Medium Voltage Distribution

Catalogue | 2013

Ringmaster
Ring Main Unit

Ringmaster range

General contents

Presentation

AMTED399086EN

Ring main units

19

Circuit breaker, metering


and switches

43

Remote control

91

Installation drawings

95

Schematic diagrams

107

Accessories & options

149

Schneider Electric, an overview


and order form

161
1

AMTED399086EN

Presentation

AMTED399086EN

Contents

Applications

Switchgear description

Standards and quality

Time Fuse Link (TFL) protection

VIP protection relays

Sepam series 10

Fault passage indicators and VPIS

13

Network remote control

14

Ringmaster selection guide

17

Presentation

Applications

Ringmaster is the ideal choice for all your MV applications.


From simple transformer protection, or sectionalising with remote
control, to multi-panel metered consumer switchboards,
the Ringmaster range from Schneider Electric offers a solution.
Quality engineering for extreme climates enables Ringmaster
to provide flexibility for any location.
Covering a wide range of options with an indoor and outdoor IP54
design and ratings up to 13.8 kV, 630 A and 21 kA, Ringmaster
has proved successful in markets around the world.

Product advantages
Simple, clear operation combined with compact size,
high functionality and reliability extends the applications
of the Ringmaster range.
Safety to personnel
Fully certified internal arc design.
Indoor/outdoor design
No need for expensive switchrooms.
Self-powered protection
Not reliant on costly battery chargers.
Compact
Reduced dimensions, gives reduced civil costs.
Virtually maintenance free
Low lifetime costs.
Modular design
Quick, simple & easy to install.
Proven design
Assured consistent quality.
ISO 9001 quality certification.

PE40438

Environmental
Manufactured to ISO 14001 environmental standards.
Direct mounting to transformer
No cable connection needed thus cost saving in term of cable
and cable connection when directly mounted to transformers
Plug in motor
Directly mountable to a pre-wired live RMU on site, in less than 1 min.
SCADA compatible with T200E
Internal arc - 21 kA A-FLR on gas module
High performance
Switch rated up to 5000 numbers mechanical operations (in option).
High strength
10 mm thick tank provides the much needed strength to be study
enough to face harsh environment and provide reliable supply.
Metalised tank
Tank is coated with metal coating of 50 microns, ensuring complete
earth screening, making it highly suitable to be placed in public areas.

AMTED399086EN

Switchgear description

Presentation

A variety of different panel types are available for each unit within the range, together
with a number of optional accessories enabling Ringmaster to satisfy the most
complex system specification.

General characteristics

b Integral self-powered protection with TFL,


adjustable curve & relay options
b IP54 enclosure
b Simple to follow mimic providing user-friendly
operation
b Earth screened cast-resin gas module

PE57064

PE57061

Free standing,
non-extensible,
cable connected
ring main unit.

PE57067

PE57062

b Range of dry type metering units


b Mechanical tripped on-fault indication
b Resin encapsulated busbars in air bus chamber
for extensible version
b Direct coupling to transformers or cable connection.

Transformer mounted,
non-extensible ring main unit,
incorporated in a packaged
substation.

PE57065

b Gas pressure indicator as standard


b Anti-reflex operating handle with facilities for
electrical operation
b Interlocked MV cable test access (no need to
remove cable terminations or use loose earthing
devices)

A multitude of configurations

Transformer mounted,
extensible ring main unit,
incorporated in a packaged
substation.

PE57066

PE57063

Free standing,
extensible
cable connected
ring main unit

Free standing,
non-extensible
circuit breaker.

PE57070

PE57068

Free standing
double extensible
cable connected ring main unit.

AMTED399086EN

Cable connected
extensible switchboard.

Free standing,
non-extensible, top entry,
cable connected ring main unit.

Presentation

Standards and quality

Standard and quality assurance


Manufactured to BS EN ISO 9001.
Ringmaster meets the following standards and has obtained approval from the UK
Electricity Association: IEC 62271-100, IEC 60265, IEC 62271-200, BS EN 60265
and ENA TS 41-36.
Environmental Management System BSEN ISO 14001 OHSAS 18001 Management
of Health and Safety.

Conformity with standards in force


Ringmaster meets the current national or international standards in force:
(IEC, BS, IS).
The main electro-technical standards cover:
b The design of the functional units and switchgear
b Medium voltage switchgear (interruption, sectionalizing, insulation)
b Current and voltage transformers
b Low voltage switchgear
b SF6 gas
b Cables and conductors
b Graphs and diagrams
b Tests
b International electro-technical vocabulary.

PE58325

A quality and safety approach


Both sites ie. Leeds in UK and Hyderabad in India, are, for many years,
been committed to a global quality approach and are certified:
b ISO 9001: 2000
b ISO 14001: 2004
b OHSAS 18001 (since 1999).

Tests on the devices


Various factory tests are carried out on Ringmaster before it is shipped to the
customer:
b Tank leak-tightness test
b Mechanical test for control mechanisms
b Dielectric tests.
The Ringmaster switchboards comply with the requirements of the following standards and regulations:
Description

IEC standard

IEC classes

EN standard

Switchboard

IEC 62271-200
IEC 62271-1

LSC partition class PM


Continuity of service of the cable
connection and fuse compartments:
LSC2A (1)

EN 62271-200
EN 62271-1

Behaviour in the event of internal faults

IEC 62271-200

Earthing switch

IEC 62271-102

E2

EN 62271-200

Ring switch

IEC 62271-103

M1, E3, C1

Circuit-breaker

IEC 62271-100

M1, E2

Current transformer

IEC 60044-1

EN 60044-1

Voltage transformer

IEC 60044-2

EN 60044-2

Voltage presence indicators

IEC 61958

EN 61958

Voltage detection systems

IEC 61243-5

EN 61243-5

Protection against accidental contact, foreign bodies


and ingress of water

IEC 60529

EN 60529 1

EN 62271-102
EN 62271-100

Installation

HD 637 S

Operation of the electrical equipment

EN 50110

AMTED399086EN

Time Fuse Link (TFL) protection

Presentation

Self-powered reliability

TFL protection
An effective low cost option without compromising reliability.
CT operated trip coils (with TFL) provides phase overcurrent and earth fault inverse
time protection, the characteristic being given by a Time Fuse Link (TFL).
This option is suitable for transformer protection up to 1600 kVA.
DE60245-1

Recommended Time Fuse Link (TFL) settings to ESI 12-6


(kV)
3.3

CT ratio = 50/5
earth fault setting
= 25 A
6.6
(instantaneous
trip)
11

13.8
CT ratio = 100/5 3.3
earth fault setting
= 30 A
6.6
(instantaneous
trip)
11

DE60249

13.8

Voltage Transformer rated power (kVA)


200
315
500
800
1000
10 A
150 A
5A
10 A
15 A
150 A 250 A 400 A
3A
5A
10 A
15 A
200 A 300 A 400 A 560 A
3A
5A
10 A
15 A
200 A 300 A 400 A 560 A
5A
10 A
15 A
150 A 250 A 400 A
5A
7.5 A 12.5 A 15 A
250 A 400 A 560 A 560 A
5A
7.5 A 10 A
400 A 560 A 630 A
5A
7.5 A 10 A
400 A 560 A 630 A

1250

12.5 A
630 A
12.5 A
630 A

1600

15 A
630 A
15 A
630 A

TFL
LV fuse
TFL
LV fuse
TFL
LV fuse
TFL
LV fuse
TFL
LV fuse
TFL
LV fuse
TFL
LV fuse
TFL
LV fuse

Benefits
b Low cost
b Fast clearance of LV faults
b Simple to replace
b Proven protection to EA standards
b Fast tripping for MV earth faults
b Improved discrimination with LV fuse
Principle of operation
The current transformer feeds a trip coil that is normally shunted by a time fuse link.
In the event of a fault the fuse ruptures, diverting all the fault current through the trip
coil, tripping the breaker. A residually connected trip coil provides instantaneous
earth fault protection.

Protection application guide


Product
Application

CE2, CN2, RN2c, RE2c


Transformers
200-1600 kVA
b

CE6, RN6c

400-3800 kVA

Transformers
1900-12000 kVA

Ring feeders
1900-12000 kVA

Incomers
1900-12000 kVA

Time fuse Link


b
b
b
b
IDMT VIP 300
Note: a protection co-ordination study may be necessary to verify the type of protection. Consult your local Schneider Electric sales engineer if in doubt.

Protection selection guide


Primary current (A)

10

Equivalent transformer rating at 11 kV


200 kVA
Application
Panel
Protection
Transformer
CE2/CN2
Time Fuse Link b
protection
RE2c/RN2c
IDMT - VIP 30/35 b
RE2c/RN2c
IDMT - VIP 300
Feeder
CE6/RN6c
IDMT - VIP 300
protection

AMTED399086EN

20

80

100

125

200

630

400 kVA

1600 kVA

1900 kVA

2400 kVA

3800 kVA

12000 kVA

b
b
b

b
b
b

b
b
b

b
b
b

b
b

Presentation

VIP protection relays


Self-powered reliability

PE57160

VIP 300 - the leading protection relay providing


a wide range of selectivity and quality of supply
The VIP 300 is a three phase overcurrent and earth fault protection device, providing
protection for networks and equipment. Being an integral part of the highly successful
Ringmaster range, its main function is to detect phase and earth faults within the
network and to trip the circuit breaker.

Flexibility
VIP 300
b Pick-up current ranges: RN2c, RE2c, CN2, CE2
Overcurrent: 20-200 A.
Earth fault: 2-160 A.
CE6 and RN6c Overcurrent: 80-800 A.
Earth fault: 8 A to 640 A.
Hardened electronics Certified EMC performance to IEC
60255 and EN 50061, EN50082.
b Separate overcurrent and earth fault trip indication.
b Flashing LEDs indicate when the relay is operating under
fault conditions.

The relay provides for a wide range of protection settings for most applications.
The IDMT characteristics employed for both the overcurrent and earth fault elements
can be easily adjusted to provide discrimination with upstream MV and downstream
LV protective devices. Fast power-up of the VIP 300 also provides immediate
protection and can detect faults instructing the CB to trip in less than 40 ms.

Reliability
The relay has a self monitoring device and diagnostic routine that constantly checks
the operation of the relay automatically.

PE57159

Self-powered reliability
The VIP 300 protection relay is a self powered microprocessor based device which
requires no external DC power source or batteries, making it the ideal solution for
location in remote areas where auxiliary supplies are not readily available.

Ease of use
VIP 300 has improved operation and control with the relay settings being clearly
displayed on the front panel. Manual reset flags show separate tripped on fault for
either phase or earth fault conditions.

PE56826

VIP 35
provides protection against phase-to-phase faults
and earth faults.

Testing
The VAP 6 hand held test unit, is available to provide a simple check of the integrity
of the relay and can also be used to perform trip tests on the circuit breaker.
The circuit breaker trip inhibit facility allows the relay to be tested without tripping
the circuit breaker. Secondary injection can be carried out using conventional test
equipment.
The VIP 30 and VIP 35 are self-powered devices, requiring no external DC power
source or batteries. They are designed for use in distribution networks providing
protection for transformers.

VAP 6

AMTED399086EN

Presentation

Sepam series 10

PB103446

Sepam series 10 is a high-quality protection relay that represents the most costeffective solution available for essential protection functions. Highly ergonomic, it is
easy to install and set up.

Sepam series 10 specifics


Sepam series 10 monitors phase and/or earth-fault currents. Three models meet a
wide range of different needs :
b N: Sepam series 10 N protects against earth faults
b B: Sepam series 10 B protects against overloads, phase-to-phase faults and earth
faults
b A: Sepam series 10 A provides the same functions as Sepam series 10 B, with
also a communication port, more inputs and outputs, and additional protection and
monitoring functions.
Sepam series 10

Simplicity
b Easy operation - screen, keys, pictograms, etc., good ergonomics
b Fast set-up - installation, wiring, parameter setting directly on the relay without a PC.
Reliability
b Guaranteed protection of life and property - high-quality product, compliance
with standards, continuous self-test
b Safety of operating personnel - all accessible parts are made of insulating
materials, light and compact product with no sharp edges
b Environmentally friendly - compliance with the European RoHS directive, low
energy consumption, manufacture in factory certified ISO 14001 and recyclable to
more than 85%.
Productivity
b Attractive, cost-effective product - easy to understand, no unnecessary
complications, suited to user needs
b Improved availability of electricity - precise tripping set points and times, logic
discrimination, detailed information made spontaneously available to operator
following tripping.
b Reduced maintenance costs - continuous self-tests to extend periods between
maintenance.
Functions
Protections
Earth-fault protection

ANSI
code

Standard
50N/51N
Sensitive
High sensitivity
Phase-overcurrent protection
50/51
Thermal overload protection
49RMS
Phase-overcurrent and earth fault protection
cold load pick-up
Logic discrimination
Blocking send
68
Blocking reception
External tripping
Measurements
Earth-fault current
Phase currents
Peak demand currents
Control and supervision
Circuit breaker tripping and lockout
86
Tripping indication
Trip-circuit supervision
Remote circuit-breaker control
Record of last fault
Record of last five events
Communication
Modbus
IEC 60870-5-103

Sepam series 10
N
B
A
v

v
v
v
b
b
b

v
v
v
b
b
b

b
b
b

b
b
b

b
b
b

b
b

b
b

b
b
b
b

b
b
b

Inputs/Outputs (number)
Earth-fault current inputs
Phase-current inputs
Logic relay outputs
Logic inputs
Communication port
b Function available.
v Function availability depends on the Sepam model.

AMTED399086EN

1
3
-

1
2 or 3
3
-

1
3
7
4
1

Sepam series 10

Presentation

User-machine interface and dimensions

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15

Back-lit display
Status LEDs
Fault LEDs
Button for Sepam reset and maximeter reset
Battery housing (Sepam series 10 A)
Protection cover for settings
Identification zone
Lead-seal accessory
Button for setting selection and confirmation
Buttons for selection in a menu
Button to cancel entry
Buttons for setting adjustments
Button for menu selection and LED test
Menu pictograms
Cursor for menu selection

DE53450_SE

User-machine interface

DE53451_SE

Dimensions

Characteristics

10

Applicable to

Value

Dimensions

series 10

180 x 140 x 90 mm / 7.09" x 5.51" x 3.54"

Weight depending on
number of current inputs

series 10 N 1
series 10 B 3
series 10 A 4

1.15 kg/2.53 pounds


1.26 kg/2.78 pounds
1.46 kg/3.22 pounds

Type of battery

series 10 A

1/2 AA Li 3.6 V

AMTED399086EN

Sepam series 10

Presentation

Protection functions

DE53229

Earth-fault protection (ANSI 50N-51N)


Earth-fault protection detects overcurrents caused by phase-to-earth faults. It uses
measurements of the fundamental component of the earth-fault current.

2 independent set points (Io> and Io>>)


b The low set point (Io>) offers definite time (DT) or IDMT settings with various types
of standardized curves (IEC, IEEE, RI) and it is possible to enable an IDMT timer hold.
b The high set point (Io>>) offers only the definite time (DT) setting. The minimum
setting results in instantaneous operation (ANSI 50).
Depending on the required level of sensitivity, there are three types of Sepam relays.
Io>

Io>>

Io

Sensitivity
Standard

Sensor
3 phase CTs or 1 earth-fault protection CT,
with rated primary current Ino

Setting range
0.1...24 Ino

Sensitive (1)

3 phase CTs or 1 earth-fault protection CT, with rated


primary current Ino

0.01...2.4 Ino

High
sensitivity

Special core balance CSH or GO, with ratio of 470/1

0.2...240 A primary,
i.e. 0.0004...0.5 Ino

(1) Setting not available with Sepam series 10N.

Phase-overcurrent protection (ANSI 50-51)


Phase-overcurrent protection detects overcurrents caused by phase-to-phase faults.
It uses the measurements of the fundamental component of currents drawn from two
or three phase CTs, with a secondary rating of 1 A or 5 A.

DE53228

2 independent set points (I> and I>>)


b The low set point (I>) offers definite time (DT) or IDMT settings with various types
of standardized curves (IEC, IEEE, RI) and it is possible to enable an IDMT timer hold.
b The high set point (I>>) offers only the definite time (DT) setting.
The minimum setting results in instantaneous operation (ANSI 50).
t

Thermal image overload protection (ANSI 49 RMS)


This protection function is used to protect cables and HV/LV transformers against
overloads, based on measurement of the current drawn.
The function is based on a thermal model which calculates the temperature rise from
current measurements. The current measured is an RMS 3-phase current which
takes into account harmonics up to number 13.
Two protection settings
b The continuous maximum permissible current setting which corresponds to the
maximum thermal withstand of the protected devices (the continuous permissible
current corresponds to a temperature rise of 100%).
b The setting for the equipment heating and cooling time constant.

Ith

AMTED399086EN

I>

I>>

11

Sepam series 10

Presentation

DE53195

Protection functions

Protection function 50/51, 50N/51N

Sec
1000

Tripping curve
b
b
b
b
b
b
b
b
b

100

DT: Definite time


SIT/A: IEC standard inverse
VIT/B: IEC very inverse
LTI/B: IEC long-time inverse
EIT/C: IEC extremely inverse
MI/D: IEEE moderately inverse
VI/E: IEEE very inverse
EI/F: IEEE extremely inverse
RI

I>, I>> set points


DT curve

10
LTI/B
RI
SIT/A

0.1...24 In (minimum: 1 A)

IDMT curves

0.1...2.4 In (minimum: 1 A)

Accuracy
Drop out/pick up ratio

5% or 0.02 In
95%

Transient overshoot

< 10%

Io>, Io>> set points

VIT/B

DT curve

Standard version
Sensitive version

EIT/C

High sensitivity Rating 0.224 A


version
Rating 2.0240 A

0.1
1

10

20

IEC curves SI, VI, LTI, EI and RI curve

I/I>
or
Io/Io>

IDMT curves Standard version

DE53194

Sensitive version
Sec
High sensitivity Rating 0.224 A
version
Rating 2.0240 A

1000

100

Setting range: 0.124 Ino


(minimum: 1 A)
Setting range: 0.012.4 Ino
(minimum: 0.1 A)
Setting range: 0.00040.05 Ino
(Ino = 470 A)
Setting range: 0.0040.5 Ino
(Ino = 470 A)
Setting range: 0.22.4 Ino
(minimum: 1 A)
Setting range: 0.010.24 Ino
(minimum: 0.1 A)
Setting range: 0.00040.005 Ino
(Ino = 470 A)
Setting range: 0.0040.05 Ino
(Ino = 470 A)

Accuracy

5% or 0.02 Ino

Drop out/pick up ratio

95%

Transient overshoot

< 10%

Time delay
DT curve

TMS: 0.02...2 (step: 0.01)

IEEE curve

TD: 0.5...15 (step: 0.1)

Accuracy

DT curve: 2% or 20 ms
IDMT curves: 5% or 20 ms

MI
VI

Timer hold

EI

Accuracy

Selection: ON/OFF. Common setting for


I> and Io> set points
2% or 20 ms

10

0.05...300 s

IEC, RI curves

Characteristic times
0.1
1

IEEE curves MI, VI, EI

10

20

I/I>
or
Io/Io>

Operation time

< 40 ms at 2 x set point (typically 25 ms)

Overshoot time

< 40 ms at 2 x set point

Reset time

< 50 ms at 2 x set point

Protection function 49RMS


Set points
Alarm set point
Trip set point

Setting range
Setting range
Accuracy
Drop out/pick up ratio

50...100% of permissible thermal capacity


0.1...2.4 In (value of permissible current)
5% or 0.02 In
95%

Setting range
Tripping-time accuracy

1...120 min in 1 min steps


2% or 2 s

Time delay
Time constant

12

AMTED399086EN

Presentation

Fault passage indicators


and VPIS

PE57784

Fault passage indicators


Flair 21D, 22D is a family of DIN format fault passage indicators.
They are small in size, self-powered and adapt automatically to the network.
The Flair range increases your power availability by providing indicators suitable
for fault locating and MV network load management.
Flair 22D

Flair 200C
Easergy Flair 200C is a remote monitoring unit designed to be installed in the MV
substations of a public-private distribution network or in customers substations.

PE57570

Voltage presence indicators VPIS


A voltage presence indicating device can be integrated in all the functional units,
either on the cable side. It can be used to check whether or not a voltage
is present across the cables.

PE58177

Flair 200C

VPIS V2

AMTED399086EN

13

Network remote control

Presentation

SCADA

PE58319

Complete visibility
Gain energy insight and control with power monitoring
and control software

Real-time, high speed response


Our range of power management software delivers a reliable, flexibleand high
performance monitoring and control solution designed to reduce outages and
increase power efficienc.
It is built to handle user requirements from the smallest to the most demanding
enterprises, while still providing high time performance and reliability.
Easy-to-use configurationtools and powerful features enable faster development
and deployment of any size of application.
Object-based, standard graphics and symbols provide operators with an interactive
and user-friendly interface. Intuitive commands and controls increase efficiencyof
operators to interact with the system interface. It will control your system with high
reliability, performance and data integrity through the use of advanced architectures,
such as hot/warm redundant I/O device configurations,self-healing ring
communications, and primary and standby server configurations.Comprehensive
user-based security is integrated into all interface elements, ensuring a secure
control system.

Reliable, flexible and scalable platform design

DE59861

Power Management solutions by Schneider Electric offer complete redundancy


for communications, network servers, alarming, trending, and data synchronisation.

14

AMTED399086EN

Network remote control

Presentation

T200E telecontrol

Ringmaster and T200E


Control your Ringmaster from a remote position
The Schneider Electric Easergy T200E telecontrol cabinet, which links the
Ringmaster to a control centres automation system, allows you to manage
a secondary distribution network from a remote point. Network faults can be
identified and isolated and the network reconfigured in seconds without manual
intervention, which substantially improves the quality of supply.
The small and compact Easergy T200E can be easily mounted directly onto
the Ringmaster, saving installation costs and valuable floor space.

PE57071

PE57069

Telecontrol equipment can be added any time after installation. This makes
Ringmaster RMUs even more cost-effective to install, since a control system
can be bought separately if needed at a later date. Other RTUs can also be
integrated if required.

Internal view
of Easergy T200E

Ringmaster C with Easergy T200E

AMTED399086EN

15

Network remote control

Presentation

Easergy L500

Continuity of service guaranteed by an overall


telecontrol offer
Schneider Electric offers you a complete solution, including:

DE40901EN

PE56312

b the Easergy T200 E telecontrol interface,


b MT switchgear that is adapted for telecontrol.
HV/MV

RN2C

RN2C

RN2C

MV ring
Communication network

Network control centre


L500 network monitoring screen

RN2C

RN2C

RN2C

PE57073EN

Easergy L500, a low cost solution


to immediately improve your SAIDI (1)
(1) SAIDI: system average interruption duration index

Easergy L500 is a SCADA providing all the functions needed to operate


the MV network in real time
b Pre-configured with Easergy range products:
v MV/LV substations equipped with T200 E or Flair 200C
v overhead line equipped with Flite 116/G200
b Broad range of transmission supports: Radio, GSM, GPRS, PSTN, LL, FO.
Advantages
b Simple implementation:
v one to two weeks only for 20 MV/LV substations
v configuration, training and handling within a few days
b Short return on investment
b Simple and fast evolutions by operations managers
b Service quality and operations rapidly improved.

16

AMTED399086EN

Ringmaster selection guide

PE57072-1

Presentation

RN2c or RN6c

RE2c or RE6c

RDE2c or RDE6c MU2 or MU6

CN2

SN6

CE2 or CE6

SE6

200 A or 630 A
non extensible
ring main unit

200 A or 630 A
extensible
ring main unit

200 A or 630 A
double extensible
ring main unit

200 A
non extensible
circuit breaker

630 A
non extensible
switch

200 A or 630 A
extensible
circuit breaker

630 A
extensible
switch

200 A or 630 A
feeder
metering unit

Key to product references


Ringmaster is available as standard panel types, allowing easy selection and
specification. The product references are made up as follows:

R
C
S
DE
c
N
E
MU

Ring main unit


Circuit breaker
Switch
Double Extensible

2
6
16
21

200 A
630 A
16 kA
21 kA

compact
Non-Extensible
Extensible
Metering unit

Example: CN2-T1/16 = circuit breaker, non extensible, 200 A, 16 kA fault rating.


The Ringmaster catalogue allows easy selection and specification, based on a broad
range of worldwide applications.
Included in this publication is:
b panel type specifications
b details of optional accessories
b schematic diagrams
b Installation drawings.

Accessories
Accessories for the Ringmaster range are supplied either fitted or loose, where
stated enabling simple panel configuration on site. Details of accessories are
contained within the panel type pages.

General arrangement drawings


General arrangement drawings are given for each panel type.
This allows you to quickly size up switchrooms and calculate external connections
at the pre-order stage.

Need more information?


If your requirements are not listed, please contact your local Schneider Electric
representative, or contact us on:
Tel: +44 (0) 113 290 3500
Web: www.schneider-electric.com

Electronic catalogue requests


Electronic copies of this selection guide are available free of charge upon request.
For this, and other MV literature, please email your full contact details to Email:
MVSwitchgearGB@schneider-electric.com

AMTED399086EN

17

18

AMTED399086EN

Ring main units

Contents

Characteristics - Electrical & Mechanical

20

Non-extensible ring main units

22

Specification
Accessories

Non-extensible ring main units 200 A

25

RN2c-T1, RN2c-T2, RN2c-T3, RN2c-T4, RN2c-T5, RN2c-T25

Non-extensible ring main units 630 A

31

RN6c-T1, RN6c-T25

Extensible ring main units

33

Specification
Accessories

Extensible ring main units 200 A

36

RE2c-T1, RE2c-T2, RE2c-T3, RE2c-T4, RE2c-T25

Double Extensible ring main unit 200 A or 630 A

41

RDE2c, RDE6c

AMTED399086EN

19

Ring main units

Characteristics - Electrical &


Mechanical

Characteristics of Ringmaster
Rated voltage (Ur)

kV

12

13.8

Rated frequency (fr)

Hz

50/60

50/60

Rated lightning impulse withstand voltage (Up)

kV

75

95

Rated power frequency withstand voltage (Ud)

kV

28

38

Ring switches (Ir)

630

630

Circuit breaker (Ir)

200/630

200/630

Ring switch rated short time withstand, 3 s (Ik)

kA

16

21

Ring switch earth short time withstand, 3 s (Ik)

kA

16

21

Ring switch peak making current (Ip)

kA

40

53

Ring switch earth peak making current (Ip)

kA

40

53

Circuit breaker short time withstand, 3 s (Ik)

kA

16

21

Ciruit breaker earth short time withstand, 3 s (Ik)

kA

16

21

Circuit breaker peak making current (Ip)

kA

40

53

Circuit breaker earth peak making current (Ip)

kA

40

53

Internal arc withstand

kA

16

21

Rated current

Number of operating cycles


Mechanical: ring switch (main)

1000

1000

ring switch (in option)

5000

5000

ring switch (earth)

1000

1000

circuit breaker (main)

2000

2000

circuit breaker (earth)

1000

1000

circuit breaker (at rated short circuit breaking current) 11

10

SF6 gas

20

Pressure

bar G

0.35

0.55

Weight (RN2c/RN6c)

516

592

Weight (RE2c)

612

703

AMTED399086EN

Ring main units

Characteristics - Electrical &


Mechanical

Characteristics of RMR switch


Rated voltage (Ur)

kV

12

13.8

Rated frequency (fr)

Hz

50/60

50/60

Rated lightning impulse withstand voltage (Up)

kV

75

95

Rated power frequency withstand voltage (Ud)

kV

28

38

Rated current
Switches (Ir)

630

630

Switch rated short time withstand, 3 s (Ik)

kA

16

21

Switch earth short time withstand, 3 s (Ik)

kA

16

21

Switch peak making current (Ip)

kA

40

53

Switch earth peak making current (Ip)

kA

40

53

Internal arc withstand

kA

16

21

Number of operating cycles


Mechanical: switch (main)

1000

1000

switch (in option)

2000

2000

switch (earth)

1000

1000

SF6 gas
Pressure

bar G

0.35

0.55

Weight

429

493

Characteristics of RMR circuit breaker


Rated voltage (Ur)

kV

12

13.8

Rated frequency (fr)

Hz

50/60

50/60

Rated lightning impulse withstand voltage (Up)

kV

75

95

Rated power frequency withstand voltage (Ud)

kV

28

38
200/630

Rated current
Circuit breaker (Ir)

200/630

Circuit breaker short time withstand, 3 s (Ik)

kA

16

21

Ciruit breaker earth short time withstand, 3 s (Ik)

kA

16

21

Circuit breaker peak making current (Ip)

kA

40

53

Circuit breaker earth peak making current (Ip)

kA

40

53

Internal arc withstand

kA

16

21

Mechanical: circuit breaker (main)

2000

2000

circuit breaker (earth)

1000

1000

Number of operating cycles

circuit breaker (at rated short circuit breaking current) 11

10

SF6 gas

AMTED399086EN

Pressure

bar G

0.35

0.55

Weight

429

493

21

Non-extensible ring main units

Ring main units

Specification

RN2c-T1
TFL

RN2c-T2
VIP 300

RN2c-T3
VIP 30

RN2c-T4
VIP 35

RN2c-T5
Glass TFL

RN2c-T25
Sepam 10

RN6c-T1
VIP 300

RN6c-T25
Sepam 10

b
b
b
O

b
b
b
O

b
b
b
O

b
b
b
O

b
b
b
O

b
b
b
O

b
b

b
b

b
b

b
b

b
b

b
b

b
b

b
b

b
b
O
b
O
b

b
b
O
b
O
b

b
b
O
b
O
b

b
b
O
b
O
b

b
b
O
b
O
b

b
b
O
b
O
b

b
b
b
O
b
O
b

b
b
b
O
b
O
b

b
b
b
O

b
b
b
O

b
b
b
O

b
b
b
O

b
b
b
O

b
b
b
O

b
b
b
O

b
b
b
O

Environment
Indoor / outdoor
IP54
Transformer mounted
Freestanding

Ratings
Busbars 630 A
Circuit breaker normal rated current 200 A
Circuit breaker normal rated current 630 A
Switch normal rated current 630 A
12 kV 16 kA 3 seconds 75 kV BIL
13.8 kV 21 kA 3 seconds 95 kV BIL
Ring switch cable earth switch 16 kA 3 seconds
Ring switch cable earth switch 21 kA 3 seconds
Circuit breaker earth switch 3.15 kA

Mechanism
Independent manual
Provision for motorised mechanism LH ring switch
Provision for motorised mechanism RH ring switch
Provision for motorised mechanism circuit breaker

