Distance Protection

ZIV Aplicaciones y Tecnologa S. A.

PROTECTION FUNCTIONS
Function

Description

21+21N

Distance protection for phase and ground faults

50Sup

Overcurrent for distance monitoring


Load encroachment logic
Protection schemes for distance elements
Fuse failure detector
Close onto fault logic
Remote breaker open detector
Dead Line Detector

68/78

Power swing blocking and/or tripping (out of step tripping)

25

Synchronism check

79

3-pole/1-pole recloser

50BF

Breaker failure protection

ZIV Aplicaciones y Tecnologa S. A.

PROTECTION FUNCTIONS
Function

Description

46

Open phase detector

49

Thermal image protection

50F

Three phase instantaneous overcurrent elements (A,B,C)

50N

Three ground instantaneous overcurrent elements

50Q

Three negative sequence instantaneous elements

51F

Three phase time delay overcurrent elements (A,B,C)

51N

Three ground time delay overcurrent elements

51Q

Three negative sequence time delay overcurrent elements

67

Phase directional unit (A,B,C)

67N

Ground directional unit

67Q

Negative sequence directional unit


Protection schemes for 67N/67Q

ZIV Aplicaciones y Tecnologa S. A.

PROTECTION FUNCTIONS
Function
50STUB

Description
Stub bus protection

59

Three phase overvoltage elements (A,B,C)

27

Three phase undervoltage elements (A,B,C)

59N

Two ground overvoltage elements

81M

Three overfrequency elements

81m

Three underfrequency elements

81D

Three rate of frequency change elements


Single/three pole tripping for 21+21N and 67N/67Q
Suitable for cables and overheadlines with series capacitor
compensation
Mutual coupling compensation for parallel lines

ZIV Aplicaciones y Tecnologa S. A.

ADITIONAL FUNCTIONS
Description
Breaker supervision
Fault locator (compensates for load flow and mutual coupling)
Trip masks for distance zones or for auxiliary units
Programmable logic (executed each 2 ms)
Oscillography with analog and digital signals
Records: events, fault reports and metering logs
Measurement
Control
Communications
User interface (alphanumeric display and keypad/programmable push bottons
for operations or commands)
Integrated simulator
ZIV Aplicaciones y Tecnologa S. A.

INPUTS / OUTPUTS
4 x V + 5 x I 5 x V + 8 x I (depending on the model)
1 alarm output (watchdog)
Digital inputs (all programmable):
10 in 2 U box
22 in 3 U box
34 in 4 U box
37 in 6 U box
Outputs (all programmable and strong: anyone can be used as trip / close
output)
10 in 2 U box (4 can be fast for teleprotection)
23 in 3 U box (4 can be fast for teleprotection)
36 in 4 U box (4 can be fast for teleprotection)
44 in 6 U box (4 can be fast for teleprotection)
Connectors with ring lugs
ZIV Aplicaciones y Tecnologa S. A.

DISTANCE PROTECTION
5 distance zones (all reversible)
6 independent measuring elements for each zone
Impedance reaches, resistive reaches and time delays
independent for ground and phase units
Selectable characteristic independent for phase and ground
faults:
Mho (dynamic and variable)
Quadrilateral
Both combined (AND / OR)
Reaches (Z1) and zero sequence compensation factors
(K0=Z0/Z1) independent for each zone in module and angle
ZIV Aplicaciones y Tecnologa S. A.

MHO CHARACTERISTIC
Advantages of polarizing with V1M:
Variable characteristic (V1 action):
Proper operation for zero voltage single phase and twophase faults
Dynamic characteristic (memory action):
Proper operation for zero voltage three phase faults and for
voltage inversions (series compensation)

ZIV Aplicaciones y Tecnologa S. A.

MHO CHARACTERISTIC
ESL

IF2
IF1 -jXC

ZSL

ZSR

F1

F2
V1

XI

ZL

V2

XI

F2
V2

V1 F1
IF1=Irelay

ZSL I V1
F1
ZIV Aplicaciones y Tecnologa S. A.

