Documente Academic
Documente Profesional
Documente Cultură
SILVER
CERTIFICATION COURSE
TELECOM SUPPORT INFRASTRUCTURE
BATTERY UPS AND EARTHING
Version 2 June 2014
INDEX
2.1
Introduction ..................................................................... 2
2.2
Objective........................................................................... 2
2.3
2.4
2.5
2.6
2.7
2.8
Summary ........................................................................ 33
2.9
2.10
Page 1 of 36
INTRODUCTION
2.2
OBJECTIVE
2.3
2.4
2.5
2.6
2.7
2.8
SUMMARY
2.9
2.10
2.1
INTRODUCTION
The secondary cell batteries can be utilized in many ways. However presently
float working is adopted. The two type of batteries used are Conventional batteries and
Maintenance Free VRLA batteries. Maintenance free, valve-regulated lead-acid (VRLA)
batteries ensure a reliable, effective and user friendly source of power. It is spill proof,
leak proof and explosion resistant and there is no need to add water or to clean terminals.
Uninterrupted Power Supply (UPS) is required to provide stable AC in the event
of failure of Mains. It comprises of Battery banks coupled with inverter. An inverter is an
electrical device that converts direct current (DC) obtained from battery to alternating
current (AC); the converted AC can be at any required voltage and frequency with the use
of appropriate transformers, switching, and control circuits.
Earthing is an essential part of any electric /electronic system to prevent damage
and for proper operation of telecom equipment. Utmost care is required to be taken for
provision of proper and effective earthing for various telecom installations.
2.2
OBJECTIVE
The objective of this chapter is:
Page 2 of 36
2.3
In this system the electrical energy derived from the supply mains is first
converted into chemical energy and stored in the battery Subsequently the chemical
energy is reconverted into electrical energy when the battery discharges into the exchange
load. In the charge discharge system the entire DC supply for the equipment is taken from
the battery.
ii)
In this system, the DC electrical energy for the operation of the equipment is
drawn directly from the public AC power supply system through mains conversion
equipment and the standby battery is kept fully charged and idle, i.e. not connected to the
load. Whenever there is mains failure the equipment load is immediately transferred from
the mains conversion equipment to the standby battery.
Page 3 of 36
Float System:
It is a variation of the standby battery scheme as in this system also, the battery
supplies only the emergency reserve requirements of the equipment during mains failure.
Unlike the standby battery scheme, the battery is always kept connected across the load in
the float system in a fully charged state. But the operating conditions are so maintained
that the floated battery does not discharge into the load as long as the mains power supply
is available. The main distinction between the floating battery scheme and the standby
battery scheme is that in the float scheme, there is absolutely no break in the DC power
supply when the mains supply fails as the emergency battery takes over the load
instantaneously. It is not the case for the standby scheme.
Page 4 of 36
practically all the DC power requirements are taken directly from the public AC mains
supply through converters. With the battery connected in parallel almost full battery
capacity is available to carry the equipment load under mains failure conditions. It is
usually to provide a battery capacity equivalent to six times the busy hour load in float
systems.
2.3.1
Operating procedure
The operating procedure for floating batteries depends to a great extent on the
floating voltage. The floating voltage cannot be higher than 2.35 volts per cell since
beyond this limit, overcharging and vigorous gassing of the battery occurs. The lower
limit for the floating voltage of a lead acid cell is 2 volts, since below this voltage, the
battery will discharge. Within the permissible range of floating voltage from 2.0 to 2.35
volts per cell, three distinct types of full float schemes have been evolved. They are as
follows:Batteries floated between 2.02 to 2.07 volt per cell or divided battery float system.
Batteries floated between 2.15 to 2.20 volt per cell or parallel battery float system.
Batteries floated between 2.24 to 2.30 volt per cell or end cell switching system.
2.3.2
2.3.3
Page 5 of 36
Initial Charging
Initial charging is the charge received by any battery for the first time after
installation. The following procedure is a general guideline for the first or initial charge.
The instructions given by the manufacturer is to be followed strictly.
General:
Make sure that the battery room is well ventilated. Install batteries so that they are
not exposed to direct rays from the sun and are away from steam pipes, radiators and
other heat generating equipment, as a warm battery tends to have a self discharge at an
accelerated rate, increasing the load on the power supply and shortening life of the
battery. Align the cells and make sure all connections are tight.