Protection & control - circuit breaker


b
CTs dual ratio - 100/50/5 A class X
CTs ratio - 200/1 A class X
CTs ratio - 200/100/1 5P20
CTs ratio - 500/200/1 A class X
CTs ratio - 800/400/1 A class X
CTs ratio - 800/400/1 5P20
Overcurrent & earth fault CT operated trip coils - TFL b
Overcurrent & earth fault CT operated trip coils glass TFL
Overcurrent relay - VIP 30
Overcurrent & earth fault relay - VIP 35
IDMT overcurrent & earth fault relay - VIP 300
IDMT Relay Sepam 10
Multi voltage shunt trip coil (see accessories page 23) O

b
b
b
b

b
b
b
b

b
b

b
b
b

b
b

b
b
O
b
O

b
b
O
b
O

b
b
O
b
O

b
b
O
b
O

b
b
O
b
O

b
b
O
b
O

b
b
O
b
O

b
b
O
b
O

b
O

b
O

b
O

b
O

b
O

b
O

b
b

b
b

b
b
O

b
b
O

b
b
O

b
b
O

b
b
O

b
b
O

b
b
O

b
b
O

RN2c-T4/16
RN2c-T4/21
RMINST-06
Page 103
RMINST-05
Page 157

RN2c-T5/16
RN2c-T5/21
RMINST-06
Page 103
RMINST-05
Page 157
RMSCH-01
Page 112

RN2c-T25/21
RMINST-06
Page 103
RMINST-05
Page 157

RN6c-T1/16
RN6c-T1/21
RMINST-06
Page 103
RMINST-05
Page 157

RN6c-T25/21
RMINST-06
Page 103
RMINST-05
Page 157

Indication
Mechanical ON/OFF
Mechanical EARTH/MAIN
VPIS indication 3.3 - 13.8 kV
Gas pressure indicator (-25C to +55C)
RSW aux contacts 1NO & 1NC

Test facility
Integral ring cable test facility
Integral circuit breaker test facility

Standard features
Operating handle

Cable (see available cable kit accessories)


Bottom entry up 1 x 3C 300 mm2
Bottom entry up 3 x 1C 630 mm2
Top entry cables (indoor only)

Order codes
12 kV, 16 kA, 75 kV BIL, 0.55bG
RN2c-T1/16 RN2c-T2/16 RN2c-T3/16
13.8 kV, 21 kA, 95 kV BIL, 0.8bG
RN2c-T1/21 RN2c-T2/21 RN2c-T3/21
General arrangement drawing - transformer mounted RMINST-06 RMINST-06 RMINST-06
Page 103
Page 103 Page 103
General arrangement drawing - freestanding
RMINST-05 RMINST-05 RMINST-05
Page 157
Page 157
Page 157
Schematic diagram - TFL
RMSCH-01
Page 112
Schematic diagram - VIP 30
RMSCH-02
Page 113
Schematic diagram - VIP 35
Schematic diagram - VIP 300
Schematic diagram - Sepam 10

RMSCH-15
Page 115

RMSCH-03
Page 114

RMSCH-42
Page 120
RMSCH-43-46
Pages 116-119

RMSCH-43-46
Pages 116-119

Key: b Standard feature O Optional feature

22

AMTED399086EN

Non-extensible ring main units

Ring main units

Accessories

RN2c-T1 RN2c-T2 RN2c-T3 RN2c-T4 RN2c-T5 RN2c-T25 RN6c-T1 RN6c-T25 Kit no.
TFL
VIP 300
VIP 30
VIP 35
Glass TFL Sepam 10 VIP 300 Sepam 10

Cable kits
v
Circuit breaker cable box
Circuit breaker cable box with integral cable test facility v
O
Gland plate 1 x 3C
O
Gland plate 3 x 1C
O
Small gland plate 1 x 3C
O
Blank aluminium gland plate
O
Brass wiping gland 1 x 3C
O
Brass wiping gland 3 x 1C
O
Small brass wiping gland 1 x 3C
O
Tubular gland 1 x 3C
O
Tubular gland 3 x 1C
O
Small tubular gland
O
CES5 gland
O
CES5 gland plate 1 x 3C
O
CES5 gland adaptor
O
6 x ECON cable termination kit
O
3 x STD ECON end cap
O
3 x ECON cable termination kit
v
Top entry cables RH cable box (indoor only)
v
Top entry cables LH cable box (indoor only)
v
Rsw extension box for 2 x 3C cables (left hand)
v
Rsw extension box for 2 x 3C (right hand)
O
Angled gland plate 1 x 3C
O
Split gland plate 1 x 3C

v
v

v
v

v
v

v
v

v
v

O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
v
v
v
v
O
O

O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
v
v
v
v
O
O

O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
v
v
v
v
O
O

O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
v
v
v
v
O
O

v
O
O
O
O
O
O
v
O

v
O
O
O
O
O
O
v
O

v
O
O
O
O
O
O
v
O

b
b
b
b
Operating handle
v
v
v
v
LH ring switch control auxiliary sw for motorised
mechanism provision
v
v
v
v
LH ring switch termination block for motorised
mechanism provision (not Easergy)
v
v
v
v
RH ring switch control auxiliary sw for motorised
mechanism provision
v
v
v
v
RH ring switch termination block for motorised
mechanism provision (not Easergy)
v
v
v
v
Provision for motorised mechanism circuit breaker
v
v
v
v
Motorised mechanism - specify voltage
v
v
v
v
CB Termination block for motorised
mechanism provision (not Easergy)
v
v
v
v
Shunt trip coil (20-250 V DC, 110-250 V AC) TFL
v
v
v
v
Shunt trip coil (20-250 V DC, 110-250 V AC) VIP
v
v
v
v
Ring switch cable VPIS indication (3.3-13.8 kV)
v
v
v
v
Circuit breaker cable VPIS indication (11-13.8 kV)
v
v
v
v
Circuit breaker cable VPIS indication (3.3-7.2 kV)
O
O
O
O
Phase indication device
O
O
O
O
VAP 6 test unit for VIP 300/30/35
v
v
v
v
Emergency trip push button
v
v
v
v
Gas pressure switch for remote indication only
Key: b Standard feature v Factory fitted accessory O Loose accessory, assembled on site

RMR-A/F47
RMR-F325

O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
v
v
v
v
O
O

O
O
O
O

O
O
O
O

O
O
O
O
O
O
O
O
O
O
O
v
v
v
v
O
O

O
O
O
O
O
O
O
O
O
O
O
v
v
v
v
O
O

RMR-A316
RMR-A319
RMR-A322
RMR-A320
RMR-A10
RMR-A11
RMR-A105
RMR-A12
RMR-A13
RMR-A106
RMR-A120
RMR-A321
RMR-A525
RMR-A314
RMR-A370
RMR-A315
RMR-F303
RMR-F302
RMR-F523
RMR-F522
RMR-A317
RMR-A318

v
O
O
O
O
O
O
v
O

v
O
O
O
O
O
O
v
O

v
O
O
O
O
O
O
v
O

v
O
O
O
O
O
O
v
O

RMR-A/F323
RMR-A20
RMR-A343
RMR-A344
RMR-A22
RMR-A342
RMR-A17
RMR-A350
RMR-A201

b
v

b
v

b
v

b
v

RMR-F345
RMR-F328

RMR-F363

RMR-F329

RMR-F364

v
v
v

v
v
v

b
v
v

b
v
v

RMR-F543
RMR-F507
RMR-F365

v
v
v
v
v
O
O
v
v

v
v
v
v
v
O
O
v
v

v
v
v
v
v
O
O
v
v

v
v
v
v
v
O
O
v
v

RMR-F581
RMR-F582
RMR-F341
RMR-F340
RMR-F347
RMR-A374
RMR-A202
RMR-F339
RMR-F368

Installation items
Transformer mounting kit
Extension trunking (to clear transformer radiators)
Set of padlocks - 11 no
Anti-vandal fixings, including tool
Foundation bolts (not required for transformer mounting)
Multicore pilot glands
Time Fuse Link (set of 2 - specify rating as table page 156)
RN2c to MU2 installation kit
Ariel mounting bracket

v
O
O
O
O
O
O
v
O

Operational items

AMTED399086EN

23

Non-extensible ring main units

Ring main units

Accessories

RN2c-T1
TFL

RN2c-T2
VIP 300

RN2c-T3
VIP 30

RN2c-T4
VIP 35

RN2c-T5 RN2c-T25 RN6c-T1


Glass TFL Sepam 10 VIP 300

RN6c-T25 Kit no.


Sepam 10

v
v
v
v

v
v
v
v

v
v
v
v

v
v
v
v

v
v
v
v

v
v
v
v

v
v
v
v

v
v
v
v

RMR-F337
RMR-F338
RMR-F335
RMR-F336

O
O
O
O
O
O
O
O
O
O

O
O
O
O
O
O
O
O
O
O

O
O
O
O
O
O
O
O
O
O

O
O
O
O
O
O
O
O
O
O

O
O
O
O
O
O
O
O
O
O

O
O
O
O
O
O
O
O
O
O

RMR-F310
RMR-A304
RMR-A305
RMR-A308
RMR-A309
RMR-A422
RMR-A277
RMR-A278
RMR-A279
RMR-A57

Mechanical interlocks
Circuit breaker - key free, EARTH ON
Circuit breaker - key free, MAIN OFF
Switch - key free, SWITCH OFF LH
Switch - key free, SWITCH OFF RH
N. B. specify lock symbol at time of ordering
(3 digits max) not available with motor mechanisms

Earth fault passage indication (choose provision kit


and an EFPI required if not using Easergy T200E)
O
O
Phase & earth fault provision for Easergy T200E
O
O
EFPI provision kit, inside cable box
O
O
EFPI provision kit, CT outside cable box
O
O
EFPI provision kit, inside cable box, top entry
O
O
EFPI provision kit, outside cable box, top entry
O
O
Bowden RR EFPI and CT
O
O
Bowden STD EFPI type NB
O
O
Bowden LV reset EFPI type NB1
O
O
Bowden LV reset & alarm type NB2
O
O
Fundamentals ER FIND EFPI and CT
N. B. above CTs are ring type for split core please consult Schneider Electric
Key: v Factory fitted accessory O Loose accessory, assembled on site

24

AMTED399086EN

Ring main units

Non-extensible ring main unit


200 A
RN2c-T1

DE60180

Transformer protection up to 1.6 MVA at 11 kV


Protection & control - CB
Overcurrent and earth fault protection using CT operated trip coils with provision for
time fuse links
Protection CTs - 100/50/5 A class X
Transformer ratings
See table on Time Fuse Link - page 7
Documents
Transformer mounted installation drawing ref: RMINST-06
Freestanding installation drawing ref: RMINST-05
Schematic drawing ref: RMSCH-01

DE60181

Environment
Indoor/outdoor
IP54
Ratings
Busbars 630 A
Short time withstand 16/21 kA 3 s
Internal arc 16/21 kA 1 s IAC class AF, A-FLR available on gas enclosure only
Normal current rating 630 A/200 A
Normal rated voltage 12/13.8 kV
Normal rated BIL 75/95 kV
Operating mechanism
Independent manual
Standard features
Ring cable earth switch, 16/21 kA 3 s
Transformer earth switch, 16/21 kA 3 s
Anti-reflex operating handle
Provision for motorised mechanism LH/RH ring switch with plug interface
Indication
Mechanical tripped on fault flag indicator
Mechanical ON/OFF indicator
Mechanical earth/main indicator
Gas pressure indicator
CB auxiliary contacts 1NO 1NC
CB earth position selected 1NO
CB earth ON, 1NO
Test facility
Integral ring switch cable test facility
Cable
Bottom entry up to 1 x 3C 300 mm2
Bottom entry up to 3 x 1C 630 mm2
Accessories - see table, page 23
CB, LH, RH motor kits
LH, RH ring switch indication 1NO 1NC earth On 1NO
Multi voltage shunt trip coil 20-48 V DC - 110-250 V AC/DC
VPIS indication
Inverted cable boxes (indoor only)
Transformer mounting kit
Freestanding tee-off cable box
Order information
Code
RN2c-T1/16
RN2c-T1/21

AMTED399086EN

Rating
16 kA, 12 kV, 75 kV BIL
21 kA, 13.8 kV, 95 kV BIL

25

Ring main units

Non-extensible ring main unit


200 A
RN2c-T2

DE60180

Transformer protection up to 3.5 MVA at 11 kV


Protection & control - CB
Self powered IDMT overcurrent and earth fault relay, VIP 300. In accordance with
IEC 60255 and BS142
Protection CTs - 200/1 A class X
b Setting range:
v Overcurrent: 20-200 A
v Earth fault: 2-160 A
Transformer ratings
See table on Time Fuse Link - page 7

DE60185

Documents
Transformer mounted installation drawing ref: RMINST-06
Freestanding installation drawing ref: RMINST-05
Schematic drawing ref: RMSCH-03
Environment
Indoor/outdoor
IP54
Ratings
Busbars 630 A
Short time withstand 16/21 kA 3 s
Internal arc 16/21 kA 1 s IAC class AF, A-FLR available on gas enclosure only
Normal current rating 630 A/200 A
Normal rated voltage 12/13.8 kV
Normal rated BIL 75/95 kV
Operating mechanism
Independent manual
Standard features
Ring cable earth switch, 16/21 kA 3 s
Transformer earth switch, 16/21 kA 3 s
Anti-reflex operating handle
Provision for motorised mechanism LH/RH ring switch with plug interface
Indication
Mechanical tripped on fault flag indicator
Mechanical ON/OFF indicator
Mechanical earth/main indicator
Gas pressure indicator
CB auxiliary contacts 1NO 1NC
CB earth position selected 1NO
CB earth ON, 1NO
Test facility
Integral ring switch cable test facility
Cable
Bottom entry up to 1 x 3C 300 mm2
Bottom entry up to 3 x 1C 630 mm2
Accessories - see table, page 23
CB LH, RH motor kits
LH, RH ring switch indication 1NO 1NC earth On 1NO
Multi voltage shunt trip coil 20-48 V DC - 110-250 V AC/DC
VPIS indication
Inverted cable boxes (indoor only)
Transformer mounting kit
Freestanding tee-off cable box
Order information
Code
RN2c-T2/16
RN2c-T2/21

26

Rating
16 kA, 12 kV, 75 kV BIL
21 kA, 13.8 kV, 95 kV BIL

AMTED399086EN

Ring main units

Non-extensible ring main unit


200 A
RN2c-T3

DE60180

MV transformer protection
Protection & control - CB
Self powered overcurrent relay, VIP 30.
Protection CTs - 500/200/1 A class X
b Setting range: 500/1 A
v Overcurrent: 20-200 A
b Setting range: 200/1 A
v Overcurrent: 8-80 A
Transformer ratings
See table on Time Fuse Link - page 7

DE60182

Documents
Transformer mounted installation drawing ref: RMINST-06
Freestanding installation drawing ref: RMINST-05
Schematic drawing ref: RMSCH-02
Environment
Indoor/outdoor
IP54
Ratings
Busbars 630 A
Short time withstand 16/21 kA 3 s
Internal arc 16/21 kA 1 s IAC class AF, A-FLR available on gas enclosure only
Normal current rating 630 A/200 A
Normal rated voltage 12/13.8 kV
Normal rated BIL 75/95 kV
Operating mechanism
Independent manual
Standard features
Ring cable earth switch, 16/21 kA 3 s
Transformer earth switch, 16/21 kA 3 s
Anti-reflex operating handle
Provision for motorised mechanism LH/RH ring switch with plug interface
Indication
Mechanical tripped on fault flag indicator
Mechanical ON/OFF indicator
Mechanical earth/main indicator
Gas pressure indicator
CB auxiliary contacts 1NO 1NC
CB earth position selected 1NO
CB earth ON, 1NO
Test facility
Integral ring switch cable test facility
Cable
Bottom entry up to 1 x 3C 300 mm2
Bottom entry up to 3 x 1C 630 mm2
Accessories - see table, page 23
CB, LH, RH motor kit
LH, RH ring switch indication 1NO 1NC earth On 1NO
Multi voltage shunt trip coil 20-48 V DC - 110-250 V AC/DC
VPIS indication
Inverted cable box (indoor only)
Transformer mounting kit
Freestanding tee-off cable box
Order information
Code
RN2c-T3/16
RN2c-T3/21

AMTED399086EN

Rating
16 kA, 12 kV, 75 kV BIL
21 kA, 13.8 kV, 95 kV BIL

27

Ring main units

Non-extensible ring main unit


200 A
RN2c-T4

DE60180

MV transformer protection
Protection & control - CB
Self powered overcurrent and earth fault relay, VIP 35.
Protection CTs - 500/200/1 A class X
CH30 core balance CT
b Setting range: 500/1 A
v Overcurrent: 20-200 A
v Earth fault: 25-300 A
b Setting range: 200/1 A
v Overcurrent: 8-80 A
v Earth fault: 10-120 A
Transformer ratings
See table on Time Fuse Link - page 7

DE60183

Documents
Transformer mounted installation drawing ref: RMINST-06
Freestanding installation drawing ref: RMINST-05
Schematic drawing ref: RMSCH-15
Environment
Indoor/outdoor
IP54
Ratings
Busbars 630 A
Short time withstand 16/21 kA 3 s
Internal arc 16/21 kA 1 s IAC class AF, A-FLR available on gas enclosure only
Normal current rating 630 A/200 A
Normal rated voltage 12/13.8 kV
Normal rated BIL 75/95 kV
Operating mechanism
Independent manual
Standard features
Ring cable earth switch, 16/21 kA 3 s
Transformer earth switch, 16/21 kA 3 s
Anti-reflex operating handle
Provision for motorised mechanism LH/RH ring switch with plug interface
Indication
Mechanical tripped on fault flag indicator
Mechanical ON/OFF indicator
Mechanical earth/main indicator
Gas pressure indicator
CB auxiliary contacts 1NO 1NC
CB earth position selected 1NO
CB earth ON, 1NO
Test facility
Integral ring switch cable test facility
Cable
Bottom entry up to 1 x 3C 300 mm2
Bottom entry up to 3 x 1C 630 mm2
Accessories - see table, page 23
CB, LH, RH motor kits
LH, RH ring switch indication 1NO 1NC earth On 1NO
Multi voltage shunt trip coil 20-48 V DC - 110-250 V AC/DC
VPIS indication
Inverted cable boxes (indoor only)
Transformer mounting kit
Freestanding tee-off cable box
Order information
Code
RN2c-T4/16
RN2c-T4/21

28

Rating
16 kA, 12 kV, 75 kV BIL
21 kA, 13.8 kV, 95 kV BIL

AMTED399086EN

Ring main units

Non-extensible ring main unit


200 A
RN2c-T5

DE60180

Transformer protection up to 1.6 MVA at 11 kV


Protection & control - CB
Overcurrent and earth fault protection using CT operated trip coils with provision for
time fuse links (glass fuse link)
Protection CTs - 100/50/5 A class X
Transformer ratings
See table on Time Fuse Link - page 7
Documents
Transformer mounted installation drawing ref: RMINST-06
Freestanding installation drawing ref: RMINST-05
Schematic drawing ref: RMSCH-01

DE60184

Environment
Indoor/outdoor
IP54
Ratings
Busbars 630 A
Short time withstand 16/21 kA 3 s
Internal arc 16/21 kA 1 s IAC class AF, A-FLR available on gas enclosure only
Normal current rating 630 A/200 A
Normal rated voltage 12/13.8 kV
Normal rated BIL 75/95 kV
Operating mechanism
Independent manual
Standard features
Ring cable earth switch, 16/21 kA 3 s
Transformer earth switch, 16/21 kA 3 s
Anti-reflex operating handle
Provision for motorised mechanism LH/RH ring switch with plug interface
Indication
Mechanical tripped on fault flag indicator
Mechanical ON/OFF indicator
Mechanical earth/main indicator
Gas pressure indicator
CB auxiliary contacts 1NO 1NC
CB earth position selected 1NO
CB earth ON, 1NO
Test facility
Integral ring switch cable test facility
Cable
Bottom entry up to 1 x 3C 300 mm2
Bottom entry up to 3 x 1C 630 mm2
Accessories - see table, page 23
CB, LH, RH motor kits
LH, RH ring switch indication 1NO 1NC earth On 1NO
Multi voltage shunt trip coil 20-48 V DC - 110-250 V AC/DC
VPIS indication
Inverted cable boxes (indoor only)
Transformer mounting kit
Freestanding tee off cable box
Order information
Code
RN2c-T5/16
RN2c-T5/21

AMTED399086EN

Rating
16 kA, 12 kV, 75 kV BIL
21 kA, 13.8 kV, 95 kV BIL

29

Non-extensible ring main unit


200 A

Ring main units

RN2c-T25
DE60180

Transformer protection up to 3.5 MVA at 11 kV


Protection & control - CB
IDMT overcurrent, earth-fault and thermal overload relay,
Sepam series 10. In accordance with IEC 60255
Power supply 24-48 VDC required
Protection CTs - 200/100/1 A 5P20
Setting range (200/1):
overcurrent: 20 - 200 A, earth-fault: 2 - 480 A, sensitive earth-fault: 0.2 - 24 A
Setting range (100/1):
overcurrent: 10 - 200 A, earth-fault: 1 - 240 A, sensitive earth-fault: 0.2 - 24 A

DE59800

Documents (1)
Schematic drawing ref:
RN2c-T25B: RMSCH-43
RN2c-T25BS: RMSCH-44
RN2c-T25A: RMSCH-45
RN2c-T25AS: RMSCH-46
50/51
50N/51N
49RMS

Environment
Indoor/outdoor
IP54
Ratings
Busbar 630 A
Short time withstand 16/21 kA 3 s
Internal arc 16/21 kA 1 s IAC class AF, A-FLR available on gas enclosure only
Normal current rating 630 A/200 A
Normal rated voltage 12/13.8 kV
Normal rated BIL 75/95 kV
Operating mechanism
Independent manual

Sepam 10 functions

ANSI
code

RN2c-T25 (1)
B

BS A

Standard
0.012.4 In (2)

50N/51N b

Sensitive
0.224 A

50G/51G

AS

Protection
Earth-fault
protection

Phase-overcurrent protection
0.124 I (3)

50/51

Thermal overload protection

49RMS

Phase-overcurrent and
earth-fault cold load pick-up

Logic
Blocking send
68
discrimination Blocking reception

External tripping via digital input


Measurement
Earth-fault current

Phase currents

Peak demand currents

Standard features
Ring switch cable earth switch, 16/21 kA 3 s
Transformer earth switch, 16/21 kA 3 s
Anti-reflex operating handle
Provision for motorised mechanism LH/RH ring switch
Multi voltage shunt trip coil 20-48 V DC - 110-250 V AC/DC
Indication
Mechanical tripped on fault flag indication
Mechanical ON/OFF indication
Mechanical earth/main indication
Gas pressure indication
CB auxiliary contacts 1NO 1NC (3)
CB earth position selected 1NO
CB earth ON, 1NO
Test facility
Integral ring switch cable test facility
Cable
Bottom entry up to 1 x 3C 300 mm
Bottom entry up to 3 x 1C 630 mm

Circuit breaker tripping


and lockout

86

Tripping annunciation

30

Relay watchdog contact

Remote CB position monitoring

Accessories - see table, page 23


CB, LH, RH motor kit
RH and LH ring switch indication auxiliary contacts 1NO 1NC
Earth ON auxiliary contact 1NO
VPIS indication
Inverted cable box (indoor only)
Transformer mounting kit (4)
Freestanding tee-off cable box

Order information

Modbus

IEC 60870-5-103

Control and supervision

Tripped on fault, volt free contact

Record of last fault


Record of last five events

Communications

(1) B (basic), BS (basic + sensitive earth-fault), A (advanced),


AS (advanced + sensitive earth-fault)
(2) In = Primary CT ratio
(3) Only with T25B and T25BS
(4) BS + AS not available with transformer mounted units.

30

Code (1)
RN2c-T25B/21
RN2c-T25BS/21
RN2c-T25A/21
RN2c-T25AS/21

Rating
21 kA, 13.8 kV, 95 kV BIL
21 kA, 13.8 kV, 95 kV BIL
21 kA, 13.8 kV, 95 kV BIL
21 kA, 13.8 kV, 95 kV BIL

AMTED399086EN

Ring main units

Non-extensible ring main unit


630 A
RN6c-T1

DE60180

Network sectionalising up to 12 MVA 11 kV


Protection & control - CB
Self powered IDMT overcurrent and earth fault relay, VIP 300. In accordance with
IEC 60255 and BS142
Protection CTs - 800/400/1 A class X
b Setting range: 800/1 A ratio
v Overcurrent: 80-800 A
v Earth fault: 8-640 A
b Setting range: 400/1 A
v Overcurrent: 40-400 A
v Earth fault: 4-320 A

DE60186

Documents
Freestanding installation drawing ref: RMINST-05
Schematic drawing ref: RMSCH-42
Environment
Indoor/outdoor
IP54
Ratings
Busbars 630 A
Short time withstand 16/21 kA 3 s
Internal arc 16/21 kA 1 s IAC class AF, A-FLR available on gas enclosure only
Normal current rating 630 A/630 A
Normal rated voltage 12/13.8 kV
Normal rated BIL 75/95 kV
Operating mechanism
Independent manual
Standard features
Circuit breaker earth switch 16/21 kA
Ring cable earth switch, 16/21 kA 3 s
Anti-reflex operating handle
Provision for motorised mechanism LH/RH ring switch and circuit breaker with plug
interface
Indication
Mechanical tripped on fault flag indicator
Mechanical ON/OFF indicator
Mechanical earth/main indicator
Gas pressure indicator
CB auxiliary contacts 1NO 1NC
CB earth position selected 1NO
CB earth ON, 1NO
Test facility
Integral ring switch and circuit breaker test facility
Cable
Bottom entry up to 1 x 3C 300 mm2
Bottom entry up to 3 x 1C 630 mm2
Accessories - see table, page 23
CB, LH, RH motor kits
LH, RH ring switch indication 1NO 1NC earth On 1NO
Multi voltage shunt trip coil 20-48 V DC - 110-250 V AC/DC
VPIS indication
Inverted cable boxes (indoor only)
Freestanding
Order information
Code
RN6c-T1/16
RN6c-T1/21

AMTED399086EN

Rating
16 kA, 12 kV, 75 kV BIL
21 kA, 13.8 kV, 95 kV BIL

31

Non-extensible ring main unit


630 A

Ring main units

RN6c-T25
DE60180

Network sectionalising up to 12 MVA at 11 kV


Protection & control - CB
IDMT overcurrent, earth-fault and thermal overload relay,
Sepam series 10. In accordance with IEC 60255
Power supply 24-48 VDC required
Protection CTs - 800/400/1 A 5P20
Setting range (800/1):
overcurrent: 80 - 630 A, earth-fault: 8 - 1920 A, sensitive earth-fault: 0.2 - 24 A
Setting range (400/1):
overcurrent: 40 - 630 A, earth-fault: 4 - 960 A, sensitive earth-fault: 0.2 - 24 A

DE59800

Documents (1)
Schematic drawing ref:
RN6c-T25B: RMSCH-43
RN6c-T25BS: RMSCH-44
RN6c-T25A: RMSCH-45
RN6c-T25AS: RMSCH-46
50/51
50N/51N
49RMS

Environment
Indoor/outdoor
IP54
Ratings
Busbar 630 A
Short time withstand 16/21 kA 3 s
Internal arc 16/21 kA 1 s IAC class AF, A-FLR available on gas enclosure only
Normal current rating 630 A
Normal rated voltage 12/13.8 kV
Normal rated BIL 75/95 kV
Operating mechanism
Independent manual

Sepam 10 functions

ANSI
code

RN6c-T25 (1)
B

BS A

Standard
0.012.4 In (2)

50N/51N b

Sensitive
0.224 A

50G/51G

AS

Protection
Earth-fault
protection

Phase-overcurrent protection
0.124 In (2)

50/51

Thermal overload protection

49RMS

Phase-overcurrent and
earth-fault cold load pick-up

Logic
Blocking send
68
discrimination Blocking reception

External tripping via digital input


Measurement
Earth-fault current

Phase currents

Peak demand currents

Standard features
Ring switch cable earth switch, 16/21 kA 3 s
Transformer earth switch, 16/21 kA 3 s
Anti-reflex operating handle
Provision for motorised mechanism LH/RH ring switch
Multi voltage shunt trip coil 20-48 V DC - 110-250 V AC/DC
Indication
Mechanical tripped on fault flag indication
Mechanical ON/OFF indication
Mechanical earth/main indication
Gas pressure indication
CB auxiliary contacts 1NO 1NC (3)
CB earth position selected 1NO
CB earth ON, 1NO
Test facility
Integral ring switch cable test facility
Cable
Bottom entry up to 1 x 3C 300 mm
Bottom entry up to 3 x 1C 630 mm

Circuit breaker tripping


and lockout

86

Tripping annunciation

30

Relay watchdog contact

Remote CB position monitoring

Accessories - see table, page 23


CB, LH, RH motor kit
RH and LH ring switch indication auxiliary contacts 1NO 1NC
Earth ON auxiliary contact 1NO
VPIS indication
Inverted cable box (indoor only)
Transformer mounting kit (4)
Freestanding tee-off cable box

Order information

Modbus

IEC 60870-5-103

Control and supervision

Tripped on fault, volt free contact

Record of last fault


Record of last five events

Communications

(1) B (basic), BS (basic + sensitive earth-fault), A (advanced),


AS (advanced + sensitive earth-fault)
(2) In = Primary CT ratio
(3) Only with T25B and T25BS
(4) BS + AS not available with transformer mounted units.