( ZSR+ ZL) I

R I
IF2

F2
V1

Irelay

R I
9

MHO CHARACTERISTIC
PHASE-GROUND FAULTS

PHASE-PHASE FAULTS

Fop = [I + I 0 (K0n 1)] Z1n V

Fop = I Z1n V

Fpol = V1M

Fpol = V 1M

XI

90 [arg (Fop ) arg (Fpol )] 90


Ieq1 Z11
F

IF RF

XI

I Z11
F

IF

V
I

Ieq1

ZSL (Ieq Icarga)

ZIV Aplicaciones y Tecnologa S. A.

R I
V1M

RF
2

RI
ZSL (I Icarga)

V 1M

10

QUADRILATERAL CHARACTERISTIC
Reactance element (load and non homogeneity compensation)

Zr

Resistive limiters

Directional unit

ZIV Aplicaciones y Tecnologa S. A.

11

REACTANCE ELEMENT
SINGLE PHASE TO GROUND FAULT

Va = Ieq Z 1LF + IFa RF


ESLC

Z1SL

Ieq = Ia + I 0 (K 0 1)

Z1LF

Z1LF

Ic
ESLB

Z1SL

Z1LF

Z1LF

Z1SR

ESRB

Ib
Z1LF

Z1LF

Z1SL

ESRC

Ic

Ib
ESLA

Z1SR

IFa

Ia

Z1SR

ESRA

Ia

RF
ZSN

ZN

ZN

ZSN

Vc Vb Va
ZIV Aplicaciones y Tecnologa S. A.

12

REACTANCE ELEMENT
PHASE-PHASE (TO GROUND) FAULT

Vab = Ieq Z 1LF + IFab RF / 2 Ieq = Iab = Ia Ib


ESLC

Z1SL

Z1LF

Z1LF

Ic
ESLB

Z1SL

Z1SR

IFab = IFa IFb


ESRC

Ic
Z1LF

Z1LF
IFb

Ib

RF/2

Z1SR

ESRB

Ib

Rg

RF/2
ESLA

Z1LF

Z1SL
Ia

IFa Z1LF

Z1SR

ESRA

Ia

Vc Vb Va
ZIV Aplicaciones y Tecnologa S. A.

13

REACTANCE ELEMENT
Vr = Ieq Z1LF + IF RF

IF
Zr = Z1LF +
RF
Ieq
ERROR

X I Ieq Z1F

IF RF

Fr

F
Ieq Z1LF

Z1F

Vr

Z1LF

IF
RF
Ieq

Fr

Zr

Ieq

RI
ZIV Aplicaciones y Tecnologa S. A.

R
14

REACTANCE ELEMENT
LOAD FLOW

depends on

HOMOGENEITY

NO LOAD FLOW AND HOMOGENOUS SYSTEM

LOAD FLOW AND HOMOGENEOUS SYSTEM

<0
>0

FORWARD LOAD FLOW


REVERSE LOAD FLOW

NO LOAD FLOW AND NON HOMOGENOUS SYSTEM


= arg
ZIV Aplicaciones y Tecnologa S. A.

Z1LF+Z1SL
Z1L+Z1SL+Z1SR

15

REACTANCE ELEMENT
LOAD FLOW AND HOMOGENOUS SYSTEM
Fpol = I 2
Fpol = I Ipf

Single line to ground fault

Fpol parallel to IF

Phase-phase fault
(with or without ground)

Avoid Underreaching effect (>0)


Z1F

Fr

IF
RF
Ieq

F
Z1LF

Avoid Overreaching effect (<0)


X

Z1LF F

Zr

IF
RF
Ieq

Fr

Z1F

Zr

Fpol
Ieq

R
ZIV Aplicaciones y Tecnologa S. A.

Fpol = I Ipf

Fpol
Ieq

R
16

REACTANCE ELEMENT
NO LOAD FLOW AND NON HOMOGENOUS SYSTEM

Z1LF+Z1SL

Fpol NON parallel to IF (angle= ) = arg Z1L+Z1SL+Z1SR


X

Z1LF

Z1F

Zr

Tilting angle is introduced

IF
RF
Ieq
Fr

Fpol
Ieq

= arg

Z1L+Z1SL
Z1L+Z1SL+Z1SR

Faults at 100%

R
ZIV Aplicaciones y Tecnologa S. A.