Initial Charge
Before placing the battery on charge, check and record the open circuit voltage of
every cell. After this connect the battery for charging continuously at the rate specified
for 80 hours or as specified by the manufacturer by using direct current. The voltage
output from the charger should be minimum 2.7 volts per cell. Another method of
charging prescribed is start the charging @ 14% of AH capacity and as the cells start
gassing reduce the rate of charge to 7% till the end of the charge.
As soon as the battery is put on charge, take another set of voltage readings and
enter these readings opposite to open circuit voltage readings. This is to check if there are
any reversed cells and to avoid reverse connection of the entire battery. If the battery is
connected properly and there are no reversed cells, proceed with charging. During first
charge take individual cell voltage, S. G. and temperature readings for every eight hours
and record
The cells are considered to be fully charged when values of cell voltage and S.G.
of electrolyte corrected to 27o C remain constant for three consecutive hours at the end of
approximately 80 hours of charging. However in spite of achieving constancy of S.G. and
voltage readings, initial charge has to be continued for 80 hours (in the case of 80 hrs of
charge method). The voltage at the end of initial charge will be 2.65 to 2.7 volts per cell
The temperature of electrolyte in the cells at any period of charge should not be
allowed to rise beyond 50o C
At the end of charging the S.G. of electrolyte is to be adjusted to 1.200 0.005 at
27 o C. If the S.G. at the end of charging is above 1.200, add distilled water and if it is
below 1.200 add 1.400 S.G. acid. If any of the cells show abnormally low S.G. / voltage
at the end of 80 hours initial charging inform the supplier.After ensuring that the cell is
fully charged, give a rest of 12 to 24hrs and conduct test discharge to ensure the
following.
Normally the capacity does not reach 100% until 4 or 5 cycles of charge
discharges.
2.3.5
Test Discharge
Test discharge is conducted at 10 hr rate.
Page 6 of 36
Discharging procedure
Connect cable lugs to the cable for connecting artificial load to the battery.
Prepare artificial load.
Connect the connecting cable to the artificial load.
Disconnect the battery from the float /charger.
Connect the connecting cable to the ammeter in the circuit.
Take the open circuit voltage of the battery and of each individual cell.
Connect the connecting cable to the battery fuse output by nut and bolts in
battery room.
Adjust the artificial load to get 10hour discharge rate. Adjust the artificial
load frequently to maintain constant current.
The total voltage of the battery, the voltage, specific gravity and
temperature of each cell should be read at the beginning of the discharge
and at hourly intervals up to the 8th hour and these readings are taken
every 15 minutes after 8-1/2 hours of discharge. These readings should be
recorded in the form given.
Stop discharge if the electrolyte temperature exceeds 37.8 c (100F) and
start discharge when the temperature falls sufficiently below 35 c.
The test discharge shall be stopped as soon as the overall battery voltage
reaches a value equivalent to 1.85 V x no. Of cells in series (44.4 V for 24
cell Battery) or when the voltage across any cell falls to 1.70V whichever
is earlier.
Cells have to be recharged soon after discharge
Page 7 of 36
Recharging
Recharging is done at two rates. The staring rate being maintained till the cells
reach 2.4 Volts per cell, after which at the finishing rate till end of charge. The high rate
of charge is normally 14 % and finishing rate is 7 % of battery capacity. Charging should
be completed at 7% of the capacity till full charge. Alternatively, the cells can be charged
at 10 hour rate till constancy. The battery is considered fully charged when all the cells
gas freely for 2 hours and the cell voltage and S.G. remain constant for 3 consecutive
hours thereafter.
It is recommended to conduct cycles of discharge and charge as above before
connecting to the associated equipment. Find out the efficiency of the battery. If 100%
capacity is attained in the 1st discharge itself then there is no need to discharge it for a
second time. Strict adherence to the instructions and maintenance manual supplied by
manufacturer is a must for making any complaint to the supplier. All records as per the
suppliers is instructions must be maintained.
