Sunteți pe pagina 1din 12

W7100G

Discharge Water
Temperature Control
PRODUCT DATA

FEATURES
• Up to six stages of cooling provided.
• Expandable system up to 10 cooling stages using a
W7101.
• Advanced proportional plus integral microprocessor
control algorithm minimizes droop.
• Soft start to minimize compressor cycling during
system start up.
• Adjustable minimum on/off timing and time delay
between stages of either 30 or 60 seconds.
• Adjustable setpoint from 10 to 110°F (-12 to 43°C).
• Adjustable reset differential from 5 to 20°F (3 to 11K).
• Adjustable control band from 0 to 10°F (0 to 6K).
• Reset signal from either an outdoor air or space
sensor.
• C7170 sensor can be used for sensing water
temperature.
• LED show which stages of cooling are energized.
APPLICATION
The microprocessor-based W7100G Discharge Water
Temperature Control maintains an average discharge
water temperature for reciprocating chiller applications, by
staging on and off compressors or unloaders as required.
The W7100 can provide up to 10 stages of cooling using a
W7101 Satellite Sequencer.

Contents
Application ........................................................................ 1
Features ........................................................................... 1
Specifications ................................................................... 2
Ordering Information ........................................................ 2
Installation ........................................................................ 3
Operation .......................................................................... 6
Settings and Adjustments ................................................. 8
System Checkout ............................................................. 9
Troubleshooting ................................................................ 10

® U.S. Registered Trademark


Copyright © 2001 Honeywell • All Rights Reserved 63-4046—1
W7100G DISCHARGE WATER TEMPERATURE CONTROL

SPECIFICATIONS
W7100G Model Features: Humidity Rating: 5 to 90 percent RH noncondensing.
• 6 stage cooling, controls reciprocating chillers.
• W7101 satellite expansion to 10 cooling stages. Mounting: Four mounting holes in base. Use No. 6 screws
• Adjustable setpoint. (not provided).

Dimensions: See Fig. 1. Approvals:


Underwriter’s Laboratories Inc. Component Recognized.
Electrical Ratings:
Input Voltage and Frequency (terminals TR-TR): Additional System Components:
At 60 Hz: 20 to 30 Vac. C7170A1010 Discharge Water Sensor: senses discharge
At 50 Hz: 20 to 26.4 Vac. water temperature, provides input to W7100G sensor
Power Consumption: terminals T and T1.
Device: 12 VA at 24 Vac and 50 to 60 Hz. Transformer (required): Provides 24 Vac power for all
On/Off Stages (Cool 1 through 6): See Table 1. components of the W7100G control system.
(Size transformer to match system load.)
Table 1. Power Consumption On/Off Stages (Cool 1-6).
Accessories:
Contact Voltage (Vac) Inrush (VA) Running (VA) T7047C1025 Remote Temperature Sensor: Discharge water
N.O. 24 240 60 temperature reset from controlled space.
N.C. 24 75 30 S96381037 Reset Setpoint Potentiometer: Use one or more
T7047C1025 with S963B1037.
N.O. 120/240 750 75 C7031G1016 Outdoor Air Sensor: Reset of discharge water
N.O. 120/240 240 40 from outdoor air temperature.
C7170A1010 Discharge Water Temperature Sensor: Senses
Switching: Spdt relays. discharge water temperature for input to W7100G.
W7101A1003 Satellite Sequencer: Adds up to 4 ON/OFF
Wiring Terminals: 1/4 in. quick-connect. stages of cooling to W7100 switching capability.
121371A Copper Immersion Well: Required for C7170A
Sensor Input Signal (See Fig. 2): Immersion Sensor.
Positive temperature coefficient: 4.8 ohms/°F (2.6 ohms/°C). 121371E Stainless Steel Immersion Well Required for
Resistance: 3484 ohms at 77°F (25°C). C7170A Immersion Sensor.
107406 Heat Conduction Compound: Required for minimum
Number of Stages Input: thermal lag.
Resistor value (across terminals 7 and 6) to determine num- AT72D1683 System Transformer: 40 VA, 120 Vac.
ber of ON/OFF stages. (See Table 2). AT87A1106 System Transformer: 50 VA, 120/208/240 Vac.
AT88A1005 System Transformer: 75 VA, 120 Vac.
Temperature Ratings: AT88A1021 System Transformer: 75 VA, 208/240 Vac.
Ambient: -40°F to +150°F (-40°C to +66°C). 4074EDJ Resistor Kit and Test Plug: Used in controller
Shipping: -30°F to +150°F (-34°C to +66°C). checkout.
4074EFV Resistor Kit for W7100G System Configuration:
Used to select number of stages controlled.