17

REACTANCE ELEMENT
PHASE-PHASE FAULTS

PHASE-GROUND FAULTS
Fop = [I + I 0 ( K 0n 1)] Z1n V

Fop = I Z1n V

Fpol = I Ipf

Fpol = I Ipf

Fpol = I 2

0 [arg (Fop ) arg (Fpol ) ] 180


XI

C2
Ieq1 Z11

Fop

IF RF

XI

C2
Fop

I Z11

C1

Fpol

Ieq1

RI

ZIV Aplicaciones y Tecnologa S. A.

C1

Fpol

IF RF / 2

RI
18

DIRECTIONAL UNIT
Advantages of polarizing with V1M:
Variable line (V1 action):
Proper operation for zero voltage single phase and twophase faults
Dynamic line (memory action):
Proper operation for zero voltage three phase faults and for
voltage inversions (series compensation)

ZIV Aplicaciones y Tecnologa S. A.

19

DIRECTIONAL UNIT
ESL

ZSL

IF2
IF1 -jXC

ZSR

F1

F2

XI

ZL

V1

V2

XI
V1 F1
IF1=Irelay

ZSL I

V1
F1

ZIV Aplicaciones y Tecnologa S. A.

R I
IF2

F2
V2

( ZSR+ ZL) I

F2
V1

Irelay

R I
20

DIRECTIONAL UNIT
PHASE-PHASE FAULTS

PHASE-GROUND FAULTS
Fop= I

Fop = I

Fpol = V1M

Fpol = V1M

(90+ ) [arg(Fop) arg(Fpol)] (90 )


XI

XI
F

V
I

ZSL (Ieq Icarga)

R I

V1M

C3

ZSL (I Icarga)
I

ZIV Aplicaciones y Tecnologa S. A.

RI

V 1M

C3

21

RESISTIVE LIMITER
PHASE-PHASE FAULTS

PHASE-GROUND FAULTS
Fop = I RGn V

Fpol = I RGn

Fop = I RPnV Fpol = I RPn

= bucle= n [arg(I) arg(Ieqn)]

= n

(90 + ) [arg(Fop) arg(Fpol)]


XI

XI
Ieq1 Z11

IF RF

C4

F
V

buc1

I RG1

I Z11
F

IF

RF
2

I
Ieq1

11

RI

ZIV Aplicaciones y Tecnologa S. A.

C4

I RP1

11

RI

22

QUADRILATERAL: PHASE-GROUND FAULTS

ZIV Aplicaciones y Tecnologa S. A.

23

QUADRILATERAL: PHASE-PHASE FAULTS

ZIV Aplicaciones y Tecnologa S. A.

24

PHASE SELECTOR
Based on angle between Ia2 and Ia1 fault currents
For faults with zero sequence infeed uses phase
undervoltage units
Allows:
Single pole tripping on single-phase-ground faults
Blocking leading phase on phase-phase-ground faults
For phase-phase-ground faults the lagging phase-earth
loop can not be blocked: helps phase-phase loop in some
kind of faults
ZIV Aplicaciones y Tecnologa S. A.

25

PHASE SELECTOR
PHASE-PHASE FAULT
Ia 2 > 0.05 In

Ia 2
> 10%
Ia1

GROUND FAULT
Ia0 > 0.05 In

Ia0
> 8%
Ia1

= arg(Ia 2) arg(Ia1 _ f )

ZIV Aplicaciones y Tecnologa S. A.

26

PHASE-PHASE-GROUND
FAULTS
ABG FAULT:

AG BG FAULT:

AG unit overreaches
BG unit underreaches

AG and BG units operate


correctly

Ia
Z1LF

Ia
Z1LF

Z1LF

Z1LF

Ib
Va

Vb

RF
IFa

Rg
ZN

RF
IFb

Ib
Va

Vb

RF
IFa

RF
IFb
IFT

IFT
ZN

The AB unit can be complemented with the BG unit

ZIV Aplicaciones y Tecnologa S. A.

27

FAULT DETECTOR
Sequence currents increment detection (I0, Ia1, Ia2)
Sequence currents levels exceeded (I0, Ia2)
Sealed-in by operation of distance units, overcurrent units, close onto
fault detector and stub bus protection
Supervises the tripping produced by distance units, overcurrent units,
close onto fault detector, stub bus protection and remote breaker open
detector
Determines the fault inception time (allows the selection of prefault and
postfault values: current and voltage)

ZIV Aplicaciones y Tecnologa S. A.

28

FAULT DETECTOR

ZIV Aplicaciones y Tecnologa S. A.

