the burning train will continue to the next station
A train behind the burning train will have to stop. It may drive backwards
to the station from where it came, but reversing the train traffic may take
some time. Possibly, the fire may burn down the catenary overhead line
before this is done.
If the tunnel contains only a single track, then air flow will be in direction
of the running trains and thus preventing smoke from reaching the train
behind the burning train. This direction of the air flow will be maintained
by the ventilation systems, such that the passengers can escape in smokefree air, if it is not possible to drive the train back to the previous station.
In case of a tunnel with two tracks, as is the case here, there will be no distinct airflow protecting a train behind the burning train. A longitudinal
ventilation system is not suitable for protecting the train in this situation, as
it may adversely affect trains in the other track on the opposite side of the
fire. The train may be protected if smoke can be extracted at a location between the burning train and the stopped train.
P:\57050Z\188 (Korea deep railway tunnel)\Report Evac and Vent\72156-2 Evacuation and ventilation.docx
15
A train, that has passed the burning train, will continue to the next station.
For a train, that has not yet passed the burning train, may attempt to drive
past the burning train, but this may be dangerous, as the fire may burn
down the catenary overhead line, stopping the train close to the fire. If the
passengers have already started evacuation from the burning train, driving
past the burning train is not an option.
If the train instead is stopped, then it may drive back to the station from
where it came, but as described above this may be prevented by the burning down of the catenary overhead line. A stopped train may be protected
if smoke can be extracted at a location between the burning train and the
stopped train.
The access of the fire brigade in a railway tunnel may generally be by one of
the following means:
Through a station or emergency access shaft and then along the tunnel.
Movement in the tunnel may be along an emergency walkway or along the
tracks by means of a small trolley, which is located in a room at the stations and in the bottom of the emergency shafts.
Using an emergency train. Emergency trains located at each end of the line
would not be able to drive to the scene of the accidents, due to the trains
stopped in the system in an emergency. Having an emergency train located
at a side track at each station would be a very costly option.
4.5
ALARP principle
P:\57050Z\188 (Korea deep railway tunnel)\Report Evac and Vent\72156-2 Evacuation and ventilation.docx
16
High risk
Unacceptable
region
ALARP/
ALARA
region:
Broadly
acceptable
region Negligible risk
Figure 4-1
ALARP principle
P:\57050Z\188 (Korea deep railway tunnel)\Report Evac and Vent\72156-2 Evacuation and ventilation.docx
17
During normal as well as congested operation, to obtain acceptable environmental conditions for the passengers in the trains.
5.1
During fire accidents to ensure smoke-free escape routes via the escape
corridor, the shelters and the stairs. In the option with dividing wall, to ensure smoke-free corridor under the tracks for fire brigade approach to the
scene of the fire.
P:\57050Z\188 (Korea deep railway tunnel)\Report Evac and Vent\72156-2 Evacuation and ventilation.docx
18
P:\57050Z\188 (Korea deep railway tunnel)\Report Evac and Vent\72156-2 Evacuation and ventilation.docx
19
Basic option
6.1
The cross section of the basic option is single tube tunnel with two railway
tracks. The tunnel has an internal diameter of 11.060 m.
The tunnel is equipped with ventilation as described below. The jet fans are
used as supplementary fans for the tunnel ventilation.
On each side of the two railway tracks there is a 0.8 m wide emergency walkway.
Jet fans
Walkway
Walkway
Ventilation of
emergency shelter
Utilities
Shelter
Figure 6-1
P:\57050Z\188 (Korea deep railway tunnel)\Report Evac and Vent\72156-2 Evacuation and ventilation.docx
20
In an emergency situation the trains can be evacuated via the emergency walkway to the evacuation shaft. Furthermore under the tracks there are shelters
which are accessible through emergency hatches located between the railway
tracks.
The shelters can resist the design fire. They are equipped with a separate system for fresh air supply and they have signboards with instructions for evacuated passengers. Also they are equipped with intercom and cameras connected to the railway system control center, so the passengers will be able to
communicate with the staff of the control center in an emergency situation.
