Introduction:
The over current protection required for transformers is consider for Protection of
Transformer only.Such over current protection will not necessarily protect the primary or secondary conductors or
equipment connected on the secondary side of the transformer.
When voltage is switched on to energize a transformer, the transformer core normally saturates. This results
in a large inrush current which is greatest during the first half cycle (approximately0.01 second) and becomes
progressively less severe over the next several cycles (approximately 1 second) until the transformer reaches its
normal magnetizing current.
To accommodate this inrush current, fuses are often selected which have time-current withstand values of at
least 12 times transformer primary rated current for 0.1 second and 25 times for 0.01 second. Some small drytype transformers may have substantially greater inrush currents.
To avoid using over sized conductors, over current devices should be selected at about 110 to 125 percent
of the transformer full-load current rating. And when using such smaller over current protection, devices should be
of the time-delay type (on the primary side) to compensate for inrush currents which reach 8 to 10 times the fullload primary current of the transformer for about 0.1 s when energized initially.
Protection of secondary conductors has to be provided completely separately from any primary-side
protection.
A supervised location is a location where conditions of maintenance and supervision ensure that only
qualified persons will monitor and service the transformer installation.
Over current protection for a transformer on the primary side is typically a circuit breaker. In some instances
where there is not a high voltage panel, there is a fused disconnect instead.
It is important to note that the over current device on the primary side must be sized based on the
transformer KVA rating and not sized based on the secondary load to the transformer
Rating of Pri. Fuse at Point A= 300% of Pri. Full Load Current or Next higher Standard size. or
Rating of Pri. Circuit Breaker at Point A= 600% of Pri. Full Load Current or Next higher Standard size.
Rating of Sec. Fuse / Circuit Breaker at Point B= 125% of Sec. Full Load Current or Next higher Standard
size.
Rating of Sec. Fuse at Point B= 250% of Sec. Full Load Current or Next higher Standard size. or
Rating of Sec. Circuit Breaker at Point B= 300% of Sec. Full Load Current.
OR Rating of Primary Circuit Breaker =6X39A=236A, So Standard Size of Circuit Breaker =250A.
Rating of Pri. Fuse at Point A= 300% of Primary Full Load Current or Next higher Standard size.
Rating of Pri. Circuit Breaker at Point A= 400% of Primary Full Load Current or Next higher Standard size.
Rating of Sec. Fuse / Circuit Breaker at Point B= 125% of Sec. Full Load Current or Next higher Standard
size.
Rating of Sec. Fuse at Point B= 225% of Sec. Full Load Current or Next higher Standard size.
Rating of Sec. Circuit Breaker at Point B= 250% of Sec. Full Load Current or Next higher Standard size.
Rating of Pri. Fuse = 3X87A= 262A, So Next Standard Size of Fuse =300A.
OR Rating of Pri. Circuit Breaker =4X87A=348A, So Next Standard Size of Circuit Breaker =400A.
OR Rating of Sec. Circuit Breaker =2.5X525A=1312A, So Next Standard Size of Circuit Breaker =1600A.
Rating of Pri. Fuse at Point A= 250% of Primary Full Load Current or Next higher Standard size.
Rating of Pri. Circuit Breaker at Point A= 300% of Primary Full Load Current or Next higher Standard size.
Rating of Pri. Fuse at Point A= 300% of Pri. Full Load Current or Next Lower Standard size.
Rating of Pri. Circuit Breaker at Point A= 600% of Pri. Full Load Current or Next Lower Standard size.
Rating of Sec. Fuse / Circuit Breaker at Point B= 250% of Sec. Full Load Current or Next higher Standard
size.
Rating of Sec. Fuse at Point B= 250% of Sec. Full Load Current or Next Lower Standard size.
Rating of Sec. Circuit Breaker at Point B= 300% of Sec. Full Load Current or Next Lower Standard size.
Rating of Primary Fuse = 3X39A= 118A, So Next Lower Standard Size of Fuse =110A.
OR Rating of Primary Circuit Breaker =6X39A=236A, So Next Lower Standard Size of Circuit Breaker
=225A.
Rating of Secondary of Fuse / Circuit Breaker = 2.5X1043A=2609A, So Standard Size of Fuse =2500A.
Rating of Pri. Fuse at Point A= 300% of Pri. Full Load Current or Next Lower Standard size.
Rating of Pri. Circuit Breaker at Point A= 400% of Pri. Full Load Current or Next Lower Standard size.
Rating of Sec. Fuse / Circuit Breaker at Point B= 250% of Sec. Full Load Current or Next higher Standard
size.
Rating of Sec. Fuse at Point B= 225% of Sec. Full Load Current or Next Lower Standard size.
Rating of Sec. Circuit Breaker at Point B= 250% of Sec. Full Load Current or Next Lower Standard size.