2.4
One of the primary requirements of any telephone system is that service shall be
available to the subscribers at all times. The electrical energy required for signaling,
switching, speech transmission etc. in telephone exchanges is derived either directly or
indirectly from the public electricity system. In order to provide uninterrupted service, the
exchange power supply system is designed to give continuous energy to the system. So
provision is also made for alternate source of supply in the event of mains failure. This
emergency energy is derived from Batteries of secondary cells or a combination of
battery and prime mover generator sets.
The secondary cells in general use in our dept. are of lead acid type. Secondary
cells are electrolytic cells for generation of electric energy. These cells can be restored to
its original condition after they are discharged. This restoration is done by passing a
current in a direction opposite to the flow of current in the cell during the discharge.
2.4.1
There are three types of storage (secondary) cells in use. They are (1) lead-leadacid type (2) Nickel-iron-alkaline and (3) Nickel-Cadmium alkaline type. In telecom only
lead-lead-acid type is used. They are commonly known as lead acid type cell. These cells
have electrodes of lead immersed in an electrolyte of dilute sulphuric acid in a suitable
container
There are two lead-acid designs in use today: the flooded and the valve regulated
(VRLA). Of the two designs, the flooded battery is the more reliable and should be the
battery of choice for mission critical applications. VRLA batteries have the advantage of
lower cost and lower space requirements
Page 8 of 36
2.5
VRLA Technology
The electrode reaction in all lead acid batteries including VRLA battery is
basically identical. As the battery is discharged, the lead dioxide positive active material
and the spongy lead negative active material react with the sulphuric acid electrolyte to
form lead sulphate and water. During charge, this process is reversed. The Columbic
efficiency of the charging process is less than 100% on reaching final stage of charging or
under over charge conditions, the charging energy is consumed for electrolytic
decomposition of water and the positive plates generate oxygen gas and the negative
plates generate hydrogen gas.
EETP/ BSNL Silver Certification Course /Ver.02/June 2014
For Restricted Circulation
Page 9 of 36
Under typical charging conditions, oxygen at the positive plate occurs before
hydrogen evolution at the negative. This feature is utilized in the design of VRLA
batteries. In flooded cells, the oxygen gas evolved at the positive plate bubbles upwards
through the electrolyte and is released through the vents. In MF-VRLA batteries the
oxygen gas evolved, at the positive plate, instead of bubbling upwards is transported in
the gas phase through the separator medium to the negative plate. The separator is a
highly absorbent glass matrix type with very high porosity, designed to have pore volume
in excess of the electrolyte volume (starved electrolyte design), due to which the oxygen
gas finds an unimpeded path to the negative plate.
The oxygen gas gets reduced by reaction with the spongy lead at the negative
plate, turning a part of it into a partially discharged condition, there by effectively
suppressing the hydrogen gas evolution at the negative plate. This is what is known as the
oxygen recombination principle. The part of negative plate which was partially
discharged is then reverted to the original spongy lead by subsequent charging.
Thus, a negative plate keeps equilibrium between the amount which turns into
spongy lead by charging and the amount of spongy lead which turns into lead sulphate by
absorbing the oxygen gas generated at the positive plate. The oxygen recombination
principle can be shown by the following reaction:
Reaction at positive plate:
(1)
H2O = O2 + 2e
Reaction at negative plate :
Pb + 1/2O2
PbO+H2SO4 =
PbSO4 + H2O
(2)
PbO
(3)
To reaction (1)
PbSO4 + 2H+ + 2e =
(4)
Pb + H2SO4
To reaction (3)
To reaction (2)
H2O
Page 10 of
Freshening Charge
Batteries lose some charge during transportation as well as during the period prior
to installation. A battery should be installed and given a freshening charge after receipt as
soon as possible. Battery positive (+) terminal should be connected to charge positive (+)
terminal and battery negative (-) terminal to charger negative (-) terminal.
The charge intervals for storage are given below.
Temp in centigrade
32
6.0
37
4.5
42
3.0
47
2.25
52
1.5
Storage beyond this period without freshening charge can result in excessive
sulphation of the plates.
