Documente Academic
Documente Profesional
Documente Cultură
Mounting
Terminal strip overview
I/O lists
Wiring
AGC 200
Installation Instructions
Table of contents
1.
2.
3.
4.
MOUNTING ............................................................................... 14
MOUNTING OF THE UNIT....................................................................... 14
PANEL CUTOUT ................................................................................... 14
MOUNTING INSTRUCTIONS ................................................................... 14
MOUNTING OF GASKET (OPTION L1)..................................................... 14
5.
HARDWARE ............................................................................. 15
UNIT REAR SIDE OVERVIEW ................................................................. 15
TERMINAL STRIP OVERVIEW, AGC 21X, 223, 232, 242, 243 ................ 16
TERMINAL STRIP OVERVIEW, AGC 244/245/246.................................. 23
6.
WIRINGS ................................................................................... 30
AC CONNECTIONS ............................................................................... 30
DC CONNECTIONS............................................................................... 39
COMMUNICATION................................................................................. 44
7.
DEIF A/S
Page 2 of 57
AGC 200
Installation Instructions
Intended users
These installation instructions are mainly intended for the panel builder
designer in charge. On the basis of this document, the panel builder
designer will give the electrician the information he needs in order to
install the AGC 200, e.g. detailed electrical drawings. In some cases,
the electrician may use these installation instructions himself.
Contents/overall structure
This document is divided into chapters, and in order to make the
structure simple and easy to use, each chapter will begin from the top
of a new page.
DEIF A/S
Page 3 of 57
AGC 200
Installation Instructions
Safety issues
Installing the unit implies work with dangerous currents and voltages.
Therefore, the installation of the AGC 200 should only be carried out by
authorised personnel who understand the risks involved in the working
with live electrical equipment.
Be aware of the hazardous live currents and voltages.
Do not touch any AC measurement inputs as this
could lead to injury or death.
Notes
Throughout this document, a number of notes with helpful user
information will be presented. To ensure that these are noticed, they
will be highlighted in order to separate them from the general text.
Note symbol
The notes provide general information which will be
helpful for the reader to bear in mind.
DEIF A/S
Page 4 of 57
AGC 200
Installation Instructions
Warning symbol
The warnings indicate a potentially dangerous
situation which could result in death, personal injury
or damaged equipment if certain guidelines are not
followed.
UL applications
These flat surface panel mounted controllers are intended to be used in
Listed Generator Assemblies where the suitability of the combination
has been determined by Underwriters Laboratories.
These devices have been evaluated for fire and shock only. The
accuracy and/or reliability of the voltage regulating function have not
been evaluated. Metering, monitoring, protection and signalling
functions have not been evaluated.
DEIF A/S
Page 5 of 57
AGC 200
Installation Instructions
Type of product
The AGC 200 is a micro-processor based control unit containing all
necessary functions for protection and control of a gen-set.
It contains all necessary 3-phase measuring circuits, and all values and
alarms are presented on the LCD display
Options
The AGC 200 product range consists of different basic versions, which
can be supplemented with the flexible options needed to provide the
optimum solution. The options cover e.g. various protections for
generator, busbar and mains, serial communication, additional operator
panels, etc.
DEIF A/S
Page 6 of 57
AGC 200
Installation Instructions
Variants
The following variants of the AGC 200 are available:
With engine communication (CANbus) as standard:
AGC 212:
AGC 213:
Standard functions
Operation modes
DEIF A/S
Start/stop sequences
Page 7 of 57
AGC 200
DEIF A/S
Installation Instructions
Page 8 of 57
AGC 200
Installation Instructions
Overcurrent, 6 levels
Reverse power, 2 levels
Voltage dependent overcurrent
Overvoltage, 2 levels
Undervoltage, 3 levels
Overfrequency, 3 levels
Underfrequency, 3 levels
Overload, 5 levels
Unbalanced current
Unbalanced voltage
Loss of excitation/Q<
Overexcitation/Q>
Multi-inputs, 3 configurable
Digital inputs
Display
M-logic
General
DEIF A/S
USB interface to PC
Free PC utility software for commissioning
Additional functions available
Page 9 of 57
AGC 200
Installation Instructions
AGC 200
No.
