Documente Academic
Documente Profesional
Documente Cultură
1MRS750745-MUM
Issued:
Version:
20.10.1998
M/27.10.2006
Configuration Guideline
Contents
1. About this manual .....................................................................9
1.1.
1.2.
1.3.
1.4.
1.5.
1.6.
1.7.
General .........................................................................................9
Use of symbols ..............................................................................9
Document conventions ................................................................10
Abbreviations ..............................................................................10
Terminology ................................................................................11
Related documents .....................................................................11
Document revisions .....................................................................12
General .......................................................................................63
Digital inputs and outputs ............................................................63
Explicit feedback path .................................................................64
Analog inputs ..............................................................................65
1MRS750745-MUM
Configuration Guideline
6.5.
6.6.
6.7.
6.8.
1MRS750745-MUM
Configuration Guideline
1MRS750745-MUM
Configuration Guideline
1MRS750745-MUM
Configuration Guideline
Copyrights
The information in this document is subject to change without notice and should not
be construed as a commitment by ABB Oy. ABB Oy assumes no responsibility for
any errors that may appear in this document.
In no event shall ABB Oy be liable for direct, indirect, special, incidental or
consequential damages of any nature or kind arising from the use of this document,
nor shall ABB Oy be liable for incidental or consequential damages arising from use
of any software or hardware described in this document.
This document and parts thereof must not be reproduced or copied without written
permission from ABB Oy, and the contents thereof must not be imparted to a third
party nor used for any unauthorized purpose.
The software or hardware described in this document is furnished under alicense and
may be used, copied, or disclosed only in accordance with the terms of such license.
Copyright 2006 ABB Oy
All rights reserved.
Trademarks
ABB is a registered trademark of ABB Group. All other brand or product names
mentioned in this document may be trademarks or registered trademarks of their
respective holders.
Guarantee
Please inquire about the terms of guarantee from your nearest ABB representative.
1MRS750745-MUM
Configuration Guideline
1.
1.1.
General
This guideline describes in general the procedures for configuring REF 54_ feeder
terminals, REM 54_ machine terminals, RET 54_ transformer terminals and
REC 523 remote monitoring and control units correctly with the Relay
Configuration Tool. In this document, the term device is used when referring to
all the above mentioned products.
Chapter 5. Editing the relay configurations describes step-by-step the engineering
actions required to create a relay configuration for a single device.
Chapter 6. Main configuration rules defines a set of programming rules that should
be followed while creating the configuration. These rules should be carefully
checked when finalizing the configuration.
Chapter 7. Engineering tips provides some engineering tips for doing the
configuration.
For instructions on operating the tool itself, refer to the operators manual for
CAP 505 (see Section 1.6. Related documents). This version of the Configuration
Guideline complies with products of Release 3.01. For information about the
changes and additions compared to earlier revisions, refer to the technical reference
manual of the appropriate product (see Section 1.6. Related documents).
For information on what RE_ 5__ products support which add-on protocols, refer to
the product manuals (Section 1.6. Related documents).
Note that in this manual, the examples and dialog box pictures of the Relay
Configuration Tool refer to REF 54_ feeder terminals (except Fig. 5.5.-1). The
corresponding cases and dialog boxes can be slightly different for REM 54_, RET
54_ and REC 523.
1.2.
Use of symbols
This publication includes warning, caution, and information icons that point out
safety-related conditions or other important information. It also includes tip icons to
point out useful information to the reader. The corresponding icons should be
interpreted as follows:
The electrical warning icon indicates the presence of a hazard which
could result in electrical shock.
1. Except REC 523 of revision D or later, and REM 54_ of Release 2.5
9
1MRS750745-MUM
Configuration Guideline
The tip icon indicates advice on, for example, how to design your
project or how to use a certain function.
Although warning hazards are related to personal injury, and caution hazards are
associated with equipment or property damage, it should be understood that
operation of damaged equipment could, under certain operational conditions, result
in degraded process performance leading to personal injury or death. Therefore,
comply fully with all warning and caution notices.
1.3.
Document conventions
The following conventions are used for the presentation of material:
The words in names of screen elements (for example, the title in the title bar of a
dialog box, the label for a field of a dialog box) are initially capitalized.
The names of push and toggle buttons are boldfaced. For example, click OK.
The names of menus and menu items are boldfaced. For example, the File menu.
The following convention is used for menu operations: Menu Name > Menu
Item > Cascaded Menu Item. For example: select File > Open > New
Project.
1.4.
Abbreviations
ASD
CPU
CSI
FBD
HMI
I/O
LCD
LED
LON
NV
PLC
POU
PWM
RCT
RMS
RS
RTD
VD
10
1MRS750745-MUM
1.5.
Terminology
device
DNP 3.0
IEC 60870-5-101
IEC 60870-5-103
MIMIC
Modbus
RCT project file
SPA
1.6.
Related documents
Document
ID
Manuals for REF 54_, REM 54_, RET 54_ and REC 523
1MRS750526-MUM
1MRS750500-MUM
1MRS750915-MUM
54_a
1MRS750527-MUM
1MRS755225
1MRS750881-MUM
1MRS750915-MUM
1MRS750889-MCD
1MRS755238
1MRS750781-MUM
1MRS151023-MUM
1MRS752015-MUM
1MRS755260
1MRS750958-MUM
1MRS750956-MUM
Tool-specific manuals
CAP 505 Installation and Commissioning Manualb
1MRS751273-MEN
Manualb
1MRS751709-MUM
Manualb
1MRS755277
11
1MRS750745-MUM
Configuration Guideline
Document
ID
1MRS751270-MEN
1MRS751271-MUM
1MRS751275-MEN
1MRS751272-MEN
Manualb
1MRS751274-MEN
1MRS752008-MUM
1.7.
12
Document revisions
Version
Date
G
H
K
L
M
02.04.2004
20.01.2005
01.03.2005
08.07.2005
27.10.2006
History
Manual updated
RET 54_ added to manual
Updates according to REC 523 revision F
Updates according to REF 54_, Release 3.5
Layout updated, minor corrections.
1MRS750745-MUM
Configuration Guideline
2.
Safety information
Dangerous voltages can occur on the connectors, even though
the auxiliary voltage has been disconnected.
Non-observance can result in death, personal injury or
substantial property damage.
Only a competent electrician is allowed to carry out the electrical
installation.
National and local electrical safety regulations must always be
followed.
The frame of the device has to be carefully earthed.
13
14
1MRS750745-MUM
Configuration Guideline
3.
15
16
1MRS750745-MUM
Configuration Guideline
4.
17
18
1MRS750745-MUM
Configuration Guideline
5.
5.1.
Getting started
1. Start up the CAP 505 tool by double clicking the tool icon.
2. Add a new object as an empty configuration to the CAP 505 environment. For
instructions, refer to the operators manual for CAP 505 (see Section 1.6.
Related documents). The program opens an empty project template (see
Fig. 5.1.-1) with a toolbar at the top.
3. Build the project tree structure by inserting libraries, program organisation units
(POUs) and target-specific items to the project tree.
The project tree editor is a window in which the whole project is represented as a
tree. The project tree is illustrated with several icons. Most of the icons represent a
file of the project, and different looking icons represent different types of files. The
tree always contains 4 subtrees: Libraries, Data Types, Logical POUs and Physical
Hardware.
ProjectTree
5.1.1.
Libraries
Before editing any worksheets of POUs, the whole project tree structure must be
build. The function block library (protection, control, measurement, condition
monitoring and standard functions) needed in the relay configuration needs to be
inserted to the Libraries subtree. For instructions on announcing libraries, refer to
the tutorial manual for the Relay Configuration Tool, see Section 1.6. Related
documents.
Before inserting a library to the project, close all open worksheets in
order to avoid confusing the I/O description of the function blocks.
19
1MRS750745-MUM
Configuration Guideline
The programs, function blocks (for example NOC3Low, the low-set stage of nondirectional three-phase overcurrent protection) and functions of the library can be
reused in the new project, which is edited.
The library, for example REFLIB01 for REF 54_ (see Fig. 5.1.1.-1), includes the full
set of function blocks, but only those ordered by the customer can be used in the
configuration.
If a configuration is transferred to a newer version of the product, the
library in the project must also be updated.
ref/rem/ret/reclib01
Fig. 5.1.1.-1
Libraries for REF 54_, REM 54_, RET 54_ and REC 523
The library version to be selected depends on the software revision of the product as
listed in the table below. The directory path to the libraries is
<installation drive>\CAP505\Common\IECLibs\Fi.
Table 5.1.1-1
Product
Software
revision
REF 541
REF 543
20
B
C
D and E
K
A
B and C
K
C and D
E
F
G and H
K
A
B and C
K
1MRS750745-MUM
Configuration Guideline
Table 5.1.1-1
Product
Software
revision
REF 545
REM 543
5.1.2.
B
C
D and E
K
A
B
C
A
B
A
B
A
B
A
A
A
A
A
A
B
C
D
E
F
POU_unit
Fig. 5.1.2.-1
21
1MRS750745-MUM
Configuration Guideline
The description worksheet (for example ProtectT) illustrated below is for describing
the POU or the configuration element. The worksheet is automatically named by
adding a T to the name of the POU.
text
Fig. 5.1.2.-2
Description worksheet
The variable worksheet (for example ProtectV) is for the variable declaration. The
worksheet is automatically named by adding a V to the name of the POU. The
variable worksheet is not edited manually but is created by the tool.
variables
Fig. 5.1.2.-3
A code body worksheet (for example Protect) is for a code body declaration in the
form of an function block diagram (FBD). All configurations for the devices of the
RED 500 platform are made in the graphical FBD language.
A code body programmed in the FBD language is composed of functions and
function blocks that are connected to each other using variables, connection lines or
connectors. An output of a function block can be combined with the output of
another function block for example via an OR gate (refer to Section 6.1. General).
Connectors are objects that can be used instead of connection lines, for example
where the distance between two objects on the worksheet is long. The connectors
can only be used within one worksheet, and they are resolved by textual names.
22
1MRS750745-MUM
Configuration Guideline
Connectors should be used with care since the tool may not warn if a
match to a connector cannot be found (for example, the comparison
of connectors is case sensitive).
Note that visually the connectors are distinguished from variables by embedding
them with larger than signs, > >.
Connectors
Fig. 5.1.2.-4
Even though the tool permits adding several code body worksheets under one POU,
only one worksheet is recommended to be used per POU. If more space is needed
for a configuration, the worksheet size can be increased or the functionality can be
divided into several POUs.
Avoid creating very large configurations per POU since the RED 500 PLC
environment has an inherent limit for the number of input/output points per POU.
The limit is 511 I/O points and is consumed by called function block instances only.
Note that the limit is checked during the configuration downloading. If the
downloading fails for this reason, the user has to divide the POU into smaller units.
For example, the function block NOC3Low in Fig. 5.1.2.-4 includes 14 I/O points.
The I/O points are consumed regardless of whether they are connected or not.
5.1.3.
Logical POUs
In the project tree editor and in the library editor, the Logical POUs subtree
represents a directory for all the POUs related to the project. The maximum of 20
POUs can be inserted to the subtree. Fig. 5.1.3.-1 shows a Logical POUs subtree
23
1MRS750745-MUM
Configuration Guideline
LogicalPOUs
Fig. 5.1.3.-1
Each POU type has specific characteristics from the programming point of view.
A function yields exactly one data element which is evaluated from its input
parameters. In other words, a function cannot contain any internal state
information. Furthermore, a function can call other functions but not function
blocks.
A function block (FB) can return 0,1,2.. output values and can have internal
variables. Function blocks can call any other function or function block except
itself. Multiple copies of function blocks are called instances and each instance is
given an identifier.
Programs are specialized function blocks that can only be called by tasks.
Note that recursion is not allowed for any POU type.
The POU category is selected when a POU is inserted to the project tree. Fig. 5.1.3.2 below shows the dialog box for inserting POUs. The programming language
(FBD) for the POU and the return data type for functions are also selected here. The
PLC type and Processor type selections should be left to their default values.
24
1MRS750745-MUM
Configuration Guideline
InsertNewPOU
Fig. 5.1.3.-2
At first, a POU framework is created, that is, empty POUs are inserted to the project
according to the Specification for Relay Configuration filled out prior to starting the
configuration procedure. The physical hardware must be defined before creating the
actual contents for the POUs, otherwise the predefined target-specific POUs are not
available for the programmer.
The task execution intervals recommended for function blocks must be considered
already when defining the POU framework. In general, each POU forms a functional
unit for example for protection function blocks. Some function blocks, however,
require a different task than most of the same category, and must therefore be
assigned a separate POU. For example, the task execution interval of most
protection function blocks is 10 ms but Freq1St_ requires the task of 5 ms, which is
why it usually needs a separate POU. However, if all the protection function blocks
used are associated with the task of 5 ms, no separate POU is required for Freq1St_.
5.1.4.
Physical hardware
In the project tree editor, the physical hardware is represented as a subtree (see
Fig. 5.1.4.-1) after the hardware of the device, that is, Configuration, Resource and
Tasks, has been defined.
25
1MRS750745-MUM
Configuration Guideline
PhysicalHardware
Fig. 5.1.4.-1
The configuration elements available in the Physical Hardware subtree may differ
from configuration to configuration. Each terminal of the RED 500 platform can be
configured separately.
5.1.4.1.
Configuration
In the Relay Configuration Tool, the name of the configuration and the appropriate
product family, programmable logic controller (PLC) type, are first defined:
1. Select a Physical Hardware tree element and select Edit > Insert.
2. Define Name and PLC type, and click OK.
configuration_b
26
1MRS750745-MUM
Configuration Guideline
5.1.4.2.
resource
Hardware version
After selecting the processor type, click the Settings button in the dialog box (see
Fig. 5.1.4.2.-1 above) to define the correct hardware version (see Fig. 5.1.4.2.-2).
Do not click OK after selecting the correct hardware version (see
Fig. 5.1.4.2.-2), but wait until the next dialog box opens and click
the option button Analog Channels (see Fig. 5.1.4.2.-3).
The hardware version number is included in the order number of the product. The
order number is labelled on the marking strip on the front panel of the product.
Example:
Order No: REF543FC127AAAA
Note that for REC 523, the selectable relay variants are given as
order numbers, for example REC523C 033AAA. Refer to the
technical reference manual of REC 523, see Section 1.6. Related
documents)
27
1MRS750745-MUM
Configuration Guideline
hw_variant
select_analog_channels
28
1MRS750745-MUM
Configuration Guideline
Analog channels
In the dialog box for defining analog channels (Fig. 5.1.4.2.-4), click the option
button for each channel in turn, and select the measuring device and signal type for
the channels in use from the drop-down list. Select the option Not in use for other
channels.
analog_channels
29
1MRS750745-MUM
Configuration Guideline
Technical data
rated_values
Fig. 5.1.4.2.-5 Defining the rated values for the selected measuring device
Measurements
For information about the special measurements required for each
function block, refer to the Technical Descriptions of Functions (see
Section 1.6. Related documents).
