Sunteți pe pagina 1din 180

LV71_en_U1-U4_2005_Stempel_grau_kursiv.

FH10 Wed Feb 23 12:15:49 2005

Seite 3

ge
a
s

r
o
F

n
r
e
int

sivacon8PS
Busbar trunking
systems LDA/LDC
1100 A to 5000 A

Catalogue LV 71 2005

u
l
a

LV71_A2_en_U2.fm Seite 1 Mittwoch, 23. Februar 2005 2:01 14

Related catalogs
Low-Voltage
Controlgear for Industry
Order No.:
E86060-K1002-A101-A4-7600

Contents
LV 10

Contactors and contactor assemblies Semiconductor


controlgear, soft starters, controllers Circuit-breakers
Overload relays Load feeders Switch disconnectors
and fuses SIMIREL time, monitoring, coupling relays
and converters Control and signaling devices BETA
electrical installation technology: Selected products
SIGUARD safety systems SIDAC-T transformers
SIDAC-S power supplies ALPHA FIX terminal blocks

Power Distribution
Products and Systems for
Power Distribution
Order No.:
E86060-K1801-A101-A4-7600

LV 30

BETA protect installation equipment Communicationcapable circuit-breakers Compact circuit-breakers


(MCCB) Air circuit-breakers (ACB) SENTRIC switch
disconnectors and fuse switch disconnectors Switchgear, distribution systems and cabinets

SIVACON 8PS
Busbar Trunking Systems CD,
BD01, BD2 up to 1250 A
Order No.:
E86060-K1870-A101-A1-7600

LV 70

Busbar Trunking Units, Overview


System CD (25 A - 40 A) System BD01 (40 A - 160 A)
System BD2 (160 A - 1250 A)

SIVACON 8PS
Busbar Trunking Systems CD,
BD01, BD2 up to 1250 A
Order No.:
E86060-P1870-A101-A2-7600

LV 70 P

Price List
System CD (25 A - 40 A) System BD01 (40 A - 160 A)
System BD2 (160 A - 1250 A)

SIVACON 8PS
Busbar Trunking Systems
BD2A/BD2C, LDA/LDC
from 160 A to 5000 A
Order No.:
E86060-T1871-A101-A1-7600

LV 71 T

Technical Information
System Overview BD2A/BD2C System
LDA/LDC System Further Information

SIVACON 8PS
Busbar Trunking Systems
LXA/LXC over 800 A
Order No.:
E86060-T1872-A101-A1-7600

LV 72 T

Technical Information
System Overview LXA/LXC System
Further Information

Automation and Drives


The Offline Mall for A&D
Order No.:
E86060-D4001-A110-C3-7600

CA 01

All the products from Automation and Drives including


the products from the catalogs listed above.

A&D Mall

All the products from Automation and Drives including


the products from the catalogs listed above.

Internet:
http://www.siemens.de/automation/mall

Registered trademarks

Explanations

All product designations may be registered trademarks


or product names of Siemens AG or other supplying
companies. Third parties using these trademarks or
product names for their own purposes might infringe
upon the rights of the trademark owners.
Further information about low-voltage switchgear and
controlgear is available on the Internet at:
http://www.siemens.com/lowvoltage

Type: If a type designation contains * characters, it is not


complete and must be supplemented according to specifications in the list.
Order No.: For an order, BVP: must be placed before the
Order No. stated in the catalog (034262 --> BVP:034262).
Packaging size (PS): The packaging size defines the
number of units, sets or meters, for outer packaging.
Only the quantity defined by the packaging size or a
multiple thereof can be ordered!

SIVACON 8PS
Busbar Trunking
Systems LDA/LDC
from 1100 to 5000 A
Catalogue LV 71 2005

Introduction

Busbar Trunking Systems,


Overview

Invalid: LV 71 2004/2005
Errata Sheet for LV 71 2004/2005

Siemens AG 2005

LD Busbar Trunking System

Annex

Siemens LV 71 2005

Introduction

1/2

Welcome to Automation and Drives

1/3

Low-voltage switchgear
the basis for progressive solutions

1/4

Totally Integrated Automation


innovations for more productivity

1/6

Totally Integrated Power


energy distribution and management
from one source

1/8

SIVACON 8PS
Busbar Trunking Systems in Action

1/10

SIVACON 8PS
Engineering Tools for precisely
dimensioned, economical solutions

Siemens LV 71 2005

Welcome to
Automation and Drives

We would like to welcome you to Automation


and Drives and our comprehensive range of
products, systems, solutions and services for
production and process automation and
building technology worldwide.
With Totally Integrated Automation and
Totally Integrated Power, we deliver solution
platforms based on standards that offer you
a considerable savings potential.
Discover the world of our technology now. If
you need more detailed information, please
contact one of your regional Siemens
partners.
They will be glad to assist you.

1/2

Low-voltage switchgear and controlgear


the basis for progressive solutions

Everyday life would be unimaginable without electric power. Competence and innovations
in switching and electrical installation technology are prerequisites so that power can be
used without danger and user-friendly in industrial facilities and buildings. We have been
providing you with these prerequisites for more than 110 years and are permanently developing new features innovations which permit you to use power more safely and economically.
Low-voltage switchgear from Siemens offers a comprehensive and innovative range of
products covering switching devices for load feeders or the distribution of power, control
and signaling devices as well as complete cabinet systems. Multi-functional, uniform concepts such as Totally Integrated Power, Safety Integrated or ECOFAST additionally permit
our product portfolio to be combined into optimized systems.
All in all, we can provide you with innovative components for switching and electrical installation technology which utilize state-of-the-art features such as integration and communication as the basis for advanced and uniform solutions which provide you with many
benefits.

1/3

Totally Integrated Automation


innovations for more productivity

With the launch of Totally Integrated Automation in 1996, we


were the first ones on the market to consistently implement
the trend from equipment to an integrated automation
solution, and have continuously improved the system ever
since.
Whether your industry is process- and production-oriented or
a hybrid, Totally Integrated Automation is a unique "common
solution" platform that covers all the sectors.
Totally Integrated Automation is an integrated platform for the

ERP
Enterprise
Resource
Planning

MES
Manufacturing
Execution
Systems

Control

SIMATIC NET
Industrial
Communication

Ethernet

Ethernet

Production
Order
Management

Material
Management

Production
Operations
Recording

Equipment
Management

SINAUT Telecontrol
System

SIMATIC
Software

Industrial

Ethernet

SIMATIC
Machine Vision

Industrial
Ethernet

Industrial Wireless
Communication/
MOBIC

Safety Integrated

PROCESS FIELD

PROFIBUS

AS-Interface

GAMMA instabus

1/4

SIMATIC
PC-based Automation

Building
Technology

Micro-Automation
and
Actuator-Sensor
Interface Level

ECOFAST IP65
Decentral
Automation System

entire production line - from receiving to technical processing


and production areas to shipping. Thanks to the system-oriented
engineering environment, integrated, open communications
as well as intelligent diagnostics options, your plant now
benefits in every phase of the life cycle.
In fact, to this day we are the only company worldwide that
can offer a control system based on an integrated platform
for both the production and process industry.

Plant
Information
Management

Product Specification
Management System

Detailed
Production
Scheduling

Laboratory Information
Management System

SIMATIC IT Framework

Production Modeler

SENTRON
Circuit
Breakers

SIMATIC
Controller/
Automation
System

SIMATIC
Distributed
I/O

Field Instrumentation/
Analytics

SINUMERIK
Numeric
Control

SIMOTION
Motion Control
System

SIMODRIVE

SINAMICS

SIMATIC HMI
Human Machine
Interface

SIMATIC PCS 7
Process Control
System

Sensor
Technology
IQ-Sense

HART
PROFIBUS PA

SIMOCODE-DP
Motor
Protection
and Control

Drive Systems

1/5

Totally Integrated Power


energy distribution and management
from one source

Totally Integrated Power by Siemens offers integrated


solutions for energy distribution in functional and industrial
buildings covering everything from medium-high voltage to
power outlets.
Totally Integrated Power is based on integration in
planning and configuration as well as coordinated products
and systems. In addition, it features communications and
software modules for connecting power distribution systems
to industrial automation and building automation, thereby
offering a substantial savings potential.

Communications

HMI

Process/production
automation

Load
management

U
I
cos o
P
W

PROCESS FIELD BUS

Products and systems

110 kV

Planning and configuration

1/6

Graphs

Prognoses

Maintenance
Substation
Distribution
Maintenance
task

Message/
error
management

Selective
protection

Protocols

Power
quality

DATE:
EMPLOYEE

Cost center

COST CENTER
PAY PERIOD BEGINNING
PAY PERIOD ENDING

DATE
SUN

MON

TUE

WED

THUR

FRI

SAT

SUN

TOTAL

IN
OUT
IN
OUT
OVERTIME

TOTAL HOURS
DATE
SUN

MON

TUE

WED

THUR

FRI

SUN

MON

TUE

WED

THUR

FRI

SAT

SUN

TOTAL

IN

Building
automation

OUT
IN

Hall 1
Distribution 3
Infeed II

Air conditioning system


checkup
Replacing circuit
breaker contacts
Replacing meters

OUT
OVERTIME

TOTAL HOURS

central ON
OFF
local ON
OFF
tripped

DATE
SAT

SUN

TOTAL

IN
OUT
IN
OUT
OVERTIME

TOTAL HOURS
CODES
V=VACATION
H=HOLIDAY
S=SICK

REGULAR

HOLIDAY

OTHER

OVER THE HOURS


TIME & ONE-HALF

SICK

VACATION

instabus EIB

1/7

SIVACON 8PS
Busbar Trunking Systems in Action

Busbar trunking systems in the low-voltge range


perform the safe and reliable transmission and
distribution of electrical power from transformer
via main distribution board and sub-distribution
board right to the load. Siemens busbar trunking
systems are the complete and efficient answer
in this area:
The CD system
for 25 A to 40 A
The BD01 system for 40 A to 160 A
The BD2 system
for 160 A to 1250 A
The PEC system
for 800 A to 6000 A
The LD system
for 1100 A to 5000 A
The LX system
for 800 A to 6300 A

The BD 01 system is quick to install and


ideally suited for use in workshops and
trade premises, as here, at a photographers.

Alle these systems are Type-tested LV switchgear assemblies (TTA) to IEC 60 439-1 and -2.
This ensures that they offer a standard of safety
and reliability that meets the particularly high
performance expectations of automated production and for building services provision.
Performance characteristics:
Clear network structure
Unproblematic retrofitting in the event of load
changes
Low operating costs due to uninterrupted serviceability
Simple planning and installation
Room-covering systems for lighting installations and small loads
The CD system (up to 40 A) allows you to supply
lighting installations covering the whole expanse of, say, furniture showrooms, supermarkets
or greenhouses with power, and also provides
the means to easily fix them in position.
Due to its pleasing appearance, the equipment
is well suited for use in sales rooms visited by
the public. On the other hand, its high degree of
protection, to IP54, allows the CD system to be
used even in harsh environments.
The power source for loads with no fixed
location
The BD01 system is ideally suited for the power
supply (up to 160 A) in workshops and trade
premises. The trunking units are easy and quick
to put together. The anti-rotation feature on the
tap-off units makes sure that the units are
correctly fitted and allows for easy retrofitting
even while the production is running.
Other benefits: minimum stock holding and uncomplicated planning due to one standard
frame size for five different current ratings.

1/8

The ideal system for production lines


needing a great deal of power is the
LD system up to 5000 A.

In the petrochemical industry, it is the PEC system that provides


reliable and fault-free power supply.

Universal power distribution


The BD2 system (up to 1250 A) can supply
power to medium-size loads in buildings and in
all industrial applications. Prefabricated tap-off
units fitted with many differing component
combinations make this equipment universally
applicable. Two standard frame sizes covering
all current ratings simplify stock keeping and
planning.
Safe and reliable power transmission in the
petrochemical industry
The PEC resin-insulated system, up to 6000 A,
has a high degree of insulation protection and
thus an enormous resistance to external interference factors. This ensures safe and reliable
transport of power even in rough weather or in
highly dust and dirt and corrosion polluted
industrial environments. Typical applications of
this system is the petrochemical industry, waste
incinerators and power stations.
Siemens offers modular component cabinets for indication, control and monitoring of the
flow of power through busbar trunking systems. These cabinets are equipped with bus
interfaces, control circuit devices and power meters.

The LX busbar trunking system is the perfect equipment for multistorey buildings where large quantities of power need to be transported, uninfluenced by the mounting position of the system.

High system serviceability in production


The louvred LD busbar trunking system, up to
5000 A, is the system for transporting current in
production lines with a large energy requirement, such as in the automotive industry. A
separate PE busbar ensures that the protective
device in such a system responds reliably even
if the current paths are relatively long. The high
short-circuit rating allows medium-voltage
switches to be used as protective elements for
the transmission of power between transformer
and main circuit-breaker. Tap-off units up to
1250 A available as standard.
Flexible power distribution in multi-storey
buildings
The LX sandwich-style system, up to 6300 A, is
used where large quantities of power need to be
transported, uninfluenced by the mounting position of the system.
Conductor configurations with the PE conductor
insulated along its entire length, and a doublesize neutral can ensure the interference-free distribution of power in places such as radio
stations, computer centres or at internet
providers. The system is protected to IP54 as
standard, and tap-off units up to 1250 A available as standard.

1/9

SIVACON 8PS - Engineering Tools for


precisely dimensioned, economical solutions

Engineering tools from Siemens help generate


precisely dimensioned and economical planning and design solutions, even for complex applications.
MatSelect
Using MatSelect, product and material data can
be administered with self designed or
standardised classification systems. It has interfaces to Eldanorm, Datanorm, ASCII format and
ProPlan.
NetPlan
Planning software for power flow, short-circuit
calculation and device dimensioning with selectivity analysis and protective against electric
shock of low-voltage networks, available in
English, German, French and Italian.
NetSelect
Selection software for protective switches to enable star networks to be correctly dimensioned;
available in several languages.

NetPlan enables you to graphically represent the network and to


calculate the load flow and the prospective one-pole to all-pole short
circuitcurrent/load.

BusbarSelect
Selection aid for generating quotations, invitations to tender and orders for busbar trunking
systems up to 1250 A; available in several
languages.
Quotation texts
Prepared texts (in German) for generating
customer specifications in the formats: Architext
excellent, GAEB 81 and Word 97.

Should you have any queries concerning installation, functionality or application options
please mail us at
sbts.tool_support@siemens.com
We will be pleased to assist you.

In BusbarSelect, you select the trunking units for your system from a menu,
and then transfer them into an order or quotation list.

1/10

Busbar Trunking Systems,


Overview

2/2

Technical Overview

2/4

System Overview

Siemens LV 71 2005

Busbar Trunking Systems, Overview


Technical Overview

Busbar trunking systems

CD

Rated
current

Rated operational
voltage

Frequency

Number of
active conductors

Degree of
protection

Ambient
temperature
min./max.
C

V AC

Hz

30
40
2 25

400

50 ... 60

2, 3, 4, 2 4
(PE = enclosure)

IP54

5/+40

40
63
100
125
160

400

50 ... 60

4
(PE = enclosure)

IP54

5/+40

160 ... 400


500 ... 1250

690

50 ... 60

IP52,
IP54 with
accessories,
IP55 on request

5/+40

1100 ... 4000


2000 ... 5000

1000

50 ... 60

4 or 5

IP34,
IP54

5/+40

800 ... 4500


1000 ... 6300

690

50 ... 60

3, 4, 5, 6
(PE = enclosure)

IP54,
IP55 with
accessories

5/+40

NSV0_00201

2
BD01

NSV0_00241

BD2A
BD2C

NSV0_00421

LDA1 LDA8
LDC2 LDC8

NSV0_00681

LXA01 LXA10
LXC01 LXC10

NSV0_00321

2/2

Siemens LV 71 2005

Busbar Trunking Systems, Overview


Technical Overview

Mounting
position

Length

Tap-off points

Tap-off units

Material

m
Edgewise

2
3

Combustive
energy
kWh/m

On one side:
every 0.5 or 1 m
On both sides:
every 0.5 or 1 m

Up to 16 A

Insulated
Cu conductors,
painted sheet
steel housing

0.1 ... 0.48

2
Edgewise,
flat
(tap-off points
downwards)

2
3

On one side:
every 0.5 or 1 m

Up to 63 A

Insulated
Al or Cu
conductors,
painted sheet
steel housing

0.76

Can be combined with networkable


tap-off units for lighting control systems

Edgewise,
flat
and vertical

0.5 ... 3.25

Without,
on both sides:
every 0.25 or
0.5 m offset

Up to 400 A

Al or Cu busbars,
painted sheet
steel housing

0.6 ... 0.67


(without tap-off
points)

Can be combined with networkable


tap-off units for lighting control systems, remote switching and load monitoring

Horizontal,
edgewise
and vertical

0.5 ... 3.2

Without,
on one side:
every 1 m,
on both sides:
every 1 m

Up to 1250 A

Insulated
Al or Cu busbars,
painted sheet
steel housing

4.16 ... 8.83


(without tap-off
points)

Information about the LD and


LX systems: from your
Siemens sales outlet.

Without,
on one side:
every 0.5 m,
on both sides:
every 0.5 m

Up to 1250 A

Horizontal,
edgewise
and vertical

0.35 ... 3

Can be combined with networkable


tap-off units for remote switching and
load monitoring

Insulated
Al or Cu busbars,
painted aluminium housing

1.95 ... 11.07


(without tap-off
points)

Siemens LV 71 2005

2/3

Busbar Trunking Systems, Overview


System Overview

B
0

-K

D
B

2
6

1
B

B
0

-K

D
B

NSV0_00682

2/4

Siemens LV 71 2005

Busbar Trunking Systems, Overview


System Overview
Up to 40 A
CD system
Reduced planning costs by simplified engineering
Quick-release plug-in connection for fast assembly
Tap-off points on both sides for optimized utilization of the busbar
Even electrical loading of the CD system conductors achieved by connecting an equal number of tap-off plugs to each individual phase
Versatility through high degree of protection to IP54 of the standard
version
Tap-off plugs allow fast, flexible load relocation (even on live sytems).

Up to 6300 A
1

PEC system
The busbar trunking system for power transmission under extreme environmental conditions (IP68).
Detailed information about this system is available from your Siemens sales
outlet.

Up to 160 A

Networkable busbar trunking system


Networkable function expansions for combination with known tap-off
units
Applications:
large area lighting control systems
remote switching and signalling in industrial applications
load monitoring of decentral power tap-offs
EIB, AS-i and PROFIBUS bus systems
Quick, straightforward planning
Flexible with expansion and modification
Module system
Can be retrofitted to existing installations
Simple contact establishment of bus line with insulation displacement
connection feature
Can be used with the BD01, BD2, LD, and LX systems

Up to 1250 A
3

Design software
BusbarSelect
Design software for busbar trunking systems up to 1250 A
This CD-ROM is available free of charge from your Siemens sales outlet.

Technical Information
LV 71.T
Planning guide
SIVACON 8PS
Busbar trunking systems BD2A/BD2C and LDA/LDC from 160 A to 5000 A
LV72.T
Planning guide
SIVACON 8PS
Busbar trunking systems LXA/LXC over 800 A
These planning aids are available from your Siemens sales outlet.

a Catalog LV 70

Up to 5000 A
LD system
The busbar trunking system for optimized power distribution in industry.
Reliable, safe operation
Time-saving, cost-efficient assembly
Space-saving compact construction type up to 5000 A in an enclosure
Plug-in tap-off units up to 1250 A
Type-tested connection to service distribution boards and transformers

a Catalog LV 70

BD2 system
Quick, straightforward planning
Time-saving, cost-efficient assembly
Reliable, safe operation
Flexible modular system with simple solutions for every application
Early planning of power distribution possible without precise knowledge of
consumer locations
Fast operational readiness through quick, easy assembly
High degree of protection to IP54 for use in harsh industrial environments
Innovative construction:
No compensating units for expansion compensation required.

Catalog LV 72

a Catalog LV 70

BD01 system
Flexible power supply
Junction units for changes in direction
Quick, straightforward planning
Time-saving assembly
Reliable mechanical and electrical connections
High level of stability, low weight
Positive opening and closing of tap-off points
Versatile tap-off units
Few basic elements
Modular system reduces stock-holding
High degree of protection to IP54 with tap-off points at sides and bottom
for extreme ambient conditions, otherwise IP50.

LX system
The busbar trunking system for power transmission and distribution in
buildings.
Detailed information about this system is available from your Siemens sales
outlet.

4
Leaflet
E20001-A220-P309
SIVACON 8PS
Safe and flexible power distribution up to 6300 A

a Chapter 3

Siemens LV 71 2005

2/5

Busbar Trunking Systems, Overview


Notes

2/6

Siemens LV 71 2005

LD Busbar Trunking System

3/2

System overview

3/6
3/10
3/22
3/28
3/40
3/41
3/46

Selection and ordering data


Straight trunking units
Branch and junction units
Distribution board connection units
Connection units
Reduction units
Tap-off units
Accessories

3/48
3/60
3/61
3/64

Technical data
Trunking units
Connection units
Tap-off units
Weights

3/82
3/91
3/95
3/99
3/106
3/112

Engineering
Basics
Dimensioning of busbar runs,
Production of parts lists
Incoming connections
Fire barrier
Expansion compensation and fixed point
Examples
Tap-offs
Special cases

3/118
3/119
3/140
3/146

Dimensions
Straight trunking units
Connection units
Tap-off units
Accessories

3/68
3/77

Siemens LV 71 2005

LD Busbar Trunking System


System Overview

3/2

Siemens LV 71 2005

LD Busbar Trunking System


System Overview
Straight trunking units

Without or with fire barrier,


fire resistance class S 120 to DIN 4102 Part 9

Tap-off units
Modification possible while the system is energized
Leading PE(N) connecting contact during mounting

Degree of protection IP34 and IP54

IP20 touch protection of the contact assembly during


fitting and removing

4- and 5-conductor systems


Standard lengths of 1.6 m/2.4 m/3.2 m
Optional lengths of 0.5 ... 3..19 m
for horizontal and vertical installation

Coding brackets
Sealing
Cable entry at the side with additional cable
compartment

Straight trunking units with tap-off points


Tap-off points above, below or at both sides

Safety by specified sequence of fitting/removal

Coding brackets as
protection against incorrect fitting
(key-lock principle)
protection against confusing tap-off units
(4/5-conductor system)
sliding contacts for PE in 5-conductor systems

Sheet steel enclosure with IP30 or IP54 degree of


protection resulting from additional cover
Page 3/35

IP20 touch protection with the tap-off point open


Page 3/6

Distribution board connection units

Connection/feeder units

For distribution board connection to


Siemens SIVACON PV Power Distribution System
from above
from below

Incoming transformer connection, enclosed


for rated currents from 1100 ... 5000 A
connecting lugs for all standard clearances
phase sequence as required

Page 3/22

Incoming distribution board connection


for rated currents from 1100 ... 5000 A
phase sequence as required

Accessories

3
1

End flanges

Incoming cable connection


for rated currents from 1100 ... 2500 A
cable entry via cable grommets with cable supporting
rail

Distribution board blank plates


Protective sleeves
Fixing brackets
Suspension brackets

Page 3/28

Branch and junction units

Torque spanner

Page 3/40

Flexible engineering for matching to building


construction, with
elbow (L unit flat), offset elbow
knee (L unit edgewise), offset knee
Z unit
T unit
U unit
Without or with fire barrier
Page 3/10

Siemens LV 71 2005

3/3

LD Busbar Trunking System


System Overview
Type key
Straight trunking units, junction units and distribution board connection units
Rated current le [A]

Version

< 1.3 m

> 1.3 m

Code
Horizontal Horizontal No.
edgewise flat
and
vertical

Al

Al

Al

IP31

IP54

Horizontal edgewise
including offsets

Cu

1100

Cu

950

IP31/IP54

Cu

Al

900

5-conductor

1/

1200

1600 2600 1250 2100 1200 2000 1000 1550

2000

1700

1500

1200

IP34 (31)1)

2500

2100

1800

1700

IP54

1250 2000 1100 1650 1000 1600 750

3000 3400 2300 2700 2000 2600 1800 2000

3700 4400 2800 3500 2400 3200 2200 2600

4000 5000 3400 4250 2700 3600 2350 3000

Degree of protection

Fire barrier

Conductor material

4-conductor

6
N/PEN

Cu

700

Al

Cu

120 A

LDA 1 LDA 3
LDC 2 LDC 3

120 B

LDA 4 LDA 8
LDC 6 LDC 8

Fire barrier

Notes:

Positioning of
(X*, Y*, Z*)
(see Engineering)

N/PEN = 1/2 L,
possible from LD.4... to LD.8...

LD

Type

-.... +LD-L

Type suffix

LD connection units2)
Rated current le [A]

Version

IP31
Horizontal/
edgewise
Al

Cu

System
LDA

1100

Code
No.
LDC

2000

1600

2600

2000

2500

3400

3700

4400

4000

5000

1/

Al

Cu

IP34 (31) 3)

Type lug clearance [mm]

Conductor material

Notes:

State of
delivery

Adjustable
on site

150 ... 160

165 ... 180

190 ... 280

285 ... 380

450 ... 600

610 ... 750

PEN(N)-L2
200 ... 300

PEN(N)-L2
200 ... 400

450 ... 600

605 ... 750

PEN(N)-L3(1)
150 ... 250

PEN(N)-L3(1)
250 ... 350

3
1/

N/PEN = 2 L,
possible from LD.4... to LD.8...
4

LD

Type

Siemens LV 71 2005

3000

3/4

5-conductor

Degree of protection

1) IP31 for horizontal flat units.


2) Horizontal/edgewise
with connecting lugs below.
3) IP54 on request.

4-conductor

6
N/PEN

1250

-.... +AS

LD Busbar Trunking System


System Overview
Important notes
Please note the following for selection and ordering:
Dimensions

Type suffix for fire barrier

Length details in the selection tables are quoted in metres


(m). Optional lengths may be chosen in 0.01 m stages.

For the fire barrier type suffix, the distance from the hook
end (+LD-....-X*) or bolt end (+LD-L....-Y*) to the center of
the fire barrier must be entered in metres (m).
The minimum distance from the hook or bolt end to the
center of the fire barrier must be observed.

Type
All types designated with * must be completed by the corresponding dimension. Add the type suffix to the type if
appropriate.
Type suffix
The type suffixes, e. g. fixed point, fire barrier, flange plate, and phase sequence, must always be quoted together
with the type.

Type key
The LDA/LDC type keys are shown on the opposite page.
For selecting complete types, these type keys must be
transferred to the selection tables.
In special cases, the type key is to be found on the selection page itself: for example for tap-off units and cable
connection units.

Legend
Dimension Description

Dimension Description

Length of the fitted unit (straight)

For T units: Length of the basic trunking unit

AD

Distance between the center of tap-off point


and the trunking unit end at the hook

TX

Distance from center of the T branch to the


unit end at the hook

AD min

Minimum distance between the center of


the tap-off point and the trunking unit end

TY

Distance from the center of the T branch to


unit end at the bolt

AX

Unit fitted: Length of the X leg

Optional length

AY

Unit fitted: Length of the Y leg

Length of the X leg

Length of expansion compensation units

Length of the Y leg

DX

Distance between the center of the expansion compensation unit and the trunking
unit end at the hook

Length of the Z leg

Standard length

Order number supplement


For an order, BVP: mut be placed before the order
number stated in the catalog.
Example: the order number in the catalog is 034262.
When placing an order, please write BVP:034262.

Siemens LV 71 2005

3/5

LD Busbar Trunking System


Selection and Ordering Data
Straight trunking units for horizontal installation without tap-off points
Length
S/W/D
m

Type

Type suffix

Type suffix
Fire barrier

Fixed point

Standard lengths

3.2

LD.....-3,2

+LD-L....-X*

+LD-FP

2.4

LD.....-2,4

+LD-L....-X*

+LD-FP

1.6

LD.....-1,6

+LD-L....-X*

+LD-FP

Optional lengths

0.50 ... 0.89

LD.....-1W*

0.90 ... 1.59

LD.....-2W*

+LD-L....-X*

+LD-FP
+LD-FP

1.61 ... 2.39

LD.....-3W*

+LD-L....-X*

+LD-FP

2.41 ... 3.19

LD.....-4W*

+LD-L....-X*

+LD-FP

Optional lengths with double bolt

0.50 ... 0.89

LD.....-J-1W*

0.90 ... 1.59

LD.....-J-2W*

+LD-L....-Y*

+LD-FP
+LD-FP

1.60 ... 2.39

LD.....-J-3W*

+LD-L....-Y*

+LD-FP

2.40 ... 3.20

LD.....-J-4W*

+LD-L....-Y*

+LD-FP

1.20
DX = 0.6
Expansion =

LD.....-D

Expansion compensation

Dx
Fire barrier note:
Fire barrier can be used for LD.1...- to LD.7...
from 0.92 m (0.96 m for double bolt) and for LD.8...from 1.12 m (1.16 m for double bolt) length.

3/6

Siemens LV 71 2005

Complete ordering details:


See Type key/Important notes
(System overview, pages 3/4 and 3/5)
Examples: LDA1423-2W1,4,
+LD-L120A-X0,54

LD Busbar Trunking System


Selection and Ordering Data
Straight trunking units for horizontal installation with tap-off points
Length
W
m

Position1) of the
tap-off points
AD (m)

Type

Type suffix

Fixed point

above

LD.....-K-3,2-3AD

+LD-FP

bottom

LD.....-K-3,2-3ADU

+LD-FP

above or bottom

LD.....-K-3,2-3ADO+U

+LD-FP

above

LD.....-K-3,2-2AD

+LD-FP

bottom

LD.....-K-3,2-2ADU

+LD-FP

above or bottom

LD.....-K-3,2-2ADO+U

+LD-FP

Standard lengths with 3 tap-off points


3.2

0.6 + 1.6 + 2.6

AD

Standard lengths with 2 tap-off points


3.2

AD

mi

0.8 + 2.4

AD

Standard lengths with 1 tap-off point

3.2

2.4
above

LD..-K-3,2-AD2,4

+LD-FP

bottom

LD..-K-3,2-ADU2,4

+LD-FP

above or bottom

LD..-K-3,2-ADO+U2,4

+LD-FP

above

LD..-K-3,2-AD0,8

+LD-FP

bottom

LD..-K-3,2-ADU0,8

+LD-FP

above or bottom

LD..-K-3,2-ADO+U0,8

+LD-FP

AD

3.2

0.8

AD
1) Position of the tap-off point ...-AD(U) (O+U)* from the hook end.

Complete ordering details:


See Type key/Important notes
(System overview, pages 3/4 and 3/5)
Examples: LDA1423-K-3,2-3AD
LDA4623-K-3,2-2ADU

Siemens LV 71 2005

3/7

LD Busbar Trunking System


Selection and Ordering Data
Straight trunking units for horizontal installation with tap-off points
Length
W
m

Position1) of the
tap-off points
AD (m)

Type

Type suffix

Fixed point

Optional lengths with 2 tap-off points


Minimum distance between the tap-off
point and the trunking unit end AD 0.6 m
2.20 ... 2.40

above

LD.....-K-2W*-2AD*

+LD-FP

bottom

LD.....-K-2W*-2ADU*

+LD-FP

above or bottom

LD.....-K-2W*-2ADO+U*

+LD-FP

first fixed at 0.6,


second variable at
1.4 ... 1.8
in stages of 0.2

AD

mi

AD

2.41 ... 3.20

above

LD.....-K-3W*-2AD*

+LD-FP

bottom

LD.....-K-3W*-2ADU*

+LD-FP

above or bottom

LD.....-K-3W*-2ADO+U*

+LD-FP

above

LD.....-K-1W*-AD*

+LD-FP

bottom

LD.....-K-1W*-ADU*

+LD-FP

above or bottom

LD.....-K-1W*-ADO+U*

+LD-FP

first fixed at 0.6,


second variable at
1.4 ... 2.6
in stages of 0.2

Optional lengths with 1 tap-off point


1.20 ... 1.60

variable at
0.6 ... 1.0
in stages of 0.2

AD

1.61 ... 2.40

above

LD.....-K-2W*-AD*

+LD-FP

bottom

LD.....-K-2W*-ADU*

+LD-FP

above or bottom

LD.....-K-2W*-ADO+U*

+LD-FP

variable at
0.6 ... 1.8
in stages of 0.2
2.41 ... 3.20

above

LD.....-K-3W*-AD*

+LD-FP

bottom

LD.....-K-3W*-ADU*

+LD-FP

above or bottom

LD.....-K-3W*-ADO+U*

+LD-FP

variable at
0.6 ... 2.6
in stages of 0.2
1) Position of the tap-off point ...-AD(U) (O+U)* from the hook end.

