Documente Academic
Documente Profesional
Documente Cultură
Abstract
The paper discusses the operation and control algorithms of shunt and series active filters. Performance of each of these filters is studied
separately when it is connected to protect sensitive loads in a power distribution system. It is assumed that the distribution system is polluted
due to the presence of the loads that may be unbalanced and draw interharmonic currents from the feeder. Separate algorithms have been
proposed for the shunt and the series active filters. These are operated such that the voltage waveform at the sensitive load bus terminal is
a clean balanced sinusoid. The proposed algorithms are verified through the computer simulation studies using PSCAD/EMTDC software
package.
2004 Elsevier B.V. All rights reserved.
Keywords: Distribution system; Interharmonics; Pole shift control; Sensitive load; Series active filter; Shunt active filter
1. Introduction
Harmonic interferences in a power distribution system are
caused by harmonic producing power electronic loads such as
diode or thyristor converters, cycloconverters, arc furnace etc.
An arc furnace is an unbalanced, nonlinear and time variant
load that causes unbalance and voltage flicker while drawing
harmonic, interharmonic and subharmonic currents. The harmonic currents are components that have frequencies which
are integer multiples of fundamental frequency. The components with frequencies which are greater than and not an integer multiple of the fundamental frequency are interharmonic.
The term subharmonic component does not have any official
definition but is similar to interharmonic with frequency less
than the fundamental frequency [1]. Passive filters consisting
of a bank of LC filters and/or a high pass filter have been
broadly used to suppress harmonics because of a low initial
cost and high efficiency. However, the passive filters oper Corresponding author.
Tel.: +91 512 2597179/2597801(O)/2598799(R); fax: +91 512 2590063.
E-mail address: aghosh@iitk.ac.in (A. Ghosh).
0378-7796/$ see front matter 2004 Elsevier B.V. All rights reserved.
doi:10.1016/j.epsr.2004.08.003
188
189
(2)
y = Cx
0
A=
1
Lf
1
Cf
,
Rf
Lf
C = [1 0]
and
(1)
B = Vdc
Lf
zT = [ uc
C1f
0
B(z1 )
uc (k)
A(z1 )
(3)
S(z1 )
{yref (k) y(k)}
R(z1 )
(4)
B(z1 )S(z1 )
yref (k)
A(z1 )R(z1 ) + B(z1 )S(z1 )
(5)
(6)
Here, T(zl ) is the characteristic polynomial of the closedloop system. The closer is to one, the smaller will be the
control action. The controller parameters, i.e., the coefficients
of S and R are obtained by solving Eq. (6) and are substituted
in (4). The Eq. (6) is known as Aryabhatta/Bezout identity.
Once uc (k) is obtained, the control input u is obtained as:
+1 for uc > h
u=
(7)
1 for uc h
where 2h is a hysteresis band. This switching law produces
a variable switching frequency control action.
ish ]
190
Table 1
The system parameters of the shunt active filter structure shown in Fig. 3
System quantity
(8)
Parameters
50
2000
1
0.01
0.1
50
17
0.025
The proposed shunt active filter structure and control is tested through extensive simulation studies using
PSCAD/EMTDC (version 3) for the distribution system
given in Fig. 1. Two different tests are reported below.
It is desired to hold the magnitude of the B-2 bus voltage |Vtmag | to be 11 kV (LL, rms), i.e., equal to the source
voltage. The simulation results, when no shunt active filter is
connected at the bus B-2, are shown in Figs. 6 and 7. Note
that the waveforms for the phases a, b and c shown here and
in the following results are depicted by solid, dashed and dotted lines, respectively. It is assumed that the source voltages
are balanced with a peak value of 9 kV (11 kV, LL, rms).
The instantaneous three-phase B-2 bus voltages and L-1 load
currents are shown in Fig. 6. It can be seen that due to the presence of the nonlinear loads L-1 and L-2, the waveforms are
unbalanced and distorted with interharmonic components.
The currents drawn by the other loads are shown in Fig. 7.
In Fig. 7(a), the three-phase current waveforms drawn by the
load L-2 (il2 ) contain unbalance and interharmonic frequency
components as given in Appendix A (Table 1). It can be seen
from Fig. 7(b) that the currents drawn by the sensitive load
L-3 (il ) are also distorted due to the distorted B-2 voltages
shown in Fig. 6(a).
Now the shunt active filter is connected at bus B-2 as
shown in Fig. 2. The parameters of the shunt active filter,
Fig. 7. The three-phase currents flowing in the loads L-2 and L-3.