29

LOAD ENCROACHMENT

1
R2

ZIV Aplicaciones y Tecnologa S. A.

R1

R: minimum Rload
: minimum PF

30

FUSE FAILURE DETECTOR


Activation when:
Phase undervoltage units pick-up without
activation of fault detector
Input coming from MCB activates
Inhibited when any pole is open
Can block distance elements, weak infeed trip,
synchronism, dead line detector and voltage units

ZIV Aplicaciones y Tecnologa S. A.

31

FUSE FAILURE DETECTOR

ZIV Aplicaciones y Tecnologa S. A.

32

OPEN POLE DETECTOR


Detects what pole of the breaker has opened
Detection based on breaker contacts plus undercurrent
detectors
Outputs used by phase selector, distance units, fault
detector, power swing detector, fuse failure detector,
ground and negative sequence overcurrent units, recloser,
etc

ZIV Aplicaciones y Tecnologa S. A.

33

OPEN POLE DETECTOR

ZIV Aplicaciones y Tecnologa S. A.

34

OPEN POLE DETECTOR

ZIV Aplicaciones y Tecnologa S. A.

35

DISTANCE UNITS OPERATION


SINGLE PHASE UNITS

ZIV Aplicaciones y Tecnologa S. A.

36

DISTANCE UNITS OPERATION


PHASE-PHASE UNITS

ZIV Aplicaciones y Tecnologa S. A.

37

DEAD LINE DETECTOR


Operated based on undervoltage and undercurrent units
Only applicable when the VT is on the line side
Allows detecting the breaker closing without the need from
external contacts
Can be used to activate the close onto fault function

ZIV Aplicaciones y Tecnologa S. A.

38

CLOSE ONTO FAULT DETECTOR


Activated with manual close or reclose commands:
internal or external
Phase overcurrent units with second harmonic
restraint (inrush stabilization)
Zone 1 extension:
Always activated for close commands
Adjustable for reclose commands

ZIV Aplicaciones y Tecnologa S. A.

39

CLOSE ONTO FAULT DETECTOR

ZIV Aplicaciones y Tecnologa S. A.

40

POWER SWING DETECTOR


ZONE EXT
ZONE MED

X ZB
ZONE INT

Unstable
oscillation

Fast trip
Stable
oscillation

ZL

Slow trip

R
ZA

T
ZIV Aplicaciones y Tecnologa S. A.

41

POWER SWING DETECTOR


Selectable zones to be blocked
Unblocking of blocked distance zones when a fault is
detected:
Ground or phase-phase fault detection (phase selector)
Time the impedance remain inside the external zone

Tripping for unstable swings: slow/fast trip

ZIV Aplicaciones y Tecnologa S. A.

42

POWER SWING DETECTOR

ZIV Aplicaciones y Tecnologa S. A.

43

DISTANCE PROTECTION SCHEMES


Basic Scheme:
Stepped distance

Schemes without communication channel:


Zone 1 extension
Remote breaker open detector

ZIV Aplicaciones y Tecnologa S. A.

44

DISTANCE PROTECTION SCHEMES


Schemes with communication channel:
Permissive underreach transfer trip (PUTT)
Direct transfer trip (DTT)
Permissive overreach transfer trip (POTT)
Directional comparison unblocking (DCUB)
Directional comparison blocking (DCB)
User defined (programmable logic)
Binary information transmission (virtual inputs/outputs)
ZIV Aplicaciones y Tecnologa S. A.

45

DISTANCE PROTECTION SCHEMES

Complementary logics:
Echo and weak infeed trip logic
Transient blocking for current reversal (parallel lines)

ZIV Aplicaciones y Tecnologa S. A.

46

STEPPED DISTANCE
Independent timers for phase and ground faults
Timers do not drop out for evolving faults
Blocking signals coming from:
Power swing detector
Fuse failure detector
Series compensated lines logic

ZIV Aplicaciones y Tecnologa S. A.

47

STEPPED DISTANCE

ZIV Aplicaciones y Tecnologa S. A.

48

ZONE 1 EXTENSION
Zone 1 extended to overreaching zone (zone 2 or 3)
Requires fast reclosing to restore the supply as fast as
possible
Inhibited when the breaker opens; enabled again when
the breaker remains closed for a settable time
Avoids zone 1 extension when reclosing

ZIV Aplicaciones y Tecnologa S. A.