True RMS measurement and 2nd harmonic restraint measurements
If the signal type selected for an analog channel is going to be measured by any
measurement function block (MECU3A etc.), select the option True RMS mode in
the Special Measurements dialog box.
If the Inrush3 function block (3-phase transformer inrush and motor start-up current
detector) is to be used, select the option 2nd Harmonic Restraint for the analog
channels (IL1, IL2, IL3) used.
30
1MRS750745-MUM
Configuration Guideline
SpecMeasIL1
Fig. 5.1.4.2.-6 Selecting the required special measurement modes for phase
current measurement
Neutral current
When the DEF2_ function block (directional earth-fault protection) is going to be
used, select the option Intermittent earth-fault protection in the Special
Measurements dialog box for the channel via which the current I0 is measured.
The intermittent earth-fault protection can be enabled for the maximum of two
physical channels at a time. Note that the intermittent earth-fault protection requires
the residual voltage for directional operation. Therefore, the channel for the residual
voltage U0 must be defined before the selection can be made. Unless intermittent
earth-fault protection has been chosen, the following configuration error indication
appears on the display of REF 54_, REM 54_ or RET 54_ ( # denotes the number
of the analog channel in question):
System: SUPERV
Ch # error
SpecMeasIo
Fig. 5.1.4.2.-7 Selecting the required special measurement modes for neutral
current measurement
31
1MRS750745-MUM
Configuration Guideline
Frequency
When, for example, the function block MEFR1 (system frequency measurement) is
in use, frequency measurement must be selected for the channel via which the
voltage is measured for frequency measurement. For example Channel 10 (Voltage
Transformer 4, Signal type U3), click the Measurements button in the
Configuration of REF543 dialog box.
The power quality function blocks PQCU3H and PQVO3H require frequency
measurement for the channel that is connected to the FREQ_REF input, that is, the
channel for frequency reference (for more information, refer to the manuals of
PQCU3H and PQVO3H on the CD-ROM Technical Descriptions of Functions, see
Section 1.6. Related documents). Furthermore, frequency protection must be
selected if any of the function blocks SCVCSt_ or Freq1St_ is in use.
SpecMeasUL1
Fig. 5.1.4.2.-8 Selecting the required special measurement modes for frequency
measurement
32
1MRS750745-MUM
Configuration Guideline
Virtual channels
In case no measuring devices are applied for measuring residual voltage (U0) and
neutral current (I0), the virtual channels 11 and 12 can be used. If only one virtual
channel is used, the channel is numbered as channel 11 regardless of whether
residual voltage or neutral current is calculated. If both I0 and U0 are calculated,
channel 11 is used for I0S and channel 12 for U0S.
virtual_channels
Fig. 5.1.4.2.-9 Using virtual channels 11 and 12 in case no measuring devices are
applied for measuring I0 and U0
In case of the virtual channels for calculating I0 and U0, phase currents and voltages
must be associated with current and voltage measuring devices (see Fig. 5.1.4.2.-10
and Fig. 5.1.4.2.-11).
Summed_Ios
1MRS750745-MUM
Configuration Guideline
Summed_Uos
34
1MRS750745-MUM
Configuration Guideline
Digital inputs
The filter time is set for each digital input of the device via the resource settings
dialog box Binary Inputs. Inversion of the inputs can also be set. Note, however, that
the inversion of an input cannot be seen from the configuration. For further
information refer to the technical reference manual of REF 54_, REM 54_, RET 54_
or REC 523 (see Section 1.6. Related documents).
BIN_INPUT
35
1MRS750745-MUM
Configuration Guideline
Measurements
When the MEPE7 function block (power and energy measurement) is used, the
measuring mode must be selected via the resource settings dialog box
Measurements. True RMS measurement must also be selected for the channels used
by MEPE7.
Note that the measuring modes can only be selected after the analog channels have
been defined (see Fig. 5.1.4.2.-4).
MEPE7
Fig. 5.1.4.2.-13 Selecting the measuring mode for power and energy measurement
36
1MRS750745-MUM
Configuration Guideline
Condition monitoring
Values for the circuit-breaker wear function blocks CMBWEAR 1 and 2 can be set
via the resource settings dialog box Condition Monitoring.
cbwear
5.1.4.3.
Resource for REF 54_ Release 2.5 or later, REC 523 revision F
and RET 54_
The PLC type selected in the Configuration dialog box determines which processor
types are available. To select the processor type and name the resource:
1. Select an object under the Physical Hardware tree and select Edit > Insert.
2. In the opening dialog box, click the option button Resource, select the correct
processor type and name the resource.
For example, the processor type REF543R refers to a REF 543 feeder terminal
equipped with an RTD module.
37
1MRS750745-MUM
Configuration Guideline
processtype2.5
Hardware version
After selecting the processor type, click the Settings button in the dialog box (see
Fig. 5.1.4.3.-1 above) to define the correct hardware version (see Fig. 5.1.4.3.-2).
Do not click OK after selecting the correct hardware version
(Fig. 5.1.4.3.-2), but wait until the next dialog box opens and select
the option Analog Channels (see Fig. 5.1.4.3.-3).
The hardware version number is included in the order number of the product. The
order number is labelled on the marking strip on the front panel of the product.
Example:
Order No: REF543GC127AAAA
hardware2.5
38
1MRS750745-MUM
Configuration Guideline
analog_settings2.5
Analog channels
In the dialog box for defining analog channels (see Fig. 5.1.4.3.-4), click the option
button for each channel in turn, and select the measuring device and signal type for
the channels in use from the drop-down list. Select the option Not in use for other
channels.
Furthermore, the technical data and measurements for the selected channels are to
be completed correctly before the configuration is used in a real application.
analog_channels2.5
1MRS750745-MUM
Configuration Guideline
Technical data
rated_values2.5
Fig. 5.1.4.3.-5 Defining the rated values for the selected measuring device
Measurements
For information about the special measurements required for each
function block, refer to the Technical Descriptions of Functions (see
Section 1.6. Related documents).
True RMS and 2nd harmonic restraint measurements
If the signal type selected for an analog channel is going to be measured by any
measurement function block (MECU3A etc.), the true RMS mode must be selected
in the Special Measurements dialog box. Moreover, in case the Inrush3 function
block (3-phase transformer inrush and motor start-up current detector) is to be used,
the 2nd harmonic restraint must be selected for the analog channels (IL1, IL2, IL3)
used.
40
1MRS750745-MUM
Configuration Guideline
phase_measu2.5
Fig. 5.1.4.3.-6 Selecting the required special measurement modes for phase
current measurement
Neutral current
When the DEF2_ function block (directional earth-fault protection) is going to be
used, intermittent earth-fault protection must be selected for the channel via which
the current I0 is measured. The intermittent earth-fault protection can be enabled for
the physical channels I0 and I0b as well as for the virtual channels I0s and I0bs at the
same time.
The intermittent earth-fault protection requires the residual voltage for directional
operation. Therefore, the channel for the residual voltage U0 must be defined before
the selection for I0 measurement channels can be made. The amount of the U0
channels used for the intermittent earth-fault protection is limited to one. The first
available U0 channel should be selected from the list: U0, U0b, U0s and U0bs. Unless
intermittent earth-fault protection has been chosen correctly, a configuration error
indication will appear on the error list of the Relay Download Tool.
neutral_measu2.5
Fig. 5.1.4.3.-7 Selecting the required special measurement modes for neutral
current measurement
41
1MRS750745-MUM
Configuration Guideline
Frequency
When, for example, the function block MEFR1 (system frequency measurement) is
in use, frequency measurement must be selected for the channel via which the
voltage is measured for frequency measurement. For example Channel 10 (Voltage
Transformer 4, Signal type U3), click the Measurements button in the
Configuration of REF543 dialog box.
The power quality function blocks PQCU3H and PQVO3H require frequency
measurement for the channel that is connected to the FREQ_REF input, that is, the
channel for frequency reference (for more information refer to the manuals of
PQCU3H and PQVO3H on the CD-ROM Technical Descriptions of Functions, see
Section 1.6. Related documents). Furthermore, frequency protection must be
selected if any of the function blocks SCVCSt_ or Freq1St_ is in use.
freq_measu2.5
Fig. 5.1.4.3.-8 Selecting the required special measurement modes for frequency
measurement
42
1MRS750745-MUM
Configuration Guideline
Virtual channels
The virtual channels can be used if no measuring devices are applied for measuring
phase-to-phase voltages, residual voltage (U0) and neutral current (I0). The virtual
channels selected for use are numbered from the channel number 11. For further
information about the channel numbers of the calculated virtual channels, refer to
the technical reference manual of the terminal in question (see Section 1.6. Related
documents).
An example of when the virtual channels can be used is shown in Fig. 5.1.4.3.-9.
virtual_channels2.5
43
1MRS750745-MUM
Configuration Guideline
select_virtual_channels2.5
Fig. 5.1.4.3.-10 The selectable virtual channels when the configuration of the
analog channel is as in Fig. 5.1.4.3.-9
The special measurements are selectable for each used virtual channel (see
Fig. 5.1.4.3.-11 and Fig. 5.1.4.3.-12).
The special measurement view for the virtual channel Ios is shown in Fig. 5.1.4.3.11. The analog channels used for derivation and derivation equation are also shown.
The analog channels are as in Fig. 5.1.4.3.-9.
Ios_measu2.5
Fig. 5.1.4.3.-11 Special measurement view for the virtual channel Ios
Special measurement view for the virtual channel U12s is shown in the Fig. 5.1.4.3.12. The analog channels used for derivation and derivation equation are also shown.
The analog channels are as in Fig. 5.1.4.3.-9.
44
1MRS750745-MUM
Configuration Guideline
Ios_measu_2.5_2
Fig. 5.1.4.3.-12 Special measurement view for the virtual channel U12s.
After a compiled configuration is downloaded to a device, the device
checks internally whether the analog channels are correctly
configured regarding the analog inputs of function blocks.
If the connected channels have been configured incorrectly, the ERR
output signal of the specific function block activates and the analog
channel configuration error indication appears on the error list of the
Relay Download Tool. For more information, refer to Section 5.5.
Downloading the configuration.
Digital inputs
The filter time is set for each digital input of the device via the resource settings
dialog box Binary Inputs field. Inversion of the inputs can be set as well. Note,
however, that the inversion of an input cannot be seen from the configuration. For
further information, refer to the technical reference manual of the terminal in
question (see Section 1.6. Related documents).
digital_inputs2.5
45
1MRS750745-MUM
Configuration Guideline
Measurements
When the MEPE7 function block (power and energy measurement) is used, the
measuring mode must be selected by clicking the option button Measurements in the
resource settings dialog box. True RMS measurement must also be selected for the
channels used by MEPE7.
The measuring modes can only be selected after the analog channels
have been defined (see Fig. 5.1.4.3.-4).
power&energy_measu2.5
Fig. 5.1.4.3.-14 Selecting the measuring mode for power and energy measurement
Condition monitoring
Values for the circuit-breaker wear function blocks CMBWEAR 1 and 2 can be set
via the resource settings dialog box by clicking the option button Condition
Monitoring.
46
1MRS750745-MUM
Configuration Guideline
wear2rle
5.1.4.4.
Tasks
Programs and tasks
Programs are associated with tasks via the dialog boxes Properties/Task and
Properties/Program. To define task properties in the Relay Configuration Tool:
1. Select an object in the project tree.
2. Select Edit > Insert and define task name and type.
One task may include several programs. Cyclic tasks are activated within a specific
time interval and the program is executed periodically. As many as 10 POUs can be
associated to a task.
To define program properties in the Relay Configuration Tool:
1. Select a task in the project tree.
2. Select Edit > Insert and define program instance and type.
The two dialog boxes below illustrate the association of a program type (Prot_Me)
with a task (Task1) (see also Fig. 5.1.4.-1).
47
1MRS750745-MUM
Configuration Guideline
TASK1
PROT_ME
Fig. 5.1.4.4.-2 Associating the selected task with the desired program type
Task interval
Generally, operation accuracy is increased when task speed is increased, but at the
same time, the load of the microprocessors is increased as well. Although the task
speed can be freely chosen with the tool, it is necessary to define a maximum task
execution interval for each function block. If not defined, the operation accuracy and
operate times for protection functions cannot be guaranteed.
The maximum task execution interval is based on test results and it has been used in
the type testing of the function blocks. The recommended task execution interval
quaranteed by the manufacturer can be found in technical data section in the
technical description of each function block. Furthermore, certain function blocks,
for example MEDREC16, must be tied to the task given by the manufacturer in order
to enable the operation of these function blocks. For more information about the task
execution intervals of function blocks, refer to the introduction chapter in the
Technical Descriptions of Functions CD-ROM, see Section 1.6. Related documents.
For microprocessor loads, refer to Section 5.5. Downloading the configuration.
According to the standard, the Relay Configuration Tool offers a possibility to
define the tasks on two different levels:
1. Each program organisation unit (POU) can be tied to a separate task.
2. Separate function block inside a POU can be tied to any task.
48
1MRS750745-MUM
Configuration Guideline
However, the second alternative is not supported in the RED 500 environment; if a
separate function block inside a POU is given a separate task definition, it is ignored
when transferred to the device. This means that when the function blocks are being
placed in different POUs, not only the category of the function (protection, control,
and so on) but also the maximum task execution interval should be considered, since
all function blocks inside a POU run at the same speed.
Define the task execution interval for each task by selecting a task and by selecting
Edit > Insert; click the Settings button in the opening dialog. For example, the task
execution interval for Task1 in the figure below is defined as 10 ms, which means
that the program Prot_Me is run 100 times per one second. The maximum number
of tasks with different intervals is 4.
The tool automatically modifies the task setting if the set network
frequency is other than 50 Hz (see the Network Frequency text box
in Fig. 5.1.4.2.-4). For example at 60 Hz, 10 ms becomes 8.333 ms.
interval
5.2.