ORDERING INFORMATION
When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the
TRADELINE® Catalog or price sheets for complete ordering number.

If you have additional questions, need further information, or would like to comment on our products or services, please write or
phone:
1. Your local Home and Building Control Sales Office (check white pages of your phone directory).
2. Home and Building Control Customer Relations
Honeywell, 1885 Douglas Drive North
Minneapolis, Minnesota 55422-4386
In Canada—Honeywell Limited/Honeywell Limitée, 35 Dynamic Drive, Scarborough, Ontario M1V 4Z9.
International Sales and Service Offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France,
Germany, Japan, Mexico, Netherlands, Spain, Taiwan, United Kingdom, U.S.A.

63-4046—1 2
W7100G DISCHARGE WATER TEMPERATURE CONTROL

3/16 DIAMETER (5) 4 HOLES


INSTALLATION
When Installing this Product...
1. Read these instructions carefully. Failure to follow
them could damage the product or cause a hazardous
condition.
7-13/16 2. Check the ratings given in the instructions and on the
(198) product to make sure the product is suitable for your
application.
3. Installer must be a trained, experienced service
8-5/8 technician.
(219) 4. After installation is complete, check out product
operation as provided in these instructions.

WARNING: This equipment generates, uses, and can radiate


radio frequency energy, and if not installed and used in
accordance with the Instructions Manual, may cause
interference with radio communication. It has been tested
and found to comply with the limits for a Class A computing
device pursuant to Subpart J of Part 15 of FCC Rules, which
are designed to provide reasonable protection against such
interference when operated in a commercial environment.
Operation of this equipment in a residential area is likely to
5-3/4 (146) ALLOW 2 in. cause interference, in which case, users at their own expense
6-1/2 (165)
CLEARANCE
FOR ACCESS
will be required to take whatever measures may be required to
TO TEST PLUG correct the interference. Any unauthorized modification of this
equipment may result in the revocation of the owner's
authority to continue its operation.

3
(76)
CAUTION
Electrical Shock or Equipment Damage Hazard.
Can shock individuals or short equipment
circuitry.
13/16
(21) Disconnect power supply before installation.
TEST PLUG SOCKET M17910

Fig. 1. W7100 Discharge Air or Water Controller CAUTION


mounting dimensions in in. (mm). Equipment Damage Hazard.
Compressor stage ON/OFF times less than four
minutes can damage the compressor.
RESISTANCE Add external time delay relay(s) to W7100G output
(OHMS) stages to turn compressors on and off (See Fig. 3).
4200
IMPORTANT
4000 All wiring must agree with applicable codes,
ordinances and regulations.
3800

Location and Mounting


3600
Choose a location for the W7100G controller that is not
3484 ± 6.5 OHMS
exposed to the weather and where controls, connections
3400
AT 77°F [25°C] and the diagnostic analyzer socket are accessible.
(4.8 OHMS/°F)

3200 Mount the controller with four No. 8 screws through the
mounting holes in the base. See Fig. 1.
F
20 40 60 80 100 120 140 160 180 200 220 Mount the C7170A Sensor in the discharge water line using
C the selected Immersion Well and heat-conductive compound.
-7 0 10 20 30 40 50 60 70 80 90 100
TEMPERATURE (DEGREES) M3948 Mount auxiliary control system components, such as remote
potentiometers, reset sensors. etc., according to instructions
Fig. 2. Variation of C7170 Sensor resistance packed with the individual units.
as compared to temperature.

