Sunteți pe pagina 1din 6

IX International Symposium on

Lightning Protection
26th-30th November 2007 – Foz do Iguaçu, Brazil

TESTING OF LONG-FLASHOVER ARRESTERS DESIGNED FOR


DISTRIBUTION LINES

Orsino Oliveira Filho, Darcy Ramalho de


Georgij Podporkin and Acacio Wey
Mello and Gloria Suzana Gomes de Oliveira
CEPEL – Centro de Pesquisas de Energia Elétrica, Brasil Streamer Electric Company, Russia
orsino@cepel.br, darcy@cepel.br, gloria@cepel.br georgij.podporkin@streamer.ru, acacio.wey@bighost.com.br
CEPEL address: Av Horácio Macedo, 354, Cidade Universitária, PO. Box 21941-911 – Rio de Janeiro - Brazil

Abstract - Outages of overhead power lines due to lightning Arresters (LFAs) have been used for more than three
strokes are one of the main causes of shortages of electric years [2, 3]. The operating principle is based on extension
supplies and economic losses of power utilities. Pole-top of the impulse flashover channel on the arrester surface
metal oxide arresters can protect distribution lines against through the creeping discharge effect. Owing to a long
induced over-voltages, but they can be destroyed in case of
flashover length, the power arc gets extinguished. The
direct lightning stroke. Long Flashover Arresters (LFAs)
have been developed and used successfully for this purpose main advantage of LFA is that current passes outside the
and have no possibility of being destroyed because the apparatus, flowing along arrester surface. Therefore, the
current flows externally along its surface. Since field arrester cannot be destroyed by excessive current, even at
experience with 10 kV LFAs has been very successful, it was direct lightning stroke. LFA’s construction is rather
decided to work on developing 13.8 kV LFAs, considering simple and reliable.
that it is the predominant voltage level of overhead
distribution lines in Brazil and other countries. The There are several types of LFA under development. LFA
performance of LFA for quenching and dielectric tests has
of Loop type (LFA-L) is intended for protection of
been investigated through laboratory tests under conditions
that typically represent electrical energy distribution
overhead lines against induced overvoltages. Principle of
systems. Details about these tests and their results are operation and its design are detailed in [1]. LFA-Ls are
presented in this paper. Information about their design and recommended to be installed one arrester per pole with
applications are also shortly presented. phase interlacing [4]. LFA of Module type (LFA-M) can
protect overhead lines against induced overvoltages and
1 INTRODUCTION direct lightning strokes as well. In latter case it should be
installed in parallel to each insulator at a pole [3].
Outages of overhead power lines due to lightning strokes
are one of the main causes of shortages of electric Experimental exploitation of LFAs started in 1999 and
supplies and economic losses of power utilities. Widely during last three years more than 80 thousands arresters
separated pole-top metal oxide arresters can protect a were installed in various utilities. Since field experience
distribution line against induced overvoltages. The main with 10 kV LFAs in Russia is very successful, it was
problem of using pole-top metal-oxide arresters is that decided to work on developing 13.8 kV LFAs,
they can be destroyed at direct lightning stroke to an considering that it is the predominant voltage level of
overhead line [1]. overhead distribution lines in Brazil and other countries.

In many countries, covered conductors are used for Lightning has been reported as being the main source of
distribution overhead lines. Such conductors have many outages on distribution networks, corresponding to 30 to
benefits comparing with bared conductors but there is a 60 % of these system outage indexes. This is particularly
problem of conductors burn down by power arc follow, confirmed in Brazil, which has a very high incidence of
which occurs after application of lightning overvoltage lightning strokes due to its ground dimension and inter-
and flashover of insulator. Arcing horns or similar tropical location. For example, considering two Brazilian
devices, which are used in some countries for protection utility companies installed in a region with ground flash
of covered conductors against conductors burn down, do density in the range of 4 to 8 flashes/(km2.year), lightning
not protect overhead lines from lightning outages. was associated with approximately 35% and 43% of the
total number of outages monitored during 1998 to 2002.
In Russia, for lightning overvoltage and conductor-burn [5]
protection of 10 kV overhead lines, Long Flashover
The performance of LFA for quenching and dielectric
tests has been investigated through laboratory tests under
conditions that typically represent electrical energy
distribution systems. Laboratory tests for LFA-M and
LFA-L were performed in Russia and Brazil, respectively.
Details about these tests and their results are presented in
this paper. Information about their design and applications
are also shortly presented.