Declaring variables
The validity range of the declarations that are included in the declaration part should
be local to the POU in which the declaration part is contained. However, variables
that are declared to be global are only accessible to a POU via a
49
1MRS750745-MUM
Configuration Guideline
FB1
FB_X
a
Program A
FB2
FB_Y
FB1
FB_X
VAR
y:BOOL;
FB1:FB_X;
FB2:FB_Y;
END_VAR
VAR
FB1:FB_X;
FB2:FB_Y;
END_VAR
Configuration C
Program A
VAR_EXTERNAL
x:BOOL;
END_VAR
VAR
FB1:FB_X;
END_VAR
Program B
FB1
FB_X
FB2
FB_Y
a
VAR_GLOBAL
x:BOOL;
END_VAR
VAR_EXTERNAL
x:BOOL;
END_VAR
VAR
FB2:FB_Y;
END_VAR
50
Data type
ANY_REAL
ANY_INT
ANY_BIT
TIME
0.0
0
0 (=FALSE)
T#0s
1MRS750745-MUM
Configuration Guideline
Especially the initial values of global variables are logically significant for the
program. The user cannot choose the order in which tasks are initialised. This means
that if a task reading a global variable is initialized before another task gives the
variable its first value, it is important that an appropriate initial value has been
selected for the global variable.
CASE 1. Variables declaration
VARIABLE WORKSHEET of logical POU
******************************************************************
VAR
TRIPPING :BOOL
:= FALSE;
BLOCK
:BOOL
:= TRUE;
TMP1
:BOOL
:= FALSE;
END_VAR
VAR_EXTERNAL
PS1_4_HSPO1 :BOOL;
(* Double pole high speed power output *)
(* X4.1/10,11,12,13 *)
PS1_4_HSPO2 :BOOL;
(* Double pole high speed power output *)
(* X4.1/15,16,17,18 *)
PS1_4_HSPO3 :BOOL;
(* Double pole high speed power output *)
(* X4.1/6,7,8,9 *)
END_VAR
VAR_EXTERNAL
TCS1_ALARM :BOOL;
END_VAR
******************************************************************
******************************************************************
VAR_GLOBAL
PS1_4_HSPO1
PS1_4_HSPO2
PS1_4_HSPO3
END_VAR
VAR_GLOBAL
TCS1_ALARM
END_VAR
AT %QX 1.1.2
:BOOL
:= FALSE;
(* Double pole high speed power output X4.1/10,11,12,13 *)
AT %QX 1.2.2
:BOOL
:= FALSE;
(* Double pole high speed power output X4.1/15,16,17,18 *)
AT %QX 1.3.2
:BOOL
:= FALSE;
(* Double pole high speed power output X4.1/6,7,8,9 *)
:BOOL
:= FALSE;
******************************************************************
51
1MRS750745-MUM
Configuration Guideline
5.2.1.
Global variables
The physical contacts are defined in the Global Variables worksheet (Fig. 5.2.1.-1).
Declarations for the physical contacts are automatically defined when the correct
hardware version of RE_ 54_ is selected. Declarations for the analog channels are
created after the analog channel settings defined in the resource settings dialog box
have been approved.
The textual names of the inputs and outputs, for example BIO2-7_BI10IV (see the
figure below), can be modified. Note, however, that the address (for example
AT %IX 1.29.1 :BOOL := TRUE) following the name may not be changed.
global
Fig. 5.2.1.-1
5.2.2.
Local variables
At the beginning of each programmable controller POU type declaration there
should be at least one declaration part that specifies the types of the variables used
in the organisation unit. The declaration part should have the textual form of one of
the keywords VAR_INPUT, VAR_OUTPUT, VAR and VAR_EXTERNAL
followed by one or more declarations separated by semicolons and terminated by the
keyword END_VAR. All the comments you write must be edited in parentheses and
asterisks:.
(*******************************)
Variable declaration
(*
*)
of REF 541
(*
*)
(*******************************)
52
1MRS750745-MUM
Configuration Guideline
VAR (*AUTOINSERT*)
NOC3Low_1 :
NOC3Low; (* Erroneous nonclosed comment *
END_VAR
VAR_EXTERNAL (*AUTOINSERT*)
U12
:
SINT;
(* Measuring channel 8 *)
U23
:
SINT;
(* Measuring channel 9 *)
U31
:
SINT;
(* Measuring channel 10 *)
END_VAR
Three examples of creating the textual declaration for different kinds of graphical
programs are given below.
Example 1:
POU type: FBD program
Function block type declaration:
VAR
SIGNAL1
SIGNAL2
SIGNAL3
SIGNAL4
END_VAR
:BOOL :=FALSE;
:BOOL :=FALSE;
:BOOL :=FALSE;
:BOOL :=FALSE;
and_or_gates
Fig. 5.2.2.-1
53
1MRS750745-MUM
Configuration Guideline
Example 2:
POU type: NOC3Low, manufacturer-dependent function block
Function block type declaration:
VAR_INPUT
IL1
IL2
IL3
BS1
BS2
TRIGG
GROUP
DOUBLE
BSREG
RESET
END_VAR
VAR_OUTPUT
START
TRIP
CBFP
ERR
END_VAR
:SINT
:SINT
:SINT
:BOOL
:BOOL
:BOOL
:BOOL
:BOOL
:BOOL
:BOOL
:=0;
:=0;
:=0;
:=FALSE;
:=FALSE;
:=FALSE;
:=FALSE;
:=FALSE;
:=FALSE;
:=FALSE;
(* Analog channel *)
(* Analog channel *)
(* Analog channel *)
(* Blocking signal *)
(* Blocking signal *)
(* Triggering *)
(* Grp1/Grp2 select *)
(* Doubling signal *)
(* Blocking registering *)
(* Reset signal *)
:BOOL
:BOOL
:BOOL
:BOOL
:=FALSE;
:=FALSE;
:=FALSE;
:=FALSE;
(* Start signal *)
(* Trip signal *)
(* CBFP signal *)
(* Error signal *)
NOC3Low_b
Fig. 5.2.2.-2
54
1MRS750745-MUM
Configuration Guideline
Example 3:
POU type: Programmer-dependent FBD function block CONDIS
Function block type declaration:
condisv
Fig. 5.2.2.-3
55
1MRS750745-MUM
Configuration Guideline
condis
Fig. 5.2.2.-4
condis_control
Fig. 5.2.2.-5
1MRS750745-MUM
Configuration Guideline
5.3.
Compiling project
In the Relay Configuration Tools Make menu, select the command Build Project
to compile the whole project for the first time after editing. This means compiling
all POUs, global variables, resources and so on.
In the Make menu, use the Make command to compile the worksheets that have
been edited. The changed worksheets are marked with an asterisk, *, in the project
tree editor. The Make command is the standard mode for compiling and should
normally be used when you have finished editing.
It is recommended that the Build Project command is given once more
just before downloading the configuration to the product.
In the Relay Configuration Tool you can view the execution order of the different
functions or function blocks in your worksheet. The execution order corresponds to
the intermediate PLC code created while compiling. Note that the execution order
can only be seen if you have already compiled the worksheet by using the menu
command Make > Compile Worksheet.
5.4.
Add-on protocol
If an add-on protocol is used, the protocol mapping must be created by using the
Protocol Mapping Tool (PMT). For more information, refer to the documents in
Section 1.6. Related documents.
Table 5.4.-1
Relay version
REF 54_ Release 2.5
REF 54_ Release 3.0
REF 54_ Release 3.5
REM 54_ Release 2.5
RET 54_ Release 3.0
Modbus
DNP 3.0
IEC 60870-5-103
X
X
X
X
X
X
X
X
X
REC 523 does not have any add-on protocols, but the device
includes fixed protocols according to the devices software
configuration. In REC 523 revision F, the protocol interface can be
modified by using the Protocol Mapping Tool. In earlier releases, the
protocol interface can be modified by using the Protocol Editing
Tool. These tools are included in CAP 505. For more information on
the REC 523 protocols, refer to the technical reference manual of
REC 523 (see Section 1.6. Related documents).
5.5.
57
1MRS750745-MUM
Configuration Guideline
The parts of the project to be downloaded are selected via a dialog box. The MIMIC
configuration and the Relay Configuration Tool project can be downloaded
separately.
The project can also be downloaded separately as a compressed file.
This enables later uploading of the project from the device. The
compressed file is automatically created if the check box RCT
project has been selected (see Fig. 5.5.-1).
The target device has an inherent limitation over the size of a stored project file. If
this is exceeded, the tool interrupts the downloading and issues a warning.
It is useful to include some information of the project in the file by
giving, for example, the name of the designer, the date and the version
or other description of the configuration. To add project information,
select File > Project Info in the Relay Configuration Tool.
Add-on protocols (for example Modbus and IEC 60870-5-103) of the relay terminal
are activated in the relay according to Add-On protocol selection in object
properties.
Fig. 5.5.-1 Selecting RCT project (for REC 523, the mimic configuration is not
available)
When the configuration is downloaded, the total CPU load in percent can be checked
via the parameter Config. capacity. In the Relay Setting Tools Main menu
view, select the Configuration tab and the General subtab to view Config.
capacity parameter (on the device, select MAIN MENU/Configuration/
General/Config. capacity). If the load exceeds 100%, the downloading
fails, an indication Failed is displayed in the assisting window of the REF 54_,
58
1MRS750745-MUM
Configuration Guideline
REM 54_ or RET 54_ display, and a message appears in the CAP 505. The exceeded
CPU load can also be read via the parameter after a failed downloading, that is, the
load value can be for example 115%.
Whenever downloading fails, a storing sequence cannot be started but the device
must be reset before next downloading. Moreover, the device is automatically reset
after a failed downloading when the download dialog box in the Relay Download
Tool is closed.
Note that the exceeded CPU load must be checked before resetting; after the device
is restarted, the parameter Config. capacity only shows the load of the
previous configuration that was downloaded succesfully and has become valid
again.
5.5.1.
REF 54_ Release 2.5, RET 54_ and REC 523 revision F additions
The REF 54_ Release 2.5 and later, REC 523 revision F and RET 54_ includes the
following functions supported by the Configuration Download Tool:
Relay and configuration tool compatibility checking
Improved configuration error reporting
Easier identification of the relay configuration
Compatibility checking
The download tool verifies that the connected relay matches the type and revision
set in the relay configuration. If a mismatch occurs, downloading is not allowed.
comp
59
1MRS750745-MUM
Configuration Guideline
err
Configuration identification
The relay contains parameters for configuration identification:
Title
Author
Last modification date
Last download date of the configuration program
A parameter is also included to identify the bay in which the configuration is used.
The title and author are set from the File > Project info menu of the Relay
Configuration Tool.
The bay name is taken from the bay object in the project structure navigator or from
the protection and control object, if no bay object is used.
The last download/modification date parameters are set automatically. The
Download Tool shows the identification data of the present configuration and the
new configuration, and asks the user to verify, that the present configuration can be
overwritten before proceeding with the download.
60
1MRS750745-MUM
Configuration Guideline
The configuration identification data can also be viewed from the relay (menu path
Information/Configuration) and the Relay Setting Tool (open the
Information tab and select the Configuration subtab). Note that the relay stores a
maximum of 15 characters for each configuration identification parameter, although
more characters are allowed in the Relay Configuration Tool.
trace
61
62
1MRS750745-MUM
6.
6.1.
General
Make sure that all analog signals are connected and all necessary inputs and outputs
are wired. Note that the outputs of function blocks may not be connected together.
There are also many other FBD programming rules to follow. One of the most
typical rules is not to use the wired-OR connection. All signals that are connected to
the same output signal (both output relays and horizontal communication outputs)
must be connected via an OR gate (see Fig. 6.1.-1).
TRIP
PS1_4_HSPO1
I>
I>
OR
PS1_4_HSPO1
TRIP
PS1_4_HSPO1
I>>
I>>
6.2.
AT %IX 1.8.2
:BOOL := FALSE;
BIO2_7_PO1
AT %QX 1.13.2
:BOOL := FALSE;
Note that the parts of the line following the AT keyword may not be changed. Only
the name of the signal, that is, the part before the AT keyword, may be changed if
required.
If the names are adapted to the logical meanings of the signals, the user is
encouraged to create and to follow a naming convention. The name should indicate,
apart from the logical meaning, whether the signal is an input or output signal.
Examples of such names following a naming convention could be:
Q9_close_sta_IN
AT %IX 1.8.2
:BOOL := FALSE;
Q9_close_cmd_OUT
AT %QX 1.13.2
:BOOL := FALSE;
Access direction for the directly represented variables is restricted by their purpose.
This means that a digital input can be read but not written, see Fig. 6.2.-1 below.
Accordingly, an output can be written but not read. Note that an input can be read
from several locations within a worksheet and even from any program organisation
unit within the configuration, whereas an output can only be written from one
location at a time.
63
1MRS750745-MUM
Configuration Guideline
Digital3
Fig. 6.2.-1 Neither writing a digital input nor reading a digital output is allowed
6.3.
64
1MRS750745-MUM
Configuration Guideline
ExplFeedbck
ImplFeedbck
6.4.
Analog inputs
Analog channels defined in the resource can be connected to the analog inputs of
application function blocks on a code body worksheet. Most of the function blocks
with several analog inputs support unconnected inputs. For example, in Fig. 6.4.-1
below, the function block NOC3Low operates on only two inputs. The third and
unused input constantly measures a zero current amplitude. This function block only
requires that at least one of the three inputs is connected.
On the other hand, certain function blocks require that all analog inputs are
connected. An example of such a function block is OV3Low (see Fig. 6.4.-1 below).
If the analog channel requirements of a function block are violated, a configuration
error is generated. For more information on how analog inputs are expected to be
connected, refer to the function block manuals on the CD-ROM Technical
Descriptions of Functions, see Section 1.6. Related documents.
65
1MRS750745-MUM
Configuration Guideline
analog_inputs3
Fig. 6.4.-1 Connecting analog inputs of application function blocks. Do not use a
selector to switch between channels.
6.5.
66
1MRS750745-MUM
Configuration Guideline
6.6.
Warnings
In case of the indication
Warning: Instance xx is never used
in connection with compilation, remove the corresponding instances
of the function block from the variables worksheet of the POU. The
tool does not give a warning for unused variables, which is why they
are recommended to be removed manually.
When a global variable is added to a sheet as a copy-paste -function,
the Global option button has to be chosen (see figure below properties can be accessed by double-clicking the right mouse
button); otherwise the variable becomes a local variable of the POU,
which is due to the auto-insert feature of the tool (global variable =
VAR_EXTERNAL, local variable = VAR).
radio
6.7.
Execution order
After compilation, check the execution order in relation to the calling sequence of
POUs by using the Layout Execution Order function. Note, however, that although
the connection of simple variables to each other generates code, the execution order
cannot be seen by means of the Layout Execution Order function. If the MOVE
function is used instead of direct connection, the execution order can be utilised in
concluding whether the result is desirable, for example, the reading and writing
order of the variables.