32

Code (1)
RN6c-T25B/21
RN6c-T25BS/21
RN6c-T25A/21
RN6c-T25AS/21

Rating
21 kA, 13.8 kV, 95 kV BIL
21 kA, 13.8 kV, 95 kV BIL
21 kA, 13.8 kV, 95 kV BIL
21 kA, 13.8 kV, 95 kV BIL

AMTED399086EN

Ring main units

Extensible ring main units


Specification

RE2c-T1
TFL

RE2c-T2
VIP 300

RE2c-T3
VIP 30

RE2c-T4
VIP 35

RE2c-T25
Sepam 10

b
b
b
b
O

b
b
b
b
O

b
b
b
b
O

b
b
b
b
O

b
b
b
b
O

b
b

b
b

b
b

b
b

b
b

b
b
O
b
O
b
O

b
b
O
b
O
b
O

b
b
O
b
O
b
O

b
b
O
b
O
b
O

b
b
O
b
O
b
O

b
b
b
O

b
b
b
O

b
b
b
O

b
b
b
O

b
b
b
O

Environment
Indoor / outdoor
IP54
Transformer mounted
Freestanding
Extensible (RHS)

Ratings
Busbars 630 A
Circuit breaker normal rated current 200 A
Circuit breaker normal rated current 630 A
Switch normal rated current 630 A
12 kV 16 kA 3 seconds 75 kV BIL
13.8 kV 21 kA 3 seconds 95 kV BIL
Ring switch cable earth switch 16 kA 3 seconds
Ring switch cable earth switch 21 kA 3 seconds
Circuit breaker earth switch 3.15 kA
Extensible rmu busbar chamber 630 A

Mechanism
Independent manual
Provision for motorised mechanism LH ring switch
Provision for motorised mechanism RH ring switch
Provision for motorised mechanism circuit breaker

Protection & control - circuit breaker


CTs dual ratio - 100/50/5 A class X
CTs ratio - 200/1 A class X
CTs dual ratio 200/100/1 A 5P20
CTs ratio - 500/200/1 A class X
Overcurrent & earth fault CT operated trip coils - TFL
Overcurrent relay - VIP 30
Overcurrent & earth fault relay - VIP 35
IDMT overcurrent & earth fault relay - VIP 300
IDMT relay Sepam 10
Multi voltage shunt trip coil (see accessories)

b
b
b
b
b
b
b
O

b
b

b
b
O
b
O

b
b
O
b
O

b
b
O
b
O

b
b
O
b
O

b
b
O
b
O

b
b
O

b
b
O

b
b
O

b
b
O

b
b
O

12 kV, 16 kA, 75 kV BIL, 0.35bG

RE2c-T1/16

RE2c-T2/16

RE2c-T3/16

RE2c-T4/16

13.8 kV, 21 kA, 95 kV BIL, 0.8bG


General arrangement drawing - freestanding

RE2c-T1/21
RMINST-22
Page 102
RMSCH-01
Page 112

RE2c-T2/21
RMINST-22
Page 102

RE2c-T3/21
RMINST-22
Page 102

RE2c-T4/21
RMINST-22
Page

Indication
Mechanical ON/OFF
Mechanical EARTH/MAIN
VPIS indication 3.3 - 13.8 kV
Gas pressure indicator (-25C to +55C)
RSW aux contacts 1NO & 1NC

Test facility
Integral ring cable test facility

Standard features
Operating handle

Cable (see available cable kit accessories)


Bottom entry up 1 x 3C 300 mm2
Bottom entry up 3 x 1C 630 mm2
Top entry cables (indoor only) (left hand side only)

Order codes

Schematic diagram - TFL


Schematic diagram - VIP 30

RMSCH-02
Page 113

Schematic diagram - VIP 35


Schematic diagram - VIP 300
Schematic diagram Sepam 10

RE2c-T25/21
RMINST-22
Page 102

RMSCH-15
Page 115
RMSCH-03
Page 114
RMSCH-43-46
Pages 116-119

Key: b Standard feature O Optional feature

AMTED399086EN

33

Ring main units

Extensible ring main units


Accessories

RE2c-T1
TFL

RE2c-T2
VIP 300

RE2c-T3
VIP 30

RE2c-T4
VIP 35

RE2c-T25
Sepam 10

Kit no.

v
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
v
O
O

v
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
v
O
O

v
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
v
O
O

v
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
v
O
O

v
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
v
O
O

RMR-A/F47
RMR-A316
RMR-A319
RMR-A322
RMR-A320
RMR-A10
RMR-A10
RMR-A105
RMR-A12
RMR-A13
RMR-A106
RMR-A120
RMR-A321
RMR-A525
RMR-A314
RMR-A370
RMR-A315
RMR-A371
RMR-F302
RMR-A317
RMR-A318

v
O
O
O
O
O
O
v
O
O

v
O
O
O
O
O
O
v
O
O

v
O
O
O
O
O
O
v
O
O

v
O
O
O
O
O
O
v
O
O

v
O
O
O
O
O
O
v
O
O

RMR-A/F323
RMR-A20
RMR-A343
RMR-A344
RMR-A22
RMR-A342
RMR-A17
RMR-A350
RMR-F369
RMR-A201

b
v

b
v

b
v

RMR-F345
RMR-F328

RMR-F363

RMR-F329

RMR-F364

v
v
v
v
v
v
v
v
v
v

v
v
v
v
v
v
v
v
v
v

v
v
v
v
v
v
v
v
v
v

RMR-F543
RMR-F507
RMR-F581
RMR-F582
RMR-F341
RMR-F340
RMR-F347
RMR-A202
RMR-F339
RMR-F368

Cable kits
Extensible ring main units
Gland plate 1 x 3C
Gland plate 3 x 1C
Small gland plate 1 x 3C
Blank aluminium gland plate
Brass wiping gland 1 x 3C
Brass wiping gland 3 x 1C
Small brass wiping gland 1 x 3C
Tubular gland 1 x 3C
Tubular gland 3 x 1C
Small tubular gland 1 x 3C
CES5 gland
CES5 gland plate 1 x 3C
CES5 gland plate adaptor
6 x ECON cable termination kit
3 x STD ECON end cap
3 x ECON cable termination kit
3 x ECON end cap capacitors
Top entry cables LH cable box (indoor only)
Angled gland plate 1 x 3C
Split gland plate 1 x 3C

Installation items
Transformer mounting kit
Extension trunking (to clear radiators)
Set of padlocks - 11 no
Anti-vandal fixings, including tool
Foundation bolts (not required for transformer mounting)
Multicore pilot glands
Time Fuse Link (set of 2 - specify rating as table page 156)
RE2c to MU2 installation kit
Extensible busbar chamber 630 A
Ariel mounting bracket

Operational items
b
b
Operating handle
v
v
LH ring switch control auxiliary sw for motorised mechanism
provision
v
v
LH ring switch termination block for motorised mechanism
provision (not Easergy)
v
v
RH ring switch control auxiliary sw for motorised mechanism
provision
v
v
RH ring switch termination block for motorised mechanism
provision (not Easergy)
v
v
Provision for motorised mechanism circuit breaker
v
v
Motorised mechanism - specify voltage
v
v
Shunt trip coil (20-250 V DC, 110-250 V AC) TFL
v
v
Shunt trip coil (20-250 V DC, 110-250 V AC) VIP
v
v
Ring switch cable VPIS indication (3.3-13.8 kV)
v
v
Circuit breaker VPIS indication (11-13.8 kV)
v
v
Circuit breaker VPIS indication (3.3-7.2 kV)
v
v
VAP 6 test unit for VIP 300/30/35
v
v
Emergency trip push button
v
v
Gas pressure switch for remote indication only
Key: b Standard feature v Factory fitted accessory O Loose accessory, assembled on site

34

AMTED399086EN

Ring main units

Extensible ring main units


Accessories

RE2c-T1
TFL

RE2c-T2
VIP 300

RE2c-T3
VIP 30

RE2c-T4
VIP 35

RE2c-T25
Sepam 10

Kit no.

v
v
v
v

v
v
v
v

v
v
v
v

v
v
v
v

v
v
v
v

RMR-F337
RMR-F338
RMR-F335
RMR-F336

O
O
O
O
O
O
O
O
O
O

O
O
O
O
O
O
O
O
O
O

O
O
O
O
O
O
O
O
O
O

O
O
O
O
O
O
O
O
O
O

RMR-F310
RMR-A304
RMR-A305
RMR-A308
RMR-A309
RMR-A422
RMR-A277
RMR-A278
RMR-A279
RMR-A57

Mechanical interlocks
Circuit breaker - key free, earth on
Circuit breaker - key free, main off
Switch - key free, switch off LH
Switch - key free, switch off RH
N. B. specify lock symbol at time of ordering (3 digits max) not
available with motor mechanisms

Earth fault passage indication (choose provision kit


and an EFPI required if not using Easergy T200E)
O
Phase & earth fault provision for Easergy T200E
O
EFPI provision kit, inside cable box
O
EFPI provision kit, CT outside cable box
O
EFPI provision kit, inside cable box, top entry
O
EFPI provision kit, outside cable box, top entry
O
Bowden RR EFPI and CT
O
Bowden STD EFPI type NB
O
Bowden LV reset EFPI type NB1
O
Bowden LV reset & alarm type NB
O
Fundamentals ER FIND EFPI and CT
N. B. above CTs are ring type for split core - please consult
Schneider Electric
Key: v Factory fitted accessory O Loose accessory, assembled on site

AMTED399086EN

35

Ring main units

Extensible ring main unit 200 A


RE2c-T1

DE60211

Multiple transformer feeders or network switching points


Protection & control - CB
Overcurrent and earth fault protection using CT operated trip coils with provision for
time fuse links.
Protection CTs - 100/50/5 A class X
Transformer ratings
See table on Time Fuse Link - page 7
Documents
Freestanding installation drawing ref: RMINST-22
Schematic drawing ref: RMSCH-01
Environment
Indoor/outdoor
IP54

DE60187

Ratings
Busbars 630 A
Short time withstand 16/21 kA 3 s
Internal arc 16/21 kA 1 s IAC class AF, A-FLR available on gas enclosure only
Normal current rating 630 A/200 A
Normal rated voltage 12/13.8 kV
Normal rated BIL 75/95 kV
Operating mechanism
Independent manual
Standard features
Ring switch cable earth switch, 16/21 kA 3 s
Transformer earth switch, 16/21 kA 3 s
Anti-reflex operating handle
Extensible (RHS)
Extensible (LHS and RHS)
Provision for motorised mechanism LH/RH ring switch with plug interface
Indication
Mechanical tripped on fault flag indicator
Mechanical ON/OFF indicator
Mechanical earth/main indicator
Gas pressure indicator
CB auxiliary contacts 1NO 1NC
CB earth position selected 1NO
CB earth ON, 1NO
Test facility
Integral ring switch test facility
Cable
Bottom entry up to 1 x 3C 300 mm2
Bottom entry up to 3 x 1C 630 mm2
Accessories - see table, page 34
CB, LH, RH motor kits
LH, RH ring switch indication 1NO 1NC earth On 1NO
Multi voltage shunt trip coil 20-48 V DC - 110-250 V AC/DC
VPIS indication
Integral circuit breaker test facility
Inverted cable boxes LH, CB (indoor only)
Transformer mounting kit
Freestanding tee-off cable box
Order information
Code
RE2c-T1/16
RE2c-T1/21

36

Rating
16 kA, 12 kV, 75 kV BIL
21 kA, 13.8 kV, 95 kV BIL

AMTED399086EN

Ring main units

Extensible ring main unit 200 A


RE2c-T2

DE60211

Multiple transformer feeders or network switching points


Protection & control - CB
Self powered IDMT overcurrent and earth fault relay, VIP 300. In accordance with
IEC 60255 and BS 142.
Protection CTs - 200/1 A class X
b Setting range:
v Overcurrent: 20-200 A
v Earth fault: 2-160 A
Transformer ratings
See table on Time Fuse Link - page 7
Documents
Installation drawing ref: RMINST-22
Schematic drawing ref: RMSCH-03

DE60188

Environment
Indoor/outdoor
IP54
Ratings
Busbars 630 A
Short time withstand 16/21 kA 3 s
Internal arc 16/21 kA 1 s IAC class AF, A-FLR available on gas enclosure only
Normal current rating 630 A/200 A
Normal rated voltage 12/13.8 kV
Normal rated BIL 75/95 kV
Operating mechanism
Independent manual
Standard features
Ring switch cable earth switch, 16/21 kA 3 s
Transformer earth switch, 16/21 kA 3 s
Anti-reflex operating handle
Extensible (RHS)
Provision for motorised mechanism LH/RH ring switch
Indication
Mechanical tripped on fault flag indicator
Mechanical ON/OFF indicator
Mechanical earth/main indicator
Gas pressure indicator
CB auxiliary contacts 1NO 1NC
CB earth position selected 1NO
CB earth ON, 1NO
Test facility
Integral ring switch test facility
Cable
Bottom entry up to 1 x 3C 300 mm2
Bottom entry up to 3 x 1C 630 mm2
Accessories - see table, page 34
CB, LH, RH motor kits
LH, RH ring switch indication 1NO 1NC
Multi voltage shunt trip coil 20-48 V DC - 110-250 V AC/DC
VPIS indication
Inverted cable box LH CB (indoor only)
Transformer mounting kit
Freestanding tee-off cable box
Order information
Code
RE2c-T2/16
RE2c-T2/21

AMTED399086EN

Rating
16 kA, 12 kV, 75 kV BIL
21 kA, 13.8 kV, 95 kV BIL

37

Ring main units

Extensible ring main unit 200 A


RE2c-T3

DE60211

MV transformer protection
Protection & control - CB
Self powered overcurrent relay, VIP 30.
Protection CTs - 500/200/1 A class X
b Setting range: 500/1 A
v Overcurrent: 20-200 A
b Setting range: 200/1 A
v Overcurrent: 8-80 A
Transformer ratings
See table on Time Fuse Link - page 7
Documents
Installation drawing ref: RMINST-22
Schematic drawing ref: RMSCH-02

DE60189

Environment
Indoor/outdoor
IP54
Ratings
Busbars 630 A
Short time withstand 16/21 kA 3 s
Internal arc 16/21 kA 1 s IAC class AF, A-FLR available on gas enclosure only
Normal current rating 630 A/200 A
Normal rated voltage 12/13.8 kV
Normal rated BIL 75/95 kV
Operating mechanism
Independent manual
Standard features
Ring switch cable earth switch, 16/21 kA 3 s
Transformer earth switch, 16/21 kA 3 s
Anti-reflex operating handle
Extensible (RHS)
Provision for motorised mechanism LH/RH ring switch
Indication
Mechanical tripped on fault flag indicator
Mechanical ON/OFF indicator
Mechanical earth/main indicator
Gas pressure indicator
CB auxiliary contacts 1NO 1NC
CB earth position selected 1NO
CB earth ON, 1NO
Test facility
Integral ring switch test facility
Cable
Bottom entry up to 1 x 3C 300 mm2
Bottom entry up to 3 x 1C 630 mm2
Accessories - see table, page 34
CB, LH, RH motor kit
LH, RH ring switch indication 1NO 1NC
Multi voltage shunt trip coil 20-48 V DC - 110-250 V AC/DC
VPIS indication
Inverted cable boxes LH, CB (indoor only)
Transformer mounting kit
Freestanding tee-off cable box
Order information
Code
RE2c-T3/16
RE2c-T3/21

38

Rating
16 kA, 12 kV, 75 kV BIL
21 kA, 13.8 kV, 95 kV BIL

AMTED399086EN

Ring main units

Extensible ring main unit 200 A


RE2c-T4

DE60211

MV transformer protection
Protection & control - CB
Protection & control - CB
Self powered overcurrent and earth fault relay, VIP 35.
Protection CTs - 500/200/1 A class with CH30 core balance CT
b Setting range: 500/1 A
v Overcurrent: 20-200 A
v Earth fault 25-300 A
b Setting range: 200/1 A
v Overcurrent: 8-80 A
v Earth fault 10-120 A
Transformer ratings
See table on Time Fuse Link - page 7

DE60190

Documents
Installation drawing ref: RMINST-22
Schematic drawing ref: RMSCH-15
Environment
Indoor/outdoor
IP54
Ratings
Busbars 630 A
Short time withstand 16/21 kA 3 s
Internal arc 16/21 kA 1 s IAC class AF, A-FLR available on gas enclosure only
Normal current rating 630 A/200 A
Normal rated voltage 12/13.8 kV
Normal rated BIL 75/95 kV
Operating mechanism
Independent manual
Standard features
Ring switch cable earth switch, 16/21 kA 3 s
Transformer earth switch, 16/21 kA 3 s
Anti-reflex operating handle
Extensible (RHS)
Provision for motorised mechanism LH/RH ring switch
Indication
Mechanical tripped on fault indicator
Mechanical ON/OFF indicator
Mechanical earth/main indicator
Gas pressure indicator
CB auxiliary contacts 1NO 1NC
Earth position selected 1NO
Earth ON, 1NO
Test facility
Integral ring switch test facility
Cable
Bottom entry up to 1 x 3C 300 mm2
Bottom entry up to 3 x 1C 630 mm2
Accessories - see table page 34
CB, LH, RH motor kit
LH, RH ring switch indication 1NO 1NC
Multi voltage shunt trip coil 20-48 V DC - 110-250 V AC/DC
VPIS indication
Inverted cable boxes LH, CB (indoor only)
Transformer mounting
Freestanding tee-off cable box
Order information
Code
RE2c-T4/16
RE2c-T4/21

AMTED399086EN

Rating
16 kA, 12 kV, 75 kV BIL
21 kA, 13.8 kV, 95 kV BIL

39

Extensible ring main unit 200 A

Ring main units

RE2c-T25

DE60211

MV transformer protection
Protection & control - CB
IDMT overcurrent, earth-fault and thermal overload relay,
Sepam series 10. In accordance with IEC 60255
Power supply 24-48 VDC required
Protection CTs - 200/100/1 A 5P20
Setting range (200/1):
overcurrent: 20 - 200 A, earth-fault: 2 - 480 A, sensitive earth-fault: 0.2 - 24 A
Setting range (100/1):
overcurrent: 40 - 200 A, earth-fault: 1 - 240 A, sensitive earth-fault: 0.2 - 24 A

DE59801

Documents (1)
Schematic drawing ref:
RN2c-T25B: RMSCH-43
RN2c-T25BS: RMSCH-44
RN2c-T25A: RMSCH-45
RN2c-T25AS: RMSCH-46
50/51
50N/51N
49RMS

Environment
Indoor/outdoor
IP54

50/51
50N/51N
49RMS

Ratings
Busbar 630 A
Short time withstand 16/21 kA 3 s
Internal arc 16/21 kA 1 s IAC class AF, A-FLR available on gas enclosure only
Normal current rating 630 A/200 A
Normal rated voltage 12/13.8 kV
Normal rated BIL 75/95 kV
Operating mechanism
Independent manual
Sepam 10 functions

ANSI
code

RE2c-T25 (1)
B

BS A

Standard
0.012.4 In (2)

50N/51N b

Sensitive
0.224 A

50G/51G

AS

Protection
Earth-fault
protection

Phase-overcurrent protection
0.124 In (2)

50/51

Thermal overload protection

49RMS

Phase-overcurrent and
earth-fault cold load pick-up

Logic
Blocking send
68
discrimination Blocking reception

External tripping via digital input


Measurement
Earth-fault current

Phase currents

Peak demand currents

Control and supervision

Standard features
Ring switch cable earth switch, 16/21 kA 3 s
Transformer earth switch, 16/21 kA 3 s
Anti-reflex operating handle
Extensible RHS
Provision for motorised mechanism LH/RH ring switch
Multi voltage shunt trip coil 20-48 V DC - 110-250 V AC/DC
Indication
Mechanical tripped on fault flag indication
Mechanical ON/OFF indication
Mechanical earth/main indication
Gas pressure indication
CB auxiliary contacts 1NO 1NC (3)
CB earth position selected 1NO
CB earth ON, 1NO
Test facility
Integral ring switch cable test facility
Cable
Bottom entry up to 1 x 3C 300 mm
Bottom entry up to 3 x 1C 630 mm

Circuit breaker tripping


and lockout

86

Tripping annunciation

30

Relay watchdog contact

Remote CB position monitoring

Accessories - see table, page 34


CB, LH, RH motor kit
RH and LH ring switch indication auxiliary contacts 1NO 1NC
Earth ON auxiliary contact 1NO
VPIS indication
Inverted cable box (indoor only)
Transformer mounting kit (4)
Freestanding tee-off cable box

Order information

Modbus

IEC 60870-5-103

Tripped on fault, volt free contact

Record of last fault


Record of last five events

Communications

(1) B (basic), BS (basic + sensitive earth-fault), A (advanced),


AS (advanced + sensitive earth-fault)
(2) In = Primary CT ratio
(3) Only with T25B and T25BS
(4) BS + AS not available with transformer mounted units.

40

Code (1)
RN2c-T25B/21
RN2c-T25BS/21
RN2c-T25A/21
RN2c-T25AS/21

Rating
21 kA, 13.8 kV, 95 kV BIL
21 kA, 13.8 kV, 95 kV BIL
21 kA, 13.8 kV, 95 kV BIL
21 kA, 13.8 kV, 95 kV BIL

AMTED399086EN

Ring main units

Double Extensible ring main unit


200 A or 630 A
RDE2c, RDE6c

DE60211-B

MV transformer protection
All options available including :
b Time Fuse Link (TFL)
b VIP protection relays
b Sepam series 10 protection relay
Environment
Indoor/outdoor
IP54
Ratings
Busbar 630 A
Short time withstand 16/21 kA 3 s
Internal arc 16/21 kA 1 s IAC class AF, A-FLR available on gas enclosure only
Normal current rating 630 A/200 A
Normal rated voltage 12/13.8 kV
Normal rated BIL 75/95 kV
Operating mechanism
Independent manual
Standard features
Ring switch cable earth switch, 16/21 kA 3 s
Transformer earth switch, 16/21 kA 3 s
Anti-reflex operating handle
Both side extensible ie. on RHS and LHS
Provision for motorised mechanism LH/RH ring switch
Multi voltage shunt trip coil 20-48 V DC - 110-250 V AC/DC
Indication
Mechanical tripped on fault flag indication
Mechanical ON/OFF indication
Mechanical earth/main indication
Gas pressure indication
CB auxiliary contacts 1NO 1NC (3)
CB earth position selected 1NO
CB earth ON, 1NO
Test facility
Integral ring switch cable test facility
Cable
Bottom entry up to 1 x 3C 300 mm
Bottom entry up to 3 x 1C 630 mm
Accessories - see table, page 34
CB, LH, RH motor kit
RH and LH ring switch indication auxiliary contacts 1NO 1NC
Earth ON auxiliary contact 1NO
VPIS indication
Inverted cable box (indoor only)
Transformer mounting kit
Freestanding tee-off cable box
Order information (Please consult us)

AMTED399086EN

41

42

AMTED399086EN

Circuit breaker, metering


and switches

Contents

Non-extensible circuit breakers 200 A


Specification - Accessories
CN2-T1, CN2-T6, CN2-T25

44
46

Non-extensible switches 630 A


Specification - Accessories
SN6-S1, SN6-S2

49
51

Non-extensible metering units 200 A


Specification - Accessories
MU2-M1, MU2-M2, MU2-M3

53
55

Non-extensible metering units 630 A


Specification - Accessories
MU6-N**

58
60

Extensible circuit breakers 200 A


Specification - Accessories
CE2-T2, CE2-T7, CE2-T*, CE2-T12, CE2-T**,
CE2-T13, CE2-T15, CE2-T16, CE2-T25

61
64
69

Extensible circuit breakers 630 A


Specification - Accessories
CE6-T4, CE6-T*, CE6-T8, CE6-T25, CE6-T**

73
75

Extensible switches 630 A


Specification - Accessories
SE6-S1, SE6-S2, SE6-E1

80
82

Extensible bus-section 630 A


Specification - Accessories
SE6-B1, CE6-B3, CE6-B5

AMTED399086EN

85
87

43

Circuit breaker, metering


and switches

Non-extensible circuit breakers


200 A
Specification
CN2-T1
VIP 300

CN2-T6
TFL

CN2-T25
Sepam 10

b
b

b
b

b
b

b
b
O
b
O
b

b
b
O
b
O
b

b
b
O
b
O
b

b
O

b
O

b
b

b
b

b
b
b

b
b
O
b
b

b
b
O
b
b

b
b
O
b
b

b
b

b
b

b
b

b
b

b
b

b
b

Environment
Indoor / outdoor
IP54

Ratings
Normal rated current 200 A
12 kV 16 kA 3 seconds 75 kV BIL
13.8 kV 21 kA 3 seconds 95 kV BIL
Cable earth switch 16 kA 3 seconds
Cable earth switch 21 kA 3 seconds
Transformer earth switch 3.15 kA 3 seconds

Mechanism
Independent manual

Protection & control - circuit breaker


CTs dual ratio - 100/50/5 A class X
CTs ratio - 200/1 A class X
CTs dual ratio 200/100/1 A 5P20
Overcurrent & earth fault CT operated trip coils
Time fuse Link
IDMT overcurrent & earth fault relay - VIP 300
IDMT overcurrent and earth fault relay Sepam 10
20 V-250 shunt trip coil
Circuit breaker auxiliary switch 1NO 2NC

b
b

Indication
Mechanical ON/OFF
Mechanical EARTH/MAIN
VPIS indication (6.6 - 13.8 kV)
Auxiliary switch contacts 1NO 2NC
Gas pressure indicator

Test facility
Integral cable test facility

Standard features
Operating handle
Transformer earth switch 3.15 kA 3 seconds

Cable (see available cable kit accessories)


Bottom entry up 300 mm2 1 x 3C
Bottom entry up 630 mm2 3 x 1C
Key: b Standard feature O Optional feature

44

AMTED399086EN

Circuit breaker, metering


and switches

Non-extensible circuit breakers


200 A
Accessories
CN2-T1
VIP 300

CN2-T6
TFL

CN2-T25
Sepam 10

Kit no.

v
O
O
O
O
O
O
O
O
O

v
O
O
O
O
O
O
O
O
O

v
O
O
O
O
O
O
O
O
O

RMR-F47
RMR-A48
RMR-A49
RMR-A50 Blank
RMR-A52
RMR-A10
RMR-A11
RMR-A12
RMR-A13
RMR-A132

O
O
O
O

O
O
O
O
O

O
O
O
O
O

RMR-A18/6
RMR-A19
RMR-A22
RMR-A16
RMR-A17

b
v
O
O
O

b
v
O
O

b
v
O
O

RMR-A23
RMR-F108
RMR-A24
RMR-A81
RMR-A202

v
v
v

v
v
v

v
v
v

RMR-F85
RMR-F86
RMR-F110

CN2-T1/16
CN2-T1/21
RMINST-04 Page 101
RMINST-09 Page 158
RMSCH-26 Page 127

CN2-T6/16
CN2-T6/21
RMINST-04 Page 101
RMINST-09 Page 158
RMSCH-11 Page 126

Cable kits
Tee-off cable box
Gland plate 1 x 3C
Gland plate 3 x 1C
Angled gland plates (RMR)
Blank aluminium gland plate
Brass wiping gland 1 x 3C
Brass wiping gland 3 x 1C
Tubular gland 1 x 3C
Tubular gland 3 x 1C
CES5 gland plate 1 x 3C

Installation items
Set of padlocks - 6 no
Anti-vandal fixings, including tool
Foundation bolts (not required for transformer mounting)
Multicore pilot glands
Time Fuse Link (set of 2 - specify rating as table page 156)

Operational items
Operating handle
VPIS indication (6.6-13.8 kV)
Neon lamp test unit (including lamp)
Neon lamp
VAP 6 test unit for VIP 300

Mechanical interlocks
Key free, earth on
Key free, unit off
Transformer earth switch, key free, earth on
N. B. specify lock symbol at time of ordering (3 digits max) not
available with motor mechanisms

Order codes
12 kV, 16 kA, 75 kV BIL, 0.35bG
13.8 kV, 21 kA, 95 kV BIL, 0.55bG
General arrangement drawing - transformer mounted
General arrangement drawing - freestanding
Schematic diagram

CN2-T25/21
RMINST-04 Page 101
RMINST-09 Page 158
RMSCH-47 to 50
Page 122 to 125

Key: b Standard feature v Factory fitted accessory O Loose accessory, assembled on site

AMTED399086EN

45

Circuit breaker, metering


and switches

Non-extensible circuit breaker


200 A
CN2-T1

DE60250

Transformer protection up to 3.5 MVA


Protection & control - CB
Self powered IDMT overcurrent and earth fault relay, VIP 300. In accordance with
IEC 60255 and BS142
Protection CTs - 200/1 A class X
b Setting range:
v Overcurrent: 20-200 A
v Earth fault: 2-160 A
Shunt trip coil, 20 V DC-250 V AC
Transformer ratings
See table on Time Fuse Link - page 7
Documents
Transformer mounted installation drawing ref: RMINST-04
Installation drawing for freestanding unit with tee-off cable box ref: RMINST-09
Schematic drawing ref: RMSCH-26
Environment
Indoor/outdoor
IP54
Ratings
Busbars 630 A
Short time withstand 16/21 kA 3 s
Internal arc 16/21 kA 1 s IAC class AF, A-FLR available on gas enclosure only
Normal current rating 200 A
Normal rated voltage 12/13.8 kV
Normal rated BIL 75/95 kV
Operating mechanism
Independent manual
Standard features
Tee-off earth switch, 3.15 kA 3 s
Cable earth switch, 16/21 kA 3 s
Anti-reflex operating handle
Indication
Mechanical tripped on fault indicator
Mechanical ON/OFF indicator
Mechanical earth/main indicator
Gas pressure indicator
CB auxiliary contacts 1NO 2 NC
Test facility
Integral cable test facilities
Cable
Bottom entry up to 300 mm2 1 x 3C
Bottom entry up to 630 mm2 3 x 1C
Accessories
Tee-off cable box
Glands and plates
Interlocks
See page 45 for details
Order information
Code
CN2-T1/16
CN2-T1/21

46

Rating
16 kA, 12 kV, 75 kV BIL
21 kA, 13.8 kV, 95 kV BIL

AMTED399086EN

Circuit breaker, metering


and switches

Non-extensible circuit breaker


200 A
CN2-T6

DE60192

Transformer protection up to 1.5 MVA


Protection & control - CB
Overcurrent and earth fault protection using CT operated trip coils with provision for
time fuse links.
Protection CTs - 100/50/5 A class X
Shunt trip coil, 20 V DC-250 V AC
Transformer ratings
See table on Time Fuse Link - page 7
Documents
Transformer mounted installation drawing ref: RMINST-04
Installation drawing for freestanding unit with tee-off cable box ref: RMINST-09
Schematic drawing ref: RMSCH-11
Environment
Indoor/outdoor
IP54
Ratings
Busbars 630 A
Short time withstand 16/21 kA 3 s
Internal arc 16/21 kA 1 s IAC class AF, A-FLR available on gas enclosure only
Normal current rating 200 A
Normal rated voltage 12/13.8 kV
Normal rated BIL 75/95 kV
Operating mechanism
Independent manual
Standard features
Transformer earth switch, 16/21 kA 3 s
Cable earth switch, 16/21 kA 3 s
Anti-reflex operating handle
Indication
Mechanical tripped on fault indicator
Mechanical ON/OFF indicator
Mechanical earth/main indicator
Gas pressure indicator
CB auxiliary contacts 1NO 2 NC
Test facility
Integral cable test facilities
Cable
Bottom entry up to 300 mm2 1 x 3C
Bottom entry up to 630 mm2 3 x 1C
Accessories
Tee-off cable box
Glands and plates
Interlocks
See page 45 for details
Order information
Code
CN2-T6/16
CN2-T6/21

AMTED399086EN

Rating
16 kA, 12 kV, 75 kV BIL
21 kA, 13.8 kV, 95 kV BIL

47

Non-extensible circuit breaker


200 A

Circuit breaker, metering


and switches

CN2-T25
DE59802

Transformer protection up to 3.5 MVA


Protection & control - CB
IDMT overcurrent, earth-fault and thermal overload relay,
Sepam series 10. In accordance with IEC 60255
Power supply 24-48 VDC required
Protection CTs - 200/100/1 A 5P20
Setting range (200/1):
overcurrent: 20 - 200 A, earth-fault: 2 - 480 A, sensitive earth-fault: 0.2 - 24 A
Setting range (100/1):
overcurrent: 10 - 200 A, earth-fault: 1 - 240 A, sensitive earth-fault: 0.2 - 24 A

50/51
50N/51N
49RMS

Documents (1)
Schematic drawing ref:
CN2-T25B: RMSCH-47
CN2-T25BS: RMSCH-48
CN2-T25A: RMSCH-49
CN2-T25AS: RMSCH-50
Environment
Indoor/outdoor
IP54
Ratings
Busbar 630 A
Short time withstand 16/21 kA 3 s
Internal arc 16/21 kA 1 s IAC class AF, A-FLR available on gas enclosure only
Normal current rating 200 A
Normal rated voltage 12/13.8 kV
Normal rated BIL 75/95 kV
Operating mechanism
Independent manual
Sepam 10 functions

ANSI
code

CN2-T25 (1)
B

BS A

Standard
0.012.4 In (2)

50N/51N b

Sensitive
0.224 A

50G/51G

AS

Protection
Earth-fault
protection

Phase-overcurrent protection
0.124 In (2)

50/51

Thermal overload protection

49RMS

Standard features
Transformer earth switch, 16/21 kA 3 s
Cable earth switch, 16/21 kA 3 s
Anti-reflex operating handle
Indication
Mechanical tripped on fault flag indication
Mechanical ON/OFF indication
Mechanical earth/main indication
Gas pressure indication
CB auxiliary contacts 1NO 1NC (3

Phase-overcurrent and
earth-fault cold load pick-up

Test facility
Integral ring switch cable test facility

Logic
Blocking send
68
discrimination Blocking reception

Cable
Bottom entry up to 1 x 3C 300 mm
Bottom entry up to 3 x 1C 630 mm

External tripping via digital input


Measurement
Earth-fault current

Phase currents

Peak demand currents

Order information

Control and supervision


Circuit breaker tripping
and lockout

86

Tripping annunciation

30

Relay watchdog contact

Remote CB position monitoring

Modbus

IEC 60870-5-103

Tripped on fault, volt free contact

Record of last fault


Record of last five events

Accessories - see table, page 45


Tee-off cable box
Glands and plates
Interlocks

Code (1)
CN2-T25B/21
CN2-T25BS/21
CN2-T25A/21
CN2-T25AS/21

Rating
21 kA, 13.8 kV, 95 kV BIL
21 kA, 13.8 kV, 95 kV BIL
21 kA, 13.8 kV, 95 kV BIL
21 kA, 13.8 kV, 95 kV BIL

Communications

(1) B (basic), BS (basic + sensitive earth-fault), A (advanced),


AS (advanced + sensitive earth-fault)
(2) In = Primary CT ratio
(3) Only with T25B and T25BS.