3 63-4046—1
W7100G DISCHARGE WATER TEMPERATURE CONTROL

A resistor is initially installed by the factory (600ohm) on


POWER SUPPLY terminals 7 and 8 (see Table 2). This corresponds to the value
W7100G
CUTOUT
COOL 6
1 for controlling a 6-stage cooling system. If the system being
B
C installed has more or fewer stages of cooling, this resistor
A UNLOADER must be changed to the value shown in Table 2. The new
SETPOINT F COOL 5
B
value represents the actual number of cooling stages
60 10 C operating under the control of the W7100G. This includes
A
20
UNLOADER any stages on a W7101A sequencer connected to the
50 COOL 4
B TDR-1 W7100G control.
40 30
C TIME
RESET F A DELAY

20 5
COOL 3 COMPRESSOR Connecting Additional Stages
B
C TDR-1 Control of up to 4 additional stages of ON/OFF cooling can
15 10
A UNLOADER be added by using a W7101A Satellite Sequencer to the
COOL 2
CONTROL BAND
B 2 W7100G system as shown in Fig. 4.
C
F
A UNLOADER
10 0
COOL 1
The fixed resistor value across the W7100G terminals 7 and 8
8 2
B
C
TDR-2 (Table 2) must agree with the total number of cooling stages
6 4 A
TIME
DELAY
controlled by the W7100G and W7101A satellite. See W7101
COMPRESSOR
specification sheet, Form 63-2119, for additional details.
TDR-2
Table 2. Input Resistance for Number
1 POWER SUPPLY. PROVIDE DISCONNECT MEANS
AND OVERLOAD PROTECTION AS REQUIRED. of Controlled Stages.
2 TIMER MUST BE MINIMUM OFF TYPE TIMER. Resistance
4 MINUTES MINIMUM ON AND OFF IS RECOMMENDED. M17916
±1% Across
Terminals 4074EFV Bag
Fig. 3. Wiring W7100G using minimum on and minimum Assembly Wire
off timer(s) on compressor stages. Total Number of 7 and 8a
Cooling Stages (Ohms) Colorsb
1 (W7100 only) 100 Blue
Wiring 2 (W7100 only) 200 Red
W7100G wiring and hookup diagram is shown in Fig. 4.
3 (W7100 only) 300 Yellow
4 (W7100 only) 400 Brown
CAUTION 5 (W7100 only) 500 Green
Erratic System Operation Hazard. 6 (W7100 only) 600 Shipped with Control
Failure to follow proper wiring practices can
introduce disruptive electrical interference (noise). 7 (W7100,W7101A) 700 Orange
Keep wiring at least one foot away from large inductive 8 (W7100,W7101A) 800 White
loads such as motors line starters, lighting ballasts,
9 (W7100,W7101A) 900 Violet
and large power distribution panels.
Shielded cable is required in installations where these 10 (W7100,W7101A) 1000 Black
guidelines cannot be met. a Use
Ground shield only to grounded controller case. 1/8W resistors.
b 4074EFV
Bag Assembly available separately.

Changing Number of Controlled Stages


A fixed resistor is installed across the number of stages input
(terminals 7 and 8). The resistor value tells the W7100G how
many stages of cooling are to be controlled. This affects the
control behavior and determines how many stages the
W7100G will turn on and off.

63-4046—1 4
W7100G DISCHARGE WATER TEMPERATURE CONTROL

L1
(HOT)
1 L2
TRANSFORMER 2 W7100A DISCHARGE AIR CONTROLLER 1

COOL 6
GND B
TR 24VAC C
TR A COOL 6
COOL 5
SETPOINT F B

90 40
C

85
45
A COOL 5
10 80
60
COOL 4
10 FAST 55

NUMBER OF
75
B
S963B1037 REMOTE 9 RESPONSE 70
65
60
C
POTENTIOMETER STAGES RESISTOR 9
NO. STAGES
RESET F A COOL 4
3 8
COOL

7 HEAT COOL 3
6 RESET 20
20 5
5
B
31 13 C
T
4 T1
SENSOR
15
11
10
A COOL 3
15
10
COOL 2
P2 REMOTE B
T7047C1025 SPACE RESET P1 SETPOINT CONTROL BAND
C
SENSOR OR C7013G1016
OUTDOOR RESET SENSOR C7100 5
16 2 A COOL 2
DISCHARGE 4 14 4 COOL 1
SENSOR 3 SATELLITE B
2 12 6 C
10 8
1 A COOL 1
5 RW
0 TO 500 OHM 7
REMOTE SETPOINT
POTENTIOMETER
8
W7101A SATELLITE SEQUENCER
1 POWER SUPPLY. PROVIDE DISCONNECT MEANS
AND OVERLOAD PROTECTION AS REQUIRED. COOL 1
GND B 8
2 USE SAME TRANSFORMER FOR SATELLITE AS FOR W7100. TR 24VAC C
TR A COOL 7
3 USE ONLY WITH SPACE RESET SENSOR. CONNECT IN COOL 2
SERIES AS SHOWN. B
C
4 WHEN RESET NOT USED, JUMPER TERMINALS 6 AND 7 A
COOL 8
COOL 3
ON W7100. HEAT 4
B
5 WHEN REMOTE SETPOINT NOT USED, JUMPER TERMINALS C