The distance between big shafts, i.e. shafts with both stairs and ventilation is
assumed to be 2500 m. This distance is chosen as a reasonable distance for fire
brigade emergency access for the tunnel. In between the big shafts there are
small ventilation shafts (5 m2 or around 3 m diameter). These shafts can be
used for smoke exhaust to make sure that the route to and from big shafts, as far
as possible, is free of smoke in an emergency situation. The exact location of
the shafts can vary in order to accommodate the actual distance between stations.
The main features of the basic option are summarized in the Table 10-1.
6.2
Tunnel ventilation
The tunnel ventilation is divided in sections: from station to station. Only for
one typical section the tunnel ventilation system is described in the text and
shown in Figure 6-1.
At stations:
- Reversible ventilation plant for supply/extraction.
- Piston effect shafts.
In the tunnel:
- Jet fans to be used as booster fans for the tunnel ventilation in particular
cases.
P:\57050Z\188 (Korea deep railway tunnel)\Report Evac and Vent\72156-2 Evacuation and ventilation.docx
21
2500
L
1250
2500
1250
1250
1250
Emergency
Exit
Smoke
exhaust
Emergency
Exit
Smoke
exhaust
Station
Shelte
Shelte
Shelter
Shelter
Shelter
Shelter
Stopped train
Jet Fan
Fresh air supply
Smoke exhaust
Smoke exhaust
Escape route
Figure 6-2
P:\57050Z\188 (Korea deep railway tunnel)\Report Evac and Vent\72156-2 Evacuation and ventilation.docx
22
The ventilation plants for pressurization of shelters, corridor and staircases will
be started when a fire occurs.
Because there are two tracks, there may be trains trapped in front of the burning
train on the other track and behind it on the same track. Therefore longitudinal
ventilation can not be used during the evacuation.
As shown in Figure 6-2 the trapped trains on both side of the fire site can be
free of smoke. The fresh air supply from stations and emergency shafts create a
flow with a velocity vCritical. The jet fans can be used to maintain the velocity.
After the evacuation, the Fire Brigade can change to longitudinal ventilation, to
get smoke-free access to the fire site from the one side. The Ventilation plants
shall therefore have the necessary capacity to maintain an air flow with critical
velocity. During this operation, it may be necessary to use the jet fans.
6.3
P:\57050Z\188 (Korea deep railway tunnel)\Report Evac and Vent\72156-2 Evacuation and ventilation.docx
23
length of the shelter should be several times the length of the train. The layout
of the shelter requires further consideration taking into account:
How the passengers shall spread along the very long shelter from the
access stairs.
Considering the small width of the shelter, it may be difficult to establish a design that will work in an emergency. E.g. the first passengers entering the shelter may stop immediately within the shelter, such that the following passengers
will not be able to enter the shelter.
It follows from Figure 6-1 that the width of the staircases leading down to shelter is in the order of 0.8 m. This is less than the widths indicated in Table 4-1
(1.12 m width of cross passage indicated by NFPA 130, and 1.4 m width of escape door indicated by 2001/16/EC). However, with the present tunnel diameter it is hardly possible to make a wider staircase.
The evacuation capacity of a staircase of a certain width is less than the evacuation capacity of a walkway of the same width. Even though the passengers initially may only walk on one of the walkways away from the burning train they
may later spread on both walkways. There should therefore be three stairs at
each end of the shelter in order to provide a capacity corresponding to the two
walkways. (According to NFPA 130, Ref. /1/, the capacity of a walkway is
0.0819 persons per mm and minute and the capacity of stairs 0.0555 persons
per mm and minute).
The design of the entrances to the staircases need further considerations regarding how the lid down to the stairs will open and how handrails preventing the
passengers from falling down into the staircase hole are arranged.
A rough calculation, using NFPA 130 as described in section 4.4, of time for
the passengers to reach safety within the shelters gives the following results:
The time for the passengers to walk past the end of train on one walkway is
estimated at 674 / (0.0819 min-1 mm-1 0.8 m) = 10.3 min.
The time to walk from the end of the train to the entrance to the shelter will
be maximum 500 m will be 500 m / 38 m/min = 13.2 min.
P:\57050Z\188 (Korea deep railway tunnel)\Report Evac and Vent\72156-2 Evacuation and ventilation.docx
24
The total time until the last passenger is within the shelter is thus 24 min.