Rating of Primary Fuse = 3X39A= 118A, So Next Lower Standard Size of Fuse =110A.
OR Rating of Primary Circuit Breaker =4X39A=157A, So Next Lower Standard Size of Circuit Breaker
=150A.
Rating of Secondary of Fuse / Circuit Breaker = 2.5X1043A=2609A, So Standard Size of Fuse =2500A.
Here we see two notable conditions while we select Fuse / Circuit Breaker in Supervised Location and
Unsupervised Location.
First notable Condition is Primary Over current Protection. In Unsupervised Location Fuse in Primary side is
300% of Primary Current or Next Higher Standard size and in Supervised Location is 300% of Primary Current
or Next Lower Standard size. Here Primary Over current Protection is same in both conditions (300%) But
Selecting Size of Fuse/Circuit Breaker is Different.
Lets us Check with the Example for 750KVA, 11KV/415V 3Phase Transformer.
In Unsupervised Location: Rating of Primary Fuse = 3X39A= 118A, So Next Higher Standard Size
=125A
In Supervised Location: Rating of Primary Fuse = 3X39A= 118A, So Next Lower Standard Size =110A
Second notable Condition is Secondary Over current Protection increased from 125% to 250% for
unsupervised to Supervised Location.
LocationLimitat
TransformerR
Primary Protection
ions
ated
Secondary Protection
Impedance
Less
than
600
Volts
Any location
Circuit
Fuse
Circuit
Fuse
C.B or
Breaker
Rating
Breaker
Rating
Fuse
600%
300%
300 %
250%
125%
(NH)
(NH)
( NH)
(NH)
(NH)
400%
300%
250%
225%
125%
(NH)
(NH)
(NH)
(NH)
(NH)
300%
250%
Not
Not
Not
(NH)
(NH)
required
required
required
Less than 6%
600%
300%
300%
250%
250%
6% To 10%
400%
300%
250%
225%
250%
Less than 6%
6% To 10%
Supervisedlocati
Any
ons
only
Rating of Pri. Fuse / C.B at Point A= 300% of Pri. Full Load Current or Next Lower Standard size.
Example: 1KVA, 480/230 3Phase Transformer, Full Load Current at Pri. Side=1000/(1.732X480)=1A
Rating of Primary Fuse = 3X1A= 3A, So Next Lower Standard Size of Fuse =3A.
Rating of Sec. Fuse / C.B at Point A= 167% of Pri. Full Load Current or Next Lower Standard size.
Example: 3KVA, 480/230 3Phase Transformer, Full Load Current at Pri. Side=3000/(1.732X480)=4A
Rating of Primary Fuse = 1.67X4A= 6A, So Next Lower Standard Size of Fuse =6A.
Rating of Pri. Fuse / C.B at Point A= 125% of Pri. Full Load Current or Next Higher Standard size.
Example: 15KVA, 480/230 3Phase Transformer, Full Load Current at Pri. Side=15000/(1.732X480)=18A
Rating of Primary Fuse = 1.25X18A= 23A, So Next Higher Standard Size of Fuse =25A.
Rating of Pri. Fuse / C.B at Point A= 250% of Pri. Full Load Current or Next Lower Standard size.
Rating of Sec. Fuse / C.B at Point A= 250% of Pri. Full Load Current or Next Lower Standard size.
Rating of Pri. Fuse / C.B at Point A= 250% of Pri. Full Load Current or Lower Higher Standard size.
Example: 25KVA, 480/230 3Phase Transformer, Full Load Current at Pri. Side=125000/(1.732X480)=30A
Rating of Primary Fuse = 2.50X30A= 75A, So Next Lower Standard Size of Fuse =70A.
Rating of Pri. Fuse / C.B at Point B= 167% of Sec. Full Load Current or Lower Standard size.
Example: 3KVA, 480/230 3Phase Transformer, Full Load Current at Sec. Side=3000/(1.732X230)=8A
Rating of Primary Fuse = 1.67X8A= 13A, So Next Lower Standard Size of Fuse =9A.
Rating of Pri. Fuse / C.B at Point A= 125% of Pri. Full Load Current or Higher Standard size.
Example: 15KVA, 480/230 3Phase Transformer, Full Load Current at Sec. Side=15000/(1.732X230)=38A
Rating of Primary Fuse = 1.25X38A= 48A, So Next Higher Standard Size of Fuse =50A.
Maximum Rating of Over current Protection for Transformers Less than 600 Volts
ProtectionMethod
Primary Protection
More than
2A to 9A
9A
Primary only
Secondary Protection
Less
More than 9A
than 2A
Less than
9A
125%(NH)
167%
300%
Not required
Not required
250%
250%
250%
125%(NH)
167%
protection
Primary and
secondary protection