P AND P1. WHEN USED, TURN SETPOINT KNOB ON W7100 6 A COOL 9


COOL 4
TO MINIMUM POSITION. 7 FUNCTION HEAT
3
6 SELECT B
6 TO USE COOL 3 AND 4, REMOVE JUMPER FROM TERMINALS C

6 AND 7 ON THE W7101A SEQUENCER. A COOL 10


HEAT 2
7 B
GROUND CASE OF REMOTE SETPOINT POTENTIOMETER C 6
TO PREVENT PROBLEMS DUE TO STATIC ELECTRICITY. A
5
8 4 HEAT 1
USE SATELLITE ONLY IF ADDITIONAL STAGING IS REQUIRED. 3 CONTROL B
C
9 2
INSTALL CORRECT VALUE FOR NUMBER OF STAGES CONTROLLED. 1 A

10
FAST RESPONSE INPUT REFERS TO THE MINIMUM ON TIME,
MINIMUM OFF TIME AND MINIMUM TIME DELAY BETWEEN STAGES. M17911
LEAVE OPEN FOR 60 SEC. TIMINGS, JUMPER FOR 30 SEC TIMINGS.

Fig. 4. Connections for W7100G 10-stage cooling, with W7101 Satellite Sequencer,
discharge sensor, reset sensor(s) and remote setpoint potentiometer.

5 63-4046—1
W7100G DISCHARGE WATER TEMPERATURE CONTROL

OPERATION
Chiller System Description (Fig. 5) 5. At point C, the discharge water temperature has fallen
below the lower control band.
Chiller systems are used to provide cold water for many 6. If the minimum ON time has elapsed for that stage, the
types of end uses. The cold water may be piped to many air highest stage that is on shuts off.
handling units located throughout a building. These units then 7. This sequence continues until the cooling demand
provide cooling and ventilation for individual zones throughout increases (point D) at which time stages sequence ON
that building. Chillers are also used to supply cold fluid for a in the same manner as before.
variety of process applications. In either case, precise 8. As a rule, any time the discharge water temperature:
discharge water temperature control is desired. a. is above the upper control band limit, a stage turns
on.
b. falls below the lower control band limit, a stage turns
W7100G off.
DISCHARGE
WATER CONTROL

PUMP
Reset of Discharge Water Temperature
CHILLER
BARREL Industrial Applications
COMPRESSOR(S) Reset of discharge water temperature is not recommended in
a W7100G industrial application, because loads on industrial
RETURN
WATER
REMOTE SUPPLY WATER applications typically require a constant temperature fluid for
SETPOINT TO SYSTEM LOAD M17921
cooling. Check industrial process manufacturers for specific
details.
Fig. 5. Chiller system.

Environmental Applications
Discharge Water Temperature In order to save additional energy under lighter loading
Control Operation conditions, it may be desirable to change or reset the
discharge water temperature setpoint based on either space
The W7100G uses an integrating control band concept to
or outside air temperatures. Reset has proved itself on hot
provide close, stable temperature control in discharge water
water boilers as an energy saving opportunity. These same
chiller systems. The control band concept matches required
energy saving techniques can also be applied to chillers, to
operating capacity to chiller load, while the integral action
more evenly match system capacity with system load.
minimizes the offset from the control setpoint which normally
occurs in proportional-only type controllers.
Reset from Space Temperature
The control band setting is centered on the discharge waters
A chiller that is being used to chill water for single or multiple
setpoint (see Fig. 6). The control band setting is adjustable
air handling units can be made more efficient by resetting the
from 0 to 10°F (0 to 6°C). This adjustment is used to stabilize
discharge water temperature up as the average space
system operation.
temperature goes below a space temperature setpoint.