3/8

Siemens LV 71 2005

Complete ordering details:


See Type key/Important notes
(System overview, pages 3/4 and 3/5)
Examples: LDA1423-K-2W2,20-ADU1,4 +LD-FP
LDA4623-K-3W2,60-AD1,6

LD Busbar Trunking System


Selection and Ordering Data
Straight trunking units for vertical installation, always with expansion
and fixed point
Length
S/W
m

Position1) of the
tap-off points
AD (m)

Type

Type suffix
Fire barrier

Standard lengths
3.2

LD.....-V-3,2

+LD-L....-X*

2.4

LD.....-V-2,4

+LD-L....-X*

2.29 ... 2.80

LD.....-V-1W*

+LD-L....-X*

2.81 ... 3.00

LD.....-V-2W*

+LD-L....-X*

3.01 ... 3.19

LD.....-V-3W*

+LD-L....-X*

Optional lengths

Standard lengths with 1 tap-off point


above

3.2

1.4

LD.....-K-V-3,2-AD1,4

+LD-L....-X*

3.2

1.8

LD.....-K-V-3,2-AD1,8

+LD-L....-X*

2.4

1.4

LD.....-K-V-2,4-AD1,4

AD
Optional lengths with 1 tap-off point
above
2.29 ... 2.80

W
2.81 ... 3.00
3.01 ... 3.19

AD

1.4

LD.....-K-V-1W*-AD1,4

1.8

LD.....-K-V-1W*-AD1,8

+LD-L....-X*

1.4

LD.....-K-V-2W*-AD1,4

1.8

LD.....-K-V-2W*-AD1,8

1.4

LD.....-K-V-3W*-AD1,4

+LD-L....-X*

1.8

LD.....-K-V-3W*-AD1,8

+LD-L....-X*

+LD-L....-X*

1) Position of the tap-off point ...-AD(U) (O+U)* from the hook end.

Fire barrier note:


Minimum fire barrier dimensions owing to integrated expansion compensation:
For LD.1...- to LD.8...-: X 1,10.
For AD 1.8 trunking units, the fire barrier is possiblefrom X 2.45 on.
For AD 1.4 trunking units, the fire barrier is possible from X 2.05 on.

Complete ordering details:


See Type key/Important notes
(System overview, pages 3/4 and 3/5)
Examples: LDA1423-V-1W2,60 +LD-L120A-X1,8
LDA4623-K-V-2W2,90-AD1,4

Siemens LV 71 2005

3/9

LD Busbar Trunking System


Selection and Ordering Data
Junction units for horizontal installation
Length

Type

Type suffix
Fire barrier

X 0.5/Y 0.5

LD.....-LR

X 0.51 ... 1.24/Y 0.5

LD.....-LR-X*

+LD-L....-X*

X 0.5/Y 0.51 ... 1.24

LD.....-LR-Y*

+LD-L....-Y*

X/Y 0.51 ... 1.24

LD.....-LR-X*/Y*

+LD-L....-X*
+LD-L....-Y*

X 0.5/Y 0.5

LD.....-LL

X 0.51 ... 1.24/Y 0.5

LD.....-LL-X*

+LD-L....-X*

X 0.5/Y 0.51 ... 1.24

LD.....-LL-Y*

+LD-L....-Y*

X/Y 0.51 ... 1.24

LD.....-LL-X*/Y*

+LD-L....-X*
+LD-L....-Y*

X 0.5/Y 0.5
Z 0.36 ... 0.99 with LD.1 to LD.3
Z 0.48 ... 0.99 with LD.4 to LD.8

LD.....-ZR-Z*

X 0.5/Y 0.5
Z 0.36 ... 0.99 with LD.1 to LD.3
Z 0.48 ... 0.99 with LD.4 to LD.8

LD.....-ZL-Z*

Elbow trunking units


right
Y

left

Z trunking units, flat


right

X
Y

left

Fire barrier note:


Fire barrier possible with optional length from
X 0.86 or Y 0.90 with LD.1...- to LD.3...X 0.92 or Y 0.96 with LD.4...- to LD.7...X 1.12 or Y 1.16 with LD.8...-

3/10

Siemens LV 71 2005

Complete ordering details:


See Type key/Important notes
(System overview, pages 3/4 and 3/5)
Examples: LDA1423-LR-X1,22 +LD-L120A-X0,65
LDA4623-ZL-Z0,84

LD Busbar Trunking System


Selection and Ordering Data
Junction units for horizontal installation
Length

Type

X 0.5/Y 0.5
Z 0.46 ... 0.99 with LD.1 to LD.3
Z 0.58 ... 0.99 with LD.4 to LD.8

LD.....-UR-Z*

X 0.5/Y 0.5
Z 0.46 ... 0.99 with LD.1 to LD.3
Z 0.58 ... 0.99 with LD.4 to LD.8

LD.....-UL-Z*

Type suffix
Fire barrier

U trunking units, flat


right

left

X
Complete ordering details:
See Type key/Important notes
(System overview, pages 3/4 and 3/5)
Examples: LDA4623-UL-Z0,84

Siemens LV 71 2005

3/11

LD Busbar Trunking System


Selection and Ordering Data
Junction units for horizontal and vertical installation
Length

Type

Type suffix
Fire barrier

X 0.5/Y 0.5

LD.....-LV

X 0.51 ... 1.24/Y 0.5

LD.....-LV-X*

+LD-L....-X*

X 0.5/Y 0.51 ... 1.24

LD.....-LV-Y*

+LD-L....-Y*

X/Y 0.51 ... 1.24

LD.....-LV-X*/Y*

+LD-L....-X*
+LD-L....-Y*

X 0.5/Y 0.5

LD.....-LH

X 0.51 ... 1.24/Y 0.5

LD.....-LH-X*

+LD-L....-X*

X 0.5/Y 0.51 ... 1.24

LD.....-LH-Y*

+LD-L....-Y*

X/Y 0.51 ... 1.24

LD.....-LH-X*/Y*

+LD-L....-X*
+LD-L....-Y*

X 0.5/Y 0.5
Z 0.36 ... 0.99

LD.....-ZV-Z*

X 0.5/Y 0.5
Z 0.36 ... 0.99

LD.....-ZH-Z*

Knee trunking units

front

X
rear

X
Y

Z trunking units, edgewise


front

X
rear

Fire barrier note:


Fire barrier possible for elbow units with optional length from
X 0.86 or Y 0.90 with LD.1...- to LD.7...X 1.06 or Y 1.10 with LD.8...-

3/12

Siemens LV 71 2005

Complete ordering details:


See Type key/Important notes
(System overview, pages 3/4 and 3/5)
Examples: LDA1423-LV-X1,22 +LD-L120A-X0,65

LD Busbar Trunking System


Selection and Ordering Data
Junction units for horizontal and vertical installation
Length

Type

X 0.5/Y 0.5
Z 0.5 ... 0.99

LD.....-UV-Z*

X 0.5/Y 0.5
Z 0.5 ... 0.99

LD.....-UH-Z*

Type suffix
Fire barrier

U trunking units, edgewise


front

rear

Y
Complete ordering details:
See Type key/Important notes
(System overview, pages 3/4 and 3/5)
Examples: LDA1423-UV-Z0,89

Siemens LV 71 2005

3/13

LD Busbar Trunking System


Selection and Ordering Data
Junction units for horizontal and vertical installation
Length

Type

Type suffix
Fire barrier

X 0.5/Y 0.5

LD.....-LVR

X 0.51 ... 1.24/Y 0.5

LD.....-LVR-X*

+LD-L....-X*

X 0.5/Y 0.51 ... 1.24

LD.....-LVR-Y*

+LD-L....-Y*

X/Y 0.51 ... 1.24

LD.....-LVR-X*/Y*

+LD-L....-X*
+LD-L....-Y*

X 0.5/Y 0.5
Z 0.36 ... 1.30 with LD.1 to LD.3
Z 0.42 ... 1.30 with LD.4 to LD.8

LD.....-LVR-Z*

+LD-L....-Z*

X 0.5/Y 0.5

LD.....-LHR

X 0.51 ... 1.24/Y 0.5

LD.....-LHR-X*

+LD-L....-X*

X 0.5/Y 0.51 ... 1.24

LD.....-LHR-Y*

+LD-L....-Y*

X/Y 0.51 ... 1.24

LD.....-LHR-X*/Y*

+LD-L....-X*
+LD-L....-Y*

X 0.5/Y 0.5
Z 0.36 ... 1.30 with LD.1 to LD.3
Z 0.42 ... 1.30 with LD.4 to LD.8

LD.....-LHR-Z*

+LD-L....-Z*

Offset knee trunking units

front right

front right with Z dimension

3
X

rear right

rear right with Z dimension

Fire barrier note:


Fire barrier possible for offset elbow units with optional length from
X 0.86 or Y 0.90 or Z 0.84 with LD.1...- to LD.3...X 0.92 or Y 0.90 or Z 0.90 with LD.4...- to LD.7...X 1.12 or Y 1.10 or Z 1.10 with LD.8...-

3/14

Siemens LV 71 2005

Complete ordering details:


See Type key/Important notes
(System overview, pages 3/4 and 3/5)
Examples: LDA1423-LVR-X1,22 +LD-L120A-X0,65
LDA4623-LHR

LD Busbar Trunking System


Selection and Ordering Data
Junction units for horizontal and vertical installation
Length

Type

Type suffix
Fire barrier

X 0.5/Y 0.5

LD.....-LVL

X 0.51 ... 1.24/Y 0.5

LD.....-LVL-X*

+LD-L....-X*

X 0.5/Y 0.51 ... 1.24

LD.....-LVL-Y*

+LD-L....-Y*

X/Y 0.51 ... 1.24

LD.....-LVL-X*/Y*

+LD-L....-X*
+LD-L....-Y*

X 0,5/Y 0,5
Z 0,36 ... 1,30 with LD.1 to LD.3
Z 0,42 ... 1,30 with LD.4 to LD.8

LD.....-LVL-Z*

+LD-L....-Z*

X 0.5/Y 0.5

LD.....-LHL

X 0.51 ... 1.24/Y 0.5

LD.....-LHL-X*

+LD-L....-X*

X 0.5/Y 0.51 ... 1.24

LD.....-LHL-Y*

+LD-L....-Y*

X/Y 0.51 to 1.24

LD.....-LHL-X*/Y*

+LD-L....-X*
+LD-L....-Y*

X 0.5/Y 0.5
Z 0.36 ... 1.30 with LD.1 to LD.3
Z 0.42 ... 1.30 with LD.4 to LD.8

LD.....-LHL-Z*

+LD-L....-Z*

Offset knee trunking units

front left

front left with Z dimension

rear left

rear left with Z dimension

Fire barrier note:


Fire barrier possible for offset elbow units with optional length from
X 0.86 or Y 0.90 or Z 0.84 with LD.1...- to LD.3...X 0.92 or Y 0.90 or Z 0.90 with LD.4...- to LD.7...X 1.12 or Y 1.10 or Z 1.10 with LD.8...-

Complete ordering details:


See Type key/Important notes
(System overview, pages 3/4 and 3/5)
Examples: LDA1423-LHL-X1,22 +LD-L120A-X0,65
LDA4623-LVL
Siemens LV 71 2005

3/15

LD Busbar Trunking System


Selection and Ordering Data
Junction units for horizontal and vertical installation
Length

Type

Type suffix
Fire barrier

X 0.5/Y0.5

LD.....-LRV

X 0.51 ... 1.24/Y 0.5

LD.....-LRV-X*

+LD-L....-X*

X 0.5/Y0.51 ... 1.24

LD.....-LRV-Y*

+LD-L....-Y*

X/Y 0.51 ... 1.24

LD.....-LRV-X*/Y*

+LD-L....-X*
+LD-L....-Y*

X 0.5/Y 0.5
Z 0.36 ... 1.30 with LD.1 to LD.3
Z 0.42 ... 1.30 with LD.4 to LD.8

LD.....-LRV-Z*

+LD-L....-Z*

X 0.5/Y 0.5

LD.....-LRH

X 0.51 ... 1.24/Y 0.5

LD.....-LRH-X*

+LD-L....-X*

X 0.5/Y 0.51 ... 1.24

LD.....-LRH-Y*

+LD-L....-Y*

X/Y 0.51 ... 1.24

LD.....-LRH-X*/Y*

+LD-L....-X*
+LD-L....-Y*

X 0.5/Y 0.5
Z 0.36 ... 1.30 with LD.1 to LD.3
Z 0.42 ... 1.30 with LD.4 to LD.8

LD.....-LRH-Z*

+LD-L....-Z*

Offset elbow trunking units


right front

right front with Z dimension

3
X
right rear

right rear with Z dimension

Fire barrier note:


Fire barrier possible for offset elbow units with optional length from
X 0.86 or Y 0.90 or Z 0.84 with LD.1...- to LD.3...X 0.86 or Y 0.96 or Z 0.90 with LD.4...- to LD.7...X 1.06 or Y 1.16 or Z 1.10 with LD.8...-

3/16

Siemens LV 71 2005

Complete ordering details:


See Type key/Important notes
(System overview, pages 3/4 and 3/5)
Examples: LDA1423-LRV-X1,22 +LD-L120A-X0,65
LDA4623-LRH

LD Busbar Trunking System


Selection and Ordering Data
Junction units for horizontal and vertical installation
Length

Type

Type suffix
Fire barrier

X 0.5/Y 0.5

LD.....-LLV

X 0.51 ... 1.24/Y 0.5

LD.....-LLV-X*

+LD-L....-X*

X 0.5/Y 0.51 ... 1.24

LD.....-LLV-Y*

+LD-L....-Y*

X/Y 0.51 ... 1.24

LD.....-LLV-X*/Y*

+LD-L....-X*
+LD-L....-Y*

X 0.5/Y 0.5
Z 0.36 ... 1.30 with LD.1 to LD.3
Z 0.42 ... 1.30 with LD.4 to LD.8

LD.....-LLV-Z*

+LD-L....-Z*

Offset elbow trunking units


left front

left front with Z dimension

left rear

X 0.5/Y0.5

LD.....-LLH

X 0.51 ... 1.24/Y0.5

LD.....-LLH-X*

+LD-L....-X*

X 0.5/Y0.51 ... 1.24

LD.....-LLH-Y*

+LD-L....-Y*

X/Y 0.51 ... 1.24

LD.....-LLH-X*/Y*

+LD-L....-X*
+LD-L....-Y*

X 0.5/Y 0.5
Z 0.36 ... 1.30 with LD.1 to LD.3
Z 0.42 ... 1.30 with LD.4 to LD.8

LD.....-LLH-Z*

+LD-L....-Z*

X
left rear with Z dimension

Fire barrier note:


Fire barrier possiblefor offset elbow units with optional length from
X 0.86 or Y 0.90 or Z 0.84 with LD.1...- to LD.3...X 0.92 or Y 0.90 or Z 0.90 with LD.4...- to LD.7...X 1.12 or Y 1.10 or Z 1.10 with LD.8...-

Complete ordering details:


See Type key/Important notes
(System overview, pages 3/4 and 3/5)
Examples: LDA1423-LLH-X1,22 +LD-L120A-X0,65
LDA4623-LLV

Siemens LV 71 2005

3/17

LD Busbar Trunking System


Selection and Ordering Data
Junction units for horizontal and vertical installation
l

Length
m

Type

T 1.2 trunking unit


(TX 0.58 and TY 0.62)
A 0.5 branching unit

LD.....-T-AD-T

Trunking unit as -T-AD-T


AX 0.5 and AY 0.3 branching unit

LD.....-T-AD-TVR

Trunking unit as above


AX 0.5 and AY 0.3 branching unit

LD.....-T-AD-TVL

T units with branching unit above

straight

TY
TX

offset, front right

AX

AY

offset, front left

AY

AX

Complete ordering details:


Example: LDA1423-T-AD-TVL

3/18

Siemens LV 71 2005

LD Busbar Trunking System


Selection and Ordering Data
Junction units for horizontal and vertical installation
Length
m

Type

Trunking unit as -T-AD-T


AX 0.5 and AY 0.3 branching unit

LD.....-T-AD-THR

Trunking unit as above


AX 0.5 and AY 0.3 branching unit

LD.....-T-AD-THL

T units with branching unit above

AY

offset, rear right

AX

AX

AY

offset, rear left

3
Complete ordering details:
Example: LDA1423-T-AD-THL

Siemens LV 71 2005

3/19

LD Busbar Trunking System


Selection and Ordering Data
Junction units for horizontal and vertical installation
Length
m

Type

T 1.2 trunking unit


(TX 0.58 and TY 0.62)
A 0.5 branching unit

LD.....-T-ADU-T

Trunking unit as -T-ADU-T


AX 0.5 and AY 0.3 branching unit

LD.....-T-ADU-TVR

Trunking unit as above


AX 0.5 and AY 0.3 branching unit

LD.....-T-ADU-TVL

T units with branching unit below


straight

TY
T

TX

offset, front right

AY

3
AX

AY

offset, front left

AX

Complete ordering details:


Example: LDA1423-T-ADU-TVL

3/20

Siemens LV 71 2005

LD Busbar Trunking System


Selection and Ordering Data
Junction units for horizontal and vertical installation
Length
m

Type

Trunking unit as -T-ADU-T


AX 0.5 and AY 0.3 branching unit

LD.....-T-ADU-THR

Trunking unit as above


AX 0.5 and AY 0.3 branching unit

LD.....-T-ADU-THL

T units with branching unit below

AY

offset, rear right

AX
offset, rear left

AX

AY

3
Complete ordering details:
Example: LDA1423-T-ADU-THL

Siemens LV 71 2005

3/21

LD Busbar Trunking System


Selection and ordering data
Distribution board connection units for non-Siemens distribution boards, cable connection and AS connection/feeder units
Length

Type

Type suffix
Fire barrier

Distribution board connecting flange


S 0.185
LD-VEG1

LD.4... to LD.8...

LD-VEG2

X 0.5/Y 0.3

LD.....-VEV

X 0.51 ... 1.24/Y 0.3

LD.....-VEV-X*

X 0.5/Y 0.3

LD.....-VEH

X 0.51 ... 1.24/Y 0.3

LD.....-VEH-X*

LD.1... to LD.3...

VE knee
front
+LD-L....-X*

+LD-L....-X*

rear

Fire barrier note:


Fire barrier possible for VE knee with optional length from:
X 0.86 with LD.1...- to LD.7...X 1.06 with LD.8...-

3/22

Siemens LV 71 2005

Complete ordering details:


See Type key/Important notes
(System overview, pages 3/4 and 3/5)
Example: LDA1423-VEV-X1,22 +LD-L120A-X0,65

LD Busbar Trunking System


Selection and ordering data
Distribution board connection units for non-Siemens distribution boards, cable connection and AS connection/feeder units
Length

Type

X 0.5/Y 0.3

LD.....-VEVR

X 0.51 ... 1.24/Y 0.3

LD.....-VEVR-X*

X 0.5/Y 0.3
Z 0.36 ... 1.30 with LD.1 to LD.3
Z 0.42 ... 1.30 with LD.4 to LD.8

LD.....-VEVR-Z*

X 0.5/Y 0.3

LD.....-VEVL

X 0.51 ... 1.24/Y 0.3

LD.....-VEVL-X*

X 0.5/Y 0.3
Z 0.36 ... 1.30 with LD.1 to LD.3
Z 0.42 ... 1.30 with LD.4 to LD.8

LD.....-VEVL-Z*

Type suffix
Fire barrier

Offset VE knee
front right
+LD-L....-X*

front right with Z dimension

front left
+LD-L....-X*

front left with Z dimension

Fire barrier note:


Fire barrier possible for offset VE knee with optional length from:
X 0.86 with LD.1...- to LD.3...X 0.92 with LD.4...- to LD.7...X 1.12 with LD.8...-

Complete ordering details:


See Type key/Important notes
(System overview, pages 3/4 and 3/5)
Examples: LDA1423-VEVL-Z0,9
LDA1423-VEVR-X1,22 +LD-L120A-X0,65

Siemens LV 71 2005

3/23

LD Busbar Trunking System


Selection and ordering data
Distribution board connection units for non-Siemens distribution boards, cable connection and AS connection/feeder units
Length

Type

X 0.5/Y 0.3

LD.....-VEHR

X 0.51 ... 1.24/Y 0.3

LD.....-VEHR-X*

X 0.5/Y 0.3
Z 0.36 ... 1.30 with LD.1 to LD.3
Z 0.42 ... 1.30 with LD.4 to LD.8

LD.....-VEHR-Z*

X 0.5/Y 0.3

LD.....-VEHL

X 0.51 ... 1.24/Y 0.3

LD.....-VEHL-X*

X 0.5/Y 0.3
Z 0.36 ... 1.30 with LD.1 to LD.3
Z 0.42 ... 1.30 with LD.4 to LD.8

LD.....-VEHL-Z*

Type suffix
Fire barrier

Offset VE knee
rear right
+LD-L....-X*

rear right with Z dimension

Y
rear left

+LD-L....-X*

Y
rear left with Z dimension

X
Fire barrier note:
Fire barrier possible for offset VE knee with optional length from:
X 0.86 with LD.1 ...- to LD.3...X 0.92 with LD.4...- to LD.7...X 1.12 with LD.8...-

3/24

Siemens LV 71 2005

Complete ordering details:


See Type key/Important notes
(System overview, pages 3/4 and 3/5)
Examples: LDA4523-VEHL-Z0,9
LDA1423-VEHR-X1,22 +LD-L120A-X0,65

LD Busbar Trunking System


Selection and ordering data
Distribution board connection units for SIVACON 8PV and 8PT power distribution systems
Length

Type

Type suffix
Fire barrier

W 0.50 ... 1.60

LD.....-VEU-1W*

+LD-L....-X*

W 1.61 ... 2.40

LD.....-VEU-2W*

+LD-L....-X*

W 1.41 ... 3.20

LD.....-VEU-3W*

+LD-L....-X*

X 0.5/Y 0.5

LD.....-VEU-LV

X 0.51 ... 1.24/Y 0.5

LD.....-VEU-LV-X*

+LD-L....-X*

X 0.5/Y 0.51 ... 1.24

LD.....-VEU-LV-Y*

+LD-L....-Y*

X/Y 0.51 ... 1.24

LD.....-VEU-LV-X*/Y*

+LD-L....-X*
+LD-L....-Y*

X 0.5/Y 0.5

LD.....-VEU-LH

X 0.51 ... 1.24/Y 0.5

LD.....-VEU-LH-X*

+LD-L....-X*

X 0.5/Y 0.51 ... 1.24

LD.....-VEU-LH-Y*

+LD-L....-Y*

X/Y 0.51 ... 1.24

LD.....-VEU-LH-X*/Y*

+LD-L....-X*
+LD-L....-Y*

Trunking units

straight

Knee

front

rear

Fire barrier note:


Fire barrier possible for knee with optional length from:
X 0.86 with LD.1 ...- to LD.7...X 1.06 with LD.8...-

Complete ordering details:


See Type key/Important notes
(System overview, pages 3/4 and 3/5)
Example: LDA1423-VEU-LH-X1,22
+LD-L120A-X0.65

Siemens LV 71 2005

3/25

LD Busbar Trunking System


Selection and ordering data
Distribution board connection units for SIVACON 8PV and 8PT power distribution systems
Length

Type

Type suffix
Fire barrier

X 0.5/Y 0.5

LD.....-VEU-LVR

X 0.51 ... 1.24/Y 0.5

LD.....-VEU-LVR-X*

+LD-L....-X*

X 0.5/Y 0.51 ... 1.24

LD.....-VEU-LVR-Y*

+LD-L....-Y*

X/Y 0.51 ... 1.24

LD.....-VEU-LVR-X*/Y*

+LD-L....-X*
+LD-L....-Y*

X 0.5/Y 0.5
Z 0.36 ... 1.30 with LD.1 to LD.3
Z 0.42 ... 1.30 with LD.4 to LD.8

LD.....-VEU-LVR-Z*

+LD-L....-Z*

X 0.5/Y 0.5

LD.....-VEU-LVL

X 0.51 ... 1.24/Y 0.5

LD.....-VEU-LVL-X*

+LD-L....-X*

X 0.5/Y 0.51 ... 1.24

LD.....-VEU-LVL-Y*

+LD-L....-Y*

X/Y 0.51 ... 1.24

LD.....-VEU-LVL-X*/Y*

+LD-L....-X*
+LD-L....-Y*

X 0.5/Y 0.5
Z 0.36 ... 1.30 with LD.1 to LD.3
Z 0.42 ... 1.30 with LD.4 to LD.8

LD.....-VEU-LVL-Z*

+LD-L....-Z*

Offset knee

front right

front right with Z dimension

front left

front left with Z dimension

Fire barrier note:


Fire barrier possible for offset knee with optional length from:
X 0.86 or Z 0.84 with LD.1...- to LD.3...X 0.92 or Z 0.90 with LD.4...- to LD.7...X 1.12 or Z 1.10 with LD.8...-

3/26

Siemens LV 71 2005

Complete ordering details:


See Type key/Important notes
(System overview, pages 3/4 and 3/5)
Examples: LDA4623-VEU-LVR-Z0,84
LDA1423-VEU-LVL-X1,20
+LD-L120A-X0,80

LD Busbar Trunking System


Selection and ordering data
Distribution board connection units for SIVACON 8PV and 8PT power distribution systems
Length

Type

Type suffix
Fire barrier

X 0.5/Y 0.5

LD.....-VEU-LHR

X 0.51 ... 1.24/Y 0.5

LD.....-VEU-LHR-X*

+LD-L....-X*

X 0.5/Y 0.51 ... 1.24

LD.....-VEU-LHR-Y*

+LD-L....-Y*

X/Y 0.51 ... 1.24

LD.....-VEU-LHR-X*/Y*

+LD-L....-X*
+LD-L....-Y*

X 0.5/Y 0.5
Z 0.36 ... 1.30 with LD.1 to LD.3
Z 0.42 ... 1.30 with LD.4 to LD.8

LD.....-VEU-LHR-Z*

+LD-L....-Z*

Offset knee

rear right

rear right with Z dimension

3
Z

rear left
X 0.5/Y 0.5

LD.....-VEU-LHL

X 0.51 ... 1.24/Y 0.5

LD.....-VEU-LHL-X*

+LD-L....-X*

X 0.5/Y 0.51 ... 1.24

LD.....-VEU-LHL-Y*

+LD-L....-Y*

X/Y 0.51 ... 1.24

LD.....-VEU-LHL-X*/Y*

+LD-L....-X*
+LD-L....-Y*

X 0.5/Y 0.5
Z 0.36 ... 1.30 with LD.1 to LD.3
Z 0.42 ... 1.30 with LD.4 to LD.8

LD.....-VEU-LHL-Z*

+LD-L....-Z*

rear left with Z dimension

Fire barrier note:


Fire barrier possible for offset knee with optional length from:
X 0.86 or Z 0.84 with LD.1...- to LD.3...X 0.92 or Z 0.90 with LD.4...- to LD.7...X 1.12 or Z 1.10 with LD.8...-

Complete ordering details:


See Type key/Important notes
(System overview, pages 3/4 and 3/5)
Examples: LDA4623-VEU-LHR-Z0,84
LDA1423-VEU-LHL-X1,22
+LD-L120A-X0,65

Siemens LV 71 2005

3/27

LD Busbar Trunking System


Selection and ordering data
AS 1, AS 2 and AS 4 connection/feeder units
Mounting position of
trunking units to be connected

Phase sequence
Transformer
and LD connection

Type

Note:
Values in brackets and dotted
lines are only valid for the
5-conductor system

Type suffix
Phase sequence
Transformer and
LD connection

Setting range of lug clearance [mm]


State of delivery Adjustable on
site to

AS1: Length 725 mm


AS2: Length 1085 mm
AS4: Length 1930 mm

150 ... 160

165 ... 180

190 ... 280

285 ... 380

450 ... 600

605 ... 750

PEN(N) L3(1)
150 ... 250

PEN(N) L3(1)
250 ... 350

64
05

_0

V0

NS

Type suffix
Flange plate for
enclosure of
distribution board/
transformer

LD.....-AS.

+LD-1A

+LD-FLP

LD.....-AS.

+LD-2A

+LD-FLP

LD.....-AS.

+LD-1B

+LD-FLP

LD.....-AS.

+LD-2B

+LD-FLP

60

05

_0

V0

NS

(PE)
PEN(N)
L3
L2
L1

(PE)
65
05

_0

V0

NS

61
05

_0

V0

NS

L3

PEN(N)

L2
L1

6
56
00

NS

60

05

_0

V0

0_

V
NS

(PE)

L2

L1

L3
PEN(N)

(PE)

67
05

_0

V0

NS

61
05

_0

V0

NS

L1
L2
L3
PEN(N)

Note for lug clearance:


Lug clearances are adjustable on site: A larger clearance of the terminal lugs can be attained by turning the lugs. The lug clearances given
are valid for flexible ribbon conductors and copper bars with a width
of 120 mm.

3/28

Siemens LV 71 2005

Note for flange plate:


Flanging to enclosure of distribution board/transformer:
With fitting a flange plate of aluminium (Type suffix
+LD-FLP), the connection unit can be flanged to the enclosure
of the distribution board/transformer.

LD Busbar Trunking System


Selection and ordering data
AS 1, AS 2 and AS 4 connection/feeder units
Mounting position of
trunking units to be connected

Phase sequence
Transformer
and LD connection

Type

Note:
Values in brackets and dotted
lines are only valid for the
5-conductor system

Type suffix
Phase sequence
Transformer and
LD connection

Setting range of lug clearance [mm]


State of delivery Adjustable on
site to

AS1: Length 725 mm


AS2: Length 1085 mm
AS4: Length 1930 mm

150 ... 160

165 ... 180

190 ... 280

285 ... 380

450 ... 600

605 ... 750

PEN(N) L3(1)
150 ... 250

PEN(N) L3(1)
250 ... 350

68
05

_0

V0

NS

Type suffix
Flange plate for
enclosure of
distribution board/
transformer

LD.....-AS.

+LD-1C

+LD-FLP

LD.....-AS.

+LD-2C

+LD-FLP

LD.....-AS.

+LD-1D

+LD-FLP

LD.....-AS.

+LD-2D

+LD-FLP

60

05

_0

V0

NS

(PE)
PEN(N)
L1
L2
L3

(PE)

69
05

_0

V0

NS

61
05

_0

V0

NS

L1

PEN(N)

L2
L3

70
05

_0

V0

NS

60

05

_0

V0

NS

(PE)
L3
L2
L1
PEN(N)

(PE)

71
05

_0

V0

NS

L2

61
05

_0

V0

NS

L3

L1
PEN(N)

Note for lug clearance:


Lug clearances are adjustable on site: A larger clearance of the terminal lugs can be attained by turning the lugs. The lug clearances given
are valid for flexible ribbon conductors and copper bars with a width
of 120 mm.

Note for flange plate:


Flanging to enclosure of distribution board/transformer:
With fitting a flange plate of aluminium (Type suffix
+LD-FLP), the connection unit can be flanged to the enclosure
of the distribution board/transformer.

Siemens LV 71 2005

3/29

LD Busbar Trunking System


Selection and ordering data
AS 3 connection/feeder units
Mounting position of
trunking units to be connected

Phase sequence
Transformer
and LD connection

Type

Note:
Values in brackets and dotted
lines are only valid for the
5-conductor system

Type suffix
Phase sequence
Transformer and
LD connection

Setting range of lug clearance [mm]


State of delivery Adjustable on
site to

AS3: Length 1430 mm


3

72
05

_0

V0

NS

Type suffix
Flange plate for
enclosure of
distribution board/
transformer

450 ... 600

605 ... 750

PEN(N) L3(1)
200 ... 300

PEN(N) L3(1)
200 ... 400

LD.....-AS3

+LD-1E

+LD-FLP

LD.....-AS3

+LD-2E

+LD-FLP

LD.....-AS3

+LD-1F

+LD-FLP

LD.....-AS3

+LD-2F

+LD-FLP

60

05

_0

V0

NS

(PE)
L3
PEN(N)

L2
L1

(PE)

73
05

_0

V0

NS

61
05

_0

V0

NS

L3
PEN(N)
L2

L1

74
05

_0

V0

NS

60

05

_0

V0

NS

(PE)
L1
L3

L2
PEN(N)

(PE)

75
05

_0

V0

NS

61
05

_0

V0

NS

L1
L2
PEN(N)
L3

Note for lug clearance:


Lug clearances are adjustable on site: A larger clearance of the terminal lugs can be attained by turning the lugs. The lug clearances given
are valid for flexible ribbon conductors and copper bars with a width
of 120 mm.

3/30

Siemens LV 71 2005

Note for flange plate:


Flanging to enclosure of distribution board/transformer:
With fitting a flange plate of aluminium (Type suffix
+LD-FLP), the connection unit can be flanged to the enclosure
of the distribution board/transformer.