49

ZONE 1 EXTENSION

ZIV Aplicaciones y Tecnologa S. A.

50

PUTT
Carrier sending by zone 1 (underreaching)
Settable carrier time
Can be complemented by weak infeed logic (trip)
Optional carrier sending by open breaker
Blocking signals coming from:
Power swing detector
Digital input
ZIV Aplicaciones y Tecnologa S. A.

51

PUTT

ZIV Aplicaciones y Tecnologa S. A.

52

DTT
Similar to PUTT but with direct trip by carrier reception
Settable carrier time
Settable security time to avoid erroneous operations
due to noise in the communication channel
Optional carrier sending by open breaker
Blocking signals coming from:
Power swing detector (only blocks carrier sending)
Digital input
ZIV Aplicaciones y Tecnologa S. A.

53

DTT

ZIV Aplicaciones y Tecnologa S. A.

54

POTT
Carrier sending by overreaching zone
Settable carrier time
Can be complemented by weak infeed (echo or
echo+trip) and current reversal logics
Optional carrier sending by open breaker
Blocking signals coming from:
Power swing detector
Digital input
ZIV Aplicaciones y Tecnologa S. A.

55

POTT

ZIV Aplicaciones y Tecnologa S. A.

56

DCUB
Similar to POTT but allows instantaneous tripping for a
time window (150 ms) even if the carrier is lost
Requires frequency-shifted PLC equipment
Settable carrier time
Can be complemented by weak infeed (echo or echo+trip)
and current reversal logics
Optional carrier sending by open breaker
Blocking signals coming from:
Power swing detector
Digital input
ZIV Aplicaciones y Tecnologa S. A.

57

DCUB

ZIV Aplicaciones y Tecnologa S. A.

58

DCB
Carrier sending by reverse zone (zone 4 or zone 5) or nondirectional overcurrent units (fast carrier sending)
Settable time delay for overreaching zone operation
Implicit current reversal logic
Carrier stop input / output
Blocking signals (inhibite tripping and generate carrier)
coming from:
Power swing detector
Digital input

ZIV Aplicaciones y Tecnologa S. A.

59

DCB

ZIV Aplicaciones y Tecnologa S. A.

60

WEAK INFEED LOGIC


Selectable logic output: NON, ECHO or ECHO+TRIP
Settable security time to avoid erroneous echo sendings
due to noise in the communication channel
Implicit current reversal logic
Settable voltage threshold for weak infeed trip
Phase selector based on undervoltage units
Optional weak infeed trip blocking by fuse failure detector

ZIV Aplicaciones y Tecnologa S. A.

61

WEAK INFEED LOGIC

ZIV Aplicaciones y Tecnologa S. A.

62

CURRENT REVERSAL LOGIC


Can be applied in any permissive overreaching scheme
Blocking signal for overreaching zone is activated by
reverse zone (zone 4 or zone 5) pick-up
Settable blocking time delay

ZIV Aplicaciones y Tecnologa S. A.

63

CURRENT REVERSAL LOGIC

ZIV Aplicaciones y Tecnologa S. A.

64

REMOTE BREAKER OPEN DETECTOR


Allows zone 2 instantaneous tripping once the remote
breaker is detected as open (three-phase):
Loss of load (undercurrent detectors)
Capacitive current detection (long lines)

(90 ) [arg(I ) arg(V )] (90 + )

ZIV Aplicaciones y Tecnologa S. A.

65

REMOTE BREAKER OPEN DETECTOR

ZIV Aplicaciones y Tecnologa S. A.

66

OVERCURRENT UNITS
Phase, ground and negative sequence / instantaneous and
time delayed
Selectable torque control: non-directional / forward /
reverse
Selectable directional unit (torque control type)
Torque control disable input
Time delay reset input
Blocking signals coming from:
Digital input
Open pole detectors (ground and negative sequence
units)
Series compensated lines logic
ZIV Aplicaciones y Tecnologa S. A.

67

PHASE INSTANTANEOUS
OVERCURRENT UNITS

ZIV Aplicaciones y Tecnologa S. A.

68

GROUND INSTANTANEOUS
OVERCURRENT UNITS

ZIV Aplicaciones y Tecnologa S. A.

69

NEGATIVE SEQUENCE
INSTANTANEOUS OVERCURRENT UNITS

ZIV Aplicaciones y Tecnologa S. A.