48

AMTED399086EN

Circuit breaker, metering


and switches

Non-extensible switches 630 A


Specification

SN6-S1
Manual operation

SN6-S2
Provision for actuator

b
b

b
b

b
b
b
b

b
b
b
b

b
b
O

b
b
O

b
b
O
b
O
O

b
b

b
b

b
b

b
b

Environment
Indoor / outdoor
IP54

Ratings
Normal rated current 630 A
13.8 kV 21 kA 3 seconds 95 kV BIL
Cable earth switch 21 kA 3 seconds
Transformer earth switch 3.15 kA 3 seconds

Mechanism
Independent manual
Provision for actuator 24 V DC
Actuator 24 V DC

Indication
Mechanical ON/OFF
Mechanical EARTH/MAIN
VPIS indication (6.6 - 13.8 kV)
Auxiliary switch contacts 1NO 2NC
Phase and earth fault detection CTs for Easergy 200E
Provision for EFPI

Test facility
Integral cable test facility

Standard features
Operating handle
Transformer earth switch 3.15 kA 3 seconds

Cable (see available cable kit accessories)


Bottom entry up 300 mm2 1 x 3C
Bottom entry up 630 mm2 3 x 1C
Key: b Standard feature O Optional feature

AMTED399086EN

49

Circuit breaker, metering


and switches

Non-extensible switches 630 A


Accessories

SN6-S1
Manual operation

SN6-S2
Provision for actuator

Kit no.

v
O
O
O
O
O
O
O
O
O

v
O
O
O
O
O
O
O
O
O

RMR-F47
RMR-A48
RMR-A49
RMR-A50
RMR-A52
RMR-A10
RMR-A11
RMR-A12
RMR-A13
RMR-A132

O
O
O
O

O
O
O
O

RMR-A18/6
RMR-A19
RMR-A22
RMR-A16

b
v

b
v

O
O

O
O
v

RMR-A23
RMR-F108
RMR-A24
RMR-A81
RMR-F67

RMR-F85
RMR-F86
RMR-F110

Cable kits
Tee-off cable box
Gland plate 1 x 3C
Gland plate 3 x 1C
Angled gland plates (RMR)
Blank aluminium gland plate
Brass wiping gland 1 x 3C
Brass wiping gland 3 x 1C
Tubular gland 1 x 3C
Tubular gland 3 x 1C
CES5 gland plate 1 x 3C

Installation items
Set of padlocks - 6 no
Anti-vandal fixings, including tool
Foundation bolts (not required for transformer mounting)
Multicore pilot glands

Operational items
Operating handle
VPIS indication (6.6-13.8 kV)
Neon lamp test unit (including lamp)
Neon lamp
Actuator 24 V DC

Mechanical interlocks
Key free, earth on
Key free, unit off
Transformer earth switch, key free, earth on
N. B. specify lock symbol at time of ordering (3 digits max) not
available with motor mechanisms

v
v
v

Order codes
13.8 kV, 21 kA, 95 kVBIL, 0.35bG
SN6-S1/21
General arrangement drawing - transformer mounted
RMINST-04 Page 101
General arrangement drawing - freestanding
RMINST-09 Page 158
Schematic diagram
N/A
Key: b Standard feature v Factory fitted accessory O Loose accessory, assembled on site

50

SN6-S2/21
RMINST-04 Page 101
RMINST-09 Page 158
RMSCH-28 Page 145

AMTED399086EN

Circuit breaker, metering


and switches

Non-extensible switch 630 A


SN6-S1

DE60193

Switch disconnector
Protection & control - CB
Non-automatic
Documents
Installation drawing ref: RMINST-04
Installation drawing for freestanding unit with tee-off cable box ref: RMINST-09
Schematic drawing ref: N/A
Environment
Indoor/outdoor
IP54
Ratings
Busbars 630 A
Short time withstand 21 kA 3 s
Internal arc 16/21 kA 1 s IAC class AF, A-FLR available on gas enclosure only
Normal current rating 630 A
Normal rated voltage 13.8 kV
Normal rated BIL 95 kV
Operating mechanism
Independent manual
Standard features
Transformer earth switch, 16/21 kA 3 s
Cable earth switch, 21 kA 3 s
Anti-reflex operating handle
Indication
Mechanical ON/OFF indicator
Mechanical earth/main indicator
Gas pressure indicator
Test facility
Integral cable test facilities
Cable
Bottom entry up to 300 mm2 1 x 3C
Bottom entry up to 630 mm2 3 x 1C
Accessories
Tee-off cable box
VPIS indication
Glands and plates
Interlocks
See page 50 for details
Order information
Code
SN6-S1/21

AMTED399086EN

Rating
21 kA, 13.8 kV, 95 kV BIL

51

Circuit breaker, metering


and switches

Non-extensible switch 630 A


SN6-S2

DE60194

Switch disconnector
Protection & control - CB
Non-automatic
Documents
Installation drawing ref: RMINST-04
Installation drawing for freestanding unit with tee-off cable box ref: RMINST-09
Schematic drawing ref: RMSCH-28
Environment
Indoor/outdoor
IP54
Ratings
Busbars 630 A
Short time withstand 21 kA 3 s
Internal arc 16/21 kA 1 s IAC class AF, A-FLR available on gas enclosure only
Normal current rating 630 A
Normal rated voltage 13.8 kV
Normal rated BIL 95 kV
Operating mechanism
Independent manual
Provision for actuator, 24 V DC
Standard features
Transformer earth switch, 16/21 kA 3 s
Cable earth switch, 21 kA 3 s
Anti-reflex operating handle
Indication
Mechanical ON/OFF indicator
Mechanical earth/main indicator
Gas pressure indicator
Auxiliary contacts 1NO 2NC
Earth selected auxiliary contact 1NO
Test facility
Integral cable test facilities
Cable
Bottom entry up to 300 mm2 1 x 3C
Bottom entry up to 630 mm2 3 x 1C
Accessories
Tee-off cable box
Actuator, 24 V DC
VPIS indication
Glands and plates
See page 50 for details
Order information
Code
SN6-S2/21

52

Rating
21 kA, 13.8 kV, 95 kV BIL

AMTED399086EN

Circuit breaker, metering


and switches

Non-extensible metering unit


200 A
Specification
MU2-M1

MU2-M2

MU2-M3

b
b

b
b

b
b

b
b

b
b

b
b

Environment
Indoor / outdoor
IP54

Ratings
Normal rated current 200 A
12 kV 16 kA 1 second 75 kV BIL

Metering (1)
CTs -50/25/5 A 0.5s 7.5 VA
CTs -100/50/5 A 0.5s 10 VA
CTs -200/100/5 A 0.5s 10 VA
VTs -11 kV/110 V 0.5 50 VA

b
b
b

b
b

Cable (see available cable kit accessories)


O
O
Bottom entry up 300 mm2 1 x 3C
O
O
Bottom entry up 630 mm2 3 x 1C
Key: b Standard feature O Optional feature
(1) CTs - 2 phases (L1 & L3), VTs phase to phase. 6.6 kV VTs are available - Contact Schneider Electric

AMTED399086EN

O
O

53

Circuit breaker, metering


and switches

Non-extensible metering unit


200 A
Accessories
MU2-M1

MU2-M2

MU2-M3

Kit no.

v
O
O
O
O
O
O
O
O
O

O
O
O
O
O
O
O
O
O

O
O
O
O
O
O
O
O
O

RMR-F47
RMR-A48
RMR-A49
RMR-A51 Blank
RMR-A52
RMR-A10
RMR-A11
RMR-A12
RMR-A13
RMR-A132

O
O
O
O
O

O
O
O
O
O

O
O
O
O
O

RMR-A18/6
RMR-A22
RMR-A16
RMR-A350
RMR-A90

MU2-M2/16
RMINST-07/08
Pages 105 - 104
RMSCH-14 Page 121

MU2-M3/16
RMINST-07/08
Pages 105 - 104
RMSCH-14 Page 121

Cable kits
Tee-off cable box
Gland plate 1 x 3C
Gland plate 3 x 1C
Angled gland plates (RMU)
Blank aluminium gland plate
Brass wiping gland 1 x 3C
Brass wiping gland 3 x 1C
Tubular gland 1 x 3C
Tubular gland 3 x 1C
CES5 gland plate 1 x 3C

Installation items
Set of padlocks - XX no
Foundation bolts (not required for transformer mounting)
Multicore pilot glands
RMU - MU2 installation kit
Freestanding installation kit

Order codes
12 kV, 16 kA, 75 kV BIL
General arrangement drawing - transformer mounted

MU2-M1/16
RMINST-07/08
Pages 105 - 104
Schematic diagram
RMSCH-14 Page 121
Key: v Factory fitted accessory O Loose accessory, assembled on site

54

AMTED399086EN

Circuit breaker, metering


and switches

Non-extensible metering unit


200 A
MU2-M1

DE60210

Non-extensible metering unit


Protection & control - CB
N/A
Metering transformers
b Metering CTs L1 & L3 phases
v 50/25/5 A
v 7.5 VA class 0.5s
b Metering VT ph - ph
v 11 kV/110 V 50 VA
v class 0.5
Documents
Installation drawing ref: RMINST-07/08
Schematic drawing ref: RMSCH-14
Environment
Indoor/outdoor
IP54
Ratings
Short time withstand 16 kA 1 s
Normal current rating 200 A
Normal rated voltage 12 kV
Normal rated BIL 75 kV
Standard features
Direct coupling between RMU and transformer (optional freestanding cable
connection)
Cable connection
Bottom entry up to 300 mm2 1 x 3C
Bottom entry up to 630 mm2 3 x 1C
Accessories
Cable box
Glands and plates
Installation kits
See page 54 for details
Order information
Code
MU2-M1/16

AMTED399086EN

Rating
16 kA, 12 kV, 75 kV BIL

55

Circuit breaker, metering


and switches

Non-extensible metering unit


200 A
MU2-M2

DE60210

Non-extensible metering unit


Protection & control - CB
N/A
Metering transformers
b Metering CTs L1 & L3 phases
v 100/50/5 A
v 10 VA class 0.5s
b Metering VT ph - ph
v 11 kV/110 V 50 VA
v class 0.5
Documents
Installation drawing ref: RMINST-07/08
Schematic drawing ref: RMSCH-14
Environment
Indoor/outdoor
IP54
Ratings
Short time withstand 16 kA 1 s
Normal current rating 200 A
Normal rated voltage 12 kV
Normal rated BIL 75 kV
Standard features
Direct coupling between RMU and transformer (optional freestanding cable
connection)
Cable connection
Bottom entry up to 300 mm2 1 x 3C
Bottom entry up to 630 mm2 3 x 1C
Accessories
Cable box
Glands and plates
Installation kits
See page 54 for details
Order information
Code
MU2-M2/16

56

Rating
16 kA, 12 kV, 75 kV BIL

AMTED399086EN

Circuit breaker, metering


and switches

Non-extensible metering unit


200 A
MU2-M3

DE60210

Non-extensible metering unit


Protection & control - CB
N/A
Metering transformers
b Metering CTs L1 & L3 phases
v 200/100/5 A
v 10 VA class 0.5s
b Metering VT ph - ph
v 11 kV/110 V 50 VA
v class 0.5
Documents
Installation drawing ref: RMINST-07/08
Schematic drawing ref: RMSCH-14
Environment
Indoor/outdoor
IP54
Ratings
Short time withstand 16 kA 1 s
Normal current rating 200 A
Normal rated voltage 12 kV
Normal rated BIL 75 kV
Standard features
Direct coupling between RMU and transformer
(optional freestanding cable connection)
Cable connection
Bottom entry up to 300 mm2 1 x 3C
Bottom entry up to 630 mm2 3 x 1C
Accessories
Cable box
Glands and plates
Installation kits
See page 54 for details
Order information
Code
MU2-M3/16

AMTED399086EN

Rating
16 kA, 12 kV, 75 kV BIL

57

Circuit breaker, metering


and switches

Non-extensible metering units


630 A
Specification
MU6-N1

MU6-N2

MU6-N3

MU6-N5

b
b

b
b

b
b

b
b

b
b

b
b

b
b

b
b

Environment
Indoor / outdoor
IP54

Ratings
Normal rated current 630 A
12 kV 16 kA 1 second 75 kV BIL

Metering (1)
CTs - 400/600/5 A 10 VA
CTs - 600/5 A 10 VA
CTs - 400/5 A 10 VA
CTs - 600/300/5 A 10 VA
VTs - 11 kV/110 V 0.5 50 VA
VTs - 11 kV/6.6 kV/110 V 0.5 50 VA

b
b
b
b
b

b
b

Cable (see available cable kit accessories)


O
O
Bottom entry up 300 mm2 1 x 3C
O
O
Bottom entry up 630 mm2 3 x 1C
Key: b Standard feature O Optional feature
(1) CTs - 2 phases (L1 & L3), VTs phase to phase 6.6 kV VTs are available - Contact Schneider Electric

58

O
O

O
O

AMTED399086EN

Circuit breaker, metering


and switches

Non-extensible metering units


630 A
Accessories
MU6-N1

MU6-N2

MU6-N3

MU6-N5

Kit no.

v
O
O
O
O
O
O
O
O
O

v
O
O
O
O
O
O
O
O
O

v
O
O
O
O
O
O
O
O
O

v
O
O
O
O
O
O
O
O
O

RMR-F47
RMR-A48
RMR-A49
RMR-A51 Blank
RMR-A52
RMR-A10
RMR-A11
RMR-A12
RMR-A13
RMR-A132

O
O
O
O
O

O
O
O
O
O

O
O
O
O
O

O
O
O
O
O

RMR-A18/6
RMR-A22
RMR-A16
RMR-A350
RMR-A90

MU6-N3/16
RMINST-07/08
Pages 105 - 104
RMSCH-14
Page 121

MU6-N5/16
RMINST-07/08
Pages 105 - 104
RMSCH-14
Page 121

Cable kits
Tee-off cable box
Gland plate 1 x 3C
Gland plate 3 x 1C
Angled gland plates (RMU)
Blank aluminium gland plate
Brass wiping gland 1 x 3C
Brass wiping gland 3 x 1C
Tubular gland 1 x 3C
Tubular gland 3 x 1C
CES5 gland plate 1 x 3C

Installation items
Set of padlocks - XX no
Foundation bolts (not required for transformer mounting)
Multicore pilot glands
RMU - MU6 installation kit
Freestanding installation kit

Order codes
12 kV, 16 kA, 75 kVBIL
General arrangement drawing - transformer mounted

MU6-N1/16
MU6-N2/16
RMINST-07/08
RMINST-07/08
Pages 105 - 104 Pages 105 - 104
Schematic diagram
RMSCH-14
RMSCH-14
Page 121
Page 121
Key: b Standard feature v Factory fitted accessory O Loose accessory, assembled on site

AMTED399086EN

59

Circuit breaker, metering


and switches

Non-extensible metering units


630 A
MU6-N**

DE60210

Non-extensible metering unit


Protection & control - CB
N/A
Metering transformers
b Metering CTs L1 & L3 phases (16 kA, 12 kV, 75 kV BIL)
10 VA class 0.5s
400/200/5 A
600/5 A
400/5 A
600/300/5 A

N1/16
b

N2/16

N3/16

N5/16

b
b
b

b Metering VT ph - ph (16 kA, 12 kV, 75 kV BIL)


50 VA class 0.5
11 kV/110 V
11 kV/6.6 kV/110 V

N1/16
b

N2/16
b

N3/16
b

N5/16
b

Documents
Installation drawing ref: RMINST-07/08
Schematic drawing ref: RMSCH-14
Environment
Indoor/outdoor
IP54
Ratings
Short time withstand 16 kA 1 s
Normal current rating 630 A
Normal rated voltage 12 kV
Normal rated BIL 75 kV
Standard features
Direct coupling between RMU and transformer
(optional freestanding cable connection)
Cable connection
Bottom entry up to 300 mm2 1 x 3C
Bottom entry up to 630 mm2 3 x 1C
Accessories
Cable box
Glands and plates
Installation kits
See page 59 for details
Order information
Code
MU6-N**

60

Rating
16 kA, 12 kV, 75 kV BIL

AMTED399086EN

Circuit breaker, metering


and switches

Extensible circuit breakers


200 A
Specification

(*) See complete titles footer

CE2- CE2- CE2- CE2- CE2- CE2- CE2- CE2- CE2- CE2- CE2- CE2- CE2T2
T3
T7
T11 T12 T13 T14 T15 T16 T19 T20 T21 T25

Environment
Indoor / outdoor
IP54

b
b

b
b

b
b

b
b

b
b

b
b

b
b

b
b

b
b

b
b

b
b

b
b

b
b

b
b
b

b
b
b

b
b
b

b
b
b

b
b
b

b
b
b

b
b
b

b
b
b

b
b
b

b
b
b

b
b
b

b
b
b

b
b
b

O
b

O
b

O
b

O
b

O
b

O
b

O
b

O
b

O
b

O
b

O
b

O
b

O
b

b
b

b
b

b
b

b
b

O
b

O
b

O
b

O
b

b
b

b
b

b
b

b
b

b
b
b

b
b

Ratings
Busbars 630 A
Circuit breaker normal rated current 200 A
12 kV 16 kA 3 seconds 75 kV BIL
13.8 kV 21 kA 3 seconds 95 kV BIL
Cable earth switch 16 kA 3 seconds
Cable earth switch 21 kA 3 seconds

Mechanism
Independent manual
Provision for actuator 24 V DC
Actuator 24 V DC
Operating handle

Protection system
CTs dual ratio - 500/200/1 A class x
Overcurrent relay - VIP 30
CTs dual ratio - 100/50/5 A class X
CTs dual ratio 200/100/1 A 5P20
CT ratio - 200/1 A class X
Overcurrent & earth fault CT operated trip coils
Overcurrent & earth fault relay VIP 35
Time fuse link
IDMT overcurrent & earth fault relay - VIP 300
IDMT overcurrent and earth fault relay Sepam 10
20 V-250 shunt trip coil
Auxiliary switch 1NO 2NC

b
b
b

b
b
O
b

b
b

b
b

b
b

b
b

b
b

b
b

b
b

b
b

b
b

b
b
b

Metering
b

CTs -200/100/5 A 0.5s 10 VA


VTs -13.8 kV/110 V 0.5 10 VA 13.8/110 V/110 V 0.5 50 VA 3P 20 VA
VTs -11 kV/110 V 0.5 50 VA
VTs -6.6 kV/110 V 0.5 50 VA
VTs phase - phase, CTs L1 & L3
VTs phase - earth, CTs L1, L2 & L3

b
b
b

b
b

Indication
Mechanical ON/OFF
Mechanical EARTH/MAIN
Cable VPIS indication (6.6 - 13.8 kV)
Auxiliary switch contacts 1NO 2NC
Earth selected auxiliary contacts 1NO

b
b

b
b

b
b

b
b

b
b

b
b

b
b

b
b

b
b

b
b

b
b

b
b

b
b

O
b

O
b

O
b

O
b

O
b
b

O
b
b

O
b
b

O
b

O
b

O
b

O
b

O
b
b

O
b

b
b

b
b

b
b

b
b

b
b

b
b

b
b

b
b

b
b

b
b

b
b

b
b

b
b

Test facility
Integral cable test facility

Cable
Bottom entry up to 300 mm2 1 x 3C
Bottom entry up to 630 mm2 3 x 1C
Top entry cables
Key: b Standard feature O Optional feature

(*) Complete titles:


CE2-T2 - VIP 300
CE2-T3 - VIP 300 + Metering [Phase - Phase] (VT 11 kV/110 V)
CE2-T7 - Time Fuse Link (TFL)
CE2-T11 - VIP 300 + Metering [Phase - Phase] (VT 6.6 kV/110 V)
CE2-T12 - VIP 300 + Provision for Actuator
CE2-T13 - VIP 300 + Provision for Actuator + Metering [Phase - Phase] (VT 11 kV/110 V)
CE2-T14 - VIP 300 + Provision for Actuator + Metering [Phase - Phase] (VT 6.6 kV/110 V)
CE2-T15 - VIP 30
CE2-T16 - VIP 35
CE2-T19 - VIP 300 + Metering [Phase - Earth] (VT 13.8 kV/110 V)
CE2-T20 - VIP 300 + Metering [Phase - Earth] (VT 11 kV/110 V)
CE2-T21 - VIP 300 + Provision for Actuator + Metering [Phase - Earth] (VT 13.8 kV/110 V)
CE2-T25 - Sepam 10

AMTED399086EN

61

Extensible circuit breakers


200 A

Circuit breaker, metering


and switches

Accessories
(*) See complete titles
footer
Cable kits

CE2T2

CE2T3

CE2T7

CE2T11

CE2T12

CE2T13

CE2T14

CE2T15

CE2T16

CE2T19

CE2T20

CE2T21

CE2T25

Kit no.

Gland plate 1 x 3C
Gland plate 3 x 1C
Angled gland plates (RMR)
Blank aluminium gland plate
Brass wiping gland 1 x 3C
Brass wiping gland 3 x 1C
Tubular gland 1 x 3C
Tubular gland 3 x 1C
CES5 gland plate 1 x 3C
Top entry cables standard panels
Top entry cables MU6 only

O
O
O
O
O
O
O
O
O
v

O
O
O
O
O
O
O
O
O

O
O
O
O
O
O
O
O
O
v

O
O
O
O
O
O
O
O
O

O
O
O
O
O
O
O
O
O
v

O
O
O
O
O
O
O
O
O

O
O
O
O
O
O
O
O
O

O
O
O
O
O
O
O
O
O
v

O
O
O
O
O
O
O
O
O
v

O
O
O
O
O
O
O
O
O

O
O
O
O
O
O
O
O
O

O
O
O
O
O
O
O
O
O

O
O
O
O
O
O
O
O
O
v

RMR-A48
RMR-A49
RMR-A50
RMR-A52
RMR-A10
RMR-A11
RMR-A12
RMR-A13
RMR-A132
RMR-F93
RMR-F94

O
O
O
b

O
O
b

O
O
b

O
O
O
b

O
O
O
b

O
O
O
b

O
O
b

RMR-A14
RMR-A78
RMR-A15
RMR-A18/6
RMR-A22

Installation items
3 phase busbars 630 A
3 phase busbars 630 A
Busbar end kit
Set of padlocks - 6 no
Foundation bolts (not required
for transformer mounting)
Multicore pilot glands
Time Fuse Link (set of 2 - specify
rating as table page 156)

O
O
b
O

O
O

RMR-A16
RMR-A17

b
v

b
v

b
v

b
v

b
v

b
v

b
v

b
v

b
v

b
v

b
v

b
v

b
v

RMR-A23
RMR-F108

RMR-A24

O
O

O
O

O
O

O
O
v
v

O
O
v
v

O
O
v
v

O
O

O
O

O
O

O
O

O
O

RMR-A81
RMR-A202
RMR-F67
RMR-F391

v
v

v
v

v
v

RMR-F85
RMR-F86

O
O
b

O
O
O
b

O
O
b

O
O
O
b

O
O
O
b

Operational items
Operating handle
Cable VPIS indication
(6.6 - 13.8 kV)
Neon lamp test unit
(including lamp)
Neon lamp
VAP 6 test unit for VIP 300
Actuator 24 V DC
Polarity conversion kit (1)

Mechanical interlocks
v
v
v
v
Key free, EARTH ON
v
v
v
v
Key free, MAIN OFF
N. B. specify lock symbol at time
of ordering (3 digits max)
not available with motor
mechanisms
Key: b Standard feature v Factory fitted accessory O Loose accessory, assembled on site
(1) Only required when unit is used with RE2c ring main units and automation.
(*) Complete titles:
CE2-T2 - VIP 300
CE2-T3 - VIP 300 + Metering [Phase - Phase] (VT 11 kV/110 V)
CE2-T7 - Time Fuse Link (TFL)
CE2-T11 - VIP 300 + Metering [Phase - Phase] (VT 6.6 kV/110 V)
CE2-T12 - VIP 300 + Provision for Actuator
CE2-T13 - VIP 300 + Provision for Actuator + Metering [Phase - Phase] (VT 11 kV/110 V)
CE2-T14 - VIP 300 + Provision for Actuator + Metering [Phase - Phase] (VT 6.6 kV/110 V)
CE2-T15 - VIP 30
CE2-T16 - VIP 35
CE2-T19 - VIP 300 + Metering [Phase - Earth] (VT 13.8 kV/110 V)
CE2-T20 - VIP 300 + Metering [Phase - Earth] (VT 11 kV/110 V)
CE2-T21 - VIP 300 + Provision for Actuator + Metering [Phase - Earth] (VT 13.8 kV/110 V)
CE2-T25 - Sepam 10

62

AMTED399086EN

Extensible circuit breakers


200 A

Circuit breaker, metering


and switches

Accessories
(*) See complete titles
footer
Earth fault passage
indication (choose
provision kit and an EFPI
required if not using
Easergy 200E)

CE2T2

CE2T3

CE2T7

CE2T11

CE2T12

CE2T13

CE2T14

CE2T15

CE2T16

CE2T19

CE2T20

CE2T21

CE2T25

Kit no.

EFPI provision kit, inside


cable box
Bowden STD EFPI type NB
Bowden LV reset EFPI type NB1
Bowden LV reset & alarm
type NB2
Bowden RR EFPI and CT
Fundamentals ER FIND
EFPI and CT

RMR-F30

O
O
O

O
O
O

O
O
O

O
O
O

O
O
O

O
O
O

O
O
O

O
O
O

O
O
O

O
O
O

O
O
O

O
O
O

O
O
O

RMR-A277
RMR-A278
RMR-A279

O
O

O
O

O
O

O
O

O
O

O
O

O
O

O
O

O
O

O
O

O
O

O
O

O
O

RMR-A56
RMR-A57

RMR-A80

Ancillary items
Tool box

Order code
12 kV, 16 kA, 75 kV BIL, 0.35bG CE2CE2CE2CE2CE2CE2CE2CE2CE2N/A
CE2N/A
N/A
T2/16 T3/16 T7/16 T11/16 T12/16 T13/16 T14/16 T15/16 T16/16
T20/16
13.8 kV, 21 kA, 95 kV BIL, 0.55bG CE2CE2CE2CE2CE2CE2CE2CE2CE2CE2N/A
CE2CE2T2/21 T3/21 T7/21 T11/21 T12/21 T13/21 T14/21 T15/21 T16/21 T19/21
T21/21 T25/21
General arrangement drawing RMINST-03 RMINST-02 RMINST-03 RMINST-02 RMINST-03 RMINST-02 RMINST-02 RMINST-03 RMINST-03 RMINST-02 RMINST-02 RMINST-02 RMINST-03
Page 100

Schematic drawing

Page 99

Page 100

Page 99

Page 100

Page 99

Page 99

Page 100

Page 100

Page 99

Page 99

Page 99

Page 100

RMSCH-07 RMSCH-09 RMSCH-06 RMSCH-09 RMSCH-19 RMSCH-20 RMSCH-20 RMSCH-07 RMSCH-07 RMSCH-35 RMSCH-35 RMSCH-36 RMSCH-47 to 50
Page 129 Page 131 Page 128 Page 131 Page 135 Page 136 Page 136 Page 129 Page 129 Page 141 Page 141 Page 142 Pages 122 to 125

Key: b Standard feature v Factory fitted accessory O Loose accessory, assembled on site
(*) Complete titles:
CE2-T2 - VIP 300
CE2-T3 - VIP 300 + Metering [Phase - Phase] (VT 11 kV/110 V)
CE2-T7 - Time Fuse Link (TFL)
CE2-T11 - VIP 300 + Metering [Phase - Phase] (VT 6.6 kV/110 V)
CE2-T12 - VIP 300 + Provision for Actuator
CE2-T13 - VIP 300 + Provision for Actuator + Metering [Phase - Phase] (VT 11 kV/110 V)
CE2-T14 - VIP 300 + Provision for Actuator + Metering [Phase - Phase] (VT 6.6 kV/110 V)
CE2-T15 - VIP 30
CE2-T16 - VIP 35
CE2-T19 - VIP 300 + Metering [Phase - Earth] (VT 13.8 kV/110 V)
CE2-T20 - VIP 300 + Metering [Phase - Earth] (VT 11 kV/110 V)
CE2-T21 - VIP 300 + Provision for Actuator + Metering [Phase - Earth] (VT 13.8 kV/110 V)
CE2-T25 - Sepam 10

AMTED399086EN

63

Circuit breaker, metering


and switches

Extensible circuit breaker 200 A


CE2-T2

DE60251

Feeder protection up to 3.5 MVA at 11 kV


Protection & control - CB
Self powered IDMT overcurrent and earth fault relay, VIP 300. In accordance with
IEC 60255 and BS142.
Protection CTs - 200/1 A class X
Shunt trip coil, 20 V DC-250 V AC
b Setting range:
v Overcurrent: 20-200 A
v Earth fault: 2-160 A
Documents
Installation drawing ref: RMINST-03
Schematic drawing ref: RMSCH-07
Environment
Indoor/outdoor
IP54
Ratings
Busbars 630 A
Short time withstand 16/21 kA 3 s
Internal arc 16/21 kA 1 s IAC class AF, A-FLR available on gas enclosure only
Normal current rating 200 A
Normal rated voltage 12/13.8 kV
Normal rated BIL 75/95 kV
Operating mechanism
Independent manual
Standard features
Cable earth switch, 16/21 kA 3 s
Anti-reflex operating handle
Indication
Mechanical tripped on fault flag indicator
Mechanical ON/OFF indicator
Mechanical earth/main indicator
Auxiliary contacts,1NO 2NC
Gas pressure indicator
Test facility
Integral cable test facilities
Cable
Bottom entry up to 300 mm2 1 x 3C
Bottom entry up to 630 mm2 3 x 1C
Accessories
VPIS indication
Glands and plates
Interlocks
Operating handle
Busbar kit
Top entry cables
See page 62 for details
Order information
Code
CE2-T2/16
CE2-T2/21

64

Rating
16 kA, 12 kV, 75 kV BIL
21 kA, 13.8 kV, 95 kV BIL

AMTED399086EN

Circuit breaker, metering


and switches

Extensible circuit breaker 200 A


CE2-T7

DE60196

Transformer protection up to 1.5 MVA at 11 kV


Protection & control - CB
Overcurrent and earth fault protection using CT operated trip coils with provision
for time fuse links.
Protection CTs - 100/50/5 A class X
Shunt trip coil, 20 V DC-250 V AC
Documents
Installation drawing ref: RMINST-03
Schematic drawing ref: RMSCH-06
Environment
Indoor/outdoor
IP54
Ratings
Busbars 630 A
Short time withstand 16/21 kA 3 s
Internal arc 16/21 kA 1 s IAC class AF, A-FLR available on gas enclosure only
Normal current rating 200 A
Normal rated voltage 12/13.8 kV
Normal rated BIL 75/95 kV
Operating mechanism
Independent manual
Standard features
Cable earth switch, 16/21 kA 3 s
Anti-reflex operating handle
Indication
Mechanical tripped on fault flag indicator
Mechanical ON/OFF indicator
Mechanical earth/main indicator
Auxiliary contacts,1NO 2NC
Gas pressure indicator
Test facility
Integral cable test facility
Cable
Bottom entry up to 300 mm2 1 x 3C
Bottom entry up to 630 mm2 3 x 1C
Accessories
VPIS indication
Glands and plates
Interlocks
Operating handle
Busbar kit
Top entry cables
See page 62 for details
Order information
Code
CE2-T7/16
CE2-T7/21

AMTED399086EN

Rating
16 kA, 12 kV, 75 kV BIL
21 kA, 13.8 kV, 95 kV BIL

65

Circuit breaker, metering


and switches

Extensible circuit breaker 200 A


CE2-T*

DE60252

Feeder protection up to 3.5 MVA at 11 kV


Protection & control - CB
Self powered IDMT overcurrent and earth fault relay, VIP 300. In accordance with
IEC 60255 and BS142.
Protection CTs - 200/1 A class X
Shunt trip coil, 20 V DC-250 V AC
b Setting range:
v Overcurrent: 20-200 A
v Earth fault: 2-160 A

(Select VT rating and switchgear rating from table below).