MoveExpl
Fig. 6.7.-1 Direct connection of variables and a connection via the MOVE
function
67
1MRS750745-MUM
Configuration Guideline
EXECUTIObw
Fig. 6.7.-2 The INTERLOCKING variable is updated (TMP1) during the task
execution cycle (see the execution order 1,2,3)
In addition, the execution order may be illogical or even incorrect considering the
functionality.
EXECUTE2bw
Fig. 6.7.-3 The implicit feedback (TMP1) delays the updating of the
INTERLOCKING variable by one task execution cycle
6.8.
F-key
The freely programmable F-key of REF 54_, REM 54_ and RET 54_ is declared as
VAR_GLOBAL in the global variable worksheet as follows:
F001V021:BOOL:=0;
(*
68
*)
1MRS750745-MUM
Configuration Guideline
medrec6
Fig. 6.8.-1 Example of using F-key with the disturbance recorder function block
MEDREC16
The variables below are internal variables of the system and are thus not
recommended to be used like the F-key parameter.
F001V011:BOOL:=0;
(*
*)
F001V012:BOOL:=0;
(*
*)
F001V013:BOOL:=0;
(*
*)
F001V020:BOOL:=0;
(*
*)
F002V004:BOOL:=0;
(*
*)
F002V005:USINT:=0;
(*
*)
F002V006:BOOL:=0;
(*
*)
F900V251:BOOL:=0;
(*
*)
F900V252:BOOL:=0;
(*
*)
F000V251:BOOL:=0;
(*
*)
F000V252:BOOL:=0;
(*
*)
69
70
1MRS750745-MUM
Configuration Guideline
7.
Engineering tips
7.1.
Horizontal communication
This example includes four (4) bays. The logic is basically the same in every bay.
The intention of this guideline is to point out how to ensure the horizontal inter-bay
communication, including correct state indication of control objects via LON
communication. The logic also includes an alarm function in case of a broken fibre
optic. Incorrect updating of interlocking information blocks the control of objects,
but the blocking can be bypassed by setting the device to the bypass mode.
7.1.1.
7.1.1.1.
COMM_IN
COMM_IN_ signals are converted into Boolean logic mode by INT2BOOL
function blocks. The B0 output signal (BLOCK1) in an INT2BOOL function block
is used for blocking the control of objects except for the one that is sending the
signal. In other words, only one object can be controlled at a time. Furthermore,
Comm-Check_ signals are used for checking the condition of fibre optics. Signals
for bay interlocking are also received. See Fig. 7.1.1.1.-1.
71
1MRS750745-MUM
Configuration Guideline
comm_in
7.1.1.2.
COMM_OUT
Communication signals sent from one bay to other bays include the reservation of
control objects, updating of communication output signals and some indications
needed in other bays. Overall, digital signals are sent via LON and converted from
Boolean logic to unsigned integer (UINT, 16 bits) values.
72
1MRS750745-MUM
Configuration Guideline
comm_out
7.1.1.3.
update all
73
1MRS750745-MUM
Configuration Guideline
7.1.1.4.
check
7.1.1.5.
Blocking
If horizontal communication has failed, the BLOCK2 signal is sent to every
controllable function block to prevent the control of local objects. Furthermore, the
HMI alarm indication 8 (in REF 54_ , REM 54_ or RET 54_) is activated.
The BLOCK1 signal is used to create a mutual exclusion effect between bays. The
signal is activated by horizontal communication when a control object is selected in
one of the other bays.
74
1MRS750745-MUM
Configuration Guideline
BLOCK
7.1.1.6.
Control of objects
The control of an object, for example a breaker, can be executed if the BLOCK input
is not active (TRUE). Accordingly, an object cannot be controlled during the
reservation of other objects (in the same bay or in other bays) or the failing of
horizontal communication.
However, the blocking can be bypassed by setting the terminal to the bypass mode
(MAIN MENU/Control/General/Interlocking Bypass). The bypass
mode overrides interlockings provided the bypass signal is included in the logic (see
also Section 7.1.1.7. Bypass mode).
Q1
Fig. 7.1.1.6.-1 Defining the bypass mode for the control object
75
1MRS750745-MUM
Configuration Guideline
7.1.1.7.
Bypass mode
The bypass mode signal can be generated in the logic via the COLOCAT function
block. After activation of the bypass mode, the BYPASS signal is active and
therefore prevents activation of the BLOCK input.
bypass
7.2.
76
1MRS750745-MUM
Configuration Guideline
8.
77
78
1MRS750745-MUM
9.
9.1.
General data
Project name:
Date:
Substation name:
Software revision
Order number:
REF54 __ __ __ __ __ __ __ __ __ __(for
example REF543HC127AAAA)
Handled by:
Company:
Telephone number:
Fax number:
79
1MRS750745-MUM
Configuration Guideline
9.2.
Electrotechnical data
9.2.1.
Analog inputs
Table 9.2.1-1
Channel
1
2...5
6
7...10
Further information:
Module type
Board
MIM
X1.1
27
25
24
22
21
MIMX1.1.fh8
19
18
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
Terminal number
Connected
object
100V
Ch 10
X1.1:25, X1.1:27
VT4
100V
Ch 9
X1.1:22, X1.1:24
VT3
100V
Ch 8
X1.1:19, X1.1:21
VT2
100V
Ch 7
X1.1:16, X1.1:18
VT1
Ch 6
CT5
Ch 5
CT4
Ch 4
CT3
Ch 3
CT2
Ch 2
CT1
0,2A
1A
1A
5A
1A
5A
1A
5A
1A
5A
Signal type
MIMX1.1
80
1MRS750745-MUM
Module type
Board
SIM
X2.1
Terminal
number
DIFF
X2.2
DIFF
X2.3
DIFF
X2.4
DIFF
X2.5
DIFF
X2.6
DIFF
X2.7
DIFF
SIMX2.fh8
X2.8
DIFF
X2.9
DIFF
Ch 10, sensor
X2.1
Ch 9, sensor
X2.2
Ch 8, sensor
X2.3
Ch 7, sensor
X2.4
Ch 5, sensor
X2.5
Ch 4, sensor
X2.6
Ch 3, sensor
X2.7
Ch 2, sensor
X2.8
Ch 1, sensor
X2.9
Connected
object
Signal type
Simx2
9.2.2.
System frequency
50 Hz
Digital inputs
Module type
Board
PS1
(REF541,
REF543)
PS1X4.2.fh8
9.2.3.
60 Hz
Terminal
number
Connected
object
X4.2
1
2
PS1_4_BI1
X4.2:1, X4.2:2
1)
4
5
PS1_4_BI2
X4.2:4, X4.2:5
1)
6
7
PS1_4_BI3
X4.2:6, X4.2:7
1)
81
1MRS750745-MUM
Configuration Guideline
Module type
Board
BIO1
Connected
object
X5.1
1
2
3
BIO1_5_BI1
X5.1:1, X5.1:2
BIO1_5_BI2
X5.1:2, X5.1:3
4
5
6
BIO1_5_BI3
X5.1:4, X5.1:5
BIO1_5_BI4
X5.1:5, X5.1:6
7
8
9
BIO1_5_BI5
X5.1:7, X5.1:8
BIO1_5_BI6
X5.1:8, X5.1:9
BIO1_5_BI7
X5.1:10, X5.1:11
BIO1_5_BI8
X5.1:11, X5.1:12
BIO1_5_BI9
X5.1:13, X5.1:14
1)
BIO1_5_BI10
X5.1:15, X5.1:16
1)
BIO1_5_BI11
X5.1:17, X5.1:18
1)
10
11
12
BIO1X5.1.fh8
Terminal
number
13
14
15
16
17
18
Module type
BIO1
(REF 545)
Board
X6.1
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
Terminal
number
Connected
object
BIO1_6_BI1
X6.1:1, X6.1:2
BIO1_6_BI2
X6.1:2, X6.1:3
BIO1_6_BI3
X6.1:4, X6.1:5
BIO1_6_BI4
X6.1:5, X6.1:6
BIO1_6_BI5
X6.1:7, X6.1:8
BIO1_6_BI6
X6.1:8, X6.1:9
BIO1_6_BI7
X6.1:10, X6.1:11
BIO1_6_BI8
X6.1:11, X6.1:12
BIO1_6_BI9
X6.1:13, X6.1:14
1)
BIO1_6_BI10
X6.1:15, X6.1:16
1)
BIO1_6_BI11
X6.1:17, X6.1:18
1)
Further information:
82
Module type
Board
BIO1
Terminal
number
Connected
object
X5.2:1, X5.2:2
1)
X5.2
BIO1X5.2.fh8
1
2
BIO1_5_BI12
Module type
Board
BIO2
(REF543,
REF545)
X7.1
Terminal
number
Connected
object
1
2
3
BIO2_7_BI1
X7.1:1, X7.1:2
BIO2_7_BI2
X7.1:2, X7.1:3
4
5
6
BIO2_7_BI3
X7.1:4, X7.1:5
BIO2_7_BI4
X7.1:5, X7.1:6
7
8
9
BIO2_7_BI5
X7.1:7, X7.1:8
BIO2_7_BI6
X7.1:8, X7.1:9
BIO2_7_BI7
X7.1:10, X7.1:11
BIO2_7_BI8
X7.1:11, X7.1:12
13
14
BIO2_7_BI9
X7.1:13, X7.1:14
1)
15
16
BIO2_7_BI10
X7.1:15, X7.1:16
1)
10
11
12
BIO2X7.1.fh8
1MRS750745-MUM
Further information:
83
1MRS750745-MUM
Configuration Guideline
9.2.4.
Digital outputs
Module type Connected
object
PS1
(REF541,
REF543)
Terminal
number
1)
Board
PS1_4_ACFail
Mains
X4.1:1, X4.1:2
1)
PS1_4_TempAlarm
X4.1
1
2
X4.1
3
4
IRF
5
6
X4.1:6, X4.1:7,
X4.1:8, X4.1:9
7
9
8
PS1_4_HSPO3
10
X4.1:10, X4.1:11,
X4.1:12, X4.1:13
1)
PS1_4_HSPO1
PS1_4_TCS1
11
13
12
TCS1
1)
16
18
17
PS1_4_HSPO2
PS1_4_TCS2
TCS2
1) Please indicate whether the trip circuit supervision inputs will be configured to use or not
PS1X4.1
Terminal
number
1)
Board
PS2_4_ACFail
Mains
X4.1:1, X4.1:2
1)
PS2_4_TempAlarm
PS1X4.1.fh8
15
X4.1:15, X4.1:16,
X4.1:17, X4.1:18
X4.1
1
2
X4.1
3
4
IRF
5
6
X4.1:6, X4.1:7,
X4.1:8, X4.1:9
7
9
8
PS2_4_HSPO3
10
X4.1:10, X4.1:11,
X4.1:12, X4.1:13
1)
PS2_4_HSPO1
PS2_4_TCS1
TCS1
11
13
12
1)
PS2_4_HSPO2
PS2_4_TCS2
TCS2
16
18
17
PS2X4.1.fh8
15
X4.1:15, X4.1:16,
X4.1:17, X4.1:18
1) Please indicate whether the trip circuit supervision inputs will be configured to use or not
PS2X4.1
Further information:
84
Configuration Guideline
Terminal
number
Board
PS1
(REF541,
REF543)
X4.2
8
X4.2:8, X4.2:9,
X4.2:10, X4.2:11
PS1_4_HSPO4
X4.2:12, X4.2:13,
X4.2:14, X4.2:15
PS1_4_HSPO5
9
11
10
12
13
15
14
X4.2:16, X4.2:17,
X4.2:18
PS1_4_SO1
PS1X4.2o.fh8
16
17
18
PS1X4.2o
Module type Connected
object
Terminal
number
Board
PS2
(REF545)
X4.2
1
X4.2:1, X4.2:2,
X4.2:3, X4.2:4
PS2_4_HSPO4
X4.2:5, X4.2:6,
X4.2:7, X4.2:8
PS2_4_HSPO5
X4.2:9, X4.2:10,
X4.2:11, X4.2:12
PS2_4_HSPO6
X4.2:13, X4.2:14,
X4.2:15, X4.2:16
PS2_4_HSPO7
X4.2:17, X4.2:18
PS2_4_HSPO8
2
4
3
5
6
8
7
9
10
12
11
13
14
16
15
17
18
PS2X4.2o.fh8
1MRS750745-MUM
PS2X4.2o
Further information:
85
1MRS750745-MUM
Configuration Guideline
Terminal
number
Board
BIO1
X5.2
3
X5.2:3, X5.2:4
BIO1_5_SO1
X5.2:5, X5.2:6
BIO1_5_SO2
BIO1_5_SO3
4
5
6
7
9
8
10
12
BIO1_5_SO4
11
13
15
BIO1_5_SO5
BIO1_5_SO6
14
16
18
17
BIO1X5.2o.fh8
BIO1X5.2o
Module type Connected
object
Terminal
number
Board
BIO1
(REF545)
X6.2
3
X6.2:3, X6.2:4
BIO1_6_SO1
X6.2:5, X6.2:6
BIO1_6_SO2
BIO1_6_SO3
BIO1_6_SO4
4
5
6
7
9
8
10
12
11
BIO1_6_SO5
BIO1_6_SO6
14
16
18
17
BIO1X6.2.fh8
13
15
BIO1X6.2
Further information:
86
Configuration Guideline
Terminal
number
Board
BIO2
(REF543,
REF545)
X7.1
X7.1:17, X7.1:18
BIO2_7_PO1
BIO2X7.1o.fh8
17
18
BIO2X7.1o
Terminal
number
Board
X7.2
X7.2:1, X7.2:2
BIO2_7_PO2
1
2
3
X7.2:3, X7.2:4,
X7.2:5, X7.2:6
BIO2_7_PO3
4
6
5
7
X7.2:7, X7.2:8,
X7.2:9, X7.2:10
BIO2_7_PO4
X7.2:11, X7.2:12,
X7.2:13, X7.2:14
BIO2_7_PO5
8
10
9
11
12
14
13
15
X7.2:15, X7.2:16,
X7.2:17, X7.2:18
BIO2_7_PO6
16
18
17
BIO2X7.2.fh8
1MRS750745-MUM
BIO2X7.2
Further information:
87
1MRS750745-MUM
Configuration Guideline
9.2.5.
RTD module
9.2.5.1.