Setting
6071
Gen-set mode
Setting
AMF
AMF
Island operation
LOAD
AGC
200
AGC
200
No.
Setting
6071
Gen-set mode
DEIF A/S
Setting
Island operation
Island operation
Page 10 of 57
AGC 200
Installation Instructions
AGC 200
No.
Setting
6071
Gen-set mode
Setting
Fixed power
Fixed power
Peak shaving
AGC 200
AGC 200
No.
Setting
6071
Gen-set mode
Setting
Peak shaving
Peak shaving
Load takeover
AGC 200
No.
Setting
6071
Gen-set mode
DEIF A/S
Setting
Load takeover
Load takeover
Page 11 of 57
AGC 200
Installation Instructions
AGC 200
No.
Setting
6071
Gen-set mode
Setting
Mains power export
AGC 200
AGC 200
No.
Setting
6071
Gen-set mode
DEIF A/S
Setting
Island operation
Island operation
Page 12 of 57
AGC 200
Installation Instructions
AGC
242/243
generator
controllers
DEIF A/S
Page 13 of 57
AGC 200
Installation Instructions
4. Mounting
Mounting of the unit
The unit is designed for mounting in the panel front. The technical
specifications in chapter 7 include detailed information about:
Unit dimensions
Panel cutout
Panel cutout
In order to ensure optimum mounting, the switchboard door must be
cut out according to the panel cutout illustration presented in chapter 7.
Mounting instructions
Fasten the unit with the screw clamps supplied with the unit. These are
to be tightened approx. 0.3 Nm (0.25-0.3 Nm). Tighten with diagonal
sequence method.
DEIF A/S
Page 14 of 57
AGC 200
Installation Instructions
5. Hardware
Unit rear side overview
Page 15 of 57
AGC 200
Installation Instructions
AGC 21x:
CAN C only.
AGC 22x/23x: CAN A and C only.
DEIF A/S
Page 16 of 57
AGC 200
Installation Instructions
LEFT
Multi-in 1
Multi-in 2
Multi-in 3
Multi-in common
RPM MPU/tacho
RPM common
RPM W/NPN/PNP
RIGHT
46
47
48
49
50
51
52
77
78
79
80
81
82
83
84
85
86
87
88
89
90
91
92
93
Di 77 Configurable
Di 78 Configurable
Di 79 Configurable
Di 80 Configurable
Di 81 Configurable
Di 82 Configurable
Di 83 Configurable
Di 84 Configurable
Di 85 Configurable
Di 86 Configurable
MB ON / Di 87
MB OFF / Di 88
GB ON
GB OFF
Common
Not used
D+ (charger gen.)