70

PHASE TIME-DELAYED
OVERCURRENT UNITS

ZIV Aplicaciones y Tecnologa S. A.

71

GROUND TIME-DELAYED
OVERCURRENT UNITS

ZIV Aplicaciones y Tecnologa S. A.

72

NEGATIVE SEQUENCE
TIME-DELAYED OVERCURRENT UNITS

ZIV Aplicaciones y Tecnologa S. A.

73

DIRECTIONAL UNITS
Phase directional units:
Polarized by quadrature memory phase-phase voltage
Ground directional units:
Polarized by zero-sequence voltage
Polarized by current coming from an earth clamp
Negative sequence directional units:
Polarized by negative sequence voltage
Distance zone 2 can act as directional unit for o/c
Two setting options available in case of loss of polarization
(can be applied to fuse failure): blocking/permission

ZIV Aplicaciones y Tecnologa S. A.

74

DIRECTIONAL UNITS

ZIV Aplicaciones y Tecnologa S. A.

75

DIRECTIONAL UNITS
Polarization voltage compensator factor for ground
and negative sequence directional units:
F _ POL67 N = (V 0 + I 0 KCOMP _ 67 N ANG _ 67 N )

F _ POL67Q = (V 2 + I 2 KCOMP _ 67Q ANG _ 67Q)

Applications:
Increase polarization voltage: makes it higher than
minimum level for polarization (strong zero/negative
sequence sources)
Invert polarization voltage: compensates inversions in
series compensated lines
ZIV Aplicaciones y Tecnologa S. A.

76

DIRECTIONAL UNITS
V 0 = ZA0 ( I 0)

Forward fault
IF

IF

I0

ZA0

p x ZL0

V 0 = ( ZL0 + ZB0) I 0

Reverse fault
I0

(1-p) x ZL0

ZB0

ZA0

V0

ZL0

ZB0

V0

I0 K

-V0
COMP_67N

ANG_67N

I0

Forward
Reverse
ZIV Aplicaciones y Tecnologa S. A.

77

DIRECTIONAL UNITS
Negative sequence voltage inversion if, with
line side CT: XC>XSL2
Vpolarization Compensation
K COMP _ 67Q > XC

FORWARD FAULT
I2

I 2 jXSL2

I 2 K COMP _ 67Q

IF

I2
jXSL2

-jXC

jmXL2
V2

j(1-m)XL2

jXSR2

V 2 = I 2 ( jXSL 2 jXC )

I 2 ( jXC )
ZIV Aplicaciones y Tecnologa S. A.

78

DIRECTIONAL UNITS
Attention with reverse faults!: do not
overcompensate Vpolarization
K COMP _ 67 Q < XL 2 + XSR 2
V 2 = I 2 ( jXL2 + jXSR2)

REVERSE FAULT
IF

jXSL2

-jXC

I2

jXL2

I 2 KCOMP_ 67Q
jXSR2

V2

I2

ZIV Aplicaciones y Tecnologa S. A.

79

O/C PROTECTION SCHEMES


For ground or negative sequence directional O/C (67N/67Q)
Permissive underreach transfer trip (PUTT)
Direct transfer trip (DTT)
Permissive overreach transfer trip (POTT)
Directional comparison unblocking (DCUB)
Directional comparison blocking (DCB)
User defined (programmable logic)
Echo and week infeed tripping
Transient blocking for current reversal
ZIV Aplicaciones y Tecnologa S. A.

80

OPEN PHASE DETECTOR


Only operates with series faults (broken conductor)
Independent from load current (I2/I1 ratio)

ZIV Aplicaciones y Tecnologa S. A.

81

SYNCHROCHECK UNIT
Includes logic to check voltages on both sides of the
breaker. Setting options that allow reclose or manual
close:
Dead line/live bus
Live line/dead bus
Dead line/dead bus
In case of live line/live bus three conditions can be
checked:
Voltage magnitudes difference
Voltage angles difference
Frequency difference
Compensation for the breaker closing time
Synchronism for two breakers
ZIV Aplicaciones y Tecnologa S. A.

82

SYNCHROCHECK UNIT

ZIV Aplicaciones y Tecnologa S. A.

