TAC Xenta 102-AX

VAV Controller with Actuator and


Airflow Transducer

6 Mar 2002

TAC Xenta 102-AX is a zone controller intended for VAV


heating and cooling applications with one or two stages of
reheating. The controller keeps a constant temperature in
the zone by controlling the air flow and heating stages. By
using a carbon dioxide sensor, the air quality can be controlled in the zone.
TAC Xenta 102-AX is equipped with an integrated, static
air velocity transducer and a motorized bidirectional actuator in a single package.
The differential pressure air velocity transducer requires a
minimum of maintenance. Thus it is also well suited to be
placed in the zone return air duct.
The controller is a LONMARK compliant device aimed at
communicating on a LONTALK TP/FT-10 network via a
twisted-pair, unpolarized cable. It is able to operate both
as a stand-alone unit and as part of a system. All relevant
network variables can be monitored and configured via
the Network Plug-in or, locally, via the intelligent thermostat device I/STAT or the commissioning device M/STAT.
TECHNICAL DATA
Supply voltage, single class two source,
.............................................. 24 V AC +/-10%, 5060 Hz
Power consumption:
Controller ................................................................... 8 VA
Digital outputs, each ...................................... max. 18 VA
Total, all outputs ............................................. max. 48 VA
Ambient temperature:
Operation ....................... 0 C to +50 C (32 F to 122 F)
Storage ........................ -20 C to +50 C (-4 F to 122 F)
Humidity ............................. 10 to 90% RH, non-condensing
Enclosure:
Dimensions ........... 19715963 mm (7.75"x6.25"x2.50")
Enclosure rating .................................. NEMA 1 and IP 10
Meets .. UL94-5V UL flammability for plenum applications
Weight .................................................... 1.04 kg (2.30 lb.)
Inputs Digital:
Dry Contact, excitation .......................... 5 V DC at 0.5 mA
Input Analog:
Thermistor type ........... 10 kOhm NTC (Dale 1M1002-C3)
Accuracy ......................... 0.25 % typical span (resistance)
Resolution ....................................................... 0.1 % span
Velocity Pressure Input:
Span ............................. 0249 Pa (01.0" Water column)
Accuracy .................... 5 % at 250 Pa (1.0" Water column)
Resolution ..................... 1.07 Pa (0.0043" Water column)
Sensor fitting ...... FRPE polyethylene tubing 6.3 mm (")
Dead-End device No air consumption
Outputs:
Low voltage TRIAC ................ 24 V AC, voltage sourcing,
...................... max. 0.75 A (2 A total for all three outputs)
Torque rating ........................................... 6 Nm (53 lb.-in.)
Stroke ........................................ 0 to 95, fully adjustable
Timing ............................. 2.4 sec/degree rotation (50 Hz)
........................................... 2 sec/degree rotation (60 Hz)
Position indication ................................... Visual indication
Manual override ..................... Push-button clutch release
Subject to modification.

1 (8)

Terminations ............ Removable screw terminal connectors


Damper linkage: round shaft extending a minimum of
25 mm (1") from the box, diameter .............. 12.7 mm (")
Application program:
Cycle time .................................................................... 1 s
Indication LED colors:
Power On ................................................................ green
LON network activity transmission .......................... amber
LON network activity receive ................................... green
Neuron service ........................................................ amber
Interoperability standard conforms to:
.......................... LONMARK Interoperability Guidelines and
.................... LONMARK Functional Profile: VAV Controller
Communication protocol ...................................... LONTALK
Physical channel ................................. TP/FT-10, 78 kbps
Neuron type ............................................. 3150, 10 MHz
Complies with the requirements of:
FCC Part 15
C-Tick
CE ............................................................ EN 61326:1998
UL916 Energy Management Equipment
US Patent no. RE37, 245E (reissue of no. 5,450,999)
Part numbers, TAC Xenta 102-AX:
Controller ........................................................ 0-073-0540
I/STAT, LED version ....................................... ISTAT-A-C
I/STAT, LCD version .................................. ISTAT-LDC-C
M/STAT, LED version ................................... MSTAT-A-C
S/STAT .......................................................... SLIDESTAT
TTS100WJ ...................................................... TTS100WJ
Installation Handbook .................................... 0-004-7838
SW and HW Reference Handbook ................ 0-004-7839
Installation Instruction ....................................... 0FL-4063
Pocket Reference Card ..................................... 0FL-4064