In order to accomplish this, space sensors (such as


A DISCHARGE WATER TEMPERATURE
B T7047C1025) are strategically located in the building to
D
UPPER CONTROL BAND LIMIT
measure average space temperature. It is recommended that
ADJUSTABLE at least 4 sensors be installed and wired to provide a signal
CONTROL
BAND proportional to the average space temperature. The setpoint
0 TO 10 F W7100 SETPOINT of the reset potentiometer should be set at the lowest desired
cooling temperature of the building. See Fig. 7 for space reset
operation (algorithm). See Fig. 8 for wiring details.
LOWER CONTROL BAND LIMIT M17917
C
As the average space temperature drops below the setpoint
Fig. 6. Discharge water control algorithm operation. of the reset sensors, the W7100G discharge temperature
setpoint is reset upward by an adjustable amount. Maximum
A description of how chiller control stages operate follows: reset occurs when the average space temperature is 3°F
1. Using Fig. 6 and beginning at point A, the discharge (1.7°C) below the setpoint of those sensors. At this time,
water temperature is above the upper control band limit the W7100G setpoint will be fully reset.
and the minimum OFF time has elapsed (selectable
either 30 or 60 seconds, using fast response input). In reset applications where high humidity can be a concern,
2. The W7100 first stage energizes. an outdoor air thermostat can be installed to override the reset
3. At point B, the discharge water temperature is still function. In lieu of outdoor air override an indoor space
above the upper control band limit. humidistat can also be used. See Fig. 8 for wiring diagrams.
4. If the minimum time between stages has elapsed
(selectable), the next highest cooling stage energizes.

63-4046—1 6
W7100G DISCHARGE WATER TEMPERATURE CONTROL

In applications where outdoor temperature does have a major


SPACE RESET effect on the cooling load of a building, outdoor reset can have
MECHANICAL
COOLING SETPOINT FULL RESET the same advantages as space reset. Fig. 9 shows the
outdoor air reset operation (algorithm).

As the outdoor air temperature rises above 70°F (21°C),


ADJUSTABLE RESET the W7100G discharge water temperature setpoint is reset
5 TO 20°F (3 TO 11K)
NO
downward. The reset amount is adjustable and it continues
RESET until the outside air temperature reaches 90°F (32°C). At this
point, the discharge water temperature is being controlled at
the W7100G setpoint.
SPACE 3°F (2K) SETPOINT OF
M17920 TEMPERATURE BELOW RESET RESET SENSOR
The outdoor air temperature reset strategy should only be
employed where outdoor air temperature has a major effect
Fig. 7. Space reset algorithm. on the building cooling load.

S963B1037 OUTDOOR RESET


1
COOLING SETPOINT FULL RESET

T675 TO W7100
R
OUTDOOR AIR TERMINALS
W THERMOSTAT 6 AND 7
60 F [16 C] 3 ADJUSTABLE RESET
5 TO 20°F (3 TO 11K)
NO
1-ZONE CIRCUIT RESET
S963B1037 1 W7100
2
SETPOINT
OUTDOOR AIR TEMPERATURE
ZONE 1 ZONE 3 M17919 T-LOW T-HIGH
T1 T3 R T675 TO W7100
OUTDOOR AIR TERMINALS
ZONE 2 ZONE 4
W THERMOSTAT 6 AND 7 Fig. 9. Outdoor reset schedule using C7031G1016.
60 F [16 C]
T2 T4

4-ZONE AVERAGING RESET CIRCUIT


W7100 LED Operation
The W7100 has one LED for each staged output. The LED
S963B1037
2 1 on the W7100 lights simultaneously as that stage relay
ZONE 1 ZONE 4 ZONE 7 energizes. With the LED not lit, the stage cannot energize.
T1 T4 T7 When the relay stage energizes, the normally closed contacts
open, and the normally open contacts close.
ZONE 2 ZONE 5 ZONE 8 T675 TO W7100
T2 R OUTDOOR AIR
T5 T8 TERMINALS
W THERMOSTAT
60 F [16 C]
6 AND 7 Reset Modifications
ZONE 3 ZONE 6 ZONE 9
T3 T6
While the outdoor air and the indoor air reset algorithms are
T9
software imbedded, it is possible to modify the outside air
reset start and stop temperatures. To do this, a resistor must
9-ZONE AVERAGING RESET CIRCUIT be placed in parallel with the outside air sensor (Rp) and a
resistor must be placed in series with the outside air sensor
1 S963B1037 REMOTE SETPOINT POTENTIOMETER REQUIRED TO
PERMIT ADJUSTMENT OF RESET CONTROL POINT. (USE ONLY (Rs). See Fig. 10.
WITH SPACE SENSORS. DO NOT USE WITH OUTDOOR SENSORS.)