LD Busbar Trunking System


Selection and ordering data
AS 3 connection/feeder units
Mounting position of
trunking units to be connected

Phase sequence
Transformer
and LD connection

Type

Note:
Values in brackets and dotted
lines are only valid for the
5-conductor system

Type suffix
Phase sequence
Transformer and
LD connection

Setting range of lug clearance [mm]


State of delivery Adjustable on
site to

AS3: Length 1430 mm


3

76
05

_0

V0

NS

Type suffix
Flange plate for
enclosure of
distribution board/
transformer

450 ... 600

605 ... 750

PEN(N) L3(1)
200 ... 300

PEN(N) L3(1)
200 ... 400

LD.....-AS3

+LD-1G

+LD-FLP

LD.....-AS3

+LD-2G

+LD-FLP

LD.....-AS3

+LD-1H

+LD-FLP

LD.....-AS3

+LD-2H

+LD-FLP

60

05

_0

V0

NS

(PE)
L1
PEN(N)

L2
L3

(PE)

77
05

_0

V0

NS

61
05

_0

V0

NS

L2

L1
PEN(N)

L3

78
05

_0

V0

NS

60

05

_0

V0

NS

(PE)
L3
L1

L2
PEN(N)

(PE)

79
05

_0

V0

NS

61
05

_0

V0

NS

L3
L2
PEN(N)
L1

Note for lug clearance:


Lug clearances are adjustable on site: A larger clearance of the terminal lugs can be attained by turning the lugs. The lug clearances given
are valid for flexible ribbon conductors and copper bars with a width
of 120 mm.

Note for flange plate:


Flanging to enclosure of distribution board/transformer:
With fitting a flange plate of aluminium (Type suffix
+LD-FLP), the connection unit can be flanged to the enclosure
of the distribution board/transformer.

Siemens LV 71 2005

3/31

LD Busbar Trunking System


Selection and ordering data
AS1 and AS2 connection/feeder units with T tap-off
Mounting position of
trunking units to be connected

Phase sequence
Transformer
and LD connection

Type

Note:
Values in brackets and dotted
lines are only valid for the
5-conductor system

Type suffix
Phase sequence
Transformer and
LD connection

Type suffix
Flange plate for
enclosure of
distribution board/
transformer

Setting range of lug clearance [mm]


State of delivery Adjustable on
site to

AS1: Length 725 mm


AS2: Length 1085 mm

150 160

165 180

Additionally, a VEG, VEV or VEH


must be engineered.

190 280

285 380

+LD-1A

+LD-FLP

LD.....-AS.-T

+LD-1B

+LD-FLP

(PE)
PEN(N)
L3

NSV0_00580

NSV0_00530

LD.....-AS.-T

L2

(PE)
L1
L3
PEN(N)

L2

NSV0_00580

NSV0_00532

L1

Note for lug clearance:


Lug clearances are adjustable on site: A larger clearance of the terminal lugs can be attained by turning the lugs. The lug clearances given
are valid for flexible ribbon conductors and copper bars with a width
of 120 mm.

3/32

Siemens LV 71 2005

Note for flange plate:


Flanging to enclosure of distribution board/transformer:
With fitting a flange plate of aluminium (Type suffix
+LD-FLP), the connection unit can be flanged to the enclosure
of the distribution board/transformer.

LD Busbar Trunking System


Selection and ordering data
AS1 and AS2 connection/feeder units with T tap-off
Mounting position of
trunking units to be connected

Phase sequence
Transformer
and LD connection

Type

Note:
Values in brackets and dotted
lines are only valid for the
5-conductor system

Type suffix
Phase sequence
Transformer and
LD connection

Type suffix
Flange plate for
enclosure of
distribution board/
transformer

Setting range of lug clearance [mm]


State of delivery Adjustable on
site to

AS1: Length 725 mm


AS2: Length 1085 mm

150 160

165 180

Additionally, a VEG, VEV or VEH


must be engineered.

190 280

285 380

+LD-1C

+LD-FLP

LD.....-AS.-T

+LD-1D

+LD-FLP

(PE)

L1
L2

(PE)

L2

L3

NSV0_00580

NSV0_00536

L3

PEN(N)

NSV0_00580

NSV0_00534

LD.....-AS.-T

L1
PEN(N)

Note for lug clearance:


Lug clearances are adjustable on site: A larger clearance of the terminal lugs can be attained by turning the lugs. The lug clearances given
are valid for flexible ribbon conductors and copper bars with a width
of 120 mm.

Note for flange plate:


Flanging to enclosure of distribution board/transformer:
With fitting a flange plate of aluminium (Type suffix
+LD-FLP), the connection unit can be flanged to the enclosure
of the distribution board/transformer.

Siemens LV 71 2005

3/33

LD Busbar Trunking System


Selection and ordering data
AS3 connection/feeder units with T tap-off
Mounting position of
trunking units to be connected

Phase sequence
Transformer
and LD connection

Type

Note:
Values in brackets and dotted
lines are only valid for the
5-conductor system

Type suffix
Phase sequence
Transformer and
LD connection

Type suffix
Flange plate for
enclosure of
distribution board/
transformer

Setting range of lug clearance [mm]


State of delivery Adjustable on
site to

AS3: Length 1430 mm


Additionally, a VEG, VEV or VEH
must be engineered.

450 600

605 750

PEN(N) L3(1)
200 300

PEN(N) L3(1)
200 400

+LD-1E

+LD-FLP

LD.....-AS3-T

+LD-1F

+LD-FLP

NSV0_00538a

LD.....-AS3-T

L2

NSV0_00580

(PE)
L3
PEN(N)

L1

(PE)

L3

L2
PEN(N)

L1

NSV0_00580

NSV0_00540a

Note for lug clearance:


Lug clearances are adjustable on site: A larger clearance of the terminal lugs can be attained by turning the lugs. The lug clearances given
are valid for flexible ribbon conductors and copper bars with a width
of 120 mm.

3/34

Siemens LV 71 2005

Note for flange plate:


Flanging to enclosure of distribution board/transformer:
With fitting a flange plate of aluminium (Type suffix
+LD-FLP), the connection unit can be flanged to the enclosure
of the distribution board/transformer.

LD Busbar Trunking System


Selection and ordering data
AS3 connection/feeder units with T tap-off
Mounting position of
trunking units to be connected

Phase sequence
Transformer
and LD connection

Type

Note:
Values in brackets and dotted
lines are only valid for the
5-conductor system

Type suffix
Phase sequence
Transformer and
LD connection

Type suffix
Flange plate for
enclosure of
distribution board/
transformer

Setting range of lug clearance [mm]


State of delivery Adjustable on
site to

AS3: Length 1430 mm


Additionally, a VEG, VEV or VEH
must be engineered.

450 600

605 750

PEN(N) L3(1)
200 300

PEN(N) L3(1)
200 400

+LD-1G

+LD-FLP

LD.....-AS3-T

+LD-1H

+LD-FLP

NSV0_00542a

LD.....-AS3-T

L2

NSV0_00580

(PE)
L1
PEN(N)

L3

(PE)

L1

L2
PEN(N)

L3

NSV0_00580

NSV0_00544a

Note for lug clearance:


Lug clearances are adjustable on site: A larger clearance of the terminal lugs can be attained by turning the lugs. The lug clearances given
are valid for flexible ribbon conductors and copper bars with a width
of 120 mm.

Note for flange plate:


Flanging to enclosure of distribution board/transformer:
With fitting a flange plate of aluminium (Type suffix
+LD-FLP), the connection unit can be flanged to the enclosure
of the distribution board/transformer.

Siemens LV 71 2005

3/35

LD Busbar Trunking System


Selection and ordering data
AS4 connection/feeder units with T tap-off
Mounting position of
trunking units to be connected

Phase sequence
Transformer
and LD connection

Type

Note:
Values in brackets and dotted
lines are only valid for the
5-conductor system

Type suffix
Phase sequence
Transformer and
LD connection

Type suffix
Flange plate for
enclosure of
distribution board/
transformer

Setting range of lug clearance [mm]


State of delivery Adjustable on
site to

AS4: Length 1930 mm


Additionally, a VEG, VEV or VEH
must be engineered.

450 600

605 750

PEN(N) L3(1)
150 250

PEN(N) L3(1)
250 350

+LD-1A

+LD-FLP

LD.....-AS4-2T

+LD-1B

+LD-FLP

LD.....-AS4-1T

+LD-1B

+LD-FLP

LD.....-AS4-2T

+LD-1A

+LD-FLP

(PE)
PEN(N)
L3

NSV0_00547

L2

(PE)

PEN(N)
L3
L2

(PE)

NSV0_00580

NSV0_00548

L1

NSV0_00581

L1

NSV0_00580

NSV0_00546

LD.....-AS4-1T

L1
L3
PEN(N)

L2

L1
L2
L3
PEN(N)

NSV0_00581

NSV0_00549

(PE)

Note for lug clearance:


Lug clearances are adjustable on site: A larger clearance of the terminal lugs can be attained by turning the lugs. The lug clearances given
are valid for flexible ribbon conductors and copper bars with a width
of 120 mm.

3/36

Siemens LV 71 2005

Note for flange plate:


Flanging to enclosure of distribution board/transformer:
With fitting a flange plate of aluminium (Type suffix
+LD-FLP), the connection unit can be flanged to the enclosure
of the distribution board/transformer.

LD Busbar Trunking System


Selection and ordering data
AS4 connection/feeder units with T tap-off
Mounting position of
trunking units to be connected

Phase sequence
Transformer
and LD connection

Type

Note:
Values in brackets and dotted
lines are only valid for the
5-conductor system

Type suffix
Phase sequence
Transformer and
LD connection

Type suffix
Flange plate for
enclosure of
distribution board/
transformer

Setting range of lug clearance [mm]


State of delivery Adjustable on
site to

AS4: Length 1930 mm


Additionally, a VEG, VEV or VEH
must be engineered.

450 600

605 750

PEN(N) L3(1)
150 250

PEN(N) L3(1)
250 350

+LD-1C

+LD-FLP

LD.....-AS4-2T

+LD-1D

+LD-FLP

LD.....-AS4-1T

+LD-1D

+LD-FLP

LD.....-AS4-2T

+LD-1C

+LD-FLP

(PE)
PEN(N)
L1
L2

NSV0_00551

(PE)

PEN(N)
L1
L2

(PE)

NSV0_00580

NSV0_00552

L3

NSV0_00581

L3

NSV0_00580

NSV0_00550

LD.....-AS4-1T

L3
L1
PEN(N)

L2

L3
L2
L1
PEN(N)

NSV0_00581

NSV0_00553

(PE)

Note for lug clearance:


Lug clearances are adjustable on site: A larger clearance of the terminal lugs can be attained by turning the lugs. The lug clearances given
are valid for flexible ribbon conductors and copper bars with a width
of 120 mm.

Note for flange plate:


Flanging to enclosure of distribution board/transformer:
With fitting a flange plate of aluminium (Type suffix
+LD-FLP), the connection unit can be flanged to the enclosure
of the distribution board/transformer.

Siemens LV 71 2005

3/37

LD Busbar Trunking System


Selection and ordering data
Incoming cable connection units
Phase sequence
Transformer
and LD connection

Type suffix1)
Base plate of aluminiums

Type

Rated current [A]


IP 31
Al

Version
Code
No.

IP 54
Cu

Al

1100

4-conductor

5-conductor

Cu

900

N/PEN

1250

2000

1000

1600

1/

1600

2600

1200

2100

2000

1600

2500

2000

Al

Cable entries

Cu

System

Siemens LV 71 2005

IP31

IP54

max. [mm2]

LDA 1, LDA 2

4 300

LDC 2, LDA 3, LDA 4

6 300

LDC 3, LDA 5

8 300

LD.....-KE1

+LD-BPAL

LD.....-KE2

+LD-BPAL

1) Note for cable entries:


For single-core cable entries, the type suffix Base plate of aluminium must be indicated.

3/38

Degree of protection

Conductor material

Note:
N/PEN = 1/2 L possible with LDA 4(5)...

LD Busbar Trunking System


Selection and ordering data
FA 1 adapters for connection to non-Siemens distribution boards
Type
LDA

LDC

Rated current
Ie
A

LDA
system

1100

1250

1600

2000

2500

3000

3700

4000

Code
No.

2
3

Version

Rated current
Ie
A

LDC
system

Code
No.

2000

2600

4-conductor

5-conductor

N/PEN

1/

Degree of protection
3400

4400

5000

IP00

Conductor material
Al

Cu

Note:
N/PEN = 1/2 L possible from
LD.4... to LD.8...

LD.....-FA1

Note:
Screws, conical spring washers and threaded plates
are incuded in the scope of supply.
Note for short-circuit strength:
Note for limit temperature:
When adapters for connection to non-Siemens distribution boards are The short-circuit strength of the connection units for nonused, it must be assured, that the admissible limit temperature of 100 K Siemens distribution boards are determinated by the design
for the busbars, at an ambient temperature of 35 C im 24-h-Mittel, is of the terminal assemblies of the distribution system.
not exceeded.
The rated current values given in the table are valid for a limit temperature of 100 K.

Siemens LV 71 2005

3/39

LD Busbar Trunking System


Selection and ordering data
Reduction units for horizontal and vertical installation
Degree of protection Length S
m

Rated current Conductor cross-section


N/PEN of the
7/8/9-conductor system
A

Type
4-conductor-system

Type
5-conductor-system

LDA5413/LDA3423

LDA5613/LDA3623

LDA5423/LDA3423

LDA5623/LDA3623

LDA5415/LDA3425

LDA5615/LDA3625

LDA5425/LDA3425

LDA5625/LDA3625

LDC7413/LDC3423

LDC7613/LDC3623

LDC7423/LDC3423

LDC7623/LDC3623

LDC7415/LDC3425

LDC7615/LDC3625

LDC7425/LDC3425

LDC7625/LDC3625

LDA
for horizontal (vertical) installation
IP 31

1.2

1600 (1250)

IP 54

1.2

1200 (1200)

1/

L
1/

L
LDC
for horizontal (vertical) installation

IP 31

1.2

2600 (2100)

1/

L
IP 54

1.2

2000 (2000)

1/

2 L

Complete ordering details:


Example: LDC7423/LDC3423

3/40

Siemens LV 71 2005

LD Busbar Trunking System


Selection and ordering data
Tap-off units with GSTA fuse switch disconnectors
Type
LD system

Type suffix

Code No.

LDA 1... to LDA 3...


LDC 2... to LDC 3...

LDA 4.1. to LDA 8.1.


LDC 6.1. to LDC 8.1.

LDA 4.2. to LDA 8.2.


LDC 6.2. to LDC 8.2.

Version
4

4-conductor

5-conductor

Rated current le [A]


Ue = 400 V

Ue = 690 V

IP 30

IP 54

IP 30

IP 54

31ST125

1 125

1 125

1 100

1 100

32ST125

2 125

2 100

2 100

2 100

3ST250

1 250

1 200

1 200

1 200

3ST400

1 400

1 315

1 315

3ST630

1 630

1 500

1 500

1 315
(630)1)

1 500

LD-K-.AK./.......
LD-K-.AK./.......

see next page

Equipment features:
Fuse switch-disconnector with virtually instantaneous switching (3-pole version)
sizes NH 00, 2x NH 00, NH 1, NH2, NH3
Can be fitted/removed while the system is live
Degree of protection IP30 as standard, IP54 with type suffix
Cable entry for multi-core or single-core cables (Type suffix always equired)
Cable entry at the end (standard), at the side as a type suffix
Electrical interlock and trip indication (on request)
Current measurement (on request)
Note:
1) 630 A when using fuse links of make Jean-Mller, Type M3 gL 630/69,
Article No. N306900

Examples for complete ordering details:


LD-K-1AK4/3ST250 +LD-ML
LD-K-1AK4/3ST250 +LD-ML +LD-IP54

Siemens LV 71 2005

3/41

LD Busbar Trunking System


Selection and ordering data
Tap-off units with GSTA fuse switch disconnectors
Type

Type suffix

LD-K-.AK./.......

+LD-ML

LD-K-.AK./.......

+LD-EL

LD-K-.AK./.......

+BD2-800-KR

LD-K-.AK./.......

+LD-IP54

LD-K-.AK./.......

+LD-DS

Type suffixes
Cable entry
Multi-core
Single-core

1)

Cable entry at the side


(additional cabling box)

Degree of protection IP54

3
Accessory box for loose spacers
for the respective tap-off point2)

Note:
1) Aluminium plate, not drilled
2) For storing the loose spacers for the respective tap-off point.

3/42

Siemens LV 71 2005

Examples for complete ordering details:


LD-K-1AK4/3ST250 +LD-ML
LD-K-1AK4/3ST250 +LD-ML +LD-IP54

LD Busbar Trunking System


Selection and ordering data
Tap-off units with GSTZ fuse switch disconnectors
Type
LD system

Type suffix

Code No.

LDA 1... to LDA 3...


LDC 2... to LDC 3...

LDA 4.1. to LDA 8.1.


LDC 6.1. to LDC 8.1.

LDA 4.2. to LDA 8.2.


LDC 6.2. to LDC 8.2.

Version
4

4-conductor

5-conductor

Rated current le [A]


Ue = 400 V

Ue = 690 V

400

315

630

500 (630) 1)

LD-K-.AK./GSTZ.

Equipment features:
Rated current 400 A and 630 A
Fuse switch-disconnectors (GSTZ) sizes NH 2, NH 3 (3-pole version)
Can be fitted/removed while the system is live
Degree of protection IP30 as standard, IP54 as a type suffix
Cable entry for multi-core or single-core cables
(Type suffix always required)
Cable entry at the end or side
Cable entry
Multi-core

+LD-AB4

Single-core2),
1 cable per phase

+LD-AB7

Single-core2),
2 cables per phase

+LD-AB8

Door hinged on
the left

+LD-TL2

Door hinged on
the right

+LD-TR2

Degree of protection IP54, with door

Note:
1) 630 A when using fuse links of make Jean-Mller, Type M3 gL 630/69,
Article No. N306900.
2) Aluminium plate, drilled, with PG glands
(see Technical Data).

Examples for complete ordering details:


LD-K-1AK4/GSTZ2 +LD-AB4
LD-K-1AK4/GSTZ2 +LD-AB4 +LD-TR2

Siemens LV 71 2005

3/43

LD Busbar Trunking System


Selection and ordering data
Tap-off units up to 570 A with circuit-breaker
Type
LD system

Type suffix

Code No.

LDA 1... to LDA 3...


LDC 2... to LDC 3...

LDA 4.1. to LDA 8.1.


LDC 6.1. to LDC 8.1.

LDA 4.2. to LDA 8.2.


LDC 6.2. to LDC 8.2.

Version
4

4-conductor

5-conductor

Rated current le
80

80 A

100

100 A

125

125 A

160

160 A

200

200 A

250

250 A

400

400 A

570

570 A

Circuit-breaker

Circuit-breaker with handle

LD-K-.AK./LSH . . . H-.

Circuit-breaker with motor drive

LD-K-.AK./LSM . . . H-.

3-pole

4-pole

Equipment features:
Circuit-breaker (3- and 4-pole version), H version (high capacity)
Can be fitted/removed while the system is live
Degree of protection IP54 as standard
Cable entry for multi-core or single-core cables at the side
Standard auxiliary contact and trip-indicating auxiliary contact as standard
Control connections wired to terminal
Handle (black) for manual drive
External power supply AC 220 ... 240 V, 50/60 Hz for motor drive
Type suffixes for tap-off units
Releases

Circuit-breaker version

Undervoltage release

up to 250 A

+U-NZM 7 (220 240 V AC)

400 ... 570 A

+U-NZM 10 (220 240 V AC)

up to 250 A

+A-NZM 7 (220 240 V AC)

400 ... 570 A

+A-NZM 10 (220 240 V AC)

Shunt release

NEW: Standard tap-off units with Siemens circuit-breakers.


Units up to 630 A will be published in the next catalog version (2006),
as product development and tests have not yet been completed.
For preliminary solutions, please contact your product managers.
(Type suffix always required)

3/44

Siemens LV 71 2005

LD Busbar Trunking System


Selection and ordering data
Tap-off units from 800 to 1250 A with circuit-breaker
Type
LD system

Type suffix

Code No.

LDA 1... to LDA 3...


LDC 2... to LDC 3...

LDA 4.1. to LDA 8.1.


LDC 6.1. to LDC 8.1.

LDA 4.2. to LDA 8.2.


LDC 6.2. to LDC 8.2.

Version
4

4-conductor

5-conductor

Circuit-breaker
AE

3-pole

BE

4-pole

Rated current le
at Ue = AC 400 V

Circuit-breaker with handle

LD-K-.AK./LSH-. . . . . -LS

Circuit-breaker with motor drive

LD-K-.AK./LSM-. . . . . -LS

2
58
_00
V0
NS

800

800 A

1000

1000 A

1250

1250 A

583

_00

V0

NS

Equipment features:
Circuit-breaker (3- and 4-pole version) for system protection, L version (100 kA)
Can be fitted/removed while the system is live
Degree of protection IP54 as standard
Cable entry for multi-core or single-core cables 1) at the side
With adjustable overload release and fixed-set short-circuit-release
4-pole circuit-breakers without overload and short-circuit-release
in the N -conductor
with two auxiliary switches (1 NO + 1 NC) and an alarm switch (1 NO)
Control connections wired to terminal
Handle (black) for manual drive
External power supply AC 220 ... 250 V, 50/60 Hz for motor drive
Type suffixes for tap-off units
Auxiliary releases

Version

Undervoltage release

AC 220 ... 250 V

+2H

Shunt release

AC 208 ... 277 V

+8T

1) Aluminium plate not drilled, cable glands not included in the scope of supply.

Siemens LV 71 2005

3/45

LD Busbar Trunking System


Selection and ordering data
Accessories for horizontal und vertical installation
Length

for system

Number of
loose spacers
supplied

Type

LD.142. to LD.342.

LD-1EF4-H

LD.162. to LD.362.

LD-1EF6-H

LD.441. to LD.841.

LD-2EF4-H

LD.461. to LD.861.

LD-2EF6-H

LD.442. to LD.842.

LD-3EF4-H

LD.462. to LD.862.

LD-3EF6-H

m
End flanges with hooks
0.325

End flanges with bolts


0.325

LD.142. to LD.342.

LD-1EF4-B

LD.162. to LD.362.

LD-1EF6-B

LD.441. to LD.841.

LD-2EF4-B

LD.461. to LD.861.

LD-2EF6-B

LD.442. to LD.842.

LD-3EF4-B

LD.462. to LD.862.

LD-3EF6-B

LD.1 to LD.3

LD-VE-BF1

LD.4 to LD.8

LD-VE-BF2

LD.1 to LD.3

LD-DF1

LD.4 to LD.8

LD-DF2

Distribution board blank plate

0.325

Protective sleeves
0.25

3/46

Siemens LV 71 2005

LD Busbar Trunking System


Selection and ordering data
Accessories for horizontal und vertical installation
Length

for system

Number of
loose spacers
supplied

Type

Suspension bracket for horizontal suspension


LD.1 to LD.3

LD-B1

LD.4 to LD.8

LD-B2

LD.1 to LD.8

LD-BV

Fixing bracket for vertical fixing

3
Torque spanner
LD.1 to LD.8

LD-DR

Siemens LV 71 2005

3/47

LD Busbar Trunking System


Technical Data
LDA.4.. Trunking Units
Siemens LV 71 2005Catalog LV 71 EN, Chapter 3, Part 1

Type

LDA.4.. system (4-conductor system)

Standards and Regulations

IEC 60439-1 and -2,


EN 60439-1 and -2 (VDE 0660 Part 500 and Part 502),
NF C 63-410 and -411,
BS 5486 Part 1 and 2,
SEV/ASE 3625-1 and 2

Climatic Proofing

Damp heat, constant, to IEC 60068-2-78


Damp heat, cyclic, to IEC 60068-2-30

Ambient temperature, min./max./mean level over 24 hours

5/+40/+35

Degree of protection
ventilated (horizontal busbar edgewise)

IP34

enclosed

IP54

Busbars edgewise in the system

Standard mounting position


Torque for single-bolt clamp terminal

Nm

80

Busbar surface treatment

Insulation-plated, nickel-plated and tinned


over the entire length

Material of trunking units, tap-off units

Powder spray paint finished steel enclosure

Color of trunking units, tap-off units

RAL 7035 (light grey)

Dimensions

See Dimension drawings, page 3/118

Weight

See page 3/64

Rated insulation voltage

V~

1000

to EN 60664-1 (VDE 0110 Part 1)

1200

Overvoltage category/pollution degree


to EN 60947

III/3

for power transmission to EN 60947

IV/3

Rated operational voltage


with vervoltage category III/3

V~

1000

with vervoltage category IV/3

V~

690

Rated frequency

Hz

16 2/3 ... 60

3/48

Siemens LV 71 2005

LD Busbar Trunking System


Technical Data
LDA.4.. Trunking Units
System-dependent data

LDA 142. LDA 242. LDA 342. LDA 441. LDA 442. LDA 541. LDA 542.
PEN = L PEN = L PEN = L PEN = L PEN = L PEN = L PEN = L

Rated current Ie1)


horizontal/edgewise2)

IP34

Ie

1100

1250

1600

2000

2000

2500

2500

IP54

Ie

900

1000

1200

1500

1500

1800

1800

IP34

Ie

950

1100

1250

1700

1700

2100

2100

IP54

Ie

900

1000

1200

1500

1500

1800

1800

IP31/IP54

Ie

700

750

1000

1200

1200

1700

1700

Resistance

R'20

m/m 0.073

0.047

0.047

0.037

0.037

0.023

0.024

Reactance

X'20

m/m 0.045

0.043

0.043

0.025

0.030

0.023

0.030

Impedance

Z'20

m/m 0.086

0.064

0.064

0.044

0.047

0.033

0.038

of the conductors
at 50 Hz and after
attaining operational
temperature

Resistance

R'

m/m 0.086

0.054

0.057

0.043

0.044

0.027

0.028

Reactance

X'

m/m 0.046

0.043

0.043

0.025

0.029

0.023

0.029

Impedance

Z'

m/m 0.098

0.069

0.072

0.049

0.053

0.036

0.041

of the conductors
for 4-conductor systems
in the event of a fault
to EN 60439-2, Annex F

Resistance

R'F

m/m 0.143

0.106

0.106

0.106

0.081

0.075

0.055

Reactance

X'F

m/m 0.166

0.178

0.178

0.103

0.116

0.109

0.115

Impedance

Z'F

m/m 0.219

0.207

0.207

0.147

0.142

0.132

0.128

R'0

m/m 0.284

0.217

0.217

0.242

0.173

0.180

0.120

X'0

m/m 0.232

0.200

0.200

0.154

0.174

0.154

0.154

Z'0

m/m 0.366

0.295

0.295

0.286

0.246

0.237

0.195

ICW

kA

70

80

110

110

125

125

vertical
horizontal/flat
Impedance
of the conductors
at 50 Hz and +20 C
busbar temperature

Zero impedance
for 4-conductor systems
to IEC 60909,
EN 60909 (VDE 0102)
Short-circuit strength
Rated short-time
withstand current

rms value t = 0.1 s

55

rms value t = 1 s

ICW

kA

40

55

58

80

80

110

110

Rated impulse
withstand current

peak value

IPK

kA

121

154

176

242

242

275

275

Aluminium

Conductor material
Number of busbars

L1, L2, L3

mm2

406

706

706

812

812

1412

1412

PEN

mm2

406

706

706

406

812

706

1412

Trunking unit without


tap-off point

kWh/
m

4.16

4.16

4.16

6.73

6.73

6.73

6.73

Per tap-off point

kWh

7.80

7.80

7.80

10.80

10.80

10.80

10.80

Conductor cross-section
Combustive energy

Max. fixing intervals


For normal
mechanical load

1) Dependent on the degree of protection and type of mounting.


2) Including adjustments in height F1.3 m.

Siemens LV 71 2005

3/49

LD Busbar Trunking System


Technical Data
LDA.4.. Trunking Units
System-dependent data

LDA 641. LDA 642.


PEN = L PEN = L

LDA 741. LDA 742.


PEN = L PEN = L

LDA 841. LDA 842.


PEN = L PEN = L

Rated current Ie1)


horizontal/edgewise2)
vertical
horizontal/flat

IP34

Ie

3000

3000

3700

3700

4000

4000

IP54

Ie

2000

2000

2400

2400

2700

2700

IP34

Ie

2300

2300

2800

2800

3400

3400

IP54

Ie

2000

2000

2400

2400

2700

2700

IP31/IP54

Ie

1800

1800

2200

2200

2350

2350

Resistance

R'20

m/m 0.023

0.024

0.017

0.016

0.015

0.013

Reactance

X'20

m/m 0.023

0.029

0.019

0.022

0.017

0.019

Impedance

Z'20

m/m 0.033

0.037

0.026

0.027

0.023

0.023

Resistance

R'

m/m 0.030

0.029

0.021

0.020

0.018

0.016

Reactance

X'

m/m 0.024

0.029

0.019

0.022

0.017

0.019

Impedance

Z'

m/m 0.038

0.041

0.029

0.030

0.025

0.025

Resistance

R'F

m/m 0.075

0.056

0.055

0.041

0.049

0.038

Reactance

X'F

m/m 0.109

0.119

0.083

0.093

0.086

0.080

Impedance

Z'F

m/m 0.132

0.131

0.099

0.101

0.099

0.088

R'0

m/m 0.180

0.120

0.126

0.090

0.110

0.075

X'0

m/m 0.154

0.153

0.097

0.119

0.086

0.087

Z'0

m/m 0.237

0.194

0.159

0.149

0.140

0.115

Impedance
of the conductors
at 50 Hz and +20 C
busbar temperature
of the conductors
at 50 Hz and after
attaining operational
temperature
of the conductors
for 4-conductor systems
in the event of a fault
to EN 60439-2, Annex F

Zero impedance
for 4-conductor systems
to IEC 60909,
EN 60909 (VDE 0102)
Short-circuit strength
Rated short-time
withstand current

rms value t = 0.1 s

ICW

kA

130

130

130

130

130

130

rms value t = 1 s

ICW

kA

116

116

116

116

116

116

Rated impulse
withstand current

peak value

IPK

kA

286

286

286

286

286

286

Aluminium

Conductor material
Number of busbars

L1, L2, L3

mm2

1412

1412

2044

2044

2464

2464

PEN

mm2

706

1412

1022

2044

1232

2464

Trunking unit without


tap-off point

kWh/
m

6.73

6.73

7.99

7.99

8.83

8.83

Per tap-off point

kWh

10.80

10.80

10.80

10.80

10.80

10.80

Conductor cross-section
Combustive energy

Max. fixing intervals


For normal
mechanical load

1) Dependent on the degree of protection and type of mounting.


2) Including adjustments in height F1.3 m.

3/50

Siemens LV 71 2005

LD Busbar Trunking System


Technical Data
LDA.6.. Trunking Units
Type

LDA.6.. system (5-conductor system)

Standards and Regulations

IEC 60439-1 and -2,


EN 60439-1 and -2 (VDE 0660 Part 500 and Part 502),
NF C 63-410 and -411,
BS 5486 Part 1 and 2,
SEV/ASE 3625-1 and 2

Climatic Proofing

Damp heat, constant, to IEC 60068-2-78


Damp heat, cyclic, to IEC 60068-2-30

Ambient temperature, min./max./mean level over 24 hours

5/+40/+35

Degree of protection
ventilated (horizontal busbar edgewise)

IP34

enclosed

IP54

Busbars edgewise in the system

Standard mounting position


Torque for single-bolt clamp terminal

Nm

80

Busbar surface treatment

Insulation-plated, nickel-plated and tinned


over the entire length

Material of trunking units, tap-off units

Powder spray paint finished steel enclosure

Color of trunking units, tap-off units

RAL 7035 (light grey)

Dimensions

See Dimension drawings, page 3/118

Weight

See page 3/64

Rated insulation voltage

V~

1000

to EN 60664-1 (VDE 0110 Part 1)

1200

Overvoltage category/pollution degree


to EN 60947

III/3

for power transmission to EN 60947

IV/3

Rated operational voltage


with vervoltage category III/3

V~

1000

with vervoltage category IV/3

V~

690

Rated frequency

Hz

16 2/3 ... 60

Siemens LV 71 2005

3/51

LD Busbar Trunking System


Technical Data
LDA.6.. Trunking Units
System-dependent data

LDA 162. LDA 262. LDA 362. LDA 461. LDA 462. LDA561. LDA562.
N=L
N=L
N=L
N = L
N=L
N = L
N=L

Rated current Ie1)


horizontal/edgewise2)

IP34

Ie

1100

1250

1600

2000

2000

2500

2500

IP54

Ie

900

1000

1200

1500

1500

1800

1800

IP34

Ie

950

1100

1250

1700

1700

2100

2100

IP54

Ie

900

1000

1200

1500

1500

1800

1800

IP31/IP54

Ie

700

750

1000

1200

1200

1700

1700

of the conductors
at 50 Hz and +20 C
busbar temperature

Resistance

R'20

m/m 0.075

0.048

0.048

0.036

0.036

0.023

0.025

Reactance

X'20

m/m 0.043

0.043

0.043

0.025

0.029

0.024

0.031

Impedance

Z'20

m/m 0.086

0.064

0.064

0.044

0.046

0.033

0.040

of the conductors
at 50 Hz and after
attaining operational
temperature

Resistance

R'

m/m 0.088

0.054

0.059

0.042

0.043

0.028

0.029

Reactance

X'

m/m 0.045

0.043

0.042

0.025

0.030

0.024

0.031

Impedance

Z'

m/m 0.099

0.069

0.072

0.049

0.052

0.037

0.042

R'F

m/m 0.150

0.108

0.108

0.129

0.119

0.092

0.084

X'F

m/m 0.204

0.201

0.201

0.142

0.138

0.134

0.131

Z'F

m/m 0.253

0.228

0.228

0.192

0.182

0.163

0.156

Resistance

R'F

m/m 0.156

0.108

0.108

0.112

0.083

0.076

0.056

Reactance

X'F

m/m 0.173

0.173

0.173

0.108

0.113

0.106

0.114

Impedance

Z'F

m/m 0.233

0.204

0.204

0.155

0.140

0.130

0.127

for 5-conductor systems


(PE)
to IEC 60909,
EN 60909 (VDE 0102)

R'0

m/m 0.315

0.240

0.240

0.301

0.292

0.217

0.213

X'0

m/m 0.401

0.393

0.393

0.267

0.291

0.202

0.265

Z'0

m/m 0.510

0.460

0.460

0.402

0.412

0.297

0.340

for 5-conductor systems


(N)
to IEC 60909,
EN 60909 (VDE 0102)

R'0

m/m 0.339

0.231

0.231

0.267

0.179

0.181

0.121

X'0

m/m 0.245

0.219

0.219

0.144

0.165

0.128

0.167

Z'0

m/m 0.418

0.319

0.319

0.303

0.243

0.221

0.206

ICW

kA

70

80

110

110

125

125

vertical
horizontal/flat
Impedance

Resistance
of the conductors for
5-conductor systems (PE) Reactance
in the event of a fault
to EN 60439-2, Annex F Impedance

of the conductors for


5-conductor systems (N)
in the event of a fault
to EN 60439-2, Annex F
Zero impedance

Short-circuit strength
Rated short-time
withstand current

rms value t = 0.1 s


rms value t = 1 s

ICW

kA

40

55

58

80

80

110

110

Rated impulse
withstand current

peak value

IPK

kA

121

154

176

242

242

275

275

Rated short-time
withstand current
of the 5th conductor

rms value t = 0.1 s

ICW

kA

33

42

48

66

66

75

75

rms value t = 1 s

ICW

kA

24

33

35

48

48

66

66

Conductor material

55

Aluminium

Number of busbars

L1, L2, L3

mm2

406

706

706

812

812

1412

1412

mm2

406

706

706

406

812

706

1412

PE

mm2

406

706

706

406

406

706

706

Trunking unit without


tap-off point

kWh/
m

4.16

4.16

4.16

6.73

6.73

6.73

6.73

Per tap-off point

kWh

7.80

7.80

7.80

10.80

10.80

10.80

10.80

Conductor cross-section

Combustive energy

Max. fixing intervals


For normal
mechanical load

1) Dependent on the degree of protection and type of mounting.