The ventilation system will extract the smoke from the ventilation shaft nearest
to the train. Hence, there will be a probability of 0.5 that the train is located
such that the evacuation, described above of the 674 passengers, will be in a
smoke-filled tunnel.
The estimated 24 minutes in the smoke-filled tunnel seems to be a high figure,
considering that the fire may develop in the full 15 MW fire within the order of
15 minutes (general assumption stated in paragraph 2.2.1 of Ref. /2/), of which
a few minutes may have passed before the train stops.
Hence, even though the 24 minutes are calculated using a very rough method, it
seems as if the evacuation facilities will have to be improved. This could be
done by increasing the internal diameter of the tunnel, such that the walkway
becomes wider, which would also allow an increase of the width of the emergency shelter.
Another possibility will be to design the tunnel such that the passengers can
also escape form the other side of the train and go to the walkway along the
other side of the tunnel. However, this will to some extent conflict with the location between the tracks of the stairs to the emergency shelters.
The distance between entrances to the emergency shelters could also be reduced, but this would lead to that there will be a continuous emergency shelter
under the tracks, and then the option described in the next section may be better.
It is noted that to our knowledge the concept of having escape to the room below the railway track has not yet been used in any railway tunnel. The concept
has been used in road tunnels, but using it in a railway tunnel may be more difficult due to the large number of passengers that can be onboard a train, and the
smaller dimensions of railway tunnels compared to road tunnels.
P:\57050Z\188 (Korea deep railway tunnel)\Report Evac and Vent\72156-2 Evacuation and ventilation.docx
25
It is noted that if the emergency exits and stations are also used for smoke extraction, then the maximum length of smoke-filled tunnel would be reduced to
1250 m / 2 = 625 m, but this would have adverse consequences for the ability
of the fire brigade to intervene, see below.
P:\57050Z\188 (Korea deep railway tunnel)\Report Evac and Vent\72156-2 Evacuation and ventilation.docx
26
7.1
The cross section of this option is the same as the basic option, with the exception that under the tracks, it is assumed that there is an emergency corridor instead of shelters.
The tunnel is equipped with ventilation as described below. The jet fans are
used as supplementary fans for the tunnel ventilation.
In an emergency situation the trains can be evacuated via the emergency walkway to the nearest hatch to the emergency corridor. The hatches for the emergency corridor are located between the railway tracks. Via the safety corridor
the passengers can walk to the nearest emergency evacuation shaft.
The emergency corridor below the railway tracks can resist the design fire. It is
equipped with a separate system for fresh air supply.
The location of big shafts with stairs and ventilation and small ventilation
shafts is the same as for the basic option, please see section 6.1.
The main features of this option are summarized in the Table 10-1.
P:\57050Z\188 (Korea deep railway tunnel)\Report Evac and Vent\72156-2 Evacuation and ventilation.docx
27
Jet fans
Walkway
Walkway
Ventilation of
emergency corridor
Utilities
Emergency
corridor
Figure 7-1
7.2
Tunnel ventilation
The tunnel ventilation for this option is almost identical to the ventilation for
the basic option with the exception that there are no shelters, but the corridor
under the tracks will be used as escape corridor.
The tunnel ventilation is divided in sections: from station to station. Only for
one typical section the tunnel ventilation system is described in the text and
shown in Figure 7-1.
At stations:
- Reversible ventilation plant for supply/extraction.
- Piston effect shafts.
At emergency shafts (2500 m from the station and 2500 m between shafts):
- Ventilation plant for air supply to the tunnel.
P:\57050Z\188 (Korea deep railway tunnel)\Report Evac and Vent\72156-2 Evacuation and ventilation.docx
28
In the tunnel:
- Jet fans to be used as booster fans for the tunnel ventilation in particular
cases.
2500
L
1250
2500
1250
1250
1250
Emergency
Exit
Smoke
exhaust
Emergency
Exit
Smoke
exhaust
Station
50 50
Emergency
hatches
Emergency
hatches
Jet Fan
Fresh air supply
Smoke exhaust
Smoke exhaust
Escape route
Figure 7-2
P:\57050Z\188 (Korea deep railway tunnel)\Report Evac and Vent\72156-2 Evacuation and ventilation.docx
29
During congested operation it will be necessary to supply fresh air to the tunnel
from the supply plants next to the location of the stopped train. The polluted air
can be extracted through the extraction shafts.