0-003-2237-0 (EN)

APPLICATION EXAMPLE
Carbon Wall
Occupancy
dioxide Module Sensor
Sensor

Two Electrical
Reheat Stages,
Relays

and Damper

Air Flow Sensor

Fan

Figure 1

FUNCTIONS
The TAC Xenta 102-AX VAV controller
is a component of a single path VAV air
delivery system (Figure 1).
The controller has an integrated static
air velocity transducer and a motorized
bidirectional actuator. Other features:

CO2 monitoring;
reheat control;
damper control;
heating/cooling changeover;
occupancy/light control.

Reheating control may be done in


several ways:

3-stage heating
Pulse Width Modulation (up to 999 s)
Increase/decrease (floating)

Fan control can be enabled/disabled,


either in a parallel or serial mode.
The TAC Xenta 102-AX VAV can
operate in a stand-alone configuration
or as part of an interconnected network.
All network variables are preconfigured
at the factory. This reduces setup time
for both stand-alone and integrated
configurations and allows stand-alone
operation by providing the required
data. Please refer to figure 2.

nvoSetPtOffset
nvoStatOccBtn
nvoUnvInput4

UnivIn4 Sense 1
nvoAuxTemp2
nvoCO2sensor
nvoUnvInput3

UnivIn3 Sense 1
nvoLocalOccLatch
nvoUnvInput2

UnivIn2 Sense 1
VAV Controller 1
nvoAuxTemp1
nvoEmergCmd
nvoUnvInput1

nviRelStPt
nviActuatorState

nviUnvOutput1

UnivOut1 Object 1
nviUnvOutput2

UnivOut2 Object 1

nviUnvOutput3

UnivOut3 Object 1

nvoActualValue

UnivIn1 Sense 1
Damper Actuator 1
nvoAirFlow
nvoAirPressure

Airflow sense

Air flow calibration and essential configuration can be made directly from the
wall module (I/STAT) and the hand-held
M/STAT.
Plug-In
When the controller is connected to a
LonMaker LNS 3 network, a software
Plug-In is provided to simplify the
setting and monitoring of the controller
functions, for example the Network
Variables and the Configuration
Parameters.
0-003-2237-0 (EN)

nviStPointOffset
nvoBoxFlow
nviOccCmd
nvoEffectSetPt
nviAirFlowReset
nvoFanLoad
nviApplicMode
nvoFlowControlPt
nviBoxFlow
nvoHeat1Load
nviOutsideTemp
nvoHeat2Load
nviCO2
nvoHighSpaceTemp
nviOccLocalLatch
nvoLowStaticPres
nviDuctInTemp
nvoOAirFlowRatio
nviEmergCmd
nvoOccpncyStatus
nviEnergyHoldOff
nvoSpaceTemp
nviManOverride
nvoTerminalLoad
nviRemoteOccBtn
nvoUnitStatus
nviSetPoint
nvoMotorPositn
nviSpaceTemp X/STAT

2 (8)

(Internal signals shown)

Figure 2

OPERATING AND APPLICATION MODES


Occupied mode
Occupied mode is used when the zone
is occupied. This mode is also the default mode after a reset or a power up.

Warmup
Max. Flow

Cooling
Max. Flow

Air Flow
Heating Min. Flow

+100%

Cooling Min. Flow

Standby mode
The standby mode is to raise the active
cooling setpoint/lower the heating setpoint when the zone is temporarily
unoccupied.
Bypass mode
When the TAC Xenta VAV controller is
in unoccupied scheduled times of the
day or week, a push-button Bypass, or
manual override from the local wall
module (for example I/STAT or S/STAT)
can activate the Bypass mode to the
occupied setpoints for an adjustable
override period.
If the button is pressed again before the
defined override period expires, the unit
will return operation to unoccupied
setpoints unless the local hardware
input or the network input are calling for
occupancy.
Unoccupied mode
Unoccupied is to prevent the zone from
overheating/overcooling after-hours.
Morning Warmup
Adjusting the temperature, before a set
time, so that the correct comfort temperature is reached as required.
Night Purge
Using cool night air to ventilate the
building in Unoccupied mode.
Emergency pressurization/depressurization
Optional pressurization control supporting smoke control systems for the entire
area served.