Page 11 of
Time
2.25
30 hrs
2.30
12 hrs
Note: Time periods listed in Table 1 are for temperatures from 15oC to 40C. For
temperatures below 15C double the number of hours. Charging
The charging current should be limited to a maximum of 0.2 times of AH
Capacity. Widely accepted charging methods use a current of 0.1xC10 (C10 = AH
Capacity when discharged at 10 hr rate) Example:
A 2000 AH VRLA battery is to be charged as under
0.2 x 2000
0.2 x 2000 = 400 Amps or
0.1 x 2000 = 200 Amps ( as per TEC recommendation)
Raise the voltage to the maximum value not exceeding 2.37 volts per cell
permitted by the system equipment. When charging current has tapered and stabilized (no
further reduction for three hours), charge for the hours shown in the above table or until
the lowest cell voltage ceases to rise. Correct charge time for the temperature at the time
of stabilization. To determine lowest cell, monitoring should be performed during the
final 10% of the charge time. All POWER STACK batteries are rated to an end cell
voltage of 1.75 VPC at all rates of discharge.
2.5.5
Page 12 of
Given below are the float and boost voltage recommended for the POWER
STACK battery system. The average Volts per cell (VPC) value of the series string
should be set to the recommended voltage under Float and Boost conditions.
RECOMMENDED FLOAT VOLTAGE 2.25 VPC AT 27C
RECOMMENDED BOOST VOLTAGE 2.30 VPC AT 27C
Modern constant voltage output charging equipment is recommended for the
floating charger method of operation of batteries. This type of charger, properly adjusted
to the recommended float voltage and following recommended surveillance procedures,
will assist in obtaining consistent serviceability and optimum life. The charging current
for the battery should be limited to 20% of its nominal AH capacity.
After the battery has been given its freshening charge (refer to section 4), the
charger should be adjusted to provide the recommended float voltage at the battery
terminals. Do not use float voltages lower or higher than those recommended. This will
result in reduced capacity and/or reduced battery life.
2.5.7
Pilot Cell- A pilot cell is selected in the series string to reflect the general
condition of all cells in the battery. The cell selected should be the lowest cell
voltage in the series string following the initial charge.. Reading and recording
pilot cell voltage monthly serves as an indicator of battery condition between
scheduled overall individual cell readings.
Temporary Non-use- An installed battery that is expected to stand idle for over
6 months should be treated as follows. Give the battery an equalizing charge
as per section 6. Following the equalizing charge, open connections at the
battery terminals to remove charge and load from the battery. Every six
months, temporarily connect battery to charger and give it an equalizing
charge. To return the battery to normal service, re-connect the battery to the
charger and load, give an equalizing charge and return the battery to float
operation.
Determination of State of Charge of VRLA Batteries
Sealed Maintenance Free Valve Regulated Lead Acid Batteries represent the state
of the art in Lead Acid technology.
The maintenance-free feature of these batteries often raises a practical problem in
the field. How can the battery bank be monitored? In conventional flooded batteries, the
specific gravity of the electrolyte gives a fairly good indication of the state of charge of
the battery. However, in a VRLA battery, it is not possible to measure the specific gravity
of the electrolyte since it is completely absorbed in the spun glass microporous separator.
The terminal voltage of the battery is directly related to the concentration of the
electrolyte. Therefore, if one were to measure the open circuit voltage of the battery, the
state of charge can be determined. The Open Circuit Voltage (OCV) readings should be
taken 24 hrs after charging is discontinued. The OCV value is co-related to the state of
charge of VRLA batteries as per the table enclosed.
Sometimes, it may not possible to disconnect the batteries from service for 24 hrs.
and then check the OCVs. Then the pattern of charging current delivered by a
EETP/ BSNL Silver Certification Course /Ver.02/June 2014
36
For Restricted Circulation
Page 13 of
0.43
C5
0.58
C3
0.68
CAUTION:
It was noticed in some of the exchanges during the normal course of day to day
working, the exchange failing due to low voltage condition even though the batteries
appear to be in healthy condition while they are on float as indicated by the daily readings
recorded. To avoid this it is recommended that the batteries be discharged periodically;
say once in a month by switching off the FR and the exchange load may be allowed to be
taken by the battery for half an hour. The individual cell readings are to be taken and no
cell voltage should fall below 2.10 V. Some cells which are faulty, may show negative
values with reference to the other cells. If the voltage of any individual cell differs from
others in this manner it is recommended that the cell be replaced.