2) Including adjustments in height F1.3 m.

3/52

Siemens LV 71 2005

LD Busbar Trunking System


Technical Data
LDA.6.. Trunking Units
System-dependent data

LDA 661.
N = L

LDA 662.
N=L

LDA 761.
N = L

LDA 762.
N =L

LDA 861.
N = L

LDA 862.
N =L

Rated current Ie1)


horizontal/edgewise2)
vertical
horizontal/flat

IP34

Ie

3000

3000

3700

3700

4000

4000

IP54

Ie

2000

2000

2400

2400

2700

2700

IP34

Ie

2300

2300

2800

2800

3400

3400

IP54

Ie

2000

2000

2400

2400

2700

2700

IP31/IP54

Ie

1800

1800

2200

2200

2350

2350

Resistance

R'20

m/m 0.023

0.023

0.017

0.018

0.014

0.015

Reactance

X'20

m/m 0.024

0.029

0.019

0.025

0.022

0.021

Impedance
of the conductors
at 50 Hz and +20 C
busbar temperature
of the conductors
at 50 Hz and after
attaining operational
temperature

Impedance

Z'20

m/m 0.033

0.037

0.026

0.030

0.026

0.026

Resistance

R'

m/m 0.029

0.030

0.020

0.021

0.017

0.018

Reactance

X'

m/m 0.024

0.031

0.020

0.025

0.021

0.021

Impedance

Z'

m/m 0.037

0.043

0.028

0.033

0.027

0.027

R'F

m/m 0.092

0.084

0.068

0.065

0.055

0.056

X'F

m/m 0.134

0.133

0.110

0.114

0.102

0.105

Z'F

m/m 0.163

0.157

0.129

0.131

0.116

0.119

Resistance

R'F

m/m 0.076

0.057

0.053

0.042

0.049

0.037

Reactance

X'F

m/m 0.106

0.113

0.080

0.091

0.084

0.086

Impedance

Z'F

m/m 0.130

0.127

0.096

0.100

0.097

0.094

Resistance
of the conductors for
5-conductor systems (PE) Reactance
in the event of a fault
Impedance
to EN 60439-2, Annex F
of the conductors for
5-conductor systems (N)
in the event of a fault
to EN 60439-2, Annex F
Zero impedance
for 5-conductor systems
(PE)
to IEC 60909,
EN 60909 (VDE 0102)
for 5-conductor systems
(N)
to IEC 60909,
EN 60909 (VDE 0102)

R'0

m/m 0.217

0.212

0.163

0.166

0.145

0.146

X'0

m/m 0.202

0.263

0.175

0.220

0.196

0.196

Z'0

m/m 0.297

0.338

0.240

0.275

0.243

0.244

R'0

m/m 0.181

0.122

0.130

0.089

0.115

0.079

X'0

m/m 0.128

0.155

0.102

0.093

0.095

0.100

Z'0

m/m 0.221

0.198

0.165

0.129

0.149

0.127

ICW

kA

130

130

130

130

130

130

Short-circuit strength
Rated short-time
withstand current

rms value t = 0.1 s


rms value t = 1 s

ICW

kA

116

116

116

116

116

116

Rated impulse
withstand current

peak value

IPK

kA

286

286

286

286

286

286

Rated short-time
withstand current
of the 5th conductor

rms value t = 0.1 s

ICW

kA

78

78

78

78

78

78

rms value t = 1 s

ICW

kA

70

70

70

70

70

70

Conductor material

Aluminium

Number of busbars

L1, L2, L3

mm2

1412

1412

2044

2044

2464

2464

mm2

706

1412

1022

2044

1232

2464

PE

mm2

706

706

1022

1022

1232

1232

Trunking unit without


tap-off point

kWh/
m

6.73

6.73

7.99

7.99

8.83

8.83

Per tap-off point

kWh

10.80

10.80

10.80

10.80

10.80

10.80

Conductor cross-section

Combustive energy

Max. fixing intervals


For normal
mechanical load

1) Dependent on the degree of protection and type of mounting.


2) Including adjustments in height F1.3 m.

Siemens LV 71 2005

3/53

LD Busbar Trunking System


Technical Data
LDC.4.. Trunking Units
Type

LDC.4.. system (4-conductor system)

Standards and Regulations

IEC 60439-1 and -2,


EN 60439-1 and -2 (VDE 0660 Part 500 and Part 502),
NF C 63-410 and -411,
BS 5486 Part 1 and 2,
SEV/ASE 3625-1 and 2

Climatic Proofing

Damp heat, constant, to IEC 60068-2-78


Damp heat, cyclic, to IEC 60068-2-30

Ambient temperature, min./max./mean level over 24 hours

5/+40/+35

Degree of protection
ventilated

IP34

enclosed

IP54

Busbars edgewise in the system

Standard mounting position


Torque for single-bolt clamp terminal

Nm

Insulation-plated and tinned over the entire length

Material of trunking units, tap-off units

Powder spray paint finished steel enclosure

Color of trunking units, tap-off units

RAL 7035 (light grey)

Dimensions

See Dimension drawings, page 3/118


See page 3/64

Weight

80

Busbar surface treatment

Rated insulation voltage

V~

1000

to EN 60664-1 (VDE 0110 Part 1)

1200

Overvoltage category/pollution degree


to EN 60947

III/3

for power transmission to EN 60947

IV/3

Rated operational voltage


with vervoltage category III/3

V~

1000

with vervoltage category IV/3

V~

690

Rated frequency

Hz

16 2/3 ... 60

3/54

Siemens LV 71 2005

LD Busbar Trunking System


Technical Data
LDC.4.. Trunking Units
System-dependent data

LDC 242.
PEN = L

LDC 342.
PEN = L

LDC 641.
PEN = L

LDC 642.
PEN = L

Rated current Ie1)


horizontal/edgewise2)

IP34

Ie

2000

2600

3400

3400

IP54

Ie

1600

2000

2600

2600

IP34

Ie

1650

2100

2700

2700

IP54

Ie

1600

2000

2600

2600

IP31/IP54

Ie

1200

1550

2000

2000

of the conductors
at 50 Hz and +20 C
busbar temperature

Resistance

R'20

m/m 0.030

0.026

0.015

0.015

Reactance

X'20

m/m 0.042

0.035

0.026

0.026

Impedance

Z'20

m/m 0.052

0.043

0.030

0.030

of the conductors
at 50 Hz and after attaining
operational temperature

Resistance

R'

m/m 0.037

0.028

0.017

0.018

Reactance

X'

m/m 0.042

0.036

0.026

0.027

Impedance

Z'

m/m 0.056

0.046

0.031

0.032

Resistance

R'F

m/m 0.075

0.056

0.048

0.037

Reactance

X'F

m/m 0.170

0.163

0.107

0.107

Impedance

Z'F

m/m 0.186

0.173

0.117

0.113

vertical
horizontal/flat
Impedance

of the conductors
in the event of a fault
to EN 60439-2, Annex F
Zero impedance
to IEC 60909,
EN 60909 (VDE 0102)

R'0

m/m 0.144

0.114

0.116

0.079

X'0

m/m 0.199

0.225

0.124

0.130

Z'0

m/m 0.246

0.252

0.169

0.152

Short-circuit strength
Rated short-time withstand
current

rms value t = 0.1 s

ICW

kA

80

80

130

130

rms value t = 1 s

ICW

kA

58

58

116

116

Rated impulse withstand


current

peak value

IPK

kA

176

176

286

286

Copper

Conductor material
Number of busbars

L1, L2, L3

mm2

706

1022

1412

1412

PEN

mm2

706

1022

706

1412

Trunking unit without tap-off


point

kWh/
m

4.16

4.88

6.73

6.73

Per tap-off point

kWh

7.80

7.80

10.80

10.80

Conductor cross-section
Combustive energy

Max. fixing intervals


For normal
mechanical load

1) Dependent on the degree of protection and type of mounting.


2) Including adjustments in height F1.3 m.

Siemens LV 71 2005

3/55

LD Busbar Trunking System


Technical Data
LDC.4.. Trunking Units
System-dependent data

LDC 741.
PEN = L

LDC 742.
PEN = L

LDC 841.
PEN = L

LDC 842.
PEN = L

Rated current Ie1)


horizontal/edgewise2)
vertical
horizontal/flat

IP34

Ie

4400

4400

5000

5000

IP54

Ie

3200

3200

3600

3600

IP34

Ie

3500

3500

4250

4250

IP54

Ie

3200

3200

3600

3600

IP31/IP54

Ie

2600

2600

3000

3000

Resistance

R'20

m/m 0.012

0.012

0.008

0.009

Reactance

X'20

m/m 0.023

0.021

0.021

0.018

Impedance
of the conductors
at 50 Hz and +20 C
busbar temperature
of the conductors
at 50 Hz and after attaining
operational temperature
of the conductors
in the event of a fault
to EN 60439-2, Annex F

Impedance

Z'20

m/m 0.026

0.024

0.022

0.020

Resistance

R'

m/m 0.012

0.013

0.011

0.011

Reactance

X'

m/m 0.023

0.022

0.020

0.018

Impedance

Z'

m/m 0.026

0.025

0.023

0.021

Resistance

R'F

m/m 0.036

0.027

0.031

0.026

Reactance

X'F

m/m 0.090

0.086

0.073

0.080

Impedance

Z'F

m/m 0.097

0.090

0.079

0.085

Zero impedance

to IEC 60909,
EN 60909 (VDE 0102)

R'0

m/m 0.083

0.056

0.070

0.050

X'0

m/m 0.072

0.093

0.088

0.106

Z'0

m/m 0.109

0.109

0.113

0.118

Short-circuit strength
Rated short-time withstand
current
Rated impulse withstand
current

rms value t = 0.1 s

ICW

kA

130

130

130

130

rms value t = 1 s

ICW

kA

116

116

116

116

peak value

IPK

kA

286

286

286

286

Copper

Conductor material
Number of busbars

L1, L2, L3

mm2

2044

2044

2464

2464

PEN

mm2

1022

2044

1232

2464

Trunking unit without tap-off


point

kWh/
m

7.99

7.99

8.83

8.83

Per tap-off point

kWh

10.80

10.80

10.80

10.80

Conductor cross-section
Combustive energy

Max. fixing intervals


For normal
mechanical load

1) Dependent on the degree of protection and type of mounting.


2) Including adjustments in height F1.3 m.

3/56

Siemens LV 71 2005

LD Busbar Trunking System


Technical Data
LDC.6.. Trunking Units
Type

LDC.6.. system (5-conductor system)

Standards and Regulations

IEC 60439-1 and -2,


EN 60439-1 and -2 (VDE 0660 Part 500 and Part 502),
NF C 63-410 and -411,
BS 5486 Part 1 and 2,
SEV/ASE 3625-1 and 2

Climatic Proofing

Damp heat, constant ,to IEC 60068-2-78


Damp heat, cyclic, to IEC 60068-2-30

Ambient temperature, min./max./mean level over 24 hours

5/+40/+35

Degree of protection
ventilated

IP34

enclosed

IP54

Busbars edgewise in the system

Standard mounting position


Torque for single-bolt clamp terminal

Nm

80

Busbar surface treatment

Insulation-plated and tinned over the entire length

Material of trunking units, tap-off units

Powder spray paint finished steel enclosure

Color of trunking units, tap-off units

RAL 7035 (light grey)

Dimensions

See Dimension drawings, page 3/118


See page 3/64

Weight

Rated insulation voltage

V~

1000

to EN 60664-1 (VDE 0110 Part 1)

1200

Overvoltage category/pollution degree


to EN 60947

III/3

for power transmission to EN 60947

IV/3

Rated operational voltage


with vervoltage category III/3

V~

1000

with vervoltage category IV/3

V~

690

Rated frequency

Hz

16 2/3 ... 60

Siemens LV 71 2005

3/57

LD Busbar Trunking System


Technical Data
LDC.6.. Trunking Units
System-dependent data

LDC 262.
N =L

LDC 362.
N=L

LDC 661.
N = L

LDC 662.
N =L

Rated current Ie1)


horizontal/edgewise2)
vertical
horizontal/flat

IP34

Ie

2000

2600

3400

3400

IP54

Ie

1600

2000

2600

2600

IP34

Ie

1650

2100

2700

2700

IP54

Ie

1600

2000

2600

2600

IP31/IP54

Ie

1200

1550

2000

2000

Resistance

R'20

m/m 0.036

0.029

0.015

0.017

Reactance

X'20

m/m 0.043

0.037

0.027

0.027

Impedance
of the conductors
at 50 Hz and +20 C
busbar temperature

Impedance

Z'20

m/m 0.056

0.047

0.031

0.032

Resistance

R'

m/m 0.037

0.031

0.017

0.018

Reactance

X'

m/m 0.043

0.038

0.028

0.028

Impedance

Z'

m/m 0.057

0.049

0.033

0.034

of the conductors
for 5-conductor systems (PE)
in the event of a fault
to EN60439-2, Annex F

Resistance

R'F

m/m 0.081

0.060

0.062

0.058

Reactance

X'F

m/m 0.204

0.186

0.139

0.124

Impedance

Z'F

m/m 0.220

0.195

0.153

0.137

of the conductors
for 5-conductor systems (N)
in the event of a fault
to EN 60439-2, Annex F

Resistance

R'F

m/m 0.078

0.059

0.048

0.037

Reactance

X'F

m/m 0.193

0.149

0.110

0.105

Impedance

Z'F

m/m 0.208

0.160

0.120

0.112

of the conductors
at 50 Hz and after attaining
operational temperature

Zero impedance
for 5-conductor systems (PE)
to IEC 60909,
EN 60909 (VDE 0102)
for 5-conductor systems (N)
to IEC 60909,
EN 60909 (VDE 0102)

R'0

m/m 0.179

0.134

0.149

0.149

X'0

m/m 0.387

0.357

0.238

0.248

Z'0

m/m 0.426

0.381

0.281

0.289

R'0

m/m 0.150

0.110

0.119

0.080

X'0

m/m 0.189

0.180

0.145

0.135

Z'0

m/m 0.241

0.211

0.187

0.157

Short-circuit strength
Rated short-time withstand
current
Rated impulse withstand
current
Rated short-time withstand
current of the 5th conductor

rms value t = 0.1 s

ICW

kA

80

80

130

130

rms value t = 1 s

ICW

kA

58

58

116

116

peak value

IPK

kA

176

176

286

286

rms value t = 0.1 s

ICW

kA

48

48

78

78

rms value t = 1 s

ICW

kA

35

35

70

70

Copper

Conductor material
Number of busbars

L1, L2, L3

mm2

706

1022

1412

1412

mm2

706

1022

706

1412

PE

mm2

706

1022

706

706

Trunking unit without tap-off


point

kWh/
m

4.16

4.88

6.73

6.73

Per tap-off point

kWh

7.80

7.80

10.80

10.80

Conductor cross-section

Combustive energy

Max. fixing intervals


For normal
mechanical load

1) Dependent on the degree of protection and type of mounting.


2) Including adjustments in height F1.3 m.

3/58

Siemens LV 71 2005

LD Busbar Trunking System


Technical Data
LDC.6.. Trunking Units
System-dependent data

LDC 761.
N = L

LDC 762.
N=L

LDC 861.
N = L

LDC 862.
N =L

Rated current Ie1)


horizontal/edgewise2)

IP34

Ie

4400

4400

5000

5000

IP54

Ie

3200

3200

3600

3600

IP34

Ie

3500

3500

4250

4250

IP54

Ie

3200

3200

3600

3600

IP31/IP54

Ie

2600

2600

3000

3000

of the conductors
at 50 Hz and +20 C
busbar temperature

Resistance

R'20

m/m 0.011

0.014

0.012

0.012

Reactance

X'20

m/m 0.023

0.021

0.018

0.020

Impedance

Z'20

m/m 0.025

0.025

0.022

0.023

of the conductors
at 50 Hz and after attaining
operational temperature

Resistance

R'

m/m 0.013

0.015

0.013

0.013

Reactance

X'

m/m 0.024

0.022

0.020

0.020

Impedance

Z'

m/m 0.027

0.027

0.024

0.024

of the conductors
for 5-conductor systems (PE)
in the event of a fault
to EN 60439-2, Annex F

Resistance

R'F

m/m 0.048

0.050

0.045

0.048

Reactance

X'F

m/m 0.118

0.133

0.123

0.119

Impedance

Z'F

m/m 0.127

0.142

0.131

0.128

of the conductors
for 5-conductor systems (N)
in the event of a fault
to EN 60439-2, Annex F

Resistance

R'F

m/m 0.038

0.027

0.031

0.025

Reactance

X'F

m/m 0.092

0.089

0.082

0.079

Impedance

Z'F

m/m 0.100

0.093

0.088

0.083

vertical
horizontal/flat
Impedance

Zero impedance
for 5-conductor systems (PE)
to IEC 60909,
EN 60909 (VDE 0102)
for 5-conductor systems (N)
to IEC 60909,
EN 60909 (VDE 0102)

R'0

m/m 0.116

0.100

0.103

0.103

X'0

m/m 0.186

0.216

0.188

0.184

Z'0

m/m 0.219

0.238

0.214

0.211

R'0

m/m 0.087

0.058

0.072

0.050

X'0

m/m 0.105

0.112

0.093

0.091

Z'0

m/m 0.137

0.126

0.118

0.104

Short-circuit strength
Rated short-time withstand
current

rms value t = 0.1 s

ICW

kA

130

130

130

130

rms value t = 1 s

ICW

kA

116

116

116

116

Rated impulse withstand


current

peak value

IPK

kA

286

286

286

286

Rated short-time withstand


current of the 5th conductor

rms value t = 0.1 s

ICW

kA

78

78

78

78

rms value t = 1 s

ICW

kA

70

70

70

70

Copper

Conductor material
Number of busbars

L1, L2, L3

mm2

2044

2044

2464

2464

mm2

1022

2044

1232

2464

PE

mm2

1022

1022

1232

1232

Trunking unit without tap-off


point

kWh/
m

7.99

7.99

8.83

8.83

Per tap-off point

kWh

10.80

10.80

10.80

10.80

Conductor cross-section

Combustive energy

Max. fixing intervals


For normal
mechanical load

1) Dependent on the degree of protection and type of mounting.


2) Including adjustments in height F1.3 m.

Siemens LV 71 2005

3/59

LD Busbar Trunking System


Technical Data
Feeder units
Connection/feeder units and
transformer/distribution board connection

Cable connection units


Rated currents

Rated currents
The rated currents can be found in the type key on the
selection pages.

The rated currents can be found in the type key on the


selection pages.
Short-circuit strength

Short-circuit strength
The short-circuit rating corresponds to the system size of
the selected transformer/distribution board connection
unit.
Example: LDA 3423AS 1
+LD-1 A
The short-circuit rating in this case corresponds to the
LD system LDA 3423.
The limit temperature and short-circuit rating is also
determined by the connected busbar trunking system.
Degree of protection

When a transformer is connected that is not enclosed,


the connection unit has degree of protection IP00
(due to the exposed connection lugs).
When flange connected to a distribution board or
enclosed transformer, the connection unit has the
degree of protection of the board or transformer
enclosure concerned. However, the maximum
protection is IP34 or IP54.

The short-circuit rating corresponds to the system size.


Example: LDA 3423KE 1
The rated short-time withstand current Icw (Power case
value t = 0.1 s) in this case corresponds to the LD system
LDA 3423, and is 80 kA.
Degree of protection
The degree of protection for the cable entries is IP31
or IP54.
Adapters for Connection to Non-Siemens Distribution
Boards
Rated currents
The rated currents can be found in the type key on the
selection pages. Further details can be found in the
Engineering - Incoming Connections Section.
Short-circuit strength
See Engineering Incoming Connections.

3/60

Siemens LV 71 2005

LD Busbar Trunking System


Technical Data
Tap-off units with GSTA fuse switch-disconnectors
Standards and Regulations

IEC 60439-1 and -2,


EN 60439-1 and -2 (VDE 0660 Part 500 and Part 502)

Climatic Proofing

Damp heat, constant, to IEC 60068-2-78


Damp heat, cyclic, to IEC 60068-2-30

Ambient temperature,
min./max./mean level over 24 hours

5/40/35

Degree of protection
Standard

IP30

with retrofit kit

IP54

Cable enries
Multi-core cable with cabling box fitted for side
cable entry

3 cable grommets (size KT 4) for cable diameters from 14 to 68 mm


3 cable grommets (size KT 4) for cable diameters from 14 to 68 mm

Single-core cable

Aluminium plate, not drilled, for cable glands 10 x PG 29

Terminal capacity (copper)

GSTA 00 (125 A)

GSTA 1 (250 A)

GSTA 2 (400 A)

GSTA 3 (630 A)

Bolt connection

M8

M10

M10

M10

mm

min. 1 10

min. 1 25

min. 1 25

min. 1 25

mm

max. 1 95

max. 1 150

max. 1 240

max. 2 24

mm

min. 1 10

min. 1 25

min. 1 25

min. 1 25

mm

max. 1 95

max. 1 150

max. 1 240

max. 2 240

L1, L2, L3
N/PEN/PE
Color of tap-off units

RAL 7035 (light grey)

Dimensions

See Dimension drawings, pages 3/140 and 3/141

Weights

See page 3/66

Material of tap-off units

Sheet steel, tin-plated/tin-plated and painted

Rated insulation voltage Ui


to EN 60664-1 (VDE 0110 Part 1)

V~

690

800

III/3

Overvoltage category/pollution degree


to EN 60947-1
Rated frequency

Hz

50

Rated operational voltage Ue

V~

400

Rated current Ie with degree of protection

690
IP30

IP54

GSTA 00

125

100

1001)

1001)

2 GSTA 00

2 125

2 100

2 1001)

2 1001)

200

2001)

2001)
3151)
5001)

GSTA 1

IP30

IP54

250

GSTA 2

400

315

3151)

GSTA 3

630

500

5001) (630)2)

Switching capacity of the fitted


fuse switch-disconnector to EN 60947-3
Short-circuit strength
for protection by fuses Ip3)

AC-22 B
kA

AC-22 B

120

1) See IEC 60269-2-1, Table I.


2) 630 A when using fuse links of make Jean Mller,
Order type M3 gL 630/69, Article No. N306900
3) 2-pole test of the fuse switch-disconnector with three conductors
connected in series. The details apply to fuse links of make Jean Mller,
operational class gL.

Siemens LV 71 2005

3/61

LD Busbar Trunking System


Technical Data
Tap-off units with GSTZ fuse switch-disconnectors
Standards and Regulations

IEC 60439-1 and -2,


EN 60439-1 and -2 (VDE 0660 Part 500 and Part 502)

Climatic Proofing

Damp heat, constant, to IEC 60068-2-78


Damp heat, cyclic, to IEC 60068-2-30

Ambient temperature,
min./max./mean level over 24 hours

5/40/35

Degree of protection
Standard

IP30

with door (Type 2)

IP54

Cable enries
Multi-core cable (+LD-AB 4)

M12 bolt-type terminal

Single-core cable (+LD-AB 7(8))

2 x cable grommets (size KT 4) for cable diameter from 14 to 68 mm


Aluminium plate, fitted with cable gland

Number and size of cable glands

+LD-AB 7
(1 cable per phase)

+LD-AB 8
(2 cables per phase)

for cable diameter

4 PG 36

10 PG 36

21 ... 32 mm

1 PG 29

15 ... 25 mm

(for smaller cable diameters, use reduction cable glands of make Wiska)

Terminal capacity (copper)


LD-K-.AK./GSTZ 2

LD-K-.AK./GSTZ 3

mm

1 95 ... 240 or

1 300 or

mm

2 50 ... 120

2 95 ... 240

mm

1 50 ... 240 oder

1 150 ... 300 oder

mm

2 25 ... 120

2 50 ... 240

Bolt connection

L1, L2, L3
N/PEN/PE
Color of tap-off units

RAL 7035 (light grey)

Dimensions

See Dimension drawings, page 3/142

Weights

See page to 3/66

Material of tap-off units

Sheet steel, tin-plated/tin-plated and painted

Rated insulation voltage Ui


to EN 60664-1 (VDE 0110 Part 1)

V~

690

800
III/3

Overvoltage category/pollution degree


to EN 60947-1
Rated frequency

Hz

50

Rated operational voltage Ue

V~

400

690

GSTA 2

400

3151)

GSTA 3

630

5001) (630)2)

AC-22 B

AC-22 B

Rated current Ie

Switching capacity of the fitted


fuse switch-disconnector to EN 60947-3
Short-circuit strength
for protection by fuses Ip3)

kA

120

1) See IEC 60269-2-1, Table I.


2) 630 A when using fuse links of make Jean Mller,
Order type M3 gL 630/69, Article No. N306900
3) 2-pole test of the fuse switch-disconnector with three conductors connected in
series. The details apply to fuse links of make Jean Mller, operational class gL.

3/62

Siemens LV 71 2005

LD Busbar Trunking System


Technical Data
Tap-off units with circuit breakers
Standards and Regulations

IEC 60439-1 and -2,


EN 60439-1 and -2 (VDE 0660 Part 500 and Part 502)

Climatic Proofing

Damp heat, constant, to IEC 60068-2-78


Damp heat, cyclic, to IEC 60068-2-30

Ambient temperature,
min./max./mean level over 24 hours

5/40/35
IP54

Degree of protection
Cable enries
Multi-core cable
(lateral cable entry)

Size 1:
2 cable grommets (KT 3)

Single-core cable
(lateral cable entry)

Aluminium plate, not drilled, for cable glands 10 x PG 36 or 24 x M40

Terminal capacity (copper)

Size 1:
(NZM 7)
A

Rated current Ie
Bolt connection
(for single and multi-core cable)
L1, L2, L3; N/PEN/PE

max.

Size 2:
(NZM 10)

Size 3:
(3VL7)

(160 ... 250)

400

570

800 ... 1250

M8

M8

M12

M12

M12

(1)2 X (4) X (50)25

2 x (4) x 70

2 x (4) x 70

4 x (4) x 70

2 X (4) X 70
or
1 X (4) X 150

2 X (4) X 120
or
1 X (4) X 240

2 x (4) x 120
or
2 X (4) X 240

4 X (4) X 240

1 x 4(5) x 35

Color of tap-off units

RAL 7035 (light grey)

Dimensions

See Dimension drawings, pages 3/143 to 3/145

Weights

See page 3/66

Sheet steel, tin-plated and painted

Material of tap-off units


Rated insulation voltage Ui
to EN 60664-1 (VDE 0110 Part 1)

Size 3:
4 cable
grommets
(KT 4)

(80 ... 125)

min. mm2 1 x 4(5) x 16


mm2

Size 2:
2 cable grommets (KT 4)

V~

690

800
III/3

Overvoltage category/pollution degree


to EN 60947-1
Rated frequency

Hz

50

Rated operational voltage Ue

V~

400 (690)

Kurzschlussfestigkeit

Size 1:
(NZM 7)

Size 2:
(NZM 10)

Size 3:
(3VL7)

Switching capacity of the circuitbreaker

at rated operational voltage

400 (690)

400 (690)

415 (690)

Conditional short-circuit strength Icc


(values in brackets apply to 690 V)

kA

100 (10)

100 (30)

100 (35)

NEW: Standard tap-off units with Siemens circuit-breakers.


Units up to 630 A will be published in the next catalog version (2006),
as product development and tests have not yet been completed.
For preliminary solutions, please contact your product managers.

Siemens LV 71 2005

3/63

LD Busbar Trunking System


Technical Data
Weights
Trunking units
Trunking units with aluminium conductors
Specified weights are weights per metre (kg/m) for
trunking units without tap-off points to degree of
protection IP34.
LDA 1...

LDA 2...

LDA 3...

LDA 4...

LDA 5...

LDA 6...

LDA 7...

LDA 8...

LDA.413

21.7

27.4

27.4

33.7

37.2

LDA.423

16.7

20.0

20.0

22.9

29.4

29.4

36.6

40.6

LDA.613

22.9

29.4

29.4

36.6

40.6

LDA.623

17.9

22.0

22.0

24.1

31.4

31.4

39.5

44.0

An increase in weight of 7 kg per tap-off point must


be allowed for trunking units with tap-off points.
An increase in weight of 0.6 kg/m must be allowed for
degree of protection IP54.
Trunking units with copper conductors

Specified weights are weights per metre (kg/m) for


trunking units without tap-off points to degree of
protection IP34.

LDC 2...

LDC 3...

LDC 6...

LDC 7...

LDC 8...

LDC .413

60.3

82.0

100.2

LDC .423

38.8

51.2

67.0

91.8

112.6

LDC .613

67.0

91.8

112.6

LDC .623

45.5

61.0

73.7

101.6

125.0

An increase in weight of 7 kg per tap-off point must


be allowed for trunking units with tap-off points.
An increase in weight of 0.6 kg/m must be allowed for
degree of protection IP54.

3/64

Siemens LV 71 2005

LD Busbar Trunking System


Technical Data
Weights
Connection/feeder units and
transformer/distribution board connection
The weights are quoted in kg per item.
LDA 6413

LDA 6613

LDA 7413

LDA 7613

LDA 8413

LDA 8613

LDA ....-AS 1

48.2

49.8

54.1

56.0

57.6

59.8

LDA ....-AS 2

52.9

68.1

61.0

77.0

69.9

81.7

LDA ....-AS 3

57.6

78.7

67.7

89.1

72.4

94.1

LDA ....-AS 4

64.3

97.0

77.4

110.5

85.4

118.7

LDA 3423

LDA 3623

LDA 6423

LDA 6623

LDA 7423

LDA 7623

LDA 8423

LDA 8623

LDA ....-AS 1

32.4

33.9

50.6

52.1

57.0

59.0

61.3

63.5

LDA ....-AS 2

35.1

47.4

56.0

71.2

65.0

81.0

70.8

86.6

LDA ....-AS 3

37.8

55.6

61.3

82.3

73.0

94.4

78.3

99.9

LDA ....-AS 4

41.6

68.8

69.6

101.7

83.9

117.1

93.1

126.4

LDC 6413

LDC 6613

LDC 7413

LDC 7613

LDC 8413

LDC 8613

LDC ....-AS 1

86.6

91.6

105.9

112.4

117.6

124.9

LDC ....-AS 2

102.4

121.0

129.0

149.0

144.9

165.8

LDC ....-AS 3

117.6

142.1

151.1

176.9

171.1

197.8

LDC ....-AS 4

139.6

175.8

182.9

220.5

209.1

247.5

LDC 3423

LDC 3623

LDC 6423

LDC 6623

LDC 7423

LDC 7623

LDC 8423

LDC 8623

LDC ....-AS 1

65.4

71.8

94.4

99.5

116.6

123.0

130.0

137.2

LDC ....-AS 2

78.6

95.7

112.5

131.2

142.9

162.9

160.8

181.7

LDC ....-AS 3

91.2

113.8

129.9

154.4

168.1

194.0

191.1

217.8

LDC ....-AS 4

103.4

141.5

153.0

191.2

204.6

242.2

234.5

272.9

Cable connection units


The weights are quoted in kg per item.