Heat Stages: 5 4 3 2 1
1 Warmup
0%
2 Fan
3 Heat 1
-50%
4 Heat 2
5 Heat 3
-100% Heating
Band

+50%

Terminal Load
0%

Cooling
Band
Offset
Cooling
Setpoint

Offset
Heating
Setpoint

Figure 3

Air Quality Control


The controller includes an additional air
quality controller, which will modulate
the airflow to maintain the carbon dioxide level in the zone between set
limits, see figure 4.

Air flow
100%

max.

min.
0%

low limit

high limit

CO2 level
(ppm)
Figure 4

Pre-cooling
Lowering the temperature during the
night to anticipate and lessen the cooling
demand during the day.

CABLES AND ACCESSORIES


Cables

Accessories

G and G0:
Min. cross-sectional area 0,75 and
1,5 mm (AWG 18 and 14).

I/STAT

C1 and C2:
TP/FT-10 allows the user to wire the
control devices with virtually no
topology restrictions.
The max. wire distance in one
segment depends on the type of wire
and the topology.

M/STAT

The TAC Xenta Network guide (part


no. 0-004-7460) gives a more
detailed description.

TTS100WJ

An intelligent wall-mount sensor


with display and keypad control.

A thermistor wall-mount sensor with


an M/STAT communication jack.

Portable maintenance version of


I/STAT, equipped with interface
cable and connector.
S/STAT
A wall-mount sensor with bypass
button, a slide potentiometer to
adjust the temperature setpoint and
an M/STAT communication jack.
3 (8)

0-003-2237-0 (EN)

OPERATING
MODES (CONTD.)
LONMARK OBJECTS
AND NETWORK VARIABLES
VAV Controller
Object Type: # 8010

mode
00 HVAC_AUTO
01 HVAC_HEAT
02 HVAC_MRNG_WRMUP
03 HVAC_COOL
04 HVAC_NIGHT_PURGE
06 HVAC_OFF

Mandatory Network Variables


00 HVAC_AUTO
01 HVAC_HEAT
02 HVAC_MRNG_WRMUP
03 HVAC_COOL
04 HVAC_NIGHT_PURGE

nv1

nviSpaceTemp
SNVT_temp_p

nv3

nvoSpaceTemp
SNVT_temp_p

nv2

nviSetPoint
SNVT_temp_p

nv4

nvoUnitStatus
SNVT_hvac_status

06 HVAC_OFF
09 HVAC_FAN_ONLY
FF HVAC_NUL
00 OC_OCCUPIED
01 OC_UNOCCUPIED
02 OC_BYPASS
03 OC_STANDBY
FF OC_NUL
00 EMERG_NORMAL
01 EMERG_PRESSURIZE
02 EMERG_DEPRESSURIZE
03 EMERG_PURGE
04 EMERG_SHUTDOWN
FF EMERG_NUL

09 HVAC_FAN_ONLY

Optional Network Variables

FF HVAC_NUL

nv5

nviApplicMode
SNVT_hvac_mode

nv16

nvoEffectSetPt
SNVT_temp_p

nv6

nviManOverride
SNVT_hvac_overid

nv17

nvoFlowControlPt
SNVT_flow

nv7

nviStPointOffset
SNVT_temp_p

nv18

nvoBoxFlow
SNVT_flow

nv8

nviOccCmd
SNVT_occupancy

nv19

nvoTerminalLoad
SNVT_lev_percent

nv9

nviEmergCmd
SNVT_hvac_emerg

nv10

nviBoxFlow
SNVT_flow

nv11

nviEnergyHoldOff
SNVT_switch

nv13

nviCO2
SNVT_ppm

nv15

nviDuctInTemp
SNVT_temp_p

Configuration Properties
nciMinDelTempSnd
nciSpacTempHiLim
nciSpacTempHiHys
nciSpacTempLoLim
nciSpacTempLoHys
nciOvrBehavSpTem
nciOvrDefltSpTem
nciOvrValueSpTem
nciSetPnts
nciSetpntOffRnge
nciMaxFlow
nciMinFlow
nciMaxFlowWarmup
nciMinFlowWarmup
nciMinFlowHeat
nciMinFlowStand
nciUnoccuAirFlow
nciAirFlowFanOff
nciAirFlowFanOn