Emergency conditions (Fire in the tunnel)
In case the burning train is stopped at station platform, the smoke will be extracted by the ventilation plant at the station.
If the burning train stops between two stations the smoke will be extracted
through the smoke exhaust shaft next to the burning train.
Fresh air can be supplied from emergency shafts or stations. See Figure 7-2.
The ventilation plants for pressurization of escape corridor and staircases will
be started when a fire occurs.
Because there are two tracks, there may be trains trapped in front of the burning
train on the other track and behind it on the same track. Therefore longitudinal
ventilation can not be used during the evacuation.
As shown in Figure 7-2, the trapped trains on both side of the fire site can be
free of smoke. The fresh air supply from stations and emergency shafts create a
flow with a velocity vCritical. The jet fans can be used to maintain the velocity.
After the evacuation, the Fire Brigade can change to longitudinal ventilation, to
get smoke-free access to the fire site from the one side. The Ventilation plants
shall therefore have the necessary capacity to maintain an air flow with critical
velocity. During this operation, it may be necessary to use the jet fans.
7.3
P:\57050Z\188 (Korea deep railway tunnel)\Report Evac and Vent\72156-2 Evacuation and ventilation.docx
30
having passed the end of the train, will be maximum 100 m as opposed to the
maximum 500 m considered in section 6.3.1. This will take 2.6 minutes using
the model of NFPA 130, and the total time until the last passenger is within the
emergency corridor becomes 13 minutes as opposed to the 24 minutes in section 6.3.1.
This is still a long time considering that a very rough method has been used,
and depending on the results of a proper evacuation analysis it may be required
to increase the tunnel diameter in order to increase the width of the walkway.
As indicated in section 6.3.1 the width of the stairs leading down to the emergency corridor may be considered not to meet the requirements stated in Table
4-1.
As noted in section 6.3.1 the concept of having escape to the room below the
railway track has to our knowledge not yet been used in any railway tunnel.
The concept has been used in road tunnels, but using it in a railway tunnel may
be more difficult due to the large number of passengers that can be onboard a
train, and the smaller dimensions of railway tunnels compared to road tunnels.
P:\57050Z\188 (Korea deep railway tunnel)\Report Evac and Vent\72156-2 Evacuation and ventilation.docx
31
8.1
The cross section of this option is the same as the basic option with the exception that it is assumed that the only path of evacuation is via the emergency
walkways.
The tunnel is equipped with many small ventilation shafts, around 3 m diameter. These ventilation shafts with relatively small diameter are assumed to be
constructed using a shaft boring machine or raise boring.
As for the basic option and the option with emergency corridor, see section 6
and 7, it assumed that the distance between big shafts with stairs and ventilation
is 2500 m. The distance between small ventilation shafts is 500 m. This distance makes sure that the distance to a smoke-free area is the same as to cross
passages as required from common international standards, see Table 4-1.
In an emergency situation the trains can be evacuated via the emergency walkway to the nearest emergency exit shaft. The protection of the passengers during emergency evacuation relies on the use of intensive ventilation with advanced control.
The main features of this option are summarized in the Table 10-1.
P:\57050Z\188 (Korea deep railway tunnel)\Report Evac and Vent\72156-2 Evacuation and ventilation.docx
32
Jet fans
Walkway
Walkway
No specific
use
Figure 8-1
8.2
Tunnel ventilation
The tunnel ventilation for this option is almost identical with the ventilation for
the basic option with the exception that there is short distance between ventilation shafts (500 m in stead of 1250 m) and that smoke extraction will normally be from two exhaust shafts as opposed to one. With the short distance between smoke exhaust the extent of the smoke plume will be reduced.
The tunnel ventilation is divided in sections: from station to station. Only for
one typical section the tunnel ventilation system is described in the text and
shown in Figure 8-1.
At stations:
- Reversible ventilation plant for supply/extraction.
- Piston effect shafts.