LD.....-KE 1(2)

LD.....-KE 1(2)

LD.....-KE 1(2)

LD.....-KE 1(2)

LDA 142.

LDA 162.

LDA 242.

LDA 262.

LDA 342.

LDA 362.

85

92

85

92

107

114

LDA 441.

LDA 461.

LDA 541.

LDA 561.

115

122

135

142

LDA 442.

LDA 462.

LDA 542.

LDA 562.

117

124

137

144

LDC 242.

LDC 262.

LDC 342.

LDC 362.

115

122

127

134

Siemens LV 71 2005

3/65

LD Busbar Trunking System


Technical Data
Weights
Connection units for non-Siemens distribution boards
Aluminium conductors
4-conductor systems

Tap-off units
Tap-off units with GSTA fuse switch-disconnector

5-conductor systems

Weight
kg

Weight
kg

Weight
kg
LD-K-.AK./ST...

33

LDA 2420-FA 1

11

LDA 2620-FA 1

15

+LD-IP 54

1.5

LDA 3420-FA 1

23

LDA 3620-FA 1

32

+BD 2-800-KR

LDA 5410-FA 1

32

LDA 5610-FA 1

40

LDA 7410-FA 1

52

LDA 7610-FA 1

65

LDA 8410-FA 1

62

LDA 8610-FA 1

77

LDA 5420-FA 1

37

LDA 5620-FA 1

44

LDA 7420-FA 1

59

LDA 7620-FA 1

70

LDA 8420-FA 1

69

LDA 8620-FA 1

82

Copper conductors
4-conductor systems

Tap-off units with GSTZ fuse switch-disconnector


Weight
kg
LD-K-.AK./GSTZ.

66

+LD-T.2

Tap-off units with circuit-breaker and handle


5-conductor systems

Weight
kg

Weight
kg

Weight
kg
LD-K-.AK./LSH....-. (NZM 7)

37

LDC 2420-FA 1

26

LDC 2620-FA 1

36

LD-K-.AK./LSH....-. (NZM 10) 58

LDC 3420-FA 1

57

LDC 3620-FA 1

79

LD-K-.AK./LSH.....-LS

LDC 6410-FA 1

96

LDC 6610-FA 1

120

LDC 7410-FA 1

118

LDC 7610-FA 1

147

LDC 8410-FA 1

139

LDC 8610-FA 1

174

LDC 6420-FA 1

110

LDC 6620-FA 1

132

LDC 7420-FA 1

135

LDC 7620-FA 1

162

LDC 8420-FA 1

159

LDC 8620-FA 1

191

Tap-off units with circuit-breaker and remote drive


Weight
kg
LD-K-.AK./LSM....-. (NZM 7)

37

LD-K-.AK./LSM....-. (NZM 10) 58


LD-K-.AK./LSM.....-LS

3/66

Siemens LV 71 2005

LD Busbar Trunking System


Technical Data
Weights
Accessories
End flanges

Protective sleeves
Weight
kg

Weight
kg

LD-1 EF.H

5.50

LD-DF 1

3.20

LD-2 EF.H

6.00

LD-DF 2

3.60

LD-3 EF.H

6.20

LD-1 EF.B

8.00

LD-2 EF.B

10.00

LD-3 EF.B

10.50

Distribution board blank flanges


Weight
kg
LD-VE-BF 1

5.00

LD-VE-BF 2

6.00

Suspension bracket for horizontal suspension


Weight
kg
LD-B 1

0.40

LD-B 2

0.76

Fixing bracket for vertical fixing


Weight
kg
LD-BV (Paar)

5.50

Distribution board connection flanges


Weight
kg
LD-VEG 1 (-5)

4.60

LD-VEG 2 (-5)

5.50

Torque spanner
Weight
kg
LD-DR

1.60

Siemens LV 71 2005

3/67

LD Busbar Trunking System


Engineering
Principles
Basic technical information
Conductor material

Three mounting positions of the busbars can be distinguished:


.

LD busbar systems are avaiable with aluminium LDA and


copper LDC as the conductor material.
A special surface treatment allows the two conductor
materials to be combined with one another.
Busbar trunking systems with aluminium as the conductor material are preferred due to their lower weight and
lower costs
Horizontal, edgewise

LDA busbar trunking systems with aluminium conductor


material
Aluminium busbar
Layer of nickel, tin coating
Insulation with high thermal stability

Horizontal, flat

Vertical

Degree of protection and rated current


LDC busbar trunking systems with copper conductor material
Copper busbar
Tin coating
Insulation with high thermal stability

With degree of protection IP54 with plain top plates,


a reduction of the rated current must be taken into
account, also due to temperature rise conditions (see
Technical data section).

Mounting position and rated current

In this case, a distinction between the horizontal/edgewise and vertical mounting positions is not required.

he rated current of the LDA/LDC system depends on the


mounting position of the busbars inside the trunking
unit.
The highest rated current is possible in the horizontal,
edgewise position with IP31 degree of protection and
perforated top plates.
For flat mounting, vertical mounting or increases in
height > 1.3 m, the rated current is lower, due to temperature rise conditions (see the Technical Data section).

3/68

Siemens LV 71 2005

LD Busbar Trunking System


Engineering
Principles
Number of busbars and phase sequence
The LD busbar trunking system is available in two sizes.
The design of the busbar pack depends on the size, the
supply system type and the application in question. With
respect to the supply system, 4- and 5-conductor systems
are distinguished.

The PEN or N cross-section depends on the application in


question and can be selected as a full (L) or half ( L)
phase cross-section.

Size

4-conductor

5-conductor

80 mm 180 mm

PEN = L

N=L

LDA 1.2. to LDA 3.2.


LDC 2.2. to LDC 3.2.

PEN

N PE

L1 L2 L3

240 mm 180 mm

L1 L2 L3

PEN = L

LDA 4.1. to LDA 8.1.


LDC 6.1. to LDC 8.1.

N=L

PEN

3
L11 L21 L31

L32 L22 L12

PEN = L
LDA 4.2. to LDA 8.2.
LDC 6.2. to LDC 8.2.

PE

L11 L21 L31

L32 L22 L12

N=L

PEN PEN

L11 L21 L31

L32 L22 L12

N N

L11 L21 L31

PE

L32 L22 L12

The cross-section depends on the rated current and


has been selected here as an example.

Siemens LV 71 2005

3/69

LD Busbar Trunking System


Engineering
Principles
Type definition of trunking units
When selecting an LD trunking unit, the system size
(LDA(C)...) and the type must be defined.
The system size is governed by the rated current required.
The rated current depends on the position of the busbars
within the trunking unit, such as horizontal or edgewise.
See also the Engineering Connectin/Feeder Unit section,
Mounting position of LD connection/feeder units.
The critical factors for type definition are:
Position of the hook and the single-bolt terminal block
Position of the PEN
for 4-pole systems
LDA 142. to LDA 342.
and
LDC 242. to LDC 342.
Position of L12
for 4-pole systems
LDA 44.. to LDA 84..
and
LDC 64.. to LDC 84..
Position of the PE
for 5-pole systems
LDA 162. to LDA 862.
and
LDC 262. to LDC 862.

Mark hook end by or depending on the direction in


which the hook opens.
Mark bolt end (single-bolt clamp terminal) by .
Nut for the single-bolt clamp terminal, always on the side of
the PE(N) or L12
Trunking unit length (without flange cover)
The position of the PE(N) or L12 is marked with a thick solid
line on the unit, and is always on the right when viewed with
the open hook pointing downwards.

3/70

To determine the type, the trunking unit must mentally


be turned to the original position illustrated. The hook is
open at the bottom, PE(N) or L12 is to the right, and the
busbar run points away from the viewer
V

Junction unit to
V = the front
H = the rear
R = the right
L = the left

Straight trunking units

Direction of view

Siemens LV 71 2005

Straight trunking units may be ordered as standard or


optional lengths. They may be with or without tap-off
points. A trunking unit with double bolts may be ordered
only as an optional length, and is designated -J-.
Designitions

Examples

Straight trunking unit,


standard length

LDA(C).... -3,2

Straight trunking unit,


optional length

LDA(C).... -1W0,85

Straight trunking unit,


standard length
+ 3 coded tap-off points

LDA(C).... -K-3,2-3AD

Straight trunking unit,


optional length
with double bolt

LDA(C).... -J-2W1,1

Straight trunking unit,


with extension compensation

LDA(C).... -D

Straight trunking unit,


Standard vertical length

LDA(C).... -V-3,2

LD Busbar Trunking System


Engineering
Principles
X-/Y-/Z-lengths for trunking units
Junction unit limbs have a fixed designation:
Hook end: X-length
Bolt end: Y-length
The third dimension is the Z length
(if appropriate).

For Z and U units, the type is governed by the direction of


the Z length:
Y

Examples of type definition


Z

For simple changes in direction, the type designation is


governed by the direction of the Y-length.
Offset junction units are governed by the direction of the
Y-lengths and the offset position.

Z/U units
e. g.: -ZV

Direction of the Z length


Z unit

For T units, the basic unit and the branch unit are considered separately from one another
Elbow or knee junction unit
e. g.: -LR

T-AD

Direction change to the right


Elbow or knee

T-ADU

V
R

Offset change in direction


e. g.: -LHL
Direction of the offset
Direction of the Y length
Elbow or knee

T units
Viewed in the direction of the basic unit
Viewed in the direction of the branching unit
e. g.: LDA(C)....-T-ADU-TVR
Direction of the offset
Direction of the Y length
T branching unit
T tap-off below
T basic unit

For basic units, the position of the branch point for TADU, T-AD units must be considered. The branch units
are regarded as an offset change in direction.

Siemens LV 71 2005

3/71

LD Busbar Trunking System


Engineering
Principles
Basic
unit

Branching unit

Basic
unit

-TVR

LDA(C)...T-ADU

-T

Branching unit

0,5 m

-T

LDA(C)...T-AD

0,3 m

-TVL

0,5

Basic unit with branching unit above

3/72

Siemens LV 71 2005

Basic unit with branching unit below

LD Busbar Trunking System


Engineering
Principles
Type definition of trunking units with tap-off points
Tap-off points are provided only on straight trunking
units. The type is designated by stating the trunking unit
length and the surface(s) on which the tap-off point(s) is/
are required:
AD = tap-off point above
ADU = tap-off point below
ADO+U = tap-off point above and below
Only one tap-off unit may be fitted at the same tapoff point even on -ADO+U.
Optional tap-off points must be at least 0.6 m away
from the unit end.

4-pole

AD

ADU

5-pole

Hook end
Bolt end
Unit length
Coding bracket
Tap-off point
PE(N) or L12
Position of the tap-off point(s)

Designitions

Examples

Standard length,
3 tap-off points above

LDA(C).... -K-3,2-3AD

Standard length,
3 tap-off points below

LDA(C).... -K-3,2-3ADU

Optional length,
1 tap-off point each above and
below

LDA(C).... -K-1W1,4-ADO+U

Coding brackets are arranged on both sides of the


trunking units, at the tap-off points.
This ensures that tap-off units LD-K-.AK.... equipped with
mating elements can be allocated to the respective busbar system (busbar run) without risk of incorrect connection.
For safety reasons (to preclude incorrect connection),
LDA/LDC trunking units with tap-off points must not
be combined with LD trunking units having uncoded
tap-off points of an earlier type.

Siemens LV 71 2005

3/73

LD Busbar Trunking System


Engineering
Principles
Offset, double bolt
The offset designates the offset of the hook in relation to
the busbar pack within the double-bolt trunking unit to
allow correct insertion in the single-bolt clamp terminal
and to ensure that the phases cannot be incorrectly connected.

Case 1
1

Where the busbar run starts and ends with a single-bolt


clamp terminal, e. g. for distribution board/distribution
board connections or transformer/distribution board connections, a double-bolt element is required somewhere in
the busbar run.

No trunking unit with a double bolt is required for busbar runs that end with an end flange.

L3

L2

L1

L1

L2

NSV0_00585

L3
Mounting sequence
Double-bolt unit
Case 2

NSV0_00584

2
1

Front

NSV0_00586

With an offset, the direction of the hook position


changes. Therefore the point at which the double-bolt is
positioned is important for installation.
Case 1: Insert the bolt end from above into the hook
end which is open upwards.
Case 2: Fit the hook end which is open at the bottom
into the bolt end from above, ensuring that the phase
positions are the same.

Mounting sequence
Double-bolt unit

3/74

Siemens LV 71 2005

LD Busbar Trunking System


Engineering
Principles
Clearance from structural bodies
Installation of horizontal busbar runs

0,3 m

min. 0,34 m 1)
min. 0,4 m 2)

min. 0,3 m

min. 0,18 m

1) For LD.1 to LD.3


2) For LD.4 to LD.8

The minimum distance is 0.18 m for IP31 systems and 0.20 m for IP54.
Part of the building structure
Aperture for the busbar trunking run
Trunking unit connection point at minimum clearance from structural surface
LD(-K) run
Tap-off below
Tap-off unit
Tap-off above
Minimum clearance depends on size of tap-off unit used

The minimum clearances quoted must, in all circumstances, be observed so that the trunking unit can be fitted together and the single-bolt clamp terminal tightened. The minimum clearances take account of the
dimensions of the torque spanner.

Clearance to the ceiling

Dmin. = 0.18 m

Clearance to the wall

W min. = 0,1 m

The minimum wall clearance Wmin depends on:


The position of the screw for tightening the single-bolt
clamp terminal. The minimum space requirement is
0.1 m.
The dimensions of the tap-off unit chosen for power
distribution.

The minimum ceiling clearance Dmin depends on:


The dimensions of the tap-off unit chosen for power
distribution. It must still be possible to open the door/
top cover of the tap-off unit and to install/remove the
tap-off units.
The ventilation of the system. The minimum clearance
to ensure adequate ventilation is 0.18 m.
The facility to install/remove the trunking units. The
minimum clearance required for the manoeuvre corresponds to the trunking unit height of 0.18 m.

Siemens LV 71 2005

3/75

LD Busbar Trunking System


Engineering
Principles
Installation of vertical busbar runs

b
W2 min.

250

20 120

LD-BV

50

50

W1 min.

Tap-off unit
LD-BV fixing bracket for vertical fixing

60

200

The minimum wall clearance W1min at the side depends


on:
The dimensions of the tap-off unit chosen for power
distribution.
The space required for installation/removal of the
trunking units:
At least 0.1 m must be allowed for the torque spanner.
The fixing screws for the vertical fixing brackets must
still be adequately accessible.

a
View from the front

The minimal wall clearance W2min depends on:


The adjustment range of the vertical fixing bracket
(min. 0.02 m) to compensate for wall unevenness.
Any fixing material required on site, such as a C section. The choice of the appropriate C section is dictated by the respective load. The fixing brackets can
also be fixed directly on the wall, provided the wall is
not uneven.

3/76

Siemens LV 71 2005

min.20

LD system
To be supplied on site

Type

LDA 1-LDA 3
LDC 2-LDC 3
LDA 4-LDA 8
LDC 6-LDC 7

300

Depending on the
required C profile

357

LD Busbar Trunking System


Engineering
Dimensioning of busbar runs, production of parts lists
Project management
Engineering is split into six steps.

Decide on and draw busbar runs

Example: Engineering of busbar trunking systems for a


factory floor.

Draw a scale plan view of the busbar layout on the


floor plans. Coordinat the busbar layout with other
equipment installers involved.
Transfer the dimensions decided on to an isometric
representation.
Pay attention to the usefulness of the tap-off points,
since these must be engineered in the LD system. Take
note of the minimum intervals required for fitting the
corresponding tap-off units.
When engineering the horizontal busbar runs, pay
attention to the PE(N) position for LDA(C)1 to LDA(C)3
or the L12 position for LDA(C)4 to LDA(C)8 for vertical
mounting.

Determine and check building dimensions


Procure floor plans to scale.
Check drawing dimensions on site.
Record dimensions on site if no floor plans are available.
Immediately after receipt of order, make order reservation in the production factory.

200 mm

200 mm

15,88 m
20,00 m

Distribution board (front)


Craneway
Ventilation
Furnace system (exhaust pipe)

7,68 m

7,68 m

21,0 m

21,0 m

15,88 m
20,00 m
Spacing of distribution boards
Room width
LD busbar run

Define interfaces and links


Interface discussions
Discuss with the customer about technical requirements and physical configurations, floor plans etc.
To be held with other equipment installers (heating,
ventilation, sanitation, transformer suppliers) with
regard to dimensioning, lug spacings and precise locations.
To be held with distribution board suppliers/builders: provide connection units for non-Siemens distribution boards in good time.
Obtain information about fire divisions.

Siemens LV 71 2005

3/77

LD Busbar Trunking System

NSV0_00587

Engineering
Dimensioning of busbar runs, production of parts lists

3
Engineer the branch and junction points
Engineer complex direction changes first:
If necessary, produce a section drawing
Clarify customized solutions (special solutions) immediately with the specialist department.

500

200

Special solutions have longer lead times and are more


expensive than standard units, since the cost for clarification, ordering and production is higher than for standard
units.

200

500

min. 110

min. 110

max. 510

max. 510

300

180

1480

Engineer simple direction changes:


For simple horizontal/vertical direction changes use
standard types with standard lengths.
Preferably engineer optional lengths using straight
trunking units.

3/78

Siemens LV 71 2005

180

LD Busbar Trunking System


Engineering
Dimensioning of busbar runs, production of parts lists
Use straight lengths to complete the run

Only straight optional lengths should be used.

Fill the sections between the branch and junction


points using standard lengths.
Last of all measure up for the custom lengths required.
Limit their number to the minimum in order to avoid
longer lead times.

The fewer the number of optional lengths used, the


shorter is the lead time.
Order optional lengths immediately, as construction
progresses.

50
0
00

13

00

86

00

00

2
00

00

500

1000
500

50

42

00
50

500

50

98

50

00

0
40

50

500

50

22

00

50

00

500

10

3
NSV0_00589

1800

1800

185

2020

00

50

185

1200

50

500

00

42

50

00

500

1000

12

50

Siemens LV 71 2005

3/79

LD Busbar Trunking System


Engineering
Dimensioning of busbar runs, production of parts lists
Produce the parts list

86

00

00

0
13

00

9
7

1000

1000

16

6
6

00

50

98

17

11
0

00

13

10

2020

7
12

15

14

1800

185

1800

3
Sequence to be followed:
Enter the dimensions of the connection/feeder units,
straight trunking units, branch and junction points and
tap-off points etc. on the run.
Define types
Produce parts list
(same types = same Item No. = 1 line in the parts list)

Siemens LV 71 2005

NSV0_00590

185

42
7
34

3/80

00
5
2W 20
0
*

50

20
22

00
9

500

0
20

20

2W

1200

10

Item No.

Type

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17

LD-VEG 2
LDA 4413-J-1W0,52
LDA 4413-LH
LDA 4413-1W0,8
LDA 4413-2,4
LDA 4413-LV
LDA 4413-3,2
LDA 4413-D
LDA 4413-LR
LDA 4413-2W*
LDA 4413-LL
LDA 4413-4W2,6
LDA 5413-LH
LDA 5413-2W1,34
LDA 4413-LV-X0,98
LDA 4413-3W2,0
LDA 4413-2W*
LD B2
LD BV
LD DR

Quantity
2
1
4
1
3
2
7
1
3
1
1
1
1
1
1
1
1
10
2
1

LD Busbar Trunking System


Engineering
Dimensioning of busbar runs, production of parts lists
Order processing
If appropriate, agree staged deliveries for large orders.
Always mark parts with the Drawing Item No., in order
to ensure identification at the construction site.
When orders are awarded
Match delivery dates to the various construction
phases/construction progress.
Ensure delivery for installation at different points on
the construction site by structured busbar run designation or staggered ordering.
Customized special solutions (SOND)
Contact the specialist department about the order
data immediately after the order is awarded, and have
them specify the details (allocation of the Version No.).
Immediately after order clarification, order in accordance with the applicable procedure sequence and, in
parallel with this, send one copy of the order to our
specialist department.
Customized special solutions always have longer lead
times.

Customized lengths
Order when contract awarded
When the length range is known (1W*, 2W*, 3W*
oder 4W*), place order without dimensions with the
note custom length, precise dimension to follow
and quote the contract number of the order already
awarded.
Once the exact dimension is known, this is passed on as
binding.
Place order after exact definition of dimensions, in a
separate order.
Order documents
The order documents comprise:
SOP/SAP ordering sheet
Parts list
Engineering drawing with drawing reference numbers
of the parts
SOND documents for our specialist department.

Siemens LV 71 2005

3/81

LD Busbar Trunking System


Engineering
Connection Units
LD connection/feeder units
System sizes

Application

LD.3... for LD.1 to LD.3


LD.6... for LD.4 to LD.6
LD.7... for LD.7
LD.8... for LD.8.

LD connection/feeder units are used for transformer connection and for distribution board connection for AS 1
(see page 3/86).

For each system size, there are four sizes of connection/


feeder units in order to produce the various lug spacings:
AS1, AS2, AS3 and AS4 as well as AS1-T, AS2-T, AS3-T and
AS4-.T.

The connection/feeder units AS.-T with T branch are connected to the trunking units via VEG, VEV and VEH distribution board connection units.
Other applications are shown on the following pages.

NSV0_00511

Equipment
The AS connection/feeder unit is equipped as standard
with
Connection lugs
See the Dimension Section for the alignment as supplied. Conversion to larger lug spacings is possible on
site.
LD-VEG 1(2)
The flange cover of the trunking unit to be connected
is omitted during installation. The VE knee can be fitted on site, if required, to replace the factory-fitted
VEG. See the following pages in this context.

5m

72

LD....-AS1(-T)

NSV0_00512

G_NSV0_XX_00519

85

mm

10

3 x 190 - 280

LD.....-AS2(-T)

NSV0_00513

Connection lugs as supplied


Example: LD.....-AS 2.
As supplied = lug spacing range 1 (190 ... 280 mm)

G_NSV0_XX_00520

30

mm

14

3 x 285 - 380

LD....-AS3(-T)

NSV0_00514

After being changed on site


Variable on site = lug spacing range 2 (285 ... 380 mm).

30

mm

19

LD....-AS4(-.T)

3/82

Siemens LV 71 2005

LD Busbar Trunking System


Engineering
Connection Units
Suspension
As for LD trunking units, LD suspension brackets (LD-B.)
may be used for suspension.

The rated current must be reduced for connection with


transformer connection lugs pointing upwards, for example for flange connection to a distribution board from
below (on request).

Suspension is possible from the 40 mm diameter holes in


the end plates (see Dimensions Section). The holes may
be used as a transport aid.
8
51
00

E_

_D

0
SV

G_

51

00

N_

_E

0
SV

G_

The distribution board connection flange VEG, which is


supplied fitted ex-works, can be replaced on site by a VE
knee LDA(C)...-VEV(H) or an offset VE knee LDA(C)...-VE..

LD-B

LD-VEG 1(2)

Connection lugs

Lug spacings can be provided for braided cables links and


copper busbar widths 120 mm.

G_NSV0_XX_00521

Mounting position of LD connection/feeder units


The rated currents on the selection pages apply to a vertical mounting position with transformer connection lugs
pointing downwards.

6
51
00
E_
_D
V0
S
N
G_

295

185

"X"

The rated current must be reduced for connections where


the busbars are flat, e. g. for side flange connection to a
distribution board enclosure (on request).

7
51
00
E_
_D
V0
S
N
G_

Siemens LV 71 2005

3/83

LD Busbar Trunking System


Engineering
Connection Units
The position of the PE connection lug must be noted.

Positioning above transformers

The position depends on the offset of the LD connection and is defined by the type suffix +LD-1 or -2.

LDA(C)...-AS1(-T) +LD-... and LDA(C)...-AS2(-T) +LD-...


The LD connection feeder unit box must always be
positioned centrally above the transformer connection
lugs.
The reference dimension for engineering is
b = 362.5 mm = centre AS 1(-T)

View "X"

G_NSV0_EN_00522

120

Where the transformer is connected using braided cables,


the connection between the transformer connection lugs
and the LD connection/feeder units uses braided cables.
These must be provided on site and may be obtained, for
example, from the following address:
Fa. Homa GmbH & Co. KG
Essener Str. 2 10
D-46047 Oberhausen
Phone: x49-2 08-85 96 03

13,5

40
20

85

115

50 or 60

LD...6.-AS. +LD-1.
b

185

View "X"

G_NSV0_EN_00523

LD...6.-AS. +LD-2.

max. 200

a
G_NSV0_XX_00524

3/84

Siemens LV 71 2005

Type

LDA(C)...-AS 1 +...

150 ... 180

362.5

LDA(C)...-AS 2 +...

190 ... 380

542.5

LD Busbar Trunking System


Engineering
Connection Units
LDA(C)...-AS3(-T) +LD-...
The LD connection feeder unit must always be positioned centrally with the L2 lug above the L2 transformer connection lug.
The reference dimension for engineering is 715 mm.

LDA(C)...-AS4(-.T) +LD-...A (C)


The LD connection/feeder unit must always be positioned centrally with the L3 (L1) lug above the L3 (L1)
transformer connection lug.
The reference dimension for engineering is 365 mm.
1265

1015
415

185
185

365

715

L2
N
L2
450 750

450 750

150 350

c
450 750

LDA(C)...-AS4(-.T) +LD-...B(D)
The LD connection/feeder unit must always be positioned centrally with the L3 (L1) lug above the L3 (L1)
transformer connection lug.
The reference dimension for engineering is 1565 mm.
665
185

1565

L2
N
150 350

450 750

450 750

NSV0_00527a

NSV0_00525a

d
450 750

NSV0_00526a

Siemens LV 71 2005

3/85

LD Busbar Trunking System


Engineering
Connection Units
AS1(-T) LD connection/feeder units as a transformer/
distribution board connection
Application
AS 1 LD connection/feeder units are used as a connection
for LD systems fully enclosed transformers and for connection to non-Siemens distribution boards to degree of
protection IP34. Degree of protection IP54 is available on
request. The lugs have a degree of protection of IP00
Engineering
Select the LD connection/feeder unit based on the
desired phase sequence for the cables to be connected
and the PE(N), L12 position for LD connection.
Quote the type suffix +LD-FLP if the LD connection/
feeder unit is to be equipped at the factory with an
aluminium flange plate for mounting on the transformer/distribution board enclosure.
The enclosure cutout for the transformer or distribution board as well as the fixing holes must be in accordance with the dimension details from the Dimensions
Section.

In order to connect the LD connection/feeder unit, it


may be expedient for the copper to be applied
directly to the basic lugs.
The connection lugs fitted at the factory can be
removed. See the Dimensions section for dimension
details relating to the basic lugs, and the hole pattern.
The rated current must be reduced for connection
from the side or below: on request.
Example

3/86

Siemens LV 71 2005

LD Busbar Trunking System


Engineering
Connection Units
LD connection/feeder units with T branch
Application
The AS.-T LD connection/feeder units with a T branch are
used when a direct branch at the top is required, but
there is lack of space.
Engineering
For connecting the AS.-T unit to the trunking unit, an
VEG, VEV or VEH distribution board connection unit has
to be engineered.

L2

Siemens LV 71 2005

3/87

LD Busbar Trunking System


Engineering
Connection Units
Cable connection units
Application

LD...

LDA (C)...-VEV (H).

For feeding LD busbar systems when a cable connection is


unavoidable.
Description
Rated currents from 1100 A to 2600 A (IP 31),
900 A to 2100 A (IP 54)
Degrees of protection IP 31 and IP 54
Choice of the desired cable connection unit from the
selection pages
Cable connection directly to the connection busbars of
the cable connection unit (bolt terminal) for connection of

4 multi- or single-core cables


(up to 300 mm2)

LDA 1...-KE. to LDA 2...-KE.

6 multi- or single-core cables


(up to 300 mm2)

LDA 3...-KE. to LDA 4...-KE.


LDC 2...-KE.

8 multi- or single-core cables


(up to 300 mm2)

LDA 5...-KE.
LDC 3...-KE.

LD-VEG 1 (2)

3 system-dependent enclosure sizes:


Enclosure size1

LDA 1...-KE. to LDA 2...-KE.

Enclosure size 2

LDA 3...-KE. to LDA 4...-KE.


LDC 2...-KE.

Enclosure size 3

LDA 5...-KE.
LDC 3...-KE.

Standard version with metal flange plate and cable


grommets
For single-core cables, an undrilled aluminium plate is
provided ex-works (type suffix)
Connection options via LD-VEG 1(2) + trunking units or
LDA(C)....-VEV (H), LDA(C)...-VEV (H).-.

3/88

Siemens LV 71 2005

M12 bolts for cable connection are supplied as standard.


LD-VEG 1(2) is not supplied as standard with the cable
connection unit

LD Busbar Trunking System


Engineering
Connection Units
Distribution board connection
Connection to Siemens SIVACON 8PV and 8PT power
distribution boards
Connection options
An LD connection may be made from above or below.
The connection system of the SIVACON 8PV, 8PT is
located inside the distribution board.
Special distribution board connection units with a metal
rim, LDA(C)...-VEU-..., are required for connection.

The connection is made with straight, angular or offset


distribution board connection units. The position of the
connecting system inside the distribution board is of the
flat type, viewed from the front of the distribution
board.
Rated currents
During engineering, it must be remembered that the
rated currents of the distribution boards are not necessarily the same as those of the chosen busbar system.

NSV0_00528

Distribution board front


SIVACON distribution board, view from top

Connection to non-Siemens power distribution boards

(For dimensions b and d see tables, next page)

Connection options
Since the field of operation relates to customized solutions, early agreement with the distribution board manufacturer is necessary.

PE at the rear

Rated currents

121

Whoever designs and installs the connections between


the distribution board connection unit (Siemens product)
and the distribution busbars of the non-Siemens distribution board, as a rule the distribution board manufacturer,
is responsible for this work.

The rated currents can be found from the type key on the
selected pages. These details are based on IEC 60439-1
and -2 for an ambient temperature of 35 C averaged
over 24 h. The temperature limit of the insulated busbars
is 135 C.
When using FA1 adapters for connection to non-Siemens
distribution boards in distribution board installations, it is
necessary to ensure that the temperature limit is not
exceeded.
The terminal capacity for the copper connections can be
found in the Dimensions Section.

The short-circuit rating of FA1 adapters for connection to


non-Siemens distribution boards is governed by the copper connections in the distribution board installation.
Only the distribution board manufacturer can provide
the verification of the short-circuit rating of the distribution busbars.

NSV0_00529

Short-circuit strength

SIVACON distribution board, view from the front, cross-section

The FA1 unit for connection to non-Siemens distribution


boards is supplied as a type-tested unit.
The rating of the copper connections must be matched to
the required short-circuit level.

Siemens LV 71 2005

3/89

LD Busbar Trunking System


Engineering
Connection Units
Assembly type

SIVACON 8PV

Circuit-breaker size

Column width [mm]

400

500

600

600

800

800

1000

LDA(C)1 ... 3

210.5

210.5

210.5

208.5

LDA(C)4 ... 8

203

203

203

203

LDA(C)1 ... 3

200

250

300

300

LDA(C)4 ... 8

300

400

420

520

Assembly type

SIVACON 8PT, main busbars on top, main distribution board

Circuit-breaker size

Column width [mm]

400

600

600

800

800

1000

LDA(C)1 ... 3

832

832

1005.5

1005.5

LDA(C)4 ... 8

1000

1000

1000

1000

LDA(C)1 ... 3

200

335

330

460

LDA(C)4 ... 8

330

460

400

605

Assembly type

SIVACON 8PT, main busbars on top, sub distribution board

Circuit-breaker size

Column width [mm]

400

600

600

800

800

1000

LDA(C)1 ... 3

832

832

805.5

805.5

LDA(C)4 ... 8

800

800

1000

1000

LDA(C)1 ... 3

200

335

330

460

LDA(C)4 ... 8

330

460

400

605

Assembly type

SIVACON 8PT, main busbars at the rear

Circuit-breaker size

Column width [mm]

400

600

600

800

LDA(C)1 ... 3

284,5

284,5

284.5

284.5

LDA(C)4 ... 6

270.5

270.5

LDA(C)1 ... 3

200

335

320

450

LDA(C)4 ... 6

320

450

3/90

Siemens LV 71 2005

LD Busbar Trunking System


Engineering
Fire barrier
General
The fire barrier consists of an inner and an outer part.
The fire resistance class of aluminium and copper systems
conforms with S 120 to DIN 4102 Part 9. Busbar trunking
systems with fire barriers can only be supplied ex-works.

Junction units

It is not possible to retrofit the fire barrier.

X
LX

Dimensions
Straight trunking units

WJ

d
b

LY

W
LX

a
b

LY

c
Fire barrier
Centre of fire wall = centre of fire barrier
Fire wall thickness up to 0.48 m for LD.1 to LD.7 or
0.68 m for LD.8.
Fire barrier for greater wall thicknesses on request.