191
In this section, the operation and control of the series active filter is discussed. The main objective of the series active
filter is to keep the voltage waveforms across the sensitive
load bus terminals perfectly balanced against all kinds of disturbances occurring in the distribution system. An algorithm
is discussed to generate the reference voltages, which the series active filter will inject into the distribution system. A pole
shift controller has been designed such that these reference
voltages are tracked accurately.
4.1. Series active lter structure
The shunt active filter of Fig. 2 is now replaced by a series
active filter as shown in Fig. 10. The series active filter is
connected between the bus B-2 terminals and the sensitive
load (L-3) bus terminals as shown in Fig. 10. Like shunt
active filter, a filter capacitor Cf is connected in shunt with
the bus B-2 to provide a low impedance path for the harmonic
components flowing in the line currents. The voltage across
the filter capacitor will be vt as indicated in the Fig. 10. The
configuration of the series active filter is shown in Fig. 11.
It is realized by three H-bridge inverters supplied through a
common dc energy storage capacitor (Cdc ). The outputs of
the inverters are connected to three single-phase transformers
that are connected in series with the three phases at the bus B2. The injected voltages in the phases a, b and c are denoted
as vda ,vdb and vdc , respectively. An ac filter capacitor Cd
is also connected across each of the secondary windings of
the transformers to bypass the harmonics generated by the
inverter switching [12].
192
The series active filter injects voltage, vd in the bus B-2 and
cancels the effect of interharmonics in the B-2 bus voltages
vt . The KVL at bus B-2 is written as:
vt + vd = vl
(9)
(10)
(11)
where, ptav is the average power entering the B-2 bus terminals, plav is the average power supplied to the sensitive load
and the power loss in the series active filter is ploss . Since
the load voltage vl is strictly positive sequence, the average
power to the load is also positive sequence. This gives:
ptav ploss = plav = |Vl ||Il 1 |cos( )
(12)
V d0
0
V t0
(14)
V d1 = |Vl | V t1
V d2
0
V t2
Here the zero, positive and negative phasors are denoted by
the subscripts 0, 1 and 2, respectively. Also note that in (14)
and in the following discussion, the variables in upper case
bold letters indicate the fundamental phasor quantities of the
variables and those in lower case letters indicate the instantaneous values of the corresponding variables. The reference
phasor voltages (V da , V db V dc ) are then obtained by the inverse symmetrical component transformation. The instantaneous reference phase voltage (vd ) then can be obtained from
the phasor voltages. The entire operation is synchronized with
an arbitrary phase reference.
4.3. Fundamental phasor sequence components
calculation
As the loads L-1 and L-2 connected in the distribution
system (Fig. 1) are unbalanced and are drawing interharmonic
current waveforms, the B-2 bus voltages (vt ) and the currents
(il ) drawn by the load L-3 (Figs. 6 and 7) are also distorted
with unbalance and interharmon-ics. The rms fundamental
phasor sequence components of the load currents (or B-2
bus voltages) are extracted from the instantaneous sampled
values of the il (or vt ). These are obtained through a two-stage
integration and filtering process.
In the first stage, the following integral has been evaluated
[12,13]:
t+T 1 1 1
F a0
xa
2
j(t/2)
2
dt
F a1 =
1 a a xb e
T 3 t
2
F a2
xc
1 a
a
(15)
193
Table 2
Series active filter parameters for the configuration in Fig. 11
System quantity
1
0
0
C1d
Cd
,
,
A= 1
B = Vdc
d
R
L
d
Ld
Ld
C = [1
0 ] and
zT = [ uc
il ]
(16)
Parameters
50
2000
1
0.01
0.1
30
30
and
KI = 0.75
Fig. 13. The control block diagram of the series active filter.
194
and (b) that the load L-2 draws about 1.67 MW while the
load L-3 draws about 1.07 MW power from the feeder in the
steady state. The total power required by the bus B-2 is around
2.9 MW. However, the power drawn by the shunt active filter
is about 0.16 MW, which is just about 5% of the total power
drawn by the bus B-2. This is evident from the results shown
in Figs. 19(a) and (b).
195
It has been discussed in Section 4.2 that the power loss occurring in the series active filter circuit is supplied by the ac
system, i.e., from the bus B-2. This is accomplished through
a PI controller given by (17). The performance of the PI controller is shown in Fig. 20, which takes about six cycles to
reach the steady state. It can be seen from Fig. 20(a) that the
voltage across the dc capacitor reaches to its reference set
value of 5 kV in the steady state. The PI controller output,
i.e., the power loss in the inverter circuit ploss is shown in
Fig. 20(b), which is about 0.04 MW. The terminal power and
the power drawn by the load L-3 are shown in Fig. 21. It
can be seen from Figs. 21(a) and (b) that the terminal power
is about 1.11 MW and the power drawn by the load L-3 is
Fig. 19. Total power drawn by the bus B-2 and the power absorbed by the
shunt active filter.