83

BREAKER FAILURE
Current detection levels and timers are independent for
single and three phase trips
Breaker failure pick ups initiated by single pole trips
include phase segregated current detectors and timers
Non overcurrent breaker failure detection (trips from
overvoltage, frequency, Buchholz etc)
Retrip command (single/three phase)
Initiation by external protection trip: single/three pole
Breaker arc detection
Supervision of two breakers
ZIV Aplicaciones y Tecnologa S. A.

84

BREAKER FAILURE

ZIV Aplicaciones y Tecnologa S. A.

85

TRIP LOGIC
Can trip single pole for a single phase to ground fault
with:
Any distance zone
Accelarated overreaching zone
Instantaneous ground or negative sequence unit 1
Accelarated overreaching overcurrent units
Includes the following inputs:
Programmable trip
Trip Blocking
Pole n (n=A, B, C) trip blocking
Three pole trip preparation blocking

ZIV Aplicaciones y Tecnologa S. A.

86

RECLOSER
Single/three pole reclose
4 reclosing modes: 1p, 3p, 1p/3p and dependent
Up to three reclose cycles
Can operate with external protections
Internal or external synchronism check
Programmable recloser initiation masks
Can control two breakers

Independent timers for single and three pole


recloses
ZIV Aplicaciones y Tecnologa S. A.

87

RECLOSER

ZIV Aplicaciones y Tecnologa S. A.

88

SUPERVISION
Breaker supervision:
Excessive number of trips
Maintenance (accumulated kA2)
Supervision of trip and/or close circuits (up to 6)
Pole discrepancy detector

ZIV Aplicaciones y Tecnologa S. A.

89

BREAKER AND A HALF


FUNCTIONALITY
L1
B1

I1

VA VB VC VSINC1

IA1 IB1 IC1

52-1

ILNE=I1+I2

VSINC2

IA2 IB2 IC2

52-2

I2

B2
L2

ZIV Aplicaciones y Tecnologa S. A.

90

BREAKER AND A HALF


FUNCTIONALITY
Programmable directional unit
Stub bus protection more secure for CT saturation
2 breaker failure units
2 synchrocheck units
2 coordinated reclosers
Supervision (accumulated kAN) for 2 breakers

ZIV Aplicaciones y Tecnologa S. A.

91

NEW DIRECTIONAL UNIT


Directional unit more stable for CT saturation during external
faults (created with the programmable logic)

WITHOUT CT-1 SATURATION WITH CT-1 SATURATION


CT-1
I-1

I-2

I-LINE
ZL

I-2

WEAK SOURCE

CT-2

I-1

I-2

I-1
I-LINE

I-LINE

NEW DIRECTIONAL UNIT


STRONG SOURCE

ZIV Aplicaciones y Tecnologa S. A.

-90<arg(I-1)-arg(I-2)<90

92

STUB BUS PROTECTION


Overcurrent unit only in operation when the line isolator
opens
Retraint by through fault current
WITHOUT CT SATURATION: ILINE=0
L1

TI-1

89-L1

WITH CT SATURATION: ILINE0


I LNEA

I-1

ZONA DE OPERACIN

I-2
TI-2
IMIN

ZONA DE NO OPERACIN

I 1 + I 2
2

ZIV Aplicaciones y Tecnologa S. A.

93

BREAKER FAILURE
B1

I1

L1

52-1 failure
B1 Open and intertrip

52-1

Detection with I1
52-2

52-2 failure

I2

52-3 open and intertrip


52-3

Detection with I2
L2

B2

ZIV Aplicaciones y Tecnologa S. A.

94

SYNCHROCHECK UNIT

Breaker and a half

Double busbar

L1
B1
B1
B2
89-1
52-B1

VSINC1
52-0

VSINC2

VA VB VC

89-B2

89-B1

52

VSINC1

VSINC2

Position 89-2

VA VB VC
52-B2
89-2

IN-1

Position 89-B1

IN-2
Position 89-B2

B2

L2
ZIV Aplicaciones y Tecnologa S. A.

95

RECLOSER
Possibility for sequencial reclosing to avoid
closing onto fault both breakers

B1

I1

L1

52-1

Selection of the master and slave reclosers


Permission / blocking of the slave recloser when
the master one is blocked

52-2

Blocking of the recloser associated to a manually


open breaker

I2
52-3
L2
B2

ZIV Aplicaciones y Tecnologa S. A.

96