Documente Academic
Documente Profesional
Documente Cultură
Abstract
Transformers used in commercial and industrial
applications typically show impedances marked in
percentages.
While the technical definition of this percentage
or per unit impedance is that this value is a
percentage of the base impedance of the transformer, there is a more descriptive way of thinking
of it.
Absolute impedances
I2
I1
V1
V1
V2
4160 : 480
Figure 1
V2
ZL = 1
Figure 1 shows input and output voltages along with the impedance of the load. This provides enough information to calculate the
secondary current.
V
480V
= 480 amps
Equation 2: I2 = 2 =
1
ZL
Looking first at our lossless (to simplify the math) transformer,
consider that the product of primary voltage and current equals the
product of the secondary voltage and the secondary current:
Equation 3: V1 I1 = V2 I2
55.4 A
I2
I1
V1
4160V
Zeq
V2
V2
ZL = 1
Figure 2
Beginning with the 480V secondary, the base impedance is calculated as:
2
V
2
= 480
= 0.23
Equation 9: Zbase = baseLL
Sbase_3
1000000
= 0.0132
Looking into the 480V transformer from the secondary side, that
transformer would appear to place 0.0132 impedance in series
with the source.
To show how this value is not const ant, we recall the statement
that absolute impedance changes with voltage. Solving Eq 9 again
but replacing 480V with 12.47 kV:
Equation 11: Zbase =
VbaseLL2
Sbase_3
2
= 12470 = 156
1000000
Conclusion
While transformers could be marked with either per unit or absolute
impedances, the per unit calculations are preferred by power
systems engineers.
Per unit values do not change with voltage. This simplifies
calculations.
Eaton
1000 Eaton Boulevard
Cleveland, OH 44122
United States
Eaton.com
2015 Eaton
All Rights Reserved
Printed in USA
Publication No.: WP009001EN / CSSC-1412-809
February 2015