Table 3
% State of Charge
100
2.15
90
2.13
80
2.11
70
2.09
60
2.07
Page 14 of
50
2.05
40
2.03
30
2.01
20
1.97
1.95
Float charging is at 2.23 VPC and the recommended boost charge voltage is 2.30
VPC. If the charger does not have a float cum boost mode, it is important to switch over
to float after boost not later than 24 hours under steady current conditions.
2.5.8
Safety precautions
In normal use, VRLA batteries will not release hydrogen and oxygen gasses, will
not release acid mist and will not leak acid. Thus they are safer than conventional lead
acid batteries. However, under abnormal conditions, or as a result of damage, misuse or
abuse, these potentially hazardous conditions can occur. Hence the instructions given by
the supplier is to be strictly followed.
2.5.9
limits
Module arrangements
Max Modules
8 High
8 High
on
stacked
battery
The points to be taken care to observe the health of the battery and expected
residual capacity
Periodic physical inspection of each cell of the battery for cracks and leaking etc.
Discharge of battery for a short duration and recording the voltages of each cell
in the string.
Measurement of a mark deviation (>30%) in the impedance or conductance of
the cell as compared to the one recorded at the time of commissioning.
Measurement & recording of cell temp periodically.
Float Voltage of cells & its comparison with the midpoint voltage.
Float current in fully charged battery.
Page 15 of
2.5.10
Page 16 of
2.6
Page 17 of
2.6.2
DC
DC
AC Output
Battery
Circuit Description
Basic designs
In one simple inverter circuit, DC power is connected to a transformer through the
centre tap of the primary winding. A switch is rapidly switched back and forth to
allow current to flow back to the DC source following two alternate paths through
one end of the primary winding and then the other. The alternation of the direction
of current in the primary winding of the transformer produces alternating current
(AC) in the secondary circuit..
The electromechanical version of the switching device includes two stationary
contacts and a spring supported moving contact. The spring holds the movable
contact against one of the stationary contacts and an electromagnet pulls the
movable contact to the opposite stationary contact. The current in the
electromagnet is interrupted by the action of the switch so that the switch
continually switches rapidly back and forth. This type of electromechanical
inverter switch, called a vibrator or buzzer, was once used in vacuum tube
automobile radios. A similar mechanism has been used in door bells, buzzers and
Page 18 of
tattoo guns. As they became available with adequate power ratings, transistors and
various other types of semiconductor switches have been incorporated into
inverter circuit designs.
b) Input BTY
c) Output
d) Output current
2) Over load
- If the load on UPS is more than its capacity UPS will be tripped
and overload alarm comes
Page 19 of
2.6.4
3) Output High
- When output voltage becomes high UPS will be tripped and this
alarm comes.
4) Output low
When output voltage becomes low UPS will be tripped and this
alarm comes.
5) Trip
UPS Maintenance
Maintenance of the UPS consists of preventive and corrective maintenance.
Preventive maintenance consists of a scheduled list of activities. Performing these
activities keeps the UPS in good working order and helps to prevent failures.
Corrective maintenance is performed as a result of a failure. Corrective
maintenance fixes the problem and gets the unit working again.
A general guide for the maintenance requirements of the UPS systems modules,
static switches, and controls is provided. Although electronic components are not
subject to wear in the same degree as electromagnetic (EM) components, they do
require systematic maintenance.
Preventive maintenance
Periodic maintenance is required to maintain the integrity and lifetime of the
battery. Power electronic equipment also requires scheduled maintenance even
though solid-state devices are used. Preventive maintenance may require that the
UPS system be shut down. A transfer of the critical load which may not provide
the power enhancement capabilities of an UPS system is something that the user
must tolerate in order to obtain maximum reliability and minimize downtime and
repair costs.
Equipment record
This record should list the basic information on the equipment itself, e.g.,
manufacturers identification, style, serial, size, location, etc., and incorporate
inventory-control data for spare parts. Warranty requirements covering
uninterruptible operating conditions should be abstracted from the users manual.
Page 20 of
Use of records
These records provide for a workable preventive maintenance program. The
information obtained from the necessary periodic inspections can be quickly lost.
This is particularly true when test results are required. Unless records and data on
the test and performance of equipment are retained, the maintenance program will
be defeated. Unless records are updated at each succeeding test period, valuable
information is lost. Comparative test data materially assists an UPS specialist in
defining problems, especially when test results differ from manufacturers
recommended settings or actual factory test data. Significant changes in
comparative test data can, in general, be related to the equipments condition.