Metering transformers
b Metering CTs L1 & L3 phases
v 200/100/5 A
v 10 VA class 0.5s
b Metering VT
v see below
Environment
Indoor/outdoor
IP54
Ratings
Busbars 630 A
Short time withstand 16/21 kA 3 s
Internal arc 16/21 kA 1 s IAC class AF, A-FLR available on gas enclosure only
Normal current rating 200 A
Normal rated voltage 12/13.8 kV
Normal rated BIL 75/95 kV
Operating mechanism
Independent manual
Anti-reflex operating handle
Standard features
Cable earth switch, 16/21 kA 3 s
Indication
Mechanical tripped on fault flag indicator
Mechanical ON/OFF indicator
Mechanical earth/main indicator
Auxiliary contacts,1NO 2NC
Gas pressure indicator
Test facility
Integral cable test facility
Cable
Bottom entry up to 300 mm2 1 x 3C
Bottom entry up to 630 mm2 3 x 1C
Accessories
VPIS indication
Glands and plates
Interlocks
Operating handle
Busbar kit
Top entry cables
See page 62 for details
Order code
16 kA, 12 kV, 75 kV BIL
CE2-T3/16
CE2-T11/16
N/A
21 kA, 13.8 kV, 95 kV BIL
CE2-T3/21
CE2-T11/21
CE2-T19/21
b
b
Metering VT information:
Phase to phase
b
Phase to earth
b
6.6 kV/110 V
b
11 kV/110 V (1)
b
13.8 kV/110 V
General arrangement drawing RMINST-02
RMINST-02
RMINST-02
Page 99
Page 99
Page 99
Schematic diagram
RMSCH-09
RMSCH-09
RMSCH-35
Page 131
Page 131
Page 141
(1) Please consult Schneider Electric when ordering units with 95 kV BIL voltage
Tel: +44 (0)113 290 3500

66

CE2-T20/16
N/A

b
b
RMINST-02
Page 99
RMSCH-35
Page 141

AMTED399086EN

Circuit breaker, metering


and switches

Extensible circuit breaker 200 A


CE2-T12

DE60253

Feeder protection up to 3.5 MVA at 11 kV


Protection & control - CB
Self powered IDMT overcurrent and earth fault relay, VIP 300. In accordance with
IEC 60255 and BS142.
Protection CTs - 200/1 A class X
Shunt trip coil, 20 V DC-250 V AC
b Setting range:
v Overcurrent: 20-200 A
v Earth fault: 2-160 A
Documents
Installation drawing ref: RMINST-03
Schematic drawing ref: RMSCH-19
Environment
Indoor/outdoor
IP54
Ratings
Busbars 630 A
Short time withstand 16/21 kA 3 s
Internal arc 16/21 kA 1 s IAC class AF, A-FLR available on gas enclosure only
Normal current rating 200 A
Normal rated voltage 12/13.8 kV
Normal rated BIL 75/95 kV
Operating mechanism
Independent manual
Provision for actuator, 24 V DC
Standard features
Cable earth switch, 16/21 kA 3 s
Anti-reflex operating handle
Indication
Mechanical tripped on fault flag indicator
Mechanical ON/OFF indicator
Mechanical earth/main indicator
Auxiliary contacts,1NO 2 NC
Earth selected auxiliary contact1NO
Gas pressure indicator
Test facility
Integral cable test facility
Cable
Bottom entry up to 300 mm2 1 x 3C
Bottom entry up to 630 mm2 3 x 1C
Accessories
Actuator, 24 V DC
VPIS indication
Glands and plates
Interlocks
Operating handle
Busbar kit
Top entry cables
See page 62 for details
Order information
Code
CE2-T12/16
CE2-T12/21

AMTED399086EN

Rating
16 kA, 12 kV, 75 kV BIL
21 kA, 13.8 kV, 95 kV BIL

67

Circuit breaker, metering


and switches

Extensible circuit breaker 200 A


CE2-T**

DE60254

Feeder protection up to 3.5 MVA at 11 kV


Protection & control - CB
Self powered IDMT overcurrent and earth fault relay, VIP 300. In accordance with
IEC 60255 and BS142.
Protection CTs - 200/1 A class X
Shunt trip coil, 20 V DC-250 V AC
b Setting range:
v Overcurrent: 20-200 A
v Earth fault: 2-160 A

(Select VT rating and switchgear rating from table below).

Metering transformers
b Metering CTs
v 200/100/5 A
v 10 VA class 0.5s
b Metering VT
v see below
Environment
Indoor/outdoor
IP54
Ratings
Busbars 630 A
Short time withstand 16/21 kA 3 s
Internal arc 16/21 kA 1 s IAC class AF, A-FLR available on gas enclosure only
Normal current rating 200 A
Normal rated voltage 12/13.8 kV
Normal rated BIL 75/95 kV
Operating mechanism
Independent manual
Provision for actuator, 24 V DC
Standard features
Cable earth switch, 16/21 kA 3 s
Anti-reflex operating handle
Indication
Mechanical tripped on fault indicator
Mechanical ON/OFF indicator
Mechanical earth/main indicator
Auxiliary contacts,1NO 2NC
Earth selected auxiliary contact1NO
Gas pressure indicator
Test facility
Integral cable test facility
Cable
Bottom entry up to 300 mm2 1 x 3C
Bottom entry up to 630 mm2 3 x 1C
Accessories
Actuator, 24 V DC
VPIS indication
Glands and plates
Interlocks
Operating handle
Busbar kit
Top entry cables
See page 62 for details
Order code
16 kA, 12 kV, 75 kV BIL
CE2-T14/16
N/A
21 kA, 13.8 kV, 95 kV BIL
CE2-T14/21
CE2-T21/21
Metering VT information:
b
Phase to phase
b
Phase to earth
b
6.6 kV/110 V
11 kV/110 V (1)
b
13.8 kV/110 V
General arrangement drawing RMINST-02
RMINST-02
Page 99
Page 99
Schematic diagram
RMSCH-20
RMSCH-36
Page 136
Page 142
(1) Please consult Schneider Electric when ordering units with 95 kV BIL voltage
Tel: +44 (0)113 290 3500

68

AMTED399086EN

Circuit breaker, metering


and switches

Extensible circuit breaker 200 A


CE2-T13

DE60254

Feeder protection up to 3.5 MVA at 11 kV


Protection & control - CB
Self powered IDMT overcurrent and earth fault relay, VIP 300. In accordance with
IEC 60255 and BS142.
Protection CTs - 200/1 A class X
Shunt trip coil, 20 V DC-250 V AC
b Setting range:
v Overcurrent: 20-200 A
v Earth fault: 2-160 A
Metering transformers
b Metering CTs
v 200/100/5 A
v 10 VA class 0.5s
b Metering VT ph - ph
v 11 kV/110 V 50 VA
v class 0.5
Documents
Installation drawing ref: RMINST-02
Schematic drawing ref: RMSCH-20
Environment
Indoor/outdoor
IP54
Ratings
Busbars 630 A
Short time withstand 16/21 kA 3 s
Internal arc 16/21 kA 1 s IAC class AF, A-FLR available on gas enclosure only
Normal current rating 200 A
Normal rated voltage 12/13.8 kV
Normal rated BIL 75/95 kV
Operating mechanism
Independent manual
Actuator, 24 V DC
Standard features
Cable earth switch, 16/21 kA 3 s
Anti-reflex operating handle
Indication
Mechanical tripped on fault indicator
Mechanical ON/OFF indicator
Mechanical earth/main indicator
Auxiliary contacts,1NO 2NC
Earth selected auxiliary contact1NO
Gas pressure indicator
Test facility
Integral cable test facility
Cable
Bottom entry up to 300 mm2 1 x 3C
Bottom entry up to 630 mm2 3 x 1C
Accessories
VPIS indication
Glands and plates
Interlocks
Operating handle
Busbar kit
Top entry cables
See page 62 for details
Order information
Code
CE2-T13/16
CE2-T13/21

AMTED399086EN

Rating
16 kA, 12 kV, 75 kV BIL
21 kA, 13.8 kV, 95 kV BIL

69

Circuit breaker, metering


and switches

Extensible circuit breaker 200 A


CE2-T15

DE60251

Feeder protection up to 2.5 MVA at 11 kV


Protection & control - CB
Self powered overcurrent relay, VIP 30.
Protection CTs - 500/200/1 A class X
b Setting range: 500/1 A
v Overcurrent: 20-200 A
b Setting range: 200/1 A
v Overcurrent: 8-80 A
Documents
Installation drawing ref: RMINST-03
Schematic drawing ref: RMSCH-12
Environment
Indoor/outdoor
IP54
Ratings
Busbars 630 A
Short time withstand 16/21 kA 3 s
Internal arc 16/21 kA 1 s IAC class AF, A-FLR available on gas enclosure only
Normal current rating 200 A
Normal rated voltage 12/13.8 kV
Normal rated BIL 75/95 kV
Operating mechanism
Independent manual
Standard features
Cable earth switch, 16/21 kA 3 s
Anti-reflex operating handle
Indication
Mechanical tripped on fault flag indicator
Mechanical ON/OFF indicator
Mechanical earth/main indicator
Auxiliary contacts,1NO 2NC
Gas pressure indicator
Test facility
Integral cable test facilities
Cable
Bottom entry up to 300 mm2 1 x 3C
Bottom entry up to 630 mm2 3 x 1C
Accessories
VPIS indication
Glands and plates
Interlocks
Operating handle
Busbar kit
Top entry cables
See page 62 for details
Order information
Code
CE2-T15/16
CE2-T15/21

70

Rating
16 kA, 12 kV, 75 kV BIL
21 kA, 13.8 kV, 95 kV BIL

AMTED399086EN

Circuit breaker, metering


and switches

Extensible circuit breaker 200 A


CE2-T16

DE60255

Feeder protection up to 2.5 MVA at 11 kV


Protection & control - CB
Self powered IDMT overcurrent and earth fault relay, VIP 35.
Protection CTs - 500/200/1 A class X
CH30 core balance CT
b Setting range: 500/1 A
v Overcurrent: 20-200 A
v Earth fault: 25-300 A
b Setting range: 200/1 A
v Overcurrent: 8-80 A
v Earth fault: 10-120 A
Documents
Installation drawing ref: RMINST-03
Schematic drawing ref: RMSCH-13
Environment
Indoor/outdoor
IP54
Ratings
Busbars 630 A
Short time withstand 16/21 kA 3 s
Internal arc 16/21 kA 1 s IAC class AF, A-FLR available on gas enclosure only
Normal current rating 200 A
Normal rated voltage 12/13.8 kV
Normal rated BIL 75/95 kV
Operating mechanism
Independent manual
Standard features
Cable earth switch, 16/21 kA 3 s
Anti-reflex operating handle
Indication
Mechanical tripped on fault flag indicator
Mechanical ON/OFF indicator
Mechanical earth/main indicator
Auxiliary contacts,1NO 2NC
Gas pressure indicator
Test facility
Integral cable test facilities
Cable
Bottom entry up to 300 mm2 1 x 3C
Bottom entry up to 630 mm2 3 x 1C
Accessories
VPIS indication
Glands and plates
Interlocks
Operating handle
Busbar kit
Top entry cables
See page 62 for details
Order information
Code
CE2-T16/16
CE2-T16/21

AMTED399086EN

Rating
16 kA, 12 kV, 75 kV BIL
21 kA, 13.8 kV, 95 kV BIL

71

Extensible circuit breaker 200 A

Circuit breaker, metering


and switches

CE2-T25

DE59803

Transformer protection up to 3.5 MVA at 11 kV


Protection & control - CB
IDMT overcurrent, earth-fault and thermal overload relay,
Sepam series 10. In accordance with IEC 60255
Power supply 24-48 VDC required
Protection CTs - 200/100/1 A 5P20
Setting range (200/1):
overcurrent: 20 - 200 A, earth-fault: 2 - 480 A, sensitive earth-fault: 0.2 - 24 A
Setting range (100/1):
overcurrent: 10 - 200 A, earth-fault: 1 - 240 A, sensitive earth-fault: 0.2 - 24 A

50/51
50N/51N
49RMS

Documents (1)
Schematic drawing ref:
CE2 T25B: RMSCH-47
CE2 T25BS: RMSCH-48
CE2 T25A: RMSCH-49
CE2 T25AS: RMSCH-50
Environment
Indoor/outdoor
IP54
Ratings
Busbar 630 A
Short time withstand 16/21 kA 3 s
Internal arc 16/21 kA 1 s IAC class AF, A-FLR available on gas enclosure only
Normal current rating 200 A
Normal rated voltage 12/13.8 kV
Normal rated BIL 75/95 kV
Operating mechanism
Independent manual
Sepam 10 functions

ANSI
code

CE2-T25 (1)
B

BS A

Standard
0.012.4 In (2)

50N/51N b

Sensitive
0.224 A

50G/51G

AS

Protection
Earth-fault
protection

Phase-overcurrent protection
0.124 In (2)

50/51

Thermal overload protection

49RMS

Phase-overcurrent and
earth-fault cold load pick-up

Logic
Blocking send
68
discrimination Blocking reception

External tripping via digital input

Standard features
Cable earth switch, 16/21 kA 3 s
Anti-reflex operating handle
Indication
Mechanical tripped on fault flag indication
Mechanical ON/OFF indication
Mechanical earth/main indication
Gas pressure indication
CB auxiliary contacts 1NO 1NC (3)
Test facility
Integral ring switch cable test facility
Cable
Bottom entry up to 1 x 3C 300 mm
Bottom entry up to 3 x 1C 630 mm

Earth-fault current

Phase currents

Accessories - see table, page 62


Tee-off cable box
Glands and plates
Interlocks

Peak demand currents

Order information

Measurement

Control and supervision


Circuit breaker tripping
and lockout

86

Tripping annunciation

30

Relay watchdog contact

Remote CB position monitoring

Modbus

IEC 60870-5-103

Tripped on fault, volt free contact

Record of last fault


Record of last five events

Code (1)
CE2-T25B/21
CE2-T25BS/21
CE2-T25A/21
CE2-T25AS/21

Rating
21 kA, 13.8 kV, 95 kV BIL
21 kA, 13.8 kV, 95 kV BIL
21 kA, 13.8 kV, 95 kV BIL
21 kA, 13.8 kV, 95 kV BIL

Communications

(1) B (basic), BS (basic + sensitive earth-fault), A (advanced),


AS (advanced + sensitive earth-fault)
(2) In = Primary CT ratio
(3) Only with T25B and T25BS.

72

AMTED399086EN

Circuit breaker, metering


and switches

Extensible circuit breakers


630 A
Specification

(*) See complete titles footer

CE6T4

CE6T5

CE6T6

CE6T8

CE6T9

CE6T10

CE6T22

CE6T23

CE6T24

CE6T25

b
b

b
b

b
b

b
b

b
b

b
b

b
b

b
b

b
b

b
b

b
b
b

b
b
b

b
b
b

b
b
b

b
b
b

b
b
b

b
b
b

b
b
b

b
b
b

b
b
b

O
b

O
b

O
b

O
b

O
b

O
b

O
b

O
b

O
b

O
b

b
b

b
b

b
b

b
b

O
b

O
b

O
b

O
b

b
b

b
b

b
b

b
b

b
b

b
b

b
b

b
b

b
b

b
b

b
b

Environment
Indoor / outdoor
IP54

Ratings
Busbars 630 A
Circuit breaker normal rated current 630 A
12 kV 16 kA 3 seconds 75 kV BIL
13.8 kV 21 kA 3 seconds 95 kV BIL
Cable earth switch 16 kA 3 seconds
Cable earth switch 21 kA 3 seconds

Mechanism
Independent manual
Provision for actuator 24 V DC
Actuator 24 V DC
Operating handle

Protection system
CT ratio - 800/1 A class X
CT dual ratio 800/400/1 A 5P20
IDMT overcurrent & earth fault relay - VIP 300
IDMT overcurrent & earth fault relay Sepam 10
20 V-250 V shunt trip coil
Auxiliary switch 1NO 2NC

b
b
b
b

Metering
CTs - 400/200/5 A 0.5s 10 VA
VTs - 13.8 kV/110 V/110 V/ 0.5 50 VA 3P 20 VA
VTs - 11 V/110 V 0.5 50 VA
VTs - 6.6 kV/110 V 0.5 50 VA
VTs - phase - phase, CTs L1 & L3
VTs phase - earth, CTs L1, L2 & L3

b
b

b
b
b

b
b
b
b

Indication
Mechanical ON/OFF
Mechanical EARTH/MAIN
Cable VPIS indication (6.6 - 13.8 kV)
Auxiliary switch contacts 1NO 2NC
Indication CT 600/5 A 5 VA CLS 1 L2 ph
Ammeter 0-600 A
Earth selected auxiliary contacts 1NO
Gas pressure indicator

b
b

b
b

b
b

b
b

b
b

b
b

b
b

b
b

b
b

b
b

O
b
b
b

O
b
b
b

O
b
b
b

O
b
b
b

O
b

O
b
b
b
b
b

O
b
b
b

O
b
b
b
b
b

O
b
b
b

O
b
b
b
b
b

b
b

b
b

b
b

b
b

b
b

b
b

b
b

b
b

b
b

b
b

Test facility
Integral cable test facility

Cable
Bottom entry up to 300 mm2 1 x 3C
Bottom entry up to 630 mm2 3 x 1C
Top entry cables
Key: b Standard feature O Optional feature

(*) Complete titles:


CE6-T4 - VIP 300
CE6-T5 - VIP 300 + Metering [Phase - Phase] (VT 11 kV/110 V)
CE6-T6 - VIP 300 + Metering [Phase - Phase] (VT 6.6 kV/110 V)
CE6-T8 - VIP 300 + Provision for Actuator
CE6-T9 - VIP 300 + Provision for Actuator + Metering [Phase - Phase] (VT 11 kV/110 V)
CE6-T10 - VIP 300 + Provision for Actuator + Metering [Phase - Phase] (VT 6.6 kV/110 V)
CE6-T22 - VIP 300 + Metering [Phase - Earth] (VT 13.8 kV/110 V)
CE6-T23 - VIP 300 + Provision for Actuator + Metering [Phase - Earth] (VT 13.8 kV/110 V)
CE6-T24 - VIP 300 + Metering [Phase - Earth] (VT 11 kV/110 V)
CE6-T25 - Sepam 10

AMTED399086EN

73

Extensible circuit breakers


630 A

Circuit breaker, metering


and switches

Accessories
(*) See complete titles footer

CE6T4

CE6T5

CE6T6

CE6T8

CE6T9

CE6T10

CE6T22

CE6T23

CE6T24

CE6T25

Kit no.

O
O
O
O
O
O
O
O
O
v

O
O
O
O
O
O
O
O
O

O
O
O
O
O
O
O
O
O

O
O
O
O
O
O
O
O
O
v

O
O
O
O
O
O
O
O
O

O
O
O
O
O
O
O
O
O

O
O
O
O
O
O
O
O
O

O
O
O
O
O
O
O
O
O

O
O
O
O
O
O
O
O
O

O
O
O
O
O
O
O
O
O
v

RMR-A48
RMR-A49
RMR-A50
RMR-A52
RMR-A10
RMR-A11
RMR-A12
RMR-A13
RMR-A132
RMR-F93
RMR-F94

O
O
b

O
O
O
O
b

O
O
O
b

O
O
b

O
O
O
b

O
O
O
b

O
O
O
b

O
O
O
b

O
O
O
b

O
O
b

RMR-A14
RMR-A78
RMR-A15
RMR-A18/6
RMR-A22

RMR-A16

b
v

b
v

b
v

b
v

b
v

b
v

b
v

b
v

b
v

b
v

O
O
O

O
O
O

O
O

O
O
O
v
v

O
O
O
v
v

O
O
O
v
v

O
O
O

O
O
O
v
v

O
O
O

O
O

RMR-A23
RMR-A108
RMR-A24
RMR-A81
RMR-A202
RMR-F67
RMR-F391

v
Key free, EARTH ON
v
Key free, MAIN OFF
N. B. specify lock symbol at time of ordering
( 3 digits max) not available with motor
mechanisms

v
v

v
v

v
v

v
v

RMR-F85
RMR-F86

O
O
O
O
O
O

O
O
O
O
O
O

O
O
O
O
O
O

O
O
O
O
O
O

O
O
O
O
O
O

O
O
O
O
O
O

O
O
O
O
O
O

O
O
O
O
O
O

O
O
O
O
O
O

O
O
O
O
O
O

RMR-F30
RMR-A277
RMR-A278
RMR-A279
RMR-A56
RMR-A57

RMR-A80

CE6T4/16
CE6T4/21

CE6T5/16
CE6T5/21

CE6T6/16
CE6T6/21

CE6T8/16
CE6T8/21

CE6T9/16
CE6T9/21

CE6T10/16
CE6T10/21

N/A

N/A

CE6T22/21

CE6T23/21

CE6T24/16
N/A

RMINST-03
Page 100
RMSCH-08
Page 130

RMINST-02
Page 99
RMSCH-10
Page 132

RMINST-02
Page 99
RMSCH-10
Page 132

RMINST-03
Page 100
RMSCH-23
Page 139

RMINST-02
Page 99
RMSCH-24
Page 140

RMINST-02
Page 99
RMSCH-24
Page 140

RMINST-02
Page 99
RMSCH-37
Page 143

RMINST-02
Page 99
RMSCH-38
Page 144

Cable kits
Gland plate 1 x 3C
Gland plate 3 x 1C
Angled gland plates (RMR)
Blank aluminium gland plate
Brass wiping gland 1 x 3C
Brass wiping gland 3 x 1C
Tubular gland 1 x 3C
Tubular gland 3 x 1C
CES5 gland plate 1 x 3C
Top entry cables standard panels
Top entry cables MU6 only

Installation items
3 phase busbars 630 A
3 phase busbars 630 A
Busbar end kit
Set of padlocks - 6 no
Foundation bolts (not required for
transformer mounting)
Multicore pilot glands

Operational items
Operating handle
Cable VPIS indication (6.6 - 13.8 kV)
Neon lamp test unit (including lamp)
Neon lamp
VAP 6 test unit for VIP 300
Actuator 24 V DC
Polarity conversion kit (1)

Mechanical interlocks
v
v

Earth fault passage indication


(choose provision kit and an EFPI
required if not using Easergy T200E)
EFPI provision kit, inside cable box
Bowden STD EFPI type NB
Bowden LV reset EFPI type NB1
Bowden LV reset & alarm type NB2
Bowden RR EFPI and CT
Fundamentals ER FIND EFPI and CT

Ancillary items
Tool box

Order code
12 kV, 16 kA, 75 kV BIL, 0.35bG
13.8 kV, 21 kA, 95 kV BIL, 0.55bG
General arrangement drawing
Schematic drawing

RMINST-02
Page 99
RMSCH-37
Page 143

CE6T25/21
RMINST-03
Page 100
RMSCH-47 to 50
Pages 122 to 125

Key: b Standard feature v Factory fitted accessory O Loose accessory, assembled on site
(1) Only required when unit is used with RE2c ring main units and automation.
(*) Complete titles:
CE6-T4 - VIP 300
CE6-T5 - VIP 300 + Metering [Phase - Phase] (VT 11 kV/110 V)
CE6-T6 - VIP 300 + Metering [Phase - Phase] (VT 6.6 kV/110 V)
CE6-T8 - VIP 300 + Provision for Actuator
CE6-T9 - VIP 300 + Provision for Actuator + Metering [Phase - Phase] (VT 11 kV/110 V)
CE6-T10 - VIP 300 + Provision for Actuator + Metering [Phase - Phase] (VT 6.6 kV/110 V)
CE6-T22 - VIP 300 + Metering [Phase - Earth] (VT 13.8 kV/110 V)
CE6-T23 - VIP 300 + Provision for Actuator + Metering [Phase - Earth] (VT 13.8 kV/110 V)
CE6-T24 - VIP 300 + Metering [Phase - Earth] (VT 11 kV/110 V)
CE6-T25 - Sepam 10

74

AMTED399086EN

Circuit breaker, metering


and switches

Extensible circuit breaker 630 A


CE6-T4

DE60256

Feeder protection up to 12 MVA at 11 kV


Protection & control - CB
Self powered IDMT overcurrent and earth fault relay, VIP 300. In accordance with
IEC 60255 and BS142.
Protection CTs - 800/1 A class X
Shunt trip coil, 20 V DC-250 V AC
b Setting range:
v Overcurrent: 80-800 A
v Earth fault: 8-640 A
Documents
Installation drawing ref: RMINST-03
Schematic drawing ref: RMSCH-08
Environment
Indoor/outdoor
IP54
Ratings
Busbars 630 A
Short time withstand 16/21 kA 3 s
Internal arc 16/21 kA 1 s IAC class AF, A-FLR available on gas enclosure only
Normal current rating 630 A
Normal rated voltage 12/13.8 kV
Normal rated BIL 75/95 kV
Operating mechanism
Independent manual
Standard features
Cable earth switch, 16/21 kA 3 s
Anti-reflex operating handle
Indication
Mechanical tripped on fault flag indicator
Mechanical ON/OFF indicator
Mechanical earth/main indicator
Auxiliary contacts,1NO 2 NC
Ammeter 0-600 A
Indication CT L2 ph - 600/5 A class 1.0, 5 VA
Gas pressure indicator
Test facility
Integral cable test facility
Cable
Bottom entry up to 300 mm2 1 x 3C
Bottom entry up to 630 mm2 3 x 1C
Accessories
VPIS indication
Glands and plates
Interlocks
Busbar kit
Top entry cables
See page 74 for details
Order information
Code
CE6-T4/16
CE6-T4/21

AMTED399086EN

Rating
16 kA, 12 kV, 75 kV BIL
21 kA, 13.8 kV, 95 kV BIL

75

Circuit breaker, metering


and switches

Extensible circuit breaker 630 A


CE6-T*

DE60197

Feeder protection up to 12 MVA at 11 kV


Protection & control - CB
Self powered IDMT overcurrent and earth fault relay, VIP 300. In accordance with
IEC 60255 and BS142.
Protection CTs - 800/1 A class X
Shunt trip coil, 20 V DC-250 V AC
b Setting range:
v Overcurrent: 80-800 A
v Earth fault: 8-640 A

(Select VT rating and switchgear rating from table below).