2 LFA DESIGN AND OPERATION


Figure 1 - Loop-shaped LFA. a) photo of tests; b) main
2.1 LFA-L (Loop) dimensions. 1 – cable loop; 2 – clamp; 3 - steel structure; 4 –
metal tube; 5 – power line conductor; 6 – flashover channel; 7 –
Figure 1 presents an LFA of Loop type installed on a insulator; 8 - intermediate ring electrodes.
metal structure which models distribution line pole. A
piece of cable with steel cord is bent in a loop and
connected to the pole with a clamp. A metal tube is placed
over the insulated loop in its middle part forming, together
with the line conductor, a sparkover air gap S. At one arm
of the loop, intermediate ring electrodes are installed. The
loop is at the same potential as the structure. Due to a
relatively big capacitance between the metal tube and the
steel cord inside the cable, the tube is practically at the
same potential as the pole. Therefore an overvoltage
taking rise between the line conductor and the pole will be
also applied between the metal tube and the line
conductor. If the overvoltage is large enough, the
sparkover gap S will break down and the overvoltage will Figure 2 - LFA-M arrester for protection of 13.8 kV overhead
be applied between the metal tube and the steel cord lines. a) block diagram; b) electric schematic; c) arrester testing;
inside the cable to its insulation. Due to the overvoltage, a d) dimension.
creeping flashover develops from the metal tube to a
clamp of the insulated loop passing intermediate ring 3 APLICATION GUIDELINES
electrodes and next to the structure, thus completing the
discharge circuit. The intermediate electrodes have 3.1 Protection against induced overvoltages
protrusions at opposite sides. Therefore flashover channel
is broken into serially connected pieces of channels and To eliminate high short circuit currents associated with
due to this reason arc quenching is facilitated (see photo two-or three-phase lightning flashovers to ground, LFA-
in Figure 1a). Ls are recommended to be installed one arrester per pole
with phase interlacing (Figure 3).
2.2 LFA-M (Modular)
With such an arrangement, a flashover to ground results in
An LFA-M arrester consists of two cable-like pieces with a circuit comprising two phases, two arresters and two
a resistive core [3]. There are also intermediate ring grounding resistors that limit the fault current and ease arc
electrodes on its surface for the same purpose as for LFA- quenching. The higher are the values of the grounding
L (see above). The cable pieces are arranged so as to form resistance, the more effective is LFA-L operation.
three flashover modules 1, 2, 3 as shown in Figure 2. The
resistive core of the upper piece, whose resistance is R,
applies the high potential U to the surface of the lower
piece at its middle. Similarly, the resistive core of the
lower piece of the same resistance R applies the low
potential 0 to the surface of the upper piece, also at its
center. In this way the total voltage U is applied to each
flashover module at the same moment, and all three
modules are assured conditions for simultaneous initiation
of creeping discharges developing into a single long
flashover channel. Figure 3 - Schematic of LFA-L installation on a distribution
line.
3.2 Protection against direct lightning strokes The procedure for LFA-L quenching tests consisted of
firing it by injecting a current impulse through the
A direct lightning stroke causes flashover of all the sparkover air gap S (see Figure 1), being the power line
insulators on the affected pole. Therefore, in order to conductor energized by 60 Hz voltage of 7.5 kVrms to
protect the line against a direct lightning stroke, LFA-Ms ground.
should be mounted on the pole in parallel with each line
insulator (Figure 4). Phase-to-phase faults on a pole can The current impulse was obtained using an RLC-series
give rise to follow-up current on the order of 10 kA or impulse current generator, charged under 145 kVdc. The
more. In order to quench such currents, flashover length instant of the impulse injection was roughly controlled in
of the LFA-M 13.8 kV should be 1.7 m, i.e. much higher order to make it occur in a desired phase angle of the 60
than that of LFA-L (0.9 m) which intended to protect Hz current.
overhead lines against induced overvoltages.
For each test circuit condition, different cases of phase
4 QUENCHING TESTS angles were considered for injecting the impulse current.
The current limiter resistances were also varied, according
4.1 Quenching Tests for LFA-L to the circuit shown in Figure 5: R=10 Ω, 15 Ω, 20 Ω e 40
Ω. Two different types of insulator were used: porcelain
The tests for investigating the arc quenching performance pole insulator and polymer pin insulator, as shown in
of LFA-L were carried out in CEPEL’s laboratory, Rio de Figure 6.
Janeiro, Brazil, in the same installation designed for surge
arrester tests, taking advantage of the existent With the different injection phase angles and current
infrastructure used for the standardized operating duty limiter resistances, it was possible to investigate the
test. The circuit used and its main parameters are shown in quenching performance of LFA-L for various following
Figure 5. current values and durations.

4.2 Quenching Test Results for LFA-L

The quenching test arrangements are shown in Figure 7


and the results are summarized in Table I and Figure 8.