Scheduling
Scheduling of UPS and battery maintenance is normally based on the
manufacturers recommendations. Since an UPS system is vital to the operation of
critical loads, it may be considered advisable to provide more inspections than
those the manufacturer recommends. Certain items on the UPS should be
inspected daily or weekly. This inspection can be done by operating personnel, but
data should be recorded and sent to the appropriate maintenance point not more
than 5 days after being recorded. Battery maintenance should be done by
maintenance personnel. Visual monitoring data should be recorded daily for the
UPS, and if recorded for the battery, the recorded data should be handled and sent
on to the maintenance department on a weekly basis.
2.6.5
Quarterly:
Page 21 of
Visually inspect equipment for loose connections, burned insulation or any other
signs of wear.
Semiannually:
Visually check for liquid contamination from batteries and capacitors.
Clean and vacuum UPS equipment enclosures.
Check HVAC equipment and performance related to temperature and humidity.
Annually:
Conduct thermal scans on electrical connections to ensure all are tight and not
generating heat, which is the first and sometimes only indication of a problem. A
non-evasive diagnostic tool helps technicians identify hot spots invisible to the
human eye. Technicians should retorque if thermal scan provides evidence of a
loose connection. Provide a complete operational test of the system, including a
monitored battery-rundown test to determine if any battery strings or cells are near
the end of their useful lives.
Biannually:
Test UPS transfer switches, circuit breakers and maintenance bypasses. If a
generator is part of the buildings emergency-power system and feeds the UPS, it
also will need to be tested monthly or quarterly. Most facilities have a generatormaintenance schedule in place in which testing frequency is defined. A UPS
typically is sized to carry the load for a short period of time. Longer outages
require backup-power generation to maintain critical services. Each facility is
unique, and managers need to develop a maintenance schedule to suit each sites
specific needs.
2.7
Reduction of Crosstalk and Noise is achieved through proper Earthing System in the
Telecom Network.
Earthing is used to afford convenience & reliability, in the operative path of the
circuits involved in the switching apparatus of telecom circuits.
Used as return path in telegraph and voice circuits.
Earthing is used for protection of costly apparatus and persons against foreign
voltages and leakage currents.
Earthing is used for protection of buildings and equipments from lightening strikes.
Page 22 of
2.7.1
2.7.2
2.7.3
System earthing.
Equipment earthing.
System Earthing:It means connecting to the earth, the neutral point i.e the star point of generator,
transformer, rotating machines, and of grounding transformer. If neutral point of a
system is earthed, the phase to ground voltage under earth fault condition do not
rise to high value
Let us consider a system in which neutral is not earthed. If there is Earth fault on
B-phase, the voltage of R and Y (wealthy) phases to the earth becomes equal to
the line voltage. The rise in voltage causes stress on the insulation. Earthing
provides protection against such rise.
Page 23 of
2.7.4
Mesh Earthing :-
Page 24 of
Strip Electrodes:-
It shall not be smaller in size than 40 Sq.mm section if of copper and 25x4 mm if
of galvanized iron. For round conductors it should be not less than 3 mm2 in case
of copper and 6 mm2 if of galvanized iron. The length of buried conductor shall
not be less than 15 meter laid in trench not less than 0.5 meter depth.
c)
Plate Electrode:-
In it, the plate is made of either copper or galvanized iron. This type of earthing
(as shown in Fig.) is mostly used in our department. Size of copper plate shall not
be less than 600 x 600 x 3 mm. And that of G.I. be 600 x 600 x 6 mm. Plate shall
be 3 meter. Where earth resistance is not sufficient with one plate, two or more
plate electrodes may be connected in parallel. This type is most suited for
generating stations & sub-stations.
2.7.6
Earthing Conductor :The conductor from Earth Electrode to Earth shall be of the material as Earth
electrode i.e. G.I. or copper and be in the form of strip or wire size of Earthing
conductor which shall not be less than the following
However Earthing conductor, shall not be more than 150 Sq. mm in Case of G.I.,
or 100 Sq. mm in case of copper, unless otherwise specified.