RTD/analog inputs
Module type
RTD1
(REF541,
REF543)
Board
X6.1
1
2
3
4
5
6
7
8
9
Terminal
number
15
16
17
18
1)
SHUNT
+
-
SHUNT
RTD1_6_AI1
RTD1_6_AI2
RTD1_6_AI3
RTD1_6_AI4
RTD1_6_AI5
DIFF
DIFF
+
-
DIFF
SHUNT
10
11
12
13
14
Connected object
SHUNT
DIFF
+
-
DIFF
SHUNT
X6.2
1
2
3
RTD1X6._.fh8
4
5
6
7
SHUNT
DIFF
+
-
DIFF
SHUNT
8
9
10
SHUNT
Further information:
88
RTD1X6._
1MRS750745-MUM
RTD outputs
Module type
Connected object
Terminal number
Board
RTD1
(REF541,
REF543)
X6.2
X6.2:11, X6.2:12
RTD1_6_AO1
+
mA-
11
12
X6.2:13, X6.2:14
RTD1_6_AO2
+
mA-
13
14
X6.2:15, X6.2:16
RTD1_6_AO3
+
mA-
15
16
X6.2:17, X6.2:18
RTD1_6_AO4
+
mA-
17
18
RTD1X6.2.fh8
9.2.5.2.
RTD1X6.2
Further information:
9.3.
Functionality
9.3.1.
Order number
REF54 __ __ __ __ __ __ __ __ __ __
(for example REF543HD127AAAA)
89
1MRS750745-MUM
Configuration Guideline
9.3.2.
Protection
AR5Func
CUB3Low
DEF2Low
DEF2High
DEF2Inst
DOC6Low
DOC6High
DOC6Inst
Freq1St1
Freq1St2
Freq1St3
Freq1St4
Freq1St5
Fusefail
Inrush3
MotStart
NEF1Low
NEF1High
NEF1Inst
NOC3Low
NOC3High
NOC3Inst
OV3Low
OV3High
PSV3St1
PSV3St2
ROV1Low
ROV1High
ROV1Inst
SCVCSt1
SCVCSt2
TOL3Cab
TOL3Dev
UV3Low
UV3High
MEAI7
MEAI8
MEAO1
MEAO2
MEAO3
MEAO4
MECU1A
MECU1B
MECU3A
MECU3B
MEDREC16
MEFR1
MEPE7
MEVO1A
MEVO1B
MEVO3A
MEVO3B
COIND1
COIND2
COIND3
COIND4
COIND5
COIND6
COIND7
COIND8
COLOCAT
COSW1
COSW2
COSW3
COSW4
MMIALAR1
MMIALAR2
MMIALAR3
MMIALAR4
MMIALAR5
MMIALAR6
MMIALAR7
MMIALAR8
MMIDATA1
MMIDATA2
MMIDATA3
MMIDATA4
MMIDATA5
Measurement
MEAI1
MEAI2
MEAI3
MEAI4
MEAI5
MEAI6
Control
COCB1
COCB2
COCBDIR
CO3DC1
CO3DC2
CODC1
CODC2
CODC3
CODC4
CODC5
90
1MRS750745-MUM
Configuration Guideline
Condition monitoring
CMBWEAR1
CMBWEAR2
CMCU3
CMGAS1
CMGAS3
CMSCHED
CMSPRC1
CMTCS1
CMTCS2
CMTIME1
CMTIME2
CMTRAV1
CMVO3
Communication
EVENT230
General
INDRESET
MMIWAKE
SWGRP1
SWGRP2
SWGRP3
SWGRP4
SWGRP5
SWGRP6
SWGRP7
SWGRP8
SWGRP9
SWGRP10
SWGRP11
SWGRP12
SWGRP13
SWGRP14
SWGRP15
SWGRP16
SWGRP17
SWGRP18
SWGRP19
SWGRP20
Optional functions
COPFC
CUB1Cap
CUB3Cap
FLOC
9.3.3.
OL3Cap
PQCU3H
PQVO3H
PQVO3Sd
Communication
Protocol used:
Port X3.2
Modbus
DNP 3.0
IEC 60870-5-103
SPA
Port X3.3
LON
SPA
91
1MRS750745-MUM
Configuration Guideline
9.3.4.
Virtual channels
Virtual
meas.
Channel
number
Channel
number
Analog
meas. 2
Channel
number
Analog
meas. 3
I0s
IL1
IL2
IL3
I0bs
IL1b
IL2b
IL3b
U0s
U1
U2
U3
U0bs
U1b
U2b
U3b
U12s
U1
U2
U23s
U2
U3
U31s
U1
U3
U12bs
U1b
U2b
U23bs
U2b
U3b
U31bs
Further information:
92
Analog
meas. 1
U1b
U3b
Channel
number
1MRS750745-MUM
9.4.
9.4.1.
Symbol used
closed
open
undef. 0 0
undef. 1 1
Disconnector:
(truck symbols)
Circuit breaker:
Earth switch:
Further information:
93
1MRS750745-MUM
Configuration Guideline
9.4.2.
Alarm LEDs
Fill in the table below to describe the legend text used as well as the flashing
sequence and colour of the LEDs.
Descriptions for legend texts and LEDs
ON state
Colour
Flashing Text
seq.
(max. 16 characters)
off
green
yellow
red
latched, blinking
latched, steady
non-latched, blinking
Text
(max. 16 characters)
Colour
Flashing
seq.
off
green
yellow
red
latched, blinking
latched, steady
non-latched, blinking
Table 9.4.2-1
1
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
2
3
4
5
6
7
8
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Interlocking
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Further information:
94
X X
1MRS750745-MUM
Configuration Guideline
9.5.
Functionality logic
Please specify the required special PLC logic functionality (see the examples
below), by drawing or otherwise, on separate sheets and enclose all additional
information with this document (Specification for Feeder Terminal Configuration).
Example 1: Earthing sequence
Earthing of the outgoing feeder can be done by a circuit breaker when an earthing
sequence is activated, an earthing switch is earthed and no voltage is measured. If
all conditions are fulfilled, the circuit breaker can be closed after 1 second. The
figure below shows the implementation of the desired logic.
Earthing
F key
95
1MRS750745-MUM
Configuration Guideline
Voltage
9.6.
Further information:
96
1MRS750745-MUM
10.
10.1.
General data
Project name:
Date:
Substation name:
Software revision
Order number:
REM54 __ __ __ __ __ __ __ __ __ __ (for
example REM543BM212AAAA)
Handled by:
Company:
Telephone number:
Fax number:
97
1MRS750745-MUM
Configuration Guideline
10.2.
Electrotechnical data
10.2.1.
Analog inputs
10.2.1.1.
1
2...5
6
7...10
Board
MIM
X1.1
1MRS09021227
AA_/CA_
25
24
22
21
19
RemMim1
18
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
Connected
object
100V
Ch 10
X1.1:25, X1.1:27
VT4
100V
Ch 9
X1.1:22, X1.1:24
VT3
100V
Ch 8
X1.1:19, X1.1:21
VT2
100V
Ch 7
X1.1:16, X1.1:18
VT1
0.2A
1A
Ch 6
CT5
1A
5A
Ch 5
CT4
1A
5A
Ch 4
CT3
1A
5A
Ch 3
CT2
1A
5A
Ch 2
CT1
Further information:
98
Terminal number
Signal type
1MRS750745-MUM
Configuration Guideline
1
2...4
5
6
7...9
10
Board
MIM
X1.1
1MRS09021427
AA_/CA_
25
24
23
22
21
20
19
18
17
16
15
13
12
RemMim2
10.2.1.2.
10
9
8
7
6
5
4
3
2
1
Terminal number
Connected
object
Ch 10
X1.1:25, X1.1:27
VT3
1A
5A
Ch 9
CT6
1A
5A
Ch 8
CT5
1A
5A
Ch 7
CT4
100V
Ch 6
X1.1:13, X1.1:15
VT2
100V
100V
Ch 5
X1.1:10, X1.1:12
VT1
1A
5A
Ch 4
CT3
1A
5A
Ch 3
CT2
1A
5A
Ch 2
CT1
Signal type
RemMim2
Further information:
99
1MRS750745-MUM
Configuration Guideline
10.2.1.3.
1
2...5
6
7...9
10
Board
MIM
X1.1
1MRS09021627
AA_/CA_
25
24
23
22
21
20
19
18
17
16
15
RemMim3
13
12
11
10
9
8
7
6
5
4
3
2
1
Terminal number
Connected
object
Ch 10
X1.1:25, X1.1:27
VT2
1A
5A
Ch 9
CT7
1A
5A
Ch 8
CT6
1A
5A
Ch 7
CT5
100V
Ch 6
X1.1:13, X1.1:15
VT1
100V
1A
5A
Ch 5
CT4
1A
5A
Ch 4
CT3
1A
5A
Ch 3
CT2
1A
5A
Ch 2
CT1
Signal type
RemMim3
Further information:
100
1MRS750745-MUM
Configuration Guideline
1
2...5
6
7...9
10
Board
MIM
X1.1
1MRS09021827
AA_/CA_
25
24
23
22
21
20
19
18
17
16
RemMim4
10.2.1.4.
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
Terminal number
Connected
object
Ch 10
X1.1:25, X1.1:27
VT1
1A
5A
Ch 9
CT8
1A
5A
Ch 8
CT7
1A
5A
Ch 7
CT6
1A
5A
Ch 6
CT5
100V
1A
5A
Ch 5
CT4
1A
5A
Ch 4
CT3
1A
5A
Ch 3
CT2
1A
5A
Ch 2
CT1
Signal type
RemMim4
Further information:
101
1MRS750745-MUM
Configuration Guideline
10.2.1.5.
Sensor inputs
Module type
Board
SIM
X2.1
Terminal
number
DIFF
X2.2
DIFF
X2.3
DIFF
X2.4
DIFF
X2.5
DIFF
X2.6
DIFF
X2.7
DIFF
SIMX2.fh8
X2.8
DIFF
X2.9
DIFF
Ch 10, sensor
X2.1
Ch 9, sensor
X2.2
Ch 8, sensor
X2.3
Ch 7, sensor
X2.4
Ch 5, sensor
X2.5
Ch 4, sensor
X2.6
Ch 3, sensor
X2.7
Ch 2, sensor
X2.8
Ch 1, sensor
X2.9
Connected
object
Signal type
Further information:
10.2.2.
System frequency
50 Hz
102
60 Hz
1MRS750745-MUM
Digital inputs
Module type
Board
PS1X4.2b.fh8
PS1
Terminal
number
Connected
object
X4.2
1
2
PS1_4_BI1
X4.2:1, X4.2:2
1)
4
5
PS1_4_BI2
X4.2:4, X4.2:5
1)
6
7
PS1_4_BI3
X4.2:6, X4.2:7
1)
PS1X4.2b
Module type
Board
BIO1
Terminal
number
Connected
object
X5.1
1
2
3
BIO1_5_BI1
X5.1:1, X5.1:2
BIO1_5_BI2
X5.1:2, X5.1:3
4
5
6
BIO1_5_BI3
X5.1:4, X5.1:5
BIO1_5_BI4
X5.1:5, X5.1:6
7
8
9
BIO1_5_BI5
X5.1:7, X5.1:8
BIO1_5_BI6
X5.1:8, X5.1:9
BIO1_5_BI7
X5.1:10, X5.1:11
BIO1_5_BI8
X5.1:11, X5.1:12
BIO1_5_BI9
X5.1:13, X5.1:14
1)
BIO1_5_BI10
X5.1:15, X5.1:16
1)
BIO1_5_BI11
X5.1:17, X5.1:18
1)
10
11
12
BIO1X5.1.fh8
10.2.3.
13
14
15
16
17
18
BIO1X5.1
Further information:
103
1MRS750745-MUM
Configuration Guideline
Module type
Board
BIO1
Terminal
number
Connected
object
X5.2:1, X5.2:2
1)
X5.2
BIO1X5.2.fh8
1
2
BIO1_5_BI12
BIO1X5.2
Module type
Board
BIO2
(RET 543)
(RET 545)
X7.1
Connected
object
1
2
3
BIO2_7_BI1
X7.1:1, X7.1:2
BIO2_7_BI2
X7.1:2, X7.1:3
4
5
6
BIO2_7_BI3
X7.1:4, X7.1:5
BIO2_7_BI4
X7.1:5, X7.1:6
7
8
9
BIO2_7_BI5
X7.1:7, X7.1:8
BIO2_7_BI6
X7.1:8, X7.1:9
BIO2_7_BI7
X7.1:10, X7.1:11
BIO2_7_BI8
X7.1:11, X7.1:12
13
14
BIO2_7_BI9
X7.1:13, X7.1:14
1)
15
16
BIO2_7_BI10
X7.1:15, X7.1:16
1)
10
11
12
BIO2X7.1b.fh8
Terminal
number
BIO2X7.1b
Further information:
104
1MRS750745-MUM
Configuration Guideline
Digital outputs
Module type Connected
object
Terminal
number
Board
PS1
1)
PS1_4_ACFail
Mains
X4.1:1, X4.1:2
1)
PS1_4_TempAlarm
X4.1
1
2
X4.1
3
4
IRF
5
6
X4.1:6, X4.1:7,
X4.1:8, X4.1:9
7
9
8
PS1_4_HSPO3
10
X4.1:10, X4.1:11,
X4.1:12, X4.1:13
1)
PS1_4_HSPO1
PS1_4_TCS1
TCS1
11
13
12
1)
PS1_4_HSPO2
PS1_4_TCS2
TCS2
16
18
17
PS1X4.1b.fh8
15
X4.1:15, X4.1:16,
X4.1:17, X4.1:18
1) Please indicate whether the trip circuit supervision inputs will be configured to use or not
PS1X4.1b
Module type Connected
object
Terminal
number
Board
PS1
X4.2
8
X4.2:8, X4.2:9,
X4.2:10, X4.2:11
PS1_4_HSPO4
X4.2:12, X4.2:13,
X4.2:14, X4.2:15
PS1_4_HSPO5
9
11
10
12
13
15
14
16
17
X4.2:16, X4.2:17,
X4.2:18
PS1_4_SO1
18
PS1X4.2o_b.fh8
10.2.4.