Table I: Quenching Test Results for LFA-L. Vg = 145kVdc,


V60Hz = 7.5 kVrms, Ifoll = Following current.
R(Ω) Insulator Tests Ifoll (Acr) Result
Polymer pin 5 All quenching
40 170
Porcelain pole 5 All quenching
Polymer pin 3 All quenching
10 470
Porcelain pole 7 3 no quenching
Figure 4 - Protection of 13.8 kV overhead lines against direct
lightning strokes by LFA-M arresters. Polymer pin 6 1 no quenching
15 350
Porcelain pole 7 All quenching
20 Polymer pin 7 300 All quenching
R
Lg Rg
LC
Cg
parameters
Current impulse
ZnO for a typical LFA-L generator
distribution
line
TC2 TC1

DIV1 DIV2

Figure 5 – Circuit and parameters for LFA-L quenching tests.


DIV1: Voltage divider, source side; DIV2: Voltage divider,
LFA-L side; TC1: High frequency current transformer, LFA-L
current; TC2: High frequency current transformer, 60 Hz source
current; R: Current limiter resistor. R=10 , 15 , 20 and 40 Ω; LC a) Porcelain pole insulator b) Polymer pin insulator
parameters for a distribution line: C ≈ 0.5 nF, L ≈ 0.35 mH; Figure 6 – Insulators used for LFA-L quenching tests
Current impulse generator: Cg = 1µF, Lg = 21.8µH, Rg = 75Ω;
Note: The power source was a regulator, 0-15 kV, 5 MVA.
4.3 Quenching Tests for LFA-M

The quenching tests for LFA-M were performed in


NIIVA´s laboratory, St. Petersburg, Russia. The test
circuit was essentially the same shown in Figure 5, except
the power frequency which was 50 Hz and the resistance
R which was short-circuited.

Test results are summarized in Table II and some typical


oscillograms are presented in Figure 9. There are two
possibilities of current quenching: 1) when current
impulse finishes (it is called further “quenching at front”);
2) when power frequency current passes zero (it is called
further “quenching at zero”). Figure 8 b) - No quenching

4.4 Comments on Quenching Tests Figure 8 – Quenching tests results LFA-L. R=15 Ω, 1-> Source
current 400 A/div, 2-> LFA-L current 500 A/div, 3-> Source
From the quenching test results presented above for LFA- voltage 8474 V/div, 4-> LFA-L voltage 8484 V/div.
L, it can be said that it reliably (100%) interrupts the
Table II: Quenching Test Results for LFA-M, R = 0 Ω, Ishort-
power frequency current following the impulse current
circuit = 4000 A, V50Hz = 8.7 kVrms. Ifoll = Following
discharge, when tested under conditions that represent a current.
typical 13.8 kV distribution line with grounding resistance
Vg (kVdc) Tests Ifoll (Acr) Result
greater than or equal to 15 Ω.
200 5 1084 All quenching
For lower values of grounding resistance, e.g. 10Ω, 240 2 1196 All quenching
probability of arc quenching is less than 100%. Based on 248 1 1215 Quenching
the obtained results for R=10Ω, the probability of failure 248 1 1400 No quenching
can be estimated as Pf = 8/180≈0.04 and probability of
successful arc quenching Pq=1- Pf=1-0.04=0.96.

a) with polymer pin insulator b) with porcelain pole insulator


Figure 7 – Quenching test arrangement
Figure 9 a) - Quenching at zero, Ifoll ≅ 1.1 kA

Figure 9 b) - No quenching , Ifoll ≅ 1.4 kA


Figure 8 a) – Quenching
Figure 9 – Quenching test results LFA-M
As can be seen from Table II, LFA-M successfully In order to verify the impulse disruptive discharge
quenches power follow current for a circuit with short behavior of LFA, three lightning impulses with peak value
circuit current of 4 kA and for power generator voltage of of 300 kV, that is the highest possible induced
8.7 kVrms. Therefore, for lower grid voltage of 7.5 overvoltage in distribution lines, were also applied to the
kVrms, it is expected that LFA-M quench higher values of LFA test arrangement. For all insulator test arrangements,
power follow currents. the disruptive discharges occurred on the LFA at a voltage
level bellow the Basic Insulation Level (BIL).
5 DIELECTRIC TESTS
5.2 Radio interference voltage tests
In order to verify the dielectric performance of LFA
arresters with some insulators used in Brazilian Radio interference voltage (RIV) tests were also carried
distribution lines, several dielectric tests were carried out out in the arrangement with LFA and insulators. The
in CEPEL’s High Voltage Laboratories. The 15 kV criterion considered was: RIV maximum limit of 200 µV,
insulators used are shown in Figure 10. Insulators number 1MHz, under 8.8 kVrms. The tests were made in the
1, 2 and 5 are made of porcelain. Insulators 3, 4 and 6 are following conditions:
polymeric and insulator 7 has a porcelain core with • without LFA under dry condition;
polymeric protection. • with LFA-L under dry condition;
• with LFA-M under dry condition.
5.1 Lightning impulse tests It was observed that the RIV values for LFA-M with
insulator Nr. 1 exceeded the maximum limit at a voltage
The determination of the impulse withstand voltage was level close to 8.8 kV. It was also observed that in the knee
made using the up-and-down test method with 30 region, the RIV curves for LFA-M varied sharply with the
impulses, at both polarities in the following conditions: test voltage.
• without LFA under dry condition;
• with LFA under dry condition; 5.3 Power frequency tests
• with LFA under wet condition.
The determination of 60 Hz disruptive discharge voltages
LFA-L was connected to the conductor via air gap S = 3 was made considering the average of five values of
cm, while LFA-M was connected to the conductor voltages that caused disruptive discharges when applied to
directly, without air gap. the LFA-L in the test arrangement. The tests were made in
the following conditions:
During tests all flashovers occurred at LFAs while the • Without LFA-L arresters under dry condition;
insulators withstood applied impulses. The obtained • With LFA-L under dry condition;
flashover voltages of LFAs were less than flashover • Without LFA-L under wet condition;
voltages of all types of insulators. The smallest difference • With LFA-L under wet condition.
was observed for the insulator Nr. 1 and the greatest for It was observed that the disruptive discharge voltages
insulators Nr. 3, 5 and 6. obtained under dry conditions, for all LFA-L test
arrangements, were smaller than those for all tested
insulators alone. Otherwise, the results were different with
insulators number 2, 3 and 7, under wet condition. This
fact indicated that the length of the gap between LFA-L
and the conductor must be dependent of the insulator type.