Fig. 21. Power drawn at the terminals and by the load L-3.
196
Acknowledgements
The paper illustrates the operation of series and shunt active filter in a power distribution system. The purpose of connecting the active filters is to protect a load from the disturbances occurring in the system. The load is assumed to
be a sensitive load, which cannot tolerate any interruption at
all. The disturbances are due to the presence of other loads,
which are unbalanced and are drawing interharmonic current
waveform as well. The magnitude of the sensitive load bus
voltage is pre-specified.
It has been clarified that the shunt active filter eliminates
the voltage unbalance and also compensate for all kinds of
harmonics present in the B-2 bus voltage. The series active
filter is connected between B-2 bus terminals and the load
bus terminals. It has been demonstrated that the series active
filter is able to eliminate the integer and noninteger harmonics present in the sensitive load voltages and currents. The
structures have been discussed in which both the shunt and
the series active filters are realized by three H-bridge inverters connected through a common dc capacitor. The multiple
shunt active and series active filters can be connected in a big
radial or ring main distribution system to improve the power
quality at different load buses.
The authors would like to thank the Central Power Research Institute (CPRI), Bangalore, India for providing the
financial support for this work under the research project
Development of active power line conditioners for power
distribution systems.
Table A.1
System parameters for the distribution system shown in Fig. 1
System quantity
Parameters
100
11
0.3 + j2.42
0.3 + j2.42
Appendix A
See Table A.1.
References
[1] IEEE Interharmonic Task Force & CIGRE 36.05/CIRED 2 CC02
Voltage Quality Working Group, Interharmonics in power systems,
Draft, 1997.
[2] L. Gyugyi, E.C. Strycula, Active ac power filters, in: Presented at
IEEE/IAS Annual Meeting, #####, 1976, p. 529.
[3] H. Akagi, New trends in active filters for power conditioning, IEEE
Trans. Ind. Appl. 32 (6) (1996) 13121322.
[4] H. Fujita, H. Akagi, The unified power quality conditioner: the integration of series- and shunt-active filters, IEEE Trans. Power Electron. 13 (2) (1998) 315322.
[5] R. El Shatshat, M. Kazerani, M.M.A. Salama, Power quality improvement in 3-phase 3-wire distribution systems using modular
active power filter, Electric Power Syst. Res. 61 (3) (2002) 185
194.
[6] B. Singh, A. Al-Haddad, Chandra, A review of active filters for
power quality improvement, IEEE Trans. Ind. Electron. 46 (5) (1999)
960971.
[7] A. Ghosh, G. Ledwich, Load compensating DSTATCOM in weak
ac systems, IEEE Trans. Power Deliv. 18 (4) (2003) 1302
1309.
[8] A. Ghosh, A. Joshi, A new approach to load balancing and power
factor correction in power distribution system, IEEE Trans. Power
Deliv. 15 (1) (2000) 417422.
[9] A. Ghosh, G. Ledwich, O.P. Malik, G.S. Hope, Power System Stabilizer based on Adaptive Control Techniques, IEEE Trans. Power
Appl. Syst. PAS-103 (8) (1984) 19831989.
[10] A. Ghosh, A.K. Jindal, A. Joshi, Inverter control using output feedback for power compensating devices, in: IEEE TENCON 2003 Conference on Convergent Technologies for Asia-Pacific Region, vol. 1
(1417), 2003, pp. 4852.
[11] M.K. Mishra, A. Ghosh, A. Joshi, Operation of a DSTATCOM
in voltage control mode, IEEE Trans. Power Deliv. 18 (1) (2003)
258264.
[12] A. Ghosh, A.K. Jindal, A. Joshi, Design of a capacitor-supported
dynamic voltage restorer (DVR) for unbalanced and distorted loads,
IEEE Trans. Power Deliv. 19 (1) (2004) 405413.
[13] A. Ghosh, G. Ledwich, Power Quality Enhancement using Custom
Power Devices, Kluwer, Norwell, MA, 2002.
[14] A. Ghosh, A.K. Jindal, A. Joshi, Operation and control of a DSTATCOM in the presence of Non-integer harmonics, in: IEEE TENCON
2003 Conference on Convergent Technologies for Asia-Pacific Region, vol. 1 (1417), 2003, pp. 4347.