nciSetPnts.occupied_cool
.standby_cool
.unoccupied_cool
.occupied_heat
.standby_heat
.unoccupied_heat

nciOveridDuratn
nciCoolingBand
nciHeatingBand
nciCO2HiLimitCIn
nciCO2LoLimitCIn
nciCO2ThrshldCIn
nciCO2ThrshldOff
nciCO2ThrshldOn
nciOccupiedOA
nciUnoccupiedOA
nciFanTypeVAV
nciFanEnaWarmup
nciResponseRate
nciVAVSelctnCntl
nciHeatEnaWarmup
nciLoStaPriority
nciDelayReprtLoS
nciHiTempPriority
nciDelayReprtHiT
nciHomeLEDTmOut
nciSrvcModeTmOut
nciPasswordVaule

SNVT_temp_p
SNVT_temp_p
SNVT_temp_p
SNVT_temp_p
SNVT_temp_p
SNVT_override
SNVT_temp_p
SNVT_temp_p
SNVT_temp_setpt
SNVT_temp_p
SNVT_flow
SNVT_flow
SNVT_flow
SNVT_flow
SNVT_flow
SNVT_flow
SNVT_flow
SNVT_flow
SNVT_flow

heat_output_primary Heat1Load
heat_output_secondryHeat2Load
cool_output
CoolLoad
econ_output
VavLoad
fan_output
FanLoad
in_alarm

SNVT_elapsed_tm
SNVT_temp_p
SNVT_temp_p
SNVT_ppm
SNVT_ppm
SNVT_ppm
SNVT_ppm
SNVT_ppm
SNVT_flow
SNVT_flow
UNVT_fan_type
UNVT_no_yes
UNVT_response_rt
UNVT_vav_selectn
UNVT_no_yes
SNVT_count
SNVT_time_sec
SNVT_count
SNVT_time_sec
SNVT_time_sec
SNVT_time_sec
UNVT_password

Manufacturer Network Variables


nv21

nviRemoteOccBtn
SNVT_switch

nv25

nvoOccpncyStatus
SNVT_occupancy

nv22

nviOutsideTemp
SNVT_temp_p

vn26

nvoMotorPosition
SNVT_lev_percent

nv23

nviOccLocalLatch
SNVT_occupancy

vn27

nvoFanLoad
SNVT_lev_percent

nv24

nviAirFlowReset
SNVT_lev_percent

nv28

nvoHeat1Load
SNVT_lev_percent

nv29

nvoHeat2Load
SNVT_lev_percent

nv30

nvoOAirflowRatio
SNVT_lev_percent

nv31

nvoLowStaticPress
SNVT_count

nv32

nvoHighSpaceTemp
SNVT_count

Hardware Input/Output

VAV Controller Object

M/STAT, I/STAT

Figure 5

Damper Actuator
Object Type: # 8110
Mandatory Network Variables
nv1

nviRelStpt
SNVT_lev_percent

nv2

nviActuatorState
SNVT_switch

nv3

nvoActualValue
SNVT_lev_percent

Optional Network Variables


Configuration Properties
nciMaxRngeDmpr
nciMinRngeDmpr
nciOvrBehavDmpr
nciOvrDefltDmpr
nciOvrValueDmpr
nciDelayStrtDmpr
nciDelayStopDmpr
nciOutputTypDmpr
nciDirectionDmpr
nciDriveTimeDmpr
nciMinPulseDmpr

SNVT_lev_percent
SNVT_lev_percent
SNVT_override
SNVT_lev_percent
SNVT_lev_percent
SNVT_time_sec
SNVT_time_sec
UNVT_output_type
SNVT_state
SNVT_time_sec
SNVT_time_sec