In order to verify the power frequency disruptive


discharge behavior of LFA-M, 60 Hz voltages of 34
kVrms, that is the withstand voltage level for 15 kV
distribution lines, were applied to LFA-M test
arrangement, under dry and wet conditions, during 1
minute. No discharge occurred for all test arrangement
and conditions.

5.4 Pollution tests

Pollution tests were carried out in the arrangement with


Figure 10 – Insulators used in dielectric tests. LFA and insulator number 5 with a salinity of 40 kg/m3.
Each LFA type was stressed three times in its test
arrangement, during one hour, with 8.8 kVrms and no
flashover was observed. After the tests, both LFA types
presented minor marks of corrosion in the intermediate
ring electrodes, as can be seen in Figure 11.

5.5 High impulse current tests

Additionally, some high impulse currents were applied in


the same unit of LFA-L used in all quenching tests in
CEPEL. Impulse currents up to 30 kAcrest, 8/20 µs and
up to 85 kAcrest, 4/10 µs were applied to the LFA-L unit.
No damage was observed on its surface and ring
electrodes.

6 CONCLUSIONS Figure 11 – Ring electrodes after pollution tests.

Long Flashover Arresters were developed to protect


overhead distribution lines against lightning overvoltage 7 REFERENCES
and conductor-burn and have been successfully used in
Russia 10 kV lines. In order to check their dielectric and [1] IEEE Guide for Improving the Lightning Performance of
operating performances considering their possible Electric Power Overhead Distribution Lines, IEEE Std
application in 13.8 kV overhead lines, laboratory tests 1410TM- 2004.
were carried out under high voltage and impulse current [2] G. V. Podporkin, A. D. Sivaev, "Lightning Protection of
Overhead Distribution Lines by Long Flashover Arresters",
conditions. Based on the technical information and test
IEEE Transactions on Power Delivery, vol. 13, n. 3, pp.
results presented here, the following conclusions can be 814-823, July 1998.
drawn: [3] G. V. Podporkin, V.E. Pilshikov, A. D. Sivaev, “Lightning
a. Long Flashover Arresters of Loop (LFA-L) and Protection of Medium Voltage Overhead Lines by Modular
Modular (LFA-M) types had a good performance Long-Flashover Arresters", IEEE Transactions on Power
in the dielectric, lightning impulse, radio Delivery, vol. 18, n. 3, pp.781-787, July 2003.
interference, power frequency and power arc [4] G. V. Podporkin, A. D. Sivaev and V. E. Pilshikov,
quenching tests. “Application of Long Flashover Arresters for Lightning
b. LFA-Ls can protect overhead 13.8 kV lines Protection of Overhead Distribution Lines”, Proceedings of
24th International Conference on Lightning Protection
against induced overvoltages. LFA-Ls are (ICLP), 14th-18th September 1998, Birmingham, United
recommended to be installed one arrester per Kingdom, pp. 605-610.
pole with phase interlacing. [5] S. P. Silva, A. Piantini, J. L. D. Franco, J. Gonçalves,
c. LFA-Ms can protect overhead 13.8 kV lines "Lightning performance studies for a 13.8 kV distribution
against overvoltages of direct lightning strokes. network", Proc. of the VII International Symposium on
LFA-Ms should be mounted on the pole in Lightning Protection (VII SIPDA), v. 1, pp. 137-143,
parallel with each line insulator. Curitiba, Nov. 2003.

S-ar putea să vă placă și