PS1X4.2o_b
Further information:
105
1MRS750745-MUM
Configuration Guideline
Terminal
number
Board
BIO1
X5.2
3
X5.2:3, X5.2:4
BIO1_5_SO1
X5.2:5, X5.2:6
BIO1_5_SO2
BIO1_5_SO3
4
5
6
7
9
8
10
12
BIO1_5_SO4
11
13
15
BIO1_5_SO5
BIO1_5_SO6
14
16
18
17
BIO1X5.2o.fh8
BIO1X5.2o
Module type Connected
object
Terminal
number
Board
BIO2
(RET 543)
(RET 545)
X7.1
X7.1:17, X7.1:18
BIO2_7_PO1
17
18
BIO2X7.1o_b
Further information:
106
1MRS750745-MUM
Configuration Guideline
Terminal
number
Board
X7.2
X7.2:1, X7.2:2
BIO2_7_PO2
1
2
3
X7.2:3, X7.2:4,
X7.2:5, X7.2:6
BIO2_7_PO3
4
6
5
7
X7.2:7, X7.2:8,
X7.2:9, X7.2:10
BIO2_7_PO4
X7.2:11, X7.2:12,
X7.2:13, X7.2:14
BIO2_7_PO5
8
10
9
11
12
14
13
15
X7.2:15, X7.2:16,
X7.2:17, X7.2:18
BIO2_7_PO6
16
18
17
BIO2X7.2b
Further information:
107
1MRS750745-MUM
Configuration Guideline
10.2.5.
RTD module
10.2.5.1.
RTD/analog inputs
Module type
RTD1
Board
X6.1
1
2
3
4
5
6
7
8
9
Terminal
number
15
16
17
18
1)
SHUNT
+
-
SHUNT
RTD1_6_AI1
RTD1_6_AI2
RTD1_6_AI3
RTD1_6_AI4
RTD1_6_AI5
DIFF
DIFF
+
-
DIFF
SHUNT
10
11
12
13
14
Connected object
SHUNT
DIFF
+
-
DIFF
SHUNT
X6.2
1
2
3
RTD1X6._b.fh8
4
5
6
7
SHUNT
DIFF
+
-
DIFF
SHUNT
8
9
10
SHUNT
Further information:
108
RTD1X6._b
1MRS750745-MUM
RTD outputs
Module type
Connected object
Terminal number
Board
RTD1
X6.2
X6.2:11, X6.2:12
RTD1_6_AO1
+
mA-
11
12
X6.2:13, X6.2:14
RTD1_6_AO2
+
mA-
13
14
X6.2:15, X6.2:16
RTD1_6_AO3
+
mA-
15
16
X6.2:17, X6.2:18
RTD1_6_AO4
+
mA-
17
18
RTD1X6.2b.fh8
10.2.5.2.
RTD1X6.2b
Further information:
10.3.
Functionality
10.3.1.
Order number
REM54 __ __ __ __ __ __ __ __ __ __
(for example REM543CM212AAAA)
109
1MRS750745-MUM
Configuration Guideline
10.3.2.
Inrush3
MotStart
NEF1Low
NEF1High
NEF1Inst
NOC3Low
NOC3High
NOC3Inst
NPS3Low
NPS3High
NUC3St1
NUC3St2
OE1Low
OE1High
OPOW6St1
OPOW6St2
OPOW6St3
OV3Low
OV3High
PREV3
PSV3St1
PSV3St2
REF1A
ROV1Low
ROV1High
ROV1Inst
SCVCSt1
SCVCSt2
TOL3Dev
UE6Low
UE6High
UI6Low
UI6High
UPOW6St1
UPOW6St2
UPOW6St3
UV3Low
UV3High
VOC6Low
VOC6High
MEAI6
MEAI7
MEAI8
MEAO1
MEAO2
MEAO3
MEAO4
MECU1A
MECU1B
MECU3A
MEDREC16
MEFR1
MEPE7
MEVO1A
MEVO3A
CODC5
COIND1
COIND2
COIND3
COIND4
COIND5
COIND6
COIND7
COIND8
COLOCAT
COSW1
COSW2
COSW3
COSW4
MMIALAR1
MMIALAR2
MMIALAR3
MMIALAR4
MMIALAR5
MMIALAR6
MMIALAR7
MMIALAR8
MMIDATA1
MMIDATA2
MMIDATA3
MMIDATA4
MMIDATA5
Measurement
MEAI1
MEAI2
MEAI3
MEAI4
MEAI5
Control
COCB1
COCB2
COCBDIR
CO3DC1
CO3DC2
CODC1
CODC2
CODC3
CODC4
110
1MRS750745-MUM
Condition monitoring
CMBWEAR1
CMBWEAR2
CMCU3
CMGAS1
CMGAS3
CMSCHED
CMSPRC1
CMTCS1
CMTCS2
CMTIME1
CMTIME2
CMTRAV1
CMVO3
Communication
EVENT230
General
INDRESET
MMIWAKE
SWGRP1
SWGRP2
SWGRP3
SWGRP4
10.3.3.
SWGRP5
SWGRP6
SWGRP7
SWGRP8
SWGRP9
SWGRP10
SWGRP11
SWGRP12
SWGRP13
SWGRP14
SWGRP15
SWGRP16
SWGRP17
SWGRP18
SWGRP19
SWGRP20
Communication
Protocol used:
LON
SPA
Modbus
111
1MRS750745-MUM
Configuration Guideline
10.4.
10.4.1.
Symbol used
closed
Disconnector:
(truck symbols)
Circuit breaker:
Earth switch:
Further information:
112
open
undef. 0 0
undef. 1 1
1MRS750745-MUM
Configuration Guideline
10.4.2.
Alarm LEDs
Please fill in the table below to describe the legend text used as well as the flashing
sequence and colour of the LEDs.
ON state
Flashing Text
seq.
(max. 16 characters)
Colour
Flashing
seq.
off
green
yellow
red
latched, blinking
latched, steady
non-latched, blinking
Colour
off
green
yellow
red
latched, blinking
latched, steady
non-latched, blinking
Text
(max. 16 characters)
1
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
2
3
4
5
6
7
8
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Interlocking
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
X X
Further information:
113
1MRS750745-MUM
Configuration Guideline
10.5.
Functionality logic
Please specify the required special PLC logic functionality (see the examples
below), by drawing or otherwise, on separate sheets and enclose all additional
information with this document (Specification for Machine Terminal
Configuration).
Example 1: Earthing sequence
Earthing of the outgoing feeder can be done by a circuit breaker when an earthing
sequence is activated, an earthing switch is earthed and no voltage is measured. If
all conditions are fulfilled, the circuit breaker can be closed after 1 second. The
figure below shows the implementation of the desired logic.
Earthing
F key
114
1MRS750745-MUM
Configuration Guideline
Voltage
10.6.
Further information:
115
116
1MRS750745-MUM
11.
11.1.
General data
Project name:
Date:
Substation name:
Software revision
Order number:
RET54 __ __ __ __ __ __ __ __ __ __ (for
example RET543A_240AAAA)
Handled by:
Company:
Telephone number:
Fax number:
117
1MRS750745-MUM
Configuration Guideline
11.2.
Electrotechnical data
11.2.1.
Analog inputs
11.2.1.1.
2...4
5..6
7...9
10
Current transformer
Voltage transformer
Current transformer
Voltage transformer
Module type
Board
MIM
X1.1
1MRS09021427
AA_/CA_
25
24
23
22
21
20
19
18
17
16
15
13
RemMim2
12
10
9
8
7
6
5
4
3
2
1
Terminal number
Connected
object
Ch 10
X1.1:25, X1.1:27
VT3
1A
5A
Ch 9
CT6
1A
5A
Ch 8
CT5
1A
5A
Ch 7
CT4
100V
Ch 6
X1.1:13, X1.1:15
VT2
100V
Ch 5
X1.1:10, X1.1:12
VT1
1A
5A
Ch 4
CT3
1A
5A
Ch 3
CT2
1A
5A
Ch 2
CT1
100V
Signal type
RemMim2
Further information:
118
1MRS750745-MUM
Configuration Guideline
2...5
6
7...9
10
Current transformer
Voltage transformer
Current transformer
Voltage transformer
Module type
Board
MIM
X1.1
1MRS09021627
AA_/CA_
25
24
23
22
21
20
19
18
17
16
15
13
RemMim3
11.2.1.2.
12
11
10
9
8
7
6
5
4
3
2
1
Terminal number
Connected
object
Ch 10
X1.1:25, X1.1:27
VT2
1A
5A
Ch 9
CT7
1A
5A
Ch 8
CT6
1A
5A
Ch 7
CT5
100V
Ch 6
X1.1:13, X1.1:15
VT1
100V
1A
5A
Ch 5
CT4
1A
5A
Ch 4
CT3
1A
5A
Ch 3
CT2
1A
5A
Ch 2
CT1
Signal type
RemMim3
Further information:
119
1MRS750745-MUM
Configuration Guideline
11.2.1.3.
2...9
10
Current transformer
Voltage transformer
Module type
Board
MIM
X1.1
1MRS09021827
AA_/CA_
25
RemMim4
24
23
22
21
20
19
18
17
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
Terminal number
Connected
object
Ch 10
X1.1:25, X1.1:27
VT1
1A
5A
Ch 9
CT8
1A
5A
Ch 8
CT7
1A
5A
Ch 7
CT6
1A
5A
Ch 6
CT5
Ch 5
CT4
1A
5A
Ch 4
CT3
1A
5A
Ch 3
CT2
1A
5A
Ch 2
CT1
100V
1A
5A
Signal type
RemMim4
Further information:
11.2.2.
System frequency
50 Hz
120
60 Hz
1MRS750745-MUM
Digital inputs
Module type
Board
PS1X4.2b.fh8
PS1
Terminal
number
Connected
object
X4.2
1
2
PS1_4_BI1
X4.2:1, X4.2:2
1)
4
5
PS1_4_BI2
X4.2:4, X4.2:5
1)
6
7
PS1_4_BI3
X4.2:6, X4.2:7
1)
PS1X4.2b
Module type
Board
BIO1
Terminal
number
Connected
object
X5.1
1
2
3
BIO1_5_BI1
X5.1:1, X5.1:2
BIO1_5_BI2
X5.1:2, X5.1:3
4
5
6
BIO1_5_BI3
X5.1:4, X5.1:5
BIO1_5_BI4
X5.1:5, X5.1:6
7
8
9
BIO1_5_BI5
X5.1:7, X5.1:8
BIO1_5_BI6
X5.1:8, X5.1:9
BIO1_5_BI7
X5.1:10, X5.1:11
BIO1_5_BI8
X5.1:11, X5.1:12
BIO1_5_BI9
X5.1:13, X5.1:14
1)
BIO1_5_BI10
X5.1:15, X5.1:16
1)
BIO1_5_BI11
X5.1:17, X5.1:18
1)
10
11
12
BIO1X5.1.fh8
11.2.3.
13
14
15
16
17
18
BIO1X5.1
Further information:
121
1MRS750745-MUM
Configuration Guideline
Module type
Board
BIO1
Terminal
number
Connected
object
X5.2:1, X5.2:2
1)
X5.2
BIO1X5.2.fh8
1
2
BIO1_5_BI12
BIO1X5.2
Module type
Board
BIO2
(RET 543)
(RET 545)
X7.1
Connected
object
1
2
3
BIO2_7_BI1
X7.1:1, X7.1:2
BIO2_7_BI2
X7.1:2, X7.1:3
4
5
6
BIO2_7_BI3
X7.1:4, X7.1:5
BIO2_7_BI4
X7.1:5, X7.1:6
7
8
9
BIO2_7_BI5
X7.1:7, X7.1:8
BIO2_7_BI6
X7.1:8, X7.1:9
BIO2_7_BI7
X7.1:10, X7.1:11
BIO2_7_BI8
X7.1:11, X7.1:12
13
14
BIO2_7_BI9
X7.1:13, X7.1:14
1)
15
16
BIO2_7_BI10
X7.1:15, X7.1:16
1)
10
11
12
BIO2X7.1b.fh8
Terminal
number
Further information:
122
1MRS750745-MUM
Configuration Guideline
Digital outputs
Module type Connected
object
Terminal
number
Board
PS1
1)
PS1_4_ACFail
Mains
X4.1:1, X4.1:2
1)
PS1_4_TempAlarm
X4.1
1
2
X4.1
3
4
IRF
5
6
X4.1:6, X4.1:7,
X4.1:8, X4.1:9
7
9
8
PS1_4_HSPO3
10
X4.1:10, X4.1:11,
X4.1:12, X4.1:13
1)
PS1_4_HSPO1
PS1_4_TCS1
TCS1
11
13
12
1)
PS1_4_HSPO2
PS1_4_TCS2
TCS2
16
18
17
PS1X4.1b.fh8
15
X4.1:15, X4.1:16,
X4.1:17, X4.1:18
1) Please indicate whether the trip circuit supervision inputs will be configured to use or not
PS1X4.1b
Module type Connected
object
Terminal
number
Board
PS1
X4.2
8
X4.2:8, X4.2:9,
X4.2:10, X4.2:11
PS1_4_HSPO4
X4.2:12, X4.2:13,
X4.2:14, X4.2:15
PS1_4_HSPO5
9
11
10
12
13
15
14
16
17
X4.2:16, X4.2:17,
X4.2:18
PS1_4_SO1
18
PS1X4.2o_b.fh8
11.2.4.
PS1X4.2o_b
Further information:
123
1MRS750745-MUM
Configuration Guideline
Terminal
number
Board
BIO1
X5.2
3
X5.2:3, X5.2:4
BIO1_5_SO1
X5.2:5, X5.2:6
BIO1_5_SO2
BIO1_5_SO3
4
5
6
7
9
8
10
12
BIO1_5_SO4
11
13
15
BIO1_5_SO5
BIO1_5_SO6
14
16
18
17
BIO1X5.2o.fh8
BIO1X5.2o
Terminal
number
Board
BIO2
(RET 543)
(RET 545)
X7.1
X7.1:17, X7.1:18
BIO2_7_PO1
17
18
A050225
Further information:
124
1MRS750745-MUM
Configuration Guideline
Terminal
number
Board
X7.2
X7.2:1, X7.2:2
BIO2_7_PO2
1
2
3
X7.2:3, X7.2:4,
X7.2:5, X7.2:6
BIO2_7_PO3
4
6
5
7
X7.2:7, X7.2:8,
X7.2:9, X7.2:10
BIO2_7_PO4
X7.2:11, X7.2:12,
X7.2:13, X7.2:14
BIO2_7_PO5
8
10
9
11
12
14
13
15
X7.2:15, X7.2:16,
X7.2:17, X7.2:18
BIO2_7_PO6
16
18
17
A050226
Further information:
125
1MRS750745-MUM
Configuration Guideline
11.2.5.
RTD module
11.2.5.1.