Hardware Output

Damper Actuator Object


0-003-2237-0 (EN)

Motor_desired_position
Motor_position

4 (8)

Figure 6

Universal (Analog) Input 1


Object Type: # 0520

Universal (Analog) Input 2


Object Type # 0520

Mandatory Network Variables

Mandatory Network Variables

nvoUnvInput1
SNVT_lev_percent

nv1

nvoUnvInput2
SNVT_lev_percent

nv1

Optional Network Variables

Optional Network Variables

Configuration Properties
nciMaxRngeUI1
nciMinRngeUI1
nciDeltaSndUI1
nciGainUI1
nciOffsetUI1
nciOvrBehavUI1
nciOvrDefltUI1
nciOvrValueUI1
nciUniIn1Selctn
nciEmContctDebTm
nciOvrDefltEmCon
nciOvrValueEmCon
nciDelTemSndAux1
nciOffsetTemAux1
nciOvrDefltTAux1
nciOvrValueTAux1

Configuration Properties

SNVT_lev_percent
SNVT_lev_percent
SNVT_lev_percent
SNVT_muldiv
SNVT_lev_percent
SNVT_override
SNVT_lev_percent
SNVT_lev_percent
UNVT_select_UI
SNVT_elapsed_tm
SNVT_hvac_emerg
SNVT_hvac_emerg
SNVT_temp_p
SNVT_temp_p
SNVT_temp_p
SNVT_temp_p

nciMaxRngeUI2
nciMinRngeUI2
nciDeltaSndUI2
nciGainUI2
nciOffsetUI2
nciOvrBehavUI2
nciOvrDefltUI2
nciOvrValueUI2
nciUniIn2Selctn
nciOccLatchDebTm
nciOccLatchPeriod
nciOcLatchNormOp
nciOvrDefltOccLt
nciOvrValueOccLt

Manufacture Network Variables

Manufacturer Network Variables


nv2

nvoEmergCmd
SNVT_hvac_emerg

nv3

nvoAuxTemp1
SNVT_temp_p

SNVT_lev_percent
SNVT_lev_percent
SNVT_lev_percent
SNVT_muldiv
SNVT_lev_percent
SNVT_override
SNVT_lev_percent
SNVT_lev_percent
UNVT_select_UI
SNVT_elapsed_tm
SNVT_elapsed_tm
SNVT_occupancy
SNVT_occupancy
SNVT_occupancy

nvoLocalOccLatch
SNVT_occupancy

nv2

Hardware Input
Hardware Input

Analog_value[]

Analog_value[]

Universal (Analog) Input 3


Object Type: # 0520

Universal (Analog) Input 4


Object Type: # 0520

Mandatory Network Variables

Mandatory Network Variables


nvoUnvInput3
SNVT_lev_percent

nv1

Optional Network Variables

Configuration Properties

Configuration Properties

SNVT_lev_percent
SNVT_lev_percent
SNVT_lev_percent
SNVT_muldiv
SNVT_lev_percent
SNVT_override
SNVT_lev_percent
SNVT_lev_percent
UNVY_select_UI
SNVT_ppm
SNVT_ppm
SNVT_ppm
SNVT_ppm
SNVT_temp_p
SNVT_temp_p
SNVT_temp_p
SNVT_temp_p

nciMaxRngeUI4
nciMinRngeUI4
nciDeltaSndUI4
nciGainUI4
nciOffsetUI4
nciOvrBehavUI4
nciOvrDefltUI4
nciOvrValueUI4
nciUniIn4Selctn
nciSStatBtnDebTm
nciOvrDefltOccBt
nciOvrValueOccBt
nciOvrDefltSPOfs
nciOvrValueSPOfs

nv3

nv2

nvoCO2sensor
SNVT_ppm

nv3

nvoAuxTemp2
SNVT_temp_p

nvoSetPtOffset
SNVT_temp_p

nvoStatOccBtn
SNVT_switch

Hardware Input

Hardware Input

Analog_value[]

Analog_value[]