P:\57050Z\188 (Korea deep railway tunnel)\Report Evac and Vent\72156-2 Evacuation and ventilation.docx
33
At emergency shafts (2500 m from the station and 2500 m between shafts):
- Ventilation plant for air supply to the tunnel.
- Ventilation plant for air supply/pressurization of the escape corridor.
- Ventilation plant for pressurization of the staircase.
At ventilation shafts (500 m from stations and shafts and 500 m between
ventilation shafts):
- Ventilation plant for extraction.
In the tunnel:
- Jet fans to be used as booster fans for the tunnel ventilation in particular
cases.
2500
500
2500
500
Emergency
Exit
Emergency
Exit
Smoke
exhaust
Station
Jet Fan
Fresh air supply
Smoke exhaust
Smoke exhaust
Escape route
Figure 8-2
P:\57050Z\188 (Korea deep railway tunnel)\Report Evac and Vent\72156-2 Evacuation and ventilation.docx
34
8.3
P:\57050Z\188 (Korea deep railway tunnel)\Report Evac and Vent\72156-2 Evacuation and ventilation.docx
35
The smoke will be extracted at the two ventilation shafts adjacent to the burning train. Hence, the passengers escaping from the train will walk in a smokefilled tunnel until they have passed the first ventilation shaft, and then the conditions on the walkway will be significantly improved, as the exhaust ventilation should be designed, such that very little smoke is spread to the other side
of the ventilation shaft.
The 2500 m distance between emergency exits is clearly not in accordance with
the requirements to such exits stated in Table 4-1. The 500 m distance between
the ventilation shafts is in accordance with the requirements for distances between cross passages from UIC and 2001/16/EC. However, the conditions on
the other side of the ventilation shaft can hardly be considered to be as safe as
in a cross passage, such that formally the requirements in the table cannot be
considered to be met.
Most of the smoke will be extracted by the shaft that is closest to the fire.
Hence, if the train is located such that the passengers will have to walk the
maximum distance of 500 m to the nearest ventilation shaft, then they will walk
in a tunnel that is nearly smoke-free. Hence, for comparison with the other options, the situation where the fire is located with 250 m to both ventilation
shafts, such that the passengers will be exposed to half of the smoke from the
fire, is considered.
A rough calculation, using NFPA 130 as described in section 4.4, of time for
the passengers to reach safety within the shelters gives the following results:
The time for the passengers to walk past the end of train on one walkway is
estimated at 10.3 min. as indicated in section 6.3.1.
The last passenger will have to walk 250 m - 103 m = 147 m from the end
of the train to reach the ventilation shaft in accordance with the assumption
on the location of the fire. (The 103 m is the distance from the fire to the
end of the train). The time to walk this distance will be 147 m / 38 m/min =
3.9 min.
The total time until the last passenger has walked past the ventilation shaft
is thus 14 min.
This is still a long time considering that a very rough method has been used,
and depending on the results of a proper evacuation analysis, it may be required
to increase the tunnel diameter in order to increase the width of the walkway.
Another possibility will be to design the tunnel such that the passengers can
also escape form the other side of the train and go to the walkway along the
other side of the tunnel. However, this will conflict with the location between
the tracks of the stairs to the emergency corridor.
P:\57050Z\188 (Korea deep railway tunnel)\Report Evac and Vent\72156-2 Evacuation and ventilation.docx
36
As opposed to the options considered in sections 6 and 7, this option does not
include the concept of escape to a room below the track. Here, the critical issue
is instead the design of the ventilation shafts, such that spread of smoke beyond
the shafts used for smoke extraction is prevented. The reliability of the smoke
extraction shall be very high as the safety of the escaping passengers relies on
this system.
P:\57050Z\188 (Korea deep railway tunnel)\Report Evac and Vent\72156-2 Evacuation and ventilation.docx
37
9.1
For this option it is assumed that there is a fire proof dividing wall between the
two railway tracks. Due to the wall it will be necessary to increase the diameter
of the tunnel by around 2 m. This means that the internal diameter will be
around 13 m.
The wall between the two railway tracks will divide the tunnel into two separate half rooms, which will be independent regarding ventilation.
The dividing wall has closely spaced emergency doors. Through these doors
the passengers can escape to the opposite tunnel, which will constitute a safe
area in case of fire in one half of the tunnel.