Metering transformers
b Metering CTs
v 400/200/5 A
v 10 VA class 0.5s
b Metering VT
v see below
Environment
Indoor/outdoor
IP54
Ratings
Busbars 630 A
Short time withstand 16/21 kA 3 s
Internal arc 16/21 kA 1 s IAC class AF, A-FLR available on gas enclosure only
Normal current rating 630 A
Normal rated voltage 12/13.8 kV
Normal rated BIL 75/95 kV
Operating mechanism
Independent manual
Standard features
Cable earth switch, 16/21 kA 3 s
Anti-reflex operating handle
Indication
Mechanical tripped on fault flag indicator
Mechanical ON/OFF indicator
Mechanical earth/main indicator
Auxiliary contacts,1NO 2 NC
Ammeter 0-600 A
Indication CT L2 ph - 600/5 A class 1.0, 5 VA
Gas pressure indicator
Test facility
Integral cable test facility
Cable
Bottom entry up to 300 mm2 1 x 3C
Bottom entry up to 630 mm2 3 x 1C
Accessories
Actuator, 24 V DC
VPIS indication
Glands and plates
Interlocks
Busbar kit
Top entry cables
See page 74 for details
Order code
16 kA, 12 kV, 75 kV BIL
CE6-T5/16
CE6-T6/16
N/A
21 kA, 13.8 kV, 95 kV BIL
CE6-T5/21
CE6-T6/21
CE6-T22/21
b
b
Metering VT information:
Phase to phase
b
Phase to earth
b
6.6 kV/110 V
b
11 kV/110 V (1)
b
13.8 kV/110 V
General arrangement drawing RMINST-02
RMINST-02
RMINST-02
Page 99
Page 99
Page 99
Schematic diagram
RMSCH-10
RMSCH-10
RMSCH-37
Page 132
Page 132
Page 143
(1) Please consult Schneider Electric when ordering units with 95 kV BIL voltage
Tel: +44 (0)113 290 3500

76

CE6-T24/16
N/A

b
b
RMINST-02
Page 99
RMSCH-37
Page 143

AMTED399086EN

Circuit breaker, metering


and switches

Extensible circuit breaker 630 A


CE6-T8

DE60257

Feeder protection up to 12 MVA at 11 kV


Protection & control - CB
Self powered IDMT overcurrent and earth fault relay, VIP 300. In accordance with
IEC 60255 and BS142.
Protection CTs - 800/1 A class X
Shunt trip coil, 20 V DC-250 V AC
b Setting range:
v Overcurrent: 80-800 A
v Earth fault: 8-640 A
Documents
Installation drawing ref: RMINST-03
Schematic drawing ref: RMSCH-23
Environment
Indoor/outdoor
IP54
Ratings
Busbars 630 A
Short time withstand 16/21 kA 3 s
Internal arc 16/21 kA 1 s IAC class AF, A-FLR available on gas enclosure only
Normal current rating 630 A
Normal rated voltage 12/13.8 kV
Normal rated BIL 75/95 kV
Operating mechanism
Independent manual
Provision for actuator, 24 V DC
Standard features
Cable earth switch, 16/21 kA 3 s
Anti-reflex operating handle
Indication
Mechanical tripped on fault flag indicator
Mechanical ON/OFF indicator
Mechanical earth/main indicator
Auxiliary contacts,1NO 2 NC
Earth selected auxiliary contact1NO
Ammeter 0-600 A
Indication CT L2 ph - 600/5 A class 1.0, 5 VA
Gas pressure indicator
Test facility
Integral cable test facility
Cable
Bottom entry up to 300 mm2 1 x 3C
Bottom entry up to 630 mm2 3 x 1C
Accessories
Actuator, 24 V DC
VPIS indication
Glands and plates
Interlocks
Busbar kit
Top entry cables
See page 74 for details
Order information
Code
CE6-T8/16
CE6-T8/21

AMTED399086EN

Rating
16 kA, 12 kV, 75 kV BIL
21 kA, 13.8 kV, 95 kV BIL

77

Extensible circuit breaker 630 A

Circuit breaker, metering


and switches

CE6-T25

DE59803

Feeder protection up to 12 MVA at 11 kV


Protection & control - CB
IDMT overcurrent, earth-fault and thermal overload relay,
Sepam series 10. In accordance with IEC 60255
Power supply 24-48 VDC required
Protection CTs - 800/400/1 A 5P20
Setting range (800/1):
overcurrent: 80 - 630 A, earth-fault: 8 - 1920 A, sensitive earth-fault: 0.2 - 24 A
Setting range (400/1):
overcurrent: 40 - 630 A, earth-fault: 4 - 960 A, sensitive earth-fault: 0.2 - 24 A

50/51
50N/51N
49RMS

Documents (1)
Schematic drawing ref:
CE6 T25B: RMSCH-47
CE6 T25BS: RMSCH-48
CE6 T25A: RMSCH-49
CE6 T25AS: RMSCH-50
Environment
Indoor/outdoor
IP54
Ratings
Busbar 630 A
Short time withstand 16/21 kA 3 s
Internal arc 16/21 kA 1 s IAC class AF, A-FLR available on gas enclosure only
Normal current rating 630 A
Normal rated voltage 12/13.8 kV
Normal rated BIL 75/95 kV
Operating mechanism
Independent manual
Sepam 10 functions

ANSI
code

CE6-T25 (1)
B

BS A

Standard
0.012.4 In (2)

50N/51N b

Sensitive
0.224 A

50G/51G

AS

Protection
Earth-fault
protection

Phase-overcurrent protection
0.124 In (2)

50/51

Thermal overload protection

49RMS

Phase-overcurrent and
earth-fault cold load pick-up

Logic
Blocking send
68
discrimination Blocking reception

External tripping via digital input

Standard features
Cable earth switch, 16/21 kA 3 s
Anti-reflex operating handle
Indication
Mechanical tripped on fault flag indication
Mechanical ON/OFF indication
Mechanical earth/main indication
Gas pressure indication
CB auxiliary contacts 1NO 1NC (3)
Test facility
Integral ring switch cable test facility
Cable
Bottom entry up to 1 x 3C 300 mm
Bottom entry up to 3 x 1C 630 mm

Earth-fault current

Phase currents

Accessories - see table, page 74


Tee-off cable box
Glands and plates
Interlocks

Peak demand currents

Order information

Measurement

Control and supervision


Circuit breaker tripping
and lockout

86

Tripping annunciation

30

Relay watchdog contact

Remote CB position monitoring

Modbus

IEC 60870-5-103

Tripped on fault, volt free contact

Record of last fault


Record of last five events

Code (1)
CE6-T25B/21
CE6-T25BS/21
CE6-T25A/21
CE6-T25AS/21

Rating
21 kA, 13.8 kV, 95 kV BIL
21 kA, 13.8 kV, 95 kV BIL
21 kA, 13.8 kV, 95 kV BIL
21 kA, 13.8 kV, 95 kV BIL

Communications

(1) B (basic), BS (basic + sensitive earth-fault), A (advanced),


AS (advanced + sensitive earth-fault)
(2) In = Primary CT ratio
(3) Only with T25B and T25BS.

78

AMTED399086EN

Circuit breaker, metering


and switches

Extensible circuit breaker 630 A


CE6-T**

DE60199

Feeder protection up to 12 MVA at 11 kV


Protection & control - CB
Self powered IDMT overcurrent and earth fault relay, VIP 300. In accordance with
IEC 60255 and BS142.
Protection CTs - 800/1 A class X
Shunt trip coil, 20 V DC-250 V AC
b Setting range:
v Overcurrent: 80-800 A
v Earth fault: 8-640 A

(Select VT rating and switchgear rating from table below).

Metering transformers
b Metering CTs
v 400/200/5 A
v 10 VA class 0.5s
b Metering VT
v see below
Environment
Indoor/outdoor
IP54
Ratings
Busbars 630 A
Short time withstand 16/21 kA 3 s
Internal arc 16/21 kA 1 s IAC class AF, A-FLR available on gas enclosure only
Normal current rating 630 A
Normal rated voltage 12/13.8 kV
Normal rated BIL 75/95 kV
Operating mechanism
Independent manual
Standard features
Cable earth switch, 16/21 kA 3 s
Anti-reflex operating handle
Indication
Mechanical tripped on fault flag indicator
Mechanical ON/OFF indicator
Mechanical earth/main indicator
Auxiliary contacts,1NO 2 NC
Earth selected auxiliary contacts
Ammeter 0-600 A
Indication CT L2 ph- 600/5 A class 1.0, 5 VA
Gas pressure indicator
Test facility
Integral cable test facility
Cable
Bottom entry up to 300 mm2 1 x 3C
Bottom entry up to 630 mm2 3 x 1C
Accessories
VPIS indication
Glands and plates
Interlocks
Busbar kit
Top entry cables
See page 74 for details
Order code
16 kA, 12 kV, 75 kV BIL
CE6-T9/16
CE6-T10/16
N/A
21 kA, 13.8 kV, 95 kV BIL
CE6-T9/21
CE6-T10/21
CE6-T23/21
b
b
Metering VT information:
Phase to phase
b
Phase to earth
b
6.6 kV/110 V
b
11 kV/110 V (1)
b
13.8 kV/110 V
General arrangement drawing RMINST-02
RMINST-02
RMINST-02
Page 99
Page 99
Page 99
Schematic diagram
RMSCH-24
RMSCH-24
RMSCH-38
Page 140
Page 140
Page 144
(1) Please consult Schneider Electric when ordering units with 95 kV BIL voltage
Tel: +44 (0)113 290 3500

AMTED399086EN

79

Circuit breaker, metering


and switches

Extensible switches 630 A


Specification

SE6-S1
Manual operation

SE6-S2
Provision for actuator

SE6-E1
Busbar earth-switch
manual operation

b
b

b
b

b
b

b
b
b
b

b
b
b
b

b
b
b

b
b

Environment
Indoor / outdoor
IP54

Ratings
Busbars 630 A
Switch normal rated current 630 A
13.8 kV 21 kA 3 seconds 95 kV BIL
Cable earth switch 21 kA 3 seconds

Mechanism
Independent manual
Provision for actuator 24 V DC
Actuator 24 V DC
Operating handle

O
b

Indication
Mechanical ON/OFF
Mechanical EARTH/MAIN
Cable VPIS indication (6.6-13.8 kV)
Busbar VPIS indication (6.6-13.8 kV)
Auxiliary switch contacts1NO 1 NC
Phase and earth fault detection CTs for Easergy T200E
EFPI provision only CT inside box
Gas pressure indicator

b
b
v
v

b
b
v
v
v

O
b

O
O
b

b
b

Test facility
Integral cable test facility

Integral test facility


b

RH/LH busbar earthing

Cable (see available cable kit accessories)


b
Bottom entry up to 300 mm2 1 x 3C
b
Bottom entry up to 630 mm2 3 x 1C
Top entry cables
O
Key: b Standard feature v Factory fitted accessory O Loose accessory, assembled on site

80

b
b
O

AMTED399086EN

Circuit breaker, metering


and switches

Extensible switches 630 A


Accessories

SE6-S1
Manual operation

SE6-S2
Provision for
actuator

O
O
O
O
O
O
O
O
O
v

O
O
O
O
O
O
O
O
O
v

O
O
O
b

O
O
O
b

Kit no.
SE6-E1
Busbar earth-switch
manual operation

Cable kits
Gland plate 1 x 3C
Gland plate 3 x 1C
Angled gland plates (RMR)
Blank aluminium gland plate
Brass wiping gland 1 x 3C
Brass wiping gland 3 x 1C
Tubular gland 1 x 3C
Tubular gland 3 x 1C
CES5 gland plate 1 x 3C
Top entry cables

RMR-A48
RMR-A49
RMR-A50
RMR-A52
RMR-A10
RMR-A11
RMR-A12
RMR-A13
RMR-A132
RMR-F93

Installation items
3 phase busbars 630 A
Set of padlocks - 6 no
Busbar end kit (1 end kit required per switchboard)
Foundation bolts (not required for transformer mounting)
Multicore pilot glands

v
O
O
b

RMR-A14
RMR-A18/6
RMR-A15
RMR-A22
RMR-A16

RMR-A23
RMR-F108
RMR-F92
RMR-A24
RMR-A81
RMR-F67
RMR-F391

RMR-F85
RMR-F86

Operational items
Operating handle
Cable VPIS indication (6.6-13.8 kV)
Cable and busbar VPIS indication (6.6-13.8 kV)
Neon lamp test unit (including lamp)
Neon lamp
Actuator 24 V DC
Polarity conversion kit (1)

b
v
v

b
v
v

O
O

O
O
v
v

Mechanical interlocks
Key free, earth ON
Key free, main OFF
N. B. specify lock symbol at time of ordering ( 3 digits max) not
available with motor mechanisms

v
v

Indication
EFPI provision kit, inside cable box
Bowden STD EFPI NB
Bowden LV reset EFPI type NB1
Bowden LV reset & alarm type NB2
Bowden RR EFPI and CT
Fundamentals ER FIND EFPI and CT

O
O
O
O
O
O

O
O
O
O
O
O

RMR-F30
RMR-A277
RMR-A278
RMR-A279
RMR-A56
RMR-A57

Ancillary items
Tool box

RMR-A80

Order code
13.8 kV, 21 kA, 95 kV BIL, 0.55bG
General arrangement drawing

SE6-S2/21
RMINST-03
Page 100
Schematic drawing
RMSCH-29
Page 146
Key: b Standard feature v Factory fitted accessory O Loose accessory, assembled on site
(1) Only required when unit is used with RE2c ring main units and automation.

AMTED399086EN

SE6-S1/21
RMINST-03
Page 100
N/A

SE6-E1/21
RMINST-03
Page 100
N/A

81

Circuit breaker, metering


and switches

Extensible switch 630 A


SE6-S1

DE60201

Switch disconnector
Protection & control - CB
Non-automatic
Documents
Installation drawing ref: RMINST-03
Schematic drawing ref: RMSCH-N/A
Environment
Indoor/outdoor
IP54
Ratings
Busbars 630 A
Short time withstand 21 kA 3 s
Internal arc 16/21 kA 1 s IAC class AF, A-FLR available on gas enclosure only
Normal current rating 630 A
Normal rated voltage 13.8 kV
Normal rated BIL 95 kV
Operating mechanism
Independent manual
Standard features
Cable earth switch, 21 kA 3 s
Anti-reflex operating handles
Indication
Mechanical ON/OFF indicator
Mechanical earth/main indicator
Gas pressure indicator
Test facility
Integral cable test facility
Cable
Bottom entry up to 300 mm2 1 x 3C
Bottom entry up to 630 mm2 3 x 1C
Accessories
VPIS indication
Glands and plates
Interlocks
Busbar kit
Top entry cables
See page 81 for details
Order information
Code
SE6-S1/21

82

Rating
21 kA, 13.8 kV, 95 kVBIL

AMTED399086EN

Circuit breaker, metering


and switches

Extensible switch 630 A


SE6-S2

DE60202

Switch disconnector
Protection & control - CB
Non-automatic
Documents
Installation drawing ref: RMINST-03
Schematic drawing ref: RMSCH-29
Environment
Indoor/outdoor
IP54
Ratings
Busbars 630 A
Short time withstand 21 kA 3 s
Internal arc 16/21 kA 1 s IAC class AF, A-FLR available on gas enclosure only
Normal current rating 630 A
Normal rated voltage 13.8 kV
Normal rated BIL 95 kV
Operating mechanism
Independent manual
Provision for actuator, 24 V DC
Standard features
Cable earth switch, 21 kA 3 s
Anti-reflex operating handle
Indication
Mechanical ON/OFF indicator
Mechanical earth/main indicator
Auxiliary contacts,1NO 2NC
Earth selected auxiliary contact 1NO
Gas pressure indicator
Test facility
Integral cable test facility
Cable
Bottom entry up to 300 mm2 1 x 3C
Bottom entry up to 630 mm2 3 x 1C
Accessories
Actuator, 24 V DC
VPIS indication
Glands and plates
Interlocks
Busbar kit
Top entry cables
See page 81 for details
Order information
Code
SE6-S2/21

AMTED399086EN

Rating
21 kA, 13.8 kV, 95 kV BIL

83

Circuit breaker, metering


and switches

Extensible switch 630 A


SE6-E1

DE60203

Busbar earthing switch


Documents
Installation drawing ref: RMINST-03
Schematic drawing ref: RMSCH-N/A
Environment
Indoor/outdoor
IP54
Ratings
Busbars 630 A
Short time withstand 21 kA 3 s
Internal arc 16/21 kA 1 s IAC class AF, A-FLR available on gas enclosure only
Normal current rating 630 A
Normal rated voltage 13.8 kV
Normal rated BIL 95 kV
Operating mechanism
Independent manual
Standard features
Cable earth switch, 21 kA 3 s
Anti-reflex operating handle
Indication
Mechanical earth/main indicator
Gas pressure indicator
Test facility
N/A
Cable
N/A
Accessories
Interlocks
Busbar kit
See page 81 for details
Order information
Code
SE6-E1/21

84

Rating
21 kA, 13.8 kV, 95 kV BIL

AMTED399086EN

Circuit breaker, metering


and switches

Extensible bus-section 630 A


Specification

SE6-B1
Bus-section manual

CE6-B3
Bus-section manual
Metering

CE6-B5
Bus-section manual
Metering
Provision for actuator

b
b

b
b

b
b

b
b

b
b

Environment
Indoor / outdoor
IP54

Ratings
Busbars 630 A
Circuit breaker normal rated current 630 A
Switch normal rated current 630 A
12 kV 16 kA 3 seconds 75 kV BIL
13.8 kV 21 kA 3 seconds 95 kV BIL
RH busbar earth switch 16 kA 3 seconds
RH busbar earth switch 21 kA 3 seconds

b
b

O
b

O
b

b
b

O
b

b
b
b
b

b
b
b
b

b
b
b

b
b
b

b
b

b
b

b
b
b

O
b
b
b
b

O
b
b
b
b

Mechanism
Independent manual
Provision for actuator 24 V DC
Actuator 24 V DC
Operating handle

Protection system
CT ratio - 800/1 A class X
IDMT overcurrent & earth fault relay - VIP 300
20- 250 V shunt trip coil
Auxiliary switch1NO 2 NC

Metering
CTs - 400/200/5 A 0.5s 10 VA
VTs - 11 kA/110 V 0.5 50 VA
VTs phase - phase, CTs L1 & L3

Indication
Mechanical ON/OFF
Mechanical EARTH/MAIN
Earth selected auxiliary contact1NO
RH busbar VPIS indication
Auxiliary switch contacts1NO 2NC
Indication CT 600/5 A 5 VA CLS 1 L2 phase
Ammeter 0-600 A
Gas pressure indicator

Integral test facility


RH busbar earthing
LH busbar earthing ( using SE6-E1)
Key: b Standard feature O Optional feature

AMTED399086EN

85

Circuit breaker, metering


and switches

Extensible bus-section 630 A


Accessories

SE6-B1
Bus-section manual

CE6-B3
Bus-section manual
Metering

Kit no.
CE6-B5
Bus-section manual
Metering
Provision for actuator

v
v

v
v

v
v

O
O
b

O
O
b

O
O
b

b
v

b
v

b
v

O
O

O
O
O

v
v

v
v

N/A
SE6-B1/21
RMINST-01
Page 98
N/A

CE6-B3/16
CE6-B3/21
RMINST-01
Page 98
RMSCH-21
Page 137

CE6-B5/16
CE6-B5/21
RMINST-01
Page 98
RMSCH-22
Page 138

Installation items
3 phase busbars 630 A
3 phase busbars 630 A (Joggle metering)
3 phase busbars 630 A double width (metering)
Set of padlocks - XX no
Busbar end kit (1 end kit required per switchboard)
Foundation bolts (not required for transformer mounting)
Multicore pilot glands

RMR-A14
RMR-A79
RMR-A78
RMR-A18/6
RMR-A15
RMR-A22
RMR-A16

Operational items
Operating handle
LH and RH busbar VPIS indication
Neon lamp test unit (including lamp)
Neon lamp
VAP6 test unit for VIP 300
Actuator 24 V DC
Polarity conversion kit (1)

O
O
v
v

RMR-A23
RMR-F92
RMR-A24
RMR-A81
RMR-A202
RMR-F67
RMR-F391

Mechanical interlocks
Key free, earth ON
Key free, main OFF
N. B. specify lock symbol at time of ordering ( 3 digits max) not
available with motor mechanisms

RMR-F85
RMR-F86

Ancillary items
Tool box

RMR-A80

Order code
12 kV, 16 kA, 75 kV BIL, 0.35bG
13.8 kV, 21 kA, 95 kV BIL, 0.55bG
General arrangement drawing
Schematic drawing

Key: b Standard feature v Factory fitted accessory O Loose accessory, assembled on site
(1) Only required when unit is used with RE2c ring main units and automation.

86

AMTED399086EN

Circuit breaker, metering


and switches

Extensible bus-section 630 A


SE6-B1

DE60204

Bus-section disconnector
Protection & control
Non-automatic
Documents
Installation drawing ref: RMINST-01
Schematic drawing ref: N/A
Environment
Indoor/outdoor
IP54
Ratings
Busbars 630 A
Short time withstand 21 kA 3 s
Internal arc 16/21 kA 1 s IAC class AF, A-FLR available on gas enclosure only
Normal current rating 630 A
Normal rated voltage 13.8 kV
Normal rated BIL 95 kV
Operating mechanism
Independent manual
Standard features
RH busbar earth switch, 21 kA 3 s
Anti-reflex operating handle
Indication
Mechanical ON/OFF indicator
Mechanical earth/main indicator
Gas pressure indicator
Test facility
Integral RH busbar test facility
Cable
N/A
Accessories
VPIS indication
Interlocks
Busbars
See page 86 for details
Order information
Code
SE6-B1/21

AMTED399086EN

Rating
21 kA, 13.8 kV, 95 kV BIL

87

Circuit breaker, metering


and switches

Extensible bus-section 630 A


CE6-B3

DE60258

Bus-section circuit breaker


Protection & control - CB
Self powered IDMT overcurrent and earth fault relay, VIP 300. In accordance with
IEC 60255 and BS142.
Protection CTs - 800/1 A class X
Shunt trip coil, 20 V DC-250 V AC
b Setting range:
v Overcurrent: 80-800 A
v Earth fault: 8-640 A
Metering transformers
b Metering CTs
v 400/200/5 A
v 10 VA class 0.5s
b Metering VT ph-ph
v 11 kV/110 V 50 VA
v class 0.5
Documents
Installation drawing ref: RMINST-01
Schematic drawing ref: RMSCH-21
Environment
Indoor/outdoor
IP54
Ratings
Busbars 630 A
Short time withstand 16/21 kA 3 s
Internal arc 16/21 kA 1 s IAC class AF, A-FLR available on gas enclosure only
Normal current rating 630 A
Normal rated voltage 13.8 kV
Normal rated BIL 75/95 kV
Operating mechanism
Independent manual
Standard features
RH busbar earth switch, 16/21 kA 3 s
Anti-reflex operating handle
Indication
Mechanical tripped on fault flag indicator
Mechanical ON/OFF indicator
Mechanical earth/main indicator
Auxiliary contacts,1NO 2 NC
Ammeter 0-600 A
Indication CT L2 ph- 600/5 A class 1.0 5 VA
Gas pressure indicator
Test facility
Integral RH busbar test facility
Cable
N/A
Accessories
VPIS indication
Interlocks
Busbars
See page 86 for details
Order information
Code
CE6-B3/16
CE6-B3/21

88

Rating
16 kA, 12 kV, 75 kV BIL
21 kA, 13.8 kV, 95 kV BIL

AMTED399086EN

Circuit breaker, metering


and switches

Extensible bus-section 630 A


CE6-B5

DE60259

Bus-section circuit breaker


Protection & control - CB
Self powered IDMT overcurrent and earth fault relay, VIP 300. In accordance with
IEC 60255 and BS142.
Protection CTs - 800/1 A class X
Shunt trip coil, 20 V DC-250 V AC
b Setting range:
v Overcurrent: 80-800 A
v Earth fault: 8-640 A
Metering transformers
b Metering CTs
v 400/200/5 A
v 10 VA class 0.5s
b Metering VT ph-ph
v 11 kV/110 V 50 VA
v class 0.5
Documents
Installation drawing ref: RMINST-01
Schematic drawing ref: RMSCH-22
Environment
Indoor/outdoor
IP54
Ratings
Busbars 630 A
Short time withstand 16/21 kA 3 s
Internal arc 16/21 kA 1 s IAC class AF, A-FLR available on gas enclosure only
Normal current rating 630 A
Normal rated voltage 13.8 kV
Normal rated BIL 75/95 kV
Operating mechanism
Independent manual
Provision for actuator, 24 V DC
Standard features
RH busbar earth switch, 16/21 kA 3 s
Anti-reflex operating handle
Indication
Mechanical tripped on fault flag indicator
Mechanical ON/OFF indicator
Mechanical earth/main indicator
Auxiliary contacts,1NO 2 NC
Earth selected auxiliary contacts1NO
Ammeter 0-600 A
Indication CT L2 ph- 600/5 A class 1.0 5 VA
Gas pressure indicator
Test facility
Integral RH busbar test facility
Cable
N/A
Accessories
Actuator, 24 V DC
VPIS indication
Interlocks
Busbars
See page 86 for details
Order information
Code
CE6-B5/16
CE6-B5/21

AMTED399086EN

Rating
16 kA, 12 kV, 75 kV BIL
21 kA, 13.8 kV, 95 kV BIL

89

90

AMTED399086EN

Remote control

Contents

Telecontrol cabinet
Easergy T200 E - Specification
Easergy T200-E02M
Easergy T200-E04M

AMTED399086EN

92
93
93

91

Remote control

Telecontrol cabinet
Easergy T200 E - Specification

Easergy T200-E02M
2 functions

Easergy T200-E04M
4 functions

b
b

b
b

b
b
b

b
b
b

b
b

b
b

b
b
b
b

b
b
b
b

b
b
b

b
b
b

b
b
b
b

b
b
b
b

b
b
b

b
b
b

b
b
b
b

b
b
b
b

b
b
b
b
b
b
b

b
b
b
b
b
b
b

b
b
b
b
b
b
b

b
b
b
b
b
b
b

Environment
Indoor / outdoor
IP54

Communication
Modbus
IEC 870-5-101 and IEC 870-5-104
DNP3
2 additional modem ports with GSM or GPRS

Standard features
Freestanding/wall mounted/ switchgear mounted
Removable radio bracket ( no radio supplied)

Inputs to cabinet
Switch open - per switch
Switch closed - per switch
Earth selector earth/mains - per switch
1 spare - per switch

Control output to switchgear


To switch
- Open switch
- Close switch
- Reset external FPI

Output to SCADA
- Switch open
- Switch closed
- Earth selector earth/main
- Fault passage indication - phase and/or earth fault
From cabinet
- Local/remote failure
- Mains/equipment failure
- Battery and charger alarms

Local control
Push button open/close switch
Local/remote selector
Reset/test integral FPI
Power restart

Local indication
Mains present
Battery fault
Internal supplies on
Switch status - open/closed
FPI operated
Local/remote mode selected
Equipment fault (watchdog)

Battery and charger


Telecomms equipment - 12 V DC
Control unit - 12 V DC
Power supply 90-270 V AC 50 Hz 120 VA
Switchgear 24 V DC
1 x 24 Ah sealed lead acid
20 degrees C, 3 hours after loss of supply
5 c/o switch operations
Key: b Standard feature O Optional feature

92

AMTED399086EN

Remote control

Telecontrol cabinet
Easergy T200-E02M
Easergy T200-E04M

DE60195

Telecontrol cabinet - Up to 2 switch control (T200-E02M)


Telecontrol cabinet - Up to 4 switch control (T200-E04M)
Local indication
Mains failure, battery fault, internal supplies on,
Switch status - open/closed, FPI operated, local/remote mode selected, equipment
fault (Watchdog)
Inputs to cabinet
Switch open
Switch closed
Earth selector earth/mains
3 spare
Control outputs to switchgear
b To switch
v Open switch
v Close switch
v Reset FPI
Local control
Push button open/close switch
Local/remote selector
Reset/test integral FPI
Optional features
b Integral phase and earth fault passage indicator
b 3 phase RMS current measurement
b Wall mounted/freestanding
Documents
Installation drawing ref: RMINST-11
Schematic drawing ref: RMSCH-17
Environment
Indoor/outdoor
IP54
Dimensions
480 x 370 x 280 mm
Communication
b Modbus
v IEC 870-5-101 and IEC 870-5-104
v DNP3
v 2 additional modem ports with GSM or GPRS
Standard features
Switchgear mounted removable radio bracket ( no radio/modem supplied)
Outputs to SCADA
b Switch open
b Switch closed
b Earth selector earth/main
b Fault passage indication - phase and/or earth fault
b From cabinet
v Local/remote mode
v Mains/equipment failure
v other configurable alarms
Batteries and charger
Telecomms equipment - 12 V DC
Control unit - 12 V DC
Switchgear - 24 V DC
1 x 24 Ah sealed lead acid
Power supply
90-270 V AC 50 Hz 120 VA
Autonomy
20C 5 hours after loss of supply
5 C/O switch operations
Deep discharge protection
Order information
T200-E02M
T200-E04M

AMTED399086EN

93

94

AMTED399086EN

Installation drawings

Contents

Summary

96

Typical switchboard

97

Extensible units

98

ref RMINST-01, RMINST-02, RMINST-03

Non-extensible unit

101

ref RMINST-04

Extensible ring main unit

102

c/w tee off cable box - ref RMINST-22

Non-extensible ring main units

103

for transformer mounting unit - ref RMINST-06


c/w MU2 metering unit & tee off cable box - ref RMINST-08

Non-extensible metering unit

105

ref RMINST-07

Telecontrol cabinet

106

ref RMINST-11

AMTED399086EN

95

Installation drawings

Summary

Non-extensible equipment
Schematic
diagram

Page number

General arrangement
drawing

Page number

Ring main units 200 A

RN2c-T1
RN2c-T2
RN2c-T3
RN2c-T4
RN2c-T5
RN2c-T25B
RN2c-T25BS
RN2c-T25A
RN2c-T25AS

RMSCH-01
RMSCH-03
RMSCH-02
RMSCH-15
RMSCH-01
RMSCH-43
RMSCH-44
RMSCH-45
RMSCH-46

112
114
113
115
112
116
117
118
119

RMINST-06
RMINST-06
RMINST-06
RMINST-06
RMINST-06
RMINST-06
RMINST-06
RMINST-06
RMINST-06

103
103
103
103
103
103
103
103
103

Ring main units 630 A

RN6c-T1
RN6c-T25B
RN6c-T25BS
RN6c-T25A
RN6c-T25AS

RMSCH-42
RMSCH-43
RMSCH-44
RMSCH-45
RMSCH-46

120
116
117
118
119

RMINST-06
RMINST-06
RMINST-06
RMINST-06
RMINST-06

103
103
103
103
103

Circuit breakers 200 A

CN2-T1
CN2-T6
CN2-T25B
CN2-T25BS
CN2-T25A
CN2-T25AS

RMSCH-26
RMSCH-11
RMSCH-47
RMSCH-48
RMSCH-49
RMSCH-50

127
126
122
123
124
125

RMINST-04
RMINST-06
RMINST-03
RMINST-03
RMINST-03
RMINST-03

101
103
100
100
100
100

Switches 630 A

SN6-S1
SN6-S2

N/A
RMSCH-28

145

RMINST-04
RMINST-04

101
101

Metering units

MU2-M1, MU2-M2, MU2-M3


MU6-N1, MU6-N2, MU6-N3
MU6-N5

RMSCH-14
RMSCH-14
RMSCH-14

121
121
121

RMINST-07/08
RMINST-07/08
RMINST-07/08

105-104
105-104
105-104

Telecontrol cabinets

Easergy T200-E02M
Easergy T200-E04M

RMSCH-17
RMSCH-17

147
147

RMINST-11
RMINST-11

106
106

Schematic
diagram

Page number

General arrangement
drawing

Page number

Extensible equipment
Ring main units 200 A

RN2c-T1
RN2c-T2
RN2c-T3
RN2c-T4
RE2c-T25B
RE2c-T25BS
RE2c-T25A
RE2c-T25AS

RMSCH-01
RMSCH-03
RMSCH-02
RMSCH-15
RMSCH-43
RMSCH-44
RMSCH-45
RMSCH-46

112
114
113
115
116
117
118
119

RMINST-06
RMINST-06
RMINST-06
RMINST-06
RMINST-06
RMINST-06
RMINST-06
RMINST-06

103
103
103
103
103
103
103
103

Circuit breakers 200 A

CE2-T2
CE2-T3
CE2-T7
CE2-T11
CE2-T12
CE2-T13
CE2-T14
CE2-T15
CE2-T16
CE2-T19
CE2-T20
CE2-T21
CE2-T25B
CE2-T25BS
CE2-T25A
CE2-T25AS