LD.1... to
LD.7...
m

LD.8...
m

Elbow
Fire barrier
Centre of fire wall = centre of fire barrier
Fire wall thickness up to 0.48 m for LD.1 to LD.7 or
0.68 m for LD.8.
Fire barrier for greater wall thicknesses on request.
Please note: the fire barrier cannot project beyond the inner
edge of the trunking unit.

LD.1... to
LD.3...
m

LD.4... to
LD.7...
m

LD.8...
m

Leg length

0.86 ... 1.24

0.92 ... 1.24

1.12 ... 1.24

Leg length

0.90 ... 1.24

0.96 ... 1.24

1.16 ... 1.24

0.48

0.48

0.68

Minimum
optional length

0.92 ... 1.24

1.12 ... 1.24

Fire barrier
length

min. 0.44

min. 0.44

min. 0.54

WJ

0.96 ... 1.24

1.16 ... 1.24

Fire barrier
position

LX

Minimum
optional length

min. 0.48

min. 0.48

min. 0.58

0.48

0.68

Fire barrier
position

LY

Fire barrier
length
Fire barrier
position

LX

min. 0.44

min. 0.54

Fire barrier
position

LY

min. 0.48

min. 0.58

The fire barrier cannot project beyond the inner edge


of the trunking unit.

Siemens LV 71 2005

3/91

LD Busbar Trunking System


Engineering
Fire barrier

X
LX

a
b

LY

LY

LX

Knee
Fire barrier,
centre of fire wall = centre of fire barrier
Fire wall thickness up to 0.48 m for LD.1 to LD.7 or
0.68 m for LD.8.
Fire barrier for greater wall thicknesses on request.

LD.1... to
LD.3...
m

LD.4... to
LD.7...
m

LD.8...
m

Leg length

0.86 ... 1.24

0.92 ... 1.24

1.12 ... 1.24

Leg length

0.90 ... 1.24

0.96 ... 1.24

1.16 ... 1.24

0.48

0.48

0.68

LD.1... to
LD.7...
m

LD.8...

Fire barrier
length
Fire barrier
position

LX

min. 0.44

min. 0.44

min. 0.54

Fire barrier
position

LY

min. 0.48

min. 0.48

min. 0.0.58

Leg length

0.86 ... 1.24

1.06 ... 1.24

Leg length

0.90 ... 1.24

1.10 ... 1.24

Fire barrier
length

0.48

0.68

Fire barrier
position

LX

min. 0.44

min. 0.54

Fire barrier
position

LY

min. 0.48

min. 0.58

The fire barrier cannot project beyond the inner edge


of the trunking unit.

3/92

Knee, offset
Fire barrier
Centre of fire wall = centre of fire barrier
Fire wall thickness up to 0.48 m for LD.1 to LD.7 or
0.68 m for LD.8.
Fire barrier for greater wall thicknesses on request.

Siemens LV 71 2005

The fire barrier cannot project beyond the inner edge


of the trunking unit.

LD Busbar Trunking System


Engineering
Fire barrier

a
b

LZ

Elbow, offset, with variable Z dimension and fire barrier


Please note: the fire barrier cannot project beyond the inner
edge of the trunking unit.
Fire barrier,
centre of fire wall = centre of fire barrier

LD.1... to
LD.3...
m

LD.4... to
LD.7...
m

LD.8...

Leg length

0.5

0.5

0.5

Leg length

0.5

0.5

0.5

Leg length

0.84 ... 1.30

0.90 ... 1.30

1.10 ... 1.30

Fire barrier
length

0.48

0.48

0.68

Fire barrier
position

LZ

min. 0.42

min. 0.42

min. 0.52

The fire barrier cannot project beyond the inner edge


of the trunking unit.
The dimension to the centre of the fire barrier for the
type suffix +LB-A...-Z* must always be stated from the
hook end.

Siemens LV 71 2005

3/93

LD Busbar Trunking System


Engineering
Fire barrier
Positioning
Positioning in the fire wall
Type suffix

Fire barrier class


LDA 1 to LDA 3

120 A

LDA 4 to LDA 8

120 B

LDC 2 to LDC 3

120 A

LDC 6 to LDC 8

120 B

To be inserted
into fire barrier
type suffix

+LD-L....-X*
+LD-L....-Y*
+LD-L....-Z*

System

Positioning in the fire ceiling

1)

..12

20.

1) After mounting the busbar run in the fire wall/fire ceiling,


any gaps must be filled with mortar or concrete. The mortar
or concrete must comply with the appropriate standards for
maintaining the fire resistance class of the wall or ceiling,
e. g. DIN 1045 and DIN 1053 Part 1.

Dimensions of the ceiling or wall aperture


.

a
mm

b
mm

L
mm

LD.1... to LD.3...

400

400

480

LD.4... to LD.7...

450

400

400

LD.8

450

400

680

1)

PE(N)/ L12
1) After mounting the busbar run in the fire wall/fire ceiling,
any gaps must be filled with mortar or concrete. The mortar
or concrete must comply with the appropriate standards for
maintaining the fire resistance class of the wall or ceiling,
e. g. DIN 1045 and DIN 1053 Part 1.

L/2
L

Centre fire barrier is always the centre of the fire


ceiling.

3/94

Siemens LV 71 2005

LD Busbar Trunking System


Engineering
Expansion compensation and fixed point
D

Overview
The heat losses when on load cause the busbars to
expand in the trunking unit. To compensate for this
length expansion, the tightly screwed busbar pack is held
loosely in the trunking unit. Expansion compensation and
fixed point must be provided for longer, straight busbar
runs.
A distinction is drawn between three situations for engineering here:
Horizontal run
Engineering of adjustments in height
Vertical run
Horizontal busbar runs

The maximum busbar length which may be laid between


a natural fixed point and a busbar end without expansion
compensation, is 25 m.
Natural fixed points include all points of change in direction, such as
Elbow
Knee
Z units (flat, edgewise)
U units.
At natural fixed points within the maximum permissible
busbar lengths mentioned above, the busbar pack can
expand into the junction unit(s) or the end flange.
Engineered fixed points

Natural fixed points

The busbar pack is firmly connected to the enclosure, in


the factory, by the fixed point at the single-bolt clamp
terminal (type suffix +LD-FP).
+LD-FP

LD.....-D

0
10.

2,0

1
ca.
1,2
ca.

x.
ma

0m

25,

0m

12,

 Natural fixed point

The maximum busbar length that may be laid between


two natural fixed points without expansion compensation, is 10 m.
LD-.EF.-H

 Natural fixed point

The maximum busbar length which may be laid with


expansion compensation between a natural fixed point
and an engineered fixed point, is 25 m.
The expansion compensation must be located as centrally as possible between two fixed points.

x.
ma

0m

25,

a
 Natural fixed point

Siemens LV 71 2005

3/95

LD Busbar Trunking System


Engineering
Expansion compensation and fixed point
+LD-FP
LD-.EF.-H

LD-D
2,0

1
ax.

m
5,0

2
ax.

m
1,2

x.
ma

+LD-FP

+LD-FP
x.
ma

0m

25,

0m

12,

The maximum busbar length which may be laid with


expansion compensation between two engineered fixed
points, is 25 m.

The maximum busbar length which may be laid without


expansion compensation between an engineered fixed
point and the busbar end is 25 m.


3
m
3,2
3,2
1,2
3,2

+LD-FP
2,8
3,2
3,2
3,2
3,2
1,2
3,2
,5 m

3,2

0,5

00

35,


 Natural fixed point

Where a run is longer than 25 m, correspondingly more


expansion units and fixed points must be engineered.
Run length
m

Fixed points

Expansion compensation

25 ... 50

1 +LD-FP

2 LD.....-D

50 ... 75

2 +LD-FP

3 LD.....-D

.
.
.

3/96

.
.
.

Siemens LV 71 2005

.
.
.

Engineered fixed points include


T units
Reduction units
Trunking units with a built-in fixed point
Incoming connections (connection/feeder units)
Coupling units (on request).

LD Busbar Trunking System


Engineering
Expansion compensation and fixed point
Expansion compensation for adjustments in height

I/1

0,5 m

I/1
3,2 m
4,2 m

Adjustments in height  4.2 m

I/2

3,2 m
> 4,2 m

0,5 m

Adjustments in height  4.2 m


I/2

I/3

> 0,5 m

0,5 m

I/3
0,5 m


I/4

 Natural fixed point


 Branch point
 Note PE position.

Power transmission

 Natural fixed point


 Branch point
 Note PE position.

No expansion compensation is required for height adjustments of  4.2 m between two natural fixed points.

Power transmission
Power distribution
When engineering branch points, always use trunking
units for vertical installation (Item I/2).
When engineering height adjustments of > 1.3 m,
observe the associated reduction in rated current.

For height adjustments of  4.2 m, use trunking units for


vertical installation (Item I/2) between two natural fixed
points.
A straight trunking unit for vertical installation and a
standard trunking unit (Item I/3) may be combined.
Storey height
m

Trunking unit for


vertical installation
m

Trunking unit for


horizontal installation
m

3.21 ... 4.11

2.29 ... 3.19

0.92

4.12 ... 6.40

3.20

0.92 ... 3.20

Power distribution
When engineering branch points, always use trunking
units for vertical installation

Siemens LV 71 2005

3/97

LD Busbar Trunking System


Engineering
Expansion compensation and fixed point
Vertical busbar runs
Power transmission

Power distribution

 Fixed point
 Integral expansion compensation

 Fixed point
 Tap-off point
 Expansion compensation

A straight trunking unit for vertical installation and a


maximum of one standard trunking unit may be combined alternately.

When engineering tap-off points, trunking units for vertical installation must always be used, since each tap-off
point must be regarded as a fixed point.

For vertical installation, the hook end must always be at


the bottom:
The PE(N) or L12 position is correct only when the hook
is pointing downwards and is open towards the wall.
Tap-off units must always be aligned with the cable
connection area below and trunking units with the
hook open towards the wall.
If installed in the opposite direction, the busbar pack
can fall out of the trunking unit at the bottom. In standard trunking units, the busbar pack is mounted such
that it can move in the trunking unit.

3/98

Siemens LV 71 2005

LD Busbar Trunking System


Engineering
Examples
Engineering of horizontal busbar runs
The following items must be taken into account for engineering:
Position, direction and ratings of the loads or sub-distribution boards to be connected
Utilization and rated load factors
Details about feed transformers, in particular
Dimensions
Lug spacing
Phase sequence
Transformer short-circuit voltage (Uk)
Rating (kVA).
Details about distribution boards
Feed from above, below or the rear
Copper connections in the interior of the distribution board
Phase separations.
Characteristics of the installation location
Spatial dimensions
Building design with respect to fixing and suspension options
Transport routes
Environmental conditions (temperature, humidity
and chemicals)
Coordination with other system areas
Agreement of the busbar trunking system installation
plan
With the authority (e. g. building manager) in order
to avoid expensive reengineering. Plans should be
countersigned by the authority.
With (planned) supply lines for other energy media.
With the (planned) position of ventilation duct runs.
With lighting plans.
Coordination with BD runs into which electrical power
must be fed
Type of supply network (4- or 5-conductor system)
Balanced/unbalanced load (half or full PEN/N conductor cross-section)
Number and size of adjustments in height
( 1.3 m; 1.3 m)
Number and position of coded tap-off points
Fire barrier sections
Wall penetration points.

Engineering example
Object
A power distribution board is to be fed from a transformer station via an LDA/LDC busbar trunking system.
Given
Load Pinst = 1700 kW
p. f. = 0.8; Ue = 400 V
Necessary plans of the buildings and the installation
Reduction factor 1) = 0.7
Incoming supply via LD connection/feeder unit (AS 2)
Transformer rating = 1600 kVA, uk = 4 %
Suspension material to be supplied by customer
1 height adjustment >1.3 m
4-conductor system
Degree of protection for busbar run: IP31
PEN conductor = half phase conductor cross-section
Solution
The rated current is calculated using the following formula:
P inst
I B = ------------------------------------------ 10 3
3 U e cos

= Rated current (A)


IB
Ue = Rated operational voltage (V)
Pinst = Installed power (kW)
cos = Power factor (p. f.)
1) = Load/utilization factor

= Supply factor
= 1 for single-ended feed
= for double-ended feed and centre feed
1) Unless the application in question results in any different
requirement, the rated load factor from EN 60439-1 may
often be used for .
Number of main circuit

2 and 3

0.9

4 and 5

0.8

6 to 9, inclusive

0.7

10 and more

0.6

Inserting these values gives:


1700 0,7 1
3
I B = ---------------------------------------- 10 = 2147 A
3 400 0,8

After determining the rated current to be carried (in this


case: 2147 A) and choosing the LD system (horizontal
LDA 5413, height adjustment 1.3 m LDA 6413), the
following documents are produced:
Installation plan: Generation using LD engineering
tool (Busbar Plan)
Parts list: Generation using LD engineering tool
(Busbar Plan)

Siemens LV 71 2005

3/99

LD Busbar Trunking System


Engineering
Examples

0
20

00

00

86

00

01

00

4
3

10

0
20

*
50

9
500

20

2W

20

32

20

32

500 500

11

1000

15

0
40

50

50

500

50

0
20

50

98

12

5 500

50

00 00
24 34
6

0
50

350 620 620

1335

2020

L1

185

L2

500

00
0
7
0
50

0
32

50

0
32

14
15
00

42

50

13

11

PEN L3

22
00
2W 200
*

00 0
00
10

32
00

26

16

375g1810

1800

17

3
Notes

Produce parts list

Since the exact position of the ventilation duct has not


yet been defined, custom lengths must be planned in this
area. The adjustment in height at the power distribution
board is  1.3 m so that in this case it is necessary to take
account of the rated current for vertical installation, here:
LDA 6413.

Each component is given an item number.

No larger system is required for the two height adjustments in the region of the ventilation duct, here: height
differential  1.3 m.
Item
No.

Identical components are given the same item numbers.


If there is more than one run, they are distinguished by
roman numerals in the item number (for example: I/1).
This allows a component and its mounting location to be
identified uniquely at the construction site.

Type

Max. rated current


A

Description

1
2
3
4

LDA 5413-AS4 +LD-1B


LDA 5413-J-1W0,5
LDA 5413-3W2,0
LDA 5413-D

2500
2500
2500
2500

LD connection/feeder unit
Straight trunking unit (optional length with double bolt)
Straight trunking unit (optional length)
Expansion compensation

1
1
1
1

5
6
7
8

LDA 5413-2,4
LDA 5413-3,2
LDA 5413-LR
LDA 5413-2W*

2500
2500
2500
2500

Straight trunking unit (standard length)


Straight trunking unit (standard length)
Elbow, right
Straight trunking unit, customized length 1)

2
6
3
1

9
10
11
12

LDA 5413-LH
LDA 5413-LV
LDA 5413-LV-X0,98
LDA 5413-2W*

2500
2500
2500
2500

Knee, rear
Knee, front
Knee, front
Straight trunking unit, customized length 1)

2
1
1
1

13
14
15
16

LDA 5413-LL
LDA 5413-4W2,6
LDA 6413-LH
LDA 6413-2W1,34

2500
2500
2300
2300

Elbow, left
Straight trunking unit (optional length)
Knee, rear
Straight trunking unit (optional length)

1
1
1
1

17
18
19

LD-VEG 2
LD-BV
LD-B 2

Distribution board connection flange


Fixing bracket for vertical installation
Suspension bracket for horizontal suspension

1) For ordering optional lengths, see Order Processing in chapter Engineering Principles.

3/100

Siemens LV 71 2005

Quantity

1
1
11

LD Busbar Trunking System


Engineering
Examples
Engineering of adjustments in height
Height differential  1.3 m

1.30 m

Height differential > 1.3 m

a
b

> 1,30 m




d
1,30 m

c


For height adjustments of m 1.3 m no reduction in the


rated current is required for the same system size, or
there is no need for a larger system to maintain the rated
current.




Example
Ie = 2500 A > LDA 5....
Item No.

Type

Ie
A

1
2
3
4

LDA 5....
LDA 5....
LDA 5....
LDA 5....

2500
2500
2500
2500

For height adjustments of  1.3 m it is necessary to take


account of the fact that, beyond 1.3 m, the trunking units
must be designed for a rated current for vertical mounting.
Example
Ie = 2500 A
Item No.

Type

Ie
A

1
2
3
4
5

LDA 5....
LDA 7....
LDA 7....
LDA 5....
LDA 5....

2500
2800
2800
2500
2500

Siemens LV 71 2005

3/101

LD Busbar Trunking System


Engineering
Examples
Engineering of vertical busbar runs
Degree of protection
Vertical runs may be designed to degree of protection
IP34 or IP54.

Fire barrier




The type suffix L+LD-L120.-X...(Y...) is used for LDA and


LDC systems. The centre of the fire barrier is always the
centre of the fire ceiling thickness .
For LDA 8 and LDC 8 systems, the length of the outer
fire barrier is 0.68 m (otherwise 0.48 m).
Where possible, the fire barrier should be provided on
standard trunking units.
For straight trunking units for vertical installation without any tap-off point(s), the closest fire barrier position is
at X = 1.10 m due to the position of the expansion compensation.

For straight trunking units for vertical installation with a


tap-off point AD 1,4, the closest fire barrier position is at
X = 2.05 m (X = 1.95 m for LDA(C) 8).

For trunking units with a tap-off point AD 1,8, the closest


fire barrier position is at X = 2.45 m (X = 2.35 m for
LDA(C) 8)

3


Mounting position
The hooks must always point downwards with the hook
opening pointing towards the wall .
There should be a clearance of at least 0.48 m
(LDA(C) 8 = 0.58 m) from the centre of the ceiling to the
bolt end .

Fixing elements
The fixing elements must be fitted about 0.45 m below
the ceiling .

At least one pair of fixing brackets is required per trunking unit .


The adjustment capability of  50 mm allows wall
unevenness to be compensated for .
The wall clearance with the LD busbar system when using
vertical fixing brackets is at least 20 mm .

 Centre of fire barrier is always the centre of the fire ceiling.


 Hook always downwards with hook opening pointing
towards the wall.
 Minimum distance between the centre of the ceiling and the
bolt end: 0.48 m (LDA(C) 8 = 0.58 m).
 Fixing element clearance.
 At least one pair of fixing brackets is required per trunking
unit.
 Wall unevenness is compensated for by 50 mm adjustment
capability.

3/102

Siemens LV 71 2005

When engineering tap-off points, trunking units for


vertical engineering with integrated expansion and an
integrated fixed point must always be used .

LD Busbar Trunking System


Engineering
Examples
Engineering of trunking unit lengths
Height of storeys up to 3.2 m
The trunking unit length is equal to the height of
the storey.
Heights of storeys greater than 3.2 m
Trunking units with standard limb lengths should be
used.
A vertical trunking unit can be combined with a
maximum of one standard trunking unit.
The following table should be used only as a rough guide
for engineering design purposes.
A

=B

Storey height

+C

Trunking unit for


vertical installation
m

Trunking unit for


horizontal installation
m

3.21 ... 4.11

2.29 ... 3.19

0.92

4.12 ... 6.40

3.20

0.92 ... 3.20

Example 1
Height of ceiling 2.75 m, Ie = 1100 A
Degree of protection IP34,
4-conductor system, with fire barrier,
tap-off point at X = 1.4 m

Selected trunking unit:


LDA 1423-V-1W2,75-AD1,4 +LD-L120A-X2,27.
Straight trunking units with tap-off point(s) must
always be trunking units for vertical installation.
Example 2
Height of ceiling 4.80 m, Ie = 2400 A
Degree of protection IP54,
5-conductor system, without fire barrier
Selected trunking units:
LDA 7615-V-3W3,2,
LDA 7615-1,6.

Siemens LV 71 2005

3/103

LD Busbar Trunking System


Engineering
Examples
Engineering example
Details required

<




Number and height of the storeys


Ratings per storey and types of load
Utilization and rated load factors
Feed transformers (characteristic data, position)
Special requirements (degree of protection, fire barrier
etc.)
Number and size of the height adjustments (> 1.3 m)
Number of coded tap-off points required.
Given
11 storeys each with 8 residential units
Rating 38 kW per residential unit
Ue = 400 V, p. f. = 0.8, 5-conductor system,
degree of protection IP54
Rated load/utilization factor: = 0.7, = 0.45
Feed from the distribution board via LD connection
Transformer rating = 1600 kVA
Details and construction plans required for engineering the trunking
Tap-off units to be positioned at eye level.
Rated current

The rated current per storey is calculated using the following formula. The formula also allows the rated current for the tap-off units to be defined.
P inst
3
I NB = ----------------------------------------- 10
3 U e cos

INB = Rated current per storey (A)


Ue = Rated operational voltage (V)
Pinst = Total installed power per storey (kW)
cos = Power factor (p. f.)
1) = Rated load factor

1) If  is not stated, the values from the Number of main circuits table may be used. If the p. f. is not stated, this may be
assumed to be = 1 for purely domestic high-rise buildings.

8 38 0, 7
3
I NB = ----------------------------------------- 10 = 384 A
3 4 00 0, 8


For item numbers refer to the parts list for the engineering
example

3/104

Siemens LV 71 2005

LD Busbar Trunking System


Engineering
Examples
The rated current per busbar run is calculated from:
IB =

IB
2)

INB

Unless the application necessitates a change, the rated


load factor from EN 60439 may be used for .

= Rated current (A)


= Utilization factor for the total number loads

2) The local power supply utilities have good empirical values


for utilization factors; these differ between regions. Average
values are given in the Type of Load table.

IB =

Number of main circuit

2 and 3

0.9

4 and 5

0.8

6 to 9, inclusive

0.7

10 and more

0.6

Notes relating to the engineering example

11 384 0,45 = 1901 A

LDA 6515 is chosen here since IB is reduced from 3100 to


2000 A because of the degree of enclosure protection
IP54.
Once the system has been selected, the following documents are produced for the order:
Installation plan using the LD engineering tool
(Busbar Plan)
Parts list generation using the LD engineering tool
(Busbar Plan)
Binding order

Since the rated current for IP54 vertical is the same as for
horizontal systems, the complete run may be engineered
using LDA 6615.
Average values are always quoted for the utilization factors.
Types of load

Dwellings with electric cookers and


water heaters
(for about 100 connections)

0.1 ... 0.2

Off-peak storage heaters

0.9 ... 1.0

Lighting in office buildings and in


buildings for commercial use

0.8 ... 0.9

Lifts and general installations

0.6 ... 0.8

Parts list relating to the engineering example


Item
No.

Type

Max. rated current


A

Description

Quantity

LDA 6615-VEU-LV

2000

Distribution board connection units for LD


connection to SIVACON 8PV, 8PT

LDA 6615-J-1W0,5

2000

Straight trunking unit (optional length with


double bolts)

LDA 6615-LVR-Y1,13
+LD-120B-Y0,485

2000

Offset elbow with longer Y-leg and fire


barrier

LDA 6615-K-V-2,4-AD1,4

2000

Straight trunking unit for vertical installation


with one tap-off point

10

LDA 6615-2W0,93
+LD-120B-X0,45

2000

Straight trunking length (optional length)


with fire barrier

10

LD-2EF6-H

LD-K-2AK5/3ST250

End flange with hook

Tap-off unit with fuse switch-disconnector

10

LD-BV

Fixing bracket for vertical installation

10

LD-DR

Torque spanner

250

Siemens LV 71 2005

3/105

LD Busbar Trunking System


Engineering
Tap-offs
Tap-off units
All tap-off units have the following common features:
Galvanized steel enclosure with paint finish
Handles for fitting, removing or transporting the tapoff units
Door or removable cover
Guide and fixing elements for mounting on busbar
trunking system
Contact protection for fitting/removing
Safety during handling
Early-make PE or PEN
Tap-off with early-make and late-break PE or PEN conductor contact when fitting or removing the tap-off unit.
In the 5-conductor system, the PE connection is made via
sliding contacts on the coding brackets. In the 4-conductor system, this is provided by a longer PEN bar on the
contact apparatus.
A 7-conductor system (N/PEN = L) is shown by way of
example below.

PE

PE

PEN

4-conductor (TN-C system)


 Coding brackets

Fitting/removing
The LDA(C) system enables tap-off units to be fitted and
removed whilst the entire LD system is still energized.
All live parts are finger-proof during fitting and removal
(IP20).
The tap-off units should only be opened when the protective device is open, i.e. switched off.
All live internal live parts are finger-proof.
No load
A specified sequence of operations ensures that no load
current can flow when fitting or removing the tap-off
units.
Protection against direct contact
Degree of protection IP20 is provided at the open tap-off
point on the trunking unit and on the contact system of
the tap-off unit.
Cable connection safety feature
A plate which separates the cable connection area from
the component mounting area within the tap-off unit
prevents cables being inserted from touching live parts.

3/106

Siemens LV 71 2005

5-conductor (TN-S system)

LD Busbar Trunking System


Engineering
Tap-offs
Correct orientation and installation

Cable entries

Coding brackets on the tap-off unit and on the tap-off


point of the trunking unit (key-lock principle) prevent the
tap-off units from being fitted incorrectly on the tap-off
point.

Relationship between the hook opening (phase


sequence) and the tap-off unit cable entry
With the tap-off above=-AD, the cable entry is from
the hook end.

This prevents the tap-off unit from being fitted in the


opposite way round on tap-off point and ensures the correct allocation of 4- and 5-pole LD systems.

b
a
LD.....-K-AD
 Cable entry at the end
 Cable entry at the side

With the tap-off below=-ADU, the cable entry is from


the bolt end.

3
b
Illustration of a coding bracket in a 4-pole system

LD.....-K-ADU
 Cable entry at the end
 Cable entry at the side

When tap-off units are mounted on straight trunking


units for vertical installation (-V-AD), cable entry is from
the hook end.

b
Illustration of a coding bracket in a 5-pole system

a
LD.....-K-V-AD
 Cable entry at the end
 Cable entry at the side

Trunking units for vertical installation must always be


used when engineering tap-off points for vertical use
and with adjustments in height >1.3 m.

Siemens LV 71 2005

3/107

LD Busbar Trunking System


Engineering
Tap-offs
Tap-off units GSTA fuse switch-disconnectors
Sizes

Degree of protection

The compact design means that one size covers all current ratings.

Degree of protection IP 30 is standard. The high degree


of protection IP 54 (type suffix) can be provided just by
fitting an additional cover either at the factory or directly
on site.

Rated currents
The rated currents extend from 125 A to 630 A; and
1 GSTA 00 or 2 GSTA 00 may be selected for the 125 A
version.
Specified safety
Safety during fitting/removal while the system is live is
achieved by a specified fitting/removal sequence, see the
relevant intallation instruction, and by subsequent opening of the cable connection area after releasing 2 fixing
screws. The cover cannot be removed until the top section of the fuse switch-disconnector has been removed.

Degree of protection IP30

Degree of protection IP54

3/108

Siemens LV 71 2005

LD Busbar Trunking System


Engineering
Tap-offs
Cabling box and cable entry
The bolt connection is designed for cables up to
300 mm2
The standard tap-off unit version has an end cable
entry
Where side cable entry is required, a cabling box (type
suffix) can be flange connected at the factory or
directly on site.

Tap-off units with GSTZ fuse switch-disconnectors


Sizes
There is one size of the tap-off unit. It can accommodate
both, GSTZ 2 or GSTZ 3.

Cable entry at the end

Rated currents
The rated currents are 400 A and 630 A, respectively.
Safety by design
The fixed procedure for fitting/removal of the tap-off
unit provides protection against mishandling.
Degree of protection
Degree of protection IP30 without door is standard. The
high degree of protection IP54 can be achieved by fitting
a door (type suffix).
Cable entry at the side

Door hinging
A cable entry plate for a maximum of 3 multi-core cables
up to 300 mm2 is standard. The cables are supported by
an integral cable anchoring rail in the tap-off unit
(bracket clamps to be supplied on site). An undrilled aluminium entry plate for customized fitting with cable
glands on site, for single core cable entry can be obtained
by stating the relvant type suffix.

The doors may either be supplied with door hinged on


the left or door hinged on the right. When ordering,
the type suffix +LD-TL. or +LD-TR. must be used for this
purpose.

Sealing

The bolt connection is designed for cables up to 300 mm2.


The standard version is available with end or side cable
entry.

Sealing for the NH fuse switch-disconnector sizes NH 00


and NH 01 is standard. (Sealing for sizes NH 2 and NH 3
on request).

The door hinging may be converted on site.


Cable entry

For multi-core cables, the split cable entry flange is


designed for a maximum of 2 multi-core cables up to
300 mm2.
For single-core cables, the cables are inserted through a
drilled aluminium plate with PG cable glands. The number and size of the glands may be found in the Technical
Data section.
The cables are held by a cable anchoring rail within the
tap-off unit.

Siemens LV 71 2005

3/109

LD Busbar Trunking System


Engineering
Tap-offs
Tap-off units with circuit-breakers
Versions
High switching capacity (H) for size 1 (80 ... 250 A)
and 2 (400 ... 570 A)
Very high switching capacity (L) for size 3
(800 ... 1250 A)
Circuit-breaker with 3 or 4-pole versions
4-pole circuit-breakers (TN-S system) are fitted with
100 % releases for 80 ... 250 A (NZM 7)
60 % releases for 400 ... 570 A (NZM 10)
without relese in the N conductor for 800 ... 1250 A
(3VL)
The NZM circuit-breakers are fitted with NHI and RHI
standard and trip-indicating auxiliary contacts as
standard, and the 3VL circuit-breakers with two
auxiliary switches (1 NO + 1 NS) and an alarm switch
(1 NO). A shunt or undervoltage release can be
selected for the version with remote operator.
All control connections are wired to terminals.

Sizes
Three sizes depending on the circuit-breaker in use:
Size 1 for tap-off units with NZM 7 circuit-breaker
(80 ... 250 A)
Size 2 for tap-off units with NZM 10 circuit-breaker
(400 ... 570 A)
Size 3 for tap-off units with 3VL circuit-breaker
(800 ... 1250 A)

NEW: Standard tap-off units with Siemens circuit-breakers.


Units up to 630 A will be published in the next catalog version (2006),
as product development and tests have not yet been completed.
For preliminary solutions, please contact your product managers.
Rated currents and switching capacity
Rated current Ie
(tap-off unit)
A

Setting range of
overcurr. release
A

Ue

Icu (kA)
at
Ue = 690 V

Version

Icu (kA)
at
Ue = 400 V

Tap-off-unit size 1, 80 ... 250 A


80

63 ... 80

400 or 690

100

10

NZM 7 circuit-breaker,
H version (high capacity)

100

80 ... 100

400 or 690

100

10

NZM 7 circuit-breaker,
H version (high capacity)

125

80 ... 125

400 or 690

100

10

NZM 7 circuit-breaker,
H version (high capacity)

160

125 ... 160

400 or 690

100

10

NZM 7 circuit-breaker,
H version (high capacity)

200

160 ... 200

400 or 690

100

10

NZM 7 circuit-breaker,
H version (high capacity)

250

200 ... 250

400 or 690

100

10

NZM 7 circuit-breaker,
H version (high capacity)

Tap-off-unit size 2, 400 ... 570 A


400

200 ... 400

400 or 690

100

30

NZM 10 circuit-breaker,
H version (high capacity)

570

300 ... 570

400 or 690

100

30

NZM 10 circuit-breaker,
H version (high capacity)

Tap-off-unit size 3, 800 ... 1250A


800

400 ... 800

400 or 690

100

35

3VL7 circuit-breaker,
L version (very high capacity)

1000

500 ... 1000

400 or 690

100

35

3VL7 circuit-breaker,
L version (very high capacity)

1250

500 ... 1250

400 or 690

100

35

3VL7 circuit-breaker,
L version (very high capacity)

3/110

Siemens LV 71 2005

LD Busbar Trunking System


Engineering
Tap-offs
Safety during fitting

Tap-off units with circuit-breakers and motor drives

A specified sequence of operations ensures that no


load current can flow when fitting or removing the
tap-off units
Degree of protection
All tap-off units with circuit-breakers have degree of
protection IP54.
Cable entry/connecting
Terminal bolt for power cables connected between the
load and the circuit-breaker
In the event of the circuit-breaker tripping or a tap-off
unit being opened, internal area protected to IP20
(finger proof)
All tap-off units are provided with a cable entry for
multi-core and single-core cables. Entry is from the side
and both cable entry plates can be exchanged (with
each other) as required. A divisible cable entry plate is
available for use with multi-core cables. This allows
cables to be inserted easily from the top. An undrilled
aluminium plate is available for single-core cables.
Tap-off units with circuit-breakers and handles

Equipment
The tap-off unit is fitted with a remote operator (without handle) as standard. The circuit-breaker can be
operated from the outside via a cover flap (ON/OFF).
The external actuating voltage of the motor operator
spans the 220 ... 240 V AC range. Tap-off units with 3VL
span the 220 ... 250 V AC range.
The NZM circuit-breakers are fitted with NHI and RHI
standard and trip-indicating auxiliary contacts for ON,
OFF and TRIPPED signalling as standard, and the 3VL
circuit-breakers with two auxiliary switches (1 NO +
1 NC) and an alarm switch (1 NO). Potential-free contacts are connected to the terminals.
The following table provides an overview:

Equipment
The tap-off unit is fitted with a handle and cover interlock as standard. It can therefore only be opened when
the circuit-breaker is switched off.
Signaling
The NZM circuit-breakers are fitted with NHI and RHI
standard and trip-indicating auxiliary contacts as standard, and the 3VL circuit-breakers with two auxiliary
switches (1 NO + 1 NS) and an alarm switch (1 NO).
Potential-free contacts are connected to the terminals.