As the tunnel diameter is larger for this option, there will be more available
space below the railway tracks. This available space is so big, that it is possible
to have special emergency vehicles here, that can be used for fire brigade
access.
Because the opposite tunnel constitutes a safe space and because there is ample
space for fire brigade access in the space below the tracks, there are no shafts
between the railway stations.
The concept with a dividing wall corresponds to the concept for the Green
Heart Railway Tunnel in The Netherlands. Please see the illustration below.
The spacing of the emergency doors is considered to be 150 m, which is the
distance used for the Green Heart Tunnel. The width of the emergency walkway will at minimum be the 0.8 m used for the other options, but the tunnel
diameter described above should allow a walkway with a width of 1.5 m along
each side of the dividing wall as in the Green Heart Tunnel, Ref. /6/.
P:\57050Z\188 (Korea deep railway tunnel)\Report Evac and Vent\72156-2 Evacuation and ventilation.docx
38
Figure 9-1
The main features of this option are summarized in the Table 10-1.
A variant of this option will be to include shafts for emergency exit and access
as in the other options, if it is found that using the space below the tracks for
access of the fire brigade is considered not to be feasible.
Jet fans
Dividing
wall w.
emergency
doors
Walkway
Walkway
Space for fire brigade access.
Special vehicle
Ventilation of
fire brigade
access
Figure 9-2
P:\57050Z\188 (Korea deep railway tunnel)\Report Evac and Vent\72156-2 Evacuation and ventilation.docx
39
9.2
Tunnel ventilation
This option is very different from the other options as a dividing wall between
the two tracks is introduced.
With the tunnel divided into two tubes with a single track longitudinal ventilation can be used for environmental as well as for smoke ventilation. Therefore
the ventilation shafts (smoke extraction) can be omitted.
At stations:
- Reversible tunnel ventilation plant for supply/extraction.
- Ventilation plant for air supply/pressurization of the corridor
(for fire brigade approach and maintenance).
- Piston effect shafts.
In the tunnel:
- Jet fans with sufficient capacity to maintain an air velocity in each tunnel
tube vCritical.
P:\57050Z\188 (Korea deep railway tunnel)\Report Evac and Vent\72156-2 Evacuation and ventilation.docx
40
Smoke extraction
Station
Train stops
Jet Fan
Fresh air supply
Smoke exhaust
Escape route
E
Figure 9-3
Emergency door
P:\57050Z\188 (Korea deep railway tunnel)\Report Evac and Vent\72156-2 Evacuation and ventilation.docx
41
Burning train
Station
Track II
Station
Track I
Figure 9-4
As shown in Figure 9-3 trapped trains behind the burning train can be free of
smoke. The jet fans create a flow with a velocity vCritical of fresh air supplied
from stations and emergency shafts.
To avoid smoke ingress through the emergency doors during the evacuation it
will be possible to create a slightly higher pressure in the safe tunnel than in the
injured tube by operating the jet fans in a way so the smoke is sucked away in
front of the train and the fresh air is blown through the safe tunnel tube. The
principle is shown in Figure 9-4.
9.3
P:\57050Z\188 (Korea deep railway tunnel)\Report Evac and Vent\72156-2 Evacuation and ventilation.docx
42
A rough calculation, using NFPA 130 as described in section 4.4, of time for
the passengers to reach safety on the other side of the dividing wall gives the
following results:
The time for the passengers to walk past the end of train on a 0.8 m wide
walkway is estimated at 10.3 min. as indicated in section 6.3.1.
The last passenger will have to walk 150 m - 103 m = 47 m from the end
of the train to the door in the dividing wall. The time to walk this distance
will be 47 m / 38 m/min = 1.2 min.
The total time until the last passenger has passed the dividing wall is thus
12 min.
If the width of walkway is increased to 1.5 m then the time to walk past the end
of the train will be reduced to 5.5 minutes and the total time until the last passenger has passed the diving wall is reduced to 7 minutes.
It is noted that this scenario, where the fire is exactly at a door in the dividing
wall, is very unfortunate. With other locations of the fire the total time to reach
safety will be reduced.
The train in front of the burning train is driving past the next station.