RMSCH-07
RMSCH-09
RMSCH-06
RMSCH-09
RMSCH-19
RMSCH-20
RMSCH-20
RMSCH-12
RMSCH-13
RMSCH-35
RMSCH-35
RMSCH-36
RMSCH-47
RMSCH-48
RMSCH-49
RMSCH-50

129
131
128
131
135
136
136
133
134
141
141
142
122
123
124
125

RMINST-03
RMINST-02
RMINST-03
RMINST-02
RMINST-03
RMINST-02
RMINST-02
RMINST-03
RMINST-03
RMINST-02
RMINST-02
RMINST-02
RMINST-02
RMINST-02
RMINST-02
RMINST-02

100
99
100
99
100
99
99
100
100
99
99
99
99
99
99
99

Circuit breakers 630 A

CE6-T4
CE6-T5
CE6-T6
CE6-T8
CE6-T9
CE6-T10
CE6-T22
CE6-T23
CE6-T24
CE6-T25B
CE6-T25BS
CE6-T25A
CE6-T25AS

RMSCH-08
RMSCH-10
RMSCH-10
RMSCH-23
RMSCH-24
RMSCH-24
RMSCH-37
RMSCH-38
RMSCH-37
RMSCH-47
RMSCH-48
RMSCH-49
RMSCH-50

130
132
132
139
140
140
143
144
143
122
123
124
125

RMINST-03
RMINST-02
RMINST-02
RMINST-03
RMINST-02
RMINST-02
RMINST-02
RMINST-02
RMINST-02
RMINST-02
RMINST-02
RMINST-02
RMINST-02

100
99
99
100
99
99
99
99
99
99
99
99
99

Switches 630 A

SE6-S1
SE6-S2
SE6-E1

N/A
RMSCH-29
N/A

146
-

RMINST-03
RMINST-03
RMINST-03

100
100
100

Bus sections 630 A

SE6-B1
CE6-B3
CE6-B5

N/A
RMSCH-21
RMSCH-22

137
138

RMINST-01
RMINST-01
RMINST-01

98
98
98

96

AMTED399086EN

Typical switchboard

DE59806

Installation drawings

799

Note: for installation where overpressure relief of the equipment is required please contact
Schneider Electric Tel: +44 (0)113 290 3500
Note: for civil engineering and recommendations for internal arc clearances please consult
our installation and maintenance instructions Ref: SE 6251 or contact Schneider Electric
Tel: +44 (0)113 290 3500

AMTED399086EN

97

Installation drawings

Extensible unit

DE59807

ref RMINST-01

799

Panel type
SE6-B1
CE6-B3
CE6-B5
Approximate weight: 450 kg

Page number
87
88
89

Note: for installation where overpressure relief of the equipment is required please contact
Schneider Electric Tel: +44 (0)113 290 3500
Note: for civil engineering and recommendations for internal arc clearances please consult
our installation and maintenance instructions Ref: SE 6251 or contact Schneider Electric
Tel: +44 (0)113 290 3500

98

AMTED399086EN

Installation drawings

Extensible unit

DE59808

ref RMINST-02

799

Panel type
CE2-T3
CE2-T11
CE2-T13
CE2-T14
CE2-T19
CE2-T20
CE2-T21
CE6-T5
CE6-T6
CE6-T9
CE6-T10
CE6-T22
CE6-T23
CE6-T24
Approximate weight: 450 kg

Page number
66
66
69
68
66
66
68
76
76
79
79
76
79
76

Note: for installation where overpressure relief of the equipment is required please contact
Schneider Electric Tel: +44 (0)113 290 3500
Note: for civil engineering and recommendations for internal arc clearances please consult
our installation and maintenance instructions Ref: SE 6251 or contact Schneider Electric
Tel: +44 (0)113 290 3500

AMTED399086EN

99

Installation drawings

Extensible unit

DE59809

ref RMINST-03

799

Panel type
CE2-T2
CE2-T7
CE2-T12
CE6-T4
CE6-T8
SE6-S1
SE6-S2
SE6-E1
Approximate weight: 250 kg

Page number
64
65
67
75
77
82
83
84

Note: for installation where overpressure relief of the equipment is required please contact
Schneider Electric Tel: +44 (0)113 290 3500
Note: for civil engineering and recommendations for internal arc clearances please consult
our installation and maintenance instructions Ref: SE 6251 or contact Schneider Electric
Tel: +44 (0)113 290 3500

100

AMTED399086EN

Installation drawings

Non-extensible unit

DE59811

ref RMINST-04

Panel type
CN2-T1
CN2-T6
SN6-S1
SN6-S2
Approximate weight: 250 kg

Page number
46
47
51
52

Note: for installation where overpressure relief of the equipment is required please contact
Schneider Electric Tel: +44 (0)113 290 3500
Note: for civil engineering and recommendations for internal arc clearances please consult
our installation and maintenance instructions Ref: SE 6251 or contact Schneider Electric
Tel: +44 (0)113 290 3500

AMTED399086EN

101

Installation drawings

Extensible ring main unit

DE59810

c/w tee off cable box


ref RMINST-22

985

Panel type
RE2c-T1
RE2c-T2
RE2c-T3
RE2c-T4
Approximate weight: 300 kg

Page number
36
37
38
39

Note: for installation where overpressure relief of the equipment is required please contact
Schneider Electric Tel: +44 (0)113 290 3500
Note: for civil engineering and recommendations for internal arc clearances please consult
our installation and maintenance instructions Ref: SE 6251 or contact Schneider Electric
Tel: +44 (0)113 290 3500

102

AMTED399086EN

Installation drawings

Non-extensible ring main unit

DE60268

DE59812

for transformer mounting unit


ref RMINST-06

Panel type
RN2c-T1
RN2c-T2
RN2c-T3
RN2c-T4
RN2c-T5
RN6c-T1
Approximate weight: 300 kg

Page number
25
26
27
28
29
31

Note: for installation where overpressure relief of the equipment


is required please contact Schneider Electric
Tel: +44 (0)113 290 3500
Note: for civil engineering and recommendations for internal arc
clearances please consult our installation and maintenance
instructions Ref: SE 6251 or contact Schneider Electric
Tel: +44 (0)113 290 3500

AMTED399086EN

103

Installation drawings

Non-extensible ring main unit

DE59814

c/w MU2 metering unit & tee off cable box


ref RMINST-08

Panel type
Page number
MU2-M1
55
MU2-M2
56
MU2-M3
57
MU6-N1
60
MU6-N2
60
MU6-N3
60
MU6-N5
60
Approximate weight: 200 kg (MU2 only)
MU2 shown connected to a non-extensible ring main unit
Note: for installation where overpressure relief of the equipment is required please contact
Schneider Electric Tel: +44 (0)113 290 3500
Note: for civil engineering and recommendations for internal arc clearances please consult
our installation and maintenance instructions Ref: SE 6251 or contact Schneider Electric
Tel: +44 (0)113 290 3500

104

AMTED399086EN

Installation drawings

Non-extensible metering unit

DE59813

ref RMINST-07

Panel type
MU2-M1
MU2-M2
MU2-M3
MU6-N1
MU6-N2
MU6-N3
MU6-N5
Approximate weight: 450 kg

Page number
55
56
57
60
60
60
60

Note: for installation where overpressure relief of the equipment is required please contact
Schneider Electric Tel: +44 (0)113 290 3500
Note: for civil engineering and recommendations for internal arc clearances please consult
our installation and maintenance instructions Ref: SE 6251 or contact Schneider Electric
Tel: +44 (0)113 290 3500

AMTED399086EN

105

Installation drawings

Telecontrol cabinet

DE60268

DE59815

ref RMINST-11

Panel type
Page number
Easergy T200-E02
93
Easergy T200-E04
93
Approximate weight: 30 kg (Easergy only)
Note: for installation where overpressure relief of the equipment
is required please contact Schneider Electric
Tel: +44 (0)113 290 3500
Note: for civil engineering and recommendations for internal arc
clearances please consult our installation and maintenance
instructions Ref: SE 6251 or contact Schneider Electric
Tel: +44 (0)113 290 3500

106

AMTED399086EN

Schematic diagrams

Contents

Schematic legends

108

Specification

Ring main units accessories

110

Non-extensible / extensible ring main units

112

ref RMSCH-01, RMSCH-02, RMSCH-03, RMSCH-15,


RMSCH-43, RMSCH-44, RMSCH-45, RMSCH-46

Non-extensible ring main unit

120

ref RMSCH-42

Non-extensible metering unit

121

ref RMSCH-14

Non-extensible / extensible circuit breaker units

122

ref RMSCH-47, RMSCH-48, RMSCH-49, RMSCH-50

Non-extensible circuit breaker units

126

ref RMSCH-11, RMSCH-26

Extensible circuit breaker units

128

ref RMSCH-06, RMSCH-07, RMSCH-08, RMSCH-09,


RMSCH-10, RMSCH-12, RMSCH-13, RMSCH-19,
RMSCH-20, RMSCH-21, RMSCH-22, RMSCH-23, RMSCH-24,
RMSCH-35, RMSCH-36, RMSCH-37, RMSCH-38

Non-extensible switch units

145

ref RMSCH-28, RMSCH-29

Telecontrol unit block diagram

147

ref RMSCH-17

AMTED399086EN

107

Schematic diagrams

Schematic legends
Specification

Fuse schedule
F1
F2

VT secondary 16 A/link metering


VT secondary 2 A/link metering

Legends
EPS
MR
RL1
RL2
52
89
96
TFL
/b
/a
/c
A
STC
ITC
50
51
50N
51N
INC
M
EFPI
EPSR
EPSL
ESR
ESL
TRS

earth position selected auxiliary


mechanism reset switch
close relay
open relay
circuit breaker
switch
direct acting trip coil
time fuse link
normally closed auxiliary contact
normally open auxiliary contact
normally open make auxiliary contact
ammeter
shunt trip coil
integral trip coil
instantaneous overcurrent
time delayed overcurrent
instantaneous earth fault
time delayed earth fault
minimum operating current
actuator
earth fault passage indicator
earth position selector right
earth position selector left
earth switch right
earth switch left
trip reset spring

DE60269

Symbols

108

CT & VT Ratios
Panel type CT1
RN2c-T1

100/50/5 A
Class X

RN2c-T2

200/1 A
Class X

RN2c-T3

500/200/1 A
Class X

RN2c-T4

500/200/1 A
Class X

RN2c-T5

100/50/5 A
Class X

RN2c-T25

200/100/1 A
5P20

RN6c-T1

800/400/1 A
Class X

RN6c-T25

800/400/1 A
5P20

RE2c-T1

100/50/5 A
Class X

RE2c-T2

200/1 A
Class X

RE2c-T3

500/200/1 A
Class X

RE2c-T4

500/200/1 A
Class X

RE2c-T25

200/100/1 A
5P20

CT2

CT3

CT4

VT1

VT2

MU2-M1

50/25/5 A
7.5 VA Class 0.5s

11000/110 V
50 VA Class 0.5

MU2-M2

100/50/5 A
10 VA Class 0.5s

11000/110 V
50 VA Class 0.5

MU2-M3

200/100/5 A
10 VA Class 0.5s

11000/110 V
50 VA Class 0.5

CN2-T1

200/1 A
Class X

CN2-T6

100/50/5 A
Class X

CN2-T25

200/100/1 A
5P20

CE2-T7

100/50/5 A
Class X

CE2-T2

200/1 A
Class X

CE2-T3

200/1 A
Class X

200/100/5 A
10 VA Class 0.5s

11000/110 V
50 VA Class 0.5

CE2-T11

200/1 A
Class X

200/100/5 A
10 VA Class 0.5s

6600/110 V
50 VA Class 0.5

CE2-T12

200/1 A
Class X

CE2-T13

200/1 A
Class X

200/100/5 A
10 VA Class 0.5s

11000/110 V
50 VA Class 0.5

CE2-T14

200/1 A
Class X

200/100/5 A
10 VA Class 0.5s

6600/110 V
50 VA Class 0.5

CE2-T15

200/1 A
Class X

CE2-T16

200/1 A
Class X

CE2-T19

200/1 A
Class X

200/100/5 A
10 VA Class 0.5s

13800/110 V/110 V
50 VA Class 0.5
20 VA class 3 P

CE2-T20

200/1 A
Class X

200/100/5 A
10 VA Class 0.5s

11000/110 V/110 V
50 VA Class 0.5
20 VA class 3 P

CE2-T21

200/1 A
Class X

200/100/5 A
10 VA Class 0.5s

13800/110 V/110 V
50 VA Class 0.5
20 VA class 3 P

CE2-T25

200/100/1 A
5P20

AMTED399086EN

Schematic diagrams

Schematic legends
Specification

Conditions
1. All relays de-energised
2. Switches shown in open position
3. Auxiliary switch only operated between main ON and main
OFF position (i.e. does not operate in earth position).

CT and VT types
CTI
CT2
CT3
CT4
VT1
VT2

3 phase protection CTs


1 phase indication CT
2 phase metering CT
Easergy 200E phase & earth fault Ct
Ph-Ph metering VT (2 phases)
Ph-E metering VT (3 phases)

AMTED399086EN

CT & VT Ratios
Panel type CT1

CT2

CT3

CT4

VT1

VT2

CE6-T4

800/1 A
Class X

600/5 A
5 VA Class 1.0

CE6-T5

800/1 A
Class X

600/5 A
400/200/5 A
5 VA Class 1.0 10 VA Class 0.5s

11000/110 V
50 VA Class 0.5

CE6-T6

800/1 A
Class X

600/5 A
400/200/5 A
5 VA Class 1.0 10 VA Class 0.5s

6600/110 V
50 VA Class 0.5

CE6-T8

800/1 A
Class X

600/5 A
5 VA Class 1.0

CE6-T9

800/1 A
Class X

600/5 A
400/200/5 A
5 VA Class 1.0 10 VA Class 0.5s

11000/110 V
50 VA Class 0.5

CE6-T10

800/1 A
Class X

600/5 A
400/200/5 A
5 VA Class 1.0 10 VA Class 0.5s

6600/110 V
50 VA Class 0.5

CE6-T22

800/1 A
Class X

600/5 A
400/200/5 A
5 VA Class 1.0 10 VA Class 0.5s

13800/110 V/110 V
50 VA Class 0.5
20 VA class 3 P

CE6-T23

800/1 A
Class X

600/5 A
400/200/5 A
5 VA Class 1.0 10 VA Class 0.5s

13800/110 V/110 V
50 VA Class 0.5
20 VA class 3 P

CE6-T24

800/1 A
Class X

600/5 A
400/200/5 A
5 VA Class 1.0 10 VA Class 0.5s

11000/110 V/110 V
50 VA Class 0.5
20 VA class 3 P

CE6-T25

800/400/1 A
5P20

CE6-B3

800/1 A
Class X

600/5 A
400/200/5 A
5 VA Class 1.0 10 VA Class 0.5s

11000/110 V
50 VA Class 0.5

CE6-B5

800/1 A
Class X

600/5 A
400/200/5 A
5 VA Class 1.0 10 VA Class 0.5s

11000/110 V
50 VA Class 0.5

SE6-S2

800/1 A
Class X

600/5 A
5 VA Class 1.0

500/1 A
Class X

SN6-S2

800/1 A
Class X

600/5 A
5 VA Class 1.0

500/1 A
Class X

109

Ring main units accessories

DE59820

Schematic diagrams

L1

110

L2

L3

AMTED399086EN

Ring main units accessories

Schematic diagrams

DE59821

Circuit breaker

AMTED399086EN

111

Non-extensible / extensible
ring main unit

Schematic diagrams

DE59822-1

ref RMSCH-01

L1

L2

L3

PROVISION FOR
SHUNT TRIP COIL

Panel type
RN2c-T1
RE2c-T1
For explanation of symbols see page 108

112

Page number
25
36

AMTED399086EN

Non-extensible / extensible
ring main unit

Schematic diagrams

DE59824-1

ref RMSCH-02

L1

L2

L3

PROVISION FOR
SHUNT TRIP COIL

Panel type
RN2c-T3
RE2c-T3
For explanation of symbols see page 108

AMTED399086EN

Page number
27
38

113

Non-extensible / extensible
ring main unit

Schematic diagrams

DE59823-1

ref RMSCH-03

L1

L2

L3

PROVISION FOR
SHUNT TRIP COIL

Panel type
RN2c-T2
RE2c-T2
For explanation of symbols see page 108

114

Page number
26
37

AMTED399086EN

Non-extensible / extensible
ring main unit

Schematic diagrams

DE59825-1

ref RMSCH-15

L1

L2

L3

PROVISION FOR
SHUNT TRIP COIL

Panel type
RN2c-T4
RE2c-T4
For explanation of symbols see page 108

AMTED399086EN

Page number
28
39

115

Schematic diagrams

Non-extensible / extensible
ring main unit

DE59853

ref RMSCH-43

Panel type
RN2c-T25
RE2c-T25
For explanation of symbols see page 108

116

Page number
30
40

AMTED399086EN

Schematic diagrams

Non-extensible / extensible
ring main unit

DE59854

ref RMSCH-44

Panel type
RN2c-T25
RE2c-T25
For explanation of symbols see page 108

AMTED399086EN

Page number
30
40

117

Schematic diagrams

Non-extensible / extensible
ring main unit

DE59855

ref RMSCH-45

Panel type
RN2c-T25
RE2c-T25
For explanation of symbols see page 108

118

Page number
30
40

AMTED399086EN

Schematic diagrams

Non-extensible / extensible
ring main unit

DE59856

ref RMSCH-46

Panel type
Page number
RN2c-T25
30
RE2c-T25
40
For explanation of symbols see page 108

AMTED399086EN

119

Non-extensible ring main unit

Schematic diagrams

DE59826

ref RMSCH-42

L1

L2

L3

Panel type
RN6c-T1
For explanation of symbols see page 108

120

Page number
31

AMTED399086EN

Non-extensible metering unit

Schematic diagrams

DE59834

ref RMSCH-14

L1

L3

Panel type
MU2-M1
MU2-M2
MU2-M3
MU6-N1
MU6-N2
MU6-N3
MU6-N5
For explanation of symbols see page 108

AMTED399086EN

Page number
55
56
57
60
60
60
60

121

Schematic diagrams

Non-extensible / extensible
circuit breaker units

DE59857

ref RMSCH-47

Panel type
CN2-T25
CE2-T25
CE6-T25
For explanation of symbols see page 108

122

Page number
48
72
78

AMTED399086EN

Schematic diagrams

Non-extensible / extensible
circuit breaker units

DE59858

ref RMSCH-48

Panel type
CN2-T25
CE2-T25
CE6-T25
For explanation of symbols see page 108

AMTED399086EN

Page number
48
72
78

123

Schematic diagrams

Non-extensible / extensible
circuit breaker units

DE59859

ref RMSCH-49

Panel type
CN2-T25
CE2-T25
CE6-T25
For explanation of symbols see page 108

124

Page number
48
72
78

AMTED399086EN

Schematic diagrams

Non-extensible / extensible
circuit breaker units

DE59860

ref RMSCH-50

Panel type
CN2-T25
CE2-T25
CE6-T25
For explanation of symbols see page 108

AMTED399086EN

Page number
48
72
78

125

Non-extensible
circuit breaker units

Schematic diagrams

DE59833

ref RMSCH-11

L1

L2

L3

Panel type
CN2-T6
For explanation of symbols see page 108

126

Page number
47

AMTED399086EN

Non-extensible
circuit breaker units

Schematic diagrams

DE59843

ref RMSCH-26

L1

L2

L3

Panel type
CN2-T1
For explanation of symbols see page 108

AMTED399086EN

Page number
46

127

Extensible circuit breaker units

Schematic diagrams

DE59828

ref RMSCH-06

L1

L2

L3

Panel type
CE2-T7
For explanation of symbols see page 108

128

Page number
65

AMTED399086EN

Extensible circuit breaker units

Schematic diagrams

DE59829

ref RMSCH-07

L1

L2

L3

Panel type
CE2-T2
For explanation of symbols see page 108

AMTED399086EN

Page number
64

129

Extensible circuit breaker units

Schematic diagrams

DE59830

ref RMSCH-08

L1

L2

L3

L2

Panel type
CE6-T4
For explanation of symbols see page 108

130

Page number
75

AMTED399086EN

Extensible circuit breaker units

Schematic diagrams

DE59831

ref RMSCH-09

L1

L1

L2

L3

L3

Panel type
CE2-T3
CE2-T11
For explanation of symbols see page 108

AMTED399086EN

Page number
66
66

131

Extensible circuit breaker units

Schematic diagrams

DE59832

ref RMSCH-10

L1

L2

L3

L2

L2

L1

L3

Panel type
CE6-T5
CE6-T6
For explanation of symbols see page 108

132

Page number
76
76

AMTED399086EN

Schematic diagrams

Extensible circuit breaker units

DE59835

ref RMSCH-12

L1

L2

L3

Panel type
CE2-T15
For explanation of symbols see page 108

AMTED399086EN

Page number
70

133

Schematic diagrams

Extensible circuit breaker units

DE59835

ref RMSCH-13

L1

L2

L3

Panel type
CE2-T16
For explanation of symbols see page 108

134

Page number
71

AMTED399086EN

Extensible circuit breaker units

Schematic diagrams

DE59837

ref RMSCH-19

L1

L2

L3

Panel type
CE2-T12
For explanation of symbols see page 108

AMTED399086EN

Page number
67

135

Schematic diagrams

Extensible circuit breaker units

DE59838

ref RMSCH-20

L1

L1

L2

L3

L3

Panel type
CE2-T13
CE2-T14
For explanation of symbols see page 108

136

Page number
69
68

AMTED399086EN

Extensible circuit breaker units

Schematic diagrams

DE59839

ref RMSCH-21

L1

L2

L3

L2

L1

L3

Panel type
CE6-B3
For explanation of symbols see page 108

AMTED399086EN

Page number
88

137

Schematic diagrams

Extensible circuit breaker units

DE59840

ref RMSCH-22

L1

L2

L3

L2

L1

L3

Panel type
CE6-B5
For explanation of symbols see page 108

138

Page number
89

AMTED399086EN

Schematic diagrams

Extensible circuit breaker units

DE59841

ref RMSCH-23

L1

L2

L3

L2

Panel type
CE6-T8
For explanation of symbols see page 108

AMTED399086EN

Page number
77

139

Schematic diagrams

Extensible circuit breaker units

DE59842

ref RMSCH-24

L1

L2

L3

L2

L1

L3

Panel type
CE6-T9
CE6-T10
For explanation of symbols see page 108

140

Page number
79
79

AMTED399086EN

Schematic diagrams

Extensible circuit breaker units

DE59846

ref RMSCH-35

L1

L2

L3

L1

L2

L3

Panel type
CE2-T19
CE2-T20
For explanation of symbols see page 108

AMTED399086EN

Page number
66
66

141

Schematic diagrams

Extensible circuit breaker units

DE59847

ref RMSCH-36

L1

L2

L3

L1

L2

L3

Panel type
CE2-T21
For explanation of symbols see page 108

142

Page number
68

AMTED399086EN

Schematic diagrams

Extensible circuit breaker units

DE59848

ref RMSCH-37

L1

L2

L3

L2

L1

L2

L3

Panel type
CE6-T22
CE6-T24
For explanation of symbols see page 108

AMTED399086EN

Page number
76
76

143

Schematic diagrams

Extensible circuit breaker units

DE59849

ref RMSCH-38

L1

L2

L3

L2

L1

L2

L3

Panel type
CE6-T23
For explanation of symbols see page 108

144

Page number
79

AMTED399086EN

Schematic diagrams

Non-extensible switch units

DE59844

ref RMSCH-28

L1

L2

L3

Panel type
SN6-S2
For explanation of symbols see page 108

AMTED399086EN

Page number
52

145

Schematic diagrams

Non-extensible switch units

DE59845

ref RMSCH-29

L1

L2

L3

Panel type
SE6-S2
For explanation of symbols see page 108

146

Page number
83

AMTED399086EN

Schematic diagrams

Telecontrol unit block diagram

DE59827

ref RMSCH-17

90-230 V AC
50 Hz

L1
L2
L3

Panel type
Easergy T200-E02M
Easergy T200-E04M
For explanation of symbols see page 108

AMTED399086EN

Page number
93
93

147

148

AMTED399086EN

Accessories & options

Contents

Accessories description

150

MV substation remote monitoring unit - Flair 200C


Voltage indicator and relay - VD23
Fault passage indicators - Flair 21D and 22D
VPIS-V2
Motorization
Other accessories

Non-extensible ring main unit

157

c/w angled ring cable gland plates - ref RMINST-05

Tee-off cable box fitted to SN6/CN2

158

ref RMINST-09

Ringmaster range cabling accessories

159

ref RMINST-10

AMTED399086EN

149

Accessories & options

Accessories description
MV substation remote monitoring unit
Flair 200C
Voltage indicator and relay VD23

The Flair 200C is an efficient tool for reducing


repair and fault finding times.
It improves quality of service and
operation for power supply companies.

MV substation remote monitoring unit Flair 200C


A product dedicated to remote monitoring of MV substations with a high level
of function integration

PE57570

Easergy Flair 200C is a remote monitoring unit designed to be installed in the MV


substations of a public-private distribution network or in customers substations.
Easergy Flair 200C is a tool that complements control units for MV substations
(Easergy T200 I) and conventional fault passage indicators (Easergy Flair).
Easergy Flair 200C is specially designed to meet customers requirements
for the management of MV substations. It provides compact, open solutions:
b Fault passage indicator compatible with any type of earthing system
b Substation monitoring: sending of an alarm in the event of an incident
in the substation for efficient maintenance
b Power monitoring unit on the MV and LV network for improved monitoring
of load curves and improved power distribution efficiency
b Substation digital concentrator for interfacing between the substations
communicating equipment and the control centre
b Communication with the remote control centre with call management upon alarm.
Flair 200C

The VD23 is a voltage detecting system for


automatic transfer system or interlock
applications.
Various combinations:
presence or absence voltage relay
zero sequence voltage relay
phase-to-neutral or phase-to-phase voltage
phase selection.

b
v
v
v
v
v

Easy to install:
compact 96 x 48 mm DIN format
terminal connection for VPIS-VO
no need for HV transformer
hot installation
auto-adaptation of nominal voltage.

PE57787

b
v
v
v
v

Voltage indicator and relay VD23


Features
The VD23 is a compact voltage relay for 3 kV to 36 kV, 50/60 Hz medium
voltage networks. It is associated with a capacitive divider and a VPIS-VO.
b 2 output relays based on 2 functional modes:
v R1 = Voltage presence (typically used for automatic transfer switching)
v R2 = Voltage absence (typically used for interlocking of earthing switch).
b Thresholds can be set as a percent of phase-to-neutral voltage (V),
phase-to-phase voltage (U) or residual voltage (VO)
b All combinations of voltage conditions are possible:
v 3 phases and residual: V1+V2+V3+VO
v 3 phases: V1+V2+V3 or U12+U13+U23
v single phase: Vo, V1, V2, V3, U12, U13 or U23
b Output is a tripping order via two output relays with a normal or inverse active
position
b Signalling and tripping outputs may be set with a delay.

Display principle
b
b
b
v
v
b
b

VD23

Voltage value (% of Un) of L1, L2 and L3 shown on the display


Voltage presence/absence indication via LED
Settings by front pushbuttons and LCD
thresholds, delays and smart parameters
display of all settings on LCD.
Auto-adaptation of the nominal system voltage
Check on voltage status.

Advanced settings
All the combinations can be set with microswitches on the rear of the device.
The use of two relays provides safety backup operation for each combination
6 microswitches:
1 2
1
0

L1
L2
L3

VD23

3 4 5 6

1: Ph-N voltage(V) / Ph-Ph voltage(U)


2: Direct / inverse action on output relays
3: Phase 1 used / not used
4: Phase 2 used / not used
5: Phase 3 used / not used
6: Residual voltage used / not used

DM100060

Wiring (with VPIS-VO)


All the combinations can be set with microswitches on the rear of the device.
The use of two relays provides safety backup operation for each combination.

VPIS-VO

150

Voltage Voltage 24-48


absence presence Vdc

AMTED399086EN

Accessories & options

Accessories description
Fault passage indicators
Flair 21D and Flair 22D

Flair 21D, 22D is a family of DIN format


fault passage indicators. They are small in size,
self-powered and adapt automatically to the
network.
These devices use cutting-edge technology to
detect earth faults on underground MV networks
with isolated, resistor-earthed or directly earthed
neutral and overcurrents on all networks.
b Self-powered, the fault current passage
detection and indication system operates
continuously
b Adjustment-free, they are immediately
operational (numerous manual adjustments
are however possible)
b Compact, their DIN format easily fits
in MV cubicles
b Smart, they offer an ammeter/digital maximeter
function.

Applications and main features


The Flair range increases your power availability by providing indicators
suitable for fault locating and MV network load management.
b Indication of phase-phase and phase-earth faults
b Display of settings
b Indication of the faulty phase
b Display of the load current including peak demand and frequency.
These fault passage indicators are reliable and easy to use.
b Automatic setting on the site
b Fault indication with LED or outdoor lamp
b 15-year battery life for Flair 22D
b More accurate fault detection if Flair 22D is connected to voltage presence
indication system (VPIS) voltage output
b Can be factory-mounted in Premset cubicles or added on the site
b Easy on-site addition without removing MV cables using split-type current sensor.

Fault detection functions

PE57783

Overcurrent detection

Flair 21D

b Automatic mode for adjustment-free calibration of detection thresholds


b Manual mode for special override settings:
v Flair 21D: 4 detection thresholds from 200 A to 800 A, in 200 A increments,
selectable via microswitches
v Flair 22D: 8 detection thresholds from 100 A to 800 A, in 50 A increments,
configurable via the front panel keypad.
b Fault acknowledge time:
v Flair 21D: 40 ms
v Flair 22D (configurable via the front panel keypad)
- Type A from 40 to 100 ms in 20 ms increments
- Type B from 100 to 300 ms in 50 ms increments.

PE57784

Earth fault detection

Flair 22D

b Earth fault sensitivity as low as 5 A

The detector checks the 3 phases for current variations (di/dt).


A time delay of 70 s is applied for fault confirmation by the upstream
protective device.
b Automatic mode for adjustment-free calibration of detection thresholds
b Manual mode for special override settings:
v Flair 21D: 6 detection thresholds from 40 to 160 A, via microswitches
v Flair 22D (configurable via the front panel keypad):
- Type A from 20 to 200 A, in 10 A increments
- Type B from 5 to 30 A in 5 A increments and 30 to 200 A in 10 A.
b Inrush function: prevents unnecessary detection in the event of load switch-on.
Incorporates a 3 s time delay for fault filtering at network power up.
The Inrush function can be disabled via configuration on Flair 22D.

b Display of settings and faulty phase


b Automatic reset

Fault indication function


Signalling
As soon as a fault is confirmed, the indication device is activated.
b Fault indication via a red LED on the front panel
b Indication of the faulty phase (earth fault) on LCD display
b Optional remoting of indication to external flashing lamp
b Activation of a contact for retransmission to the SCADA system.