Input/output lists
In the I/O lists below, the following terms will be used in connection with
the relay outputs:
NO means Normally Open
NC means Normally Closed
Com. means common terminal
DEIF A/S
Page 17 of 57
AGC 200
Installation Instructions
Function
Technical
data
+12/24V DC 12/24V DC
+/-30%
0V DC
Not used
Description
Power supply
Function
Description
Data+ (A)
Technical
data
RS485
4
5
6
7
8
9
10
11
12
13
14
15
Data- (B)
CAN A H
CAN port A
CANshare, power
management, AOP-2 and
external I/O modules
CANshare, power
management, AOP-2 and
external I/O modules
J1939 governor and AVR
analogue regulation
CAN A L
CAN B H
CAN B L
CAN C H
CAN port B
(AGC 242
only)
CAN port C
CAN C L
Function
16
17
18
19
20
21
22
23
24
Relay 16
DEIF A/S
Relay 18
Relay 20
Not used
Relay 23
Technical
data
8A, 30V DC/
250V AC
8A, 30V DC/
250V AC
8A, 30V DC/
250V AC
8A, 36V DC
Description
Status OK/configurable
Horn/configurable
Preheat/configurable
Not used
Stop coil/configurable
With wire break monitoring
Page 18 of 57
AGC 200
Installation Instructions
Function
Technical
data
+12/24V DC Optocoupler
Digital in
Relay 26
16A, 36V DC
Relay 27
16A, 36V DC
Description
Emergency stop and common
for relay outputs 26 and 27
Crank (starter)
RUN coil
Function
28
29
30
31
32
33
34
35
Relay 28
Relay 30
Relay 32
Relay 34
Technical
data
8A, 30V DC/
250V AC
8A, 30V DC/
250V AC
8A, 30V DC/
250V AC
8A, 30V DC/
250V AC
Description
Configurable
Configurable
Configurable
Configurable
DEIF A/S
Function
Technical
data
NC
Relay 8A, 30V DC/
Com
36 250V AC
NO
Relay 39
8A, 30V DC/
250V AC
Relay 41
8A, 30V DC/
250V AC
NC
Relay 8A, 30V DC/
Com
43 250V AC
NO
Description
Mains breaker ON/
configurable
Mains breaker OFF/
configurable
Generator breaker ON
Generator breaker OFF
Page 19 of 57
AGC 200
Installation Instructions
Function
46
47
48
49
50
Multi-in 1
Multi-in 2
Multi-in 3
Common
MPU
Technical
data
Input
Input
Input
Input
RPM input
51
52
Com
W
Common
RPM input
Description
VDO/4-20 mA/Pt100/binary
VDO/4-20 mA/Pt100/binary
VDO/4-20 mA/Pt100/binary
Com. for inputs 46, 47 and 48
Magnetic pick-up/tacho
generator
Com. for inputs 50 and 52
Charge gen. W
NPN/PNP pick-up
Function
53
54
55
56
57
58
59
60
L1 s1
L1 s2
L2 s1
L2 s2
L3 s1
L3 s2
L4 s1
L4 s2
DEIF A/S
Technical
data
1 or 5A AC
Description
1 or 5A AC
Current phase L2
1 or 5A AC
Current phase L3
1 or 5A AC
Configurable: Differential
current, neutral current,
ground current or mains
current
Current phase L1
Page 20 of 57
AGC 200
Installation Instructions
Function
61
62
63
64
65
66
67
L1
L2
L3
Technical
data
100-690V AC
Not used
100-690V AC
Not used
100-690V AC
Not used
Description
Generator line 1
Generator line 2
Generator line 3
Generator neutral
Function
68
69
70
71
72
73
74
75
76
L1
L2
L3
Technical
data
100-690V AC
Not used
100-690V AC
Not used
100-690V AC
Not used
Description
Mains line 1
Mains line 2
Mains line 3
Mains neutral
Not used
Not used
All AC voltage inputs are galvanically separated from the
rest of the unit. Voltages are indicated in phase-phase
values.