RTD/analog inputs
Module type
RTD1
Board
X6.1
1
2
3
4
5
6
7
8
9
Terminal
number
15
16
17
18
1)
SHUNT
+
-
SHUNT
RTD1_6_AI1
RTD1_6_AI2
RTD1_6_AI3
RTD1_6_AI4
RTD1_6_AI5
DIFF
DIFF
+
-
DIFF
SHUNT
10
11
12
13
14
Connected object
SHUNT
DIFF
+
-
DIFF
SHUNT
X6.2
1
2
3
RTD1X6._b.fh8
4
5
6
7
SHUNT
DIFF
+
-
DIFF
SHUNT
8
9
10
SHUNT
Further information:
126
RTD1X6._b
1MRS750745-MUM
RTD outputs
Module type
Connected object
Terminal number
Board
RTD1
X6.2
X6.2:11, X6.2:12
RTD1_6_AO1
+
mA-
11
12
X6.2:13, X6.2:14
RTD1_6_AO2
+
mA-
13
14
X6.2:15, X6.2:16
RTD1_6_AO3
+
mA-
15
16
X6.2:17, X6.2:18
RTD1_6_AO4
+
mA-
17
18
RTD1X6.2b.fh8
11.2.5.2.
RTD1X6.2b
Further information:
127
1MRS750745-MUM
Configuration Guideline
11.3.
Functionality
11.3.1.
Order number
RET54 __ __ __ __ __ __ __ __ __ __
(for example RET543AC240AAAA)
11.3.2.
Freq1St4
Freq1St5
FuseFail
Inrush3
NEF1Low
NEF1High
NEF1Inst
NOC3Low
NOC3LowB
NOC3High
NOC3Inst
NPS3Low
NPS3High
OE1Low
OE1High
OV3Low
OV3High
PSV3St1
PSV3St2
REF1A
REF4A
REF4B
ROV1Low
ROV1High
ROV1Inst
TOL3Dev
UI6Low
UI6High
UV3Low
UV3High
MEAI7
MEAI8
MEAO1
MEAO2
MEAO3
MEAO4
MECU1A
MECU1B
MECU3A
MECU3B
MEDREC16
MEFR1
MEPE7
MEVO1A
MEVO1B
MEVO3A
MEVO3B
COIND1
COIND2
COIND3
COIND4
COIND5
COIND6
COIND7
COIND8
COLOCAT
COLTC
COSW1
COSW2
COSW3
COSW4
MMIALAR1
MMIALAR2
MMIALAR3
MMIALAR4
MMIALAR5
MMIALAR6
MMIALAR7
MMIALAR8
MMIDATA1
MMIDATA2
MMIDATA3
MMIDATA4
MMIDATA5
Measurement
MEAI1
MEAI2
MEAI3
MEAI4
MEAI5
MEAI6
Control
COCB1
COCB2
COCBDIR
CO3DC1
CO3DC2
CODC1
CODC2
CODC3
CODC4
CODC5
128
1MRS750745-MUM
Configuration Guideline
Condition monitoring
CMBWEAR1
CMBWEAR2
CMCU3
CMGAS1
CMGAS3
CMSCHED
CMSPRC1
CMTCS1
CMTCS2
CMTIME1
CMTIME2
CMTRAV1
CMVO3
Communication
EVENT230
General
INDRESET
MMIWAKE
SWGRP1
SWGRP2
SWGRP3
SWGRP4
11.3.3.
SWGRP5
SWGRP6
SWGRP7
SWGRP8
SWGRP9
SWGRP10
SWGRP11
SWGRP12
SWGRP13
SWGRP14
SWGRP15
SWGRP16
SWGRP17
SWGRP18
SWGRP19
SWGRP20
Communication
Protocol used:
Port X3.2
Modbus
DNP 3.0
IEC 60870-5-103
SPA
Port X3.3
LON
SPA
129
1MRS750745-MUM
Configuration Guideline
11.4.
11.4.1.
Q1
Q0
0.0A
0POS
Q4
AVR
AUT
Q9
Symbol used
0.0A
0 . 0 kW
0 . 0 A Io
closed
Disconnector:
(truck symbols)
Circuit breaker:
Earth switch:
Further information:
130
PAR
ON
open
undef. 0 0
undef. 1 1
1MRS750745-MUM
Configuration Guideline
11.4.2.
Alarm LEDs
Please fill in the table below to describe the legend text used as well as the flashing
sequence and colour of the LEDs.
ON state
Flashing Text
seq.
(max. 16 characters)
Colour
Flashing
seq.
off
green
yellow
red
latched, blinking
latched, steady
non-latched, blinking
Colour
off
green
yellow
red
latched, blinking
latched, steady
non-latched, blinking
Text
(max. 16 characters)
1
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
2
3
4
5
6
7
8
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Interlocking
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
X X
Further information:
131
1MRS750745-MUM
Configuration Guideline
11.5.
Functionality logic
Please specify the required special PLC logic functionality (see the examples
below), by drawing or otherwise, on separate sheets and enclose all additional
information with this document (Specification for Transformer Terminal
Configuration).
Example 1: Earthing sequence
Earthing of the outgoing feeder can be done by a circuit breaker when an earthing
sequence is activated, an earthing switch is earthed and no voltage is measured. If
all conditions are fulfilled, the circuit breaker can be closed after 1 second. The
figure below shows the implementation of the desired logic.
Earthing
F key
132
1MRS750745-MUM
Configuration Guideline
Voltage
11.6.
Further information:
133
134
1MRS750745-MUM
12.
12.1.
General data
Project name:
Date:
Substation name:
Software revision
Order number:
REC523 __ __ __ __ __ __ __ (for
Handled by:
Company:
Telephone number:
Fax number:
135
1MRS750745-MUM
Configuration Guideline
12.2.
Electrotechnical data
12.2.1.
Analog inputs
Table 12.2.-1 Analog input channel connections
Channel
1
2...4
5, 7...9
6
10
Further information:
136
Configuration Guideline
Board
MIM
(032 _AA,
037 _AA)
X1.1
RecMim1
Module type
9
8
7
6
5
4
3
2
1
Terminal number
Connected
object
1A
5A
Ch 4
CT3
1A
5A
Ch 3
CT2
1A
5A
Ch 2
CT1
Signal type
RecMim1
Module type
Board
MIM
(033 _AA,
038 _AA)
X1.1
27
25
24
22
21
19
Terminal number
Connected
object
100V
Ch 10
X1.1:25, X1.1:27
VT3
100V
Ch 9
X1.1:22, X1.1:24
VT2
100V
Ch 8
X1.1:19, X1.1:21
VT1
1A
5A
Ch 4
CT3
1A
5A
Ch 3
CT2
1A
5A
Ch 2
CT1
Signal type
18
16
15
RecMim2
1MRS750745-MUM
13
12
11
10
9
8
7
6
5
4
3
2
1
RecMim2
Further information:
137
1MRS750745-MUM
Configuration Guideline
Module type
Board
MIM
(034 _AA,
039 _AA)
X1.1
27
25
24
22
21
19
Terminal number
Connected
object
230V
Ch 10
X1.1:25, X1.1:27
VT3
230V
Ch 9
X1.1:22, X1.1:24
VT2
230V
Ch 8
X1.1:19, X1.1:21
VT1
Ch 5
CT4
1A
5A
Ch 4
CT3
1A
5A
Ch 3
CT2
1A
5A
Ch 2
CT1
Signal type
18
RecMim3
16
15
13
12
11
10
9
8
7
6
5
4
3
2
1
1A
5A
RecMim3
Module type
Board
MIM
(061 _AA,
066 _AA)
X1.1
27
25
24
23
22
21
20
19
18
17
16
15
13
RecMim4
12
10
9
8
7
6
5
4
3
2
1
Terminal number
Connected
object
Ch 10
X1.1:25, X1.1:27
VT3
1A
5A
Ch 9
CT6
1A
5A
Ch 8
CT5
1A
5A
Ch 7
CT4
100V
Ch 6
X1.1:13, X1.1:15
VT2
100V
100V
Ch 5
X1.1:10, X1.1:12
VT1
1A
5A
Ch 4
CT3
1A
5A
Ch 3
CT2
1A
5A
Ch 2
CT1
Signal type
RecMim4
Further information:
138
Configuration Guideline
Module type
Board
MIM
(062 _AA,
067 _AA)
X1.1
27
25
24
22
21
19
18
16
15
13
12
RecMim5
1MRS750745-MUM
Terminal number
Connected
object
100V
Ch 10
X1.1:25, X1.1:27
VT6
100V
Ch 9
X1.1:22, X1.1:24
VT5
100V
Ch 8
X1.1:19, X1.1:21
VT4
100V
Ch 7
X1.1:16, X1.1:18
VT3
100V
Ch 6
X1.1:13, X1.1:15
VT2
100V
Ch 5
X1.1:10, X1.1:12
VT1
1A
5A
Ch 4
CT3
1A
5A
Ch 3
CT2
1A
5A
Ch 2
CT1
10
9
8
7
6
5
4
3
2
1
Signal type
RecMim5
Module
type
Board
MIM
(054_AA,
059_AA
X1.1
27
25
24
23
22
21
20
19
18
17
16
15
13
12
Connected
object
100V
Ch 10
X1.1:25 X1.1:27
VT4
100V
Ch 9
X1.1:22 X1.1:24
VT3
100V
Ch 8
X1.1:19 X1.1:21
VT2
Ch 7
X1.1:16 X1.1:18
VT1
Ch 6
CT5
Ch 5
X1.1:10 X1.1:12
CT4
Ch 4
CT3
Ch 3
CT2
Ch 2
CT1
100V
0,2A
1A
1A
5A
10
9
8
7
6
5
4
3
2
1
Terminal number
1A
5A
1A
5A
1A
5A
Signal type
A050027
Further information:
139
1MRS750745-MUM
Configuration Guideline
Module type
Board
SIM
X2.1
Terminal
number
DIFF
X2.2
DIFF
X2.3
DIFF
X2.4
DIFF
X2.5
DIFF
X2.6
DIFF
X2.7
DIFF
SIMX2.fh8
X2.8
DIFF
X2.9
DIFF
Ch 10, sensor
X2.1
Ch 9, sensor
X2.2
Ch 8, sensor
X2.3
Ch 7, sensor
X2.4
Ch 5, sensor
X2.5
Ch 4, sensor
X2.6
Ch 3, sensor
X2.7
Ch 2, sensor
X2.8
Ch 1, sensor
X2.9
Connected
object
Signal type
Simx2
Further information:
12.2.1.
System frequency
50 Hz
140
60 Hz
1MRS750745-MUM
Digital inputs
Module type
Board
PSC
Terminal
number
Connected
object
PSCX7.3.fh8
X7.3
1
2
PSC_7_BI1
X4.2:1, X4.2:2
1)
3
4
PSC_7_BI2
X4.2:4, X4.2:5
1)
5
6
PSC_7_BI3
X4.2:6, X4.2:7
1)
PSCX7.3
Module type
Board
BIO1
X3.1
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
BIO1X3.1.fh8
16
Terminal
number
BIO1_3_BI1
X3.1:1, X3.1:2
BIO1_3_BI2
X3.1:2, X3.1:3
BIO1_3_BI3
X3.1:4, X3.1:5
BIO1_3_BI4
X3.1:5, X3.1:6
BIO1_3_BI5
X3.1:7, X3.1:8
BIO1_3_BI6
X3.1:8, X3.1:9
BIO1_3_BI7
X3.1:10, X3.1:11
BIO1_3_BI8
X3.1:11, X3.1:12
BIO1_3_BI9
X3.1:13, X3.1:14
BIO1_3_BI10
X3.1:15, X3.1:16
BIO1_3_BI11
X3.1:17, X3.1:18
Connected
object
17
18
BIO1X3.1
Module type
Board
BIO1
X3.2
BIO1X3.2.fh8
12.2.2.
1
2
Terminal
number
BIO1_3_BI12
Connected
object
X3.2:1, X3.2:2
BIO1X3.2
Further information:
141
1MRS750745-MUM
Configuration Guideline
12.2.3.
Digital outputs
Module type Connected
object
Terminal
number
Board
PSC
X7.3
8
PSC_7_SO1
or
Heater Output
X7.3:11, X7.3:12,
X7.3:13, X7.3:14 P S C _ 7 _ H S P O 1
9
11
12
14
13
X7.3:15, X7.3:16,
X7.3:17, X7.3:18 P S C _ 7 _ H S P O 2
PSCX7.3o.fh8
15
16
18
17
PSCX7.3o
Module type Connected
object
Terminal
number
Board
BIO1
X3.2
3
X3.2:3, X3.2:4
BIO1_3_SO1
4
5
X3.2:5, X3.2:6
BIO1_3_SO2
6
7
9
BIO1_3_SO3
X3.2:10, X3.2:11,
X3.2:12
BIO1_3_SO4
X3.2:13, X3.2:14,
X3.2:15
BIO1_3_SO5
X3.2:16, X3.2:17,
X3.2:18
BIO1_3_SO6
8
10
12
11
13
15
16
18
17
BIO1X3.2o.fh8
14
BIO1X3.2o
Further information:
142
1MRS750745-MUM
Configuration Guideline
12.3.
Functionality
12.3.1.
Order number
REC523 __ __ __ __ __ __ __
(for example REC523F033AAA)
12.3.2.
MEAI6
MEAI7
MEAI8
MECU1A
MECU1B
MECU3A
MECU3B
MEDREC16
MEFR1
MEPE7
MEVO1A
MEVO1B
MEVO3A
MEVO3B
DEF2High
DOC6Low
DOC6High
Inrush3
NEF1Low
NEF1High
NOC3Low
NOC3High
UV3Low
UV3High
CODC2
CODC3
CODC4
CODC5
COIND1
COIND2
COIND3
COIND4
COIND5
COIND6
COIND7
COIND8
COLOCAT
COPFC
CMGAS1
CMSCHED
CMSPRC1
CMTCS1
CMTCS2
CMTIME1
CMTIME2
CMTRAV1
CMVO3
Fault indication
AR5Func
CUB3Low
DEF2Low
Control
COCB1
COCB2
CO3DC1
CO3DC2
CODC1
Condition monitoring
CMBWEAR1
CMBWEAR2
CMCU3
Communication
EVENT230
143
1MRS750745-MUM
Configuration Guideline
General
INDRESET
SWGRP1
SWGRP2
SWGRP3
SWGRP4
SWGRP5
12.3.3.
SWGRP18
SWGRP19
SWGRP20
LON
IEC 60870-5-101
Modbus
SPA
DNP 3.0
Virtual channels
Virtual
meas.
12.5.
SWGRP12
SWGRP13
SWGRP14
SWGRP15
SWGRP16
SWGRP17
Communication
Protocol used:
12.4.