Indication reset
b Automatic reset upon load current recovery (configurable time delay on Flair 22D)
b Manual reset via front panel button
b Reset via external Reset input
b Reset by time delay: fixed (4 hr) for Flair 21D and adjustable using front
panel keypad (2 hr to 16 hr) for Flair 22D.

AMTED399086EN

151

Accessories & options

Accessories description
Fault passage indicators
Flair 21D and Flair 22D
Display principle

DE58715

Clear, comprehensive display

b The load current is displayed continuously


b When a fault is detected, the faulty phase is indicated
b Use the buttons on the front panel to scroll through settings and measurements.

Test
Reset

L1
L2
L3

A
Esc

I max.

Selection table
Easergy
Flair 22D

Flair 21D

Flair 22D

Overcurrent

Earth-fault

Ammeter

Maximeter

SCADA interface (relay)

External lamp

Power supply

Self-powered

Sensors

Detection

The Flair 21D, 22D range uses an integrated


detection system composed of indicators
and dedicated CTs.

Display
(4 digit LCD)
Options

EMS58352

Dual-powered

Integrated sensors are normally placed around


the bushings. Split CTs can be placed around
cables for retrofit purposes.

Communication

b (1)

External reset

Extended setting (keypad)

2-voltage output relays

Connection diagrams

Serial communication port


(1) By lithium battery

L3
L2
L1

Characteristics per product

DM100048

Model

Description

Fault passage indicator with single power supply (self-powered)


Flair 21D

Detector with autonomous power supply


External indicator lamp output powered by battery (BVP)

Fault passage indicator with dual power supply


Flair 21D

Flair 22D

Reset Indication

External indicator lamp output powered by the Flair (BVE)

L3
L2
L1

Zero sequence CT option (type B setup)


Interface with VPIS-VO possible to confirm the fault by voltage absence
VPIS-VO
option

Flair 22D

152

Detector with autonomous power supply and lithium battery

Standard applications
Flair 21D

Maintenance-free, adjustment-free fault detector

Flair 22D

Fault detector for networks with very low load current (< 2 A) with possibility
of manual adjustments.

Reset Indication

AMTED399086EN

Accessories & options

Accessories description
VPIS V2

b Voltage presence indicating system


in compliance with the IEC 62271-206 standard
(and also with the old IEC 61958 standard)
b Voltage output option for source changeover
switch application.

Description
b The VPIS V2 is a self-powered voltage presence indicating system, in compliance
with the IEC 62271-206 standard
b Connectors on the front panel allow the use of a phase comparator
(see corresponding section in the document)

PE58177

b Extended lifetime of LEDs on the front panel


b Compatibility with existing MV network devices for replacement.
The VPIS V2 consists of two parts:
v the surge protection part (always connected)
v the voltage presence indicating part (replaceable for maintenance)

VPIS V2

b Retrofit: no change necessary for the replacement of a VPIS V1 (production from


01-2000 02-2009) with a VPIS V2.
However, a special open seal is necessary (supplied with each VPIS V2)
for installation on an existing wiring harness.

PE58178

Thresholds
b In compliance with the IEC 62271-206 standard, the indicator lamp outputs of
the VPIS are lit or flashing when the network voltage is > 45% of the rated voltage.

PE58142

Voltage indicator

Voltage value
at VPIS input

IEC 62271-206:
percentage of
network voltage U
Phase-to-phase
10%

Equivalent percentage Status of VPIS


of rated voltage V
indicator lamps
Phase-to-earth
17%

Extinguished

45%

78%

Lit or flashing

The flashing frequency increases depending on the level of the network voltage.
At rated voltage, the indicator lamps seem to be lit steadily.

VPIS V2 references selection table

PE58143

Open seal

The operating range depends on the working voltage, the MV network frequency and
the type of counter element used in the cubicle.
The common operating ranges at 50/60 Hz frequencies can be found in this table.
In the event of use on a single frequency, 50 Hz or 60 Hz, the operating range can be
extended. In that case contact the cubicle offer manager.
Ringmaster
First
choice

PE58144

Standard surge protection

Second
choice

3 kV

6 kV

10 kV

15 kV

VPI62401

VPI62401

VPI62403

VPI62403

With VO

VPI62411

VPI62411

VPI62413

VPI62413

50/60 Hz

(3.4 kV-7.5 kV)

(3.4 kV-7.5 kV)

(7.1 kV-16 kV)

(7.1 kV-16 kV)

Without VO

Without VO

VPI62402

With VO

VPI62412

50/60 Hz

(5.8 kV-10 kV)

PE58145

VPIS-VO surge protection

Cover joint (not available as spare part)

AMTED399086EN

153

Accessories description

Accessories & options

Motorization

Click on the picture to see the video

Simple, fast and efficient motorization solution


As the world moves towards more smart networks, the remote operation of RMUs
will become more necessary.
Ringmaster with its Plug-in motor design offers customers to convert their pre-wired
manual operated RMUs to motorized, remotely controlled in a couple of minutes.
The plug-in motor-gear assembly, called as Motor-pack can be directly plugged
on to the mechanism on site, in live or dead condition of the Ring Main Unit.
Providing customer the benefit of enormous time saving, easiness and flexibility.
This Motorpack is universal in nature as the same Motorpack can be used
to motorize either switch or circuit breaker.

154

DSC0456

DSC0457

The whole motor unit just needs a screw to secure it in position once fitted
on the Ring Main Unit.

AMTED399086EN

Accessories description

Accessories & options

Motorization

DSC0443

DSC0444

Process of motorization

Plug-in the motorpack in its location

Secure by special nut provided


(pad lockable)

DSC0424

Position the Motorpack in front


of mechanism

Position the Motorpack to the RMU

DSC0430

DSC0434

DSC0437

Manual pre-wired Ring Main Unit

RMU with motor Ready to be operated from remote

AMTED399086EN

155

Accessories & options

Accessories description
Other accessories

Schneider Electric are able to provide a number


of accessories to enhance the basic unit
specifications. These accessories are detailed
within the panel type specifications

Accessories
These are dispatched either:
b Fitted to the unit within the works - these are accessories that are either too bulky,
or need testing prior to despatch
ie; RMR-F47 - tee-off cable box
b Loose, boxed, for you to assemble on site. These items are either those that need
to be supplied loose to ease installation: ie RMR-A48 which is a gland plate, or test
equipment such as RMR-A202, VAP6.

Options
The following pages clarify options:
RMR-F47 - Tee-off cable box (drawing RMINST 05/09)
RMR-A50 - Angled gland tray (drawing RMINST 10)
RMR-A317 - Angled gland tray (drawing RMINST 05)

DE60270

RMR-A14/A15/A78/A79
Busbar assemblies
b Each kit comprises a three phase set of busbars, 630 A
b Specify at time of ordering:
v 1 off RMR-A15 - end panel kit, plus busbar kits
v Quantity required = No. of panels - 1
Note: Different busbar kits are required for metering units and bus-sections
Busbars are dispatched loose.

RMR-A17
DE60245-1

Time Fuse Links


b 2 off time fuse links for overcurrent protection
Order code
RMR-A17/3
RMR-A17/5
RMR-A17/7
RMR-A17/10
RMR-A17/12
RMR-A17/15

Rating
3 amp
5 amp
7.5 amp
10 amp
12.5 amp
15 amp

PE58310

RMR-A202
VAP 6 test unit
b Check operation of VIP 300, VIP 30 & VIP35 IDMT relays, unit injects 20 x Is
to verify operation of microprocessor and outputs, and trip the CB.
Complete with batteries.

156

AMTED399086EN

Accessories & options

Non-extensible ring main unit

DE60246

c/w angled ring cable gland plates


ref RMINST-05

208

208

Panel type
Page number
RN2c-T1
25
RN2c-T2
26
RN2c-T3
27
RN2c-T4
28
RN2c-T5
29
Approximate weight: 300 kg
The above drawings refer to RMR-F324 tee-off cable box and RMR-A317 angled gland plate.
Note: for installation where overpressure relief of the equipment is required please contact
Schneider Electric Tel: +44 (0)113 290 3500

AMTED399086EN

157

Accessories & options

Tee-off cable box fitted


to SN6/CN2

DE60247

ref RMINST-09

Panel type
Page number
CN2-T1
46
CN2-T6
47
SN6-S1
51
SN6-S2
52
Note: for installation where overpressure relief of the equipment is required please contact
Schneider Electric Tel: +44 (0)113 290 3500

158

AMTED399086EN

Accessories & options

Ringmaster range
cabling accessories

DE59850

ref RMINST-10

799

Panel type
CE2
CE6
SE6
CN2
SN6
Approximate weight: 250 kg

AMTED399086EN

Page number
61-72
73-79
80-87
44-48
49-52

159

160

AMTED399086EN

Schneider Electric,
an overview
and order form

Contents

Applications

162

Building systems and solutions


Industrial systems and solutions
Energy and infrastructure systems and solutions
Package substations
Mining industry

Order form

170

Ring Main Unit (RMU)


Ring Modular Range (RMR) - Circuit Breaker
Ring Modular Range (RMR) - Switch
Guide Metering & Bus section

Index

AMTED399086EN

175

161

Schneider Electric,
an overview
and order form

Applications

PE58311

With over 100 years experience in the electrical industry,


Schneider Electric has established itself as a world leader in
the supply and manufacture of products for the distribution,
monitoring and control of electrical power.
Schneider Electric regards its customers as commercial
partners, who, like us, demand the highest standards of
excellence in terms of products, projects and services.
Schneider Electric is proud to provide the solutions to meet
their needs.
Schneider Electric operates the largest, dedicated sales force in the electrical industry.
Sales engineers have specialist expertise and an understanding of the customer
needs within each of the following market sectors:
b Building systems and solutions
b Industrial systems and solutions
b Energy and infrastructure systems and solutions
b Package substations
b Mining industry.

162

AMTED399086EN

Schneider Electric,
an overview
and order form

Applications
Building systems and solutions

PE58312

The real reason for putting technology into buildings is to simplify tasks, enhance
safety and improve the quality of life.
Schneider Electric knows this and has created attractive, functional products for the
residential building sector. Well being comfort and entertainment are key concepts in
this area.

The same objectives apply to commercial buildings such as offices, hotels, shopping
centres, hospitals, schools and care facilities for the elderly.
Schneider Electric offer a wide range of solutions in the area of building management
services and uses its expertise in all of these buildings to protect people and
equipment.

Schneider Electric means greater comfort, lower operating


costs and enhanced safety.

PE58313

Related industries
b Retail
b Education
b Health
b Entertainment centres
b Offices
b Warehouses
b Agriculture
b Factory
b Private residential
b Public residential.
Principal customers in the construction market
b Contracting authorities
b Main contractors
b Building engineers.

AMTED399086EN

163

Applications

Schneider Electric,
an overview
and order form

Industrial systems and solutions

PE58314

Schneider Electric focus on performance in all areas of industry.


Our products and services adapt to each specific business and environment, from
discrete manufacturing and production lines to continuous processes in a wide
variety of industries such as:
b Automotive
b Food and beverage
b Pharmaceuticals
b Construction materials
b Waste management.

PE57008

Across a wide range of applications including:


b Conveyors
b Packaging
b Materials handling
b Hoisting.

164

AMTED399086EN

Schneider Electric,
an overview
and order form

Applications
Energy and infrastructure systems
and solutions

PE58315

Schneider Electric is involved in the entire electrical distribution chain from power
plants to end users. Customer demand for complete availability, uncompromising
quality and absolute safety has made the search for excellence our key mission.
Today, electrical substation and network protection, monitoring and control are
highly effective in reducing outage time.
Proven technologies offer a wide range of simple, efficient and flexible solutions for
optimised, step by step investments.
Infrastructure
Schneider Electric is involved in developing infrastructure and transportation
systems around the world. In areas where no failures can be tolerated, such as road
and rail equipment, harbour installations and airports, Schneider Electric provides
solutions in electrical distribution, control and monitoring, automation and
supervision.

PE58316

Key markets
b Electricity distribution
b Water
b Rail
b Airports
b Seaports
b Defence
b Gas
b Telecommunications
b Road.
Principal customers in the electric power market
b Power suppliers involved in generation and distribution
b Utility companies
b Major contractors
b Large end user sites
b Government departments.

AMTED399086EN

165

Applications

Schneider Electric,
an overview
and order form

PE58321

Package substations

One stop engineered package substation


Schneider Electric engineered package substation solutions tailored to customers requirement using products from our
comprehensive range. This provides customers with a
convenient single source package substation with minimum
time and costs.
Ease of specification is guaranteed by one point of contact from initial enquiry
through manufacture, delivery, commissioning and after sales service.
Schneider Electric engineers design specific engineered solutions to fulfil customer
requirements.
Flexibility of tailored configurations are available from the wide range of Schneider
Electric products which include:
b Transformers from 315 kVA to 2000 kVA (up to 5 MVA for special applications)
b Extensible and non-extensible Ringmaster MV switchgear
b LV SAIF and shielded fusegear from 800 A to 3200 A
b LV acb and mccb pillars up to 3200 A
b Automation and monitoring systems
b Tailor made enclosures can be mounted on the transformer underbase to provide
single lift complete installation.

Unit substation 4 way LV cabinet


and Ringmaster RN2c RMU

Safety and protection of operators is ensured by direct coupling of the individual


elements with provision for isolation for maintenance.

PE58320

Cost savings are achieved by reducing the foundation area requirement due to
the direct coupling which requires minimum cabling and reduced maintenance.
Space requirements are minimised by direct connection, logistics costs minimalised
because the complete substation is delivered as a single unit. One stop package
substations also reduce the time commitment needed by customers for the overall
project.

166

AMTED399086EN

Applications

Schneider Electric,
an overview
and order form

Package substations

PE58322

One stop engineered solutions


The diversity of configurations range from compact design,
unit, in-line or specialised systems dependent on application
requirement.
Transformers can be either free breathing, conservator or
hermetically sealed type.
Substations can have remote control and automation.

PE58324

Features
b One contact
b Complete system, delivered as one unit
b Typical drawing and technical specification with tender
b Metering facilities-optional
b Remote control-optional
b Free breathing, conservator or hermetically sealed tank option
b Premium quality of Schneider Electric
b Direct coupled MV & LV equipment
b Additional enclosure option.

PE58323

Expertise in developing solutions for specialised applications


b Unit substations have MV and LV switchgear located on the same side of the
transformer tank
b In-line substations have MV and LV switchgear mounted on opposite ends of the
transformer tank
b Compact or mini substations for lower rating applications
b Specialised substations are designed to meet specific requirement.
For example, MV and LV switchgear can be mounted at a 90 angle on the
transformer tank
b Remote control options enable network automation for secondary distribution.

AMTED399086EN

167

Applications

Schneider Electric,
an overview
and order form

Mining industry

PE58317

Robust and simple solution for mine MV network


Ringmaster is a range of MV switchgear with a genuine IP 54 design to maximise
resistance to the toughest environment:
b Dust
b Pollution
b Humidity.
Cost effective and simple
b The IP54 degree of protection of the Ringmasters housing makes it possible
to be used in the most aggressive environment. No consideration needs to be taken
for an external enclosure, saving cost compared to traditional solutions.
b A virtually maintenance free design is achieved having all MV contacts housed
in a sealed for life IP67 SF6 gas filled enclosure.
b Underground handling in narrow tunnels and lifts is simplified by compact
dimensions and light weight.
Robust and safe for people
b Unlike air insulated switchgear, Ringmaster offers full encapsulation and no
primary conductor is exposed to the ambient air. Contact with conductive particles
present in dusty environment is avoided, greatly reducing the risk of partial discharge
and flash over.
b Operator safety is maximised with an advanced design fully compliant to the latest
internal arc classification as per IEC62271-200.

PE58318

Over 5000 functions of Ringmaster safely protect mine networks worldwide


b BHP Billiton, Rio Tinto, Gold Fields, Alcoa, CSA Global, Newcrest, Xstrata,
Gloucester Coal, Aditya Birla Group, AngloGold Ashanti, Anglo Coal, ASSMANG.

168

AMTED399086EN

AMTED399086EN

169

Schneider Electric,
an overview
and order form

Order form

Only one of the boxes (ticked X or filled


by
the needed value) have to be considered between each
horizontal line.
Green box X corresponds to none priced functions.

Basic RMU configuration

Ring Main Unit (RMU)

Quantity

Rated voltage Ur

(kV)

Impulse rating and short-time withstand

21 kA 3 s, 95 kVbil

RMU configuration and protection


RN2c
200 A CB
non extensible
Protection

RE2c
200 A CB
right extensible

RN6c
630 A CB
non extensible

TFL
VIP 30
VIP 35
VIP 300
Sepam 10

Metering unit MU2/MU6 - 16 kA, 75 kVbil only


Choose and fill-in from Guide Metering & Bus section, e.g.: MU2-M3

RMU options
Low gas pressure switch (contact)
VPIS on switches

3.3-13.8 kV

C type bushings on switches (Check with us for availability)

Options for circuit breaker


MV cable connection
Transformer mounted - no cable box
Free standing without transfo flange

Bottom

Free standing with flange (transformer mounting provision)


Entry
Top
Bottom
C type bushings - only if without transfo flange (Check with us for availability)
Cable entry - 1 - 3c cable
Gland plates 3 - 1c cable
Angled 1 - 3c cable
Split gland plate 1 x 3c
Blank aluminium
Cable gland Brass wiping
(only if
Small brass wiping
required)
Galvanised tubular

3 - 1c cable

1 - 3c cable

3 - 1c cable
3 - 1c cable

Heat shrinkable (CES5)

1 - 3c cable
1 - 3c cable

VPIS on breaker (only if free standing without transfo flange)


Shunt trip coil (included if VIP)

20-48 Vdc, 110-250 Vac/dc

Shunt trip coil (included if TFL)


Motor provision - auxiliary switch
Motor pack (includes motor provision)

1 x N/O, 1 x N/C
24 Vdc

Mechanical key interlock (not available with motor option)


Key free main OFF
Circuit breaker facility for cable insulation testing

Key free earth ON

Mechanical trip push button


Termination boots Econ

170

AMTED399086EN

Schneider Electric,
an overview
and order form

Only one of the boxes (ticked X or filled


by
the needed value) have to be considered between each
horizontal line.
Green box X corresponds to none priced functions.

Order form
Ring Main Unit (RMU) cont.

Options for ring switch 1 - Left hand side


Inverted cable box for top entry
Cable entry - 1 - 3c cable
Gland plates 3 - 1c cable
Angled 1 - 3c cable
Split gland plate 1 x 3c
Blank aluminium
Cable gland Brass wiping
(only if
Small brass wiping
required)
Galvanised tubular

1 - 3c cable

3 - 1c cable
3 - 1c cable

1 - 3c cable

3 - 1c cable

Heat shrinkable

1 - 3c cable

Motor provision - auxiliary switch

1 x N/O, 1 x N/C

Motor pack (includes motor provision)

24 Vdc

Mechanical key interlock (not available with motor option)


Key free main OFF
Bowden earth fault passage indication (includes external current transformer)
Self powered

LV reset

Std
Dual powered - battery

LV reset + alarm
Remote reset + alarm

Easergy T200 current transformers


Termination boots Econ

Options for ring switch 2 - Right hand side


Inverted cable box for top entry
Cable entry - 1 - 3c cable
Gland plates 3 - 1c cable
Angled 1 - 3c cable
Split gland plate 1 x 3c
Blank aluminium
Cable gland Brass wiping
(only if
Small brass wiping
required)
Galvanised tubular

3 - 1c cable

1 - 3c cable

3 - 1c cable
3 - 1c cable

Heat shrinkable

1 - 3c cable
1 - 3c cable

Motor provision - auxiliary switch

1 x N/O, 1 x N/C

Motor pack (includes motor provision)

24 Vdc

Mechanical key interlock (not available with motor option)


Key free main OFF
Termination Boots Econ

Accessories
Operating handle
Phase comparitor
VAP6
TFL fuses
(A)

7.5

Extension kit RE2c to RMR

10

12.5

15

RE2c only

Installation items - Ringmaster accessories


Transformer mounting kit
Set of 11 standard brass padlocks
Anti-vandal fixings
Set of foundation fixings
Set of multicore pilot glands
RN2c to MU2 installation kit
Ariel mounting bracket

AMTED399086EN

171

Schneider Electric,
an overview
and order form

Order form

Only one of the boxes (ticked X or filled


by
the needed value) have to be considered between each
horizontal line.
Green box X corresponds to none priced functions.

Basic RMR configuration

Ring Modular Range (RMR)


Circuit breaker

Quantity

Rated voltage Ur

(kV)

Impulse rating and short-time withstand

21 kA 3 s, 95 kVbil

Panel configuration and protection

Non extensible cable in/out


Std 3,15 kA tx earth sw.
200 A CB
200 A CB
Protection

Extensible
CE2
CE6
200 A
630 A

TFL
VIP 300
Sepam 10

Metering unit (16 kA, 75 kVbil only) & bus section


Choose and fill-in from Guide Metering & Bus section, e.g.: CE2-T3

Incoming cable box


Cable entry - 1 - 3c cable
Gland plates 3 - 1c cable
Angled 1 - 3c cable
Split gland plate 1 x 3c
Blank aluminium
Cable gland Brass wiping
(only if
Small brass wiping
required)
Galvanised tubular

3 - 1c cable

1 - 3c cable

3 - 1c cable
3 - 1c cable

Heat shrinkable

1 - 3c cable
1 - 3c cable

Outgoing cable box - Non extensible units only


MV Cable connection - Free Standing by default

Transformer mounted - No cable box

Cable entry - 1 - 3c cable


Gland plates 3 - 1c cable
Angled 1 - 3c cable
Split gland plate 1 x 3c
Blank aluminium
Cable gland Brass wiping
(only if
Small brass wiping
required)
Galvanised tubular

3 - 1c cable

1 - 3c cable

3 - 1c cable
3 - 1c cable

Heat shrinkable

1 - 3c cable
1 - 3c cable

Options
VPIS

3.3-13.8 kV

Neon lamp unit


Neon lamp with verification unit
Shunt trip coil (included if VIP)

20-48 Vdc, 110-250 Vac/dc

Shunt trip coil (included if TFL)


Motor provision - auxiliary switch

1 x N/O, 2 x N/C

Motor / Actuator - MOTOR PROVISION MUST BE SELECTED

24 Vdc

Mechanical key interlock (not available with motor option)


Tx earth sw key free earth on
Low gas pressure switch (contact)

Key free main OFF

Key free earth ON

Accessories
Operating handle
Busbar kit & end panel kit are included to assemble switchboard
Phase comparitor
VAP6
TFL fuses
(A)

7.5

10

12.5

15

Installation items - Ringmaster accessories


Set of 3 x 630 A standard 430 mm busbars
Set of two busbar end caps + plates
Extended 630 A busbars (metering units)
Set of 3 x 630 A busbar risers (bus-sections)
Set of 6 standard brass padlocks
Set of foundation fixings
Multicore pilot cable gland

172

AMTED399086EN

Schneider Electric,
an overview
and order form

Order form

Only one of the boxes (ticked X or filled


by
the needed value) have to be considered between each
horizontal line.
Green box X corresponds to none priced functions.

Basic RMR configuration

Ring Modular Range (RMR)


Switch

Quantity

Rated voltage Ur

(kV)

Impulse rating and short-time withstand

21 kA 3 s, 95 kVbil

Panel configuration
630 A non extensible cable in/out standard
630 A non extensible cable in/out with 3.15 kA tx earth switch
630 A extensible
Bus section & busbar earthing switch
Choose and fill-in from Guide Metering & Bus section, e.g.: SE6-B1

Incoming cable box


Cable entry - 1 - 3c cable
Gland plates 3 - 1c cable
Angled 1 - 3c cable
Split gland plate 1 x 3c
Blank aluminium
Cable gland Brass wiping
(only if
Small brass wiping
required)
Galvanised tubular

3 - 1c cable

1 - 3c cable

3 - 1c cable
3 - 1c cable

Heat shrinkable

1 - 3c cable
1 - 3c cable

Outgoing cable box - Non extensible units only


MV cable connection - Free Standing by default

Transformer mounted - No cable box

Cable entry - 1 - 3c cable


Gland plates 3 - 1c cable
Angled 1 - 3c cable
Split gland plate 1 x 3c
Blank aluminium
Cable gland Brass wiping
(only if
Small brass wiping
required)
Galvanised tubular

3 - 1c cable

1 - 3c cable

3 - 1c cable
3 - 1c cable

Heat shrinkable

1 - 3c cable
1 - 3c cable

Options
VPIS

3.3-13.8 kV

Neon lamp unit


Neon lamp with verification unit
Motor provision - auxiliary switch

1 x N/O, 1 x N/C

Motor / Actuator - MOTOR PROVISION MUST BE SELECTED

24 Vdc

Mechanical key interlock (not available with motor option)


Key free main OFF
Key free earth ON
Tx earth sw key free earth on
Bowden earth fault passage indication (includes external current transformer)
Self powered
Std
Dual powered - battery

LV reset

LV reset + alarm
Remote reset + alarm

Easergy T200 current transformers


Low gas pressure switch (contact)

Accessories
Operating handle
Phase comparitor

Installation items - Ringmaster accessories


Set of 3 x 630 A standard 430 mm busbars
Set of two busbar end caps + plates
Extended 630 A busbars (metering units)
Set of 3 x 630 A busbar risers (bus-sections)
Set of 6 standard brass padlocks
Set of foundation fixings
Multicore pilot cable gland

AMTED399086EN

173

Guide Metering & Bus section

Schneider Electric,
an overview
and order form

Panel
types

Motor
provision

VT
configuration

Service
voltage

Rated
voltage

Secondary
voltage

VT output/class

CT primary/
secondary
current

CT output/class

MU2 (200 A Ring Main Unit metering)


MU2-M1

NA

2 ph - ph

11 kV

12 kV

110 V

50 VA Class 0.5

50/25/5

7.5 VA Class 0.5s

MU2-M2

NA

2 ph - ph

11 kV

12 kV

110 V

50 VA Class 0.5

100/50/5

10 VA Class 0.5s

MU2-M3

NA

2 ph - ph

11 kV

12 kV

110 V

50 VA Class 0.5

200/100/5

10 VA Class 0.5s

MU2-M12

NA

3 ph - earth

11 kV

13.8 kV

110 V

50 VA Class 0.5 + 20 VA
Neutral voltage protection

200/100/5

10 VA Class 0.5s

10 VA class 0.5s

CE2-T (200 A metered circuit breaker)


CE2-T11

No motor

2 ph - ph

6.6

12

110 V

50 VA Class 0.5

200/100/5 A

CE2-T14

Motor fittable

2 ph - ph

6.6

12

110 V

50 VA Class 0.5

200/100/5 A

10 VA class 0.5s

CE2-T3

No motor

2 ph - ph

11

12

110 V

50 VA Class 0.5

200/100/5 A

10 VA class 0.5s

CE2-T13

Motor fittable

2 ph - ph

11

12

110 V

50 VA Class 0.5

200/100/5 A

10 VA class 0.5s

CE2-T20

No motor

3 ph - earth

11

17.5

110 V

50 VA Class 0.5 + 20 VA
Neutral voltage protection

200/100/5 A

10 VA class 0.5s

CE2-T19

No motor

3 ph - earth

13.8

17.5

110 V

50 VA Class 0.5 + 20 VA
Neutral Voltage Protection

200/100/5 A

10 VA class 0.5s

CE2-T21

Motor fittable

3 ph - earth

13.8

17.5

110 V

50 VA Class 0.5 + 20 VA
Neutral voltage protection

200/100/5 A

10 VA class 0.5s

10 VA class 0.5s

CE6-T (630 A metered circuit breaker)


CE6-T6

No motor

2 ph - ph

6.6

12

110 V

50 VA Class 0.5

400/200/5 A

CE6-T10

Motor fittable

2 ph - ph

6.6

12

110 V

50 VA Class 0.5

400/200/5 A

10 VA class 0.5s

CE6-T5

No motor

2 ph - ph

11

12

110 V

50 VA Class 0.5

400/200/5 A

10 VA class 0.5s

CE6-T9

Motor fittable

2 ph - ph

11

12

110 V

50 VA Class 0.5

400/200/5 A

10 VA class 0.5s

CE6-T22

No motor

3 ph - earth

13.8

17.5

110 V

50 VA Class 0.5

400/200/5 A

10 VA class 0.5s

CE6-T23

Motor fittable

3 ph - earth

13.8

17.5

110 V

50 VA Class 0.5

400/200/5 A

10 VA class 0.5s

CE6-T24

No motor

3 ph - earth

11

17.5

110 V

50 VA Class 0.5 + 20 VA
Neutral voltage protection

400/200/5 A

10 VA class 0.5s

CE6-B (630 A bus section circuit breaker)


CE6-B3

No motor

2 ph - ph

11

12

110 V

50 VA Class 0.5

400/200/5 A

10 VA class 0.5s

CE6-B5

Motor fittable

2 ph - ph

11

12

110 V

50 VA Class 0.5

400/200/5 A

10 VA class 0.5s

No VT

No VT

No VT

No VT

No CT

No CT

No VT

No VT

No VT

No VT

No CT

No CT

SE6-B (630 A bus section switch)


SE6-B1

No motor

No VT

SE6-E (630 A busbar earthing switch)


SE6-E1

174

No motor

No VT

AMTED399086EN

Schneider Electric,
an overview
and order form

Index

Page

Accessories
Actuator panel types
Angled gland trays
Applications

150
49, 61, 73
157
162

B
Busbar options sections
Bus sections

86
85

C
200 A
600 A
Circuit breakers
Control & protection

44, 45
73, 74
61, 62
7 to 12

D
Drawing index

96

E
Easergy telecontrol unit

92

I
IDMT protection
IEC/BS/IS standards

7, 11, 12
6

M
Metered CBs
Metering units
Motor retrofit

61, 62, 73, 74


53, 54
33, 34, 61, 62

P
Protection selection
Protection - TFL
Protection - VI

7
7
12

R
Ring main units extensible
Ring main units non-extensible

61, 62
22, 23

S
Schematics
Selection guide
Self powered protection
Switchboard GA
Switches

108
17
7
97
49, 80

T
Telecontrol
Telephone communication
TFL protection
Time fuse links

92
92
7
7

V
VIP protection

Please note: Due to the constant progress in standards and equipment, the characteristics shown
in the texts and images in this document are only binding once expressly confirmed by ourselves

AMTED399086EN

175

Ringmaster

176

Notes

AMTED399086EN

335, rue Joseph Monier


CS 30323
F - 92506 Rueil Malmaison Cedex (France)
Tl. : +33 (0)1 41 29 70 00
RCS Nanterre 954 503 439
Capital social 896 313 776
www.schneider-electric.com
AMTED399086EN

As standards, specifications and designs change from time


to time, please ask for confirmation of the information given
in this publication.
Design: Schneider Electric Industries SAS
Photos: Schneider Electric Industries SAS
Printed: Altavia St-Etienne - Made in France