2 ALL THERMOSTATS ARE T7047C1025 TYPE WIRED IN SERIES-


PARALLEL CONNECTION. RESISTOR (R )
OUTDOOR SERIES S
3 LOCK OUT RESET UNDER HIGH HUMIDITY CONDITIONS, SET AIR SENSOR 6
AT 60 F [16 C]. M3962 C7031G
RESISTOR W7100
(RP)
PARALLEL TERMINALS
Fig. 8. Reset from space sensor wiring.
7
M17918

Outdoor Resets
Outdoor reset can be employed as an alternative to space Fig. 10. Reset modification schematic wiring diagram.
reset (C7031G1016). The advantages to outdoor reset are
that it is simple to apply with a minimum of field wiring. The Use Table 3 to select the point at which no W7100 setpoint
disadvantage is that outdoor air temperature can have little reset will occur (T-High), and the point at which the W7100 will
effect on internal cooling load. This is best seen in the be fully reset (T-Low). The resistor values for series (Rs) and
common area of a large shopping mall, where the major parallel (Rp) resistors are at the intersection of T-High and
cooling loads are from solar heat, people and lighting. T-Low. Indicated resistor values are standard resistors and
can be purchased at any local electronics store.

NOTE: Only the outdoor air reset can be modified in the


above described manner.

7 63-4046—1
W7100G DISCHARGE WATER TEMPERATURE CONTROL

Table 3. Reset Modification Resistor Selection Chart


SETTINGS AND ADJUSTMENTS
T-High (no T-Low (full reset)
reset) 75 70 65 60 55 50
Setpoint Knob
100 Rp 14.7K 7.68K 5.36K 4.22K 3.48K 3.01K
Rs 196 324 432 511 576 634 HVAC Applications
95 Rp — 14.7K 7.68K 5.36K 4.22K 3.57K Typical setpoints for HVAC applications range from 50 to 55°F
Rs — 187 316 412 499 562 (10 to 13°C). These setpoints can change due to many
factors, including desired space temperature, required/desired
90 Rp — 0 14.7K 7.68K 5.49K 4.22K humidity conditions, etc.
Rs — 0 178 309 412 499
85 Rp — — — 14.7K 7.87K 5.49K Industrial Process Applications
Rs — — — 169 301 402 Consult process unit manufacturer for recommended settings.
80 Rp — — — — 15.0K 7.87K
Rs — — — — 158 294 Reset Knob
75 Rp — — — — — 15.0K
Rs — — — — — 147 HVAC Applications
Reset recommended for 5 to 10°F (3 to 6°C), depending on
NOTE: Resistors shown are standard values for 1/8W, 1%, desired maximum space temperature and space humidity
metal film resistors. requirements. Higher discharge water temperature can result
in higher space temperature and humidity depending on
outside air temperature and humidity, or internal latent and
sensible heat load.

Industrial Process Applications


Reset is not recommended for these applications. However,
check with process manufacturer for other recommendations.

Control Band Knob


Set for desired control band. Increasing the control band
slows down the W7100 response, and increases the
temperature deviation. Lowering the control band speeds up
the W7100 response, while decreasing the temperature
deviation from setpoint.

The control band setpoint should be as narrow as possible


without causing hunting or rapid cycling. If instability, hunting,
or rapid cycling occurs, widen the control band setpoint.

Fast Response Input


The W7100G has the capability of changing the timings
between stages, the stage minimum ON timings and the stage
minimum OFF timings.To do this, you must select which
timing is desired (either 30 or 60 seconds):
— If you desire a 30 second delay, jumper terminals 9 and 10.
— If you desire a 60 second delay, leave terminals 9 and 10
open (unjumpered).

Number Of Stages
Select the proper resistor (see Table 2) that represents the
total number of controlled stages. Place this resistor across
terminals 7and 8 on the W7100G.

63-4046—1 8
W7100G DISCHARGE WATER TEMPERATURE CONTROL

SYSTEM CHECKOUT
To field test the system, follow the steps detailed in Table 4. In
order to complete this checkout, the following equipment is
required:
— 4074EDJ Test Plug and Resistor Bag Assembly.
— 4074EFV Resistor Bag Assembly.
— Digital VOM meter.
— 195770A Test Plug.