Size 1
NZM 7
80 ... 250 A

Size 2
NZM 10
400 ... 570 A

Size 3
3VL
800 ... 1250 A

NHI

RHI

NHI

RHI

HS

AS

1 NO +
1 NC

1 NC

2 NO +
2 NC

2 NO +
2 NC

1 NO +
1 NC

1 NO

Either an undervoltage release (non-delayed) or a


shunt release can be used depending on the application at hand. These are wired to terminals. The external voltage supply has a range as follows:
Size 1 and 2 have a voltage range of 220 ... 240 V AC
for the undervoltage release and shunt release
Size 3 has a voltage range of
208 ... 277 V AC for the shunt release and
220 ... 250 V AC for the undervoltage release.
All electrical connections for motor operator, auxiliary
contact and release are wired to a terminal and are
connected (cable gland provided by customer) via a
cable entry knockout in the tap-off unit (1 PG 29).

The following table provides an overview:


Size 1
NZM 7
80 ... 250 A

Size 2
NZM 10
400 ... 570 A

Size 3
3VL
800 ... 1250 A

NHI

RHI

NHI

RHI

HS

AS

1 NO +
1 NC

1 NC

2 NO +
2 NC

2 NO +
2 NC

1 NO +
1 NC

1 NO

NEW: Standard tap-off units with Siemens circuit-breakers.


Units up to 630 A will be published in the next catalog version (2006),
as product development and tests have not yet been completed.
For preliminary solutions, please contact your product managers.

Siemens LV 71 2005

3/111

LD Busbar Trunking System


Engineering
Special cases
Reduction units

Protective sleeves
Application

LD systems which pass through wall or ceiling apertures


need a protective sleeve for mechanical protection, e. g.
against contamination by mortar.
Mounting and fitting notes
The protective sleeve can be fitted retrospectively.
It consists of a two-piece steel sleeve with a flange. The
two L-shaped sleeve halves are screwed to one another
on the trunking unit. The protective sleeve is mounted on
the trunking unit such that it can move.

S = 1.2 m

Application
Costs can be saved by reducing from 7/8/9-conductor to
4/5-conductor LD systems for longer distances over which
it can be demonstrated that the current load level is relatively low.

For walls/ceilings which are thicker than 250 mm


(= length of the protective sleeve), a second protective
sleeve may be used for extension

The voltage drop over longer distances must be taken


into account.
Engineering

Since the overall short-circuit rating of the complete run


is based on the smaller LD system, either the complete
run must be limited to this value at the feeder or the
short-circuit current must be limited to the lower value
upstream of the reduction unit, e.g. by a coupling unit
with a circuit-breaker.
The smaller LD system must not be loaded with more
than its permissible rated current.
Reduction units are equipped with a fixed point at the
factory and are thus to be regarded as engineered fixed
points.
With regard to the reduction to a busbar system with
a lower rated current, the loop impedance must be
calculated using the lowest prospective single-pole
earth-fault current.

3/112

Siemens LV 71 2005

 Protective sleeve, part 1


 Protective sleeve, part 2

The protective sleeve is not a substitute for the fire


barrier.

LD Busbar Trunking System


Engineering
Special cases
Parallel connection of LD runs
Application

Engineering

For economic reasons, it may be worthwhile to lay two


runs with aluminium conductors instead of one LD busbar
system with copper conductors.

A lateral clearance of  0.1 m is required between the


parallel runs in order to allow the single-bolt clamp terminal to be tightenend, as well as a lateral clearance
from the building structure and other obstructions of
 0.1 m

Parallel connection of LD runs allows high currents to be


carried. However, the voltage drop must be taken into
account.
Advantages
Lighter mounting weight than when high currents are
transmitted via a single busbar run.
The option of using the basic components for other
configurations, particularly in distribution installations
which are modified frequently.

When the fire barrier is used, the remaining space


between the busbar trunking systems in the wall/ceiling cutout must also be filled with fireproof mortar.
The runs should always be positioned along one
another.

0.1

Phase sequence reversal units


When carrying power over long distances using LDA(C)
busbar trunking systems, a voltage drop of variable magnitude occurs. The voltage drop is caused by the arrangement of the conductors. The impedance values (details in
the Technical data section) and the voltage drop resulting
from them are determined as a mean value during type
testing.
The use of three phase sequence reversal units achieve
that the magnitude of the voltage drop in all three
phases corresponds to this mean value. In practice, one
phase sequence reversal unit is positioned after each
third of the total length of the busbar run. Phase
sequence reversal units are available on request.

Application
Phase sequence reversal units are used where a low balanced voltage drop is to be achieved in a power transmission system and where power is carried over long distances at high load levels.
Engineering
A phase sequence reversal unit is used for each third of
the total length of the busbar run. A total of three phase
sequence reversal units is therefore required.

L
1/6 L

L1
L2
L3
PEN (N)
(PE)

1/3 L

L3
L1
L2
PEN (N)
(PE)

1/3 L

L2
L3
L1
PEN (N)
(PE)

1/6 L

L1
L2
L3
PEN (N)
(PE)

L1
L2
L3
PEN (N)
(PE)

Siemens LV 71 2005

3/113

LD Busbar Trunking System


Engineering
Special cases
Transition from LDA(C).5 to LDA(C).6
Explanation of the type suffix +LD-B(H)5 +LD-B(H)5
Application
Upgrading existing installations using the old 5-conductor version (PE = enclosure) to the new 5-conductor
system (PE conductor = separate busbar)
Connecting ID2000 distribution boards (make Moeller)
to trunking systems using the new 5-conductor system
Connecting MODAN distribution boards (make
Moeller) containing old LD connections.

Engineering
In a trunking run which uses reduction units, the loop
impedance must be calculated using the lowest prospective value of single-pole earth-fault current.
Implementation by type suffixes (+LD-B5; +LD-H5). The
transitions should always be positioned in the straight
trunking units. If the transition has to be in a junction
unit or a distribution board connection unit, the minimum limb length must be 0.65 m.
For this purpose, the first trunking unit in the new system must be ordered with a type suffix.

The type suffix to be selected draws a distinction


between two situations:
Case 1
The hook of the new trunking unit is to be connected to
the bolt of the old trunking unit.
1

3
12
LDA(C).5..-...
5-conductor system (PE = housing)

LDA(C).6..-.....+LD-H5
5-conductor system (PE = separate busbar)

LDA(C).6..-...

Case 2
The bolt of the new trunking unit is to be connected to
the hook of the old trunking unit.
1

12
LDA(C).5..-...
5-conductor system (PE = enclosure)

LDA(C).6..-.....+LD-B5
5-conductor system (PE = separate busbar)

In a trunking run which uses reduction units, the loop


impedance must be calculated using the lowest prospective value of single-pole earth-fault current.

3/114

Siemens LV 71 2005

LDA(C).6..-...

LD Busbar Trunking System


Engineering
Special cases
Changing the connection configuration
for 7/8-conductor systems
Two busbar systems with differing L12 busbar position are
to be connected.
Connections are available on request.
Case 1

L12

L12

Case 2

L12

L12

Engineering
Connection is feasible only for the following busbar systems:
4-conductor systems

5-conductor systems (old)

LDA 4413(5), LDA 5413(5),


LDA 6413(5), LDA 7413(5),
LDA 8413(5)

LDA 4513(5), LDA 5513(5),


LDA 6513(5), LDA 7513(5),
LDA 8513(5)

LDC 6413(5), LDC 7413(5),


LDC 8413(5)

LDC 6513(5), LDC 7513(5),


LDC 8513(5)

LDA 4423(5), LDA 5423(5),


LDA 6423(5), LDA 7423(5),
LDA 8423(5)

LDA 4523(5), LDA 5523(5),


LDA 6523(5), LDA 7523(5),
LDA 8523(5)

LDC 6423(5), LDC 7423(5),


LDC 8423(5)

LDC 6523(5), LDC 7523(5),


LDC 8523(5)

Connection is not feasible for 8/9-conductor systems with


an additional 5th conductor (LDA(C).6..).

Siemens LV 71 2005

3/115

LD Busbar Trunking System


Engineering
Special cases
Functional endurance class for busbar trunking systems
The functional endurance of our busbar trunking systems
has been tested in conjunction with the Promat Company
at the Braunschweig Materials Test Centre.
The tests cover all busbar trunking systems LD 1... to LD
8..., LDC 2... and LDC 3... as well as LDC 6... to LDC 8... for
power transmission (busbar trunking systems without a
tap-off point or tap-off unit).

Owing to the official certification required, the fire barrier material for our systems therefore may be obtained
only from the Promat Company.
Implementation may be carried out only by specialist
companies who have been instructed by the Promat
Company.
In addition to the marking of each trunking unit, the
installation company must provide a works certificate
based on EN 10204, Section 2.1. Marking labels are
available on request.
The works certificate is used as verification of correct
design implementation. The works certificate may be
requested from the Promat Company, together with
the documents required for correct installation.
Please refer to the responsible Promat specialist, for
questions relating to design implementation details as
well, since this documentation can provide only a
rough outline.
Further information is also contained in Promat Information Leaflets 490.15 and 660.30.
Contact address:
Promat GmbH
Postfach 10 15 64
D-40835 Ratingen
Phone:+49 (21 02) 49 32 00
Fax: +49 (21 02) 49 31 11
Contact: Dr. Wiedemann
Application
For certain applications, DIN VDE 0108 requires that functional endurance of busbar trunking systems for supplying power to parts of installations be provided for an
adequate time period,
e. g. E 90 = fire resistance period 90 min.
Fields of use with a high power requirement which are
considered for use with LD busbar trunking systems with
functional endurance are, for example, standby power
systems for supplying:
Passenger lifts with an evacuation circuit (E 30)
Water pressure boosting systems for fire-extinguisher
water supplies (E 90)
Systems for dissipating smoke and heat in the event of
a fire (E 90)
Fire-service lifts (E 90).
The main field of application extends to installations having a fire resistance period of 90 min.

3/116

Siemens LV 71 2005

Standardization
In Germany, the official certification of functional endurance in the event of fire must be provided to DIN 4102
Part 12.
The verification documents are the test certificates
quoted for the respective items and the licences from the
Institut fr Bautechnik Berlin [Institution for Construction
Technology], issued to Promat GmbH, Postfach 101564,
D-40835 Ratingen.
In the course of harmonization, efforts are being made to
adopt the German Standards throughout Europe.
Engineering
Required materials/design
The following preconditions must be satisfied to achieve
functional endurance. More detailed information may be
obtained from the Promat Company.
Only Promatect-L 500 boards from the Promat Co. and
specified fixing materials may be used for partitioning.
The tests have been carried out only with these materials. The guarantee can be satisfied only by compliance
with this requirement.
The thickness d of the duct wall (see table next page)
depends on the busbar used and on the functional
endurance class required.
The distance between suspension elements must not
exceed 1200 mm (see side view) and they must be
made of steel.
Suspension elements must be dimensioned so that the
calculated tensile stress is not greater than 6 N/mm2.
The system must be gripped by a suspension element
immediately in front of and behind the mineral fibreboard abutment points, unless it is supported directly
below such points.
Threaded rods must be fixed in the solid structure by
steel inserts (double installation depth, at least 60 mm,
maximum 500 N/insert) approved by the construction
authorities, or by inserts officially certified to comply
with the functional endurance class.
There should be no obstacles in the path of the trunking (straight run), and it must always be suspended
from solid ceilings.
Every partitioned busbar system must be permanently
marked. The Promat marking labels must be fitted at
an easily visible point at intervals of 5 m (marking
labels on request).
For overview of the materials to be used, design of the
partitions and reduction of the rated current, see
Technical Information LV 71 T, pages 5/13 to 5/15.

LD Busbar Trunking System


Engineering
Special cases
Temperature response characteristic
The diagram shows how the rated current varies with the
ambient temperature.
This function applies to all LDA/LDC systems.
130

Rated current %

120
110
100
90
80
70
60

10

15

20
25
30
35
40
45
Ambient temperature C (average over 24 hours)

50

55

60

65

Transition from the LD system (old)


to the LD system (new)

System

Rated current Ie [A]


(cross-section [mm2])

Time period

Comment

LD 4-403
LD 4-603
LD 4-1003

400
600
800

1962 1969
1962 1969
1962 1969

No longer adaptable to the present-day systems

LD 1000
LD 1250

1000 (90 6)
1250 (90 8)

1969 1971/72
1969 1976

No longer adaptable
Adaptable according to IL (systems until the end of 1990, H/B 90 8)

LD 1600

1600 (2 90 6)

1969 1971/72

No longer adaptable to the present-day systems

LD 1000

1000 (90 8)

1972 1976

Adaptable according to IL (systems until the end of 1990, H/B 90 8)

LD 1600
LD 2000
LD 3

1600 (2 90 8)
2000 (2 90 8)
1600 (2 90 8)

1971/72 1976
1971/72 1976
1976 1978

Adaptable with LDA 4 according to Internal List


(systems until the end of 1990, H/B 90 8)

LD 1
LD 2
LD 3
LD 4
LD 5
LD 6

1000 (90 8)
1250 (90 8)
1600 (130 8)
2500 (2 90 8)
3100 (2 130 8)
3500 (2 130 8)

1976 1991
1976 1991
1978 1991
1976 1991
1978 1991
1979 1986

Adaptable according to IL (systems until the end of 1990, H/W 90 8)


Adaptable according to IL (systems until the end of 1990, H/W 90 8)
Adaptable to the present-day system
Adaptable according to IL (systems until the end of 1990, H/W 90 8)
Adaptable to the present-day system
Was LD 54 Cu

LD 2 Cu
LD 3 Cu
LD 4 Cu
LD 5 Cu

1550 (90 8)
2050 (130 8)
2700 (2 90 8)
3500 (2 130 8)

1986 1991
1986 1991
1986 1991
1986 1991

Adaptable according to IL (systems until the end of 1990, H/B 90 8)


Adaptable to the present-day system
Adaptable according to IL (systems until the end of 1990, H/B 90 8)
Adaptable to the present-day system, physically identical to LD6

LDA 1
LDA 2
LDA 3
LDA 4
LDA 5
LDA 6
LDA 7
LDA 8

1100 (90 8 0.575)


1250 (90 8)
1600 (90 8)
2000 (2 90 8 0.575)
2500 (2 90 8)
3000 (2 90 8)
3700 (2 130 8)
4000 (2 155 8)

1992 to date
1992 to date
1992 to date
1992 to date
1992 to date
1992 to date
1992 to date
1992 to date

LDC 2
LDC 3
LDC 6
LDC 7
LDC 8

2000 (90 8)
2600 (130 8)
3400 (2 90 8)
4400 (2 130 8)
5000 (2 155 8)

1992 to date
1992 to date
1992 to date
1992 to date
1992 to date

A special reduction unit (+LD-B5; +LD-H5) is required for connection of


LDA.5.. (PE = enclosure) to LDA.6.. (PE = separate conductor).
Important: the loop impedance must be calculated using the lowest
prospective value of single-pole earth-fault current.

A special reduction unit (+LD-B5; +LD-H5) is required for connection of


LDC.5.. (PE = enclosure) to LDC.6.. (PE = separate conductor).
Important: the loop impedance must be calculated using the lowest
prospective value of single-pole earth-fault current.

Siemens LV 71 2005

3/117

LD Busbar Trunking System


Dimension Drawings
Straight Trunking Units
LDA (C)...-...
LDA (C)...-D-...
LDA (C)...-V-...
225

185

500 3200

20

20

85

410

LDA (C)...-J-...
185

185

500 3200

20

3
LDA (C) 1... to LDA (C) 3...

LDA (C) 1...-K-... to LDA (C) 3...-K-...


300

180
200

180
200

 Coding bracket

LDA (C) 4... to LDA (C) 8...

LDA (C) 4...-K-... to LDA (C) 8...-K-...

180
190

180
190

340

240
257

3/118

Siemens LV 71 2005

240
257

LD Busbar Trunking System


Dimension Drawings
AS transformer and distribution board connection pieces
External dimensions
LD.....-AS 1 +LD-..
Lug intervals as supplied
725

410
362.51)

3102)

902)

185

13.5
Lug type

II

II

145

20

3 150 1603)

105

40

1202)

PE

Lug intervals which can be produced on site by rotating the connection lugs

13,5

Notes

3 165 1803)

Fixing materials:
(not supplied as standard)

M12 ...-8.8 bolts


Lock washers to DIN 6796-12-FSt (2 off per bolt)
Muttern M12-8 nuts

1) Reference dimensions for engineering = centre of AS 1 (362.5 mm).


For further details, see the Engineering - Incoming Connections Section.
2) Height dimensions apply to all LD connection units.
3) Lug intervals apply to cable copper busbar widths 120 mm.

Siemens LV 71 2005

3/119

LD Busbar Trunking System


Dimension Drawings
AS transformer and distribution board connection pieces
External dimensions
LD.....-AS 2 +LD-..
Lug intervals as supplied
1085

410
542,51)

185

PE

3 190 2802)
Lug type

III

IV

IV

III

Lug intervals which can be produced on site by rotating the connection lugs

3 285 3802)

Notes

Fixing materials:
(not supplied as standard)

M12 ...-8.8 bolts


Lock washers to DIN 6796-12-FSt (2 off per bolt)
Muttern M12-8 nuts

1) Reference dimensions for engineering = centre of AS 1 (542.5 mm).


For further details, see the Engineering - Incoming Connections Section.
2) Lug intervals apply to cable copper busbar widths 120 mm.

3/120

Siemens LV 71 2005

LD Busbar Trunking System


Dimension Drawings
AS transformer and distribution board connection pieces
External dimensions
LD.....-AS 3 +LD-.E (+LD-.G)
Lug intervals as supplied
1430

410
7151)

L2

185

PEN(N)

PE

200 3002)
450 6002)
Lug type

450 6002)
VI

VII

Lug intervals which can be produced on site by rotating the connection lugs

3
L2

PEN(N)

PE

200 4002)
610 7502)

Notes

Fixing materials:
(not supplied as standard)

610 7502)

M12 ...-8.8 bolts


Lock washers to DIN 6796-12-FSt (2 off per bolt)
Muttern M12-8 nuts

1) Reference dimensions for engineering = centre of AS 3 = centre of lug L 2.


2) Lug intervals apply to cable copper busbar widths 120 mm.

Siemens LV 71 2005

3/121

LD Busbar Trunking System


Dimension Drawings
AS transformer and distribution board connection pieces
External dimensions
LD.....-AS 3 +LD-.F (+LD-.H)
Lug intervals as supplied
1430

410
7151)

PEN(N)

185

L2

PE

200 3002)
450 6002)
Lug type

VII

450 6002)
VI

Lug intervals which can be produced on site by rotating the connection lugs

3
PEN(N)

L2

PE

200 4002)
610 7502)

Notes

Fixing materials:
(not supplied as standard)

610 7502)

M12 ...-8.8 bolts


Lock washers to DIN 6796-12-FSt (2 off per bolt)
Muttern M12-8 nuts

1) Reference dimensions for engineering = centre of AS 3 = centre of lug L 2 (715 mm).


2) Lug intervals apply to cable copper busbar widths 120 mm.

3/122

Siemens LV 71 2005

LD Busbar Trunking System


Dimension Drawings
AS transformer and distribution board connection pieces
External dimensions
LD.....-AS 4 +LD-..A(C)
Lug intervals as supplied
1930

410
3651)

185

L3 (L1)

450 6002)
Lug type

VIII

450 6002)
V

PE

150 3502)
VI

VII

Lug intervals which can be produced on site by rotating the connection lugs

3
L3 (L1)
PEN(N)

605 7502)

Notes

605 7502)

150 3502)

Fixing materials:
M12 ...-8.8 bolts
(not supplied as standard) Lock washers to DIN 6796-12-FSt (2 off per bolt)
Muttern M12-8 nuts
1) Reference dimensions for engineering = centre of lug L 3 (L 1)
2) Lug intervals apply to cable copper busbar widths 120 mm.

Siemens LV 71 2005

3/123

LD Busbar Trunking System


Dimension Drawings
AS transformer and distribution board connection pieces
External dimensions
LD.....-AS 4 +LD-..B(D)
Lug intervals as supplied
1930

410
15651)

PEN (N)

L3 (L1)

150 3502)
Lug type

VII

185

L2

450 6002)

VI

(L1) L3

450 6002)
V

VIII

Lug intervals which can be produced on site by rotating the connection lugs

3
PEN (N)

L3 (L1)

150 3502)

Notes

L2

605 7502)

Fixing materials:
(not supplied as standard)

L1 (L3)

605 7502)

M12 ...-8.8 bolts


Lock washers to DIN 6796-12-FSt (2 off per bolt)
Muttern M12-8 nuts

1) Reference dimensions for engineering = centre of lug L 3 (L 1)


2) Lug intervals apply to cable copper busbar widths 120 mm.

3/124

Siemens LV 71 2005

PE

LD Busbar Trunking System


Dimension Drawings
AS transformer and distribution board connection pieces
Connection lugs
Connection lugs for AS 1 to AS 4

 PEN(N) connection lug

View Y

View Z
LDA 3...-AS. +LD-...
LDC 3...-AS. +LD-...
27

300

120
255

30

240

40
9

80

PE
10
15

View Z
LDA 6(7)...-AS. +LD-...
LDC 6...-AS. +LD

View Z
LDC 7.1.-AS. +LD-..
LDA 8.1.-AS. +LD-..
LDC 8.1.-AS. +LD-..
with half PEN(N)-conductor

View Z
LDC 7.2.-AS. +LD-..
LDA 8.2.-AS. +LD-..
LDC 8.2.-AS. +LD-..
with full PEN(N)-conducter,
all lugs are identical

357

39

10

297

PE

L.

L.

L.


PEN(N)
2 10
30

95

PE

PE
L.
PEN(N)

L.
PEN(N)
85

 PEN(N) = L for LDA 6(7).1. and


LDC 6.1.

Siemens LV 71 2005

3/125

LD Busbar Trunking System


Dimension Drawings
AS transformer and distribution board connection pieces
Connection lugs
Connection lugs for AS 1 to AS 4
60
90
15

30

20

13,5

40

120

12,5

30

a
l

Lug type

AS 1

82.5

142.5

II

68

128

III

202.5

262.5

IV

110

170

AS 3

AS 4

210

270

VII

160

220

VIII

360

420

210

270

VII

160

220

Connection lugs, Type VI for AS 3 and AS 4

Customized connection lugs

90

100 (120)
50 (60)

50 (60, 80)

40
85

15

20

30

12.5

40

120

 13.5

20

AS 2

551)
120

Notes

3/126

1) Elongated holes with centre spacing of 55 mm to provide:


50 mm spacing for connection of braided cable, width of 100 mm,
60 mm spacing for connection of braided cable, width of 120 mm.

Siemens LV 71 2005

LD Busbar Trunking System


Dimension Drawings
AS transformer and distribution board connection pieces
Connection lugs
PE connection lugs for AS 1 to AS 4
LD...6.-AS. +LD-1.

LD...6.-AS. +LD-2.

501) (60)

13,5

85

20

40

115

120

Basic lugs of the LD connection feeder unit

20

12.5

17.5

40

PE

3 x 30

120
f

Notes

1) Elongated holes with centre spacing of 55 mm to provide:


50 mm spacing for connection of braided cable, width of 100 mm,
60 mm spacing for connection of braided cable, width of 120 mm.

Siemens LV 71 2005

3/127

LD Busbar Trunking System


Dimension Drawings
AS transformer and distribution board connection pieces
Flange plate
Aluminium flange plate and enclosure cutout

PE
30


h

a 95

a 20

b 130

115

25

b 20
 Centreline of LD.....-AS = cutout centreline

Type

Type suffix
Phase sequence,
Offset

LD.3...-AS 1

+LD-...

255

LDA 6(7,8)...-AS 1

+LD-...

312

LDC 6...-AS 1

+LD-...

LDC 7(8)...-AS 1

+LD-...

LD.3...-AS 2

+LD-...

255

LDA 6(7,8)...-AS 2

+LD-...

312

LDC 6...-AS 2

+LD-...

LDC 7(8)...-AS 2

+LD-...

LD.3...-AS 3

+LD-...

255

LDA 6(7,8)...-AS 3

+LD-...

312

LDC 6...-AS 3

+LD-...

LDC 7(8)...-AS 3

+LD-...

LD.3...-AS 4

+LD-...A(C)

255

LDA 6(7,8)...-AS 4

+LD-...A(C)

312

LDC 6...-AS 4

+LD-...A(C)

LDC 7(8)...-AS 4

+LD-...A(C)

LD.3...-AS 4

+LD-...B(D)

255

LDA 6(7,8)...-AS 4

+LD-...B(D)

312

LDC 6...-AS 4

+LD-...B(D)

LDC 7(8)...-AS 4

+LD-...B(D)

3/128

Siemens LV 71 2005

115

165.5.5

164

165.5

3 165 = 495

110

1155

287.5

280

287.5

4 213.75 = 855

110

1500

+LD-.E(G) = 300
+LD-.F(H) = 600

300

+LD-.E(G) = 600
+LD-.F(H) = 300

6 200 = 1200

110

2000

250

600

600

8 212.5 = 1700

250

8 212.5 = 1700

795

205

205

205
110

205
365

600

110

205

LD Busbar Trunking System


Dimension Drawings
Cable connection units
Front view

Side view
120

205

552

15

87

87


 32  72

b
280

a
470

a + 120

10

490
 Entry

View Z
470
320
60

30

40

120

40

Cable entry plate for single-core cable (+LD-BPAL)

435

Enclosure Cable entries


size
(see
dimension b)

3 90 420

LDA 1.2.-KE. 1

450

LDA 2.2.-KE. 1

450

3 90 420

LDA 3.2.-KE. 2

650

5 90 620

LDA 4.1.-KE. 2

650

5 90 620

LDA 4.2.-KE. 2

650

5 90 620

LDC 2.2.-KE. 2

650

5 90 620

LDA 5.1.-KE. 3

800

7 90 770

LDA 5.2.-KE. 3

800

7 90 770

LDC 3.2.-KE. 3

800

7 90 770

Siemens LV 71 2005

3/129

LD Busbar Trunking System


Dimension Drawings
VE, VEU distribution board connection units
Connection to SIVACON 8PV and 8PT power distribution systems
The figures show the most important dimensional details using selected examples.
-LH angular connection units

121

x
mm

y
mm

LDA (C)....-VEU-L.

500

500

LDA (C)....-VEU-L.-X*

500 ... 1240

500

LDA (C)....-VEU-L.-Y*

500

500 ... 1240

LDA (C)....-VEU-L.-X*/Y*

500 ... 1240

500 ... 1240

-LHL-Z* offset connection units

121

x
y
mm

z
mm

LDA (C)....-VEU-L..

500

500

LD. 1 3 = 360
LD. 4 8 = 420

LDA (C)....-VEU-L..-X*

500 1240

500

LD. 1 3 = 360
LD. 4 8 = 420

LDA (C)....-VEU-L..-Y*

500

500 ... 1240 LD. 1 3 = 360


LD. 4 8 = 420

LDA (C)....-VEU-L..-X*/Y*

500 ... 1240 500 ... 1240 LD. 1 3 = 360


LD. 4 8 = 420

LDA (C)....-VEU-L..-Z*

500

3/130

244

32

x
mm

Siemens LV 71 2005

500

LD. 1 3 = 360 ... 1300


LD. 4 8 = 420 ... 1300

LD Busbar Trunking System


Dimension Drawings
VE, VEU distribution board connection units
Connection to non-Siemens power distribution systems (FA 1) and incoming cable connection units (KE)
The figures show the most important dimensional details using selected examples.
-VEH angular connection units

30

x
mm

y
mm

LDA (C)....-VE.

500

300

LDA (C)....-VE.-X*

500 ... 1240 300

-VEHL offset connection units


x

x
y
mm

z
mm

LDA (C)....-VE..

500

300

LD. 1 3 = 360
LD. 4 8 = 420

LDA (C)....-VE..-X*

500 ... 1240 300

LD. 1 3 = 360
LD. 4 8 = 420

LDA (C)....-VE..-Z*

500

LD. 1 3 = 360 ... 1300


LD. 4 8 = 420 ... 1300

300

240

30

x
mm

LD-VEG 1(2) (-5) distribution board connection flange


a

a
mm
180

LD-VEG 2 (-5)

240

185

LD-VEG 1 (-5)

Siemens LV 71 2005

3/131

LD Busbar Trunking System


Dimension Drawings
Connection units for non-Siemens distribution boards
4-pole
LDA 2420-FA 1

LDA 3420-FA 1
LDC 2420-FA 1

LDC 3420-FA 1

View A
h

207

L3

L2

L1

PEN

L2

L3

PEN

L1

9
36,5

i
175

LDA 5410-FA 1

LDA 7410-FA 1
LDC 6410-FA 1

LDC 7410-FA 1

LDA 8410-FA 1
LDC 8410-FA 11)

L12

L21

L22

L31

L32

L11

L12

L11

L12

L21

L22

L21

L22

L31

L32

L31

L32

L11

PEN

PEN

PEN

LDA 7420-FA 1
LDC 6420-FA 1

LDC 7420-FA 1

LDA 8420-FA 1
LDC 8420-FA 11)

LDA 5420-FA 1

L12

L11

L12

L21

L22

L21

L22

L32

L31

L32

L31

L32

PEN

PEN

PEN

PEN

PEN

L21

L22

L31
PEN

L12

L11

L11

1) For the length of connection lugs see table on the following page.

3/132

Siemens LV 71 2005

LD Busbar Trunking System


Dimension Drawings
Connection units for non-Siemens distribution boards
Dimensions of FA 1, 4-pole
Conductor material: Aluminium

LDA 2420-FA 1

a
mm

b
mm

c
mm

d
mm

e
mm

f
mm

90

166

LDA 3420-FA 1
LDA 5410-FA 1

242

318

g
mm

h
mm

i
mm

Connection
pattern

108.5

90

114.5

148.5

130

154.5

B
A

137

90

114.5

LDA 7410-FA 1

177

130

154.5

LDA 8410-FA 1

177

154

176

LDA 5420-FA 1

146.5

90

114.5

LDA 7420-FA 1

186.5

130

154.5

LDA 8420-FA 1

186.5

154

176

g
mm

h
mm

i
mm

Connection
pattern

Conductor material: Copper

LDC 2420-FA 1

a
mm

b
mm

c
mm

d
mm

e
mm

f
mm

90

166

LDC 3420-FA 1
LDC 6410-FA 1

242

318

148.5

90

114.5

148.5

130

154.5

B
B

177

90

114.5

LDC 7410-FA 1

177

130

154.5

LDC 8410-FA 1

197

154

176

LDC 6420-FA 1

186.5

90

114.5

LDC 7420-FA 1

186.5

130

154.5

LDC 8420-FA 1

206.5

154

176

Siemens LV 71 2005

3/133

LD Busbar Trunking System


Dimension Drawings
Connection units for non-Siemens distribution boards
Mounting information
Enclosure cutout details for connecting a 4-conductor LD system
c
d

LD...-VE..

min. 140

212

115

5,4

7,5

a
M6 12
min. 230

3
LDA 2420-FA 1
LDC 2420-FA 1

a
mm

b
mm

c
mm

d
mm

91

120

113

100

170

157

LDA 3420-FA 1
LDC 3420-FA 1

LD...-FA.