DEIF A/S
Page 21 of 57
AGC 200
Installation Instructions
Function
77
78
79
80
81
82
83
84
85
86
87
88
89
90
91
92
93
Di 77
Di 78
Di 79
Di 80
Di 81
Di 82
Di 83
Di 84
Di 85
Di 86
Di 87
Di 88
Di GB ON
Di GB OFF
Com
Di
Technical
data
Optocoupler
Optocoupler
Optocoupler
Optocoupler
Optocoupler
Optocoupler
Optocoupler
Optocoupler
Optocoupler
Optocoupler
Optocoupler
Optocoupler
Optocoupler
Optocoupler
Common
Not used
D+
Description
Configurable
Configurable
Configurable
Configurable
Configurable
Configurable
Configurable
Configurable
Configurable
Configurable
MB ON/configurable
MB OFF/configurable
Gen. breaker ON feedback
Gen. breaker OFF feedback
Common for inputs 77 to 90
Charger generator D+ running
feedback and digital running
feedback
Function
SD
Memory
Technical
data
SD memory
USB
PC conn
USB B
RJ45
TCP/IP
Ethernet
DEIF A/S
Description
Additional memory space for
lifetime logging of data
Connection for PC
programming
Modbus TCP/IP connection
Page 22 of 57
AGC 200
Installation Instructions
DEIF A/S
Page 23 of 57
AGC 200
Installation Instructions
LEFT
Multi-in 1
Multi-in 2
Multi-in 3
Multi-in common
Not used
Not used
Not used
RIGHT
46
47
48
49
50
51
52
77
78
79
80
81
82
83
84
85
86
87
88
89
90
91
92
93
Di 77 Configurable
Di 78 Configurable
Di 79 Configurable
Di 80 Configurable
Di 81 Configurable
Di 82 Configurable
Di 83 Configurable
Di 84 Configurable
Di 85 Configurable
Di 86 Configurable
MB ON / Di 87
MB OFF / Di 88
(B)TB ON
(B)TB OFF
Common
Not used
Not used
DEIF A/S
Page 24 of 57
AGC 200
Installation Instructions
Function
Technical
data
+12/24V DC 12/24V DC
+/-30%
0V DC
Not used
Description
Power supply
Function
Description
Data+ (A)
Technical
data
RS485
4
5
6
7
8
9
10
11
12
13
14
15
Data- (B)
CAN A H
CAN port A
CAN A L
CAN B H
CAN port B
CAN B L
CAN C H
CAN port C
Not used
Technical
data
8A, 30V DC/
250V AC
8A, 30V DC/
250V AC
8A, 30V DC/
250V AC
Description
CAN C L
Function
16
17
18
19
20
21
22
23
24
Relay 16
DEIF A/S
Relay 18
Relay 20
Not used
Relay 23
8A, 36V DC
Status OK/configurable
Horn/configurable
Configurable
Not used
Configurable
With wire break monitoring
Page 25 of 57
AGC 200
Installation Instructions
Function
Technical
data
+12/24V DC Optocoupler
Digital in
Relay 26
16A, 36V DC
Relay 27
16A, 36V DC
Description
Emergency stop
Not used
Not used
Function
28
29
30
31
32
33
34
35
Relay 28
Relay 30
Relay 32
Relay 34
Technical
data
8A, 30V DC/
250V AC
8A, 30V DC/
250V AC
8A, 30V DC/
250V AC
8A, 30V DC/
250V AC
Description
Configurable
Configurable
Configurable
Configurable
DEIF A/S
Function
Technical
data
NC
Relay 8A, 30V DC/
Com
36 250V AC
NO
Relay 39
8A, 30V DC/
250V AC
Relay 41
8A, 30V DC/
250V AC
NC
Relay 8A, 30V DC/
Com
43 250V AC
NO
Description
Mains breaker ON/
configurable
Mains breaker OFF/
configurable
(Bus) tie breaker ON
(Bus) tie breaker OFF
Page 26 of 57
AGC 200
Installation Instructions
Function
46
47
48
49
50
51
52
Multi-in 1
Multi-in 2
Multi-in 3
Common
Not used
Not used
Not used
Technical
data
Input
Input
Input
Input
Description
VDO/4-20 mA/Pt100/binary
VDO/4-20 mA/Pt100/binary
VDO/4-20 mA/Pt100/binary
Com. for inputs 46, 47 and 48
Function
53
54
55
56
57
58
59
60
L1 s1
L1 s2
L2 s1
L2 s2
L3 s1
L3 s2
DEIF A/S
Technical
data
1 or 5A AC
Description
1 or 5A AC
Current phase L2
1 or 5A AC
Current phase L3
Current phase L1
Not used
Page 27 of 57
AGC 200
Installation Instructions
Function
61
62
63
64
65
66
67
L1
L2
L3
Technical
data
100-690V AC
Not used
100-690V AC
Not used
100-690V AC
Not used
Description
Mains line 1 (AGC 244: BB A)
Mains line 2 (AGC 244: BB A)
Mains line 3 (AGC 244: BB A)
Neutral
Function
68
69
70
71
72
73
74
75
76
L1
L2
L3
Technical
data
100-690V AC
Not used
100-690V AC
Not used
100-690V AC
Not used
Description
Busbar line 1 (AGC 244: BB B)
Busbar line 2 (AGC 244: BB B)
Busbar line 3 (AGC 244: BB B)
Neutral
Not used
Not used
All AC voltage inputs are galvanically separated from the
rest of the unit. Voltages are indicated in phase-phase
values.