Table 4. W7100G System Checkout.


Step Action Verification
1 Disconnect power from W7100. Check for 0 Vac across W7100 TR and TR terminals.
2 Disconnect compressor and unloader line voltage power. Check for 0 Vac at compressor and unloader contactors or
relays.
3 Remove C7170A Sensor leads from W7100 and replace —
with 4074EDJ Bag Assembly 3400 ohm resistor (blue
leads).
4 Remove from W7100 any jumper installed on the Fast —
Response Terminals (9 and 10).
5 Remove from W7100 terminals 6 and 7 all wires. Place a —
4074EDJ Bag Assembly 1780 ohm resistor (red leads).
6 Jumper W7100 terminals P and P1. —
7 Remove red plastic dust plug from W7100 bottom and install —
195770A Test Plug in the revealed socket.
8 Set W7100 reset knob at 20°F (11K) —
9 Set W7100 setpoint at 10°F (-12°C) —
10 Connect 24 Vac power to the W7100 (TR and TR terminals) Check for 24 Vac across W7100 TR and TR terminals.
11 Wait 15 seconds. —
12 All W7100 stages should be energized All red LED should be on.
13 Adjust W7100 setpoint to 60°F (16°C). —
14 Wait 15 seconds. —
15 All W7100 stages should be off. All red LED should be off.
16 Remove 1780 ohm resistor from W7100 terminals 6 and 7. —
17 Jumper W7100 terminals 6 and 7. —
18 Adjust W7100 setpoint to 50°F (10°C) —
19 Wait 15 seconds. —
20 All W7100 stages should be energized. All red LED should be on.
21 Disconnect power from W7100. Check for 0 Vac across W7100 TR and TR terminals.
22 Reconnect all wiring as originally installed. —
23 Remove 195770A Test Plug and install red plastic dust —
cover.
24 Reconnect W7100 power supply, close compressor System is now operational.
disconnects, and place W7100 setpoints where desired.

9 63-4046—1
W7100G DISCHARGE WATER TEMPERATURE CONTROL

TROUBLESHOOTING (TABLE 5)
Table 5. W7100G Troubleshooting Guide.
Problem Possible Cause Corrective Action
Discharge 1. Integral setpoint not at minimum position when 1. Set integral setpoint at minimum position when
temperature used with remote setpoint. using remote setpoint.
too high. 2. System malfunction. 2. Consult HVAC manufacturer’s equipment manual
and/or building engineering requirements.
No cooling. 1. Shorted or open discharge sensor terminals T-T1. 1. Correct the wiring.
2. Open reset terminals 6-7 interpreted as maximum 2. Jumper terminals 6-7 or connect reset
reset. thermostat.
3. Remote setpoint terminals P-P1 open. 3. Jumper terminals P-P1 or connect remote
setpoint potentiometer.
4. System malfunction. 4. Consult HVAC manufacturer’s equipment manual
and/or building engineering requirements.
Short cycling. 1. Test plug left inserted in W7100 bottom. 1. Remove test plug.
2. System malfunction. 2. Consult HVAC manufacturer’s equipment manual
and/or building engineering requirements.

63-4046—1 10
11 63-4046—1
By using this Honeywell literature, you agree that Honeywell will have no liability for any damages arising out of your use
or modification to, the literature. You will defend and indemnify Honeywell, its affiliates and subsidiaries, from and against
any liability, cost, or damages, including attorneys’ fees, arising out of, or resulting from, any modification to the literature
by you.

Home and Building Control Home and Building Control Honeywell Asia Pacific Inc. Honeywell Europe S.A. Honeywell Latin American
Honeywell Honeywell Limited-Honeywell Limitée Room 3213-3225 3 Avenue du Bourget Region
1985 Douglas Drive North 35 Dynamic Drive Sun Hung Kai Centre 1140 Brussels 480 Sawgrass Corporate Parkway
Golden Valley, MN 55422 Scarborough, Ontario No. 30 Harbour Road Belgium Suite 200
M1V 4Z9 Wanchai Sunrise FL 33325
Hong Kong

63-4046—1 B.B. Rev. 9-01 www.honeywell.com/building/components

S-ar putea să vă placă și