SWGRP6
SWGRP7
SWGRP8
SWGRP9
SWGRP10
SWGRP11
Channel
number
Analog
meas. 1
Channel
number
Analog
meas. 2
Channel
number
Analog
meas. 3
I0s
IL1
IL2
IL3
I0bs
IL1b
IL2b
IL3b
U0s
U1
U2
U3
U12s
U1
U2
U23s
U2
U3
U31s
U1
U3
Channel
number
LED configuration
The optional LED panel of REC 523 includes 21 LEDs that can be freely configured
with the Relay Configuration Tool (for an example configuration, see Fig. 12.5.-1
below). Each LED has four states: on (steady), off, fast blinking (2 Hz) and slow
blinking (0.5Hz). Please specify the desired LED configuration in Table 12.5.-1
below.
144
B0
FALSE
B1
PSC_7_BattTest
Fast blink =
AC Fail occurred
Led 2:
On =
Battery Test running
Led 3:
On = Battery Poor
Off = Battery Good
Led 4:
B9
Led 5:
On = Heater on
B10
Led 6:
On =
Temp. limit exceeded
Led 7:
On = BI3 OFF
Fast blink = BI3 ON
Led 8:
B2
PSC_7_BattStatus
B4
B5
BIO1_3_BI1
B6
BIO1_3_BI2
B7
PSC_7_HeatStat
Led 1:
B3
B8
PSC_7_TempAlarm
B11
BIO1_3_BI3
B12
FALSE
B13
PSC_7_Bl1
B14
B15
NOT
A050012
Slow blink
Fast blink
LED
no
Off
1MRS750745-MUM
Purpose
1
2
3
4
5
6
7
145
1MRS750745-MUM
Configuration Guideline
Slow blink
Fast blink
Off
LED
no
On (steady)
Purpose
8
9
10
11
12
13
14
15
16
17
18
19
20
21
12.6.
Further information:
146
1MRS750745-MUM
Configuration Guideline
13.
13.1.
13.2.
147
1MRS750745-MUM
Configuration Guideline
2)
3)
4)
Oddharm.CNV
1)
Fig. 13.2.-1 Odd harmonics added to the 1.0 p.u. fundamental frequency (50Hz)
waveform are illustrated in the first picture. The second picture shows
the fundamental frequency with 0.1 p.u. third harmonic. The third
picture represents the fundamental frequency with the 0.1 p.u. third
and 0.1 p.u. fifth harmonics. In the last picture, the 0.1 p.u. seventh
harmonic is added to the fundamental frequency with the third and
fifth harmonics.
The relationship for current and voltage harmonics is shown in Fig. 13.2.-2.
Pure Sinusoid
Distorted voltage
Voltage drop
Voltdist.CNV
148
1MRS750745-MUM
Configuration Guideline
Voltage sources, that is, generation plants do not generally generate harmonics.
Harmonics are created because of power system non-linearity. Non-linear
components and loads cause distorted currents because of their operational
principles. Distorted currents flow through system impedance causing a voltage
drop for each harmonic. This results in voltage harmonics appearing at the load bus.
The created voltage distortion can be calculated if current harmonics as well as
system frequency response are known. In most cases the system frequency response
is very difficult to determine. Power system is a very large system that contains
many non-linear components. This makes it difficult to precisely predict the effects
of harmonics in different parts of the power system.
13.3.
Harmonic sources
The most important harmonic sources are basically converters and power supplies
for numerous electrical equipment. This equipment is a source for harmonics, and at
the same time, its operation principles may be very sensitive to harmonics,
especially to voltage harmonics. Still, some devices can be designed to decrease
their characteristic harmonics.
10
11
12
13
Harmonic
Currharm.CNV
13.3.1.
Fig. 13.3.1.-1 Typical current harmonics and the waveform for a switch-mode
power supply
149
1MRS750745-MUM
Configuration Guideline
13.3.2.
h = kq 1
and the magnitudes of the harmonic currents are:
I1
I h = --h
where
h
k
q
Ih
I1
The most significant harmonics for six-pulse converters are the 5th, 7th, 11th and
13th. For twelve-pulse converters, the 11th, 13th, 23rd and 25th harmonics are the
most significant.
PWM-type ASD
Typical current harmonics and the waveform for a Pulse Width Modulation-type
Adjustable Speed Drive with rated speed are shown in Fig. 13.3.2.-1 .
1.2
0.8
0.6
0.4
0.2
0
1
10
11
12
13
Harmonic
Fig. 13.3.2.-1 Current harmonics and the waveform for a PWM-type ASD
CSI-type ASD
Typical current harmonics and the waveform for a Current Source Inverter-type
Adjustable Speed Drive are shown in Fig. 13.3.2.-2.
150
HarmPWM.CNV
1MRS750745-MUM
Configuration Guideline
1.2
0.6
0.4
0.2
0
1
10
11
12
HarmCSI.CNV
1
0.8
13
Harmonic
Fig. 13.3.2.-2 Current harmonics and the waveform for a CSI-type ASD
Cycloconverter harmonics
The expressions of cycloconverter current harmonics are complex. They vary as a
function of the frequency ratio of the cycloconverter:
fh
= f i ( kq
1 ) 6nf o
where
fh
fi
k, n
q
fo
This means that harmonics may vary significantly and interharmonics (non-integer
multiple of fundamental frequency) may also appear. Characteristic harmonics for a
six-pulse cycloconverter are harmonics from fundamental to 2nd, 5th to 7th, and
11th to 13th.
13.3.3.
Arc furnaces
The harmonics produced by electric arc furnaces used for the production of steel are
unpredictable. The steel scrap to be molten is a very non-linear load and thus the
melting arc changes constantly. The arc current may be non-periodic and may
include both harmonics and interharmonics. Still, in most applications, the loworder harmonics starting with the second and ending with the seventh predominate
the non-integer harmonics. Fig. 13.3.3.-1 presents typical harmonics for an arc
furnace during the initial melting period and the refining period. These harmonics
have quite a low percentage magnitude compared to the fundamental component.
Arc furnaces form a large load with fundamental currents of several kA, which
makes arc furnaces a significant harmonic source for the power system.
151
1MRS750745-MUM
0.1
0.1
0.09
0.09
0.08
0.07
0.06
0.05
0.04
0.03
0.02
0.01
0
2
Harmonic
0.08
0.07
0.06
0.05
0.04
0.03
0.02
0.01
0
2
Harmonic
Harmfurn.CNV
Configuration Guideline
Fig. 13.3.3.-1 Typical harmonics for arc furnaces. The first picture is for the
melting phase and the second for the refining phase.
Other arching devices similar to arc furnaces are arc welding equipment.
Saturable devices
Equipment in this class includes transformers and other electromagnetic devices
with a steel core, including motors. Harmonics are generated due to the non-linear
magnetising characteristics of the steel. Harmonics are due to exciting current,
which is very rich in harmonics like the 3rd, 5th, 7th and 9th. Transformers are not
as much a concern as electronic power converters because exciting current is small
compared to the rated full load current. However, their effect will be noticeable
particularly on utility distribution systems that have hundreds of transformers. A
significant increase in triplen harmonic currents is often noticed during the early
morning hours when the load is low and thus the percentage of harmonics compared
to the fundamental is high.
Motors and synchronous generators also exhibit some distortion, although it is
generally of little consequence.
13.4.
152
Configuration Guideline
iharmonic
Xtrafo
RL
RL
RL
Harmpow.CNV
Xsystem
XC
Transformers
Transformers essentially isolate the load at higher harmonic frequencies. High-order
harmonics are not passed through transformers. Another effect of the transformers
is the isolation of triplen harmonics due to the transformer winding design. Triplen
harmonics tend to stay trapped into the delta connection and do not show up in the
line currents in the delta side. Some examples for the third harmonic current flow in
transformers are shown in Fig. 13.4.-2.
Harmtran.CNV
1MRS750745-MUM
Capacitors
Capacitor banks used for voltage control and power factor correction are the major
components that affect the system frequency response characteristics. Capacitors
can chance the system response to harmonics by creating high impedance or, on the
other hand, low impedance for harmonic currents at some frequencies. This means
that although capacitors are not harmonic sources, they may cause severe harmonic
distortion. On the other hand, capacitors can be used for creating paths with the
153
1MRS750745-MUM
Configuration Guideline
13.5.
Effects of harmonics
The main effects of voltage and current harmonics within the power system are:
Amplification of harmonic levels resulting from series and parallel resonance
Reduction of efficiency in power generation, transmission and utilisation
Ageing of the insulation of electrical plant components and thus shortening of
their useful life
Equipment maloperation
Rotating machines
A major effect of harmonic voltages and currents in rotating machinery (induction
and synchronous) is increased heating due to iron and copper losses. Harmonic
pairs, such as the fifth and seventh harmonics, have the potential for creating
mechanical oscillations in a turbine-generator or in a motor-load system. Then highstress mechanical forces may be developed. A pulsating output torque may affect the
product quality where motor loads are sensitive to torque variations.
Transformers
With the exception that harmonics applied to transformers may result in increased
audible noise, the effects of harmonics on these components usually arise from
additional heating. Current harmonics cause an increase in copper losses and stray
flux losses. Voltage harmonics cause an increase in iron losses and stress the
insulation. Additional heating may result in overheating with less than rated load.
Accelerated ageing of transformers is also possible.
Electronic equipment
Power electronic equipment is susceptible to misoperation caused by harmonic
distortion. This equipment is often dependent upon accurate determination of
voltage zero crossing or other aspects of voltage wave shape. Other types of
electronic equipment may be affected by the transmission of ac supply harmonics
through the equipment power supply or by the magnetic coupling of harmonics into
equipment components. Computers and allied equipment, such as programmable
controllers, may suffer from erratic data or malfunctions. Malfunctions may in some
154
1MRS750745-MUM
Configuration Guideline
cases have serious consequences, for example in medical equipment. Less dramatic
interference may occasionally be observed in radio and television equipment, as
well as in video recorders and audio reproduction systems.
Metering
Metering instruments initially calibrated on pure sinusoidal alternating current and
subsequently used on a distorted electricity supply may be prone to error. Both
positive and negative metering errors are possible because error is connected to the
direction of the harmonic flow. In general, the distortion must be severe (>20%)
before significant errors are detected.
Telephone interference
The presence of harmonic currents or voltages in circuitry associated with power
conversion apparatus may produce magnetic and electric fields that will impair the
satisfactory performance of the communication system that, by virtue of its
proximity and susceptibility, may be disturbed.
13.6.
13.6.1.
155
1MRS750745-MUM
Configuration Guideline
110 kV
Trafo 110/20 kV
Voltage measurement
Current measurement
20 kV
Current meas.
Current meas.
Current meas.
Load A
Harmonic
source
Load B
Compensation
Loads.CNV
M
3~
Fig. 13.6.1.-1 110/20 kV substation with different types of loads connected to the
feeders
Power quality affected by harmonics at the substation can be measured in the
incoming feeder for both voltage harmonics and current harmonics. If individual
feeders are monitored, it should be noticed that measuring the current harmonics
from each feeder is enough. The 20 kV bus voltage is common for all of the feeders.
Measuring the voltage harmonics from all the feeders results in unnecessary
information. Most of the time only the most important feeders (for example
harmonic sources) are monitored.
13.6.2.
156
1MRS750745-MUM
Configuration Guideline
3. Capacitors
Voltage limit to 120 percent of peak voltage (with harmonics) -> sum of
individual voltage harmonics <20% with rated fundamental
In case of feeders containing many individual loads and devices, it is difficult to
recommend levels according to specific devices. In such a case, the
recommendations given in standards for power quality can be followed. Then the
harmonics are monitored for the feeder itself, not for the load devices.
13.6.3.
13.6.4.
157
158
1MRS750745-MUM
Configuration Guideline
14.
Index
A
Analog channels ................................................................................. 29, 39
B
Blocking ................................................................................................... 74
Bypass mode ............................................................................................. 76
C
Code body worksheet ......................................................................... 21, 22
Communication ........................................................................................ 71
Communication signals ................................................................ 71, 72, 73
Compiling the project ............................................................................... 57
Condition monitoring ......................................................................... 37, 46
Configuration ............................................................ 17, 26, 77, 79, 97, 117
Configuration error ............................................................................. 31, 41
Configuration specification for REC 523 ............................................... 135
Control of switchgears .............................................................................. 75
Cyclic communication check ................................................................... 74
Cyclic sending generation ........................................................................ 73
D
Data types ................................................................................................. 19
Description worksheet ........................................................................ 21, 22
Digital inputs ................................................................................ 35, 45, 63
Digital outputs .......................................................................................... 63
Downloading the configuration ................................................................ 57
E
Error outputs ............................................................................................. 66
Events ....................................................................................................... 76
Execution order ........................................................................................ 67
Explicit feedback ...................................................................................... 64
F
F-key ......................................................................................................... 68
Frequency ................................................................................................. 32
G
Global variables .................................................................................. 49, 52
H
Hardware version ................................................................................ 27, 38
Harmonic restraint measurement ........................................................ 30, 40
Harmonics ............................................................................................... 147
HMI .................................................................................................... 66, 74
Horizontal communication ....................................................................... 71
159
1MRS750745-MUM
Configuration Guideline
L
Libraries ................................................................................................... 19
Logic ........................................................................................................ 71
Logical POUs ..................................................................................... 19, 23
M
Manuals .................................................................................................... 11
Measurement function blocks ...................................................... 30, 40, 76
Measurements ......................................................................... 30, 36, 40, 46
MIMIC ......................................................... 57, 93, 96, 112, 115, 130, 133
N
Neutral current .......................................................................................... 31
P
Physical hardware .............................................................................. 19, 25
Polling ...................................................................................................... 71
Power quality ......................................................................................... 147
Program Organisation Unit (POU) ........................................................... 21
Project tree ................................................................................................ 19
R
References .............................................................................................. 157
Relay configuration procedure ................................................................. 77
Relay Configuration Tool ........................................................................ 15
S
Specification for REF 54_ Feeder Terminal Configuration ..................... 79
Specification for REM 54_ Machine Terminal Configuration ................ 97
Specification for RET 54_ Transformer Terminal Configuration ......... 117
T
Task interval ............................................................................................. 48
Tasks ........................................................................................................ 47
Technical data .......................................................................................... 30
True RMS measurement ..................................................................... 30, 40
V
Variable worksheet ....................................................................... 21, 22, 51
Virtual channels .................................................................................. 33, 43
W
Warnings .................................................................................................. 67
160
1MRS750745-MUM EN 10.2006
ABB Oy
Distribution Automation
P.O. Box 699
FI-65101 Vaasa
FINLAND
Tel. +358 10 22 11
Fax. +358 10 224 1094
www.abb.com/substationautomation