The trains behind the burning train will be protected by the longitudinal
ventilation.
P:\57050Z\188 (Korea deep railway tunnel)\Report Evac and Vent\72156-2 Evacuation and ventilation.docx
43
brigade's use of the stairs will not seriously disturb the evacuation of the passengers.
The fire brigade will approach the fire in the train from the upstream side protected by the longitudinal ventilation.
It is noted that the concept of using the room below the railway track for transport of the fire brigade has to our knowledge not yet been used in any railway
tunnel. The concept has been used in road tunnels, but using it in a railway tunnel may be more difficult due to the smaller dimensions of railway tunnels
compared to road tunnels. From the size of the tunnel considered here there
should be sufficient space under the tracks, but whether there is sufficient space
to arrange appropriate access stairs for the fire brigade has not yet been established.
P:\57050Z\188 (Korea deep railway tunnel)\Report Evac and Vent\72156-2 Evacuation and ventilation.docx
44
10
Comparison
The main features of the options considered are indicated in Table 10-1.
In the basic option there is assumed to be smoke extraction to the nearest ventilation shaft, which will be within 1250 m of the burning train. This implies that
the location of the train shall be known.
With a maximum distance between entrances to the emergency shelters being
500 m, the roughly calculated evacuation time is estimated at maximum 24 minutes (reference is made to section 4.4 regarding the very rough assumptions
made). This seems to indicate that the evacuation facilities should be improved
in this option.
Considering the small width of the emergency shelter, it may be difficult to establish a design that will work in an emergency. E.g. the first passengers entering the shelter may stop immediately within the shelter, such that the following
passengers will not be able to enter the shelter.
The option "emergency corridor with frequent access" has the same ventilation
concept as the basic concept. As there are doors to the emergency corridor below the tracks every 50 m, the roughly calculated maximum evacuation time is
reduced to 13 minutes.
As the passengers entering the emergency corridor shall walk to the nearest
emergency exit maximum 1250 m away it is less likely that the first passengers
entering the corridor will block the access of following passengers than in the
basic option.
In both the basic option and the option "emergency corridor with frequent
access" the design of the entrances to the stairs need further consideration. It
may be difficult to find a suitable solution.
It is noted that to our knowledge the concept of having escape to the room below the railway track has not yet been used in any railway tunnel. The concept
has been used in road tunnels, but using it in a railway tunnel may be more difficult due to the large number of passengers that can be onboard a train, and the
smaller dimensions of railway tunnels compared to road tunnels.
P:\57050Z\188 (Korea deep railway tunnel)\Report Evac and Vent\72156-2 Evacuation and ventilation.docx
45
In both of the above options other trains will be protected against smoke from
the fire except for maximum 1250 m of the tunnel.
The fire brigade will have to proceed at maximum 1250 m in a tunnel to reach
the fire in both the above options. The ventilation system should ensure that the
tunnel here is smoke-free.
Tunnel option
1
Basic option
2
Option:
Emergency corridor with frequent access
3
Option:
Short distance
between ventilation shafts
4
Option:
Dividing wall
One tunnel,
two tracks
Internal D 11.06m
One tunnel,
two tracks
Internal D 11.06m
One tunnel,
two tracks
Internal D 11.06m
One tunnel,
two tracks separated
by wall
Internal D ~ 13 m
V every 1250 m
E every 2500 m
A every 2500 m
V every 1250 m
E every 2500 m
A every 2500 m
V every 500 m
E every 2500 m
A every 2500 m
None
Evacuation safety is
controlled with many
vent shafts
Ventilation
concept
Jet fans
Jet fans
Jet fans
Jet fans
No smoke exhaust
between stations
Overall
Concept
Shafts
V: Ventilation
E: Evacuation
A: Fire brigade
access
Emergency
evacuation
Table 10-1
In the option "short distance between ventilations shafts the passengers shall
walk away from the fire to the nearest evacuation shaft maximum 2500 m
away. As there are 500 m between smoke exhaust shafts and the smoke is ex-
P:\57050Z\188 (Korea deep railway tunnel)\Report Evac and Vent\72156-2 Evacuation and ventilation.docx
46
tracted at the exhaust shafts at both sides of the train, the passengers will only
have to walk a limited distance in smoke. The rough calculation of maximum
time for the passengers to reach a smoke-free part of the tunnel results in 14
minutes, i.e. the same order of magnitude as for the option "emergency corridor
with frequent access".
