Sunteți pe pagina 1din 3

A

2009-04-07

1st Issue

HrM

REV

DATE

DESCRIPTION

SIGN

CCI Valve Technology AB

PREPARED BY

DATE

HrM

2009-04-07

CHECKED BY

DATE

LgM

2009-04-20

TITLE:

Technical Specification for


Tag nr: HP-SCV / HP-DT
DOCUMENT NUMBER: V299356.20.40

Technical Specification.
Steam conditioning valve equipment.
Date / Rev. / User Id :
Customer :
Project :
PO. No.
Reference No.
Tag No.
No. of valves

2009-04-07 / A / Hillenaar, Maarten


Descon Engineering FZE
Bhikki CCPP
0002528
299356
HP-SCV / HP-DT
1

Operating data
Steam Inlet
Q1
p
t
h
v
K
Steam Outlet
Q2
p
t
h
v
Part free water
Condenser
p
t
h
v
Water Inlet
Qw
p
t
h
v

V299356.20.40

GT1 Startup

GT1+GT2 Nor

GT1+GT2 Max

[kg/h]
[bar a]
[C]
[kJ/kg]
[m/kg]
[-]

130000.0
42.90
536.1
3524.1
0.08456
1.275

230000.0
92.26
536.7
3475.0
0.03800
1.281

260000.0
97.11
539.6
3477.1
0.03614
1.281

[kg/h]
[bar a]
[C]
[kJ/kg]
[m/kg]
[1-x]

176221.0
2.97
133.2
2724.2
0.61169
0.029

307185.7
5.28
153.9
2749.9
0.35622
0.039

347473.7
5.99
158.8
2755.4
0.31597
0.041

[bar a]
[C]
[kJ/kg]
[m/kg]

0.080
80.00
2649.8
20.34100

0.080
80.00
2649.8
20.34100

0.080
80.00
2649.8
20.34100

[kg/h]
[bar a]
[C]
[kJ/kg]
[m/kg]

46221.0
30.00
45.0
191.0
0.00101

77185.7
30.00
45.0
191.0
0.00101

87473.7
30.00
45.0
191.0
0.00101

GT1 Startup

GT1+GT2 Nor

GT1+GT2 Max

Calculated data
Steam Valve
Kv calc
Inlet pipe
Diam ID/OD/t
Inlet Velocity
Outlet pipe
Diam ID/OD/t
Outlet Velocity
Water Valve
p Outlet
Kv calc
Inlet pipe
Diam ID/OD/t
Velocity

Page 1/2

[-]
[DN]
[mm]
[m/s]
[DN]
[mm]
[m/s]

385.7
311.4
300
237.18/323.8/43.31
69.1
54.9
800 XS
787.6/813/12.7
61.5
62.4

334.6

[bar a]
[-]
[DN]
[mm]
[m/s]

4.57
7.41
9.12
16.15
100 STD
102.26/114.3/6.02
1.6
2.6

8.33
18.69

Design
98.00
565.0

6.00
526.0

45.00
55.0

59.1

62.6

3.0

System design consideration CCI document "Installation Guidelines II500.0o/5en"


Application wizard
Industry
Process Id
Application

Pure power plant (PP)


Power/Combined Cycle dual pressure non reheat with water condensor (212212)
HP to aux steam (N)

Note: Special Design Dual Inlet !

PowerSIZ 1.3S

Selected CCI

Steam conditioning equipment.

Reference No.
Date / Rev. / User Id :

V299356.20.40

Page 2/2

2009-04-07 / A / Hillenaar, Maarten

Tag No.

HP-SCV

Valve type

VLB - 140BTC

Valve design
No. of pressure reducing stages
Seat
Leakage class
Kvc
[-]
Kvs
[-]
Control plug type
Characteristic
Spare capacity
[%]
Full Stroke
[mm]
Actuating force
[kN]
Shut-off-p
[bar a]
Desuperheater
Connections
Inlet
[DN]
Rating
Outlet
[DN]
Rating
Water inlet
[DN]
Rating
Materials
Inlet
Body
Outlet
Water connection
Stem
Plug
Seat
Packings
Design code

Single-seated
5
140
V
386
424
Fixed Cage
Modified Linear
10
130
49.3
98.0
OP4030H/4

Actuator type

STI SC/V 390-150

Model
Stroke / MaxForce
[mm/kN]
Positioner / Air supply conn
Stroking time Mod / QO / QC
Power supply
Input signal
Increasing signal
Power supply failure
Accessories

Pneumatic Piston
150 / 57.0
FastTrak / 1/2"
2.0 s / NA / NA
5.0 bar(g)
4-20 mA
Valve opens
Valve closes
1 Limit switch opened
1 Limit switch closed
1 Air bottle
1 Trip valve
1 Position transmitter (integrated in positioner)
1 Air filter regulator
1 Tropical design
1 SS tubing
1 Junction box, Plastic

300 BWE
DIN 2559, Fig. 4
800 BWE
DIN 2559, Fig. 22
100 BWE
DIN 2559, Fig. 22
EN 10222-2 11CrMo9-10
EN 10222-2 11CrMo9-10
EN 10216-2 13CrMo4-5
EN 10222-2 16Mo3
X19CrMoVNbN11-1
X19CrMoVNbN11-1
X10CrMoVNb9-1 / C21 coating
Graphite
EN 12516-2

Notes:
IP65
Tag No.

HP-DT

Dumping device

D-tube WCC

No of stages
Kvs
Material
Diameter / Length

[-]
[mm/mm]

1
5286
EN 10216-2 13CrMo4-5
800 / 1000

PowerSIZ 1.3S

S-ar putea să vă placă și