DEIF A/S
Page 28 of 57
AGC 200
Installation Instructions
Function
Technical
data
Di 77
Optocoupler
Di 78
Optocoupler
Di 79
Optocoupler
Di 80
Optocoupler
Di 81
Optocoupler
Di 82
Optocoupler
Di 83
Optocoupler
Di 84
Optocoupler
Di 85
Optocoupler
Di 86
Optocoupler
Di 87
Optocoupler
Di 88
Optocoupler
Di (B)TB ON Optocoupler
Di (B)TB
Optocoupler
OFF
Com
Common
Not used
Not used
Description
Configurable
Configurable
Configurable
Configurable
Configurable
Configurable
Configurable
Configurable
Configurable
Configurable
MB ON/configurable
MB OFF/configurable
(B)TB ON feedback
(B)TB OFF feedback
Common for inputs 77 to 90
Function
SD
Memory
Technical
data
SD memory
USB
PC conn
USB B
RJ45
TCP/IP
Ethernet
DEIF A/S
Description
Additional memory space for
lifetime logging of data
Connection for PC
programming
Modbus TCP/IP connection
Page 29 of 57
AGC 200
Installation Instructions
6. Wirings
AC connections
The AGC 200 can be wired up in three-phase, single phase or split
phase configuration.
Contact the switchboard manufacturer for accurate
information about required wiring for the specific
application.
DEIF A/S
Page 30 of 57
AGC 200
Installation Instructions
DEIF A/S
Page 31 of 57
AGC 200
Installation Instructions
DEIF A/S
Page 32 of 57
AGC 200
Installation Instructions
DEIF A/S
Page 33 of 57
AGC 200
Installation Instructions
DEIF A/S
Page 34 of 57
AGC 200
Installation Instructions
DEIF A/S
Page 35 of 57
AGC 200
Installation Instructions
DEIF A/S
Page 36 of 57
AGC 200
Installation Instructions
Page 37 of 57
AGC 200
Installation Instructions
DEIF A/S
Page 38 of 57
AGC 200
Installation Instructions
DC connections
Digital inputs
Battery positive to input:
Emergency stop:
DEIF A/S
Page 39 of 57
AGC 200
Installation Instructions
Multi-inputs
(0)4-20 mA
Active transmitter
2-wire transmitter
DEIF A/S
Page 40 of 57
AGC 200
Installation Instructions
VDO
1-wire
2-wire
NPN sensor
DEIF A/S
Page 41 of 57
AGC 200
Installation Instructions
PNP sensor
DEIF A/S
Page 42 of 57
AGC 200
Installation Instructions
D+ connection, terminal 93
Relay
Wire break
detection
Page 43 of 57
AGC 200
Installation Instructions
Communication
CANbus
Examples with three AGC 242 units connected.
It is not possible to mix CANbus wiring interface A and B.