The concept is however depending on a very accurate knowledge of the location of the tunnel fire in order for the system to function as intended. The weak
point is this advanced detection system and the control systems which opens up
for human errors in programming and operation of the system.
It is also noted that this option will formally not meet international requirements, as walking past a ventilation shaft can hardly be considered to provide
the same safety as walking into a cross passage.
Furthermore the access of the fire brigade to the burning train is more difficult
than in the above two options as there will be smoke on both sides of the train.
The operation of the ventilation system can be changed to provide access in a
smoke-free tunnel, but such change cannot be done until it is certain that it will
not adversely affect escaping passengers in the tunnel.
The advantage of this option is that the passengers need not use the space below the tracks requiring complicated design of access stairs etc.
All of the above options could be improved by providing facilities allowing the
passengers also to leave the train on the side facing the other track and go to the
opposite walkway. However, in the first two options this will conflict with the
access stairs located between the tracks.
The option with dividing wall allows the passengers to escape to the opposite
part of the tunnel. This solution results in the shortest time for passenger evacuation roughly estimated at maximum 12 or 7 minutes depending on whether the
emergency walkway is 0.8 m wide as in the other options or 1.5 m wide, which
it should be possible to include in this option due to the larger tunnel diameter.
We consider this solution for the evacuation to be more reliable than the basic
option and the option with emergency corridor, which require careful consideration of the detailed solution for access hatches for the shelter or corridor.
Regarding fire brigade access the option with dividing wall will, due to the
larger tunnel diameter, allow a separate space under the tracks which can be
used for access with special vehicles. The design of the fire brigades access
from this space to the tracks will have to be further studied in order to finally
establish whether this solution is feasible. The arrangement should be such that
the fire brigade's use of the stairs will not seriously disturb the evacuation of the
passengers.
Regarding operation of the ventilation, the dividing of the tunnel allows a more
robust solution which is easy to control, as there is only one option for the direction of the smoke ventilation.
P:\57050Z\188 (Korea deep railway tunnel)\Report Evac and Vent\72156-2 Evacuation and ventilation.docx
47
The main disadvantage of this option is the additional costs due to the increased
diameter. However, this may be more or less balanced by the savings as no
shafts are needed.
The option with a diving wall is considered to be the best from a safety point of
view. This option is therefore recommend if there are no or only insignificant
additional costs involved compared to the other options. Even if the additional
costs are larger, this option should be preferred, as long as the additional costs
are not disproportionate with the value of the reduction in risk, cf. the description of the ALARP principle in section 4.5.
P:\57050Z\188 (Korea deep railway tunnel)\Report Evac and Vent\72156-2 Evacuation and ventilation.docx
48
11
References
/1/ NFPA 130. Standard for Fixed Guideway Transit and Passenger Rail Systems. 2010 Edition.
/2/ Directive 2001/16/EC - Interoperability of the trans-European conventional
rail system. Aspect: 'Safety in railway tunnels'.
Published in the Official Journal of European Union 7.3.2008 under the
heading "Commission decision of 20 December 2007 concerning the technical specification of interoperability relating to 'safety in railway tunnels'
in the trans-European conventional and high-speed rail system.
(2008/163/EC)"
/3/ International Union of Railways: UIC code 779-9. Safety in railway tunnels. 1st edition, August 2003.
/4/ COWI: Metropolitan Express Railway. Report on records of tunnel fire
accidents. Doc. No. 72156-1, 2009-11-20.
/5/ Health & Safety Executive, UK: The tolerability of risk from nuclear power stations. 1988, revised 1992. ISBN 0 11 886368 1.
/6/ Homepage of HSL Zuid:
http://www.hslzuid.nl/hsl/uk/lijn/Safety/Safety_in_tunnels/Safety_of_Groe
ne_Hart_tunnel/index.jsp
P:\57050Z\188 (Korea deep railway tunnel)\Report Evac and Vent\72156-2 Evacuation and ventilation.docx