Universal Input Object 3

SNVT_lev_percent
SNVT_lev_percent
SNVT_lev_percent
SNVT_muldiv
SNVT_lev_percent
SNVT_override
SNVT_lev_percent
SNVT_lev_percent
UNVT_select_UI
SNVT_elapsed_tm
SNVT_switch
SNVT_switch
SNVT_temp_p
SNVT_temp_p

Manufacturer Network Variables

Manufacturer Network Variables


nv2

nvoUnvInput4
SNVT_lev_percent

nv1

Optional Network Variables

nciMaxRngeUI3
nciMinRngeUI3
nciDeltaSndUI3
nciGainUI3
nciOffsetUI3
nciOvrBehavUI3
nciOvrDefltUI3
nciOvrValueUI3
nciUniIn3Selctn
nciDelCO2SndUI3
nciOffsetCO2UI3
nciOvrDefltCO2
nciOvrValueCO2
nciDelTemSndAux2
nciOffsetTemAux2
nciOvrDefltTAux2
nciOvrValueTAux2

Figure 8

Universal Input Object 2

Figure 7

Universal Input Object 1

Universal Input Object 4

Figure 9
5 (8)

Figure 10
0-003-2237-0 (EN)

AirFlow_Input_Object
Object Type # 1

Universal (Analog) Output 1


Object Type: # 0521

Mandatory Network Variables

Mandatory Network Variables

nv1

nvoAirFlow
SNVT_flow

nv2

nvoAirPressure
SNVT_press_p

nv1

nviUnvOutput1
SNVT_lev_percent

Optional Network Variables

Optional Network Variables

Configuration Properties
nciMaxRngeUO1
nciMinRngeUO1
nciOvrBehavUO1
nciOvrDefltUO1
nciOvrValueUO1
nciDelayStartUO1
nciDelayStopUO1
nciOutputTypUO1
nciDirectionUO1
nciInvertUO1
nciMinPulseUO1
nciDriveTimeUO1

Configuration Properties
nciDuctArea
nciPickupFactor
nciBoxConstant
nciLoBoxVelPress
nciAirFlowCoeff
nciMinDelFloSnd1
nciOvrBehavFlow1
nciOvrDefltFlow1
nciOvrValueFlow1
nciCalHiPress1
nciCalLoPress1
nciCalHiCount1
nciCalLoCount1
nciGainPress1
OffsetPress1
FactAirfloCal

SNVT_area
UNVT_pickup_fact
UNVT_box_const
SNVT_press_p
SNVT_lev_percent
SNVT_flow
SNVT_override
SNVT_flow
SNVT_flow
SNVT_press_p
SNVT_press_p
SNVT_count
SNVT_count
SNVT_muldiv
UNVT_press_10th
UNVT_airflow_cal

Optional Network
Variables
Configuration
Properties

Manufacturer Network Variables

Hardware Input

Hardware Output

air_pressure
Flow

Off_Time_UO1
On_Time_UO1
Output_pin_1

Air Flow Object

Mandatory Network Variables

Optional Network Variables

Configuration Properties

SNVT_lev_percent
SNVT_lev_percent
SNVT_override
SNVT_lev_percent
SNVT_lev_percent
SNVT_time_sec
SNVT_time_sec
UNVT_output_type
SNVT_state
UNVT_invert
SNVT_time_sec
SNVT_time_sec

nciMaxRngeUO3
SNVT_lev_percent
SNVT_lev_percent
nciMinRngeUO3
SNVT_override
nciOvrBehavUO3
SNVT_lev_percent
nciOvrDefltUO3
SNVT_lev_percent
nciOvrValueUO3
SNVT_time_sec
nciDelayStartUO3
SNVT_time_sec
nciDelayStopUO3
UNVT_output_type
nciOutputTypUO3
SNVT_state
nciDirectionUO3
UNVT_invert
nciInvertUO3
Optional Network
Variables
SNVT_time_sec
nciMinPulseUO2
Configuration
Properties
SNVT_time_sec
nciDriveTimeUO3

Optional Network
Variables
Configuration
Properties
Manufacturer Network Variables