LDA 5410-FA 1
LDC 6410-FA 1

Siemens LV 71 2005

148

120

LDA 7410-FA 1
LDC 7410-FA 1

160

LDA 8410-FA 1
LDC 8410-FA 1

180

LDA 5420-FA 1
LDC 6420-FA 1

3/134

160

167

120

LDA 7420-FA 1
LDC 7420-FA 1

160

LDA 8420-FA 1
LDC 8420-FA 1

180

189

LD Busbar Trunking System


Dimension Drawings
Connection units for non-Siemens distribution boards
5-pole
LDA 2620-FA 1

LDA 3620-FA 1
LDC 2620-FA 1

LDC 3620-FA 1

View A
h

207

PE

PE

L1

L1

L2

L3

L2

L3

36,5
i

175

LDA 5610-FA 1

LDA 7610-FA 1
LDC 6610-FA 1

LDC 7610-FA 1

LDA 8610-FA 1
LDC 8610-FA 1

PE

PE

PE
L11

L12

L21
L31

L12

L11

L12

L22

L21

L22

L21

L22

L32

L31

L32

L31

L32

L11

N
g

LDC 6620-FA 1
LDC 7620-FA 1

LDA 7620-FA 1

LDA 8620-FA 1
LDC 8620-FA 11)

PE

PE

L12

L21

L22

L31

L32

L11

PE

LDA 5620-FA 1

N
g

L11

L12

L21

L22

L31

L32

L11

L12

L21

L22

L31

L32

1) For the length of connection lugs see table on the following page.
Siemens LV 71 2005

3/135

LD Busbar Trunking System


Dimension Drawings
Connection units for non-Siemens distribution boards
Dimensions of FA 1, 5-pole
Conductor material: Aluminium

LDA 2620-FA 1

a
mm

b
mm

c
mm

d
mm

e
mm

f
mm

80

156

232

127.5 108.5

LDA 3620-FA 1

g
mm

h
mm
90

i
mm

Connection
pattern

114.5 A

167.5 148.5 130

154.5 B

156

137

90

114.5 A

LDA 7610-FA 1

196

177

130

154.5 B

LDA 8610-FA 1

196

177

154

176

LDA 5620-FA 1

165.5 146.5

90

114.5 A

LDA 7620-FA 1

205.5 186.5 130

154.5 B

LDA 8620-FA 1

205.5 186.5 154

176

i
mm

Connection
pattern

LDA 5610-FA 1

308

384

Conductor material: Copper

LDC 2620-FA 1

a
mm

b
mm

c
mm

d
mm

e
mm

f
mm

80

156

232

167.5 148.5

LDC 3620-FA 1

h
mm
90

114.5 B

167.5 148.5 130

154.5 B

196

177

90

114.5 B

LDC 7610-FA 1

196

177

130

154.5 B

LDC 8610-FA 1

216

197

154

176

LDC 6620-FA 1

205.5 186.5

90

114.5 B

LDC 7620-FA 1

205.5 186.5 130

154.5 B

LDC 8620-FA 1

225.5 206.5 154

176

LDC 6610-FA 1

g
mm

3/136

Siemens LV 71 2005

308

384

LD Busbar Trunking System


Dimension Drawings
Connection units for non-Siemens distribution boards
Mounting information
Enclosure cutout details for connecting a 5-conductor LD system
c

c1

LD...-VE..

min. 140

PE

212

115

5,4

7,5

a1

M6 12
min. 250

3
LDA 2620-FA 1
LDC 2620-FA 1

LD...-FA.

a
mm

a1
mm

b
mm

c
mm

45.5

55

120

56.5

64.5 100

85

93

LDA 3620-FA 1
LDC 3620-FA 1
LDA 5610-FA 1
LDC 6610-FA 1

d
mm

160
74

83.5

120

LDA 7610-FA 1
LDC 7610-FA 1

160

LDA 8610-FA 1
LDC 8610-FA 1

180

LDA 5620-FA 1
LDC 6620-FA 1

c1
mm

83.5

93

120

LDA 7620-FA 1
LDC 7620-FA 1

160

LDA 8620-FA 1
LDC 8620-FA 1

180

94.5

157

102.5

Siemens LV 71 2005

3/137

LD Busbar Trunking System


Dimension Drawings
Connection units for non-Siemens distribution boards
Braided cable busbar connection
Cross-sections

Recommended cross-sections of braided cable busbars


Conductor material: Aluminium
Required cross-section

Connection
pattern

LDA 2420-FA 1

Cu 60 10

LDA 2620-FA 1

Cu 60 10

LDA 3420-FA 1

Cu 100 10

LDA 3620-FA 1

Cu 100 10

LDA 5410-FA 1

Cu 60 10

LDA 5420-FA 1

Cu 60 10

LDA 5610-FA 1

Cu 60 10

LDA 5620-FA 1

Cu 60 10

LDA 7410-FA 1

Cu 100 10

LDA 7420-FA 1

Cu 100 10

LDA 7610-FA 1

Cu 100 10

LDA 7620-FA 1

Cu 100 10

LDA 8410-FA 1

Cu 100 10

LDA 8420-FA 1

Cu 100 10

LDA 8610-FA 1

Cu 100 10

LDA 8620-FA 1

Cu 100 10

60

h1)

11
30
65

h1)

20

60
105

Conductor material: Copper

h1)

120

20

60
105

1)

30

60
125

1) For dimension h see FA 1 dimension tables


(4-pole and 5-pole)

3/138

Siemens LV 71 2005

Required cross-section

Connection
pattern

LDC 2420-FA 1

Cu 100 10

LDC 2620-FA 1

Cu 100 10

LDC 3420-FA 1

Cu 100 15

LDC 3620-FA 1

Cu 100 15

LDC 6410-FA 1

Cu 100 10

LDC 6420-FA 1

Cu 100 10

LDC 6610-FA 1

Cu 100 10

LDC 6620-FA 1

Cu 100 10

LDC 7410-FA 1

Cu 100 12

LDC 7420-FA 1

Cu 100 12

LDC 7610-FA 1

Cu 100 12

LDC 7620-FA 1

Cu 100 12

LDC 8410-FA 1

Cu 120 10

LDC 8420-FA 1

Cu 120 10

LDC 8610-FA 1

Cu 120 10

LDC 8620-FA 1

Cu 120 10

LD Busbar Trunking System


Dimension Drawings
Connection units for non-Siemens distribution boards
Mounting information for connections
C,D

M10 40
MA = 45 Nm

M10 40
M A = 45 Nm

M10

M10

M10

M10 40
MA = 45 Nm

M10

Note:

M10

The fixing materials illustrated here are included in the scope of supply.

Siemens LV 71 2005

3/139

LD Busbar Trunking System


Dimension Drawings
Tap-off units
Tap-off units with GSTA fuse switch-disconnectors, IP 30 degree of protection
Without cabling box (end cable entry)
With cabling box (side cable entry)
LD-K-.AK./.ST...
+BD 2-800-KR
596

161

max. 490

900

317,5

Tap-off unit fitted

Space requirement for fitting


370

424
47

494

307

131,5

3/140

Siemens LV 71 2005

LD Busbar Trunking System


Dimension Drawings
Tap-off units
Tap-off units with GSTA fuse switch-disconnectors, IP 54 degree of protection
Without cabling box (end cable entry)
With cabling box (side cable entry)
LD-K-.AK./.ST...
+BD 2-800-KR
603

161

max. 490

903.5

317.5

Tap-off unit fitted

131.5

Space requirement for fitting


370

505

318

44

430

Siemens LV 71 2005

3/141

LD Busbar Trunking System


Dimension Drawings
Tap-off units
Tap-off units with GSTZ fuse switch-disconnectors
861

44
160,5

58

43

15

15

276

134

445

Tap-off unit with door

Tap-off unit without door

518

476

275

431

167

310

710

90

Note:

3/142

The external size of the coding brackets can be found in the dimension table
for trunking units with tap-off points.

Siemens LV 71 2005

LD Busbar Trunking System


Dimension Drawings
Tap-off units
Tap-off units with NZM 7 circuit-breaker (80 ... 250 A)
LD-K.AK./LSH-...-.

LD-K.AK./LSM-...-.

158

600

317.5

Tap-off unit fitted

136.5

Space requirement for fitting

62

3
497

310

62

424

Siemens LV 71 2005

3/143

LD Busbar Trunking System


Dimension Drawings
Tap-off units
Tap-off units with NZM 10 circuit-breaker (400 ... 570 A)
LD-K.AK./LSH-...-.
LD-K.AK./LSM-...-.

187

900

387.5

Tap-off unit fitted

136.5

Space requirement for fitting

87

3/144

Siemens LV 71 2005

542

62

47

355

62

424

LD Busbar Trunking System


Dimension Drawings
Tap-off units
Tap-off units with SENTRON 3VL circuit-breaker (800 ... 1250 A)
LD-K.AK./LSH-.....-LS
LD-K.AK./LSM-.....-LS
1500

1500

60

60

G_NSV0_XX_00557

G_NSV0_XX_00554

137

137

313
907,5

Space requirement for fitting


48

Space requirement for fitting


48

424

48

G_NSV0_XX_00558

G_NSV0_XX_00555

Tap-off unit fitted

G_NSV0_XX_00559

520

442

Tap-off unit fitted

G_NSV0_XX_00556

403

700

424

907,5

403

622

48

313

Siemens LV 71 2005

3/145

LD Busbar Trunking System


Dimension Drawings
Accessories
Flanges
LD.-EF.-H.

LD.-EF.-BF.

325

LD.-EF.-B.

325

325

Protective sleeves

32

257

193

13

250

3/146

Siemens LV 71 2005

a
mm

b
mm

LD-DF 1B

213

270

LD-DF 2B

270

327

LD Busbar Trunking System


Dimension Drawings
Accessories
Suspension bracket for horizontal suspension
LD-B 1
LD-B 2
281

95

28

224

Fixing bracket for vertical fixing


LD-BV
250

50


127

200

60

a
mm

14

50

15


27,5
min. 20

LDA 1 to LDA 3

300

LDC 2 to LDC 3

300

LDA 4 to LDA 8

357

LDC 6 to LDC 8

357

 LD system
 Front
 To be supplied on site

40

Torque spanner
LD-DR

125




39


460






For 80 Nm
Socket, 22 mm
Extension
Ratchet, two-directional
Knee joint

Siemens LV 71 2005

3/147

LD Busbar Trunking System


Dimension Drawings
Notes

3/148

Siemens LV 71 2005

Annex

4/2

Glossary

4/4

Ordering notes

4/5

Siemens contacts

4/6

A&D Online services

4/7

Customer support

4/8

Alphabetical and type reference index

4/9

Condtions of sale and delivery,


export regulations

Siemens LV 71 2005

Annex
Glossary

In accordance with IEC/EN 60439-1, rated values are supplied by the manufacturers of low-voltage switchgear and controlgear assemblies. These rated values
apply for the specified operating conditions and characterise the usability of a
switchgear assembly.

The rated values should be used as a basis for co-ordination of equipment or engineering the switchgear assemblies.

(AC) Rating or rated power


IEC/EN 60947-1; 4.3.2.3

The operational power that an equipment is capable of switching at the associated rated operational voltage in accordance with the utilization category, e.g.
contactor utilization category AC-3: 37 kW at 400 V.

Rated conditional short-circuit current (Icc)


IEC/EN 60439-1; 4.5

The rated conditional short-circuit current corresponds to the prospective shortcircuit current which a circuit of a switchgear assembly can carry when protected
by a short-circuit protective device, without sustaining damage (for a specified
duration). For this reason the rated conditional short-circuit current is quoted for
tap-offs and/or feeder units with circuit-breakers, for example.

Rated conditional short-circuit current


IEC/EN 60947-1; 2.5.29

a Rated conditional short-circuit current (Iq)

Rated control circuit-voltage (Uc)


IEC/EN 60947-1; 4.5.1

Voltage which is supplied to the actuating make contact in a control circuit. Due
to the presence in the control circuit of transformers or resistors, this voltage may
differ from the rated control supply voltage.

Rated current In) (of a circuit-breaker)


IEC/EN 60947-2; 4.3.2.3

Current which for circuit-breakers is equal to the uninterrupted current and the
conventional free-air thermal current.
a Rated uninterrupted current

Rated frequency
IEC/EN 60947-1; 4.3.3

The frequency for which an equipment is designed and to which the other characteristics are refered.
a Rated uninterrupted current
Rated operational voltage

Rated impulse withstand voltage (Uimp)


IEC/EN 60947-1; 4.3.1.3

Measures the stability of the internal clearances inside a switchgear against


overvoltage peaks. The utilization of suitable switchgear can ensure that overvoltages are prevented from transfering from the mains to deenergized system
sections within it.

Rated insulation voltage (Ui)


IEC/EN 60947-1; 4.3.1.2

The voltage to which insulation tests and creepage distances refer. Under no circumstances is the highest rated operational voltage permitted to exceed the
rated insulation voltage.
a Rated operational voltage

Rated making capacity


IEC/EN 60947-1; 4.3.5.2

The current which a switchgear unit is capable of switching on in accordance


with the utilization category and at the rated operational voltage.
a Rated operational voltage

Rated operational current (Ie)


IEC/EN 60947-1; 4.3.2.3

The current that an equipment is capable of carrying, taking into account the
rated operational voltage, duration of operation, utilization category and ambient temperature.
a Rated operational voltage

Rated operational voltage (Ue)


IEC/EN 60947-1; 4.3.1.1

The voltage to which the characteristics of a switchgear unit are refered. Under
no circumstances is the highest rated operational voltage permitted to exceed
the rated insulation voltage.
a Rated insulation voltage

Rated peak short-circuit withstand current (Ipk)


IEC/EN 60439-1; 4.4

The rated peak withstand current describes as the peak value of the surge current, the dynamic strength of a circuit in a switchgear assembly. The rated shorttime withstand current is generally specified for the distribution system and/or
main busbars of a switchgear assembly.

Rated service short-circuit breaking capacity (Ics)


IEC/EN 60947-2; 4.3.5.2.2

The prospective short-circuit current which, depending on the rated operational


voltage, a circuit-breaker is capable of breaking repeatedly (test cycle OCOCO,
previously P2). After interrupting this short-circuit current value, the circuitbreaker must be capable of continuing to carry and disconnect in the event of
overloading, the rated uninterrupted current, despite its own thermal level having increased.
a Rated uninterrupted current
Rated operational voltage

4/2

Siemens LV 71 2005

Annex
Glossary
Rated short-circuit breaking capacity (Icn)
IEC/EN 60947-1; 4.3.6.3

The maximum value of current which a switchgear unit is capable of switching


off at rated operational voltage and rated frequency without sustaining damage.
It is expressed as r.m.s. value.
a Rated operational voltage

Rated short-circuit making capacity (Icm)


IEC/EN 60947-1; 4.3.6.2

The maximum value of current which a switchgear unit is capable of switching


on at a specific rated operational voltage and rated frequency without sustaining
damage. Unlike other characteristics values, this is expressed as a peak value.
a Rated operational voltage

Rated short-circuit withstand current (Icw)


IEC/EN 60439-1; 4.3

The rated short-circuit withstand current describes, as the effective value of the
short-circuit current, the thermal strength of a circuit in a switchgear assembly
during transient loading. The rated short-time withstand current is normally
determined for the duration of 1 s, and any divergent times must be stated. The
rated short-time withstand current is specified for the distribution system and/or
main busbars of a switchgear assembly.

Rated ultimate short-circuit breaking capacity (Icu)


IEC/EN 60947-2; 4.3.5.2.1

Maximum short-circuit current, which a circuit-breaker is capable of interrupting


(test cycle: OCO, previously P-1). After interrupting this current value the circuit-breaker is capable, with increased tolerances, of disconnecting in the event
of overloading.

Rated uninterrupted current (Iu)


IEC/EN 60947-1; 4.3.2.4

The current which a switchgear unit can carry in uninterrupted duty (for weeks,
months or years).

Siemens LV 71 2005

4/3

Annex
Ordering notes

Aluminium and copper surcharges


Surcharges for copper (Cu) and aluminum (Al) will be added to
the product prices; these surcharges will take the form of percentages of the list prices. Calculation of the surcharges will be
governed by the official Al quotation for aluminum and by the
Cu-DEL quotation applying on the date of receipt of order or of
call-off.
For the products in this catalog, aluminum and copper are included in the prices on the basis of 150,-- /100 kg. Aluminum and
copper quotations above that amount are calculated on the basis of the month previous to invoicing.
Calculation formula for Al/Cu surcharges:
Cu-DEL quotation or Al quotation 150
------------------------------------------------------------ Cu/Al weight (kg)
100 kg

Small orders
When small orders are placed, the costs associated with order
processing are greater than the order value. We recommend
therefore that you combine several small orders. Where this is
not possible, we unfortunately find it necessary to charge a
processing supplement of 20.-- to cover our costs for order
processing and invoicing for all orders with a net goods value of
less than 250.--.

4/4

Siemens LV 71 2005

Selection and ordering data: type


If a type designation contains * characters, it is not complete and
must be supplemented according to specifications in the list.

Order number supplement


For an order, BVP: must be placed before the order number
stated in the catalog.
Example: the order number in the catalog is 034262. When placing an order, please write BVP:034262. The price list already
contains the order numbers supplemented with BVP:

Annex
Siemens contacts

Siemens contacts worldwide


At
http://www.siemens.de/automation/partner
you can find details of Siemens contact partners worldwide
responsible for particular technologies.
You can obtain in most cases a contact partner for
Technical Support,
Spare parts/repairs,
Service,
Training,
Sales or
Consultation/engineering.
You start by selecting a
Country,
Product or
Sector.
By further specifying the remaining criteria you will find exactly
the right contact partner with his/her respective expertise.

Siemens LV 71 2005

4/5

Annex
A&D Online services

A&D in the WWW


A detailed knowledge of the range of products and services
available is essential when planning and configuring automation
systems. It goes without saying that this information must always
be fully up-to-date.
The Siemens Automation and Drives Group (A&D) has therefore
built up a comprehensive range of information in the World Wide
Web, which offers quick and easy access to all data required.
Under the address
http://www.siemens.de/automation
you will find everything you need to know about products, systems and services.

Product Selection Using the Interactive Catalog


Detailed information together with convenient interactive functions:
The interactive catalog CA 01 covers more than 80,000 products
and thus provides a full summary of the Siemens Automation
and Drives product base.
Here you will find everything that you need to solve tasks in the
fields of automation, switchgear, installation and drives.
All information is linked into a user interface which is easy to
work with and intuitive.
After selecting the product of your choice you can order at the
press of a button, by fax or by online link.
Information on the interactive catalog can be found on the Internet under

http://www.siemens.de/automation/ca01
or on CD-ROM:
Automation & Drives CA 01,
Order No.: E86060-D4001-A110-C3-7600

Easy Shopping with the A&D Mall


The A&D Mall is the virtual department store of Siemens AG in
the Internet. Here you have access to a huge range of products
presented in electronic catalogs in an informative and attractive
way.
Data transfer via EDIFACT allows the whole procedure from selection through ordering to tracking of the order to be carried out
online via the Internet.
Numerous functions are available to support you.
For example, powerful search functions make it easy to find the
required products, which can be immediately checked for availability. Customer-specific discounts and preparation of quotes
can be carried out online as well as order tracking and tracing.
Please visit the A&D Mall on the Internet under:
http://www.siemens.de/automation/mall

4/6

Siemens LV 71 2005

Annex
Customer support

Configuring and software engineering .

Support in configuring and developing with customer-oriented


services from actual configuration to implementation of the automation project. 2)

In the face of harsh competition you need optimum conditions to


keep ahead all the time:
A strong starting position, a sophisticated strategy and team
for the necessary support in every phase.
Service & Support from Siemens provides this support; with a
complete range of different services for automation and drives.
In every phase: from planning and startup to maintenance and
upgrading.

Technical support

Competent consulting in technical questions covering a wide


range of customer-oriented services for all our products and
systems.
Tel.: +49 (180) 50 50 222
Fax: +49 (180) 50 50 223
E-Mail: ad.support@siemens.com

Our specialists know when and where to act to keep the productivity and cost-effectiveness of your system running in top form.

Online support

The comprehensive information


system available round the
clock via Internet ranging from
Product Support and Service &
Support services to Support
Tools in the shop.

Service on site

With Service on site we offer services for startup and maintenance, essential for ensuring
system availability.
Tel.: +49 (180) 50 50 444 2)

http://www.siemens.com/
automation/service&support

Technical consulting

Technical assistance

Support in the planning and designing of your project. From detailed actual-state analysis,
target definition and consulting
on product and system questions right up to the creation of
the automation solution. 2)

Expert technical assistance 1)


for low-voltage controlgear,
switchgear and systems and
electrical installation.
Tel.: +49 (9 11) 8 95-59 00
Fax: +49 (9 11) 8 95-59 07

Repairs and spare parts

4
In the operating phase of a machine or automation system we
provide a comprehensive repair
and spare parts service ensuring the highest degree of operating safety and reliablity.
Tel.: +49 (180) 50 50 446 2)

Optimization and upgrading

To enhance productivity and


save costs in your project we offer high-quality services in optimization and upgrading. 2)

E-Mail: technical-assistance
@siemens.com

1) Contact:
Technical assistance for product selection Old/new coding
Competitor coding Special versions Special requirements
Sales promotion (Infoline).
Your regional contacts for sales support (prices, discounts, delivery times).
Technical support for commissioning support and after-sales service.

2) For country-specific telephone numbers go to our Internet site


http://www.siemens.com/automation/service&support

Siemens LV 71 2005

4/7

Annex
Alphabetical and type reference index
Page

Accessories
Adapters for connection

3/46, 3/47
3/33, 3/89

B
Busbars

3/68, 3/69

Knees

F
Fire barriers
Fixing brackets
Fixing elements
Fuse switch disconnectors

3/91 ... 3/94


3/47
3/47
3/41 ... 3/43,
3/108, 3/109

3/28 ... 3/31

LD.....-AS.-T

3/32 ... 3/37

LD.....-D

O
Offsets, junction units
3/97
Optional lengths, trunking units 3/6 ... 3/9
Order processing
3/81
Overcurrent protection devices
3/41 ... 3/45, 3/108 ... 3/111

P
Parallel connection of busbar runs
3/113
Partitioning
3/116
Phase sequence
3/69
Phase sequence reversal units
3/113
Project management
3/77 ... 3/82
Protective sleeves
3/46, 3/112

R
Rated current
Reduction units

3/68
3/40, 3/112

S
Standard lengths, trunking units 3/6 ... 3/9
Suspension brackets
3/47

H
Height adjustments
Horizontal busbar runs

3/97, 3/101
3/95, 3/96,
3/99, 3/100

I
Incoming cable connection units 3/38, 3/88
Installation
3/75, 3/76

J
Junction units
Knees
T units
U units
Elbows
Z units

3/10 ... 3/21


3/12, 3/14, 3/15
3/18 ... 3/21
3/11, 3/13
3/10, 3/16, 3/17
3/10, 3/12

Tap-off units

3/41 ... 3/45,


3/106 ... 3/111
Tap-off points
3/7 ... 3/9
Temperature response characteristic 3/117
Torque spanner
3/47
Transformer connection
3/84 ... 3/86
Trunking units
3/6 ... 3/9, 3/68 ... 3/81
T units
3/18 ... 3/21

U
U units

3/11, 3/13

V
Vertical busbar runs

3/98, 9/102, 3/103

Z
Z units

4/8

Siemens LV 71 2005

3/6

LD.....-AS.

Non-Siemens distribution boards


3/22 ... 3/24

Elbows
3/10, 3/16, 3/17
End flanges
3/46
Expansion compensation
3/95 ... 3/99
Expansion compensation, trunking units 3/6

LD.....-...

Moeller power distribution boards


(MODAN)
3/25 ... 3/27, 3/89

Cable connection units


3/38, 3/88
Cable entries
3/42, 3/43, 3/107
Circuit-breakers
3/44, 3/45, 3/110, 3/111
Conductor material
3/68
Connection/feeder units
3/28 ... 3/38,
3/82 ... 3/87

Page

Distribution board connecting flange 3/22


Distribution board connection
3/89
Distribution board connection units
3/22 ... 3/27
Distribution board blank plate
3/46

Type

LDA....-..., LDC....-...
3/12, 3/14, 3/15

Page

3/10, 3/12

3/6

LD.....-FA1

3/39

LD.....-J-...

3/6

LD.....-K-...
LD.....-K-V-...
LD.....-KE1, LD.....-KE2

3/7, 3/8
3/9
3/38

LD.....-LL-..., LD.....-LR-...
LD.....-LH-..., LD.....-LV-...
LD.....-LHL-...
LD.....-LHR-...
LD.....-LLH-..., LD.....-LLV-...
LD.....-LRH-..., LD.....-LRV-...
LD.....-LVL-...
LD.....-LVR-...

3/10
3/12
3/15
3/14
3/17
3/16
3/15
3/14

LD.....-UL-..., LD.....-UR-...
LD.....-UV-..., LD.....-UH-...

3/11
3/13

LD.....-T-AD-T..
LD.....-T-ADU-T..

3/18, 3/19
3/20, 3/21

LD.....-V-...
3/9
LD.....-VEG...
3/22
LD.....-VEH-...
3/22
LD.....-VEHL-...,LD.....-VEHR-...
3/24
LD.....-VEU-...
3/25 ... 3/27
LD.....-VEV-...
3/22
LD.....-VEVL-..., LD.....-VEVR-...
3/23
LD.....-ZL-..., LD.....-ZR-...
LD.....-ZH-..., LD.....-ZV-...

3/10
3/12

LDA5.../LDA3...
LDC7.../LDC3...

3/40
3/40

LD-...
LD-B1, LD-B2
LD-BV
LD-DF1, LD-DF2
LD-DR
LD-.EF.-.
LD-K-.AK./...
LD-K-.AK./GSTZ...
LD-K-.AK./LS....
LD-VE-BF1, LD-VE-BF2

3/47
3/47
3/46
3/47
3/46
3/41, 3/42
3/43
3/44, 3/45
3/46

Annex
Conditions of sale and delivery,
Export regulations

Conditions of sale and delivery


By using this catalog you can acquire hardware and software
products described therein from the Siemens AG subject to the
following terms. Please note! The scope, the quality and the conditions for supplies and services, including software products,
by any Siemens entity having a registered office outside of Germany, shall be subject exclusively to the General Terms and
Conditions of the respective Siemens entity.
for customers with a seat or registered office in the Federal
Republic of Germany
The General Terms of Payment as well as the General Conditions
for the Supply of Products and Services of the Electrical and
Electronics Industry shall apply.

Export regulations
The products listed in this catalog / price list may be subject to
European / German and/or US export regulations.
Therefore, any export requiring a license is subject to approval
by the competent authorities.
According to current provisions, the following export regulations
must be observed with respect to the products featured in this
catalog / price list:
AL

Number of the German Export List.


Products marked other than N require an export license.
In the case of software products, the export
designations of the relevant data medium must
also be generally adhered to.
Goods labeled with an AL not equal to N are
subject to a European or German export
authorization when being exported out of the
EU.

ECCN

Export Control Classification Number.


Products marked other than N are subject to a
reexport license to specific countries.
In the case of software products, the export
designations of the relevant data medium must
also be generally adhered to.
Goods labeled with an ECCN not equal to N
are subject to a US re-export authorization.

For software products, the General License Conditions for


Software Products for Automation and Drives for Customers with
Seat or registered Office in Germany shall apply.
for customers with a seat or registered office outside of Germany
The General Terms of Payment as well as the General Conditions
for Supplies of Siemens, Automation and Drives for Customers
with a Seat or registered Office outside of Germany shall apply.
For software products, the General License Conditions for Software Products for Automation and Drives for Customers with
Seat or registered Office outside of Germany shall apply.
General
The prices are in (Euro) ex works, exclusive packaging.
The sales tax (value added tax) is not included in the prices.
It shall be debited separately at the respective rate according to
the applicable legal regulations.
In addition to the prices of products which include silver, aluminium and/or copper, surcharges may be calculated if the respective limits of the notes are exceeded.
Prices are subject to change without prior notice. We will debit
the prices valid at the time of delivery.

Even without a label or with an AL: N or ECCN: N, authorization may be required due to the final destination and purpose for
which the goods are to be used.
The deciding factors are the AL or ECCN export authorization
indicated on order confirmations, delivery notes and invoices.
Errors excepted and subject to change without prior notice.

The dimensions are in mm. Illustrations are not binding.


Insofar as there are no remarks on the corresponding pages,
especially with regard to data, dimensions and weights given
these are subject to change without prior notice.
Comprehensive Terms and Conditions of Sale and Delivery are
available free of charge from your local Siemens business office
under the following Order Nos.:
6ZB5310-0KR30-0BA0
(for customers based in the Federal Republic of Germany)
6ZB5310-0KS53-0BA0
(for customers based outside of the Federal Republic of
Germany)
or download them from the Internet:
http://www.siemens.com/automation/mall
(Germany: A&D Mall Online-Help System)

Siemens LV 71 2005

4/9

Annex
Notes

Siemens AG
Automation and Drives
Low-Voltage Controls and Distribution
Postfach 48 48
90327 NRNBERG
FEDERAL REPUBLIC OF GERMANY

4/10

Siemens LV 71 2005

Order No.
E86060-K1871-A101-A2-7600
KG K 0305 0.5 BD 176 En/503115
Printed in the Federal Republic of Germany

Catalogs of the
Automation and Drives Group (A&D)
Further information can be obtained from our branch offices listed
in the appendix or at www.siemens.com/automation/partner
Automation and Drives
Interactive catalog on CD-ROM

Catalog

Low-Voltage Controls and Distribution


Low-Voltage Switchgear Controlgear for Industry

Catalog
LV 10

The Offline Mall of Automation and Drives

CA 01

Power Distribution Products and Systems


for Low-Voltage Power Distribution

LV 30

Automation Systems for Machine Tools


SINUMERIK & SIMODRIVE

SIDAC reactors and filters

LV 60

NC 60

SIVACON 8PS Busbar trunking systems


CD, BD01, BD2 up to 1250 A

LV 70

Low-Voltage Controlgear, Switchgear and Systems

LV 90

Motion Control System SIMOTION

PM 10

Drive Systems
Variable-Speed Drives
SINAMICS G130 Drive Converter Chassis Units,
SINAMICS G150 Drive Converter Cabinet Units

D 11

SINAMICS G110 Inverter Chassis Units

D 11.1

SINAMICS S120 Servo Control Drive System

D 21.2

SINAMICS S150 Drive Converter Cabinet Units

D 21.3

DC Motors

DA 12

Process Instrumentation and Analytics


Field Instruments for Process Automation
Measuring Instruments for Pressure,
Differential Pressure, Flow, Level and Temperature,
Positioners and Liquid Meters

SIMOREG DC MASTER 6RA70 Digital Chassis


Converters

DA 21.1

PDF: Indicators for panel mounting

MP 12

SIREC Recorders and Accessories

MP 20

SIMOREG K 6RA22 Analog Chassis Converters

DA 21.2

SIPART, Controllers and Software

MP 31

SIMOREG DC MASTER 6RM70 Digital Converter


Cabinet Units

DA 22

SIWAREX Weighing Systems

WT 01

SIMOVERT PM Modular Converter Systems

DA 45

Continuous Weighing and Process Protection

WT 02

SIEMOSYN Motors

DA 48

Gas Analysis Equipment for the Process Industry

PA 10

MICROMASTER 410/420/430/440 Inverters

DA 51.2

PDF: Process Analytics,


Components for the System Integration

PA 11

MICROMASTER 411/COMBIMASTER 411

DA 51.3

SIPAN Liquid Analysis

PA 20

SIMOVERT MV Medium-Voltage Drives

DA 63

SIMOVERT MASTERDRIVES Vector Control

DA 65.10

SIMOVERT MASTERDRIVES Motion Control

DA 65.11

SIMATIC Industrial Automation Systems


SIMATIC PCS Process Control System

ST 45

Synchronous and asynchronous servomotors for


SIMOVERT MASTERDRIVES

DA 65.3

PDF: SIMATIC S5/505 Automation Systems

ST 50
ST 70

SIMODRIVE 611 universal and POSMO

DA 65.4

Products for Totally Integrated Automation and


Micro Automation

Low-Voltage Three-Phase-Motors

FI 01

SIMATIC PCS 7 Process Control System

ST PCS 7

PDF: Add-ons for the SIMATIC PCS 7


Process Control System

ST PCS 7.A

Main Spindle Motors

pc-based Automation

ST PC

Feed Motors

SIMATIC Control Systems

ST DA

SIPOS Electric Actuators


Electric Rotary, Linear and Part-turn Actuators

MP 35

Electric Rotary Actuators for Nuclear Plants

MP 35.1/.2

KT 10.1
KT 10.2

Squirrel-Cage Motors, Totally Enclosed, Fan-Cooled

M 11

Automation Systems for Machine Tools SIMODRIVE

NC 60

Converter Systems SIMODRIVE 611/POSMO


Drive and Control Components for Hoisting Equipment

HE 1

Electrical Installation Technology


ALPHA Small Distribution Boards and
Distribution Boards

ET A1

ALPHA FIX Terminal Blocks

ET A5

Systems Engineering
Power supplies SITOP power

BETA Modular Installation Devices

ET B1

System cabling SIMATIC TOP connect

DELTA Switches and Outlets

ET D1

GAMMA Building Management Systems

ET G1

Factory Automation Sensors

FS 10

Human Machine Interface Systems SIMATIC HMI

ST 80

Industrial Communication for


Automation and Drives

IK PI

System Solutions
Applications and Products for Industry are part of the
interactive catalog CA 01
TELEPERM M Process Control System
AS 235, AS 235H and AS 235K automation systems

PLT 111

PDF: AS 488/TM automation systems

PLT 112

Operating and monitoring with WinCC/TM

PLT 123

CS 275 bus system

PLT 130

PDF: These catalogs are only available as pdf files.


A&D/3U/En 17.02.05

LV71_en_U1-U4_2005_Stempel_grau_kursiv.FH10 Wed Feb 23 12:15:49 2005

Seite 1

The information provided in this catalog contains descriptions


or characteristics of performance which in case of actual use
do not always apply as described or which may change as a
result of further development of the products. An obligation
to provide the respective characteristics shall only exist if
expressly agreed in the terms of contract. Availability and
technical specifications are subject to change without notice.

Token fee 0.00

Siemens AG
Automation and Drives
Low-Voltage Controls and Distribution
Postfach 48 48
90327 NRNBERG
FEDERAL REPUBLIC OF GERMANY
www.siemens.com/lowvoltage

Order No. E86060-K1871-A101-A2-7600