2.7.7
Ring earthing
Plate earthing
Spike Earthing
Page 25 of
Mesh earthing
Static earthing
Ring Earthing
Page 26 of
Page 27 of
Fig10.
Plate Earth
Page 28 of
Fig11.
Fig12.
Plate earth
Spike Earth
Page 29 of
Fig13.
Spike earth
Page 30 of
Fig14.
Earth distribution
Static Earthing
Page 31 of
The human body has a low enough volume resistivity to act as a conductor and
if insulated from earth it can accumulate electrostatic charge. A troublesome
consequence of the electrostatic potential on charged personnel is that it can be
high enough to cause damage to electrostatic sensitive devices, such as
semiconductors, when these are being handled or assembled. Antistatic or
conductive type materials can be used to avoid retention of static electricity. If
antistatic floor is not provided, anti static wrist strap, which is properly earthed,
shall be used while working on such equipments. In NT Exchanges with false
floor the jack s below the false floor are earthed for protection against static
electricity.
2.7.8
Since material resistivity does not play a part in the resistance of earth electrode to
earth and the GI pipe electrode offers comparatively lower resistance than even a
copper plate electrode, GI / CI pipe earthing may be preferred to plate earthing
wherever possible. Also to improve the earth resistance further, as per
requirements, Bentonite mixture can be used with GI pipe earthing in places
where continuous attention is available .In such places, the condensate water from
air conditioners may be directly taken to the earth pit to keep the pit constantly
wet. This earthing with Bentonite powder can be preferred to some chemical
earthing since this Bentonite method is cost effective and gives the same results of
low resistance. This Bentonite earthing may not be used for BTS Stations or in
remote areas where continuous attention is not available.
The disadvantage with Bentonite is that if it is allowed to dry, it becomes hard and
revival by addition of water becomes difficult. Since resistance to corrosion of
copper is better than any other material, the existing method of copper plate
earthing may be adopted in the areas where the effect of corrosion is high. The
method of chemical earthing adopted by private operators can also be tried at one
or two places on experimental basis. It is learnt that this has been already
practiced at one or two places. The feedback received from this place is not
encouraging. The problem indicated was that the earth resistance shot up with
passage of time. This may probably require periodical maintenance such as
keeping the earth pit wet by pouring water.
The engineering instructions issued by T&D Circle, Jabalpur in the Issue III
dt.30.04.2005 specifies that ring earthing is to be used for all transmission and
switching system.
It is gathered that the ring earthing is specifically used for tower earthing by
Telecom Wing. The engineering instructions further specifies that all the
equipments are to be connected to this ring earth for equi -potential bonding.It is
recommended that the ring earthing may be particularly used for tower earthing
and related BTS Station earthing with all the equipments connected to this ring
earth. Spike earthing requires lot of space. It is comparatively costlier. Hence the
method of spike earthing can be adopted in exceptional cases where very low and
EETP/ BSNL Silver Certification Course /Ver.02/June 2014
36
For Restricted Circulation
Page 32 of
reliable earth resistance values are required and this system of spike earthing is
not recommended for normal applications. Static earthing using anti-static floor
tiles in switch rooms of electronic exchanges are invariably being adopted and
hence no change is recommended.
RECOMMENDATIONS FOR EARTHING SYSTEM
Type of Exchange
Telecom earthing
Electrical earthing
Ground
Based
Tower & BTS
04 Nos. GI plate
earthing.
Rural Exchanges
like CDOT SBM
04 Nos. GI plate
earthing.
New
Exchanges
connection)
tech
(LT
04 Nos. GI plate or
spike earthing.
New
Exchanges
connection)
tech
(HT
04 Nos. GI plate or
spike earthing.
Note: Where soil is corrosive, G.I pipe/plate earthing can be replaced by copper
plate earthing.
2.8
SUMMARY
This unit explains the different methods of battery working. This unit covers the
different types of inverters like modified sine wave, pure sine wave, grid type, etc. It also
gives a basic idea about the circuit diagram of inverters and the UPS. The chapter also
gives the maintenance schedule for preventive and corrective maintenance of the
uninterrupted power supply.
EETP/ BSNL Silver Certification Course /Ver.02/June 2014
36
For Restricted Circulation
Page 33 of
2.9
Page 34 of
Page 35 of