Manufacturer Network Variables

Hardware Output

0-003-2237-0 (EN)

nviUnvOutput3
SNVT_lev_percent

Optional Network Variables

Configuration Properties

Universal Output Object 2

Figure 12

Mandatory Network Variables


nv1

Off_Time_UO2
On_Time_UO2
Output_pin_2

if DO

Universal (Analog) Output 3


Object Type: # 0521

nviUnvOutput2
SNVT_lev_percent

nciMaxRngeUO2
nciMinRngeUO2
nciOvrBehavUO2
nciOvrDefltUO2
nciOvrValueUO2
nciDelayStartUO2
nciDelayStopUO2
nciOutputTypeUO2
nciDirectionUO2
nciInvertUO2
nciMinPulseUO2
nciDriveTimeUO2

if PWM

Universal Output Object 1

Figure 11

Universal (Analog) Output 2


Object Type: # 0521

nv1

SNVT_lev_percent
SNVT_lev_percent
SNVT_override
SNVT_lev_percent
SNVT_lev_percent
SNVT_time_sec
SNVT_time_sec
UNVT_output_type
SNVT_state
UNVT_invert
SNVT_time_sec
SNVT_time_sec

Hardware Output

if PWM

Off_Time_UO3
On_Time_UO3
Output_pin_3

if DO

Universal Output Object 3

Figure 13
6 (8)

if PWM
if DO

Figure 14

Node Object
Object Type: # 0
Mandatory Network Variables
nv1

nviRequest
SNVT_obj_request

nv2

nvoStatus
SNVT_obj_status

Optional Network Variables


nv3

nviTimeSet
SNVT_time_stamp

nv4

nv8

nvoAlarm
SNVT_alarm
nvoFileDirectory
SNVT_address

Configuration Properties
nciProgramVersion
nciApplicVersion
nciLocation
JobNumber
nciOEMtype
nciNetworkConfig
nciMinSendTime
nciRcvHrtBt
nciSndHrtBt
nciAssignedAddr

UNVT_progm_versn
UNVT_aplic_versn
SNVT_str_asc
SNVT_str_asc
SNVT_str_asc
SNVT_config_src
SNVT_time_sec
SNVT_time_sec
SNVT_time_sec
SNVT_count

Manufacturer Network Variables


nv9

nviRawHwOutValus
UNVT_rawHwOut

nv10

nvoRawHwValues
UNVT_rawHwValues

Hardware Input/Output
All Inputs and Outputs

VAV Node Object 0

Figure 15

7 (8)

0-003-2237-0 (EN)

HARDWARE INTERFACE
TB

Term.
no.

Label
no.

Designation

Description

1
2

12
13

G
G0

24 VAC (G) input


24 VAC (G0) input

1
2
3

14
15
16

V1
V2
V3

Digital Out.: Fan Relay Load


Digital Out.: H1 Aux/Heat Relay Load (Increase)
Digital Out.: H2 Aux/Heat Relay Load (Decrease)

1
2

10
11

C1
C2

TP/FT-10 LON communication channel


TP/FT-10 LON communication channel

1
2
3

7
8
9

STAT-DATA
STAT-PWR
STAT-GND

1
2
3
4

1
2
3
4

U1
U2
U3
U4

Universal Input: Thermistor / Discrete (Duct temp. or Emergency contact)


Universal Input: Thermistor / Discrete (Occupancy sensor)
Universal Input: Thermistor / Discrete (CO2 or Outside air)
Universal Input: Resistor / Discrete (S/STAT blue and yellow)

5
6

5
6

Not used
Measurement neutral

I/STAT, M/STAT or S/STAT, white connection


I/STAT, M/STAT or S/STAT, red connection
I/STAT, M/STAT or S/STAT, black connection

DIMENSIONS

mm (in.):

197
(7.75)

63
(2.50)

159
(6.25)

Figure 16

Trademarks and registered trademarks are the property of their respective owners.
TAC Vista, TAC Menta, TAC Xenta and TAC I-Talk are registered trademarks of TAC AB. LonMark and LonWorks are registered trademarks of the Echelon Corporation.
Windows is a registered trademark of Microsoft.

tac-global.com
0-003-2237-0 (EN)

8 (8)