CANbus interface A
CANbus interface A
CANbus interface A
CANbus interface B
CANbus interface B
CANbus interface B
DEIF A/S
Page 44 of 57
AGC 200
Installation Instructions
DEIF A/S
Page 45 of 57
AGC 200
Installation Instructions
DEIF A/S
Page 46 of 57
AGC 200
Installation Instructions
DEIF A/S
Page 47 of 57
AGC 200
Installation Instructions
DEIF A/S
Page 48 of 57
AGC 200
Installation Instructions
DEIF A/S
Page 49 of 57
AGC 200
Installation Instructions
7. Technical information
Technical specifications
Accuracy:
Class 1.0
-40153070C
Temperature coefficient:
+/-0.2% of full scale per 10C
Short circuit:
5% of 3.5*nominal current
Earth current:
2% of 1A or 5A
To IEC/EN 60688
Operating temp.:
UL/cUL Listed:
-2570C (-13...158F)
Max. ambient temp. 50C/122F
-4070C (-40...158F)
Storage temp.:
-4070C (-40...158F)
Climate:
100690V AC (+20%)
100600V AC
Phase to phase
Load:
1.5 M
Frequency:
3070 Hz
DEIF A/S
Page 50 of 57
AGC 200
Meas. current:
Installation Instructions
Current overload:
4 x In continuously
20 x In, 10 sec. (max. 75A)
80 x In, 1 sec. (max. 300A)
Magnetic pick-up
input:
Aux. supply:
UL/cUL Listed:
Voltage:
2-70 V peak
Frequency: 10-10000 Hz
Resistance: 250-3000
6-36V DC continuously
9-32.5V DC
0V DC for 50 ms when coming from at least 12V
DC (cranking dropout)
Max. 25 W consumption
With option L2 -40C (-40F)
Max. 45 W consumption
The aux. supply inputs are to be protected by a
12A slow-blow fuse
Passive binary
input voltage:
Emergency stop
input voltage:
DEIF A/S
Bi-directional optocoupler
ON:
836V DC
<2 V:
OFF
Impedance: 4.7 k
ON:
+836V DC (term. 25)
<2 V:
OFF
Impedance: 4.7 k
Page 51 of 57
AGC 200
Multi-functional
inputs:
Installation Instructions
Current input:
0(4)-20 mA
From active transmitter:
0-20 mA, +/-1%
Impedance: 50
Binary input:
Dry contact inputs
3V DC internal supply, with cable supervision
Max. resistance for ON detection: 100
Pt100:
-40250C (-40482F) +/-1%
To IEC/EN 60751
VDO:
0-2500 , +/-1%
Relay outputs,
electrical rating:
Relays 16-20 and
28-43:
UL/cUL Listed:
250V AC/30V DC 8A
250V AC/30V DC 6A General use
B300 Pilot duty
Relay 23:
UL/cUL Listed:
36V DC 8A
24V DC 8A General use
36V DC 16A
24V DC 16A General use
Mounting:
Panel mounted
Front size:
Display:
DEIF A/S
Page 52 of 57
AGC 200
Installation Instructions
Safety:
Protection:
EMC/CE:
To EN 61000-6-1/2/3/4
IEC 60255-26
IEC 60533 power distr. zone
IACS UR E10 power distr. zone
Vibration:
Shock:
Bump:
Material:
DEIF A/S
Page 53 of 57
AGC 200
Installation Instructions
Response times:
(Delay set to min.)
Busbar:
Over-/undervoltage:
Over-/underfrequency:
< 50 ms
< 50 ms
Generator:
Reverse power:
Overcurrent:
Short circuit:
Directional overcurrent:
Over-/undervoltage:
Over-/underfrequency:
Overload:
Current unbalance:
Voltage unbalance:
React. power import:
React. power export:
Negative sequence I:
Negative sequence U:
Zero sequence I:
Zero sequence U:
Overspeed:
Digital inputs:
Analogue input:
Emergency stop:
Earth current:
<200 ms
<200 ms
< 40 ms
<100 ms
<200 ms
<300 ms
<200 ms
<200 ms
<200 ms
<200 ms
<200 ms
<400 ms
<400 ms
<400 ms
<400 ms
<400 ms
<250 ms
<250 ms
<200 ms
<100 ms
DEIF A/S
Page 54 of 57
AGC 200
Mains:
Installation Instructions
df/dt (ROCOF):
Vector jump:
Positive sequence:
<130 ms (4 periods)
< 40 ms
< 60 ms
UL markings:
Wiring:
Wire size:
AWG 30-12
Terminal tightening
torque:
5-7 lb-in
Mounting:
Installation:
DEIF A/S
Page 55 of 57
AGC 200
Installation Instructions
Unit dimensions
DEIF A/S
Page 56 of 57
AGC 200
Installation Instructions
Panel cutout
DEIF A/S